ComfortPoint OpenExcel 500/600 Hardware Migration Kit
Trademark Information
ComfortPointTM Open is a trademark of Honeywell International Inc.
BACnet® is a registered trademark of ASHRAE Inc.
Disclaimer
All images used in this document are for illustrative purposes only and may not match the actual product.
GENERAL
ComportPoint Open Excel 500/600 Hardware Migration Kit consists of various combinations of Adapter boards to migrate Excel 500/600 controllers (Excel 500/600s with the housing, which is XC5010B, XC5010C, XC5210C, and XC6010) to a ComfortPoint Open System. The ComfortPoint Open library applications are used to convert the Honeywell CARE control program logic to ComfortPoint Open.
ComfortPoint Open Excel 500/600 Hardware Migration Kit
The Excel 500/600 Hardware Migration Kit supports XL500/600 controllers used with the XS563 wiring base and the 14507274-001/002 extended wiring base.
The Excel 500/600 Hardware Migration Kit plugs into the existing Excel 500/600 wiring base and eliminates the need to rewire the I/O or rearrange the panel layout.
DATA SHEET
Caution
Not suitable for UUKL/Smoke Control Application.
Attention
The information provided herein is correct and up to date at the time of production. Due to Product renovation & technology upgrade, the specifications given in this data sheet are subject to change. Please contact your nearest Honeywell Building Solutions branch for current updates.
XS563 Wiring Base 14507274-001/002 Extended Wiring Base
Copyright 2017 – Honeywell International Inc. EN0B-0057 IE10 R1216
I/O MODULE COMPATIBILITY MATRIX WITH EXCEL 500/600 HARDWARE MIGRATION KIT
Figure 1 XS564 Enclosure
The Excel 500/600 Hardware Migration Kit replaces the Excel 500/600 controllers in the housing (XC5010B, XC5010C, XC5210C, and XC6010 CPUs) with XF521A, XF522A, XF523A, XF524A, XF526, XF527, and XF529 I/O modules.
The CPO-PC-6A controller is installed onto the Excel 500/600 Hardware Migration Kit using the supplied DIN Rail and the 2-wire and 4-wire harnesses for power and communication.
Figure 2 With Plant Controller and I/O modules
Figure 3 With Panel Bus I/O modules only
The Panel Bus I/O modules can be inserted in all four slots.
I/O Module Compatibility Matrix with Excel 500/600 Hardware Migration Kit
Notes
*XFR825A is not supported by the Excel 500/600 Hardware Migration Kit.
**XF526 supports PT100 - Not supported by XF821A
FEATURES
Following lists the features of the Excel 500/600 Hardware Migration Kit:
• Can be installed directly onto the XS563 wiring base and the 14507274-001/002 extended wiring base.
• Rewiring of I/O terminations is not required.
• Can mount CPO-PC-6A on Excel 500/600 Hardware Migration Kit using DIN Rail.
• Honeywell Panel Bus I/O modules can be installed directly on Excel 500/600 Hardware Migration Kit.
Plant Controller
Panel busI/O Modules
Excel 500/600Hardware Migration Kit2-wire harness
XL500/600 Wiring Base
4-wire harness
Ribbon cable
Panel busI/O Modules
Ribbon cable Excel 500/600
Hardware Migration Kit
Attention• Only dry contacts for digital inputs are allowed.• Wiring changes are required for floating
outputs.• Use of the XI581 operator panel is not
supported.• Use of the XH562 front cover is not supported.• Does not support the Excel 500/600 door
mounted version.
Excel 500/600 I/O Module
Panel I/O Module
Type Override Switches
XF521A XF821A Analog Input N/A
XF522A XFR822A Analog Output Yes
XF523A XF823A Digital Input N/A
XF524A XFR824A Digital Output Yes
XF525A XFR825A* 3-position Output
Yes
XF526** XF821A Analog Input N/A
XF527 XF822A Analog Output No
XF529 XF824A Digital Output No
EN0B-0057 IE10 R1216 2
ELECTRICAL DATA-HONEYWELL PANEL BUS I/O MODULES
SPECIFICATIONS
Electrical Data-Honeywell Panel Bus I/O Modules
The electrical specifications are same as the Honeywell Panel Bus I/O modules.
See the Panel Bus I/O Modules Data sheet (EN0B-0701GE51).
Environmental
Temperature
• Operation: 0 ~ 50°C
• Storage: -28.9 ~ 70°C
Ambient Humidity
• 5~95% relative humidity, non-condensing
Certifications
• CE
• UL916
• China RoHS 2
Mechanical data
Interface to Excel 500/600 wiring base
Compatible with Excel 500/600 system wiring base.
• Number of pins in a single slot: 18
• Pin pitch within a slot: 5.00mm
• Number of modules supported: 4
Interface to Honeywell Panel Bus I/O Modules
• Number of modules supported:
- 4 (when plant controller is not used)
- 2 (when plant controller is used)
• Slot dimension: 91 x 46mm
Interface to plant controllers
• DIN Rail width: 35mm
• DIN Rail length: 175mm for CPO-PC-6A
• DIN Rail mounting holes: 15 x 6.1mm
Plastic material
PPO
DIMENSIONS
191
47
50.4
145
44.5
All dimensions are in mm.
3 EN0B-0057 IE10 R1216
Part numbers and Accessories
The ComfortPoint Open Excel 500/600 Hardware Migration Kit is ordered using the CPO XL500/600 Migration Kit Specifier sheet. Contact your local Solution Design Centre for the Specifier sheet.
Excel 500/600 Hardware Migration Kit Part number
Note
The detailed Part numbers can be found or are selected using the Specifier.
Accessory Part Numbers
The accessories are only available in the pack quantities listed in the table below and are ordered as a set. For example, an order for 1 CPO-MX821 contains 12 pieces of CPO-MX821.
*MOQ: Minimum Order Quantity
Figure 4 Excel 500/600 Hardware Migration Kit and Blank Covers
Part number Description MOQ*
CPO-XL500MKIT-XXXX (X=0-9)
ComportPoint Open Excel 500/600 Hardware Migration Kit (for use with XS563 wiring base)
1
CPO-XL500MKITXXXXE
(X=0-9)
ComportPoint Open Excel 500/600 Hardware Migration Kit (for use with 14507274-001/-002 extended wiring base)
1
Part number Description MOQ*
CPO-MX863 CPO Excel 500/600 Base Migration Kit with 4 Blank Covers, DIN Rail and Wiring Harnesses for the plant controller; Adapter Boards not included (for use with XS563 wiring base)
10
CPO-MX863E CPO Excel 500/600 Base Migration Kit with 4 Blank Covers, DIN Rail and Wiring Harnesses for the plant controller; Adapter Boards not included. (for use with 14507274-001/-002 extended wiring base)
10
CPO-MX821 Adapter Board for XF821A Panel Bus I/O Module 12
CPO-MX822 Adapter Board for XF822A and XFR822A Panel Bus I/O Modules 12
CPO-MX823 Adapter Board for XF823A Panel Bus I/O Module 12
CPO-MX824 Adapter Board for XF824A and XFR824A Panel Bus I/O Modules 12
14507330-001/U 76mm Ribbon Cable; replaces XW568 Ribbon Cable
14507330-004/U 406mm Ribbon Cable; replaces XW569 Ribbon Cable
Blank Cover
Excel 500/600 Hardware Migration Kit
Honeywell Building Solutions
EN0B-0057 IE10 R1216December 2016© 2017 Honeywell International Inc.
1985 Douglas Drive North
Golden Valley MN 55422-4386
USA
www.honeywell.com