Transcript
Page 1: Ethylene Glycol Technical Data Sheet - AFD Petroleum · PROPERTIES Reserve Alkalinity Specific Gravity @ 60˚F Boiling Point, Reflux pH 50/50 Solution ... Inhibited Ethylene Glycol-based

GENERAL DESCRIPTION

ColorOdorPack/UnitFluid Wt. per Gal.

Florescent PinkNot OffensiveBulk/Drums9.35 - 9.45 lbs./gal.

SUITABLE APPLICATIONS

• Water Based HVAC• Process Heating and Cooling• Thermal Energy Storage

• Hydronic Heating Systems• Fire Sprinkler Systems• Solar Heating

PROPERTIES

Reserve Alkalinity

Specific Gravity @ 60˚F

Boiling Point, Reflux

pH 50/50 Solution

Total Water & Inhibitors

Total Glycols

TYPICAL VALUES

11.0 mL min.

1.125 - 1.135

317˚F

9.0 - 9.6

4%

96%

ASTM TEST METHOD

D-1121

D-1122

D-1120

D-1287

D-1123

E-202

Technical Data Sheet

Ethylene Glycol

Inhibited Ethylene Glycol-based Heat Transfer FluidThermal Charge EG heat transfer �uid is formulated of 96% weight percent ethylene glycol and has a specially designed package of industrial corrosion inhibitors. The �uid is dyed �uorescent pink to aid in leak detection.Thermal Charge EG provides freeze protection to -60˚F (-50˚C) and burst protection to -100˚F (-73˚C).

Recommended use temperature range: -60˚F (-50˚C) to 250˚F (120˚C)

11110

THERMAL CHARGE EG FLUID % VOLUME REQUIRED

For Freeze Protection

17%26%35%41%46%50%55%59%63%

For Burst Protection

12%18%23%27%

31.4%31.4%31.4%31.4%31.4%

-7-12-18-23-29-34-40-46-51

20100

-10-20-30-40-50-60

Temperature(F°) (C°)

To order, please call Old World Industries, Inc.Customer Service at 1-800-323-8755.Thermal Charge™ is a trademark of

Old World Industries, Inc. ©2010 All Rights ReservedOld World Industries, Inc. 4065

Commercial Ave. Northbrook, IL 60062-1851

CORROSION TEST RESULTS

MaterialTested

CopperStandard SolderBrassSteelCast IronCast Aluminum

ASTM D-1384Maximum Weight

Allowed

10 mg30 mg10 mg10 mg10 mg30 mg

Heat Transfer

Fluid Results

2 mg 1 mg 2 mg3 mg 0 mg2 mg

Recommended