DR. JOHN W. MILLER
DR. RICHARD R. BACHOO
CHIEF ADMINISTRATIVE OFFICER
MR. SAL CINTORINO
ASSISTANT CHIEF ADMINISTRATIVE OFFICER
JANUARY 12, 2015
PRESIDENT
POWER HOUSE
STATE PROJECT NO.: N.A.CCSU. PROJECT NO.: 02-34
LIST OF DRAWINGS
A-2
A-1
COVER SHEET
REPLACEMENT ROOF PLAN, TAPERED INSULATION PLAN & LOGISTICS SITE PLAN
OFFICE OF CENTRAL CONNECTICUT STATE UNIVERSITY ARCHITECT
ROOF REPLACEMENT PROJECT
A-3 ROOF DETAILS
ROOF DETAILS & BUILDING SECTION
CS-1 CODE INFORMATION SHEET
P-1 ROOF DRAIN PLUMBING PLAN
SU-1 SITE UTILITIES PLAN
D-1 ROOF DEMOLITION PLAN AND REFLECTED CEILING - ROOF DECK PLAN
REVISIONS
NUMBER DATE DESCRIPTION
02 CS-1
CODE INFORMATION
SHEET
CODE PLAN
STATE FIRE SAFETY CODE
1.0 CLASSIFICATION OF OCCUPANCY B (BUSINESS)
2.0 CONSTRUCTION CLASSIFICATION 2C
3.0 MINIMUM CONSTRUCTION TYPE REQUIRED 2C
4.0 ACTUAL CONSTRUCTION TYPE PROVIDED 2C
5.0 NOTIFICATION / ALARMS YES
6.0 DETECTION YES
7.0 EXTINGUISHMENT REQUIREMENTS: NO
CHAPTER 16 - STRUCTURAL DESIGN
SEISMIC DESIGN BASED ON 2003 INTERNATIONAL BUILDING CODE W/2005 CT
STATE BUILDING CODE SUPPLEMENT W/2009 CT AMENDMENT.
CALCULATIONS INDICATED SEISMIC GROUP 'B'
PER A.S.C.E. 7-02 SECOND EDITION SECTION 9.61:
EXCEPTION 2: ARCHITECTURAL COMPONENTS IN SEISMIC DESIGN CATEGORY B
(OTHER THAN PARAPETS) PROVIDED THAT THE IMPORTANCE FACTOR = 1.0
(WHICH IT DOES)
EXCEPTION 3: MECHANICAL AND ELECTRICAL COMPONENTS IN SEISMIC
CATEGORY B.
APPLICABLE CODE INFORMATION
SUMMARY OF PROJECT DESCRIPTION:
CONSTRUCTION OF THE PROPOSED NEW ROOF FOR THE POWER HOUSE . IT WILL INCLUDE :
DEMOLITION:
REMOVE EXISTING BUILT-UP ROOF SYSTEM ON FLAT ROOF AREA OF BUILDING.
REMOVE EXISTING SHINGLE ROOFING SYSTEM ON GABLE ROOF AREA OF BUILDING.
REMOVE EXISTING OBSOLETE ROOF PENETRATIONS.
REMOVE EXISTING OBSOLETE MECHANICAL SYSTEMS.
NEW CONSTRUCTION:
INFILL EXISTING OPENINGS ON ROOF DECK WITH NEW DECKING MATERIALS.
INSTALL NEW MEMBRANE ROOFING SYSTEM ON EXISTING FLAT ROOF AREA OF BUILDING..
INSTALL NEW SHINGLE ROOFING SYSTEM ON EXISTING GABLE.
INSTALL NEW EQUIPMENT CURBS ON EXISTING FLAT ROOF AREA OF BUILDING.
INTERNATIONAL EXISTING BUILDING CODE 2003
INTERNATIONAL BUILDING CODE 2003 + STATE BUILDING CODE 2005 CONNECTICUT SUPPLEMENT
2009 AMENDMENT TO THE 2005 CONNECTICUT SUPPLEMENT AND 2009 IECC
1.0 EXISTING BUILDING: YES, BUILT IN 1927
1.1 CONTINUATION OF EXISTING USE YES
1.2 CHANGE OF USE YES
2.0 NEW BUILDINGS OR ADDITIONS: NO
2.1 EXCEEDS THRESHOLD BUILDING LIMITS NO
3.0 USE GROUP CLASSIFICATION:
PRIMARY: B, BUSINESS
4.0 HEIGHT AND AREA COMPUTATION : N/A
4.2 OPEN PERIMETER COMPUTATION: N/A
4.3 AREA CONVERSION FACTOR: N/A
4.4 ACTUAL GROSS FLOOR AREA (LARGEST FLOOR) 6,378 SF
4.5 ACTUAL GROSS FLOOR AREA (ENTIRE BUILDING) 13,297 SF
4.6 ADJUSTED TABULAR AREA (ACTUAL GROSS FLOOR AREA/CONVERSION FACTOR) = N/A
4.7 ALLOWABLE BUILDING AREA PER FLOOR (CONVERSION FACTOR x TABULAR AREA) = N/A
4.8 MINIMUM TYPE OF CONSTRUCTION REQUIRED: 2C
4.9 MINIMUM TYPE OF CONSTRUCTION PROVIDED: 2C
4.10 TYPE OF CONSTRUCTION ASSUMED FOR REVIEW 2C
8.0 FIRE RESISTANT RATING OF STRUCTURE 3B ELEMENTS (TABLE 601) REFER TO CONSTRUCTION
DOCUMENTS FOR THE FOLLOWING:
8.1 EXTERIOR WALLS: EXISTING
8.2 FIRE WALLS & PARTY WALLS EXISTING
8.3 FIRE SEPARATION ASSEMBLIES:
8.3.1 FIRE ENCLOSURE OF EXITS EXISTING
8.3.2 SHAFTS EXISTING
8.3.3 OTHER SEPARATION ASSEMBLIES: EXISTING
8.4 FIRE PARTITIONS N/A
8.5 DWELLING UNIT SEPARATIONS N/A
8.6 SMOKE BARRIERS N/A
8.7 OTHER NON BEARING PARTITIONS EXISTING
8.8 INTERIOR BEARING WALLS, BEARING PARTITIONS, COLUMNS, GIRDERS, TRUSSES AND FRAMING:
8.8.1 SUPPORTING MORE THAN ONE FLOOR: EXISTING
8.7.1 SUPPORTING ONE FLOOR ONLY OR A ROOF: EXISTING
8.7.2 STRUCTURAL MEMBERS SUPPORTING WALL: EXISTING
8.9 CORRIDOR WALLS 1ST FLOOR EXISTING
8.10 FLOOR CONSTRUCTION INCLUDING BEAMS EXISTING
8.11 ROOF CONSTRUCTION
8.11.1* 15 FT OR LESS: 0 HRS
8.11.2* 15 FT OR MORE: 0 HRS
8.11.3* 20 FT OR MORE: 0 HRS
9.0 FIRE PROTECTION SYSTEM
9.1 FIRE SUPPRESSION SYSTEM NO
9.2 ALARMS YES
9.3 AUTOMATIC FIRE DETECTION SYSTEM YES
9.4 SMOKE CONTROL SYSTEM NO
9.5 SUPERVISION YES
NO
11.0 SPRINKLER PROTECTIONENTIRE BUILDING
LIMITED AREA
12.0 ADDITIONAL INFORMATION
COMMON PATH OF TRAVEL (CSBC 1013.3):
DEAD ENDS (CSBC 1016.3):
TRAVEL DISTANCE USE GROUP B (CSBC 1015.1):
75 FT. WITHOUT SPRINKLERS
20 FT. WITHOUT SPRINKLERS
200 FT. WITHOUT SPRINKLERS
10.0
DATED
- THE AMERICANS WITH DISABILITIES ACT AND PUBLIC LAW 101-336
INCLUDING 2010 GUIDELINES.
- ICC/ANSI A117.1-2003 INCLUDING THE CURRENT CONNECTICUT
BUILDING CODE
- REHABILITATION ACT 1973 INCLUDING UNIFORM FEDERAL
ACCESSIBILITY STANDARDS (UFAS) AND 504 REGULATIONS
SECTION 504
THE WORK IS BEING CONSTRUCTED IN ACCORDANCE WITH
PARTS I, II, III.
2003
CONNECTICUT STATE FIRE SAFETY CODE
2013
2003
NATIONAL ELECTRICAL CODE
INTERNATIONAL MECHANICAL CODE
INTERNATIONAL PLUMBING CODE
13.0 CODES TO WHICH THIS PROJECT WAS DESIGNED
CONNECTICUT AMENDMENTS TO THE STATE BUILDING CODE
CONNECTICUT STATE BUILDING CODE
INTERNATIONAL EXISTING BUILDING CODE
2005
2011
ENERGY CONSERVATION CODE
2003
INTERNATIONAL BUILDING CODE (IBC 2003) WITH 2005 CONNECTICUT
SUPPLEMENT WITH 2009 AMENDMENTS
2003
2009
CONNECTICUT FIRE PREVENTION CODE
KEY PLAN
ROOF PLAN
S
W
N
E
PROJECT
ROOF REPLACEMENT
HOUSE
POWER
2003
REVISIONS
NUMBER DATE DESCRIPTION
02 D-1
KEY PLAN
AND
PROJECT
ROOF REPLACEMENT
HOUSE
ROOF PLAN
POWER
1
ROOF DEMOLITION PLAN
S
W
N
E
1
KEY NOTES - ROOF DEMOLITION PLAN
#
2
3
6
2
REFLECTED CEILING - ROOF DECK PLAN
13
REPLACEMENT ROOF DECK
#
14
KEY NOTES
4
5
ROOF DEMOLITION PLAN
ROOF DECK PLAN
REFLECTED CEILING -
REVISIONS
NUMBER DATE DESCRIPTION
02 A-1
INSULATION PLAN &
KEY PLAN
REPLACEMENT ROOF
PROJECT
ROOF REPLACEMENT
HOUSE
PLAN, TAPERED
ROOF PLAN
POWER
1
REPLACEMENT ROOF PLAN
S
W
N
E
2
TAPERED INSULATION - SECTION DIAGRAM
3
LOGISTICS SITE PLAN
LOGISTICS SITE PLAN
REVISIONS
NUMBER DATE DESCRIPTION
02 A-2
BUILDING SECTION
KEY PLAN
ROOF DETAILS
PROJECT
ROOF REPLACEMENT
HOUSE
&
ROOF PLAN
POWER
S
W
N
E
5
ROOF DETAIL
4
ROOF DETAIL
2
ROOF DETAIL @ OUTRIGGER
3
ROOF DETAIL BETWEEN OUTRIGGERS
6
ROOF DETAIL @ RAKE
8
ROOF DETAIL
9
ROOF DRAIN DETAIL
1
BUILDING SECTION
7
ROOF RIDGE DETAIL
BACKER
FLASHING
AREA
APRON
FLASHING
AREA
REVISIONS
NUMBER DATE DESCRIPTION
02 A-3
KEY PLAN
PROJECT
ROOF REPLACEMENT
HOUSE
ROOF DETAILS
ROOF PLAN
POWER
S
W
N
E
2
ROOF PENETRATION DETAIL
3
TYPICAL ROOF ASSEMBLY DETAIL
4
ROOF JOINT DETAIL
1
ROOF OPENING INFILL DETAIL
5
ONE PLY CURB FLASHING DETAIL
7
VENT PIPE FLASHING ROOF DETAIL
8
ACCESS HATCH FLASHING ROOF DETAIL
BACKER FLASHING ROOF DETAIL
APRON FLASHING ROOF DETAIL
SECTION DIAGRAM
BACKER FLASHING
9
ROOF VENT INFILL DETAIL
6
ROOF VENTILATOR INFILL DETAIL
REVISIONS
NUMBER DATE DESCRIPTION
02 P-1
ROOF DRAIN
KEY PLAN
PLUMBING PLAN
PROJECT
ROOF REPLACEMENT
HOUSE
ROOF PLAN
POWER
S
W
N
E
1
ROOF DRAIN PLUMBING PLAN
2
SANITARY (NON-SEWAGE) & STORM WATER TRENCH DETAIL