LIBERTY® SERIES 1000VALVE REGULATED LEAD-CALCIUM BATTERY FOR STANDBY APPLICATIONS

Capacitiesfrom100to600Ampere-hours(8hoursto1.75VPC)343to2060Wattspercell(15minsto1.67VPC)

C&DTechnologiesvalveregulatedlead-acid(VRLA)batteriesareengineeredtoprovideperformancereliabilityandconsistencyoverthelifeoftheproduct.DesignedusingC&D’spatentedprocesses,these

productsofferlongbatterylifewithminimalmaintenance.TheversatileLiberty®Series100010-yearVRLAproductfitsvirtuallyanywhereandprovidessuperiorperformanceinthemostdemandingapplications.

SPECIFICATIONSElectrolyte at 77°F (25°C) 1.300specificgravitynominalsulfuricacid

System float voltages 2.25–2.27voltspercell

Life expectancy 10years,fullfloatserviceat77°F(25°C)

Container and cover High-impact,flame-retardantPVCFlammabilityratings:UL94-V0;ASTMD-635,self-extinguishingOxygenindex>32

Safety vent system Low-pressurereleasevalvewithflasharrester

Note:ACripplecurrentfromthechargershallnotexceed5percentofthe8hour(ampere-hour)ratingofthebattery.

UPS • DataCenters• NetworkOperationsCenters• IndustrialProcessControlFacilities• SemiconductorManufacturing• Banks&FinancialMarkets• PowerGenerationPlants• Hospital&TestingLaboratories• Emergency911responsecenters

Switchgear Utility• ElectricUtility• RailwaySignals• EmergencySystems• ManufacturingFacilities-AssemblyLines-ProcessControls• Petrochemicalprocessingplants• Pipelines

LEAD

RETURN

RECYCLE

ULRecognizedComponent

APPLICATIONS

12-373

12-373/0115/CD www.cdtechno.com

Page 2: LEAD LIBERTY SERIES 1000 - C&D Technologies• 100 percent of cells tested for conductance, voltage and capacity • Tested in accordance with Bellcore TR-NWT-000766 specifications

FEATURES & BENEFITS• Advanced,computer-controlledthermalcover-to-jarweldforgreaterreliabilityandconsistency

• Automated,state-of-the-art,cast-onstrapprocessensuresconsistent,high-quality,lowelectrical-resistancewelds

• Through-the-partitionintercellconnectionshortenscurrentpathsandincreasesperformance

• Copper-to-copperconnectionsminimizeresistance,especiallyathighrates,andshortenmaintenancetimebyreducingtheneedforretorquingconnections

• Patentedandtime-testedC&Dpostsealdesignwithsecondaryepoxysealtoincreaseintegrity -Leak-freeoperation -Superiorreliability

• Two-foldventsystem,comprisedofalow-pressuresafetyvalvewithflasharrester,minimizesbulgingandpreventsflashbackexplosionfromexternalignitionsource

• Thickradialgriddesignforbothpositiveandnegativeplatesimprovescurrentcarryingcapacityandperformanceresultinginlongfloatlife

• Fullyautomatedvacuumandfillingoperationresultsinuniformacidvolumedistributionandconsistentfloatvoltage

• Immobilizedelectrolytetechnologyusinganabsorbentglassmatdesign(AGM)offerssafehandlingandstorage

• Non-spillabledesignationforlowershippingcost•High-impactresistantPVCcontainerandcoverprovideexcellentwatervaporretention,preventingdryoutandoxygeninfiltration

MEASURABLE QUALITY AND OUTSTANDING PERFORMANCE• 100percentofcellstestedforconductance,voltageandcapacity

• TestedinaccordancewithBellcoreTR-NWT-000766specifications

• 100percentofcellstestedto95percentcapacityatthe8hourrateto1.75VPC

LS 12-100 LS 6-200 LS 4-300 LS 2-600*

Nominal voltage 12volts 6volts 4volts 2volts

Number of cells 6/unit 3/unit 2/unit 1/unit

Rated 8-hr to capacity (ampere-hours to 1.75 VPC)

100Ahto10.5volts

200Ahto5.25volts

300Ahto3.5volts

600Ahto1.75volts

Rated 15-min capacity (watts per cell to 1.67 VPC) 344 688 1030 2060

Internal resistance per cell 0.000786Ohms 0.000393Ohms 0.000262Ohms 0.000131Ohms

Short circuit current 2545A 5089A 7634A 15267A

Unit height 8.95in(227mm)

8.95in(227mm)

8.95in(227mm)

8.95in(227mm)

Unit length (includes handles)

16.58in(421mm)

16.58in(421mm)

16.58in(421mm)

16.58in(421mm)

Unit width 6.84in(174mm)

6.84in(174mm)

6.84in(174mm)

6.84in(174mm)

Weight 95lbs(43kg) 95lbs(43kg) 95lbs(43kg) 95lbs(43kg)

Plate thicknesspositive 0.140in

(3.56mm)

negative 0.085in(2.16mm)

Terminal characteristics

0.625indiameter,threadedcopperinsert,0.75indeep.Fastenwith1/4-20stainlesssteelhexbolt/washer.

*2cellsconnectedinparallelfor2-voltunits

SPECIFICATION

12-373/0115/CD 2 www.cdtechno.com

Page 3: LEAD LIBERTY SERIES 1000 - C&D Technologies• 100 percent of cells tested for conductance, voltage and capacity • Tested in accordance with Bellcore TR-NWT-000766 specifications

RATINGS IN AMPERES AT 77°F (25°C)

Final volts per cell

Reserve Time

Models 1 min 5 min 10 min 15 min 30 min 1 hr 2 hr 3 hr 4 hr 5 hr 6 hr 8 hr 10 hr 20 hr

1.95 LS12-100LS6-200LS4-300LS2-600

123.2246.5372.6739.4

115.1230.2348.5690.6

104.8209.5317.8628.6

94.6189.3287.6567.8

70.0140.1213.4420.2

45.791.4139.1274.2

28.156.385.5168.8

20.741.362.0124.0

16.332.749.098.0

13.527.040.581.0

11.623.134.769.3

9.118.127.254.3

7.515.022.545.0

4.18.312.424.8

1.90 LS12-100LS6-200LS4-300LS2-600

187.5374.9562.41124.7

169.4338.8508.21016.4

147.0293.9440.9881.8

126.8253.6380.4760.9

87.4174.9262.3524.6

55.5110.9166.4332.7

33.466.7100.1200.2

24.247.272.6145.1

19.038.157.1114.3

15.831.647.494.8

13.527.040.581.0

10.521.031.562.9

8.617.225.951.7

4.79.314.027.9

1.88 LS12-100LS6-200LS4-300LS2-600

216.1431.9616.21295.2

191.0382.3548.51148.3

161.5323.2467.9970.7

137.0273.9399.6820.2

93.0185.7273.0562.0

58.1113.5171.3350.9

34.869.7102.5208.0

25.250.474.3151.1

19.939.858.9119.5

16.533.049.099.1

14.228.342.184.7

11.022.132.965.8

9.118.127.153.9

4.89.714.428.3

1.85 LS12-100LS6-200LS4-300LS2-600

258.6517.1775.71551.4

224.2448.4672.61345.3

183.5367.0550.51100.9

151.9303.8455.8911.5

101.5203.0304.5609.0

62.4124.8187.3374.5

37.174.2111.3222.6

26.953.880.7161.4

21.242.463.6127.2

17.535.152.6105.3

15.030.044.989.9

11.623.234.869.6

9.519.028.456.9

5.09.914.929.7

1.84 LS12-100LS6-200LS4-300LS2-600

272.7545.4818.21636.4

233.9467.9701.81403.6

189.3378.6567.91135.8

155.8311.7467.5935.0

103.2206.5309.7619.4

63.3126.6189.8379.6

37.675.1112.9225.8

27.354.681.8163.6

21.643.264.4128.9

17.935.853.3106.6

15.330.645.590.9

11.923.835.270.4

9.719.528.757.4

5.110.215.030.0

1.80 LS12-100LS6-200LS4-300LS2-600

329.4658.8988.21976.5

272.4544.9817.31634.7

213.0426.0639.01278.0

171.7343.5515.21030.4

110.1220.1330.2660.3

67.0134.1201.1402.2

39.779.4119.2238.3

28.757.486.0172.1

22.545.167.6135.3

18.637.255.8111.6

15.831.747.595.1

12.224.536.773.5

10.020.029.959.9

5.210.415.631.2

1.78 LS12-100LS6-200LS4-300LS2-600

358.4716.51075.12149.6

284.2569.3852.51708.0

218.2435.1654.51305.3

175.3350.1525.91050.4

112.0224.5336.1673.4

68.0135.5204.0406.6

40.280.5120.7241.6

29.158.287.2174.6

22.845.768.5137.2

18.837.756.5113.2

16.132.148.296.4

12.424.837.274.4

10.120.230.360.6

5.310.515.831.5

1.75 LS12-100LS6-200LS4-300LS2-600

401.7803.51205.22410.4

302.2604.4906.51813.1

225.4450.7676.11352.2

180.3360.6540.91081.9

115.1230.1345.2690.4

69.4138.8208.2416.4

41.082.1123.1246.3

29.659.388.9177.8

23.346.669.9139.7

19.238.457.7115.3

16.432.749.198.2

12.625.037.575.0

10.320.630.961.9

5.410.716.132.2

Note:LibertySeries1000batteriesaretestedto95percentofpublishedratesattimeofshipmentat8hourrateto1.75VPC.AdditionalratingsandapplicationinformationisavailableintheBatterySelectionProgramatwww.cdstandbypower.net

12-373/0115/CD 3 www.cdtechno.com

Page 4: LEAD LIBERTY SERIES 1000 - C&D Technologies• 100 percent of cells tested for conductance, voltage and capacity • Tested in accordance with Bellcore TR-NWT-000766 specifications

RATINGS IN KW PER CELL AT 77°F (25°C)

Finalvoltspercell

ReserveTime

Models 1min 5min 10min 15min 20min 30min 1hr 3hr 5hr 8hr

1.95 LS12-100LS6-200LS4-300LS2-600

0.2400.4800.7201.440

0.2250.4510.6761.353

0.2070.4130.6201.239

0.1880.3750.5631.126

0.1700.3390.5091.017

0.1390.2790.4180.836

0.0910.1810.2720.544

0.0410.0830.1240.248

0.0280.0550.0830.165

0.0180.0370.0550.111

1.90 LS12-100LS6-200LS4-300LS2-600

0.3570.7131.0702.139

0.3240.6490.9731.946

0.2840.5680.8511.703

0.2470.4930.7401.480

0.2160.4310.6471.294

0.1720.3430.5151.030

0.1090.2190.3280.657

0.0480.0960.1440.289

0.0320.0630.0950.189

0.0210.0420.0630.126

1.85 LS12-100LS6-200LS4-300LS2-600

0.4790.9581.4362.873

0.4210.8421.2632.525

0.3490.6981.0472.094

0.2910.5810.8721.744

0.2490.4970.7461.492

0.1960.3920.5881.175

0.1220.2430.3650.729

0.0530.1060.1590.319

0.0350.0700.1050.209

0.0230.0460.0700.139

1.80 LS12-100LS6-200LS4-300LS2-600

0.5931.1861.7793.558

0.5021.0051.5073.015

0.3990.7991.1982.396

0.3240.6490.9731.946

0.2740.5480.8221.643

0.2110.4220.6331.265

0.1300.2600.3910.781

0.0560.1130.1690.338

0.0370.0730.1100.219

0.0240.0480.0720.145

1.75 LS12-100LS6-200LS4-300LS2-600

0.7031.4062.1094.218

0.5471.0941.6423.283

0.4160.8321.2492.497

0.3370.6731.0102.020

0.2840.5680.8531.705

0.2190.4380.6571.314

0.1340.2680.4020.804

0.0580.1160.1740.348

0.0380.0750.1130.226

0.0250.0500.0740.149

1.70 LS12-100LS6-200LS4-300LS2-600

0.8011.6022.4034.805

0.5751.1491.7243.448

0.4260.8531.2792.558

0.3430.6871.0302.060

0.2890.5790.8681.737

0.2220.4450.6671.335

0.1340.2680.4020.803

Notrecommendedtodischargelongerthan1hourbelow

1.75VPC.

1.67 LS12-100LS6-200LS4-300LS2-600

0.8571.7152.5715.143

0.5921.1861.7773.554

0.4360.8721.3092.618

0.3430.6871.0302.060

Notrecommendedtodischargelongerthan15min.below1.70VPC.

1.65 LS12-100LS6-200LS4-300LS2-600

0.8931.7872.6805.360

0.6031.2051.8083.615

0.4360.8731.3092.618

0.3440.6891.0332.067

1.63 LS12-100LS6-200LS4-300LS2-600

0.9291.8592.7885.576

0.6121.2231.8363.671

0.4370.8741.3102.620

0.3450.6911.0362.072

Note: LibertySeries1000batteriesaretestedto95percentofpublishedratesattimeofshipmentat8hourrateto1.75VPC.AdditionalratingsandapplicationinformationisavailableintheBatterySelectionProgramatwww.cdstandbypower.net

12-373/0115/CD 4 www.cdtechno.com

Page 5: LEAD LIBERTY SERIES 1000 - C&D Technologies• 100 percent of cells tested for conductance, voltage and capacity • Tested in accordance with Bellcore TR-NWT-000766 specifications

RACKSC&Disamajorsupplierofhigh-qualityVRLAbatteryrackstoTelecommunications,Switchgear&Control,andUPSmarkets.Bothstandardandmodularracksaredesignedandmanufacturedtosuitallcellconfigurations,includingmulti-rowandmulti-tierlayouts.C&Dracksmeetseismicloadingrequirements.ContactC&DTechnologiesforadditionalinformation.

Modular Rack

OPTIONAL ACCESSORIES

C&D’smodularracksprovideaflexible,efficientmethodforrackingLibertySeries1000batteries.Theseattractive,durableracksprovideaccessibilitytothebatteriesandareeasytoinstall.Racksareavailablein29inch(73.7cm)and43inch(109.2cm)lengthsandarestackable.Optionalpanelsareavailabletocompletelyencloseracks,providingacabinet-likeappearance.Pleasesee12-380formoreinformation.CompletestandbypowersystemsfromC&Dincludebatteries,racks,andelectronics.

Modular Rack with Panels

Steel JacketsFordemandingapplications,C&Dprovidesoptionalcomponentstoenhancebatterylife.Anoptionalsteeljacketisavailabletopreservejarshapeandmaintainelementcompressioninhigh-temperatureoperations.

Relay Rack Battery TraysC&Dmanufacturesawiderangeofbatterytraystomountin19inch(48.3cm)and23inch(58.4cm)relayracks.Pleasesee12-1064formoreinformation.

12-373/0115/CD 5 www.cdtechno.com

Page 6: LEAD LIBERTY SERIES 1000 - C&D Technologies• 100 percent of cells tested for conductance, voltage and capacity • Tested in accordance with Bellcore TR-NWT-000766 specifications

Copyright 2011 C&D TECHNOLOGIES, INC. Printed in U.S.A. 12-373 0115/CD

BATTERY CABINET SYSTEMSComplete,pre-packagedbatterycabinetsystemsareavailablefromC&DTechnologies.Systemsincludebatterybreakerorfuse,batterycablingandbatteries–allinstalledandreadytoconnecttoUPSuponinstallation.Optionsforbatterymonitoringwillalsobeavailable.

Powder-coatedsteelcabinetsareUL1778listedwithseismiczone4capabilityavailableasanoption.Fastactingfusesorcircuitbreakersareprovidedforsystemprotection.Batteriesaretestedtoassuresystemintegrity.