INSTRUMENT SECTION OF
LPG DEPARTMENT A
PART
OF
INSTRUMENTAION DEPARTMENT
INCORPORATED
SOPHISTICATED INSTRUMENTATION & CONTROL SYSTEM
FOR
SAFE & EFFICIENT OPERATION OF THE PLANT
SOPHISTICATED INSTRUMENTATION & CONTROL
SYSTEM
• Programmable Logic Controller
• Distributed Control System
• Advance Process Controller
SAFETY IN OIL’S LPG RECOVERY PLANT INCLUDES:
• ALARM AND SHUT-DOWN SYSTEM • SAFETY RELIEF VALVES • GAS DETECTION SYSTEM • FIRE ALARM SYSTEM • FIRE PROTECTION SYSTEM • FIRE EXTINGUISHERS • FIRE DRILL • REGULAR INSPECTION OF PLANT
L P G D E P A R T M E N T
ALARM AND SHUT-DOWN SYSTEM
• All the important equipment, process vessels etc. are provided with alarm and shut-down devices for critical operating parameters. • All the storage vessels are provided with high level alarms. • Emergency shut-down switches are provided in three different locations to shut-down the plant in case of any emergency. • Remote shut-down switches are provided in the local panels of two most important equipment- inlet gas compressor and expander- compressor. • Break glass type emergency/fire push buttons stations are provided at specific locations.
ALARMS FOR THE I/L COMPRESSOR
Alarm Parameters 1. Comp Low Oil Level (LSL-0401) 2. Comp Hi Oil Filter Pr. Diff. Pr.(PDSH)
3. Gear Hi Oil Filter Pr. Diff. Pr (PDSH-0501)
4. Comp Low Oil Pr (PDSL-0401)
5. Gear Low Oil Pr. (PSL-0502) 6. Comp Gas Filter Hi Diff. Pr. (PDSH-0413)
ALARM AND SHUT-DOWN SYSTEM OF INLET COMPRESS0R
The Inlet Compressor may be shutdown by depressing the STOP button or by opening of any safety interlock device.
Shutdown Parameters 1. Comp Low Oil Pr (PDSLL-0401) 2. Gear Low Oil Pr.(PSLL-0501) 3. Gear Hi Oil Temp(TSHH-0501) 4. Comp Hi Oil Temp(TSHH-0401) 5. Comp Hi Disch Temp (TSHH-0402) 6. Motor Over Load 1-OL 7. Comp Hi Pr (PSHH-0002) . Comp Low Suct. Pr (PSLL-0001)
3.374kg/sq.cm ; 2.812kg/sq.cm 1.100kg/sq.cm ; 1.00kg/sq.cm 57deg.C ; 85deg.C
135deg.C
1.055kg/sq.cm ;
204 Amp 37.962kg/sq.cm
Alarm & S/D Set Point
ALARM AND SHUT-DOWN SYSTEM OF EXPANDER COMPRESS0R
The Expander Compressor may be shutdown by pressing the red STOP button or by opening of any safety interlock device.
It is important to observe that all automatic valves have closed and the expander has stopped.
1. Exp.Comp Speed (SPD-) 2. Exp. I/L Screen (PDSDH-404) 3. Exp. Seal Gas (PDAL-700) 4. Exp. Thrust Bearing(PDSH-701 & 702) 5. Exp.Lub. Oil Pr Diff.Low (PDSDL-704)
Shutdown Parameters Alarm / S/D Set Point
6. Exp. Lub Oil Pr Diff alarm Low (PDAL-703) 7. Seal Gas Temp Low (TSDL-723) 8. Bearing Temp. Hi/Low (TSDH/TSDL-724) 9. Drain Lub Oil Temp. (TSDL/TSDH-725)
28350rpm / 29700rpm 3.516kg/sq.cm 2.45kg/sq.cm
14.064kg/sq.cm 26.371kg/sq.cm 27.777kg/sq.cm 16deg.C 82.2/15.55deg.C 82.2/26.60deg.C
Regen Gas & Hot Oil Heater :
1. Reg. Stack temp.(TSDH338) ; Set Pt. 477deg.C
2. Reg. Heater Outlet temp(TSDH337) ; Set Pt. 400deg.C 3. Hot Oil Stack temp (TSDH 817) ; Set Pt.350deg.C
4. Hot Oil Outlet temp(TSDH316) ; Set Pt. 345deg.C 5. Reg. Gas Low Flow (FSDL300) ; Set Pt. 0.422kg/sq.cm 6. Hot oil to Dr. Heater(FSDH-800) ; Set Pt. 0.844kg/sq.cm 7. HOT Oil to Dr.Heater (FSDL-800) ; Set Pt.0.428kg/sq.cm
MISCELLANEOUS ALARM/SHUTDOWN PARAMETERS 1. Instrument Air Pr Set Pt : 4.219 kg/sq.cm 2. Dust Filter (PDSDH306) ,, 2.461kg/sq.cm 3. Exp. Separator (PDSD406) ,, 16.174kg/sq.cm 4. Cooling water Pr. (PSDL900) ,, 1.85kg/sq.cm 5. Cooling Water temp (TSAH 900) ,, 40.5deg.C 6. Reg. Gas Cooler outlet temp(TSDH340) ,, 65deg.C 7. Dehydrator Outlet temp.(TSDH 339) ,, 76deg.C 8. Gas Detector Hi/HI-Hi Alarm ,, 20/40 % 9. I/L Motor winding temp ,, 120deg.C
10. I/L Comp. Bearing Temp. ,, 80deg.C 11. Debutaniser Reboiler Pump Leak Pr. ,, 0.105kg/sq.cm
12. I/L Filter Sep. High Level (LSDH 333) 13. De-ethaniser High Level (LSDH 440) 14. Booster Comp. Suct. Scrubber Hi. Level (LSDH 438) 15. Cold Separator High level (LSDH 439)
33 75
110 V. A.C N
44
INLET COMP.AUX.OIL PUMP MTR START RELAY CONTACT
4
3 2
2TR 180 Sec
4TR 16 ON DELAY(100Sec)
33
PDS 0401 Comp. Hi Oil Filter
31
2 3
4 4 TR 100Sec MAN
AUT
Rotary Switch
17 2MR
13L 18 2M
Comp.Aux.Oil.Pump Running
45
2MR
COMP.AUX.OIL PUMP MTR START RELAY CONTACT
GAS DETECTION SYSTEM:
•Flammable Gas Sensor •Sensing principle: Catalytic Combustion & Infrared •Detects most hydrocarbon gases in the LEL region •Rapid detection of leaky natural gas and LPG •Sensors are LPG and Natural Gas based type •Degree of Protection : IP 65 •Response Time : 10 seconds •Measuring Range : 0 – 100% • Analog Output : 4 – 20 mA with alarm facility • DCS compatibility
LOCATION OF GAS DETECTORS : •LPG Recovery Plant : • Total No of on line G.D : 20nos
•LPG Filling Plant : i) Empty & Filling shed :5nos
ii) Tanker Yard :3nos
Area: I/L Comp, Exp. Comp, De-Eth. & But.Reflx.Pump, Cooling tower, Gas & hot oil ,Bullet,Horton & Gasoline
GAS DETECTION SYSTEM Location Tag No. 1. Inlet compressor GD-01 2. Expander GD-02 3. De-ethanizer reflux pump GD-03 4. De-butanizer reflux pump GD-04 5. Old cooling tower top GD-05 6. LPG Bullet area A GD-06 7. LPG Bullet area B GD-07 8. Horton sphere pump area GD-08 9. Gasoline storage pump area GD-09 10. Hot oil heater area GD-17 11. Regen. gas heater area GD-18 12. Between de-butanizer & heater GD-19 13. De-butanizer pump area GD-20 14. New cooling tower top GD-21 15. Bullet pump house area C GD-22
Location Tag No. 16. Near Gasoline Tk. SV-18.06 GD-23 17. Near Gasoline Tk. SV-18.07 GD-24 18. Below horton sphere, S-101 GD-25 19. Below horton sphere, S-102 GD-26 Filling Plant: 20. FP cyl. Evacuation area GD-10 21. FP carousel area GD-11 22. Filling floor area 1 GD-12 23. Filling floor area 2 GD-13 24. Empty cyl. Floor 3 GD-14 25. LPG tanker filling pt. 2 GD-27 26. LPG tanker filling pt. 3 GD-28 27. LPG tanker filling pt. 4 GD-29
GAS DETECTION SYSTEM
RECOVERY PLANT AREA
BULLET AREA
HORTON SPHERE AREA
MCC ROOM
PUMP HOUSE
CT1 CT2
AIR COMP HOUSE
NEAR GATE
NEAR MCC ROOM
GD-01
NEARFIRE PUMP HOUSE
NEAR AIR COMP. HOUSE
CONDENSATE AREA
GAS DETECTION SYSTEM LOCATION OF DETECTORS: LPG RECOVERY PLANT
TOTAL QUANTITY OF DETECTORS IN RECOVERY PLANT: 19 NOS.
GD-02
GD-03
GD-04
GD-05 GD-21
GD-08
GD-25 GD-26
GD-06
GD-07
GD-22
GD-09
GD-17
GD-18
GD-19
GD-23
GD-24
EMPTY CYL. SHED FILLING SHED
CAROUSEL
GD-10 GD-11
Cy. Ev. Unit
GD-14
GD-12
GD-13
TANKER FILLING POINTS GD-27 GD-28 GD-29
GAS DETECTION SYSTEM LOCATION OF DETECTORS: LPG FILLING PLANT
TOTAL QUANTITY OF DETECTORS FILLING PLANT: 8 NOS.
FIRE PROTECTION SYSTEM :
Instrument section has provided the remote operation of deluge valves for bullet, horton spheres, condensate tanks,Debutanizer & De-ethanizer deluge valves,LPG filling sheds and tanker yards. The individual switch for LPG recovery is installed in the control panel of OLD CONTROL ROOM and for LPG Filling Plant in the outside varandha of Installation Manager’s office room.
THANKS TO ALL
1 MR 2 10
Comp. Motor Start Relay
19 R 10 2
7 5
6
3TR (30 sec) 44 43,75
22,24,59
S 39 1 4 43 1 MR
SV - 0401 Comp.Sump Vent Line valve Air Load 110 v A.C
N
42 43 1 MR
Comp. Motor Start relay
75
REMOVED
INLET COMP. CONTROL PANEL
7TR (30 min) 27
44
ON DELAY TIMER ( 30 SEC )
110 V. A.C N
1R 8 3 TR 1 15 14 3 1 6 2
1
13R
3 13 R 10 2
4
28
12L
7 TR L1 L2 3 4 3
1M
48
RUN INTERLOCK IN ELECTRICAL H.T PANEL
OFF DELAY ( 30 MIN )
ANTI RECYCLE TIMER
3, 27
5 1 3
7
COMP START
8 1TR 8 8
OFF DELAY
1 SEC COMP. STOP
RESET 6 7TR
(30 min)
REMOTE STOP 3
3
4 2
4 5
1R 10 2 7 6
5
1 TR (1Sec)
1 TR
INLET COMP. CONTROL PANEL (MODIFIED)
1, 5
26, 27
7, 52
7TR (30 min) 27
44
ON DELAY TIMER ( 30 SEC )
110 V. A.C N
1R 8 3 TR 1 15 14 3 1 6 2
1
13R
3 13 R 10 2
4
28
12L
7TR
3 4 3
1M
48
RUN INTERLOCK IN ELECTRICAL H.T PANEL
OFF DELAY ( 30 MIN )
ANTI RECYCLE TIMER
3, 27
5 1 3
7
COMP START
8 1TR 8 8
OFF DELAY
1 SEC COMP. STOP
RESET 6 7TR
(30 min)
REMOTE STOP 3
3
4 2
4 5
1R 10 2 7 6
5
1 TR (1Sec)
1 TR
INLET COMP. CONTROL PANEL (ORIGINAL)
1, 5
26, 27
7, 52
6TR
4
3 2 6TR
ON DELAY (10Sec)