Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface
Zone 2/Div. 2
BulkEthernet
- +GND
FOUNDATIONfieldbus H1
Common Alarm Output- +
DiagnosticBus 1
+-
+-
DiagnosticBus 2
Ethernet FOUNDATION
fieldbus H1
PlantAsset
Management
Alarm
Alarm InputAlarmInput
ADGW
ADMADM ADMADM
PAM/DCS
Connection
Assembly
• System integration kit for Advanced Diagnostics
• DCS integration via Diagnostic Manager or device DTM
• Simple automatic setup of Advanced Diagnostics
• Summary alarm handling
• For FOUNDATION Fieldbus H1
Function
The FieldConnex® Diagnostic Gateway is the interface
between stationary Advanced Diagnostic Modules (ADM) and
the control system. It offers access to all ADM data in two
ways: via Ethernet and the Diagnostic Manager software or via
FOUNDATION Fieldbus H1 and DTM/EDD or both.
The gateway configures itself and automatically detects the
ADMs. The Diagnostic Manager automatically finds gateways
on the same subnet. The setup of the diagnostic bus and all
connected modules is automatic. This significantly simplifies
engineering of FieldConnex® Advanced Diagnostics.
Features
®
7/21/2019 KT-MB-GT2AD.FF
http://slidepdf.com/reader/full/kt-mb-gt2adff 2/3
R e l e a s e d a t e
2 0 1 2 - 1 0 - 0
9 1 5 : 3 5
D a t e o f i s s u e
2 0 1 2 - 1 0 - 0 9
2 3 9 8 1 8_
e n g . x m l
Technical data KT-MB-GT2AD.FF
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 2
Supply
Rated voltage 19.2 ... 35 V DC SELV/PELV
Rated current 120 ... 70 mA
Power loss max. 2.5 W
Fieldbus interface
Fieldbus type FOUNDATION Fieldbus
Physical layer profile profile type 114
ITK version 6Implementation resource block1x RS
function block4x MDI, 1x MDO, 1x MAI, 1x DI
transducer block16x ADM TB, 1x IO TB
Firmware update Ethernet
Polarity polarity-sensitive
Rated voltage 9 ... 32 V
Rated current 0 mA
Ethernet Interface
Port 100 BASE-TX
Protocol TCP/IP and UDP/IP
Services ICMP , DHCP , AutoIP , HTTP
Connection type RJ-45 socket, 8-pin
Transfer rate 100 MBit/s
Diagnostic Bus
Number of Diagnostic Bus Channels 2
Number of Diagnostic Modules/Channel 31 Using Ethernet Interface , 8 Using Fieldbus Interface
Termination integrated
Cable length/Channel 30 m
Indicators/operating means
LED ERR red: Hardware fault
LED PWR green: Power on
LINK/ACT yellow
CH1, CH2 yellow: diagnostic bus activity
Outputs
Output I alarm output diagnostic bus channel 1 , volt-free contact , NC contact
Voltage 50 V DC
Current ≤ 1 A
Output II alarm output diagnostic bus channel 2 , volt-free contact , NC contact
Voltage 50 V DC
Current ≤ 1 A
Output III common alarm , volt-free contact , NC contact
Voltage 50 V DC
Current ≤ 1 A
Electrical isolation
All circuits/FE functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output I, II/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Ethernet/Supply functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Ethernet/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Diagnostic Bus/other circuits functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Low voltage
Directive 73/23/EEC EN 61010
Standard conformity
Electrical isolation IEC 62103
Electromagnetic compatibility NE 21
Protection degree IEC 60529
Fieldbus standard IEC 61158-2
Climatic conditions DIN IEC 721
Shock resistance EN 60068-2-27Vibration resistance EN 60068-2-6
Ethernet IEEE 802.3
Ambient conditions
Ambient temperature -40 ... 60 °C (-40 ... 140 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
7/21/2019 KT-MB-GT2AD.FF
http://slidepdf.com/reader/full/kt-mb-gt2adff 3/3
R e l e a s e d a t e
2 0 1 2 - 1 0 - 0
9 1 5 : 3 5
D a t e o f i s s u e
2 0 1 2 - 1 0 - 0 9
2 3 9 8 1 8_
e n g . x m l
Technical data KT-MB-GT2AD.FF
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 3
Relative humidity < 95 % non-condensing
Shock resistance 15 g 11 ms
Vibration resistance 1 g , 10 ... 150 Hz
Pollution Degree max. 2, according to IEC 60664
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Housing material Polycarbonate
Protection degree IP20
Mass 470 g
Mounting DIN rail mounting
General information
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be
observed where applicable. For information see www.pepperl-fuchs.com.
Description
1 Advanced Diagnostic Gateway Module HD2-GT-2AD.FF.IO 9 Grounding terminal
2 Diagnostic bus channel 1 alarm output 10 FF-H1
3 Diagnostic bus channel 2 alarm output 11 Diagnostic bus channel 2
4 Serial, not used 12 Diagnostic bus channel 1
5 Common alarm output 13 Motherboard MB-FB-GT.AD.FF
6 Bulk power supply connection
7 Ethernet, 8-pin RJ-45 socket
8 Enable/disable simulation switch
Dimensions
114153
7 7 . 5
1 5 5
1 3
7
2 4
13
8
10
9
11
12
5 6
All dimensions in millimeters (mm) and without tolerance indication.