FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

1 | P a g e

Table of Contents

1. Introduction ..................................................................................................................................... 2 2. Site Description ............................................................................................................................... 2 3. Measurement Requirement ............................................................................................................. 2 3.1 Measurement Equipment ................................................................................................................ 3 3.2 Measurement Location .................................................................................................................... 3 4. Result .......................................................................................................................................... 4 5. Conclusion ...................................................................................................................................... 4 Appendix Appendix A Endorsed Test Report Appendix B Calibration Certificate of the Equipment Appendix C Certificate of Accreditation Appendix D Measurement Photos

Page 3: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

2 | P a g e

1. Introduction

This measurement report is prepared by Fugro Technical Services Limited (FTS). It includes the assessment criteria, measurement methodology and results.

2. Site Description

The project site is located along Campus Circuit East in the Chinese University of Hong Kong. The building consists of 3 blocks – Wing A, Wing B and Wing C. It is under major renovation and the work is being conducted in two phases. Wing A and Wing B will be conducted in first phase and Wing C will be conducted in the second phase. The general layout plan of the project site is shown in Figure 2.1.

3. Measurement Requirement

The requirements as stipulated in A Guide on Indoor Air Quality Certification Scheme for Offices and Public Places [2019] will be used as reference in this project. The measurements were conducted by an IAQ Certificate Issuing Body (CIB) in representative locations after building completion. The Certificate of Accreditation is shown in Appendix C. The measuring parameters are listed in Table 3.1.

Wing A

Wing B

Wing C

Page 4: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

3 | P a g e

Table 3.1 Monitoring Parameters and Criteria

Parameters Unit 8-hour average

Excellent Class Good Class

Total Volatile Organic Compounds (TVOC)

μg/m3 < 200 < 600

ppbv < 87 < 261

Formaldehyde (HCHO) μg/m3 < 30 < 100

ppbv < 24 < 81

The methodology listed in “A Guide on Indoor Air Quality Certification Scheme for Offices and Public Places [2019]” (The Guide) shall be followed.

3.1 Measurement Equipment

The technical information of measuring equipment is listed in Table 3.2. Calibration certificates of the measurement equipment are shown in Appendix B. Table 3.2 Measurement Equipment for IAQ

Parameters Model of equipment Serial Number Expiry Date

TVOC ppbRAE 3000 – PGM-7340 594-911965, 594-000835

19/08/2020 19/08/2020;

HCHO Riken Keiki FP-31 8Z3050138; 8Z3050134

21/05/2021; 19/06/2021

3.2 Measurement Location

Total 14 number of indoor primary locations were designated for the IAQ measurements. All measurement locations are marked in Table 3.4.

Table 3.4 Measurement Locations

Location ID Floor Room

1 1 C117

2 1 C122

3 2 C220

4 2 C229

5 3 C315

6 3 C318

7 4 C406

8 4 C409 9 5 C504

10 5 C515

11 6 C616

12 6 C630

13 7 C703

14 7 C731

Page 5: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

4 | P a g e

4. Result Measurements were conducted on 19th June 2020, 8th and 9th July 2020. Measurement photo records can be found in Appendix D. Table 4.1 Result Summary

Sample ID Location Measurement Date TVOC HCHO Compliance

(Yes/No) ppbv ppbv

1 C117

09/07/20

95 16 Yes

2 C122 135 28 Yes

3 C220 65 26 Yes

4 C229 161 41 Yes

5 C315

08/07/20

66 20 Yes

6 C318 150 28 Yes

7 C406 137 29 Yes

8 C409 89 24 Yes

9 C504

19/06/20

107 30 Yes

10 C515 106 20 Yes

11 C616 201 40 Yes

12 C630 56 24 Yes

13 C703 127 31 Yes

14 C731 73 24 Yes

IAQ Good Class Criteria - <261 <81 -

5. Conclusion

Measurement results show that the indoor sources of TVOC and HCHO at 14 locations meet the standard of Good Class criteria in A Guide on Indoor Air Quality Certification Scheme for Offices and Public Places [2019].

Page 6: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

APPENDIX A

Endorsed Test Report

Page 7: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

Test Report on Analysis of Air Client : The Chinese University of Hong Kong

Project : VOC and Formaldehyde Measurement for Jockey Club Postgraduate

Hall 1

Sample Description : 14 samples of air

Test Required : 1. Total Volatile Organic Compounds (TVOC) 2. Formaldehyde (HCHO)

Date of in-situ sampling : 19/06/20, 08/07/20 – 09/07/20

Test Method Used

Parameters Methodology Model of equipment Sampling Period

TVOC Measured by a real-time TVOC monitor with photo-ionization detector

ppbRAE 3000 – PGM-7340 Four half-an-hour time slot

evenly distributed within the 8-hour sampling period

HCHO Measured by real-time monitor with Photoelectric photometry method

Riken Keiki FP-31

Equipment Used

Parameters Model of equipment Serial Number Expiry Date

TVOC ppbRAE 3000 – PGM-7340 594-911965, 594-000835

19/08/2020 19/08/2020;

HCHO Riken Keiki FP-31 8Z3050138; 8Z3050134

21/05/2021; 19/06/2021

Note: This report refers only to the sample(s) tested.

Page 8: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 9: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

APPENDIX B

Calibration Certificates of Equipment

Page 10: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 11: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 12: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 13: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 14: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 15: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 16: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 17: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 18: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

APPENDIX C

Certificate of Accreditation

Page 19: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval
Page 20: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

APPENDIX D

Measurement Photo Record

Page 21: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

Room C117 Room C122

Room C220 Room C229

Room C315 Room C318

Page 22: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

Room C406 Room C409

Room C504 Room C515

Room C616 Room C630

Page 23: FUGRO TECHNICAL SERVICES LIMITED - pgh.cuhk.edu.hk · The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval

FUGRO TECHNICAL SERVICES LIMITED

Room 723-726, 7/F, Block B, Profit Industrial Building

1-15 Kwai Fung Crescent

Kwai Fong

Hong Kong

Report No.: 0071/20/ED/0114

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

Room C703 Room C731


Recommended