Page 1: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

0-106/00Ident. No. 822-085

Operating manual

High Voltage Testing Sets

PGK 70 HBPGK 70 - 2,5 HB

PGK 110 HBPGK 150 HBPGK 260 HB

BAUR Prüf- und Messtechnik GmbHRaiffeisenstrasse 8, A-6832 Sulz / Austria

Tel +43 / 55 22 / 49 41-0Fax +43 / 55 22 / 49 4 13

e-mail: [email protected]: http://www.baur.at

Page 2: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

0-2

Page 3: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

0-3

For fast finding of important information the corresponding textpassages are marked with symbols (symbols not stated here areself-explaining).

More and special information concerning the respective subject areavailable from BAUR.

Important unit information!In any case, read carefully!

Important information text.

Observeinfo signs!

Guide to this Operating Instruction

Copyright

© BAUR Prüf- und Messtechnik GmbH,A-6832 Sulz / AustriaAll rights reserved.No part of this publication may be reproduced, transmitted, stored ina data processin gsystem or translated into another languagewithout the written permission of BAUR / Sulz, Austria.

In the interest of our customers we reserve the rights formodifications due to technical progress. Illustrations, descriptionsand delivery content are therefore not binding.

© Copyright by BAUR

This manual contains all information necessary for the correcthandling and use of the high voltage testing set PGK 70 HB,PGK 70 - 2,5 HB, PGK 110 HB, PGK 150 HB und PGK 260 HB.Before using the surge voltage generator, please read carfully thisOperating Instruction.

Preface

If you have any question, please contact directly

BAUR Prüf- und Messtechnik GmbH, Raiffeisenstrasse 8A-6832 Sulz / Austria

or refer to your nearest BAUR representative.

Please read now andavoid damage and injury later!

- The PGK 70 HB, PGK 70 - 2,5 HB, PGK 110 HB, PGK 150 HBund PGK 260 HB is built in accordance with today's state ofengineering and is safe to operate. Individual components andthe finished unit are inspected continually by our qualified staffwithin the framework of our Quality Assurance Provisions. Eachunit is subjected to thorough testing prior to shipment.

Guide to this Operating Instruction, Copyright, Preface

Subject to modification!

Safety Precautions

Tel +43 / 55 22 / 49 41-0Fax +43 / 55 22 / 49 41 3

Page 4: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

0-4

- It is imperative to every person who is involved with theinstallation, start-up, operation and maintenance to have read andunderstood the complete Operating Instruction.

- It is the responsibility of the customer to ensur that onlyauthorized persons may be allowed to use the high voltagetesting sets.

The user- is qualivied and properly instructed and has the necessary

experience.- knows the relevant standards, accident prevention rules and

operating conditions.- is able to carry out the necessary operations and is aware of

the possible dangers involved.- must immediately inform his superior about any conditions of

the unit that could affect safety.

The high voltage testing sets are to be applied exclusively forvoltage proof testing of electrical equipment.

The local safety and accident prevention requirements arealways applicable to the operation of the PGK 70 HB, PGK70 - 2,5 HB, PGK 110 HB, PGK 150 HB and PGK 260 HB unit.

At the customer's written request we undertake to repair or replaceat our discretion and as quickly as possible all parts that becomefaulty or useless as the demonstrable results of poor material, faultydesign or defective execution.We bear the costs for repairs and replaced parts, exclusivetransportation of the goods, packing and insurance.

The 12 month warranty time starts with delivery.We shall bear the costs of any faulty parts requiring replacement,but not the costs of transport to us an back to the customer, not thecosts of packing and insurance! We shall not be liable for anydamage resulting from normal wear and tear, improper handling, non-observance of Operating Instruction and safety requirements. Weshall also refuse to accept any liability if the customer carries outrepairs or changes to the unit himself or has others carry out them!The warranty does not cover damage in transit, batteries, fuses andany readjustments in accordance with the Operating Instruction!We draw attention in addition to the "General Terms of Sales andDelivery" of.

Warranty

Safety Precautions, Warranty

Safety Precautions, Continued

Only authorized personnel!

Use the PGK 70 HB, PGK 70 - 2,5 HB,PGK 110 HB, PGK 150 HB and

PGK 260 HB unit as directed!

12 month warranty time

BAUR Prüf- und Messtechnik GmbH, Raiffeisenstrasse 8A-6832 Sulz / Austria

Page 5: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

0-5

Contents

1. Product Information...................................................................... 1-1Overview ...................................................................................... 1-1

Design and function ..................................................................... 1-2

Display and operating elements ................................................... 1-4

Technical data ............................................................................. 1-5

PGK Load curves ........................................................................ 1-6

2. Packing and Shipping .................................................................. 2-1Damage during transport ............................................................. 2-1

3. Placing into operation .................................................................. 3-1Overview ...................................................................................... 3-1

Connect to earth .......................................................................... 3-2

Switch on .................................................................................... 3-2

Switch off ..................................................................................... 3-4

EMERGENCY-OFF ..................................................................... 3-4

Change operating mode ............................................................... 3-5

4. Servicing / Maintenance............................................................... 4-1Overview ...................................................................................... 4-1

General ....................................................................................... 4-2

Fuse ............................................................................................ 4-2

Contents

Page 6: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

0-6

Contents, Continued

Contents

5. Options, Accessories and Ordering Information ..................... 5-1Overview ...................................................................................... 5-1

Options ....................................................................................... 5-2

Accessories ................................................................................ 5-3

Ordering information .................................................................... 5-5

Page 7: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-1

1. Product Information

Subject Page

Design and function 1-2

Display and operating elements 1-4

Technical data 1-5

PGK Load curves 1-6

1. Product-Information

Overview

This section contains all necessary information about the HighVoltage Testing Sets PGK HB.

This section contains the following subjects:

General viewPGK 70 HB

Page 8: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-2

1. Product Information

Design and Function:

With the PGK 70 - 2,5 HB, PGK 110 HB, PGK 150 HB and thePGK 260 the corona protection hood is used as oil expansion tank(conservator) and may not be removed or damaged. With thePGK 70 HB an air cushion in the housing (tube) works as acompressible volume for absorbing the oil expansion. That’s whythe H.V. unit may only be stored, shipped and operated vertically.

Generation of high voltage is carried out by a H.V. transformersupplied by an variable transformer. During D.C. operation a half-wave rectifier is connected after the H.V. transformer. By turning thehalf-wave rectifier the polarity of the output voltage can be changed.The capacity of the test object acts as smoothing capacitor. DuringA.C. operation, a damping resistor is connected to the H.V. circuitinstead of the half-wave rectifier (with PGK 260 HB: option - notincluded)

The H.V. units of the PGK HB instruments are equipped with apotential grading ring which can also be used as carrying ring. Theinstruments may be not operated without this potential grading ring.

The PGK HB instruments are designed as two-part High VoltageTesting Sets.• Operating unit with all indicating/operating elements, with power

supply and safety devices.• High Voltage unit as oil-filled housing with High Voltage trans-

former with the choice of a rectifier bar for half-wave rectificationor a resistance bar as a damping resistor.

Design

Depending on the load by the test object and the voltage set, thePGK HB instruments are operating in one of the two operatingranges Continuous Operation and Short-time Operation.

Continuous operation:Within this operating range, from no-load to nominal rating up tocut off load the instrument can be loaded continuously.

Short-time operation:Within this operating range from cut off load to short circuit theinstrument switches current-limiting lamps into the primary circuit ofthe H.V. transformer in order to reduce the thermal load of theinstrument. Additionally, as a protection against overload theovercurrent protection switch (5) with its thermal and magnetictripping characteristic is tripped after a specific period terminatingoperation. The time until tripping depends on load and takes fromseconds (during short-circuit) to hours (at maximum load).

Operating ranges

High Voltage generation

Page 9: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-3

1. Product Information

The mA-meter is connected into the H.V. circuit on earth side.

D.C. operation:The mA-meter shows the arithmethic mean value of the outputcurrent.

A.C. operation: (option with PGK 260 HB)The rectification value of the A.C. is measured by the instrument.However, the display shows the appropriate rms value. That’s whythere can be deviations of the displayed value from the true rmsvalue if the measured current is not sinusoidle. During no-load themA-meter shows the current which flows via the self-capacitance ofthe H.V. transformer. Must be considered during measurements ontest objects.

The kV-meter is connected to a tapping of the H.V. winding and iscurrent-compensated. The compensation is balancing the voltagedrop at the internal resistance of the test instrument.

D.C. operation:The kV-meter shows the peak value of the output voltage. If theself-capacitance of the test object is very low it is possible that theinsulation current of the test object results in a high ripple. In thiscase, note that the displayed value and the arithmetic mean valueof the test voltage can be clearly different.

Display during A.C. operation:(option with PGK 260 HB)As with the mA-meter the kV-meter also measures the rectificationvalue and displays the rms value.

kV - meter

mA - meter

Page 10: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-4

1. Product Information

1 Mains switch as overcurrent safety switch with thermaltripping

2 Pushbutton „Ready to switch on“ ( )

3 Pushbutton „High Voltage On“ ( I ) with pilot lamp(clearing of H.V.)

4 Pushbutton „High Voltage Off“ ( )

5 Overcurrent safety switch with thermal and magnetictripping

6 Voltmeter for display of output voltage in kV

7 Amperemeter for display of output current in mA

8 Measuring range switch for amperemeter

9 Selector switch for operating mode (+ / ~ / -)

10 Measuring range switch for voltmeter

11 Variable transformer for setting the output voltage

12 Lockabel Emergency off momentary contact switch

13 Indicator lamp, green14 Indicator lamp, red

Display and operating elements

Page 11: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-5

1. Product Information

PGK PGK 70 PGK PGK PGK unit70 HB - 2,5 HB 110 HB 150 HB 260 HB

Mains voltage see type plate V ~

Mains frequency 45 to 60 45 to 60 45 to 60 45 to 60 45 to 60 Hz

Power consumption atnominal working point 640 3200 1380 1380 2600 VA

Max. power consumption(in short-circuit operation) 1200 6500 2650 2650 5000 VA

Power output at nominalworking point AC/DC 330/190 2750/1260 1260/495 990/530 1665/1000 VA/W

Max. output voltageACeff/DC in no-load 56/78 56/78 94/126 110/160 185/260 kV

Output voltage ACeff/DCat nominal working point 47/66 55/62 90/108 110/137 185/250 kV

Max. output currentACeff/DC at short-circuit 20/12 117/84 30/17 23/20 20/20 mA

Accuracy of kV-meter 2,5 2,5 2,5 2,5 2,5 %

Accuracy of mA-meter 2,5 2,5 2,5 2,5 2,5 %

Dimensions of operating unit 502 x 502x 502 x 502 x 502 xhousing (W x H x D) 242 x 290 242 x 290 242 x 290 242 x 290 242 x 290 mm

Dimensionsof H.V. unit(height / diameter) 810/385 1130/455 1130/455 1450/455 2050/1270 mm

Weight of operating unit 13,5 22 17 17 19 kg

Weight of H.V. unit 27 93 75 85 260 kg

Relative humidity not condensing

Ambient temperature working: 0...+45° Cstorage: -20...+60° C

Technical Data

Page 12: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-6

1. Product Information

PGK output load curves

Page 13: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-7

1. Product Information

Page 14: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-8

1. Product Information

Load curve PGK 110 HB AC

1-8

Load curve PGK 110 HB DC

0

10

20

30

40

50

60

70

80

90

100

0 5 10 15 20 25 30 35

I / kV

U /

kV

0

20

40

60

80

100

120

140

0 5 10 15 20

I / mA

U /

kV

mA

Page 15: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-9

1. Product Information

Load curve PGK 150 HB AC

LLoad curve PGK 150 HB DC

0

10

20

30

40

50

60

70

80

90

100

110

120

130

0 3 6 9 12 15 18 21 24

I / mA

U /

kV

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

0 2 4 6 8 10 12 14 16 18 20 22

I / mA

U /

kV

Page 16: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

1-10

1. Product Information

0

20

40

60

80

100

120

140

160

180

200

220

0 5 10 15 20 25

I / mA

U / k

v

Attention : maximum admissibleoutput voltage 190 kV rms.

Load curve PGK 260 HB DC

Load curve PGK 260 HB AC

0

20

40

60

80

100

120

140

160

180

200

220

240

260

280

300

320

0 2 4 6 8 10 12 14 16 18 20 22

I / mA

U /

kV

Attention : maximum admissible output voltage 260 kV

Page 17: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

2. Packing and Shipping

Complains concerning damages should be made to us withoutdelay, using a standard transport damage claims form.

Confirmation of visible damage should immediately be obtainedfrom the carrier. The extent and probable cause of the damageshould be stated.

If damage is discovered during unpacking, contact the responsibletransportation company immediately. Request a written lossassessment and make them responsible for the damage!

We also refer to the ‘General Terms of Sales and Delivery’ of:

The Test Sets ar shipped in robust cardboard cartons or in shippingcontainers on wooden pallets. If the instruments are not usedimmediately, always keep in the closed carton or shipping containerand store in dry rooms!

The H.V. unit may only be transported and operated vertically. It isimportant that the tube is not bended so when packing in shippingcontainers it may not be used as a support. For securing the H.V.unit mounting holes are in the base plate. Additionally, the H.V. unitcan be also fasten to the potential grading ring. Please note that thecorona protection hood (with the exception of the PGK 70 HB) isnot a solid part but a hollow body filled partly with oil which must beprotected against impacts and collisions.

2. Packing and Shipping

Damage during transport

2-1

BAUR Prüf- und Messtechnik GmbH,A-6832 Sulz / Austria

Page 18: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

2. Packing and Shipping

Notes

2-2

Page 19: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

3. Placing into Operation

3-1

Subject Page

Connect to earth 3-2

Prepare test 3-2

Switch on 3-3

Switch off 3-4

EMERGENCY OFF 3-4

Change operating mode 3-5

3. Placing into Operation

Overview

In this section you will find all necessary information to put the HighVoltage Testing Sets PGK 70 HB, PGK 70 - 2,5 HB, PGK 110 HB,PGK 150 HB and PGK 260 HB into operation.

This section contains the following subjects:

Page 20: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

3. Placing into Operation

3-2

Connect to earth

It is absolutely necessary to connect the H.V. unit to earth and tothe test object via one of the two earthing screws on the base plate.

The earth lead should be as short as possible and must have a lowimpedance (min. cross-section of 4 mm², copper).

••••• Isolate all connections from the test object, secure againstrepeated switch-on and make sure that zero voltage conditionexists.

••••• Insulate nearby items which are under voltage.! It must be assured that nearby items under voltage do

not result in breakovers or breakdowns, due toapplying the test voltage to the test object.

••••• Insert rectification resp. resistor bar (option with PGK 260 HB)according to the desired operating mode.

••••• Connect operating unit and H.V. unit.

••••• Install H.V. connection to the test object.

••••• Connect instrument to mains according to specifications on typeplate.

••••• Turn variable transformer (11) to the left position.

••••• Set measuring range selector switch for the kV-meter (10) to „II“.

••••• Set measuring range selector switch for the mA-meter (8) to thehighest range in order to avoid damage to the instrument.Short overloads (breakdowns and short-circuits at the testobject) are no danger to the mA-meter if ten times the value ofthe relevant measuring range is not exceeded.

••••• Turn mode selector switch (9) to selected operating mode(„+“, „-“ or „-“).

Prepare test

Page 21: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

3. Placing into Operation

3-3

Before going into operation, local safety requirements andsafety precautions for the protection against direct or indirectcontact of live parts have to be met accordingly!

• Switch on instrument with mains switch (1)

• The instrument is in operating condition "IN OPERATION"! the green indication lamp (13) is illuminated

• Press pushbutton "Ready to switch on" (2). In case theovercurrent protection switch (5) has tripped, a buzzing soundoccurs during depression of the "Ready to switch on" push-button . Instrument goes into operating condition "READY TOSWITCH ON" only if

! the EMERGENCY-OFF pushbutton switch is notdepressed,

! the overcurrent protection switch (5) has not beentripped.

The instrument is in operating condition "READY TO SWITCH ON"! the green indicator lamp (13) is out,! the red indicator lamp (14) is illuminated.

• Press pushbutton "High Voltage On" I (3)

The high voltage transformer will be connected to the mains voltageonly, if

! the variable transformer is in its left position (neutralposition)

! the shorting bar of the discharge unit (option) is fullyopen.

The instrument is in operating condition "IN OPERATION"! the pilot lamp "In operation" I of the pushbutton

switch (3) is illuminated.

• Adjust to desired voltage using the variable transformer (11).

Switch on

Page 22: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

3. Placing into Operation

3-4

• Turn back variable transformer (11) to its left position.

• Press pushbutton "High voltage off" (4)

••••• The instrument returns into the operating condition „READY FOROPERATION“. The high voltage transformer is disconnectedfrom the supply voltage

! the pilot lamp "IN OPERATION" of pushbuttonI (3) is out

! the red indicator lamp (14) is out! the green indicator lamp (13) is illuminated! the shorting bar of the discharge unit (option) affects

the High Voltage output of the instrument anddischarges the connected capacities via the dischargeresistor.

• Switch off with mains switch.

• Press EMERGENCY-OFF momentary contact switch (12).

••••• The instrument returns to the operating condition „READY FOROPERATION“. The high voltage transformer will be isolated fromthe supply voltage.

! the indicator lamp "In operation" I of pushbuttonswitch (3) is out

! the red indicator lamp (14) is out! the green indicator lamp (13) is illuminated

••••• The instrument can only be placed in the operating condition„READY TO SWITCH ON“ by pressing the pushbuttonswitch (2) „Ready to switch on“ if the EMERGENCY OFFmomentary contact switch has been unlocked with the key.

••••• By pressing the EMERGENCY OFF momentary contact switchand taking out the key, unauthorized use of the instrument canbe prevented.

Because High Voltage measuring is not carried out directly at theHigh Voltage output no more voltage is shown on the kV-meter afterswitching off the instrument although the test object could becharged to full voltage! Before cancelling the safety precautions, itis essential that all live parts must be discharged, earthed andshorted!

Discharge test object with discharge bar

Switch off

see table on page 5-3 / Discharge bar

Use discharge bar suitable to the particular instrument andnote that different discharge times must be met depending ontest object capacity and the discharge bar used.

EMERGENCY OFF

Discharge, Connect to earth, Short out

Page 23: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

3. Placing into Operation

3-5

Turn mode selector switch (9) into desired position (+ / ~ / -)

Change operating mode of instrument (option with PGK 260 HB)

••••• Unscrew knurled screw (or ball nut of PGK 70 HB) on H.V.output.

••••• Loosen threaded insert with screwed-on rectifier bar (resistorbar) using supplied spanner.

• Slowly pull out bar (the oil should be dripped off from the bar).

• Unscrew threaded insert from bar.

• Screw on threaded insert to desired bar (with rectifier bar on theside of desired polarity).

! The resistor bar is marked on one end with "~"(front end of screw plug)

! The rectifier bar is marked on the ends with "+" and "-"

! If negative H.V. should be want the "-" mark must beon top (at the H.V. output)

••••• Clean bar with dry (or slightly dampened in petroleum ether) andfuzz-free clothes.

••••• Slowly insert cleaned bar into the tube.

When operating mode is changed very frequently, it must beobserved that always so much insulating oil is within the tube thatthe bar is immersed in the oil up to the top metal cap. Theinstrument is filled with insulating oil Technol US 4000 by themanufacturer (see Maintenance).

Change mode of operating unit

Change mode of High Voltage unit

Page 24: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

3. Placing into Operation

3-6

Notes

Page 25: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

4. Servicing / Maintenance

4-1

4. Servicing / Maintenance

Overview

In this section you will find all necessary information regardingservicing and maintenance of the High Voltage Testing SetsPGK 70 HB, PGK 70 - 2.5 HB, PGK 110 HB, PGK 150 HB andPGK 260 HB.

This section contains the following subjects:

Subject Page

General 4-2

Fuse 4-2

Page 26: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

4. Servicing / Maintenance

4-2

General

• In order to avoid leakage currents or creeping discharges at thetube or cone of the High Voltage unit it must be kept clean. Forthis purpose, use only fuzz-free clothes dampened in petroleumether.

• From time to time, check function of limiter lamps in theoperating unit. This can be easily carried out in short-circuitoperation by slowly increasing the voltage at the variabletransformer until lamps light up.

• Oil for refilling around the rectifier or resistor bar is available fromBAUR.

••••• 0.8lt insulation oil Technol US 4000ID no. 471-716

Fuse

Designation Value Dimension Ident.No. Remarks

F1, F2 0,16 AT Ø 5 x 20 mm 563-005 Mains transformer, primary

F3, F4 2 AF Ø 5 x 20 mm 563-020 + 12V control

F5, F6 3,15 AT Ø 5 x 20 mm 563-021 Discharge unit (option)

(S4, F10) 16 AT Mains switch

F11

PGK 70 HB 2 A High voltage transformer, primary

PGK 110 HB 6 A High voltage transformer, primary

PGK 150 HB 6 A High voltage transformer, primary

PGK 260 HB 10 A High voltage transformer, primary

PGK 70/2,5 HB 14 A High voltage transformer, primary

Page 27: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

5-1

5. Options, Accessories and Ordering Information

In this section you will find all necessary information regardingoptions and accessories available for the High Voltage Testing SetsPGK 70 HB, PGK 70 - 2.5 HB, PGK 110 HB, PGK 150 HB andPGK 260 HB.

5. Options, Accessories and Ordering Information

Overview

This section contains the following subjects:

Subject Page

Options 5-2

Accessories 5-3

Ordering information 5-5

Page 28: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

5. Options, Accessories and Ordering Information

5-2

For PGK HB instruments an automatic discharge unit is availableconsisting of a short-circuit bar activated by a rotary magnet and adischarge resistor connected in series between test object and testinstrument. Control is accomplished via the operating unit. Bypressing pushbutton ‘Ready to switch on’ (2) the short-circuitbar is moved away from the corona protection hood. Reaching theend position is monitored. When the instrument is back in operatingcondition ‘READY FOR OPERATION’ a short-circuit bar is movedto the corona protection hood by a spring. A discharge resistor isresponsible for discharging the connected capacitances.

As additional accessory a folding tripod can be supplied. It makesoperation of the instrument easier if no working table is available.Working height is approx. 90cm.

In order to make shipping of the PGK HB Sets to the customerseasier a transport case is available.

For the H.V. units a moving frame with big steering rollers can besupplied.

Options

Folding tripod

Discharge unit

Moving frame

Transport case

Page 29: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

5-3

5. Options, Accessories and Ordering Information

PGK unit 70 HB 70 - 2,5 HB 110 HB 150 HB 260 HB

Discharge bar ES 70 ES 70 ES 110 ES 150 ES 260

max. permissible voltage 80 kV 80 kV 120 kV 180 kV 280 kV

max. permissible discharge energy 12.000 Ws 12.000 Ws 18.000 Ws 27.000 Ws 42.000 Ws

Time between 2 discharges 10 min. 10 min. 10 min. 10 min. 10 min.

Accessories

The PGK HB instruments are supplied with the accessoriesspecified below. The rectifier bar is in the H.V. unit when suppliedand the instrument is in the operating mode ‘negative D.C.’.

The rectifier bar supplied with the instrument is used for protectingthe instrument against transient voltages and high currents in caseof short-circuit during A.C. operation.

Rectifier bar (option with PGK 260)

PGK unit 70 HB 70/2,5 HB 110 HB 150 HB 260 HB

Resistance value 33 kΩ 3 kΩ 30 kΩ 99 kΩ 132 kΩ

Tolerance ± 10 % ± 10 % ± 10 % ± 10 % ± 10 %

Is used for loosening the threaded insert when changing theoperating mode of the instrument. It is a cylindrical spanner whichis inserted into the two holes in the threaded insert.

Spanner for replacing rectifier /resistor bar

For discharging capacitive test objects during D.C. operation thedischarge bars ES 70 - ES 260 are used.

Discharge bar

As earth connection between H.V. unit and test object a flexiblecopper earth lead with a length of 2,5 m and a cross-section of4mm² is supplied. On both ends cable lugs are attached with a holediameter of 8,5 mm.

Earth lead

Page 30: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

5. Options, Accessories and Ordering Information

5-4

Mains supply

Connection H.V. / Operating unit

High Voltage connecting leads

The PGK HB instruments are supplied with a plugable mainssupply cable with a 1,5 mm² cross-section and with a length of2,5 m.

Ident.No. Type554-015 Powercord with safety plug554-016 Powercord with US plug554-017 Powercord with free cable end

Connecting lead between H.V. and operating unit is 5 m long and isconnected with lockable connectors on both sides.

A High Voltage insulated wire with a length of 5 m and a cross-section of 1,5 mm² is used as High Voltage connecting lead.The instrument side is equipped with a cable lug with hole diam.8,5 mm (with PGK 70 HB a banana plug with 4 mm) and the testobject side is equipped with an alligator clip.

Page 31: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

5-5

5. Options, Accessories and Ordering Information

Mains voltage220-230V 110-120V*) 240V

High Voltage Test Set PGK 70/2,5 HB 411-011 411-111 411-211

Operating unit 470-031 470-032 470-033

High Voltage unit 470-047 470-047 470-047

Discharge bar ES 70 12kWs 411-510 411-510 411-510

Mains connection 554-015 554-016**) 554-017

Connecting cable H.V. / Operating unit, 5 m 471-933 471-933 471-933

Earth lead, 3 m 460-462 460-462 460-462

High Voltage connection, 2,5 m with alligator clip 460-477 460-477 460-477

Spanner for replacingrectifier / resistor bar 460-459 460-459 460-459

Rectifier bar (built in) 470-063 470-063 470-063

Resistor bar fo A.C. operation 470-064 470-064 470-064

Moving frame H.V. unit 470-577

Folding tripod for 19" units, working heightapprox. 90 cm 411-536

Automatic discharge device EM 70/2,5, 45kWs 470-621

Emergency Off unit with signal lamps, 25 m 471-219

Emergency Off unit with signal lamps, 50 m 470-809

ransport case for H.V. / Operating unit 19" (WxHxD)720x1716x720 mm 411-537

Mains voltage220-230V 110-120V*) 240V

High Voltage Test Set PGK 70 HB with accessories 411-010 411-110 411-210

Operating unit 470-006 470-007 470-008

High Voltage unit 470-042 470-042 470-042

Discharge bar ES 70 12kWs 411-510 411-510 411-510

Mains connection 554-015 554-016 554-017

Connecting cable H.V. / Operating unit, 5 m 471-933 471-933 471-933

Earth lead, 3 m 460-462 460-462 460-462

High Voltage connection, 2,5 m with alligator clip 460-476 460-476 460-476

Spanner for replacingrectifier / resistor bar 460-459 460-459 460-459

Rectifier bar (built in) 470-062 470-062 470-062

Resistor bar fo A.C. operation 470-061 470-061 470-061

Folding tripod for 19" units, working heightapprox. 90cm 411-536

Automatic discharge device EM 70, 20kWs 470-620

Emergency Off unit with signal lamps, 25 m 471-219

Emergency Off unit with signal lamps, 50 m 470-809

Transport case for operating unit 19" (WxHxD)626x383x382 mm 470-765

Transport case for High Voltage unit (WxHxD)440x940x440 mm 411-530

Ordering information PGK 70 HB

Item supplied

Item supplied

Ordering information PGK 70/2,5 HB

Options

Optionen

*): Delivery includes external autotransformer; mains connection cable without termination, fix mounted **) fix installed mains connection

*): Delivery includes external autotransformer; mains connection cable withouttermination, fix mounted

Page 32: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

5. Options, Accessories and Ordering Information

5-6

Mains voltage220-230V 110-120V*) 240V

High Voltage Test Set PGK 110 HB with accessories 411-017 411-117 411-217

Operating unit 470-444 470-445 470-446

High Voltage unit 470-449 470-449 470-449

Discharge bar ES 110 18kWs 411-511 411-511 411-511

Mains connection 554-015 554-016 554-017

Connecting cable H.V. / Operating unit, 5 m 471-933 471-933 471-933

Earth lead, 3 m 460-462 460-462 460-462

High Voltage connection, 2,5 m with alligator clip 460-477 460-477 460-477

Spanner for replacingrectifier / resistor bar 460-459 460-459 460-459

Rectifier bar (built in) 470-439 470-439 470-439

Resistor bar for A.C. operation 470-440 470-440 470-440

Moving frame High Voltage unit 470-577

Folding tripod for 19" units,working height approx. 90 cm 411-536

Automatic discharge device EM 110, 45kWs 470-622

Emergency Off unit with signal lamps, 25 m 471-219

Emergency Off unit with signal lamps, 50 m 470-809

Transport case for H.V. / Operating unit (WxHxD)670x1680x760 mm 471-179

Ordering information PGK 110 HB

Items supplied

Ordering information PGK 150 HB220-230V 110-120V*) 240V

High Voltage Test Set PGK 150 HB with accessories 411-013 411-113 411-213

Operating unit 470-016 470-017 470-018

High Voltage unit 470-044 470-044 470-044

Discharge bar ES 150 411-512 411-512 411-512

Mains connection 554-015 554-016 554-017

Connection cable H.V. / Operating unit, 5 m 471-933 471-933 471-933

Earth lead, 3 m 460-462 460-462 460-462

High Voltage connection, 2,5 m with alligator clip 460-477 460-477 460-477

Spanner for replacingrectifier / resistor bar 460-459 460-459 460-459

Rectifier bar (built-in) 470-057 470-057 470-057

Resistor bar for A.C. operation 470-058 470-058 470-058

Moving frame High Voltage unit 470-577

Folding tripod for 19" units,working height approx. 90 cm 411-536

Automatic discharge device EM 150, 45kWs 470-624

Emergency Off unit with signal lamps, 25 m 471-219

Emergency Off unit with signal lamps, 50 m 470-809

Transport case for H.V. / Operating unit (WxHxD)720x720x1970 mm 471-178

Mains voltage

Items supplied

Options

Options

*): Delivery includes external autotransformer; mains connection cable withouttermination, fix mounted

*): Delivery includes external autotransformer; mains connection cable withouttermination, fix mounted

Page 33: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

5-7

5. Options, Accessories and Ordering Information

Mains voltage220-230V 110-120V*) 240V

High Voltage Test Set PGK 260 HB with accessories 411-016 411-116 411-216

Operating unit 470-026 470-027 470-028

High Voltage unit 470-046 470-046 470-046

Discharge bar ES 260 42kWs 411-514 411-514 411-514

Mains connection 554-015 554-016 554-017

Connection cable H.V. / Operating unit, 5 m 471-933 471-933 471-933

Earth lead 3 m 460-462 460-462 460-462

High Voltage connection, 2,5 m with alligator clip 460-477 460-477 460-477

Spanner for replacingrectifier / resistor bar 460-459 460-459 460-459

Rectifier bar (built in) 470-060 470-060 470-060

Resistor bar for A.C. operation 470-059

Moving frame High Voltage unit 470-584

Folding tripod for 19" units,working height approx. 90 cm 411-536

Automatic discharge device EM 260 470-627

Emergency Off unit with signal lamps, 25 m 471-219

Emergency Off unit with signal lamps, 50 m 470-809

Transport case for H.V. / Operating unit (WxHxD)1350x2220x1350 mm 411-533

Items supplied

Ordering information PGK 260 HB

Options

*): Delivery includes external autotransformer; mains connection cable withouttermination, fix mounted

Page 34: Operating manual - User Equip: New & Used Test Equipmentuserequip.com/files/specs/5871/PGK70 HB_manual.pdf · 0-1 Ident. No. 822-085 06/00 Operating manual High Voltage Testing Sets

5. Options, Accessories and Ordering Information

5-8

Notes


Recommended