Produced on 20/11/2007 with VRV Xpress V2.4.1 - database Central 5.4
Project name
Reference .
Client name .
Selection parameters of the indoor units can be found under the chapter Indoor unit detailsSelection parameters of the outdoor units can be found under the chapter Outdoor unit detailsOnly the data published in the data book are correct. This program uses close approximations of these data.
1. Material ListModel Qty Description
RXYQ12P7W1B 1 Heat pump VRV III P COMPACT
RXYQ14P7W1B 2 Heat pump VRV III P COMPACT
RXYQ18P7W1B 1 Heat pump VRV III P COMPACT
RXYQ20P7W1B 1 Heat pump VRV III P COMPACT
RXYQ5P7W1B 1 Heat pump VRV III P COMPACT
RXYQ8P7W1B 1 Heat pump VRV III P COMPACT
FXZQ50M8 28 Z - 4-way blow ceiling mounted cassette (600x600)
VKM100GAV1 1 GA - Ventilation Air Reclaim
VKM50GAV1 1 GA - Ventilation Air Reclaim
VKM80GAMV1 2 GAM - Ventilation Air Reclaim
VKM80GAV1 7 GA - Ventilation Air Reclaim
KHRQ22M20T7 7 REFNET branch piping kit
KHRQ22M29T7 11 REFNET branch piping kit
KHRQ22M64T7 14 REFNET branch piping kit
DCS302B51 1 Centralised
BRC1D527 28 Wired remote control
BYFQ60BW1 28 Decoration panel
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 outdoors
VKM devices are considered as indoor units. They have an influence on the selection of outdoor units, the piping diagram, the wiring diagram and the centralized controller diagram.
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 1
2. Indoor Unit Details
2.1. Table of AbbreviationsName Logical name of the device Rq HC Required heating capacity
FCU Device model name HC Available heating capacity (with freeze-up correction)
Tmp C Indoor conditions in cooling (dry bulb temp. / RH) Airflow Supplied airflow at low and high fan speed
Rq TC Required total cooling capacity Sound Sound pressure low and high
TC Available total cooling capacity MCA Minimum Circuit Amps
Rq SC Required sensible cooling capacity WxHxD WidthxHeightxDepth
SC Available sensible cooling capacity Wght Weight of the device
Tmp H Indoor temperature in heating
2.2. Type A - Outdoor Unit - RXYQ20P7W1B
Actual capacity data at conditions and combination ratio (102%) as entered
Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD
°C kW kW kW kW °C kW kW m³/h dBA A mm
Type A - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575
Type A - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575
Type A - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575
Type A - FCU 4 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575
Type A - FCU 5 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575
Type A - FCU 6 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575
Type A - FCU 7 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575
Type A - VKM 1 VKM80GAMV1 24,0 / 50% n/a 7,1 n/a 4,5 20,0 n/a 7,2 640-750 36-36 4,3 1764x387x1214
Type A - VKM 2 VKM80GAMV1 24,0 / 50% n/a 7,1 n/a 4,5 20,0 n/a 7,2 640-750 36-36 4,3 1764x387x1214
Total 45,1 33,1 45,8
Diversified capacity data at conditions as entered and 100% combination ratio
Name TC SC HC
kW kW kW
Type A - FCU 1 4,4 3,5 4,6
Type A - FCU 2 4,4 3,5 4,6
Type A - FCU 3 4,4 3,5 4,6
Type A - FCU 4 4,4 3,5 4,6
Type A - FCU 5 4,4 3,5 4,6
Type A - FCU 6 4,4 3,5 4,6
Type A - FCU 7 4,4 3,5 4,6
Type A - VKM 1 7,1 4,5 7,3
Type A - VKM 2 7,1 4,5 7,3
Total 45,3 33,2 46,6
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 2
2.3. Type B - Outdoor Unit - RXYQ18P7W1B
Actual capacity data at conditions and combination ratio (102%) as entered
Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD
°C kW kW kW kW °C kW kW m³/h dBA A mm
Type B - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type B - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type B - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type B - FCU 4 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type B - FCU 5 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type B - FCU 6 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type B - VKM 1 VKM80GAV1 24,0 / 50% n/a 6,9 n/a 4,4 20,0 n/a 6,6 640-750 37,5-37,5 4,3 1764x387x1214
Type B - VKM 2 VKM80GAV1 24,0 / 50% n/a 6,9 n/a 4,4 20,0 n/a 6,6 640-750 37,5-37,5 4,3 1764x387x1214
Total 39,7 29,2 38,1
Diversified capacity data at conditions as entered and 100% combination ratio
Name TC SC HC
kW kW kW
Type B - FCU 1 4,3 3,4 4,2
Type B - FCU 2 4,3 3,4 4,2
Type B - FCU 3 4,3 3,4 4,2
Type B - FCU 4 4,3 3,4 4,2
Type B - FCU 5 4,3 3,4 4,2
Type B - FCU 6 4,3 3,4 4,2
Type B - VKM 1 6,9 4,4 6,8
Type B - VKM 2 6,9 4,4 6,8
Total 39,9 29,3 39,0
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 3
2.4. Type C - Outdoor Unit - RXYQ14P7W1B
Actual capacity data at conditions and combination ratio (100%) as entered
Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD
°C kW kW kW kW °C kW kW m³/h dBA A mm
Type C - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575
Type C - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575
Type C - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575
Type C - FCU 4 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575
Type C - FCU 5 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575
Type C - VKM 1 VKM100GAV1 24,0 / 50% n/a 9,3 n/a 5,9 20,0 n/a 9,8 820-950 38-38 4,3 1764x387x1214
Total 32,7 23,6 34,2
Diversified capacity data at conditions as entered and 100% combination ratio
Name TC SC HC
kW kW kW
Type C - FCU 1 4,7 3,6 4,9
Type C - FCU 2 4,7 3,6 4,9
Type C - FCU 3 4,7 3,6 4,9
Type C - FCU 4 4,7 3,6 4,9
Type C - FCU 5 4,7 3,6 4,9
Type C - VKM 1 9,3 5,9 9,8
Total 32,7 23,6 34,2
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 4
2.5. Type D - Outdoor Unit - RXYQ14P7W1B
Actual capacity data at conditions and combination ratio (103%) as entered
Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD
°C kW kW kW kW °C kW kW m³/h dBA A mm
Type D - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,6 n/a 3,5 20,0 n/a 4,8 600-840 33-41 0,9 575x286x575
Type D - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,6 n/a 3,5 20,0 n/a 4,8 600-840 33-41 0,9 575x286x575
Type D - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,6 n/a 3,5 20,0 n/a 4,8 600-840 33-41 0,9 575x286x575
Type D - FCU 4 FXZQ50M8 24,0 / 50% n/a 4,6 n/a 3,5 20,0 n/a 4,8 600-840 33-41 0,9 575x286x575
Type D - VKM 1 VKM80GAV1 24,0 / 50% n/a 7,4 n/a 4,7 20,0 n/a 7,6 640-750 37,5-37,5 4,3 1764x387x1214
Type D - VKM 2 VKM80GAV1 24,0 / 50% n/a 7,4 n/a 4,7 20,0 n/a 7,6 640-750 37,5-37,5 4,3 1764x387x1214
Total 33,4 23,5 34,3
Diversified capacity data at conditions as entered and 100% combination ratio
Name TC SC HC
kW kW kW
Type D - FCU 1 4,7 3,6 4,9
Type D - FCU 2 4,7 3,6 4,9
Type D - FCU 3 4,7 3,6 4,9
Type D - FCU 4 4,7 3,6 4,9
Type D - VKM 1 7,5 4,7 7,8
Type D - VKM 2 7,5 4,7 7,8
Total 33,6 23,6 35,2
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 5
2.6. Type E - Outdoor Unit - RXYQ12P7W1B
Actual capacity data at conditions and combination ratio (103%) as entered
Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD
°C kW kW kW kW °C kW kW m³/h dBA A mm
Type E - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,5 n/a 3,5 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type E - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,5 n/a 3,5 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type E - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,5 n/a 3,5 20,0 n/a 4,1 600-840 33-41 0,9 575x286x575
Type E - VKM 1 VKM80GAV1 24,0 / 50% n/a 7,3 n/a 4,6 20,0 n/a 6,5 640-750 37,5-37,5 4,3 1764x387x1214
Type E - VKM 2 VKM80GAV1 24,0 / 50% n/a 7,3 n/a 4,6 20,0 n/a 6,5 640-750 37,5-37,5 4,3 1764x387x1214
Total 28,1 19,6 25,1
Diversified capacity data at conditions as entered and 100% combination ratio
Name TC SC HC
kW kW kW
Type E - FCU 1 4,6 3,5 4,2
Type E - FCU 2 4,6 3,5 4,2
Type E - FCU 3 4,6 3,5 4,2
Type E - VKM 1 7,3 4,6 6,7
Type E - VKM 2 7,3 4,6 6,7
Total 28,3 19,7 25,9
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 6
2.7. Type F - Outdoor Unit - RXYQ8P7W1B
Actual capacity data at conditions and combination ratio (90%) as entered
Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD
°C kW kW kW kW °C kW kW m³/h dBA A mm
Type F - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 5,2 600-840 33-41 0,9 575x286x575
Type F - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 5,2 600-840 33-41 0,9 575x286x575
Type F - VKM 1 VKM80GAV1 24,0 / 50% n/a 7,1 n/a 4,5 20,0 n/a 8,3 640-750 37,5-37,5 4,3 1764x387x1214
Total 15,9 11,4 18,7
Diversified capacity data at conditions as entered and 100% combination ratio
Name TC SC HC
kW kW kW
Type F - FCU 1 4,4 3,4 5,2
Type F - FCU 2 4,4 3,4 5,2
Type F - VKM 1 7,1 4,5 8,3
Total 15,9 11,4 18,7
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 7
2.8. Type G - Outdoor Unit - RXYQ5P7W1B
Actual capacity data at conditions and combination ratio (80%) as entered
Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD
°C kW kW kW kW °C kW kW m³/h dBA A mm
Type G - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,2 n/a 3,3 20,0 n/a 5,4 600-840 33-41 0,9 575x286x575
Type F - VKM 1 VKM50GAV1 24,0 / 50% n/a 4,2 n/a 2,7 20,0 n/a 5,4 440-500 36-36 4,3 1764x387x832
Total 8,4 6,0 10,8
Diversified capacity data at conditions as entered and 100% combination ratio
Name TC SC HC
kW kW kW
Type G - FCU 1 4,2 3,3 5,4
Type F - VKM 1 4,2 2,7 5,4
Total 8,4 6,0 10,8
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 8
3. Outdoor Unit Details
3.1. Table of AbbreviationsName Logical name of the device Refrig Standard factory refrigerant charge (5m actual piping length),
Model Device model name excluding extra refrigerant charge
Comb Combination percentage For calculation of extra refrigerant charge refer to the VRV databook
Tmp C Outdoor temperature in cooling (dry bulb) PS Power supply (voltage and phases)
CC Cooling capacity Run Amps Running Amps
EER EER at selection and nominal conditions St Curr Starting current
Tmp H Outdoor temperature in heating (dry bulb) Fuses Fuses
HC Heating capacity (with freeze-up correction) WxHxD WidthxHeightxDepth
COP COP at selection and nominal conditions Wght Weight of the device
Piping Largest distance from indoor unit to outdoor unit
3.2. Outdoor DetailsName Model Comb Tmp C CC EER Tmp H HC COP Piping Refrig
% °C kW °C kW m kg
Type A - Outdoor Unit RXYQ20P7W1B 102 37,0 49,6 3,7 / 3,7 -7,0 45,8 3,1 / 4,1 45,0 16,3
* RXYQ12P7W1B
* RXYQ8P7W1B
Type B - Outdoor Unit RXYQ18P7W1B 102 37,0 43,5 3 / 3 -7,0 38,1 2,9 / 3,7 45,0 12,7
Type C - Outdoor Unit RXYQ14P7W1B 100 37,0 34,9 3,2 / 3,2 -7,0 34,2 2,8 / 4 45,0 12,3
Type D - Outdoor Unit RXYQ14P7W1B 103 37,0 35,7 3,2 / 3,2 -7,0 34,3 2,8 / 4 45,0 12,3
Type E - Outdoor Unit RXYQ12P7W1B 103 37,0 30,0 3,5 / 3,5 -7,0 25,1 3,1 / 4 45,0 8,6
Type F - Outdoor Unit RXYQ8P7W1B 90 37,0 19,5 4 / 4 -7,0 20,8 3,2 / 4,3 45,0 7,7
Type G - Outdoor Unit RXYQ5P7W1B 80 37,0 12,2 4 / 4 -7,0 13,5 2,9 / 4 45,0 6,2
Name Model PS Run Amps St Curr Fuses WxHxD Wght
A A mm kg
Type A - Outdoor Unit RXYQ20P7W1B 400V 3Nph 1860x1680x765 427
* RXYQ12P7W1B 14 75 cfr. local legislation
* RXYQ8P7W1B 7,5 cfr. local legislation
Type B - Outdoor Unit RXYQ18P7W1B 400V 3Nph 24,2 85 cfr. local legislation 1240x1680x765 325
Type C - Outdoor Unit RXYQ14P7W1B 400V 3Nph 18,4 84 cfr. local legislation 1240x1680x765 317
Type D - Outdoor Unit RXYQ14P7W1B 400V 3Nph 18,4 84 cfr. local legislation 1240x1680x765 317
Type E - Outdoor Unit RXYQ12P7W1B 400V 3Nph 14 75 cfr. local legislation 930x1680x765 240
Type F - Outdoor Unit RXYQ8P7W1B 400V 3Nph 7,5 cfr. local legislation 930x1680x765 187
Type G - Outdoor Unit RXYQ5P7W1B 400V 3Nph 5,1 cfr. local legislation 635x1680x765 159
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 9
4. Piping DiagramsPipes marked with * in the diagrams must be connected to the device with a reducing joint.
4.1. Piping Type A - Outdoor Unit
RXYQ12P7W1B
RXYQ8P7W1B
Ty pe A - Outdoor UnitRXYQ20P7W1B
12,7x28,6
9,5x19,1
BHFQ22P1007
KHRQ22M64T7
15,9x28,6Ty pe A - FCU 1
FXZQ50M86,4x12,7
KHRQ22M64T7
15,9x28,6Ty pe A - FCU 2
FXZQ50M86,4x12,7
KHRQ22M64T7
12,7x28,6Ty pe A - FCU 3
FXZQ50M86,4x12,7
KHRQ22M64T7
12,7x28,6Ty pe A - FCU 4
FXZQ50M86,4x12,7
KHRQ22M64T7
12,7x28,6Ty pe A - FCU 5
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe A - FCU 6
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe A - FCU 7
FXZQ50M86,4x12,7
KHRQ22M20T7
9,5x19,1Ty pe A - VKM 1VKM80GAMV1
6,4x12,7
Ty pe A - VKM 2VKM80GAMV1
6,4x12,7
4.2. Piping Type B - Outdoor Unit
Ty pe B - Outdoor UnitRXYQ18P7W1B
KHRQ22M64T7
15,9x28,6Ty pe B - FCU 1
FXZQ50M86,4x12,7
KHRQ22M64T7
12,7x28,6Ty pe B - FCU 2
FXZQ50M86,4x12,7
KHRQ22M64T7
12,7x28,6Ty pe B - FCU 3
FXZQ50M86,4x12,7
KHRQ22M64T7
12,7x28,6Ty pe B - FCU 4
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe B - FCU 5
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe B - FCU 6
FXZQ50M86,4x12,7
KHRQ22M20T7
9,5x19,1Ty pe B - VKM 1
VKM80GAV16,4x12,7
Ty pe B - VKM 2VKM80GAV1
6,4x12,7
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 10
4.3. Piping Type C - Outdoor Unit
Ty pe C - Outdoor UnitRXYQ14P7W1B
KHRQ22M64T7
12,7x28,6Ty pe C - FCU 1
FXZQ50M86,4x12,7
KHRQ22M64T7
12,7x28,6Ty pe C - FCU 2
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe C - FCU 3
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe C - FCU 4
FXZQ50M86,4x12,7
KHRQ22M20T7
9,5x19,1Ty pe C - FCU 5
FXZQ50M86,4x12,7
Ty pe C - VKM 1VKM100GAV1
6,4x12,7
4.4. Piping Type D - Outdoor Unit
Ty pe D - Outdoor UnitRXYQ14P7W1B
KHRQ22M64T7
12,7x28,6Ty pe D - FCU 1
FXZQ50M86,4x12,7
KHRQ22M64T7
12,7x28,6Ty pe D - FCU 2
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe D - FCU 3
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe D - FCU 4
FXZQ50M86,4x12,7
KHRQ22M20T7
9,5x19,1Ty pe D - VKM 1
VKM80GAV16,4x12,7
Ty pe D - VKM 2VKM80GAV1
6,4x12,7
4.5. Piping Type E - Outdoor Unit
Ty pe E - Outdoor UnitRXYQ12P7W1B
KHRQ22M64T7
12,7x28,6Ty pe E - FCU 1
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe E - FCU 2
FXZQ50M86,4x12,7
KHRQ22M29T7
9,5x22,2Ty pe E - FCU 3
FXZQ50M86,4x12,7
KHRQ22M20T7
9,5x19,1Ty pe E - VKM 1
VKM80GAV16,4x12,7
Ty pe E - VKM 2VKM80GAV1
6,4x12,7
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 11
4.6. Piping Type F - Outdoor Unit
Ty pe F - Outdoor UnitRXYQ8P7W1B
KHRQ22M29T7
9,5x19,1Ty pe F - FCU 1
FXZQ50M86,4x12,7
KHRQ22M20T7
9,5x15,9Ty pe F - FCU 2
FXZQ50M86,4x12,7
Ty pe F - VKM 1VKM80GAV1
6,4x12,7
4.7. Piping Type G - Outdoor Unit
Ty pe G - Outdoor UnitRXYQ5P7W1B
KHRQ22M20T7
9,5x15,9Ty pe G - FCU 1
FXZQ50M86,4x12,7
Ty pe F - VKM 1VKM50GAV1
6,4x12,7
5. Wiring Diagrams
P1P2 = 16-2 AWG 2 core non screened stranded wire (non polarity wiring system)F1F2 = 16-2 AWG 2 core non screened stranded wire (non polarity wiring system)
5.1. Centralized Controllerscentralised DCS302B51
centralised Ty pe A - Outdoor UnitRXYQ20P7W1B
Ty pe B - Outdoor UnitRXYQ18P7W1B
Ty pe C - Outdoor UnitRXYQ14P7W1B
Ty pe D - Outdoor UnitRXYQ14P7W1B
Ty pe E - Outdoor UnitRXYQ12P7W1B
Ty pe F - Outdoor UnitRXYQ8P7W1B
Ty pe G - Outdoor UnitRXYQ5P7W1B
F1,F2
L,N
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
OUT F1,F2
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 12
5.2. Wiring Type A - Outdoor Unit
RXYQ12P7W1B
RXYQ8P7W1B
Ty pe A - Outdoor UnitRXYQ20P7W1B
Q1,Q2
Q1,Q2
L1,L2,L3,N
22,7A 3Nph
L1,L2,L3,N
18,5A 3Nph
F1,F2IN F1,F2
Ty pe A - FCU 1FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe A - FCU 2FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe A - FCU 3FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe A - FCU 4FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe A - FCU 5FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe A - FCU 6FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe A - FCU 7FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe A - VKM 1VKM80GAMV1
L,N
F1,F2
Ty pe A - VKM 2VKM80GAMV1
L,N
14,9A 1ph
OUT F1,F2
to centralized controller
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 13
5.3. Wiring Type B - Outdoor Unit
Ty pe B - Outdoor UnitRXYQ18P7W1B
L1,L2,L3,N 32,5A 3Nph
F1,F2IN F1,F2
Ty pe B - FCU 1FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe B - FCU 2FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe B - FCU 3FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe B - FCU 4FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe B - FCU 5FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe B - FCU 6FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe B - VKM 1VKM80GAV1
L,N
F1,F2
Ty pe B - VKM 2VKM80GAV1
L,N
14A 1ph
OUT F1,F2
to centralized controller
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 14
5.4. Wiring Type C - Outdoor Unit
Ty pe C - Outdoor UnitRXYQ14P7W1B
L1,L2,L3,N 31,5A 3Nph
F1,F2IN F1,F2
Ty pe C - FCU 1FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe C - FCU 2FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe C - FCU 3FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe C - FCU 4FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe C - FCU 5FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe C - VKM 1VKM100GAV1
L,N
8,8A 1ph
OUT F1,F2
to centralized controller
5.5. Wiring Type D - Outdoor Unit
Ty pe D - Outdoor UnitRXYQ14P7W1B
L1,L2,L3,N 31,5A 3Nph
F1,F2IN F1,F2
Ty pe D - FCU 1FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe D - FCU 2FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe D - FCU 3FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe D - FCU 4FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe D - VKM 1VKM80GAV1
L,N
F1,F2
Ty pe D - VKM 2VKM80GAV1
L,N
12,2A 1ph
OUT F1,F2
to centralized controller
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 15
5.6. Wiring Type E - Outdoor Unit
Ty pe E - Outdoor UnitRXYQ12P7W1B
L1,L2,L3,N 22,7A 3Nph
F1,F2IN F1,F2
Ty pe E - FCU 1FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe E - FCU 2FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe E - FCU 3FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe E - VKM 1VKM80GAV1
L,N
F1,F2
Ty pe E - VKM 2VKM80GAV1
L,N
11,3A 1ph
OUT F1,F2
to centralized controller
5.7. Wiring Type F - Outdoor Unit
Ty pe F - Outdoor UnitRXYQ8P7W1B
L1,L2,L3,N 18,5A 3Nph
F1,F2IN F1,F2
Ty pe F - FCU 1FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe F - FCU 2FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe F - VKM 1VKM80GAV1
L,N
6,1A 1ph
OUT F1,F2
to centralized controller
5.8. Wiring Type G - Outdoor Unit
Ty pe G - Outdoor UnitRXYQ5P7W1B
L1,L2,L3,N 11,9A 3Nph
F1,F2IN F1,F2
Ty pe G - FCU 1FXZQ50M8
L,N
BRC1D527P1,P2
F1,F2
Ty pe F - VKM 1VKM50GAV1
L,N
5,2A 1ph
OUT F1,F2
to centralized controller
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 16
6. Device Options
6.1. Outdoor Unit OptionsModel Description Used by
BHFQ22P1007 Outdoor unit multi connection piping kit for 2 outdoors Type A - Outdoor Unit [RXYQ20P7W1B]
6.2. Indoor Unit OptionsModel Description Used by
BYFQ60BW1 Decoration panel Type A - FCU 2 [FXZQ50M8] Type A - FCU 3 [FXZQ50M8] Type A - FCU 4 [FXZQ50M8]
Type A - FCU 5 [FXZQ50M8] Type A - FCU 6 [FXZQ50M8] Type A - FCU 1 [FXZQ50M8]
Type B - FCU 1 [FXZQ50M8] Type B - FCU 2 [FXZQ50M8] Type A - FCU 7 [FXZQ50M8]
Type B - FCU 3 [FXZQ50M8] Type B - FCU 4 [FXZQ50M8] Type B - FCU 5 [FXZQ50M8]
Type B - FCU 6 [FXZQ50M8] Type C - FCU 1 [FXZQ50M8] Type C - FCU 2 [FXZQ50M8]
Type C - FCU 3 [FXZQ50M8] Type C - FCU 4 [FXZQ50M8] Type C - FCU 5 [FXZQ50M8]
Type D - FCU 1 [FXZQ50M8] Type D - FCU 2 [FXZQ50M8] Type D - FCU 3 [FXZQ50M8]
Type D - FCU 4 [FXZQ50M8] Type E - FCU 1 [FXZQ50M8] Type E - FCU 2 [FXZQ50M8]
Type E - FCU 3 [FXZQ50M8] Type F - FCU 1 [FXZQ50M8] Type F - FCU 2 [FXZQ50M8]
Type G - FCU 1 [FXZQ50M8]
The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.
Page 17