DS193
ICF Finish System 100% Textured Acrylic Finishing Systems (TAFS) For Use Over Insulating Concrete Forms (ICF)
ICF Finish System Installation Details
TABLE OF CONTENTS
TAFS®OVER INSULATING CONCRETE FORMS
NOTE
DETAIL
TAFS Over ICFs CutawayBase Detail- Height Adjuster
Head/Sill- Bucksaver Rough Buck ICF 0.0.06ICF 0.0.05ICF 0.0.04ICF 0.0.03ICF 0.0.02ICF 0.0.01
Base Detail- Tapered Cut Form
ICF 0.0.07
Base Detail- Cut Form
Base Detail- EPS TrimBase Detail- Without Inspection Strip
DRYVIT MAKES NO REPRESENTATION REGARDINGCONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDINGCODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS ORPROJECT LOCATIONS. ALL COMPONENTS INDICATED INILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BEREQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BEDESIGNED, DETAILED AND ENGINEERED BYREPRESENTATIVES OF THE ARCHITECT, OWNER ORCONTRACTOR TO BE IN CONFORMANCE WITH MODEL CODES,ARCHITECTURAL AND ENGINEERING REQUIREMENTSPERTAINING TO SPECIFIC BUILDING PROJECTS.
DRYVIT MAKES NO WARRANTY, EXPRESSED ORIMPLIED, AS TO THE ARCHITECTURAL DESIGN,ENGINEERING, OR WORKMANSHIP OF PROJECTSUTILIZING DRYVIT SYSTEMS OR PRODUCTS.
THE LIABILITIES OF DRYVIT SHALL BE ASSTATED IN THE DRYVIT STANDARDWARRANTY. CONTACT DRYVIT FOR A FULLAND COMPLETE COPY OF THIS WARRANTY.
with EPS TrimHead/Sill- Wood Rough Buck
with EPS TrimICF 0.0.08
Head/Sill- Bucksaver Rough Buck ICF 0.0.09Head/Sill- Wood Rough Buck ICF 0.0.10
ICF 0.0.11Head/Sill- Flange MountICF 0.0.12Head/Sill- Recessed
ICF 0.0.13A/C PenetrationICF 0.0.14Eave Detail- Recessed Top PlateICF 0.0.15Eave Detail- Exposed Top PlateICF 0.0.16Eave Detail- Steel Roof RaftersICF 0.0.17Sloped Roof/Wall IntersectionICF 0.0.18Transition to Existing WallICF 0.0.19Transition Across ColumnICF 0.0.20Parapet Termination
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
Cutaway
ICF 0.0.01
TAFS OVER ICFs®
BY OTHERS
DRYVIT TAFS
BY OTHERS
DRYVIT TAFS OVERADDITIONAL LAYER OF EPS
Dryvit TAFSOver ICF
ICF
DRYVIT BASE COAT
DRYVIT REINFORCING MESH
DRYVIT BASE COAT
DRYVIT FINISH
ICF
DRYVIT ADHESIVE
EXPANDED POLYSTYRENEINSULATION BOARD (MIN. 1")
DRYVIT BASE COAT
DRYVIT REINFORCING MESH
DRYVIT BASE COAT
DRYVIT FINISH
Dryvit TAFSOver AdditionalLayer of EPSOver ICF
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DOCUMENTS
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT DRYFLEX
BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
WATERPROOFING MEMBRANE
& DRAINAGE / PROTECTION
BOARD AS SPEC'D
DRYFLEX TO BE LAPPED OVER
WATERPROOFING AT GRADE
LEVEL MIN 6"
DRYVIT FINISH
BURIED WEB FORM UNIT
SEE DETAIL BELOW
ELEV. OF TERMITE INSPECTION
STRIP ABOVE FIN. GRADE
6" TO 8" AS PER CODE
TEMPORARY PLYWOOD
FORM FASTENED TO WEBS
PRIOR TO CONCRETE PLACEMENT
TO CREATE INSPECTION STRIP
HEIGHT ADJUSTER (3-3/8")
2.
1. NOTE:
DETAIL RECOMMENDED WHEN ANINSPECTION STRIP IS REQUIREDBY LOCAL JURISDICTION OR BYPEST CONTROL OPERATORS
MINOR CRACKING IS POSSIBLE INTHE FINISHED EXTERIOR SURFACEAT ICF/CONCRETE TRANSITIONS
3.
FORM SPACE TO BE EQUAL
TO HEIGHT ADJUSTER AT
OPPOSITE SIDE OF FORM
APPLY REINFORCED DRYVIT
DRYFLEX® BASE COAT OVERINSPECTION STRIP EXTENDING
MIN. 6" OVER ICF ABOVE AND
BELOW, AND MIN. 12" FROM
GRADE
Base Detail - Height Adjuster
ICF 0.0.02
TAFS OVER ICFs®
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
ICF 0.0.03
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
SEE DETAIL BELOW
CUT SECTION OF FORM
4" MIN. OR AS REQUIRED
BY CODE
APPLY REINFORCED DRYVIT
DRYFLEX® BASE COAT OVERINSPECTION STRIP EXTENDING
MIN. 6" OVER ICF ABOVE AND
BELOW, AND MIN. 12" FROM GRADE
ELEV. OF TERMITE INSPECTION
STRIP ABOVE FIN. GRADE
6" TO 8" AS PER CODE
WATERPROOFING MEMBRANE
& DRAINAGE / PROTECTION
BOARD AS SPEC'D
DRYFLEX TO BE LAPPED OVER
WATERPROOFING AT GRADE
LEVEL MIN 6"
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE
COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT DRYFLEX
BASE COAT
TEMPORARY PLYWOOD
FORM FASTENED TO WEBS
PRIOR TO CONCRETE PLACEMENT
TO CREATE INSPECTION STRIP
DRYVIT FINISH
BURIED WEB FORM UNIT
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DOCUMENTS
MINOR CRACKING IS POSSIBLE INTHE FINISHED EXTERIOR SURFACEAT ICF/CONCRETE TRANSITIONS
DETAIL RECOMMENDED WHEN ANINSPECTION STRIP IS REQUIREDBY LOCAL JURISDICTION OR BYPEST CONTROL OPERATORS
1. NOTE:
2.
3.
Base Detail - Cut Form
®
ICF 0.0.04
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DOCUMENTS
MINOR CRACKING IS POSSIBLE INTHE FINISHED EXTERIOR SURFACEAT ICF/CONCRETE TRANSITIONS
DETAIL RECOMMENDED WHEN ANINSPECTION STRIP IS REQUIREDBY LOCAL JURISDICTION OR BYPEST CONTROL OPERATORS
1. NOTE:
2.
3.
4" MIN. OR AS REQUIRED BY CODE
CUT SECTION OF FORM
WITH 45° TAPER
APPLY REINFORCED DRYVIT
DRYFLEX® BASE COAT OVERINSPECTION STRIP EXTENDING MIN. 6"
OVER ICF ABOVE AND BELOW,
AND MIN. 12" FROM GRADE
BURIED WEB FORM UNIT
ELEV. OF TERMITE INSPECTION
STRIP ABOVE FIN. GRADE
6" TO 8" AS PER CODE
WATERPROOFING MEMBRANE
& DRAINAGE / PROTECTION
BOARD AS SPEC'D
DRYFLEX TO BE LAPPED
OVER WATERPROOFING AT
GRADE LEVEL MIN 6"
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT COMPATIBLE SEALANT
EPS FILLER MIN 1" ATTACHED
TO ICF WITH DRYVIT ADHESIVE
DRYVIT FINISH
Base Detail - Tapered Cut Form
®
ICF 0.0.05
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
BURIED WEB FORM UNIT
APPLY REINFORCED DRYVIT
DRYFLEX BASE COAT MIN.
12" FROM GRADE
WATERPROOFING MEMBRANE
& DRAINAGE / PROTECTION
BOARD AS SPEC'D
DRYFLEX TO BE LAPPED
OVER WATERPROOFING AT
GRADE LEVEL MIN 6"
MIN 6:12 SLOPE ON ALL
PROJECTING SURFACES
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT DRYFLEX®BASE COAT
EPS SHAPE
DRYVIT FINISH
DRYVIT ADHESIVE
SEE DETAIL 1, 2, & 3 WHENPROTECTION FROM WOODBORING INSECTS ISDETERMINED TO BENECESSARY
NOTE:1. DRYVIT RECOMMENDS THAT GROUND
FLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATEDON CONTRACT DOCUMENTS
2.
Base Detail - EPS Trim
®
ICF 0.0.06
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
DRYVIT FINISH
BURIED WEB FORM UNIT
WATERPROOFING MEMBRANE
& DRAINAGE / PROTECTION
BOARD AS SPEC'D
DRYFLEX TO BE LAPPED
OVER WATERPROOFING AT
GRADE LEVEL MIN 6"
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT DRYFLEX®BASE COAT (MIN. 6" ON EACH SIDE
OF ICF JOINT)
APPLY REINFORCED DRYVIT
DRYFLEX BASE COAT MIN. 12"
FROM GRADE
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATEDON CONTRACT DOCUMENTS
1. NOTE:
SEE DETAIL 1, 2, & 3 WHENPROTECTION FROM WOODBORING INSECTS ISDETERMINED TO BENECESSARY
2.
Base Detail - Without Inspection Strip
®
ICF 0.0.07
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
VINYL BUCK SYSTEM
DRYVIT FINISH
DRYVIT ADHESIVE
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
BURIED WEB FORM UNIT
FLANGE MOUNT WINDOW
MIN 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
MIN 6:12 SLOPE ON ALL
PROJECTING SURFACES
DRYVIT COLOR PRIME™ ORDEMANDIT® ON SURFACES TO
RECEIVE SEALANT
DRYVIT AQUAFLASH SYSTEM OR
DRYVIT FLASHING TAPE™ EXTENDED OVER ENTIRE SILL AND
ONTO FRONT FACE OF VERTICAL WALL
ATTACH EPS SHAPE WITH
VERTICAL NOTCHED TROWEL
ADHESIVE PATTERN
MIN 6:12 SLOPE ON ALL
PROJECTING SURFACES
MIN 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
DRYVIT AQUAFLASHâ SYSTEM ORDRYVIT BACKSTOPâ NT AND GRID TAPE
ALONG HEAD & JAMBS EXTENDED
TO THE INSIDE FACE OF THE WALL
EPS SHAPE
1/2" GYPSUM BRD.
Head/Sill - Bucksaver Rough Buck With EPS Trim
®
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
THIS DETAIL ISRECOMMENDED FOR USEIN COMBUSTIBLECONSTRUCTION ONLY.
NOTE:1. 2.
ICF 0.0.08
FLANGE MOUNT WINDOW
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
MIN 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
DRYVIT COLOR PRIME™ ORDEMANDIT® ON SURFACES TO
RECEIVE SEALANT
ATTACH EPS SHAPE WITH
VERTICAL NOTCHED TROWEL
ADHESIVE PATTERN
DRYVIT AQUAFLASH SYSTEM OR
DRYVIT FLASHING TAPE™EXTENDED OVER ENTIRE SILL AND
ONTO FRONT FACE OF VERTICAL WALL
MIN 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
DRYVIT AQUAFLASHâ SYSTEMOR DRYVIT BACKSTOPâ NT AND
GRID TAPE™ ALONG HEAD & JAMBS
EXTENDED TO THE INSIDE
FACE OF THE WALL
2"x12" ROUGH BUCK
W/ SILL GASKET
PRESSURE TREATED
AS SPECIFIED
2"X4" INSIDE & OUTSIDE FACE
TO PERMIT CONCRETE
PLACEMENT
DRYVIT ADHESIVE
MIN 6:12 SLOPE ON ALL
PROJECTING SURFACES
DRYVIT FINISH
EPS SHAPE
BURIED WEB FORM UNIT
MIN 6:12 SLOPE ON ALL
PROJECTING SURFACES
1/2" GYPSUM BRD.
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
THIS DETAIL ISRECOMMENDED FOR USEIN COMBUSTIBLECONSTRUCTION ONLY.
NOTE:1. 2.
Head/Sill - Wood Rough Buck With EPS TrimTAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
ICF 0.0.09
COLOR PRIME™ OR DEMANDIT® ONSURFACES TO RECEIVE SEALANT
MIN. 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
Head/Sill - Bucksaver Rough Buck
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
CONTINUOUS TO INSIDE FACE
OF THE OPENING
SEALANT
METAL FLASHING EXTENDED
TO INSIDE FACE OF WALL
1/2" GYPSUM BRD.
VINYL BUCK SYSTEM
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
TRIM VINYL BUCKSAVER BACK
FROM OUTSIDE FACE OF THE FORM
TO ALLOW FOAM TO DRYVIT COATING
CONTACT
BURIED WEB FORM UNIT
DRIP
EPS ATTACHED WITH
DRYVIT AP ADHESIVE™
DRYVIT FINISH
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
THIS DETAIL ISRECOMMENDED FOR USEIN COMBUSTIBLECONSTRUCTION ONLY.
NOTE:1. 2.
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
ICF 0.0.10
SEALANT
METAL FLASHING EXTENDED
TO INSIDE FACE OF FRAMING
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
CONTINUOUS TO INSIDE FACE
OF THE OPENING
2"X3" INSIDE & OUTSIDE FACE
TO PERMIT CONCRETE
PLACEMENT
Head/Sill - Wood Rough Buck
BURIED WEB FORM UNIT
DRYVIT FINISH
DRIP
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
EPS ATTACHED WITH
DRYVIT AP ADHESIVE™
COLOR PRIME™ OR DEMANDIT® ONSURFACES TO RECEIVE SEALANT
MIN. 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
1/2" GYPSUM BRD.
RECESSED 2"x6" BUCK
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
THIS DETAIL ISRECOMMENDED FOR USEIN COMBUSTIBLECONSTRUCTION ONLY.
NOTE:1. 2.
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
ICF 0.0.11
MIN. 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
ATTACH EPS SHAPE WITH
VERTICAL NOTCHED TROWEL
ADHESIVE PATTERN
DRYVIT AQUAFLASH SYSTEM OR
DRYVIT FLASHING TAPE™EXTENDED OVER ENTIRE SILL AND
ONTO FRONT FACE OF VERTICAL WALL
MIN 6:12 SLOPE ON ALL
PROJECTING SURFACES
Head/Sill - Flange Mount
DRYVIT ADHESIVE
BURIED WEB FORM UNIT
MIN. 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
FLANGE MOUNT WINDOW
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
MIN 6:12 SLOPE ON ALL
PROJECTING SURFACES
DRYVIT COLOR PRIME™ ORDEMANDIT® ON SURFACES TO
RECEIVE SEALANT
DRYVIT AQUAFLASHâ SYSTEM ORDRYVIT BACKSTOPâ NT AND GRID TAPE
ALONG HEAD & JAMBS EXTENDED
TO THE INSIDE FACE OF THE WALL
DRYVIT FINISH
EPS SHAPE
1/2" GYPSUM BRD.
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
ICF 0.0.12
METAL FLASHING EXTENDED
TO INSIDE FACE OF WALL
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
CONTINUOUS TO INSIDE FACE
OF THE OPENING
Head/Sill - Recessed
SEALANT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
COLOR PRIME™ OR DEMANDIT® ONSURFACES TO RECEIVE SEALANT
MIN. 1/2" DRYVIT COMPATIBLE
SEALANT AND CLOSED CELL
BACKER ROD (TYP.)
1/2" GYPSUM BRD.
BURIED WEB FORM UNIT
DRYVIT FINISH
EPS ATTACHED WITH
DRYVIT AP ADHESIVE™
DRIP
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
ICF 0.0.13
2" x 4" BLOCKING FOR STEEL
INSERT FASTENING POINT
AS SPEC'D BY A.C.
INSTALLATION
PTAC SLEEVE INSERT
AS SPEC'D
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
WRAPPED TO THE INSIDE FACE
OF THE FRAMING
DRYVIT COMPATIBLE SEALANT
AND CLOSED CELL BACKER ROD (TYP.)
DRYVIT COMPATIBLE SEALANT AND
CLOSED CELL BACKER ROD (TYP.) WITH
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
MIN. 1/2" DIMENSION BETWEEN
ICF AND PTAC SLEEVE
METAL FLASHING EXTENDED
TO INSIDE FACE OF WALL
SEALANT
BURIED WEB FORM UNIT
A/C Penetration
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
ICF 0.0.14
ALUM. SOFFIT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
WRAPPED OVER TOP PLATE
DRYVIT FINISH
BURIED WEB FORM UNIT
2"x6" RECESSED PLATE
ON SILL GASKET ANCHORED
TO CONCRETE PER LOCAL
CODE REQMT.
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
1/2" GYPSUM BRD.
Eave Detail - Recessed Top Plate
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
ICF 0.0.15
ALUM. SOFFIT
BURIED WEB FORM UNIT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
WRAPPED OVER TOP PLATE
2"x12" EXPOSED PLATE
ON SILL GASKET ANCHORED
TO CONCRETE PER LOCAL
CODE REQMT.
Eave Detail - Exposed Top Plate
1/2" GYPSUM BRD.
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
ICF 0.0.16
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
WRAPPED OVER TOP OF
CONCRETE BEARING
BURIED WEB FORM UNIT
STEEL ROOF FRAMING
CONCRETE POURED
FLUSH WITH TOP OF FORM
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
1/2" GYPSUM BRD.
Eave Detail - Steel Roof Rafters
ALUM. SOFFIT
DRYVIT FINISH
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
ICF 0.0.17
DRYVIT COMPATIBLE SEALANT
AND CLOSED CELL BACKER ROD
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
BURIED WEB FORM UNIT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
FLASHING FASTENED TO CONCRETE
INSTALLED IN A WEATHERBOARD
FASHION AS PER NATIONAL
ROOFING CONTRACTORS
ASSOCIATION (NRCA)
Sloped Roof/Wall Intersection
MIN. 3/4"
MIN. 2 1/2"
MIN. 4"
2. SHINGLES SHOULD BEINSTALLED PER NRCAGUIDELINES TO OVERLAP STEPFLASHINGS AND EXTEND ALLTHE WAY TO THE VERTICALWALL
ROOFING PAPER
ROOF RAFTER
DRYVIT FINISH
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
ICF 0.0.18
THE JOINT BETWEEN THE TWOWALLS MAY OR MAY NOT BE ASTRUCTURAL CONNECTION WITHDOWELS AS SPEC'D BY THESTRUCTURAL ENGINEER
IT IS THE RESPONSIBILITY OF THEDESIGNER AND CONTRACTOR TODESIGN AND CONSTRUCT THEWALLS SO THE EXTERIOR FINISHOF BOTH THE ICF WALL AND THECMU WALL ARE IN THE SAMEPLANE
DRYVIT FINISH
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT EIFS
BACK WRAP EPS SECTION
WITH MESH AND BASE COAT
DRYVIT DEMANDIT® ORCOLOR PRIME™ ON SURFACES TO
RECEIVE SEALANT WITH BACKER ROD
SEE DETAIL BELOW
3.
2.
DRYVIT DEMANDIT OR COLOR PRIME
ON SURFACES TO RECEIVE SEALANT
EXSTG. CONCRETE
BLOCK WALL
DRYVIT COMPATIBLE SEALANT
AND CLOSED CELL BACKER ROD
Transition to Existing Wall
3/4"
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
ICF 0.0.19
STEEL COLUMN ANCHORED
IN PLACE
WOOD BLOCKING
NELSON STUDS CAST
INTO CONCRETE
EPS INSERT
BURIED WEB FORM UNIT
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT AP ADHESIVE™
Transition Across Column
1/2" GYPSUM BRD.
PLAN VIEW
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DOCUMENTS
NOTE:1.
ICF 0.0.20
DRYVIT REINFORCING MESH
EMBEDDED IN DRYVIT BASE COAT
BURIED WEB FORM UNIT
DRYVIT BASE COAT WRAPPED
ONTO CONCRETE
ROOFING AS SPEC'D
ROOFING MEMBRANE LAPPED
OVER PARAPET BLOCK
Parapet Termination
WOOD SPACER
DRYVIT FINISH
PARAPET CAP
SEALANT
MIN. 2 1/2" OVERLAP
RETAINING CLIP
TAFS OVER ICFs
©
The architecture, engineering, and design of the project using the
Dryvit products is the responsibility of the project's design
professional. All systems must comply with local building codes and
standards. This detail is for general information and guidance only
and Dryvit specifically disclaims any liability for the use of this detail
and for the architecture, design, engineering or workmanship of any
project. The project design professional determines, in its sole
discretion, whether this detail or a functionally equivalent detail is
best suited for the project. Use of a functionally equivalent detail does
not violate Dryvit's warranty. This detail is subject to change without
notice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc. 1969
Issued: 10/2016
®
Sheets and ViewsModel
ICF TOC.pdfSheets and ViewsModel
TAFs ICF 0.0.02.pdfSheets and ViewsModel
TAFs ICF 0.0.03.pdfSheets and ViewsModel
TAFs ICF 0.0.04.pdfSheets and ViewsModel
TAFs ICF 0.0.05.pdfSheets and ViewsModel
TAFs ICF 0.0.06.pdfSheets and ViewsModel
TAFs ICF 0.0.07.pdfSheets and ViewsModel
TAFs ICF 0.0.08.pdfSheets and ViewsModel
TAFs ICF 0.0.09.pdfSheets and ViewsModel
TAFs ICF 0.0.10.pdfSheets and ViewsModel
TAFs ICF 0.0.11.pdfSheets and ViewsModel
TAFs ICF 0.0.12.pdfSheets and ViewsModel
TAFs ICF 0.0.13.pdfSheets and ViewsModel
TAFs ICF 0.0.14.pdfSheets and ViewsModel
TAFs ICF 0.0.15.pdfSheets and ViewsModel
TAFs ICF 0.0.16.pdfSheets and ViewsModel
TAFs ICF 0.0.17.pdfSheets and ViewsModel
TAFs ICF 0.0.18.pdfSheets and ViewsModel
TAFs ICF 0.0.19.pdfSheets and ViewsModel
TAFs ICF 0.0.20.pdfSheets and ViewsModel