8/13/2019 OLTC Technical Data
1/46
Technical Data General SectionTechnical Data TD 61
www.reinhausen.com
8/13/2019 OLTC Technical Data
2/46
2 TD 61/02 061/02/01/0
Survey
NOTE
These technical data are intended for the calculator and designer of the transformer. This release replaces all previous releaseswhich then become invalid.Dimensional drawings and connection diagrams are subject to change without prior notice.
Drawings submitted during bidding and ordering are always binding.Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the manufactureris responsible for selecting the correct properties of the on-load tap-changer so that the requirements of thetransformer are met.
This general section pertains to the following technical data.
VACUTAP VT ........................................... TD 124
VACUTAP VV ........................................... TD 203
VACUTAP VR ........................................... TD 237
OILTAP V ........................................... TD 82
OILTAP MS ........................................... TD 60
OILTAP M ........................................... TD 50
OILTAP RM ........................................... TD 130
OILTAP R ........................................... TD 115
OILTAP G ........................................... TD 48
DEETAP U ........................................... TD 51
Survey
8/13/2019 OLTC Technical Data
3/46
3TD 61/02061/02/01/0
1 General .................................................................................................................................................................................................................. 5
1.1 How it functions .................................................................................................................................................................................... 5
1.2 Basic connections of the tap winding ............................................................................................................................................ 6
2 Characteristic properties of the on-load tap-changer ..................................................................................................................... 7
2.1 Designations of the on-load tap-changer .................................................................................................................................... 7
2.2 Through-current, step voltage and step capacity ....................................................................................................................... 10
2.3 Insulation ................................................................................................................................................................................................. 11
2.4 Overload .................................................................................................................................................................................................. 112.4.1 Through-currents greater than rated through-current .............................................................................................. 112.4.2 Operation at increased transformer power with improved cooling ....................................................................... 112.4.3 Required specifications for modes which are not defined by IEC 60354 or ANSI C57.91 ............................... 12
2.5 Short-circuit stress on on-load tap-changers and off-circuit tap-changers .................................................................... 12
2.6 Forced current division ........................................................................................................................................................................ 12
2.7 Permissible overexcitation .................................................................................................................................................................. 13
2.8 Multiple-column on-load tap-changers ........................................................................................................................................ 13
2.9 On-load tap-changer applications with variable step voltage............................................................................................... 13
2.10 Coarse tap winding/tapped winding, leakage inductance ....................................................................................................... 14
2.11 Potential connection of the tap winding ...................................................................................................................................... 14
2.12 On-load tap-changer in transformers for arcing furnaces (cf. also ordering sheets) ..................................................... 19
2.13 Installing the on-load tap-changer and off-circuit tap-changer ......................................................................................... 19
2.14 Activating the on-load tap-changer during the transformer test ........................................................................................ 19
2.15 Special applications .............................................................................................................................................................................. 19
2.16 Insulation oils ......................................................................................................................................................................................... 19
2.17 Service in arctic areas .......................................................................................................................................................................... 19
2.18 Hermetically sealed transformer with gas cushion .................................................................................................................... 19
2.19 Parallel jumpers for parallel connection of tap selector planes ............................................................................................ 19
3 Important information on design and installation ............................................................................................................................ 20
3.1 Designation of the terminal contacts of the tap selector and operating positions ........................................................ 20
3.2 Oil suction pipe ...................................................................................................................................................................................... 213.3 Oil filter unit ........................................................................................................................................................................................... 21
Table of Contents
Table of Contents
8/13/2019 OLTC Technical Data
4/46
4 TD 61/02 061/02/01/0
Table of Contents
4 Protective relay RS 2001 ............................................................................................................................................................................... 21
5 Motor-drive units ED-S, ED-L ..................................................................................................................................................................... 22
5.1 Function .................................................................................................................................................................................................. 22
5.2 Type designations .................................................................................................................................................................................. 22
5.3 Technical data of the motor-drive unit ......................................................................................................................................... 23
6 Drive shaft ............................................................................................................................................................................................................ 24
7 Selecting the on-load tap-changer ............................................................................................................................................................ 24
7.1 Selection principle ................................................................................................................................................................................ 24
7.2 Examples of selecting the on-load tap-changer ......................................................................................................................... 25
8 Appendix ............................................................................................................................................................................................................... 28
Table of Contents
8/13/2019 OLTC Technical Data
5/46
5TD 61/02061/02/01/0
1 General
1 General
1.1 Function principle
The on-load tap-changer provides uninterrupted voltageregulation of transformers under load. The voltage isregulated by changing the voltage ratio. This is done in steps.The transformer is equipped with a tap winding whosetappings are connected with the tap selector of the on-loadtap-changer.
This is the reason the on-load tap-changer is designed forimmersed installation in the transformer tank (fig. 1) to keep
the distances from the tap winding terminals to the tapselectors short. The on-load tap-changer is activated by amotor-drive. Drive shafts and bevel gear units mechanicallyconnect the motor-drive to the on-load tap-changer head.
Exception: The on-load tap-changer VACUTAP VT is fixed tothe active part of the dry-type transformer.
8997590D
Fig. 1 Transformer with on-load tap-changer, drawing
1 - On-load tap-changer2 Motor-drive3 Protective relay4 Oil conservator
Fig. 2aConnection principle of the on-load tap-changerconsisting of diverter switch and tap selector
On-load tap-changer (diverter switch-tap selectorprinciple)
The tap selector selects the desired tap which is then con-nected to the no-load side of the diverter switch. This tapthen accepts the service current with the next diverter switchoperation.
The functions of the diverter switch and tap selector aretime-correlated during the tap change, seefig. 2aforconnection principle.
KHW 370 - 4
Tap selector
Diverter switch
8/13/2019 OLTC Technical Data
6/46
6 TD 61/02 061/02/01/0
1 General
1.2 Basic connection of the tap winding (see fig. 3)
For possible basic connections, see the technical data of thepertinent tap-changer type.
Fig. 3 Basic connections
a Without change-over selectorb With reversing switchc With coarse tap selector
a b c
KHW 114-4
On-load tap-changer (selector switch principle)
It combines the characteristics of a diverter switch and a tapselector. The change-over from one tap to the next takesplace in only one switching process, see fig. 2bfor connec-tion principle.
Fig. 2bConnection principle of the on-load tap-changer based onthe selector switch principle
EV1004
8/13/2019 OLTC Technical Data
7/46
7TD 61/02061/02/01/0
2 Characteristic properties of the on-load tap-changer
2 Characteristic properties of the on-load tap-changer
2.1 Designations of the on-load tap-changer
Each type of on-load tap-changer is available in manydesigns, varying by number of poles, maximum ratedthrough-current, highest voltage for equipment Um, tapselector size, and basic connection diagram. For this reason,the designation of a certain on-load tap-changer modelmust also indicate these features (see fig. 4). This gives theon-load tap-changer an unique identification.
Number of steps and basic connection diagram
The tap selector can be extensively adjusted to the requirednumber of steps and the connection of the tap winding.The applicable basic connection diagrams are differentiatedby tap selector contacts (10 to 18), number of operatingpositions, number of mid-positions, and the change-overselector design. Fig. 5shows the designation of the basicconnection diagram.
The adjustment position is the position in which the on-loadtap-changer is delivered. The on-load tap-changer must be inadjustment position mode during maintenance work (re-moval or installation of the on-load tap-changer unit).
For further details, see the pertinent operating/maintenanceinstructions.Each design connection diagram of the on-load tap-changerexplicitly specifies the adjustment position.
The mid-position is the position in which the K contact isconnected in the reversing switch or coarse tap design.The mid-position is usually also the adjustment position (seedesign connection diagram of the on-load tap-changer).
1 mid-position: With 1 mid-position, there is no positionwith the same voltage before or after the K contact.
3 mid-positions: With 3 mid-positions, there is no change in
voltage before and after the K contact.Jumpered contacts are not considered as mid-positions.
Type
M I 601 123 / B 10 19 1 W
Basic connection diagram
Number of
poles Tap selector size
Max. rated
through-current in A
and additionalidentification of
the design
Highest voltage for
equipment Umin kV
Fig. 4Designation of the on-load tap-changerExample: On-load tap-changer, type M, 1-pole, max. ratedthrough-current 600 A, highest voltage for equipmentUm= 123 kV, tap selector size B, tap selector in acc. w. basicconnection diagram 10 19 1 W
10 19 1 W
Tap selector pitch Mid-position(s) Change-over selector
0
1
10 Max. 3 G W
12 operating positions Coarse Reversing
14 tap selector switch16
18
without change- with change-over
over selector selector
10 09 19
12 11 23
14 13 27
16 15 31
18 17 35
Fig. 5Designation of the basic connection diagram
Example:Tap selector pitch 10, max. of 19 operating positions,1 mid-position, change-over selector designed asreversing switch
8/13/2019 OLTC Technical Data
8/46
8 TD 61/02 061/02/01/0
- / -
I
II
III
A
200
250300
350
400
500
600
800
1200
1500
1600
2000
2400
3000
1
2
3
Y
D
kV
36
40
72,5
76
123/76
123
145
170
245
300
362
B
C
D
DE
E
without change-over with change-over selector
9 VT
10 M, MS, R, RM, G, V, VV M, MS, R, RM, G, V, VV
12 M, MS, R, RM, G, V, VV M, MS, R, RM, G, V, VV
14 V, M, MS, R, RM, G V, M, MS, R, RM, G
16 M, R, RM, G M, R, RM, G
18 M, R, RM, (G) M, R, RM, (G)
22 M
without change-over with change-over selector
9 9
10 10 19
12 12 23
14 14 27
16 16 31
18 18 35
22 22
0
1
3W
G
1) Up to max. 107 operating positions (only type M)
OILTAPG
VACUTAPVT
VACUTAPVV
2 pole
x x
RI, GI
RI (forced current division)
RI
G
MI, RMI
OILTAPV
OILTAPM / MS
OILTAPR / RM
xxxx x xxx x xx xx xxBasic connection diagram
No. of poles
MI, RMI, RI, GI
M, MS, RM, R, G
MS, M, RM, R, G
VV
MS, M, RM, R, G, VIII Y
V, VV
No. of configured
sectors
(only 1-pole) 3 sectors
Application
Tap selector size
Not with selector switches and VACUTAPVV
R, G
M, RM
M, RM, R, G
M, RM, R
M, MS
On request
Um
1 sector
MS, M, RM, R, G,
V, VV
VT
Not for single-pole tap-changers
Application not with neutral point
Application with neutral point
2 sectors
MI, RMI; R
MI
M, RM, VV
M, VT I
3 pole
V (special design), VV
M, V
MSV (special design, not V I), VV
Reversing switch /
coarse tap 1)
1 mid-position
3 mid-positionsReversing switch
Coarse tap
0 mid-positions (without change-over selector)Mid-positions
Number of max.
operating positions
IUm
Type
V III D
Contacts
1 pole
V (not V I)
2 Characteristic properties of the on-load tap-changer
On-load tap-changer designations
8/13/2019 OLTC Technical Data
9/46
9TD 61/02061/02/01/0
2 Characteristic properties of the on-load tap-changer
Off-circuit tap-changer designations
- -
Off-circuit tap-changer U
Number of poles III
300
600
800
1000
>1000
06
12
18
05
11
17Y
D
ME
MD
SP
YD
S
xxxx
Contact circle 750 mm,
max. of 17 operating positions
Contact circle 550 mm,
max. of 11 operating positions
600 A
on request
1000 A
800 A
Contact circle 350 mm,
max. of 5 operating positions
x x
Max. rated through-
current
Highest voltage for
equipment Um [kV]
3 poles
300 A
xx
Basic connection diagram
xxx xx xx
17 operating positions
11 operating positions
5 operating positionsMax. number of
operating positions
Type of connection Linear off-circuit tap-changer for neutral application
Special connection
Linear off-circuit tap-changer for delta application
Single bridging off-circuit tap-changer
Double bridging off-circuit tap-changer
Series-parallel off-circuit tap-changer
Star-delta off-circuit tap-changer
Contact circle pitch
17.5
36
72.5
123
170
>170 on request
8/13/2019 OLTC Technical Data
10/46
10 TD 61/02 061/02/01/0
2.2 Through-current, step voltage and step capacity
The through-currentis the current flowing through the on-load tap-changer and off-circuit tap-changer while in service.The through-current of an on-load tap-changer usuallyvaries along the voltage regulating range (e. g., while therated power of the transformer remains the same).The maximum through-current which a transformer canhandle continuously must be used for the rating of the on-load tap-changer and off-circuit tap-changer. This maximumcontinuously permissible through-current of the transformer
is the rated through-current Iuof the on-load tap-changeror of the off-circuit tap-changer.
The step voltage is the operating voltage between adjacenttaps. The step voltage can remain the same or vary over theentire setting range. If the step voltage varies, the maximumstep voltage Ustof the transformer is used to rate the on-load tap-changer and the off-circuit tap-changer.
The maximum rated through-current Iumvaries with thedesign and is the maximum through-current of an on-loadtap-changer and off-circuit tap-changer to which the cur-rent-related type tests refer.
Therated step voltage Uiof an on-load tap-changer is thehighest permissible step voltage for a certain value of therated through-current Iu. Together with a rated through-current, it is known as the related rated step voltage.
The max. rated step voltage Uimvaries with the design andis the max. permissible step voltage of an on-load tap-changer and off-circuit tap-changer.
The transition resistors of the on-load tap-changer are de-signed for the existing values of the maximum step voltageUstand the rated through-current Iu of the transformer forwhich the on-load tap-changer is to be used.
Since the permissible rated through-current Iuand thepermissible step voltage Ustvary with the value of the tran-sition resistors, these rated values refer to the particularapplication.
If an on-load tap-changer is to be used with values forstep voltage and through-current other than thosedeclared in the order (e. g., transformer power increased dueto improved cooling or use of the on-load tap-changer inanother transformer), MR must determine whether this ispossible or whether the transition resistors must be changed.
This also applies when the desired new rated values Iuand
Ustare below the original values since the design of thetransition resistors not only affects the switching capacitystress of the contacts but uniform contact wear is alsodesired.
Fig. 5 Rated step capacity diagram of a diverter switch1 - upper limit point2 - lower limit point
The rated step capacity PStNis the product of ratedthrough-current Iuand related rated step voltage Ui:PStN
= Iu x Ui
Fig. 5shows the typical load limits of a diverter switch.This means that the permissible range on the voltage side islimited by the max. rated step voltage Uimand, on thecurrent side, by the max. rated through-current Ium.
The points of the curve located between limit points 1 and 2are determined by the permissible rated switching capacity.The permissible switching capacity between limit points 1
and 2 corresponds to related pairs of values for Iuand Uiand may be constant or varying.
The rated step capacity diagram as well as individual valuesfor Iuand Uiin limit points 1 and 2 are specified separatelyfor each type of on-load tap-changer (see TD of the parti-cular type).
The limit step capacityis the greatest step capacity whichcan be safely transferred. Every MR on-load tap-changer canswitch at least twice the rated through-current Iuat stepvoltage Ustfor which the on-load tap-changer was designed.
This limit switching capacity is documented with the type
test as prescribed by IEC 60214. Tap change operations withcurrents greater than twice the rated through-current Iumust be prevented with suitable measures.
Iu
KHW 371-3
Ui = Uim
Iu = Ium
Ui
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
11/46
11TD 61/02061/02/01/0
2.3 Insulation
The insulation strength of the various insulation distances ofthe on-load tap-changer and off-circuit tap-changer is de-termined by the individual technical data of the particulartype of tap-changer. The specified rated withstand voltagesof the insulation apply to new, thoroughly dried insulatingmaterial in treated transformer oil (at an ambienttemperature of at least 10 C).
Selection of an on-load tap-changer and off-circuit tap-
changer requires the following information.- The maximum network-frequency voltages during service
- The power frequency test voltages occurring during thetransformer test
- The impulse voltages (lightning impulse, switching im-pulse, wave cut off at the back and wave cut off at thefront) occurring during the transformer test
The transformer manufacturer is responsible for the correctselection of the rated withstand voltages as required by on-site insulation coordination. The required rated withstandvoltages must be provided for the different insulation
distances.
- Against ground
- With multiple-phase types, between the phases
- Between contacts of one phase
The required specifications depend on the type of regulation(e.g., with on-load tap-changers: regulation without change-over selector, reversing switch arrangement, coarse tappingarrangement) and the type of tap-changer. The relevantinsulation distances and their relation to the voltages of thetransformer windings are described in the technical data of
the particular tap-changer type.
2.4 Overload
2.4.1 Through-currents higher than rated through-current
MR on-load tap-changers and off-circuit tap-changers canbe used for all transformer loads as described in IEC60354:1991 (Loading guide for oil-immersed transformers)and ANSI C57.91-1995 (Guide for loading mineral-oil-immersed transformers).
IEC 60354 differentiates between three modes.
- Normal cyclic loading
- Long-time emergency cyclic loading
- Short-time emergency loading
ANSI C57.91 differentiates between four modes:
- Normal life expectancy loading
- Planned loading beyond nameplate rating
- Long-time emergency loading
- Short-time emergency loading
Suitability of an on-load tap-changer for the above modes isdocumented with the type test in accordance with IEC60214-1989.
With normal cyclic loading or normal life expectancyloading mode, through-currents greater than the ratedthrough-current may occur during a daily load cycle. If theoperating conditions described by IEC 60354 or ANSI C57.91are adhered to (i.e., duration and power during a daily cycle,transformer oil temperature, and so on), this constitutesnormal service and not an extraordinary load. For thisreason, through-currents greater than the rated through-current which may occur briefly in the above modes do not
need to be given special consideration when selecting theon-load tap-changer.
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
12/46
12 TD 61/02 061/02/01/0
2.4.2 Operation at increased transformer load withimproved cooling
Keep the following points in mind when specifying therequired rated through-current of an on-load tap-changer.
When a transformer is run with different capacities due todifferent conditions (e.g., type of cooling, ambient temper-ature), the greatest load must be taken as the basis for therated power when selecting the on-load tap-changer.See also IEC 60076-1:1993. This is necessary since the oil
temperature in the transformer is not reduced despite in-creased transformer cooling due to the increased load and,in contrast to the transformer, the external conditions of theon-load tap-changer are not improved. Another reason isthe design of the transition resistors of on-load tap-changersbased on the greatest through-current so that the switchingcapacity stress on the contacts of the on-load tap-changer islimited to permissible values.
2.4.3 Required specifications for modes which are notdefined by IEC 60354 or ANSI C57.91
When asked about overload conditions, MR requests a
definition based on the above modes to avoidmisunderstandings and to clearly describe the conditions ofservice. If the requested mode cannot be defined in relationto IEC 60354 or ANSI C57.91, the following specificationsbecome necessary.
- Through-currents and related load duration during onedays cycle
- Oil temperature of the transformer during one days cycle
- Expected number of tap changes during the load phasesof one days cycle (only for on-load tap-changers)
- Duration of overload service in days/weeks/months- Frequency of this overload service (e. g., once a year or
rarely, only when other transformers fail)
2.5 Stress on on-load tap-changers and off-circuittap-changers due to short circuit
Permissible stress due to short circuits is listed below.
- Rated short-time withstand current as r.m.s. value ofpermissible short-circuit current
- Rated peak withstand current as highest permissible peak
value of the short-circuit current- Rated short-circuit duration as permissible short-circuit
duration during stress with rated short-time withstandcurrent
All MR on-load tap-changers and off-circuit tap-changersmeet at least the requirements of IEC 60214:1989 pertainingto short-circuit strength. Calculation of permissible short-circuit duration with stress of short-time currents lower thanthe rated short-time withstand current, or calculation of thepermissible short-time current for short-circuit durationslonger than the rated short-circuit duration is possible withthe help of the following equation.
Ix *tx= IK *tK
with
IK: Rated short-time withstand current
tK: Rated short-circuit duration
Ix: Permissible short-time current for
short-circuit duration tx(with t
x
always greater than tk)
tx: Permissible short-circuit duration for
stress with Ix(with I
xalways smaller
than Ik)
Due to the dynamic stress alone from the impulse current, animpulse current greater than the rated peak withstand cur-rent is not permitted. This is the reason that recalculation of
the rated values for higher impulse currents and short-timecurrents for shorter short-circuit durations is not permitted!
Short-circuit stresses usually occur only rarely on transfor-mers in service. With applications with very frequent short-circuit stresses (e.g., special test transformers), this must beallowed for by selecting an on-load tap-changer with greatershort-circuit resistance. Information on amount and fre-quency of the expected short-circuit stresses is necessary forthis.
2.6 Forced current division
With single-pole on-load tap-changers and off-circuit tap-changers for large rated through-currents, current paths areconnected in parallel. A distinction is made between applica-tions with and without forced current division.
Applications with and without forced current division withthe same rated through-current require different on-loadtap-changer and off-circuit tap-changer designs. The mean-ing of forced current division differs for on-load tap-chan-gers and off-circuit tap-changers.
On-load tap-changerDuring the change-over operation of the diverter switch,uniform division of the current on the parallel contacts must
be ensured. This always requires a divided tap winding and adivided main winding. Leakage impedance between theparallel main windings must be at least three times the valueof the transition resistor of the on-load tap-changer.
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
13/46
13TD 61/02061/02/01/0
It is imperative that MR be consulted about theseapplications. You will need a drawing of the completewinding arrangement with all parallel winding parts.
Off-circuit tap-changer:The tap winding must be completely divided. In addition,some windings on the tap winding next to the main windingmust also be divided.
In arrangements with forced current division, parallelcontacts may not be jumpered. The voltage between the
parallel tap windings when stressed with impulse voltagemust be considered. The transformer manufacturer mustspecify the required impulse voltage strength between theparallel tap windings.
2.7 Permissible overexcitation
MR on-load tap-changers meet the requirements of IEC60076-1:1993 (5% overexcitation) and ANSI IEEE C57.12.00-2000 (10% overexcitation) .
2.8 Multiple-column on-load tap-changers
Regardless of whether activated by one or more motor-drives, multiple-column on-load tap-changers (e.g., 3 x M I)do not switch synchronously. When delta connections with avery large regulation range and very low voltage in an endposition are regulated where the voltage can then only begenerated from a few taps, this can cause excessively highcirculating currents in the delta winding (varies with con-nection group and short-circuit impedance of the transfor-mer). In such cases, the transformer manufacturer mustspecify the circulating current for different positions of theon-load tap-changer in the three phases so that MR canconsider the required increased switching capacity when
selecting the on-load tap-changer and designing thetransition resistors.
2.9 On-load tap-changer applications with variablestep voltage
In applications with variable step voltage, the greatestpossible step voltage must always be specified for theselection of the on-load tap-changer. Examples of suchapplications include:
- Variable magnetic flow
- Tap windings with different numbers of turns
- Load and position-dependent step voltage for phase-shifter transformers
- Service under unusually great fluctuation of the systemvoltage
When different value pairs of step voltage and relatedthrough-current are required for an on-load tap-changer,the combination must consist of maximum step voltage andmaximum through-current within the permissible switchingcapacity range of the pertinent on-load tap-changer type,even when the step voltage and this through-current do notoccur at the same time.
Example:A transformer is being run at constant power within a largerange of fluctuating line voltage. Then the highest step
voltage occurs with highest system voltage together with alow through-current in relation to the transformer load, andthe greatest through-current occurs together with the loweststep voltage at the lowest system voltage.The on-load tap-changer must then be designed as if thehighest step voltage occurs together with the highestthrough-current.
The reason for this is the necessary adjustment of the tran-sition resistance to both the step voltage and the through-current. In general, the following applies to this adjustment:High step voltages require high values for the transitionresistance. In contrast, high through-currents require lowvalues for the transition resistance.Therefore, a solution to transition resistance adjustment isonly possible if there is a resistance value which is suitableboth for the highest step voltage and the highest through-current. Otherwise, the value of the transition resistance inthe above example would have to be continuously adjustedto the different system voltages.
There is always a suitable resistance value if the value pair ofhighest step voltage and highest through-current is withinthe permissible switching capacity. If this pair of values islocated just outside the permissible switching capacity range,MR must check individual cases to determine whether asolution for the adjustment of the transition resistance is stillpossible. When the permissible switching capacity range issignificantly exceeded, an on-load tap-changer type withgreater switching capacity must be used.
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
14/46
14 TD 61/02 061/02/01/0
2.10 Coarse tap winding/tapped winding, leakageinductance
During the change-over operation from the end of thetapped winding to the end of the coarse tap winding (mid-position, see fig. 6)and the reverse switching direction, allturns of the coarse tap winding and the entire tappedwinding are located between the selected and pre-selectedtap.With these switching operations, this results in a muchhigher leakage inductance for the circuit of the on-load tap-
changer as the internal resistance of the step voltage thanfor all other switching operations during which only theleakage inductance of a step takes effect and this induc-tance can be ignored for the function of the on-load tap-changer.
The leakage inductance described above for coarse tap wind-ing/tapped winding generates a phase shift between break-ing current and recovery voltage on the resistor contacts ofthe diverter switch which may cause longer arcing times.
This leakage inductance must be specified for adjustment ofthe on-load tap-changer to these operating conditions.
In extreme cases, this leakage inductance can be the deter-mining factor for selecting the on-load tap-changer type.
KHW 447-4
Fig. 6 Leakage inductance in the mid-position
Fig. 7 Standard values without tie-in resistors
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
50.00
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320
R, G
M, MS, RM
V V
V
Breaking current Is [mA]
RecoveryvoltageUw(
kV)
2.11 Potential connection of the tap winding
The tap winding is briefly galvanically isolated from the mainwinding during the change-over operation of the reversingswitch or coarse tap selector. It assumes a potential resultingfrom the voltages of the adjacent windings and the couplingcapacities to these windings or to grounded parts. This po-tential shift of the tap winding generates correspondingvoltages between the breaking change-over selector contactssince one contact is always connected with the tap windingand the other contact is always connected with the main
winding.This voltage is called the recovery voltage Uw. When thechange-over selector contacts open, a capacitive currentcaused by the above coupling capacities of the tap windingmust be interrupted. This current is called the breaking cur-rent Is. The recovery voltage Uwand the breaking current Ismay cause excessive discharges on the change-over selector.The permissible range of recovery voltage Uwand breakingcurrent Isis shown in fig. 7for the various on-load tap-changer types.
Without tie-in resistors
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
15/46
15TD 61/02061/02/01/0
Fig. 8 Potential connections
(Reversing switch is in mid-position)a Tie-in resistor Rpb With potential switch Sp
and tie-in resistor Rp
a Connection to potential of the tap winding by a per-manently installed ohmic resistor (tie-in resistor)
b Potential switchConnection to potential of the tap winding by aohmic resistor which is only inserted (by a potentialswitch) during the change-over selector operation.
The constructive solutions for a and b vary depending on thetype of on-load tap-changer. For additional details pertain-ing to our delivery program, see TD 48, TD 50, TD 60, TD 82,TD 115, TD 130, TD 203 and TD 237.
KHW 164-2
a b
If appropriate calculations result in values outside the per-missible range shown in fig. 7, the tap winding must beconnected to a fixed potential during the switching opera-tion. This is accomplished with the following measures(see fig. 8).
Due to the potential connection of the tap winding with atie-in resistor, the recovery voltage Uwis decreased on thechange-over selector contacts while the breaking current Isisincreased by the additional current via the tie-in resistor. Fig.9shows for the different on-load tap-changer types therange of recovery voltage Uwand breaking current Iswhichcan be used without consulting with MR when tie-in resistorsare used.This figure applies to all cases where the breaking current Isis primarily determined by the tie-in resistor.
With tie-in resistors
Fig. 9 Standard values for tie-in resistor, breakingcurrent Isprimarily determined by tie-in resistor.
Since the recovery voltage Uwand breaking current Isarenot the only important criteria for evaluating the permissibleswitching capacity of a change-over selector, an evaluationby MR is required when the ranges in fig. 7 and fig. 9areexceeded.
Since a decrease in the recovery voltage Uwdue to the tie-inresistor is always accompanied by an increase in the breakingcurrent Is, a solution with permissible change-over selectorcapacity cannot always be found for winding arrangementswith poor capacitive coupling. If this is true, a change-overselector with a higher permissible breaking current must thenbe used or the winding arrangement must be changed. This iswhy prompt examination of the change-over selector capa-city is particularly important for high-power transformers(i.e., large coupling capacities) and high operating voltages(i. e., great potential shift of the tap winding during change-over selector operation).
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320
Breaking current Is [mA]
V V
V
M, MS, RM
R, G
RecoveryvoltageUw(
kV)
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
16/46
16 TD 61/02 061/02/01/0
Calculation of the recovery voltage Uwand the breakingcurrent Isas well as the design of the possibly necessary tie-in resistor can be handled by MR.
The following information is required for this.
- Winding arrangement (i.e., location of the tap windingwith respect to the adjacent windings)
- Capacitance of the tap winding to the adjacent windingsor capacitance of the tap winding against ground oradjacent grounded windings
- A.c. operating voltage across windings or the positions ofthe windings which are adjacent to the tap winding
In addition, the following information is needed todimension the tie-in measure.
- Expected stress due to lightning impulse voltage acrosshalf the tap winding
- A.c. voltage across half the tap winding under operatingand test conditions can usually be deduced from thenormal ordering specifications for the on-load tap-changers.
Example of the estimated calculation of the recoveryvoltage on the change-over selector
TransformerRated power: 13 MVAHigh voltage winding: 132 kV + 10%Delta connection: 50 HzTap winding with reversing switch(fig. 10)
Double concentric arrangement of the high voltage windingwith inside main winding (disk-type coils) and outside tapwinding (see page 17, fig. 11).Winding capacities:C1 = 1810 pF (between main and tap winding)C2 = 950 pF (between tap winding and ground)
On-load tap-changer:MS I 301/MS II 302 - 170/B-10 19 3 W
Fig. 10 Connection of the high voltage winding
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
17/46
17TD 61/02061/02/01/0
Fig. 11 Winding arrangement with the related windingcapacities
as well as for voltage exceeding C1
and consequently, the vector variable and the correspondingabsolute value can be calculated as follows:
Core Tank
US OS
Fig. 12 Vectorial diagram for calculation of therecovery voltages on change-over selectorcontacts (+) and (-)
Assuming that winding capacities C1 and C2 are effective inthe middle of the winding, the following equation applies torecovery voltages Uw+and Uw-(see fig. 12below).
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
18/46
18 TD 61/02 061/02/01/0
For C1 = 1810 pF C2 = 950 pF U1 = 132 kV UF = 13,2 kV
the following computational values result for the amount of recovery voltages UW+and UW-:
The breaking currents Is+und Isare:
Using the above number values, the following results:
Is+ = 63.97 mA
Is = 52.75 mA
Due to the high values for Uwa tie-in resistor is required.
After a tie-in resistor Rp = 280 k is installed, the following values are obtained:
Uw+= 19.6 kV Uw= 14.4 kV
Is+= 72.0 mA Is= 53.0 mA
Is--=.C2 + j .(C1 + C2)
U1 UF
2
U1
2 .3
Is+=.C2 + j .(C1 + C2)
U1 + UF
2
U1
2 .3
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
19/46
19TD 61/02061/02/01/0
2.12 On-load tap-changer in transformers for arcingfurnaces (cf. also ordering sheets)
When in service, overloads of up to 2.5 times the ratedtransformer load occur in on-load tap-changers which areused in transformers for arcing furnaces. The on-load tap-changers must be adjusted to these operating conditions.
Types V V, MS, M, RM, R and G: The permissible step voltage isreduced for the required rated through-current to 80 % ofthe relevant rated step voltages specified in the applicable TD.
Type V: V 200 (250) is not designed for this type of service.With V 350 (400) the rated through-current is limited to200 A.
2.13 Installing the on-load tap-changer and off-circuittap-changer
The on-load tap-changer and off-circuit tap-changer mustbe installed vertically. The maximum deviation is 1.
2.14 Activating the on-load tap-changer during thetransformer test
When the transformer is excited, the on-load tap-changermay only be activated under rated frequency. This alsoapplies to no load service.
2.15 Special applications
Examples: High voltage direct current, generator operation,phase shifter, traction transformer, portion of the harmonicwaves > 10 %
Please see extra ordering sheet.
2.16 Insulation oilsTo fill the oil compartment and the related oil conservator,use only new mineral oil for transformers in accordance withIEC 60296 (specification for unused mineral insulating oilsfor transformers and switchgear) and IEC 60422 (supervisionand maintenance guide for mineral insulating oils in electri-cal equipment).
2.17 Service in artic areas
If on-load tap-changer oil temperatures of less than -25 Care expected, this must be specified on the ordering sheet sothat a temperature control can be provided for reliableservice. The temperature control consists of the thermosensor and the measuring amplifier. The thermo sensor isinstalled in the on-load tap-changer head cover. It recordsthe temperature of the oil in the on-load tap-changer.The measuring amplifier is installed in the motor-drive. It isconnected to the control current circuit so that the motor-
drive is blocked for electrical service when the temperaturecontrol is activated.
Remember that ambient temperatures below -45 C maydestroy the gaskets of on-load tap-changers and accessories.
2.18 Hermetically sealed transformer with gas cushion
This is available on request. Requests to MR for informationon implementation must contain the maximum gas cushiondensity below the transformer cover.
2.19 Parallel jumpers for parallel connection of tapselector planes
a) With forced current division:
Parallel jumpers are not permitted
b) With unforced current division:
Parallel jumpers on the tap selector terminals are stillmandatory even when the tap winding was wound in twoor more wires and each of these coil taps is connected asa tapping connection to the terminal contacts.
This reliably prevents the following:
Introduction of circulating currents into the current
paths of tap selector and diverter switch Arcing on movable tap selector contacts due tocommutation
Overvoltages between adjacent tap selector terminalsconnected in parallel
The parallel jumpers are also required to ensure the tie-inresistor takes effect for all parallel connected windingparts when tie-in measures are used.
2 Characteristic properties of the on-load tap-changer
8/13/2019 OLTC Technical Data
20/46
20 TD 61/02 061/02/01/0
Position 19 18 17 11 10 9 3 2 1
Current-carrying
selector switch 9 8 7 1 K 9 3 2 1terminal
Change-over 0 0 0 +selector connects
0 0 0 0 0 + 0 +
0 + 0 + 0 +
Operation Raise
in direction Lower
Hand crank Clockwiserotation Counterclockwise
Tap selector Counterclockwise
contact bridge Clockwise
Motor drive by motor contactor K2control by motor contactor K1
>>
>
< >
>
8/13/2019 OLTC Technical Data
21/46
21TD 61/02061/02/01/0
3 Important information on construction and installation
4 Protective relay
Fig. 14Suction pipe connection S and draining cockE = bleeding valve
3.2 Oil suction pipe
OILTAP on-load tap-changers are usually equipped with anoil suction pipe (see fig. 14) .
On-load tap-changer VACUTAP are equipped with suctionpipe connection S, but not with an oil suction pipe.
KHW 379-2
3.3 Oil filter unit
The oil filter unit is used to clean or clean and dry the switchingoil in the on-load tap-changer.The unit can be fitted with a paper filter (only for cleaning) or acombi filter (for cleaning and drying). For more information, seemanual BA 18.
4 Protective relay
For information, see manual BA 59.
8/13/2019 OLTC Technical Data
22/46
22 TD 61/02 061/02/01/0
5 Motor-drive units ED-S, ED-L
5 Motor-drive units ED-S, ED-L
5.1 Function
The modularly designed motor-drive unit ED is used to adjustthe operating positions of on-load tap-changers/off-circuittap-changers in regulating transformers to the particularservice requirements.
The on-load tap-change operation is initiated by activatingthe motor-drive unit (single control pulse, from a device ofthe TAPCON series, for example). This tap changing opera-tion is always concluded regardless of whether additional
control pulses are output during the tap changing operation.Another tap change is not possible until all control devicesare at rest.
Fig. 15shows the switching sequence of an on-load tap-change operation.The dimensional drawings for motor-drive unit ED-S/ED-L(898801/898802) are listed in appendix 8.
Fig. 15 Switching sequence of an on-load tap-changeoperation
5.2 Type designations
The different basic designs of the ED motor-drive unit are identified with clear product designations.
Type designation Description Versions
ED100-ST Product designation Electric Drive
ED 100-ST Transmission gear design 100 = Small transmission gear (motor, 6.5 Nm)
200 = Large transmission gear (motor, 13/18 Nm)
ED 100-ST Protective housing design S = Small protective housing
L = Large protective housing
ED 100-ST Special applications = None
M = Monitoring
C = Plunger coil design
T = Voltage regulator TAPCON 240
MotorMotorMotorMotorMotordrivedrivedrivedrivedrive
TapTapTapTapTapselector
DiverterDiverterDiverterDiverterDiverterswitchoperation
Diverter switchDiverter switchDiverter switchDiverter switchDiverter switchcontactcontactcontactcontactcontactmovementmovementmovementmovementmovement
33 sections
Winding
KHW 220from KHW 938
8/13/2019 OLTC Technical Data
23/46
23TD 61/02061/02/01/0
5 Motor-drive units ED-S, ED-L
5.3 Technical data of the motor-drive unit
The technical data apply to the standard design but may differ from the delivered model. Subject to change without priornotice.
Motor-drive unit ED 100/200-S/L
Motor power 0.75 kW 2.0 kW 2.2 kW
Voltage 3 AC/N 230/400 V
Current 1.9 A 5.2 A 6.2 A
Frequency 50 Hz
Synchronous speed 1500 1/min
Rotation of the drive shaft per switching operation 16.5
Running time per tap change operationg ca. 5.4 s
Rated torque of the drive shaft 45 Nm 95 Nm 130 Nm
Hand crank rotations per switching operation 33 54
Max. number of operating positions 35
Voltage of the controller and heater AC 230 V
Power consumption of the control current circuit(control/operation) 100 VA/25 VA
Heating capacity 50 W with ED 100/200 S 60 W with ED 100/200 L
Temperature range (ambient temperature) -30 C to +50C
Test voltage against ground 2 kV
Weight ED 100 S: 80 kg ED 200 S: 80 kgED 100 L: 130 kg ED 200 L: 130 kg ED 200 L: 130 kg
8/13/2019 OLTC Technical Data
24/46
24 TD 61/02 061/02/01/0
6 Drive shaft
7 Selecting the on-load tap-changer
7.1 Selection principle
Optimum technical and economic results are obtained byselecting an on-load tap-changer which just meets therequirements of the service and test conditions of thetransformer. Safety margins for the individual on-loadtap-changer data are generally not required.
To select the on-load tap-changer, the following importantdata on the transformer winding to which the on-load tap-changer will be connected must be available.
Data of the transformer winding
1 Rated power PN2 Connection (star-point, delta, single-phase connection)3 Rated voltage, setting rang: UN(1 x %)4 Number of steps, basic connection of the tap winding5 Rated insulation level6 Voltage stress of the tap winding during test with
lightning impulse voltage and induced a.c. voltage
The following values for phase values are calculated fromthe above for the on-load tap-changer.
Basic data of the on-load tap-changer
From 1, 2 und 3: Max. tapping current ImaxFrom 3 und 4: Step voltage UStSwitching capacity PSt= USt
.Imax
The suitable on-load tap-changer is determined by thefollowing characteristics.
Determination of the on-load tap-changer -1st step
On-load tap-changer typeNumber of polesMax. rated through-current
6 Drive shaft 7 Selecting the on-load tap-changer
For information, see manual BA 42.
8/13/2019 OLTC Technical Data
25/46
25TD 61/02061/02/01/0
7 Selecting the on-load tap-changer
7.2 Example of selecting the on-load tap-changer
Example 1 (for connection, see fig. 16)
We are looking for the right on-load tap-changer for athree-phase power transformer with the following data.Rated power PN= 80 MVA,Star connectionRated voltage and setting range of the high voltage windingUN= 110 (1 11 %) kV, 9 Stufen,Reversing switch
Rated insulation level of the high voltage winding forUp= 230 kV, 50 Hz/550 kV, 1.2|50
Voltage stress on the tap winding across the setting range ofone phase (250 kV, 1.2|50/16 kV, 50 Hz, 1 min.) between twophases of the tapped winding (220 kV, 1.2|50/24 kV, 50 Hz,1 min.)
On-load tap-changer data:
Imax= 80. 103/110 (1 11 %) .3 = 472 A
USt= 110. 103.11 % / 9 .3 = 777 V
PSt= 472.777 .103 = 367 kVA
If necessary, we recommend checking the followingspecifications of the on-load tap-changer.
Breaking capacity of the diverter switchTemporary overloadPermissible short-circuit currentContact lifespan of the diverter switch
Further designation of the on-load tap-changer inaccordance with TD 61/section 2.1 must be completed byspecification of the following characteristics.
Determination of the on-load tap-changer -2nd step
Highest voltage for equipment Umof the on-load tap-changerTap selector size
Basic connection diagramNote:The technical data for the above determinedon-load tap-changer must be used. See TD 48, TD 50,TD 60, TD 82, TD 115, TD 124, TD 130, TD 203 or TD 237.
110 (1 11 %) kV
KHW 376o-3Fig. 16
8/13/2019 OLTC Technical Data
26/46
26 TD 61/02 061/02/01/0
Determination of the on-load tap-changer:
1st step
In acc. w. table 1:::::On-load tap-changer type: MNumber of poles: 3Max. rated through-current: 500 AOn-load tap-changer design: M III 500 Y
On-load tap-changerM III 500 Y123/B10 19 1 W is selected
2nd step
In acc. w. TD 50/section 1.2 (Survey: Examples of designconnection diagrams):Umof the on-load tap-changer: 123 kVTap selector size: BBasic connection diagram: 10 19 1 W
7 Selecting the on-load tap-changer
InsulationConnection
Starconnection
Rated power,maximumtapping
current
80 MVA472 A
On-loadtap changer,change-over
selector
9 steps,reversing switch
Type, number of poles,rated through-current
M III 500 Y
Um, tap selector size
123 / B
Basic connection diagram
10 19 1 W
to across theground setting range
550 kV 1.2I50 250 kV 1.2I50230 kV 50 Hz 16 kV 50 Hz
Rated voltage,setting range
110 (1 11 %) kV
8/13/2019 OLTC Technical Data
27/46
27TD 61/02061/02/01/0
7 Selecting the on-load tap-changer
110 kV
KHW 376u-3
220 (1 18 %) kV
Bild 17
Determination of the on-load tap-changer:
1st stepIn acc. w. table 1:
On-load tap-changer type: RNumber of poles: 3 x 1Max. rated through-current: 2000 AOn-load tap-changer design: 3 x R I 2002
2st stepIn acc. w. TD 115/section 1.2 Survey:
Examples of design connection diagrams:Ubof the on-load tap-changer: 110 kVUm(required): 170 kV Tap selector size: DBasic connection diagram: 12 23 1 W
On-load tap-changer data:
Imax= 600. 103/220 (1 18 %) .3 = 1920 A
USt= 220. 103.18 % / 11 .3 = 2078 V
PSt= 1600.1759 .103 = 3990 kVA
On-load tap-changer 3 x R I 2002170/D12 23 1 W is selected
InsulationRated power,
maximum
tappingcurrent
600 MVA1920 A
On-loadtap-changer,change-over
selector
11 steps,reversing switch
Type, number of poles
rated through-current
3 x R I 2002
Um, tap selector size
170 / D
Basic connection diagram
12 23 1 W
Rated voltage,setting range
220 (1 18 %) kV
Connection
autotransformer
starconnection
to across the
ground setting range
550 kV 1.2I50 480 kV 1.2I50230 kV 50 Hz 49 kV 50 Hz
Example 2 (see fig. 17)
We are looking for the right on-load tap-changer for athree-phase current auto-transformer with the followingdata.:
Rated power PN= 600 MVA,Star connectionRated voltage and setting range of the high voltage windingUN= 220 (1 18 %) kV/110 kV, 11 steps,Reversing switch
Rated insulation level of the intermediate voltage windingfor Up= 230 kV, 50 Hz/550 kV, 1.2I50.
Voltage stress on the tap winding along the setting range480 kV, 1. 2I50/49kV, 50 Hz, 1 min.
8/13/2019 OLTC Technical Data
28/46
28 TD 61/02 061/02/01/0
8 Appendix
Oil filter plant OF 100, dimension drawing ..................................................................................................................................................... 898718
Oil filter plant OF 100, control cabinet, dimension drawing ..................................................................................................................... 897688
Protective relay RS 2001, dimension drawing ................................................................................................................................................. 899084
Motor-drive unit ED-S, protective housing ...................................................................................................................................................... 898801
Motor-drive unit ED-L, protective housing ...................................................................................................................................................... 898802
Bevel gear CD 6400 .................................................................................................................................................................................................. 892916
Motor-drive unit ED-S, motor-drive unit ED-L, limit dimensions of the vertical drive shaft .......................................................... 898598
Electronic voltage regulator TAPCON 230, flush and projected panel mounting ............................................................................. 899564
Electronic voltage regulator TAPCON 240, 19-inch module rack ........................................................................................................... 899580
LED display panel, dimension drawing ............................................................................................................................................................... 899144
Position indicating instrument with square front frame, dimension drawing ..................................................................................... 897897
Position indicating instrument with rectangular front frame, dimension drawing and connection diagram ........................... 898105
Power supply unit for position indicator, dimension drawing ................................................................................................................... 898106
Digital remote position indicator, signal transmitter, dimension drawing ............................................................................................ 898699
Digital remote position indicator, 7-segment display, dimension drawing ........................................................................................... 899700
Digital remote position indicator, connection diagram ............................................................................................................................... 707281
Digital remote position indicator by selsyn transmitter, dimension drawing ................................................................................... 00711TM
8 Appendix
8/13/2019 OLTC Technical Data
29/46
29TD 61/02061/02/01/0
Oil filter plant OF 100
Dimension drawing8987182E
8/13/2019 OLTC Technical Data
30/46
30 TD 61/02 061/02/01/0
Oil filter plant OF 100
Control cabinet, dimension drawing8976882M
8/13/2019 OLTC Technical Data
31/46
31TD 61/02061/02/01/0
Protective relay RS 2001
Dimension drawing8990841E
Inspection
window
Identification label
GasketGasket
Cable gland
PG 16
Test push buttonsIN SERVICE OFF
(reset) (test tripping)
The arrow must always point towards the oil pipe leadingto the oil conservator of the transformer.
Plan view of test push buttons(cover removed)
1)NO - normally open, NC - normally closed, CO - change-over contact
The protective relay is to be connected in such a way that if it is energized, the power transformer is switched off immediately by the corresponding
circuit breakers.
Standarddesign
Specialdesignagainstsurcharge
0.65 -NO1 1.2 - NO A
3.0 - NO4.8 - NO
0.65 -NC2 1.2 - NC B
3.0 - NC4.8 - NC
0.65 -CO3 1.2 - CO C
3.0 - CO4.8 - CO
0.65 - 2NO4 1.2 - 2NO 2 A
3.0 - 2NO4.8 - 2NO
0.65 - 2NC5 1.2 - 2NC 2 B
3.0 - 2NC4.8 - 2NC
0.65 - NO + NC6 1.2 - NO + NC 1 A & 1 B
3.0 -NO + NC4.8 -NO + NC
Key of variants
Variant Arrangement of terminalsRelay designation1)Contact positions
In service Off
Design
Metal - dummy plug PG 16
Reed
contact
8/13/2019 OLTC Technical Data
32/46
32 TD 61/02 061/02/01/0
Motor-drive unit ED-S
Protective housing8988012E
Vertical guard plate with
spacing ring Hand crank
Wall of transformer tank
3 dummy plates for packing glands
special design with OLTC monitoring required
Shim
Attachment of protective housing
ca. 690 if opened 130
ca. 864 if opened 180
The cover can be opened
to the left or to the right
depending on the arrange-
ment of the hinge pins.
Aperture of fixing holes on protective housing
(rear view)
Aperture in protective housing for cables
(underside view)
* for design with
intermediate bearing
8/13/2019 OLTC Technical Data
33/46
33TD 61/02061/02/01/0
Motor-drive unit ED-L
Protective housing8988022E
Aperture of fixing holes on protective housing(rear view)
Aperture in protective housing for cables(underside view)
Vertical guard plate withspacing ring Hand crank
Wall of transformer tank
3 dummy plates for packing glands
special design with OLTC monitoring
required
Shim
Attachment of protective housing
ca. 690 if opened 130
ca. 864 if opened 180
The cover can be opened
to the left or to the right
depending on the arrange-
ment of the hinge pins.
* for design with
intermediate bearing
8/13/2019 OLTC Technical Data
34/46
34 TD 61/02 061/02/01/0
e1=205forstandarddesi
gn
e2=215fordesignwithballjoint
Bevel gear CD 6400
Dimension drawing8929166E
8/13/2019 OLTC Technical Data
35/46
35TD 61/02061/02/01/0
Motor-drive unit ED-S/ED-L with CD 6400
Limit dimensions of the vertical drive shaft8985980E
8/13/2019 OLTC Technical Data
36/46
36 TD 61/02 061/02/01/0
Electronic voltage regulator TAPCON 230
Flush and projected panel mounting8995640E
Clamp for
flush mounting
Remove crimp cable-entries for flush
mounting
Bracketing fishplatefor panel mountig
Panel cutout forflush mounting
8/13/2019 OLTC Technical Data
37/46
37TD 61/02061/02/01/0
Electronic voltage regulator TAPCON 240
19-inch module rack8995800E
8/13/2019 OLTC Technical Data
38/46
38 TD 61/02 061/02/01/0
LED display panel
Dimension drawing8991440E
8/13/2019 OLTC Technical Data
39/46
39TD 61/02061/02/01/0
Position indicating instrument with square front frame
Dimension drawing8978973M
8/13/2019 OLTC Technical Data
40/46
40 TD 61/02 061/02/01/0
Position indicating instrument with rectangular front frame
Dimension drawing and connection diagram8981053M
8/13/2019 OLTC Technical Data
41/46
41TD 61/02061/02/01/0
Power supply unit for position indicator
Dimension drawing8981062M
8/13/2019 OLTC Technical Data
42/46
42 TD 61/02 061/02/01/0
Digital remote position indicator
Signal transmitter, dimension drawing8986990M
8/13/2019 OLTC Technical Data
43/46
43TD 61/02061/02/01/0
Digital remote position indicator
7-segment display, dimension drawing8987000M
8/13/2019 OLTC Technical Data
44/46
44 TD 61/02 061/02/01/0
Digital remote position indicator
Connection diagram70728100
8/13/2019 OLTC Technical Data
45/46
45TD 61/02061/02/01/0
Digital remote position indicator by selsyn transmitter
Dimension drawing00711TM
8/13/2019 OLTC Technical Data
46/46
www.reinhausen.com
Maschinenfabrik Reinhausen GmbH Phone +49 941 40 90-0Falkensteinstrasse 8 Fax +49 941 40 90-11193059 Regensburg, Germany E-Mail [email protected]