1 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
General Needs Flatted Accommodation Fire Risk Assessment (FRA)
Regulatory Reform (Fire Safety) Order 2005
Responsible person Chief Executive-London Borough of Newham
Address of Premises
1-98 Aubrey Moore Point
Abbey Lane London E15 2RZ
The Fire Risk Assessment was undertaken by The assessor detailed in the Assessment Summary
below who has the necessary qualifications, competency and experience in Fire Risk
Management that give him/her the status of “Competent Person” as described in articles 15
and 18 of the ‘Regulatory Reform (Fire Safety) Order 2005', for properties in England & Wales,
and the 'Fire Safety (Scotland) Regulations 2006' for those in Scotland. This legislation now
supersedes all previous fire legislation for England, Wales & Scotland and forms the ‘Fire
Regulations'.
Date of Survey 01/07/2017
2 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
TABLE OF CONTENTS
SECTION 1 Assessment Summary 2 Survey Drawings 3 Risk Assessment: Summary by Area 4 Risk Assessment Details 5 Assessment Paragraphs 6 Action Summary 7 Action Details
3 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
SECTION ONE
ASSESSMENT SUMMARY
4 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Assessment Summary
Asset Image
Site Address: 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Ownership: Newham
Date Due: 01/07/2017
Date Assessed: 01/07/2017
Person managing fire safety for the premises: Head of Housing Property & Initiatives
Uploaded by
Risk Level Moderate
Risk Description
It is essential that efforts are made to reduce the risk. Risk reduction measures should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment might be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures.
Validated By
(Where Applicable)
Surveyed By Assessment Notes:
This assessment was undertaken by
98 residential flats, 22 floors, 2 staircases and 2no fireman's lifts. There is a concierge on site. Parking bays round the block. Front entrance and 2no side exits. Play area in front of the block. Tenants room on the 1st floor
5 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
The purpose of this report is to provide an assessment of the risk to life from fire in these premises,
and, where appropriate, to make recommendations to ensure compliance with fire safety legislation.
The report does not address the risk to property or business continuity from fire. If you have any
questions about this Fire Risk Assessment please contact:
Direct House, Bridge Road Depot, Abbey Road, London E15 3LX
This Fire Risk Assessment should be reviewed by a competent person if it is no longer valid, or if there has been a significant
change in the matters to which it relates, or if a fire occurs.
1. Introduction This report has been prepared as a written record of the Fire Risk Assessment, carried out at 1-
98, Aubrey Moore Point, Abbey Lane, , London under the requirements of the Regulatory
Reform (Fire Safety) Order 2005.
1.1 The objectives of this Fire Risk Assessment are: a. To identify all current significant fire hazards to which relevant persons on the premises,
or in the immediate vicinity of the premises, will be exposed.
b. To reasonably quantify the level of residual fire risk that is attributed to the premises
and its use, with regard to existing (preventive and protective) controlling measures.
c. To advise on the nature and extent of any additional (preventive and protective)
controlling measures which should be implemented in order to counteract this residual
risk, in accordance with the ‘Principles of Prevention’ as defined in Article 10 of The
Regulatory Reform (Fire Safety) Order 2005.
1.2 Risk Assessments Risk Assessments are not a ‘one off’ activity, and are part of a dynamic process. It is thus a
requirement under Article 9(3) of The Regulatory Reform (Fire Safety) Order 2005 to review and
modify the risk assessment when either:
a. There is reason to suspect that it is no longer valid, perhaps due to a gradual change in
the nature of the tenancy numbers or type, wear & tear on facilities, a large number of
small changes, an appreciation of a hazard (e.g. highlighted by fire evacuation drill), or
b. the occurrence of an incident (e.g. actual fire or near miss), which triggers a need to
review, OR there is a significant change in the matters to which it relates, (i.e. following
major organisational changes or any refurbishment, alterations or extension).
1.3 This Risk Assessment This risk assessment is a ‘dynamic’ working document that should be used as a guide to
planning future actions aimed at improving Health & Safety for tenants and others who may be
affected by a potential fire at the premise. Notwithstanding the requirements noted in Section
1.2 above, it is a requirement of London Borough of Newham that Fire Risk Assessments are
normally reviewed annually, unless otherwise advised by the Fire Risk Assessment report. Some
reasonable flexibility is permitted to accommodate logistical and financial constraints.
6 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Scope and Methodology
1.4 Statutory Requirement
Article 9 of The Regulatory Reform (Fire Safety) Order 2005 requires every responsible person
to make a suitable and sufficient assessment of the fire risks to which relevant persons are
exposed, with respect to premises within their control. This is for the purpose of identifying the
general fire precautions that are needed to comply with the requirements and prohibitions
imposed by the Order. The responsible person, or any other person who has to any extent
control of the premises, must ensure that the duties imposed by the relevant articles of The
Regulatory Reform (Fire Safety) Order 2005 are complied with in respect of those premises, so
far as the requirements relate to matters within their control. Where the premises are licensed,
an alterations notice is in force, or the responsible person has five or more employees, it is a
requirement to record the significant findings of the fire risk assessment including the measures
which have been or will be taken as a result of the assessment and details of any group of
persons identified by the assessment as being especially at risk. This report therefore
incorporates such relevant information, significant findings and recommended actions that are
considered necessary to demonstrate compliance with The Regulatory Reform (Fire Safety)
Order 2005.
1.5 Identification of Fire Hazards
In order to identify the significant fire hazards within the premise, a checklist is used which
considers the particular fire hazards associated with this type of building and the nature of the
occupancy. The hazard identification process will consider each item with due regard to the
existing ‘control measures’, which are either already inherent within the building fabric design
or are implemented through the management policy procedures for the premise. The answers
to all questions should be YES, NO or NOT APPLICABLE (Na).
1.6 Assessment of Fire Risk
Each identified hazard is assessed in accordance with the fire risk-rating matrix detailed in
Section 4.0 of this report. This matrix has due regard to the person or group of persons who are
likely to be affected by each hazard, by considering the hazards in terms of their potential to
harm (severity) and their likelihood (probability) of actually occurring. The matrix allows the
assignment of a specific risk rating for each perceived hazard, which subsequently assists in
determining the nature and extent of any necessary additional controlling measures, (both
physical and procedural deficiencies), as well as the timescale in which these measures should
be reasonably implemented.
7 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
1.7 The Fire Risk Assessment Action Schedule
This Action Schedule details the blend of technical and procedural measures, which are
considered necessary to adequately address the residual risk that has been previously
identified, semi-quantified and assigned a ‘risk-rating’. This risk control plan is essentially an
inventory of remedial / advisory actions which should be carried out by London Borough of
Newham Group or an appointed representative, within the recommended timescales. These
timescales are suggested purely to aid reasonable implementation of the Action Schedule, but
for the residual risk to be reduced to an acceptable level, it will be necessary to implement all
Action Items on the schedule. It is a requirement of London Borough of Newham that P1
timescales may not be exceeded without the recorded authorisation of a senior manager, Head
of Department or a Director.
1.8 Information Source
Information for the completion of this assessment was obtained by a semi non-invasive physical
inspection of the premise, inspection of records and drawings (where available). For accurate
identification of hazard location, digital photographs are enclosed to ‘pin-point’ the specified
hazard.
8 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
SECTION TWO
ASSESSMENT ATTACHMENTS
9 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
2. Survey Drawings and Documentation
2.1 Information Source
Information for the completion of this assessment was obtained by a semi non-invasive physical
inspection of the premise, inspection of records and drawings (where available). For accurate
identification of hazard location, digital photographs are enclosed to ‘pin-point’ the specified
hazard.
10 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
SECTION THREE
RISK ASSESSMENT: SUMMARY BY AREA
11 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
3. Risk Assessment: Summary by Area
Risk Assessment: Summary by Area
Area Risk Category Question Answer Probability Severity Risk Action Due
All Areas Arson - Fire Load 1. Is fire load close to the premises minimised?
No 2 2 Moderate (4) 01/08/2017
All Areas Arson - Security 2. Are premises adequately secured against potential arson?
No 2 2 Moderate (4) 01/08/2017
All Areas Arson - Security 3. Are there suitably located and secured provisions for the disposal of waste and recyclable material?
No 2 2 Moderate (4) 01/08/2017
All Areas Combustible Materials - Housekeeping
4. Are any potential combustible materials adequately segregated from any sources of ignition?
No 2 2 Moderate (4) 01/08/2017
All Areas Combustible Materials - Housekeeping
5. Are quantities of combustible waste allowed to accumulate in the premises such as Paper, cardboard, wood shavings, dust?
Yes 2 2 Moderate (4) 01/08/2017
All Areas Fire Detection - Alarms 6. Are fire alarm tests recorded? Na 0 0 Trivial (0) 01/07/2018
All Areas Fire Detection - Alarms 7. Is automatic detection and/or manual alarm provided in the premises? If yes, describe system.
No 1 1 Tolerable (1) 01/04/2018
12 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
All Areas Fire Detection - Alarms 8. Is further automatic detection and/or manual alarm provision required? If yes, state what.
No 0 0 Trivial (0) 01/07/2018
All Areas Fire Detection - Alarms 9. Is the alarm system adequately maintained?
Na 0 0 Trivial (0) 01/07/2018
All Areas Fire Detection - Alarms Q10. Is the fire alarm system in working order?
Na 0 0 Trivial (0) 01/07/2018
All Areas Fire Fighting Equipment - Entry 11. Is the fireman's switch working correctly?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Fire Fighting Equipment - Extinguishers
12. Are fire extinguishers adequately maintained?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Fire Fighting Equipment - Extinguishers
13. Are other fire extinguishing systems provided/accessible and in good working condition?
Na 0 0 Trivial (0) 01/07/2018
All Areas Fire Fighting Equipment - Extinguishers
14. Are portable fire extinguishers provided/accessible and in good working condition?
No 2 2 Moderate (4) 01/10/2017
All Areas Fire Fighting Equipment - Other 15. Are all bin chamber doors secure? Yes 0 0 Trivial (0) 01/07/2018
All Areas Fire Fighting Equipment - Risers 16. Are dry/wet risers in good order? Yes 0 0 Trivial (0) 01/07/2018
All Areas Fire Fighting Equipment - Risers 17. Are rising mains adequately maintained?
Na 0 0 Trivial (0) 01/07/2018
All Areas Flammable Substances - Housekeeping
18. Are there any highly flammable substances in the premises?
No 0 0 Trivial (0) 01/07/2018
All Areas General Hazards - Any Other Issues
19. Are there any other issues? Please specify
Yes 2 2 Moderate (4) 01/10/2017
All Areas Limiting Fire Spread - Compartmentation
20. Are any installed linings appropriate for limiting the spread of
No 2 2 Moderate (4) 01/10/2017
13 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
fire?
All Areas Limiting Fire Spread - Compartmentation
21. Is the current level of compartmentation adequate for the premise?
No 2 2 Moderate (4) 01/08/2017
All Areas Limiting Fire Spread - Dampers 22. Where required, are dampers provided?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Maintenance Checks - General 23. Are appropriate building maintenance checks undertaken regularly?
No 2 2 Moderate (4) 01/10/2017
All Areas Maintenance Checks - General 24. Are lifts adequately maintained? Yes 0 0 Trivial (0) 01/07/2018
All Areas Maintenance Checks - General 25. Are the premises generally well maintained?
Yes 2 2 Moderate (4) 01/10/2017
All Areas Maintenance Checks - General 26. Have all installed or portable electrical appliances been tested in accordance with regulations?
Yes 2 2 Moderate (4) 01/10/2017
All Areas Maintenance Checks - General 27. Is the lightning protection system adequately maintained?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Maintenance Checks - General 28. Is the sprinkler system adequately maintained?
Na 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Lighting 29. Are all exits and exit routes adequately illuminated (internal and external)?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Lighting 30. Are any other areas as required adequately illuminated?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Lighting 31. Are emergency escape lighting tests recorded?
Yes 0 0 Trivial (0) 01/07/2018
14 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
All Areas Means Of Escape - Lighting 32. Is the emergency escape lighting adequately maintained?
No 2 2 Moderate (4) 01/10/2017
All Areas Means Of Escape - Lighting 33. Where fitted, is the emergency escape lighting in good working order?
No 2 2 Moderate (4) 01/10/2017
All Areas Means Of Escape - Routes 34. Are all escape routes clear and unobstructed?
No 2 2 Moderate (4) 01/10/2017
All Areas Means Of Escape - Routes 35. Are all floors free from slipping/tripping hazards?
No 2 2 Moderate (4) 01/10/2017
All Areas Means Of Escape - Routes 36. Are corridors sub-divided (where appropriate)?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Routes 37. Are doors on escape routes easily opened and do they open in the correct direction?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Routes 38. Are there reasonable arrangements in the building for means of escape for disabled people?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Routes 39. Are travel distances to fire exits satisfactory - single and two-way?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Routes 40. Do all escape routes lead to a place of safety?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Routes 41. Does the escape route design meet the necessary Home Office guidelines?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Routes 42. Is adequate separation evident on all escape routes (as appropriate)?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Routes 43. Is the number and provision of exits adequate?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Routes 44. Is there adequate protection provided/installed to all escape routes?
Yes 0 0 Trivial (0) 01/07/2018
15 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
All Areas Means Of Escape - Signage 45. Are signs clearly visible and not obstructed?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Means Of Escape - Signage 46. Is there adequate provision of fire safety signs and notices?
No 2 2 Moderate (4) 01/10/2017
All Areas Other Issues - General 47. Are there any other issues to specify?
Yes 2 2 Moderate (4) 01/10/2017
All Areas Premises Management - Records And Security
48. Are there appropriate fire safety procedures in place?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Premises Management - Records And Security
49. Are there provisions in place for liaison to take place with the local fire and rescue service?
Yes 0 0 Trivial (0) 01/07/2018
All Areas Premises Management - Records And Security
50. Is there an available and suitable record of fire safety arrangements?
No 2 2 Moderate (4) 01/08/2017
All Areas Records - Fire Maintenance 51. Are fire safety maintenance records available for the premises?
No 2 2 Moderate (4) 01/08/2017
All Areas Sources Of Ignition - Smoking 52. Is there evidence of any smoking related activities taking place in non designated areas?
No 0 0 Trivial (0) 01/07/2018
All Areas Training - Evacuation 53. Where fire evacuation safety drills are considered appropriate, are they carried out at regular intervals?
Na 0 0 Trivial (0) 01/07/2018
All Areas Training - Trained Personnel 54. Are staff trained in fire safety via induction and/or annual refreshers?
No 2 2 Moderate (4) 01/10/2017
All Areas Training - Trained Personnel 55. Is fire safety training recorded? Yes 0 0 Trivial (0) 01/07/2018
16 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
SECTION FOUR
RISK ASSESSMENT DETAILS
17 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
4. Risk Assessment Details
4.1 Fire Risk Rating Matrix
The following risk rating matrix is used to enable semi-quantification of the itemised fire safety deficiencies (hazards) that were found during the recent survey of the premise.
The matrix allows the identified significant fire hazards to be classified in terms of the harmful or unwanted consequences (severity) that the hazard would cause, if it were to occur and also the likelihood (probability) that such harm will occur. These factors are considered with due regard to the existing fire safety features and procedures (controlling measures), which are either incorporated within the building design or procedurally implemented within the premise.
Risk Control Plan
Score Degree Consequence
0 Trivial No action is required and no detailed records need to be kept.
1-3 Tolerable No major additional controls required. However, there might be a need for improvements that involve minor or limited cost.
4 Moderate
It is essential that efforts are made to reduce the risk. Risk reduction measures should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment might be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures.
6 Substantial
Considerable resources might have to be allocated to reduce the risk. If the building is unoccupied, it should not be occupied until the risk has been reduced. If the building is occupied, urgent action should be taken.
9 Intolerable Building (or relevant area) should not be occupied until the risk is reduced.
Severity
Pro
bab
ility
0 1 2 3
0 0 0 0 0
1 0 1 2 3
2 0 2 4 6
3 0 3 6 9
18 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Probability Level
Level Degree Probability of Exposure to Harm 0 Very Low Risk No known instances of such an event occurring 1 Low Risk Unlikely to occur, but still possible 2 Medium Risk Likely to occur at some stage in the foreseeable future 3 Very High Risk Very likely to occur frequently and/or in the near future unless actively prevented
The product of the severity and probability factors will equate to a specific risk rating for each identified hazard. The following band matrix can then be used to assign a comparative degree of risk (Very Low , Low, Medium or Very High) to each individual fire safety deficiency. This will assist in determining the extent of any necessary additional controlling measures, as well as the timescale in which these measures should be implemented.
4.2 Assessment of Fire Risk
The table details the systematic approach that has been taken to assess the individual level of risk
that is inherent in each identified hazard / fire safety deficiency, recorded during the inspection of
this premise.
Each hazard (item) has been considered with regard to the specific group of people that it threatens;
its potential severity and its probability of being realised. Existing control measures are taken into
account before determining the nature and extent of any additional control measures deemed
necessary to contend with the residual fire risk that remains.
The table below provides timescales for remedial action proportionate to the risk.
Degree of Risk Risk Rating Score Priority Level for Action
Timescales for Remedial Action ( maximum time limits )
Very High Risk 9 P1 Within 1 Week
High Risk 6 P2 Within 3 Months
Medium Risk 4 P3 Within 6 months
Low Risk 1 to 3 P4 Within 9 months
Very Low Risk 0 to 0 P5 As required
The Action Items contained in Section 6 of this report, details the optimum measures that are considered necessary.
19 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
4.3 Sheltered Accommodation Containing Vulnerable Persons
The same method is used but the overall fire risk rating is adjusted up one level. For example, if the
individual risk ratings on the itemised schedule is a Low Risk then the fire risk rating for the premises
is categorised as Moderate Risk.
4.4 Exceptional Circumstances
Where the assessor risk or receiving manager feels the method of calculation has arrived at a grossly
disproportionate fire risk rating, the matter should be referred to the Director for consideration and
advice.
4.5 Extent of Common Areas
Internal and External Communal areas including but not limited to the following: Entrances, Exits , Escape Stairs, Landings, Lobbies, Electrical Intake/service cupboards, Pram shed areas, Refuse areas. 4.6 How are occupants who warrant special consideration identified?
In the event of an emergency any vulnerability information is obtainable from the Housing
database which is available to the LBN Emergency Officer.
20 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Arson - Fire Load
Question 1. Is fire load close to the premises minimised?
Answer Title No
Question Notes 1.Refuse/recycling bins AND BULK WASTE must not be stored directly adjacent to the building .
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/08/2017
Documents
Pic 1
Pic 1a
21 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Arson - Security
Question 2. Are premises adequately secured against potential arson?
Answer Title No
Question Notes External garage door lock had been breached - rough sleeper present - forwarded to supervisor to arrange for door to be secured.(pic 2)
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/08/2017
Documents
Pic 2
Question Details
Area All Areas
Risk Category Arson - Security
Question 3. Are there suitably located and secured provisions for the disposal of waste and recyclable material?
Answer Title No
Question Notes Refer Q1
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/08/2017
22 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Documents
Question Details
Area All Areas
Risk Category Combustible Materials - Housekeeping
Question 4. Are any potential combustible materials adequately segregated from any sources of ignition?
Answer Title No
Question Notes Combustibles found in service riser cupboards( some removed at time of inspection - concierge informed)
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/08/2017
Documents
Question Details
Area All Areas
Risk Category Combustible Materials - Housekeeping
Question 5. Are quantities of combustible waste allowed to accumulate in the premises such as Paper, cardboard, wood shavings, dust?
Answer Title Yes
Question Notes EXCESSIVE AMOUNT OF COMBUSTIBLES OUTSIDE INCLUDING PLASTIC WHEELIE BIN AND ARMCHAIR - PHONED SUPERVISOR TO REMOVE AND ESCALATED TO ENFORCEMENT /COMPLIANCE. Combustibles are being stored by tenants in communal areas.
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/08/2017
Documents
Pic 4
23 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Pic 5
Pic 5a
Pic 5c
24 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Pic 5e
Pic 5f
Pic 5d
25 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Fire Detection - Alarms
Question 6. Are fire alarm tests recorded?
Answer Title Na
Question Notes no alarm system
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Fire Detection - Alarms
Question 7. Is automatic detection and/or manual alarm provided in the premises? If yes, describe system.
Answer Title No
Question Notes
Probability 1
Severity 1
Score 1
Risk Tolerable (1)
Date Action Due 01/04/2018
26 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Documents
Question Details
Area All Areas
Risk Category Fire Detection - Alarms
Question 8. Is further automatic detection and/or manual alarm provision required? If yes, state what.
Answer Title No
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Fire Detection - Alarms
Question 9. Is the alarm system adequately maintained?
Answer Title Na
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Fire Detection - Alarms
Question Q10. Is the fire alarm system in working order?
Answer Title Na
Question Notes
Probability 0
Severity 0
27 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Fire Fighting Equipment - Entry
Question 11. Is the fireman's switch working correctly?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Fire Fighting Equipment - Extinguishers
Question 12. Are fire extinguishers adequately maintained?
Answer Title Yes
Question Notes Fire extinguishers in concierge are in date and correctly sited (pic 12) Tenants room not accessed.
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Pic 12
28 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Fire Fighting Equipment - Extinguishers
Question 13. Are other fire extinguishing systems provided/accessible and in good working condition?
Answer Title Na
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Fire Fighting Equipment - Extinguishers
Question 14. Are portable fire extinguishers provided/accessible and in good working
29 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
condition?
Answer Title No
Question Notes No fire extinguishers observed in plant rooms
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
Question Details
Area All Areas
Risk Category Fire Fighting Equipment - Other
Question 15. Are all bin chamber doors secure?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Fire Fighting Equipment - Risers
Question 16. Are dry/wet risers in good order?
Answer Title Yes
Question Notes All dry risers were inspected and seals in place.(pic 16) Tested 18/10/2016
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
30 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Fire Fighting Equipment - Risers
Question 17. Are rising mains adequately maintained?
Answer Title Na
Question Notes All dry risers were inspected and seals in place.(pic 16) Tested 18/10/2016
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Flammable Substances - Housekeeping
Question 18. Are there any highly flammable substances in the premises?
Answer Title No
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category General Hazards - Any Other Issues
Question 19. Are there any other issues? Please specify
Answer Title Yes
Question Notes 1. Ground floor service riser cupboards - overhead cables are poorly secure. 2.Tenants room unable to access
Probability 2
Severity 2
Score 4
Risk Moderate (4)
31 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Date Action Due 01/10/2017
Documents
19
19a
19b
32 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Limiting Fire Spread - Compartmentation
Question 20. Are any installed linings appropriate for limiting the spread of fire?
Answer Title No
Question Notes
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
20
20a
33 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
20b
20c
20d
34 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
20e
20f
35 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
20g
20h
36 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Limiting Fire Spread - Compartmentation
Question 21. Is the current level of compartmentation adequate for the premise?
Answer Title No
Question Notes 1.PRIOR TO COMMENCING ANY WORKS ON STAIRWELL DOORS CONFIRMATION IS REQUIRED THAT THEY MEET FD30 STANDARD (REFER pic21e) . Fire doors/closures in the following locations require easing/adjusting to ensure door close flush to frame or other wise stated in actions. 2. Fire stopping required in several areas - details in actions. Some cover panels missing in riser cupboards. Excessive use of foam observed throughout. 3. Several GERDA flat front doors missing letter boxes 4. Ground floor stairwell door to lift lobby - unable to confirm fire resistant glass panels. Examples of good fire stopping within service riser/cupboard (pics 21r,s,t,u )
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/08/2017
Documents
21
37 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
21a
38 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
21b
21c
21d
21e
39 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
21f
21g
21h
40 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
21i
21j
21k
41 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
21l
21m
42 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
21n
21o
43 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
21q
21r
21s
44 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
21t
21u
Question Details
Area All Areas
Risk Category Limiting Fire Spread - Dampers
45 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question 22. Where required, are dampers provided?
Answer Title Yes
Question Notes Chute room ground floor - there are 2 chutes - UNABLE TO CONFIRM dampers activated by fusible links are present .
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
22
Question Details
Area All Areas
Risk Category Maintenance Checks - General
Question 23. Are appropriate building maintenance checks undertaken regularly?
Answer Title No
Question Notes 1.Tenants room not access to check fixed electrical equipment . 2. Numerous ceiling wire trunking covers throughout have dropped or missing screws. 3. Twin door service risers on each floor have incorrect top bolt which drops down allowing doors to be accessed and combustibles dumped inside.
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
46 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Documents
23
23a
23b
23c
47 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
23d
Question Details
Area All Areas
Risk Category Maintenance Checks - General
Question 24. Are lifts adequately maintained?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
48 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Maintenance Checks - General
Question 25. Are the premises generally well maintained?
Answer Title Yes
Question Notes
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
Question Details
Area All Areas
Risk Category Maintenance Checks - General
Question 26. Have all installed or portable electrical appliances been tested in accordance with regulations?
Answer Title Yes
Question Notes Tenants room not accessed
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
Question Details
Area All Areas
Risk Category Maintenance Checks - General
Question 27. Is the lightning protection system adequately maintained?
Answer Title Yes
Question Notes Tested 27/01/2015
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
49 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Documents
Question Details
Area All Areas
Risk Category Maintenance Checks - General
Question 28. Is the sprinkler system adequately maintained?
Answer Title Na
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Lighting
Question 29. Are all exits and exit routes adequately illuminated (internal and external)?
Answer Title Yes
Question Notes Emergency lighting fitted to lobbies/ staircases/external (pic 29)
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
29
50 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
29a
29b
Question Details
Area All Areas
Risk Category Means Of Escape - Lighting
51 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question 30. Are any other areas as required adequately illuminated?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Lighting
Question 31. Are emergency escape lighting tests recorded?
Answer Title Yes
Question Notes Tested 01/04/2016. 2017 Programme under way.
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Lighting
Question 32. Is the emergency escape lighting adequately maintained?
Answer Title No
Question Notes Ceiling light covers were missing or dropped.
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
52 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Means Of Escape - Lighting
Question 33. Where fitted, is the emergency escape lighting in good working order?
Answer Title No
Question Notes As per Q32.
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 34. Are all escape routes clear and unobstructed?
Answer Title No
Question Notes EXTREME Storage of bulk items belonging to - called supervisor to remove asap. , bikes & scooters (outside flats ), armchair, wheelie bin, Tesco trollies stored by ground floor staircase and other items would impede safe means of egress.(pics 34,a,b,c)(also pics 5,a,b,c)
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
5
53 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
5a
5c
5f
54 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 35. Are all floors free from slipping/tripping hazards?
Answer Title No
Question Notes 1.refer Q34 also opposite - metal sit up bar has been screwed to storage cupboard presenting trip hazard. (pic 34d) 2. External - uneven paving slabs present risk of STF's (pic 35a)
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
35
55 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
35a
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 36. Are corridors sub-divided (where appropriate)?
Answer Title Yes
Question Notes Twin - lobby doors installed (pic 36)
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
36
56 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 37. Are doors on escape routes easily opened and do they open in the correct direction?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 38. Are there reasonable arrangements in the building for means of escape for disabled people?
Answer Title Yes
Question Notes LBN, in liaison with London Fire Brigade, have a stay put policy.
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 39. Are travel distances to fire exits satisfactory - single and two-way?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
57 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 40. Do all escape routes lead to a place of safety?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 41. Does the escape route design meet the necessary Home Office guidelines?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 42. Is adequate separation evident on all escape routes (as appropriate)?
Answer Title Yes
58 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 43. Is the number and provision of exits adequate?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Means Of Escape - Routes
Question 44. Is there adequate protection provided/installed to all escape routes?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
59 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Means Of Escape - Signage
Question 45. Are signs clearly visible and not obstructed?
Answer Title Yes
Question Notes Examples of signage (pics 45, a,b,c,d,e)
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
45
45a
60 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
45b
45c
61 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
45d
45e
62 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
45f
45g
63 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Means Of Escape - Signage
Question 46. Is there adequate provision of fire safety signs and notices?
Answer Title No
Question Notes Numerous fire action signs by lift call points missing or becoming unfixed and do not meet BS 5499 .
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
Question Details
Area All Areas
Risk Category Other Issues - General
Question 47. Are there any other issues to specify?
64 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Answer Title Yes
Question Notes Q47. 1.Flats either full access gained - flat front doors check - where access was gained smoke alarms tested and bathrooms , kitchens , cupboards where possible were inspected for any breaches in compartmentation. Example of good fire stopping in kitchen cupboard within a flat (pics47,a,b) 2.High number of GERDA FD30S doors where door closures had been removed . 3.Some fire internal fire alarms were not present in LEASEHOLD FLATS. 4.1st floor riser cupboard there is a small water heater permanently switched on - could possibly feed tenants room or concierge lodge.
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
47
47a
65 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
47b
47c
47d
66 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Question Details
Area All Areas
Risk Category Premises Management - Records And Security
Question 48. Are there appropriate fire safety procedures in place?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Premises Management - Records And Security
Question 49. Are there provisions in place for liaison to take place with the local fire and rescue service?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
67 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Documents
Question Details
Area All Areas
Risk Category Premises Management - Records And Security
Question 50. Is there an available and suitable record of fire safety arrangements?
Answer Title No
Question Notes
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/08/2017
Documents
Question Details
Area All Areas
Risk Category Records - Fire Maintenance
Question 51. Are fire safety maintenance records available for the premises?
Answer Title No
Question Notes
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/08/2017
Documents
Question Details
Area All Areas
Risk Category Sources Of Ignition - Smoking
Question 52. Is there evidence of any smoking related activities taking place in non designated areas?
Answer Title No
Question Notes Evidence of smoking in stairwells.(pic 52)
Probability 0
Severity 0
68 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
52
Question Details
Area All Areas
Risk Category Training - Evacuation
Question 53. Where fire evacuation safety drills are considered appropriate, are they carried out at regular intervals?
Answer Title Na
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
Question Details
Area All Areas
Risk Category Training - Trained Personnel
Question 54. Are staff trained in fire safety via induction and/or annual refreshers?
Answer Title No
Question Notes Concierge staff are trained in fire procedures but do not receive annual
69 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
refresher training or have not received training for use of fire extinguishers .
Probability 2
Severity 2
Score 4
Risk Moderate (4)
Date Action Due 01/10/2017
Documents
Question Details
Area All Areas
Risk Category Training - Trained Personnel
Question 55. Is fire safety training recorded?
Answer Title Yes
Question Notes
Probability 0
Severity 0
Score 0
Risk Trivial (0)
Date Action Due 01/07/2018
Documents
70 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
SECTION FIVE
ASSESSMENT PARAGRAPHS
71 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
72 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
SECTION SIX
ACTION SUMMARY
73 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
6. Action Summary
The timescales are deemed by London Borough of Newham to be a reasonable target for officers and managers when planning their implementation. P1 – Matters of very high risk posing an imminent threat of significant harm must be brought to the attention of the on-site management (where available) and the technical co-ordinator within London Borough of Newham by the fastest means. In any event, P1 items must be brought to the attention of the Director and Head of Department (HoD) to initiate immediate response for remedial action full controls to be in place within time specified above unless deemed necessary to remedy with immediate effect. P1 items may not exceed their target deadline without the recorded consent of a senior manager or Head of Department or Director. P2 and P3 items exceeding the target deadline must be reported. P4 items a recommendations but not a legal requirement. However, they should be remedied as budget and management constrains allow. In order to reduce the residual risk to an acceptable level, it will be necessary to implement all but P4 Action Items on the schedule.
Risk Assessment: Action Summary
Area Risk Category Action Risk Risk Due Due Date
All Areas Arson - Fire Load Other-Combustibles Moderate (4) 01/10/2017 01/10/2017
All Areas Arson - Security Relocate Where Possible Waste Disposal Provision.
Moderate (4) 01/10/2017 01/10/2017
All Areas Combustible Materials - Housekeeping
Inform Caretaking Services To Improve The Arrangements For The Disposal Of Waste And Rubbish.
Moderate (4) 01/10/2017 01/10/2017
All Areas Combustible Materials - Housekeeping
Remove Combustible Materials Moderate (4) 01/10/2017 01/10/2017
All Areas Fire Fighting Equipment - Extinguishers
Carry Out Maintenance/Servicing To Fire Extinguishers.
Trivial (0) 01/07/2018 01/07/2018
74 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
All Areas Fire Fighting Equipment - Extinguishers
Other- Provisions Moderate (4) 01/10/2017 01/10/2017
All Areas General Hazards - Any Other Issues
Other- General Moderate (4) 01/10/2017 01/10/2017
All Areas Limiting Fire Spread - Compartmentation
Carry Out Survey To Determine Fire Check Provisions Required.
Moderate (4) 01/10/2017 01/10/2017
All Areas Limiting Fire Spread - Compartmentation
Repair/Install Fire Check Linings To Compartment.
Moderate (4) 01/10/2017 01/10/2017
All Areas Limiting Fire Spread - Compartmentation
Other- Compartments Moderate (4) 01/10/2017 01/10/2017
All Areas Limiting Fire Spread - Compartmentation
Other- Doors Moderate (4) 01/10/2017 01/10/2017
All Areas Limiting Fire Spread - Dampers
Where Installed Provide Up To Date Service/Maintenance Records.
Trivial (0) 01/07/2018 01/07/2018
All Areas Maintenance Checks - General
Other- General Moderate (4) 01/10/2017 01/10/2017
All Areas Maintenance Checks - General
Remove All Rubbish. Moderate (4) 01/10/2017 01/10/2017
All Areas Maintenance Checks - General
Other- PAT Testing Moderate (4) 01/10/2017 01/10/2017
All Areas Means Of Escape - Lighting Carry Out Repair To Emergency Lighting. Moderate (4) 01/10/2017 01/10/2017
All Areas Means Of Escape - Routes Ensure Existing Exit Routes And Exits Are Available For Use And Unobstructed.
Moderate (4) 01/10/2017 01/10/2017
75 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
All Areas Means Of Escape - Routes Remove All Potential Tripping Hazards From Communal Areas.
Moderate (4) 01/10/2017 01/10/2017
All Areas Means Of Escape - Routes Remove Combustibles Items From Outside Dwellings.
Moderate (4) 01/10/2017 01/10/2017
All Areas Means Of Escape - Routes Remove/Repair Flooring To Remove Hazard.
Moderate (4) 01/10/2017 01/10/2017
All Areas Means Of Escape - Signage Other- Signage Moderate (4) 01/10/2017 01/10/2017
All Areas Means Of Escape - Signage Renew/Install Signage As Per Notes. Moderate (4) 01/10/2017 01/10/2017
All Areas Other Issues - General Other- General Moderate (4) 01/10/2017 01/10/2017
All Areas Premises Management - Records And Security
Review Current Procedures. Moderate (4) 01/10/2017 01/10/2017
All Areas Records - Fire Maintenance
Provide Up To Date Maintenance Records. Moderate (4) 01/10/2017 01/10/2017
All Areas Sources Of Ignition - Smoking
Carry Out Periodic Checks To Stop Non-Compliance.
Trivial (0) 01/07/2018 01/07/2018
All Areas Sources Of Ignition - Smoking
Ensure Tenants Are Aware Of The Smoking Policy Within The Estate.
Trivial (0) 01/07/2018 01/07/2018
All Areas Sources Of Ignition - Smoking
Provide Additional Signage. Trivial (0) 01/07/2018 01/07/2018
All Areas Training - Trained Personnel
Other- Staff Moderate (4) 01/10/2017 01/10/2017
76 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
SECTION SEVEN
ACTION DETAILS
77 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Arson - Fire Load
Action Other-Combustibles
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q1-1.Refuse/recycling bins AND BULK WASTE must not be stored directly adjacent to the building -identify suitable area and relocate and manage.(pics 1,1a)
Documents
Action Details
Area All Areas
Risk Category Arson - Security
Action Relocate Where Possible Waste Disposal Provision.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q3-Refer Q1 - action
Documents
78 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Combustible Materials - Housekeeping
Action Inform Caretaking Services To Improve The Arrangements For The Disposal Of Waste And Rubbish.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q4- Combustibles found in service riser cupboards( some removed at time of inspection - concierge informed)
Documents
Action Details
Area All Areas
Risk Category Combustible Materials - Housekeeping
Action Remove Combustible Materials
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q5- 9th floor service riser -remove combustibles. Remove all combustibles from floors 20,15,2. IMPLEMENT ZERO TOLERENCE POLICY ON ANY COMBUSTIBLES WITHIN COMMUNAL AREAS.IMMEDIATE ACTION - ADVISED CONCIERGE ON SITE TO CHECK ALL CUPBOARDS REGULARLY. Remove all unnecessary combustibles from all ground floor stores rooms / risers cupboards.
Documents
79 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Fire Fighting Equipment - Extinguishers
Action Carry Out Maintenance/Servicing To Fire Extinguishers.
Risk Trivial (0)
Date Action Due 01/07/2018
Quantity 1.00
Action Notes
Q12-Tenants room on 1st floor must be accessed and fire extinguishers checked.
Documents
Action Details
Area All Areas
Risk Category Fire Fighting Equipment - Extinguishers
Action Other- Provisions
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q14-Consider the provision of fire extinguishers in all plant rooms .
Documents
80 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category General Hazards - Any Other Issues
Action Other- General
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q19. 1.Ground floor service riser cupboards - competent person to secure all cables correctly (pics 19,a,b) IMMEDIATE ACTION WO 6381786/3 2.Tenants room 1st floor - instruct Concierge Supervisor to access room to confirm adequate housekeeping IMMEDIATE ACTION
Documents
Action Details
Area All Areas
Risk Category Limiting Fire Spread - Compartmentation
Action Carry Out Survey To Determine Fire Check Provisions Required.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q20 - 2.Carry of intrusive surveys of external cladding( this may have already been sampled see Pics20e & f for examples - ONCE ESTABLISHED - REVIEW THIS FRA.
Q21 -2.Carry out inspections of the water service riser room on all floors to ensure correct fire stopping (not possible to access into deep areas high and low without PPE - Pics 21h,i,j) Q21-4 Ground floor stairwell door to lift lobby - confirm glass panels are fire rated to 30 minutes protection or upgrade glass/replace door with FD30S. (pic20h) Carry out inspection of all roof area including plant rooms and also all external ground floor main network power intake room , all other plants rooms and also garages(including tenants) to ensure adequate compartmentation .(pics 21n,o,q )
Documents
Action Details
81 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Area All Areas
Risk Category Limiting Fire Spread - Compartmentation
Action Repair/Install Fire Check Linings To Compartment.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q20 - 1.Repaint surfaces in the following areas using class O paint - 13th floor adjacent flat , 7th floor ceiling adjacent flat 6th floor by lifts ceiling and walls 2nd floor by lifts walls and ceilings , 1st floor ceiling by flat DAMP AROUND 1st floor lift panel (water ingress?) also check all communal areas for other delamination and rectify (pics20,a,b,c,d ).
Documents
Action Details
Area All Areas
Risk Category Limiting Fire Spread - Compartmentation
Action Other- Compartments
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q21- 2.Fire stopping by competent person required - 19th floor electrical riser and excess foam , 18th floor riser cupboard by flat excess foam (pic6), 17th floor riser cupboard by flat - breach in wall (pic6a), 16th floor electrical riser - fire stop and cover plate missing (pic6b), 15th floor example of excess foam use in comms cupboard (pic6c), 12th floor electrical riser by flat - cover missing (pic6d),8th floor dry riser cupboard - fire stopping , mains water riser by flat pipe has breached wall (pic6e), 1st floor chute room - fires stopping required. Concierge lodge cupboard - firestop (pics 6m,n )GROUND FLOOR ALL AREAS - CARRY OUT FULL SURVEY AS THERE ARE MANY BREACHES IN COMPARTMENTATION THROUGH ALL AREAS and replace all trunking panels . (examples - pics 6f,g,h,i,j,k,l) IMMEDIATE ACTION WO 6381786/2
Documents
82 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Limiting Fire Spread - Compartmentation
Action Other- Doors
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q21 - 1.PRIOR TO COMMENCING ANY WORKS ON STAIRWELL DOORS CONFIRMATION IS REQUIRED THAT THEY MEET FD30 STANDARD (REFER pic21e) 20th floor- stairwell door opposite flat adjust so door meets frame (pic21) , 20th floor- stairwell door opposite flats so door meets frame (pic21a), 14th floor - stairwell door opposite flat adjust so door meets frame, 11th floor - stairwell door opposite flat adjust so door meets frame,4th floor stairwell door opposite flat adjust so door meets frame, 3rd floor stairwell door opposite - door closure appears vandalised (pic21g) , 1st floor stairwell door opposite flat adjust so door meets frame - ALSO - Stairwell doors - HAVE BEEN DAMAGED BY INSTALATION OF CLOSURES - COMPETENT PERSON TO ASSESS WHETHER THESE DOORS CAN BE SATISFACTORILY REPAIRED OR REPLACE DOORS ACCORDINGLY - CARRY OUT FULL SURVEY OF ALL STAIRWELL DOORS - EXAMPLES FOUND ON 13TH FLOOR OPPOSITE FLAT (pic21d &e). 12TH FLOOR OPPOSITE FLAT (pic21f) , 11th floor twin lobby doors
Documents
Action Details
Area All Areas
Risk Category Limiting Fire Spread - Dampers
Action Where Installed Provide Up To Date Service/Maintenance Records.
Risk Trivial (0)
Date Action Due 01/07/2018
Quantity 1.00
Action Notes
Chute room ground floor - confirm damper fusible links are present and annual maintenance is being carried out.or upgrade chutes(6 months action.(pic 22)
Documents
83 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Maintenance Checks - General
Action Other- General
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q23. 1.Tenants room - carry out fixed electrical testing and emergency lighting testing if applicable. 2.Ceiling wire trunking covers - carry out full survey and remedial repairs as necessary - defects observed on floors 18,13,12,10,8,1,ground (pics23,a) 3. Twin door service risers on each floor - carry out full survey and fit correct locking mechanism (pics 23c,d)
Documents
Action Details
Area All Areas
Risk Category Maintenance Checks - General
Action Remove All Rubbish.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q25. Tenants room - remove all rubbish and unnecessary combustibles.
Documents
84 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Maintenance Checks - General
Action Other- PAT Testing
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q26. Tenants room - Carry out PAT testing on all portable electrical equipment if applicable.
Documents
Action Details
Area All Areas
Risk Category Means Of Escape - Lighting
Action Carry Out Repair To Emergency Lighting.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q32. Carry out full survey to block to ensure all emergency lighting is in good condition. Replace missing light covers and reaffix dropped covers - carry out full survey of block - observations noted on floors 20 (both stairwells) , 19, 18, 1 (pic 29a,b)
Documents
85 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Means Of Escape - Routes
Action Ensure Existing Exit Routes And Exits Are Available For Use And Unobstructed.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q34. Remove all bikes scooter, trollies etc. from communal areas.
Q35. Remove rubbish from all communal areas.
Documents
Action Details
Area All Areas
Risk Category Means Of Escape - Routes
Action Remove All Potential Tripping Hazards From Communal Areas.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q35. Remove All Potential Tripping Hazards From Communal Areas
Documents
86 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Means Of Escape - Routes
Action Remove Combustibles Items From Outside Dwellings.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q35. Remove Combustibles Items From Outside Dwellings.
Documents
Action Details
Area All Areas
Risk Category Means Of Escape - Routes
Action Remove/Repair Flooring To Remove Hazard.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q35. Carry out Repairs to external paving WO 6381786/4
Documents
87 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Means Of Escape - Signage
Action Other- Signage
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q46. Review requirements for assembly point in THIS BLOCK AND ALL BLOCKS
Documents
Action Details
Area All Areas
Risk Category Means Of Escape - Signage
Action Renew/Install Signage As Per Notes.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q46. Check all floors - Replace all fire action signs located by lift call (pics 45f,g) IMMEDIATE ACTION Initiate programme to replace all fire action notices by each lift call point to meet BS 5499 IN ALL TALL BLOCKS 6 MONTH ACTION
Documents
88 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Other Issues - General
Action Other- General
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q47. 2.Install door closures to GERDA FD30S doors and advise tenants of importance of fire doors/closure - (Pic 47c). Over 50 % of flat front doors are missing there door closures - advise ALL flat from doors are inspected to check door closures present . 3. - no smoke or heat detectors - refer to relevant department. 4. 1st floor riser cupboard there is a small water heater permanently switched on - Clarifiy requirements for this water heater and confirm testing regime under Electrical Regs.is being carried out.(pic )47d
Documents
Action Details
Area All Areas
Risk Category Premises Management - Records And Security
Action Review Current Procedures.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q50. The current fire safety policy is draft form only and current arrangements/policies/procedures are fragmented.
Documents
89 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Records - Fire Maintenance
Action Provide Up To Date Maintenance Records.
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q51. Fire Safety maintenance records need to be made available.
Documents
Action Details
Area All Areas
Risk Category Sources Of Ignition - Smoking
Action Carry Out Periodic Checks To Stop Non-Compliance.
Risk Trivial (0)
Date Action Due 01/07/2018
Quantity 1.00
Action Notes
Q52. Estate Management to review procedures.
Documents
90 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Sources Of Ignition - Smoking
Action Ensure Tenants Are Aware Of The Smoking Policy Within The Estate.
Risk Trivial (0)
Date Action Due 01/07/2018
Quantity 1.00
Action Notes
Q52. Housing Compliance to write to tenants.
Documents
Action Details
Area All Areas
Risk Category Sources Of Ignition - Smoking
Action Provide Additional Signage.
Risk Trivial (0)
Date Action Due 01/07/2018
Quantity 1.00
Action Notes
Q52. Estate Management to provide additional signage.
Documents
91 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ
Action Details
Area All Areas
Risk Category Training - Trained Personnel
Action Other- Staff
Risk Moderate (4)
Date Action Due 01/10/2017
Quantity 1.00
Action Notes
Q55. Arrange annual refresher training for fire procedures including lift control procedure and extinguisher training.
Documents