Level Measurement - Water and Waste Water Industry
Level Measurement Technologies in the Water and Waste Water Industry
• Ultrasonic• Submersible Pressure• Guided Wave Radar• Free Space Radar• Capacitance• Vibration• Conductivity• Floats
INTERNAL
The Prosonic Family
Level Measurement - Water and Waste Water Industry
Value
Perfo
rman
ce
Prosonic TFMU30
Prosonic MFMU4x
Prosonic SFMU9x/FDU9x
Hopefully, it wasn’t a secret to you that E+H sells ultrasonic level
instruments!
INTERNAL
Secret #1 – The FMU30
Level Measurement - Water and Waste Water Industry
For on site operation
display
FieldCare (with service DTM)
Two versions: 1½”/2” with
16 ft. / 26 ft. in liquids
Certificates:Reliable software algorithms and software structure, electronic components Ex ia /IS
INTERNAL
Secret #2 – Dynamic Build Up Compensation
Level Measurement - Water and Waste Water Industry
• Unit monitors the amplitude of the signal at the transducer membrane
• When the amplitude is dampened, build up is detected
• Unit automatically adjusts power to the transducer face, continually ensuring the transducer face is free of build up
INTERNAL
Secret #3 – Decoupled Transducer Housing
Level Measurement - Water and Waste Water Industry
• Transducer housing is decoupled via an inner ring
• Eliminates false high levels due to ringing:• Caused by over tightening• Temperature effects of a metal coupling
Mechanical decoupling with an inner ring
INTERNAL
Secret #4 FDU90 Sensor – The Little Brother of the FDU9x Sensors
Level Measurement - Water and Waste Water Industry
-40°F /
176°F
(302°F)
-40°F/
203°F
-40°F /
203°F
-40°F / 221°F
(275°F)
-40°F /
176°F
-40°F / 176°FTemperature range
272315.711.811.82.7Blocking distance [in]
10 - 21
PSIA
10 - 58
PSIA
10 – 58 PSIAPressure
137493316164Max. measuring distance
(solids) [ft]
8265333310Max. measuring distance
(liquids) [ft]
FDU95FDU93FDU92FDU91FFDU91FDU90
10 - 58
PSIA
10 - 43
PSIA
10 - 58
PSIA
INTERNAL
Secret #5 Alternating Pump Control
Level Measurement - Water and Waste Water Industry
• Up to 6 pumps to program• Control possibilities:
1. By Limits (high or low)2. By pump rate (to reach a programmed pump rate in dependence of the inflow of a lift station) – “stand by function”
• Alternating function selectable• For each pump: Switch on delay, backlash function, crust
reduction and error handling programmable
Lift Station
ChannelNetwork
M
INTERNAL
Pump Control by Pump Rate
Level Measurement - Water and Waste Water Industry
Level
t min
Inflow 1
Target emptying rate
Pump 1+2+3 on
Pump 1 on
Pump 1+2 on
Switch on
Switch off
INTERNAL
Secret #6 Crust Reduction
Level Measurement - Water and Waste Water Industry
To reduce crust building at the walls of a pump shaft a variable switch point (e.g. +/- 2%) for pumps is programmable.
Why ? Crust at the wall can cause wrong readings and the customer has to clean it, using crust reduction reduce
maintenance time.
Switch on
Switch off
Level
t
+/- 2%
+/- 2%
Switch on
Switch off
+/- 2%
+/- 2%
INTERNAL
Level Measurement - Water and Waste Water Industry
Secret #7 Sludge Detection
Sludge detection:
• Ratio between Ld/Lu will be detected. For Ld/Lu smaller a programmed value the relay will set an alarm.e.g. Ld/Lu should be bigger than 0,6
Level upstream Lu Level downstream Ld
Ratio =0,80,70,60,5
e.g. Sludge detection in flumes
INTERNAL
Level Measurement - Water and Waste Water Industry
Secret #8 Backwater Detection
• The ratio of the downstream depth to the upstream depth is expressed as a percentage and referred to as the submergence ratio.
• Calibration tests show that the discharge of a flume is reduced once the submergence ratio exceeds certain specified ratios.
• Once the submergence ratio exceeds these values, the flume is operating under submerged conditions and the flow rate is adjusted according to submerged discharge tables/formulas.
• As the ratio increases, the flow rate decreases. At a ratio of 1.0, the flow rate will be 0.
Ratio = 0.8
INTERNAL
Secret #9 Measuring Level and Flow in Storm Water BasinLevel Measurement - Water and Waste Water Industry
Level
4 ... 20 mA
Over
flow
4 ... 20 mA
Storm water basin
to river
Level
Over
flow
Easy to order:
Customer chooses via structure:
- 1 x sensor FDU 9x
- 2 x 4 ... 20 mA
- Application: Flow + Level
Benefit:
Only one sensor to measure two
parameters
lower cost
INTERNAL
Sewer system monitoring
Level - Continuous Liquids - Ultrasonic
overflowbarrier
• Control the filling level if the channel is used as storm water basin
• Calculate amount of raw sewage that is discharged into the river
• Channel blockage monitoring
INTERNAL
Flow measurement in open channels and weirs
• Records volume water flowing into treatment plant.
• The relationship between level and flow in a wastewater channel is represented in a Q/h curve
• Many channel and weir configurations are stored in Prosonic S
• Other channels can be programmed via a 32-point chart or via parameters.
Level - Continuous Liquids - Ultrasonic
INTERNAL
Inlet control: Rake/screening control for cleaning
• Measurement of differential level before and after the rake/screen with Prosonic S and 2 x FDU 90/91 sensors.
Slide 18
INTERNAL
Level Measurement - Water and Waste Water Industry
Water and Waste Water Industry
What applications in Water and Wastewater would we look at
technologies other than Ultrasonic Level Transmitters?
INTERNAL
Lift Stations
Level Measurement - Water and Waste Water Industry
FMX21
Submersible Pressure
Process Indicator with Pump Control
RIA452
INTERNAL
Level Measurement - Water and Waste Water Industry
Bulk Hydrochloric Acid Storage Tank
• Replaced an Ultrasonic Transmitter• Problems
• Fumes • Center Mount – re-focused
acoustic energy
• Free Space Radar• FMR51 Success
• Not affected by vapors• Fiberglass tank does not reflect
Microwaves
INTERNAL
Level Measurement - Water and Waste Water Industry
Sludge Digester Level
• Ultrasonic Transmitter Failed• Problems
• Irregular surface - foam• Warm environment -
Condensation • Methane and Carbon Dioxide
Fumes
• Free Space Radar• FMR54 Success
• Not affected by vapors• 6GHz less affected by
condensation and foam
INTERNAL
Level Measurement - Water and Waste Water Industry
Sewage Wet Well
• Ultrasonic Transmitter Failed• Problems
• Warm environment -Condensation
• Hydrogen Sulfide Vapors
• Free Space Radar• FMR50 Success
• Not affected by vapors• TFE Antenna design sheds
condensation
INTERNAL
Level Measurement - Water and Waste Water Industry
Chemical Storage in Plastic Tanks
• Plastic vessels are often used for aggressive / corrosive liquids
• The Levelflex Guided Wave Radar can be mounted on the outside of a plastic vessel
• Microwave energy penetrates through the plastic wall and reflects off the surface of the liquid providing a non-contact measurement
INTERNAL
Level Measurement - Water and Waste Water Industry
Scum Pit
• Ultrasonic Transmitter Failed• Problems
• Foam • Irregular surface
• Free Space Radar• FMR54 Success
• 6GHz better with foam• Larger beam angle helps
with irregular surface
INTERNAL
Level Measurement - Water and Waste Water Industry
Point Level Pump Protection
• Liquiphant mounted in the suction side piping for progressive cavity pumps
• When the Liquiphant indicates the line is empty, shut down pump to prevent “Run Dry” damage