Samsung Electronics Co., LTD.Head Office (Suwon Korea) 416, Maetan-3Dong, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 443-742www.dvmsystem.com / Tel : 82-31-200-6421 / Fax : 82-31-200-0938 Ver.4
imagine refreshing comforts2008 Samsung DVM System Air Conditioner will provide you
refreshing coolness. Feel the comfort you have never experienced
with the cool, refreshing air that Samsung’s new DVM PLUS Air
Conditioners provides. Experience the maximum comfort in real
life. With Samsung, imagination comes to life.
2008 SA
MS
UN
G
SY
STE
M A
IR C
ON
DITIO
NE
RS
Ver.4
In the Digital era, products are being distinguished by their brand in addition to their functions or quality.
In 1999 Samsung Electronics has implemented its global brand communication strategy. Since then,
based on the research conducted by Interbrand INC., USA, Samsung Electronics has become one of the
fastest growing brands equities from 6.4 billion USD (2001) to over 16.85 billion USD (2007) and is now
ranked 21st on Interbrand's Top100 Global Brand List.
Samsung has increased its value by emphasizing technology as a life innovator. Samsung will remain
close to the customer through its technologies contributing to a higher quality of life.
SAMSUNG brand equity has reached 16.85 billion USD in 2007
Tremendous Investment in R & DSamsung's thrust on Product Innovation and R&D has given the company a competitive edge in the marketplace.
With an investment of over USD 4.59 billion, Samsung operates 16 R&D centers worldwide and employs
27,000 researchers of which 2,500 hold a Ph. D. As a result, Samsung has already applied for 1600 patents in
the USA. The focus of the R&D center is to customize electronics products to meet the Specific needs of
consumers in that region. Samsung R&D Centers are helping the company to continuously innovate and
introduce products customized for today’s global market.
LondonMoscow
Israel
Bangalore
Beijing
NanjingSuzhou
Giheung(3)
Yokohama
Suwon(3)San Jose
Dallas
The Best Global Brands 2007 Report Ranking by Interbrand
What is “Green Management?”SAMSUNG Electronics' corporate policy of making "Green Management, the
top priority of all corporate activities" has led to bold and continuous
measures. Such measures include developing green technologies and green
products, reducing waste and maintaining accident-free workplaces based
on the five pillars of Green Management: Management, Products, Processes,
Workplaces and Communities. SAMSUNG is not only making its products
more environmentally friendly, but is also building pollution-free workplaces by
minimizing the use of harmful substances in processes and developing
greener substitutes. With the pursuit of green management, Samsung will
continue to create new values as a digital leader in the 21st century.
SAMSUNG
Big ConfidenceGlobal LeadingCompany >>
02_ Brand Value
06_ Line-up
10_ New Technology
18_ DVM PLUS / HR
42_ Mini DVM
46_ Free Joint Multi
108_ Integrated Management System
116_ Centralized Control System
118_ Individual Control System
120_ Building Management System
123_ Accessories
Introduction
Indoor Units
Outdoor Units
Control Systems62_ Wall mounted Type
70_ Cassette Type
84_ Duct Type
92_ Floor & Convertible Type
100_ ERV System
104_ Accessories
2008 Samsung DVM System Air Conditioners have all the desirable features you can possibly get. This year’s
outdoor units with new advanced technologies are more powerful and efficient. Stylish indoor units have also
become more compact for easier installation. Complete control system helps easier control and adds
convenience. Everything is just ahead of your expectation for absolute satisfaction.
imaginebeyond your limit
2 0 0 8 S a m s u n g D V M A i r C o n d i t i o n e r s
Line-up - Outdoor Units Samsung DVM Air Conditioners runs with new refrigerant R410A, which will not pollute our global environment.
DVM PLUS III / DVM PLUS III HR
Free Joint Multi
4.0kW
2 Units
5.0kW
2 Units
6.0kW
3 Units
7.0kW
4 Units
8.0kW
4 Units
Mini DVM
4HP 5HP 6HPBasic Model
Combination Table
High Efficiency Combination
Compact Combination
Line up
High Efficiency Combination
RVXVHT080GERVXVRT080GE
8HP 10HP 12HP 14HP
8HP 10HP 12HP 14HP 16HP
DVM PLUS IIIDVM PLUS III HR
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
Line up
Compact Combination
Model 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56
RVXVHT080GERVXVRT080GE
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
RVXVHT140GERVXVRT140GE
Model 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58
RVXVHT080GERVXVRT080GE
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
60 62 64
RVXVHT140GERVXVRT140GE
RVXVHT160GERVXVRT160GE
06 07
RVXVHT140GERVXVRT140GE
RVXVHT080GERVXVRT080GE
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
RVXVHT140GERVXVRT140GE
RVXVHT160GERVXVRT160GE
DVM PLUS IIIDVM PLUS III HR
2 1
1 2 1
1
3 2
1
1
2 3 2
1
2
1
1
1
1
1
2
1
2 3
3
1
2
1
1
2
2
1
1
2
2
2
1
3 4
1
1 2 1
1
1
1
1
1 2 1
1 2
1
2 3 2
1
2
1
1
1
1
2
1
1
2 3
3
1
3
1
1
1
2
1
1
2
1
3
1
3
1
3 4
Line-up - Indoor Units
Samsung DVM Air Conditioners runs with new refrigerant R410A, which will not pollute our global environment.
Type
Slim 1Way
7K Btu/h
2.2 kW
9K Btu/h
2.8 kW
12K Btu/h
3.6 kW
15K Btu/h
4.5 kW
18K Btu/h
5.6 kW
21K Btu/h
6.0 kW
24K Btu/h
7.1 kW
30K Btu/h
9.0 kW
36K Btu/h
11.2 kW
44K Btu/h
12.8 kW
4Way cassette
Mini 4Way cassette
2Way cassette
Slim Duct
M.S.P Duct
MB
Vivace
Neo Forte
Console
Ceiling
48K Btu/h
14.0 kW
KBtu/hkW
08 09
See this year’s new technologies with your own eyes. Never ending development ofSamsung’s technologies will satisfy all your expectations. Each of this year’s new technologieswere considered to provide you the most efficient and convenient air conditioners. Experienceall the newest technologies. Feel the difference.
New Technology
imaginenever ending development
10 11
New Technology
New
Technology
New Technology
2008 SAMSUNG DVM Air Conditioners New Technology
12 13
DVI CompressorEfficient and reliable DVI Compressor coupled with VaporInjection technology has been applied to improve coolingand heating performance and energy efficiency.
DHS (Digital Hybrid System) is a brand new concept system composed of DVI compressor, vapor injectiontechnology and turbo intercooler. These 3 factors together provide highly efficient performance.
Highly efficient O8 Grooved tube hasbeen applied to reduce pressureloss while increasing heat transferperformance to improve COP.
High efficiency new G-fin improved heattransfer performance and reinforce corrosion resistance.
Turbo intercooler(Shell and Tube Type)improves cooling and heating COP andsecure reliability on long piping installation.
DVI (Digital Vapor Injection) compressorinjects optimized mid-range pressurerefrigerant to improve cooling and heatingperformance and efficiency.
Fan Guard
Ø8 Heat Exchanger
O8 Heat Exchanger
Newly Designed G-Fin
New G-Fin
Turbo Intercooler
Vapor Injection Compressor
Turbo Intercooler
DVI Compressor
OverviewNew DVM Plus III System Air Conditioner has improved its performance with remarkabletechnologies. We now introduce these notable technologies and how they improved the performance of your air conditioner. Witness the wonderful technologies that makes better world.
Turbo IntercoolerTurbo intercooler (Shell & Tube Type) improved cooling andheating COP, to secure reliability on long piping installation.● Improve COP with the application of Turbo intercooler.
● Adequate sub-cooling to ensure reliable operation on installationswith long piping (200 m).
Subcooled liquid refrigerant
Low temperature gasrefrigerant
Vapor Injection Tube
Vapor Injection Port
Low temp. liquid refrigerant
Saturated liquid refrigerant
New Technology
Digital Hybrid System
DVICompressor
VaporInjection Turbo
Intercooler
Vapor Injection TechnologyImproved cooling and heating performance and COP by anew technology of two stage compression. This technologyachieved the high heating performance and COP underthe lowest temperature, which leads the industry.● Increase refrigerant flow rates with a new Vapor Injection
technology.
● Improved Sub-cooling necessary for long piping runs whileincreasing cooling and heating performance and COP.
Temperature
High
Low
❶ ❶
❷
❷
❸
❸
❹
❹
Optimized fan guard design enhancedair flow volume which achieved the highheat transfer performance withoutincreased noise.
Fan Guard
New
Technology
New Technology
2008 SAMSUNG DVM Air Conditioners New Technology
14 15
Newly Designed Fan GuardFan Guard has been optimized to improve air volume and reduce noise and vibration.
● BLDC Motor, which is 2.7% more efficient than the competitors, has been applied.
● Applied high static pressure propeller fan and the optimum Bell Mouth form for high external static pressure. (External static pressure: 8mmAq)
New G- FinHighly efficiency new G-Fin increased heat transfer performance, reinforced corrosion resistance, and increasedoperating duration in frost condition.● Heat transfer performance improved by 13% compared to the conventional fin, even with the equivalent pressure loss.
● Epoxy Acrylic Coating reinforced corrosion resistance.
● Heating operation time is 1.4 times longer in frost condition due to new G-Fin.
Hydrophilic layer Acrylic resin + surfactantAnti corrosive layer
Epoxy acrylic
Raw aluminummaterial
0.3µm
2.0µm
92µm
Conventional (Louver Fin)DVM PLUS III (New G-Fin)
Wide Louver FinG - Fin
Cap
acity
, Pow
er o
utpu
t (W
) 5000
4000
3000
2000
1000
00 30
Time (min.)60 90 120
EVA
. CO
ND
tem
pera
ture
(°C) 60
50
40
30
20
10
0
-10
-20
-300 30
Time (min.)60
DVM PLUS III
Conventional Model
New Technology
High Efficiency O8 Heat ExchangerEfficient O8 Grooved tube reduced pressure loss while increasing heat exchange rates to improve COP.
● Groove shape is designed to be high and slim to increase heat transfer performance inside the tube.
DVM PLUS IIINew Groove Shape (High and Slim)
Competitor’s Product
Item Improved Heat ExchangerO7 ➝ O8
19% ↑14.1% ↓10.3% ↓30.8% ↑
same
DiameterHeat transfer surface areaPressure loss in heatexchangerInternal heat transfer performancePressure resistance
EvaporationCondensation
O8 Heat Exchanger and New G-fin
New
Technology
New DVM Plus III system air conditioners have become more powerful, efficient and compact.DVM Plus III is equipped with more advanced technologies to provide effective cooling andheating, save energy, and help easier installation. DVM Plus III has capacity up to 64HP withmore compact size. Be ready for the new generation of the outdoor unit.
Outdoor Units
>> 18_ DVM PLUS III / HR >> 42_ Mini DVM >> 46_ Free Joint Multi
imaginethe absolute power
Outdoor Units
16 17
Outdoor U
nits
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
18 19
Outdoor U
nits
DVM PLUS III / HR Multi Modular Technology
Comparison to Inverter IIIDVM PLUS IIIDVM PLUS III
Company ACompany A
Up to 56HP
Only 36HP
DVM PLUS IIIDVM PLUS III
Company ACompany A
Up to 64HP
Only 54HP
HighEfficiency
Combinations
Compact Combinations
Line up
DVM Plus III/HR offers the largest capacity in the industry with 64HP andboasts the highest COP levels. More compact size, with larger capacity,shows the efficiency of the product. DVM Plus III HR has all the featureswhich DVM Plus III has and offers even more features. DVM Plus III HR willgive you simultaneous cooling and heating where different air conditioning isneeded under same outdoor unit.
Basic Model
Line up
High Efficiency Combinations
RVXVHT080GERVXVRT080GE
8HP 10HP 12HP 14HP
8HP 10HP 12HP 14HP 16HP
DVM PLUS IIIDVM PLUS III HR
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
Line up
Compact Combinations
RVXVHT140GERVXVRT140GE
RVXVHT080GERVXVRT080GE
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
RVXVHT140GERVXVRT140GE
RVXVHT160GERVXVRT160GE
DVM PLUS IIIDVM PLUS III HR
Combination Table
High Efficiency Combinations
Compact Combinations
Model 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56
RVXVHT080GERVXVRT080GE
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
RVXVHT140GERVXVRT140GE
Model 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58
RVXVHT080GERVXVRT080GE
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
60 62 64
RVXVHT140GERVXVRT140GE
RVXVHT160GERVXVRT160GE
2 1
1 2 1
1
3 2
1
1
2 3 2
1
2
1
1
1
1
1
2
1
2 3
3
1
2
1
1
2
2
1
1
2
2
2
1
3 4
1
1 2 1
1
1
1
1
1 2 1
1 2
1
2 3 2
1
2
1
1
1
1
2
1
1
2 3
3
1
3
1
1
1
2
1
1
2
1
3
1
3
1
3 4
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
20 21
Outdoor U
nits
High COPHigh efficiency DVM PLUS III has improved average cooling and heatingCOP compared to conventional products and achieved the world’s TopClass energy efficiency
● DHS(Digital Hybrid System) technology increased refrigerant flow rate andevaporation enthalpy difference.
● Wide O8 Grooved pipe and G-Fin increased heat exchange efficiency.
● The best BLDC Motor in the industry and Optimum Fan Guard designincreased efficiency.
ConventionalConventional
DVM PLUS IIIDVM PLUS III
Company ACompany A
Company ACompany A
3.81 11%
10%
4.23
4.15
ConventionalConventional
DVM PLUS IIIDVM PLUS III
3.73
4.10
4.02
8HP
18HP
Model 12HP 16HPConventional Model 0.92m2 1.35m2
DVM PLUS III 0.67m2 0.92m2
Comparison to Conventional Model 73% 68%
16HP
Approx. 32%reduction
1.35m2 0.92m2
Conventional Model DVM PLUS III
ConventionalModel
DVMPLUS III
8HP 10HP 12HP 14HP 16HP
27% reduction32% reduction
The Smallest Foot Print AreaThe world’s smallest foot print provides smallest installatoinspace which saves incredible amount of time.
Space Saving
8~48HP 8~64HP
Conventional Model DVM PLUS III
The World’s Largest CapacitySamsung has achieved world’s largest capacity of 64HP by combining maximum 4 outdoor units with 5 different capacities. (8, 10, 12, 14 and 16HP) Many combinations of Heat Pump or Heat Recovery types supporting up to 64 indoor units provide consumers variety of choices for any installation condition.
● Compact combinations (8~64 HP) : Combination with the model requiring the smallest installation space.
● High-Efficiency combinations (16~56 HP) : Combination with high-efficiency model.
Digital Unit ModuleDigital Unit Module combination enables the system to alternatecompressor operation to prolong each compressor’s life cycleand improves COP with part loads
● Control the compressor capacity precisely.
● Ensure long life cycle by alternating operation of the DVI compressors.
● Improve COP using multiple heat exchangers of outdoor units at partloads.
DVIScroll
FVIScroll
DVIScroll
FVIScroll
A unit B unit
The World’s Longest Piping Length
The longest pipinglength : 220m(Equivalent Length)
Height differencesbetween indoor &
outdoor units : 50m
The first branch joint to the farthest indoor unit : 45 m(1 Size Up : 90 m)Height difference between indoor units : 15m
DVM PLUS III has an actual piping length up to 200m, with the maximum piping length of 45m from the first branchjoint to farthest indoor unit, thereby providing more convenience and flexibility for installation in commercial buildings.
Summary● The longest piping length : 220m (Equivalent Length)
● Total piping length: 1000 m
● From the first branch joint to the farthest indoor unit : 90m (with one piping Size Up)
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
22 23
Free InstallationDVM Plus III/HR provides the degree of freedom from priority of capacity when installing outdoor units in module.
DVM PLUS III
No limits.
8HP(Digital Unit)
14HP(Digital Unit)
10HP(Digital Unit)
Conventional model
A digital outdoor unit with the largestcapacity should come last.
8HP(Fixed Unit)
10HP(Fixed Unit)
14HP(Digital Unit)
Outdoor U
nits
External Static PressureTo respond to a range of various installation environments, DVM PLUS III isdesigned to be used even in external static pressure of 8 mm Aq.
Automatic Piping Length RecognitionAuto piping length recognition system saves time with no additional settings and performs the optimum operation inaccordance with piping length.
Lead-Free and RoHs
Refrigerant Leakage PreventionTo prevent refrigerant leakage, we provide how to diagnose any refrigerant leakage in operation. Also, changing service valves from flange type to brazedtype further prevents refrigerant leakage.
RoHs ComplianceAlthough RoHS restriction only applies to small and large household electronics, IT equipment, lightings, power train, toys, leisure and sportsequipment, and vending machines. Samsung expands the RoHS restrictioninto its entire range of products based on its own environmental policies.
Lead-FreeDVM Plus III is an eco-friendly product that prevents pollutionproblems caused by the use of lead, by applying lead-freeindoor and outdoor PCBs.
Heating
HeatingCooling
Cooling
Heating
Cooling
MCU(Mode Change Unit)
As DVM PLUS III HR allows a simultaneous cooling and heatingoperation with one system, there are variety range of application.
● Great for places where simultaneous cooling and heating operation isrequired. (Hotels, nursing homes, conference rooms, etc.)
● For seasonal air-conditioning which may need a simultaneous coolingand heating operation.
● In case of medium and large office, DVM PLUS III HR satisfies cooling and heating operation simultaneously for the requirements ofinterior and perimeter zone.
DVM PLUS III HR Versatile Application
Company A
An outdoor unit with the largest capacityshould come first.
14HP 10HP 8HP
Optimal operation by automatic piping length recognition
Off OffOn On
L
On
> >
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
24 25
Outdoor U
nits
Specification | DVM PLUS III / HR
Basic Model
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
DVM PLUS III DVM PLUS III HR
RVXVHT080GERVXVRT080GE
RVXVHT100GERVXVRT100GE
RVXVHT120GERVXVRT120GE
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
3/380~415/50
HP/HR
8
22.4
76,400
25.2
86,000
5.76
5.51
25
3.89
4.57
Propeller/BLDC
9.52
19.05
15.88
-
200
50 (40)
R410A
7.5
57
240
242
253
255
880x1,703x765
948x1,868x832
-5~43
-20~24
3/380~415/50
HP/HR
10
28.0
95,500
31.5
107,500
7.78
7.16
30
3.60
4.40
Propeller/BLDC
9.52
22.23
19.05
-
200
50 (40)
R410A
7.5
58
240
242
253
255
880x1,703x765
948x1,868x832
-5~43
-20~24
3/380~415/50
HP/HR
12
33.6
114,600
37.8
129,000
10.40
9.40
40
3.23
4.02
Propeller/BLDC
12.70
25.40
22.23
-
200
50 (40)
R410A
7.5
60
240
242
253
255
880x1,703x765
948x1,868x832
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
DVM PLUS III DVM PLUS III HR
RVXVHT140GERVXVRT140GE
RVXVHT160GERVXVRT160GE
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
3/380~415/50
HP/HR
14
39.2
133,800
44.1
150,500
11.00
10.40
40
3.56
4.24
Propeller/BLDC
12.70
25.40
22.23
-
200
50 (40)
R410A
11.0
60
320
323
337
340
1,200x1,703x765
1,268x1,868x832
-5~43
-20~24
3/380~415/50
HP/HR
16
44.8
152,900
50.4
172,000
14.80
15.00
50
3.03
3.36
Propeller/BLDC
12.70
28.58
22.23
-
200
50 (40)
R410A
11.0
60
320
323
337
340
1,200x1,703x765
1,268x1,868x832
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
26 27
Outdoor U
nits
Specification | DVM PLUS III / HR
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
16HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
2
3/380~415/50
HP/HR
16
44.8
152,800
50.4
172,000
11.52
11.02
50
3.89
4.57
Propeller/BLDC
12.70
28.58
22.23
6.35
200
50 (40)
R410A
7.5x2
60
240x2
242x2
253x2
255x2
(880x1,703x765)x2
(948x1,868x832)x2
-5~43
-20~24
18HP
1
1
3/380~415/50
HP/HR
18
50.4
171,900
56.7
193,500
13.54
12.67
50
3.72
4.48
Propeller/BLDC
15.88
28.58
25.40
6.35
200
50 (40)
R410A
7.5x2
60
240x2
242x2
253x2
255x2
(880x1,703x765)x2
(948x1,868x832)x2
-5~43
-20~24
20HP
2
3/380~415/50
HP/HR
20
56.0
191,000
63.0
215,000
15.56
14.32
60
3.60
4.40
Propeller/BLDC
15.88
28.58
25.40
6.35
200
50 (40)
R410A
7.5x2
61
240x2
242x2
253x2
255x2
(880x1,703x765)x2
(948x1,868x832)x2
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - High EfficiencyModel
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
22 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
1
3/380~415/50
HP/HR
22
61.6
210,100
69.3
236,500
18.18
16.56
60
3.39
4.18
Propeller/BLDC
15.88
28.58
25.40
6.35
200
50 (40)
R410A
7.5x2
62
240x2
242x2
253x2
255x2
(880x1,703x765)x2
(948x1,868x832)x2
-5~43
-20~24
24 HP
3
3/380~415/50
HP/HR
24
67.2
229,200
75.6
258,000
17.28
16.53
75
3.89
4.57
Propeller/BLDC
15.88
28.58
25.40
6.35
200
50 (40)
R410A
7.5x3
62
240x3
242x3
253x3
255x3
(880x1,703x765)x3
(948x1,868x832)x3
-5~43
-20~24
26 HP
2
1
3/380~415/50
HP/HR
26
72.8
248,300
81.9
279,500
19.30
18.18
75
3.77
4.50
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
7.5x3
63
240x3
242x3
253x3
255x3
(880x1,703x765)x3
(948x1,868x832)x3
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - High Efficiency
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
28 29
Outdoor U
nits
Specification | DVM PLUS III / HR
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
28 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
2
3/380~415/50
HP/HR
28
78.4
267,400
88.2
301,000
21.32
19.83
75
3.68
4.45
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
7.5x3
63
240x3
242x3
253x3
255x3
(880x1,703x765)x3
(948x1,868x832)x3
-5~43
-20~24
30 HP
3
3/380~415/50
HP/HR
30
84.0
286,500
94.5
322,500
23.34
21.48
100
3.60
4.40
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
7.5x3
63
240x3
242x3
253x3
255x3
(880x1,703x765)x3
(948x1,868x832)x3
-5~43
-20~24
32 HP
2
1
3/380~415/50
HP/HR
32
89.6
305,600
100.8
344,000
25.96
23.72
100
3.45
4.25
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
7.5x3
64
240x3
242x3
253x3
255x3
(880x1,703x765)x3
(948x1,868x832)x3
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - High EfficiencyModel
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
34 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
2
1
3/380~415/50
HP/HR
34
95.2
324,800
107.1
365,500
26.56
24.72
100
3.58
4.33
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
7.5x2+11x1
64
240x2+320x1
242x2+323x1
253x2+337x1
255x2+340x1
(880x1,703x765)x2+(1,200x1,703x765)x1
(948x1,868x832)x2+(1,268x1,868x832)x1
-5~43
-20~24
36 HP
1
1
1
3/380~415/50
HP/HR
36
100.8
343,900
113.4
387,000
29.18
26.96
100
3.45
4.21
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x2+11x1
64
240x2+320x1
242x2+323x1
253x2+337x1
255x2+340x1
(880x1,703x765)x2+(1,200x1,703x765)x1
(948x1,868x832)x2+(1,268x1,868x832)x1
-5~43
-20~24
38 HP
1
2
3/380~415/50
HP/HR
38
106.4
363,100
119.7
408,500
29.78
27.96
100
3.57
4.28
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x1+11x2
64
240x1+320x2
242x1+323x2
253x1+337x2
255x1+340x2
(880x1,703x765)x1+(1,200x1,703x765)x2
(948x1,868x832)x1+(1,268x1,868x832)x2
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - High Efficiency
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
30 31
Outdoor U
nits
Specification | DVM PLUS III / HR
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
40 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
2
3/380~415/50
HP/HR
40
112.0
382,200
126.0
430,000
32.40
30.20
125
3.46
4.17
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x1+11x2
65
240x1+320x2
242x1+323x2
253x1+337x2
255x1+340x2
(880x1,703x765)x1+(1,200x1,703x765)x2
(948x1,868x832)x1+(1,268x1,868x832)x2
-5~43
-20~24
42 HP
3
3/380~415/50
HP/HR
42
117.6
401,400
132.3
451,500
33.00
31.20
125
3.56
4.24
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
11x3
65
320x3
323x3
337x3
340x3
(1,200x1,703x765)x3
(1,268x1,868x832)x3
-5~43
-20~24
44 HP
3
1
3/380~415/50
HP/HR
44
123.2
420,300
138.6
473,000
34.34
31.88
125
3.59
4.35
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x3+11x1
65
240x3+320x1
242x3+323x1
253x3+337x1
255x3+340x1
(880x1,703x765)x3+(1,200x1,703x765)x1
(948x1,868x832)x3+(1,268x1,868x832)x1
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - High EfficiencyModel
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
46 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
2
1
1
3/380~415/50
HP/HR
46
128.8
439,400
144.9
494,500
36.96
34.12
125
3.48
4.25
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x3+11x1
65
240x3+320x1
242x3+323x1
253x3+337x1
255x3+340x1
(880x1,703x765)x3+(1,200x1,703x765)x1
(948x1,868x832)x3+(1,268x1,868x832)x1
-5~43
-20~24
48 HP
2
2
3/380~415/50
HP/HR
48
134.4
458,600
151.2
516,000
37.56
35.12
125
3.58
4.31
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x2+11x2
65
240x2+320x2
242x2+323x2
253x2+337x2
255x2+340x2
(880x1,703x765)x2+(1,200x1,703x765)x2
(948x1,868x832)x2+(1,268x1,868x832)x2
-5~43
-20~24
50 HP
1
1
2
3/380~415/50
HP/HR
50
140.0
477,700
157.5
537,500
40.18
37.36
150
3.48
4.22
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x2+11x2
66
240x2+320x2
242x2+323x2
253x2+337x2
255x2+340x2
(880x1,703x765)x2+(1,200x1,703x765)x2
(948x1,868x832)x2+(1,268x1,868x832)x2
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - High Efficiency
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
32 33
Outdoor U
nits
Specification | DVM PLUS III / HR
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
52 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
2
2
3/380~415/50
HP/HR
52
145.6
496,800
163.8
559,000
42.80
39.60
150
3.40
4.14
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x2+11x2
66
240x2+320x2
242x2+323x2
253x2+337x2
255x2+340x2
(880x1,703x765)x2+(1,200x1,703x765)x2
(948x1,868x832)x2+(1,268x1,868x832)x2
-5~43
-20~24
54 HP
1
3
3/380~415/50
HP/HR
54
151.2
516,000
170.1
580,500
43.40
40.60
150
3.48
4.19
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x1+11x3
66
240x1+320x3
242x1+323x3
253x1+337x3
255x1+340x3
(880x1,703x765)x1+(1,200x1,703x765)x3
(948x1,868x832)x1+(1,268x1,868x832)x3
-5~43
-20~24
56 HP
4
3/380~415/50
HP/HR
56
156.8
535,200
176.4
602,000
44.00
41.60
150
3.56
4.24
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
11x4
66
320x4
323x4
337x4
340x4
(1,200x1,703x765)x4
(1,268x1,868x832)x4
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - High EfficiencyModel
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
18 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
1
3/380~415/50
HP/HR
18
50.4
171,900
56.7
193,500
13.54
12.67
50
3.72
4.48
Propeller/BLDC
15.88
28.58
25.40
6.35
200
50 (40)
R410A
7.5x2
60
240x2
242x2
253x2
255x2
(880x1,703x765)x2
(948x1,868x832)x2
-5~43
-20~24
20 HP
2
3/380~415/50
HP/HR
20
56.0
191,000
63.0
215,000
15.56
14.32
60
3.60
4.40
Propeller/BLDC
15.88
28.58
25.40
6.35
200
50 (40)
R410A
7.5x2
61
240x2
242x2
253x2
255x2
(880x1,703x765)x2
(948x1,868x832)x2
-5~43
-20~24
22 HP
1
1
3/380~415/50
HP/HR
22
61.6
210,100
69.3
236,500
18.18
16.56
60
3.39
4.18
Propeller/BLDC
15.88
28.58
25.40
6.35
200
50 (40)
R410A
7.5x2
62
240x2
242x2
253x2
255x2
(880x1,703x765)x2
(948x1,868x832)x2
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - Compact
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
34 35
Outdoor U
nits
Specification | DVM PLUS III / HR
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
30 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
1
3/380~415/50
HP/HR
30
84.0
286,700
94.5
322,500
25.80
25.40
100
3.26
3.72
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
11x2
63
320x2
323x2
337x2
340x2
(1,200x1,703x765)x2
(1,268x1,868x832)x2
-5~43
-20~24
32 HP
2
3/380~415/50
HP/HR
32
89.6
305,800
100.8
344,000
29.60
30.00
100
3.03
3.36
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
11x2
63
320x2
323x2
337x2
340x2
(1,200x1,703x765)x2
(1,268x1,868x832)x2
-5~43
-20~24
34 HP
1
2
3/380~415/50
HP/HR
34
95.2
324,700
107.1
365,500
28.58
25.96
100
3.33
4.13
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
7.5x3
64
240x3
242x3
253x3
255x3
(880x1,703x765)x3
(948x1,868x832)x3
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - CompactModel
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
24 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
1
3/380~415/50
HP/HR
24
67.2
229,300
75.6
258,000
18.78
17.56
75
3.58
4.31
Propeller/BLDC
15.88
28.58
25.40
6.35
200
50 (40)
R410A
7.5x1+11x1
62
240x1+320x1
242x1+323x1
253x1+337x1
255x1+340x1
(880x1,703x765)x1+(1,200x1,703x765)x1
(948x1,868x832)x1+(1,268x1,868x832)x1
-5~43
-20~24
26 HP
1
1
3/380~415/50
HP/HR
26
72.8
248,400
81.9
279,500
21.40
19.80
75
3.40
4.14
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
7.5x1+11x1
62
240x1+320x1
242x1+323x1
253x1+337x1
255x1+340x1
(880x1,703x765)x1+(1,200x1,703x765)x1
(948x1,868x832)x1+(1,268x1,868x832)x1
-5~43
-20~24
28 HP
2
3/380~415/50
HP/HR
28
78.4
267,600
88.2
301,000
22.00
20.80
75
3.56
4.24
Propeller/BLDC
19.05
31.75
28.58
6.35
200
50 (40)
R410A
11x2
63
320x2
323x2
337x2
340x2
(1,200x1,703x765)x2
(1,268x1,868x832)x2
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - Compact
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
36 37
Outdoor U
nits
Specification | DVM PLUS III / HR
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
42 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
1
1
3/380~415/50
HP/HR
42
117.6
401,300
132.3
451,500
36.20
34.80
125
3.25
3.80
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x1+11x2
64
240x1+320x2
242x1+323x2
253x1+337x2
255x1+340x2
(880x1,703x765)x1+(1,200x1703x765)x2
(948x1,868x832)x1+(1,268x1748x832)x2
-5~43
-20~24
44 HP
2
1
3/380~415/50
HP/HR
44
123.2
420,500
138.6
473,000
36.80
35.80
125
3.35
3.87
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
11x3
65
320x3
323x3
337x3
340x3
(1,200x1,703x765)x3
(1,268x1,868x832)x3
-5~43
-20~24
46 HP
1
2
3/380~415/50
HP/HR
46
128.8
439,600
144.9
494,500
40.60
40.40
125
3.17
3.59
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
11x3
65
320x3
323x3
337x3
340x3
(1,200x1,703x765)x3
(1,268x1,868x832)x3
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - CompactModel
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
36 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
3
3/380~415/50
HP/HR
36
100.8
343,800
113.4
387,000
31.20
28.20
100
3.23
4.02
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x3
64
240x3
242x3
253x3
255x3
(880x1,703x765)x3
(948x1,868x832)x3
-5~43
-20~24
38 HP
2
1
3/380~415/50
HP/HR
38
106.4
363,000
119.7
408,500
31.80
29.20
125
3.35
4.10
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x2+11x1
64
240x2+320x1
242x2+323x1
253x2+337x1
255x2+340x1
(880x1,703x765)x2+(1,200x1,703x765)x1
(948x1,868x832)x2+(1,268x1,868x832)x1
-5~43
-20~24
40 HP
2
1
3/380~415/50
HP/HR
40
112.0
382,100
126.0
430,000
35.60
33.80
125
3.15
3.73
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
7.5x2+11x1
64
240x2+320x1
242x2+323x1
253x2+337x1
255x3+340x1
(880x1,703x765)x2+(1,200x1,703x765)x1
(948x1,868x832)x2+(1,268x1,868x832)x1
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - Compact
Outdoor Units - DVM PLUS III / HR 38 39
Outdoor U
nits
2008 SAMSUNG DVM Air Conditioners Outdoor Units
Specification | DVM PLUS III / HR
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
54 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
1
2
3/380~415/50
HP/HR
54
151.2
515,900
170.1
580,500
47.78
46.56
150
3.16
3.65
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x2+11x2
66
240x2+320x2
242x2+323x2
253x2+337x2
255x2+340x2
(880x1,703x765)x2+(1,200x1,703x765)x2
(948x1,868x832)x2+(1,268x1,868x832)x2
-5~43
-20~24
56 HP
1
1
2
3/380~415/50
HP/HR
56
156.8
535,100
176.4
602,000
48.38
47.56
150
3.24
3.71
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x1+11x3
66
240x1+320x3
242x1+323x3
253x1+337x3
255x1+340x3
(880x1,703x765)x1+(1,200x1,703x765)x3
(948x1,868x832)x1+(1,268x1,868x832)x3
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - CompactModel
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
48 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
3
3/380~415/50
HP/HR
48
134.4
458,700
151.2
516,000
44.40
45.00
125
3.03
3.36
Propeller/BLDC
19.05
38.10
31.75
6.35
200
50 (40)
R410A
11x3
65
320x3
323x3
337x3
340x3
(1,200x1,703x765)x3
(1,268x1,868x832)x3
-5~43
-20~24
50 HP
3
1
3/380~415/50
HP/HR
50
140.0
477,600
157.5
537,500
42.20
38.60
150
3.32
4.08
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x3+11x1
66
240x3+320x1
242x3+323x1
253x3+337x1
255x3+340x1
(880x1,703x765)x3+(1,200x1,703x765)x1
(948x1,868x832)x3+(1,268x1,868x832)x1
-5~43
-20~24
52 HP
3
1
3/380~415/50
HP/HR
52
145.6
496,700
163.8
559,000
46.00
43.20
150
3.17
3.79
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x3+11x1
66
240x3+320x1
242x3+323x1
253x3+337x1
255x3+340x1
(880x1,703x765)x3+(1,200x1,703x765)x1
(948x1,868x832)x3+(1,268x1,868x832)x1
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.
Module Type - Compact
Outdoor Units - DVM PLUS III / HR
2008 SAMSUNG DVM Air Conditioners Outdoor Units
40 41
Outdoor U
nits
Specification | DVM PLUS III / HR
Model
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
62 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
3
3/380~415/50
HP/HR
62
173.6
592,500
195.3
666,500
55.40
55.40
175
3.13
3.53
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
11x4
67
320x4
323x4
337x4
340x4
(1,200x1,703x765)x4
(1,268x1,868x832)x4
-5~43
-20~24
64 HP
4
3/380~415/50
HP/HR
64
179.2
611,600
201.6
688,000
59.20
60.00
175
3.03
3.36
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
11x4
67
320x4
323x4
337x4
340x4
(1,200x1,703x765)x4
(1,268x1,868x832)x4
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
- Specifications are subject to change without prior notice for product improvement.
Module Type - CompactModel
Power supply
Mode *1)
Performance
Power
COP
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating
Temp. Range
58 HP
Basic
Horse Power
Capacity
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type/Control
Liquid
Gas
Discharge Gas (DVM PLUS III HR)
Oil (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
RVXVRT080GE
RVXVRT100GE
RVXVRT120GE
RVXVRT140GE
RVXVRT160GE
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
kW
kW
A
-
-
-
Ø,mm
Ø,mm
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
kg
kg
mm
mm
ºC
ºC
RVXVHT080GE /
RVXVHT100GE /
RVXVHT120GE /
RVXVHT140GE /
RVXVHT160GE /
Cooling *2)
Heating *3)
Cooling
Heating
Max.Length
Max.Height
DVM PLUS III
DVM PLUS III HR
DVM PLUS III
DVM PLUS III HR
1
3
3/380~415/50
HP/HR
58
162.4
554,200
182.7
623,500
52.18
52.16
150
3.11
3.50
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x1+11x3
66
240x1+320x3
242x1+323x3
253x1+337x3
255x1+340x3
(880x1,703x765)x1+(1,200x1,703x765)x3
(948x1,868x832)x1+(1,268x1,868x832)x3
-5~43
-20~24
60 HP
1
3
3/380~415/50
HP/HR
60
168.0
573,300
189.0
645,000
54.80
54.40
175
3.07
3.47
Propeller/BLDC
22.23
44.50
38.10
6.35
200
50 (40)
R410A
7.5x1+11x3
67
240x1+320x3
242x1+323x3
253x1+337x3
255x1+340x3
(880x1,703x765)x1+(1,200x1,703x765)x3
(948x1,868x832)x1+(1,268x1,868x832)x3
-5~43
-20~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
- Specifications are subject to change without prior notice for product improvement.
Module Type - Compact
Outdoor Units - Mini DVM
2008 SAMSUNG DVM Air Conditioners Outdoor Units
42 43
Outdoor U
nits
Mini DVMMini DVM is a highly compact and reliable unit for luxurious residentialbuildings or light commercial applications with a Digital Scroll Compressorwhich ensures high energy efficiency.
Slim and Flexible
High Energy EfficiencyDigital Scroll compressor offers very high cooling and heating COP.
Compact DesignMini DVM offers easy installation with its slim and compactdesign saving installation space.
• High energy-efficient system
• Compact outdoor unit
• Wide Compatibility
• Ø1, 220~240V, 50Hz (4/5HP)• Ø3, 380~415V, 50Hz (5/6HP)
4
CO
P
3
2
1
04HP 5HP 6HP
3.33
4.05
3.04
3.87
3.053.73
Dimension
Capacity
Volume (m3)
Foot print (m2)
Height (mm)
Weight (kg)
4Hp
0.39
0.35
1,128
124
5Hp
0.39
0.35
1,128
125
6Hp
0.39
0.35
1,128
125
Various Indoor UnitsMini DVM can be combined up to 9 stylish indoor unitsblending with any interior design.
Easy MaintenanceMini DVM makes it possible to control compressor, PCB, EEVon front panel allowing simple and effortless maintenance. It is possible to react promptly to errors because they are displayed on LED of the outdoor units by error codes.
Cooling
Heating
Wide CompatibilityMini DVM can be controlled by a control solution which is
the same with that of DVM PLUS III and FJM
High ReliabilityMini DVM is highly reliable with adopted Digital ScrollCompressor which can be controlled easily.Because Digital Scroll Compressor needs just one controlPCB, it achieves simple structure and high reliability.
Outdoor Units - Mini DVM
2008 SAMSUNG DVM Air Conditioners Outdoor Units
44 45
Outdoor U
nits
Specification | Mini DVM
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
- Specifications are subject to change without prior notice for product improvement.
Power Supply
Mode *1)
Performance
Power
COP
Compressor
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating Temp.
Range
RVXMHF040EA
Horse Power
Capacity
Nominal Running
Current
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type
Piston Displacement
Output
Lubricant
Type
Output
Airflow Rate
Liquid (Flare)
Gas (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure(Cooling/Heating) *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
A
A
kW
kW
A
-
-
-
cc/Rev
kW
-
cc
-
W
m3/min
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
mm
mm
ºC
ºC
Cooling *2)
Heating *3)
Cooling
Heating
Cooling
Heating
Type
Charging
Max. Length
Max. Height
1/220~240/50
HP
4
12.5
42,600
14.5
49,400
19.0
18.0
3.75
3.58
30
3.33
4.05
Digital Scroll
58.10
-
3MAF POE
1,893
Propeller
200x2
105
9.52
15.88
100
30
R410A
5.5
55/56
124
132
932x1,128x375
1,091x1,286x472
-5~43
-20~24
RVXMHF050EA
1/220~240/50
HP
5
14.0
47,700
16.0
54,500
22.4
20.1
4.60
4.13
30
3.04
3.87
Digital Scroll
62.98
-
3MAF POE
1,893
Propeller
200x2
105
9.52
15.88
100
30
R410A
5.5
55/57
125
133
932x1,128x375
1,091x1,286x472
-5~43
-20~24
RVXMHF050GA
3/380~415/50
HP
5
14.0
47,700
16.0
45,500
8.5
7.8
4.61
4.13
20
3.04
3.87
Digital Scroll
67.13
-
3MAF POE
1,893
Propeller
200x2
105
9.52
15.88
100
30
R410A
5.5
55/57
125
133
932x1,128x375
1,091x1,286x472
-5~43
-20~24
RVXMHF060GA
3/380~415/50
HP
6
16.0
54,500
18.0
61,400
11.0
9.9
5.24
4.82
20
3.05
3.73
Digital Scroll
77.20
-
3MAF POE
1,774
Propeller
220x2
105
9.52
15.88
100
30
R410A
5.5
57/60
125
133
932x1,128x375
1,091x1,286x472
-5~43
-15~24
Model
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
- Specifications are subject to change without prior notice for product improvement.
Power Supply
Mode *1)
Performance
Power
COP
Compressor
Fan
Piping
Connections
Refrigerant
Sound
Set Size
Operating Temp.
Range
Horse Power
Capacity
Nominal Running
Current
Nominal Input
Circuit Breaker (MCCB/ELB)
Cooling
Heating
Type
Piston Displacement
Output
Lubricant
Type
Output
Airflow Rate
Liquid (Flare)
Gas (Flare)
Installation
Limitation
Type
Factory Charging
Sound Pressure(Cooling/Heating) *4)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Cooling
Heating
Ø/V/Hz
-
HP
kW
Btu/h
kW
Btu/h
A
A
kW
kW
A
-
-
-
cc/Rev
kW
-
cc
-
W
m3/min
Ø,mm
Ø,mm
m
m
-
kg
dB(A)
kg
kg
mm
mm
ºC
ºC
Cooling *2)
Heating *3)
Cooling
Heating
Cooling
Heating
Type
Charging
Max. Length
Max. Height
Model RVMMH120EZ
1/220~240/50
HP
4
12.0
40,900
14.0
47,700
18.0
18.0
3.56
3.58
-
3.37
3.91
Digital Scroll
-
-
SONTEX 200LT
-
Propeller
-
95
9.52
19.05
70
30
R22
6.5
55/56
124
132
932x1,128x375
1,091x1,286x472
-5~43
-15~24
RVMMH120GZ
3/380~415/50
HP
4
12.0
40,900
14.0
47,700
6.5
6.4
3.80
3.58
-
3.16
3.91
Digital Scroll
82.59
-
SONTEX 200LT
1,890
Propeller
-
95
9.52
19.05
70
30
R22
6.5
55/59
124
132
932x1,128x375
1,091x1,286x472
-5~43
-15~24
RVMMH140EZ
1/220~240/50
HP
5
14.0
47,700
16.0
54,500
22.5
21.5
4.65
4.50
-
3.01
3.56
Digital Scroll
93.03
-
SONTEX 200LT
1,890
Propeller
-
95
9.52
19.05
70
30
R22
6.5
55/57
125
133
932x1,128x375
1,091x1,286x472
-5~43
-15~24
RVMMH140GZ
3/380~415/50
HP
5
14.0
47,700
16.0
54,550
8.5
8.0
4.90
4.30
-
2.86
3.72
Digital Scroll
98.06
4.2
SONTEX 200LT
1,890
Propeller
-
95
9.52
19.05
70
30
R22
6.5
55/57
125
133
932x1,128x375
1,091x1,286x472
-5~43
-15~24
RVMMH160GZ
3/380~415/50
HP
6
16.0
54,500
18.0
61,400
10.2
9.9
5.55
5.20
-
2.89
3.46
Digital Scroll
107.80
-
SONTEX 200LT
1,890
Propeller
-
95
9.52
19.05
70
30
R22
6.5
57/60
125
133
932x1,128x375
1,091x1,286x472
-5~43
-15~24
Outdoor Units - Free Joint Multi
2008 SAMSUNG DVM Air Conditioners Outdoor Units
46 47
Outdoor U
nits
Free Joint MultiFree Joint Multi supports various combinations of indoor and outdoorunits, providing variety of choices and flexible installation. Therefore,Free Joint Multi is the best solution for residential buildings seekingflexible, efficient and reliable air conditioning system.
High Energy Efficiency
BLDC(Twin Rotary) Compressor
Highly Efficient BLDC Motor
- Creative motor core design- High density neodymium magnet- Concentrated type stator
Extremely Low Vibration
- Twin eccentric cams- 2 balance weights
Highly Stable Moving Parts
- Optimal material matching rollers andvanes
- Highly robust bearings- Coated vane- Coated shaft
Wide Operation Range ofOutdoor Temperature
High Performance
TBR Sine-Wave CompressorNew FJM models have applied the twin BLDC compressor with highlystable moving parts which reduced torque variation by 70% comparedto the conventional single BLDC compressor.
Conventional New
Felt StructureNew felt has been selected to reduce the noise coming out of the compressor. Double layered felt structure absorbs noise by two times andfelt is also covering top of the compressor to reduce the noise even more.
Sine Wave ControllerAll the FJM models have adopted this newly developed Sine Wave Controller. No nipple in the current wavemakes soft acoustic quality and reduces noise.
BLDC Compressor is applied on all FJM outdoor models. Current Wave
Torque Ripple
Current Wave
Torque Ripple
Current Wave
Torque Ripple
Current Wave
Torque Ripple
Conventional Square Wave Controller New Sine Wave Controller
Outdoor Units - Free Joint Multi 48 49
2008 SAMSUNG DVM Air Conditioners Outdoor Units
Outdoor U
nits
Indoor Unit
Model
MH026FBEA
MH035FBEA
MH052FBEA
MH020FVEA
MH026FVEA
MH035FVEA
MH052FVEA
MH020FNEA
MH026FNEA
MH035FNEA
MH052FNEA
MH026FJEA
MH035FJEA
MH026FKEA
MH035FKEA
MH030FMEA
MH035FMEA
MH052FMEA
MH026FEEA
MH035FEEA
MH052FUEA
Line upAvailable Outdoor Units
Combination Table
MH040FXEA2B4.0kW
2 Unit
MH050FXEA2B5.0kW
2 Unit
MH060FXEA3B6.0kW
3 Unit
MH070FXEA4B7.0kW
4 Unit
MH080FXE4B8.0kW
4 Unit
Outdoor Unit
MH040FXEA2B MH050FXEA2B MH060FXEA3B MH070FXEA4B MH080FXEA4B
Power Supply
Mode *1)
Max number of connectable indoor units
Performance
Sound
Power
Compressor
Refrigerant
Fan
Set Size
Piping
Connections
Operating
Temp. Range
MH040FXEA2B
Horse Power
Capacity
Sound Pressure (Cooling/Heating) *4)
Running
Current
Nominal Input
Circuit Breaker(MCCB/ELB)
Type
Piston Displacement
Output
Lubricant
Type
Factory Charging
Type
Output
Airflow Rate
Net Weight
Shipping Weight
Net Dimensions(WxHxD)
Shipping Dimensions(WxDxH)
Liquid(Flare)
Gas(Flare)
Installation
Limitation
Cooling
Heating
Ø/V/Hz
-
-
HP
kW
Btu/h
kW
Btu/h
dB(A)
A
A
W
W
A
-
cc/Rev
kW
-
cc
-
kg
-
W
m3/min
kg
kg
mm
mm
Ø,mm
Ø,mm
m
m
ºC
ºC
Cooling *2)
Heating *3)
Cooling
Heating
Cooling
Heating
Type
Charging
Max. Length
Max. Height
1/220~240/50
HP
2
1.5
3.9
13,307
4.4
15,013
47/48
5.2
5.1
1,140
1,120
9
TWIN BLDC INV.
19.52
5.86
POE
700
R410A
1.3
Propeller
25
25.4
41
44
790X548X285
926X630X382
6.35X2
9.52X2
30
15
-5~43
-15~24
MH050FXEA2B
1/220~240/50
HP
2
1.8
5.0
17,060
5.7
19,448
48/50
6.1
6.4
1,330
1,400
13.5
TWIN BLDC INV.
19.52
5.86
POE
700
R410A
2
Propeller
40
32.9
53
57
880X638X310
1,023X695X413
6.35X2
9.52X1+12.70X1
30
15
-5~43
-15~24
MH060FXEA3B
1/220~240/50
HP
3
2.0
5.9
20,131
6.3
21,496
49/50
7.3
6.4
1,600
1,400
14.5
TWIN BLDC INV.
19.52
5.86
POE
700
R410A
2.2
Propeller
130
41
59
63
880X798X310
1,023X889X413
6.35X3
9.52X2+12.70X1
45
15
-5~43
-15~24
MH070FXEA4B*5)
1/220~240/50
HP
4
2.5
7.0
23,884
8.6
29,343
50/51
8.7
9.2
1,900
2,000
16.6
TWIN BLDC INV.
25.18
7.77
POE
700
R410A
2.8
Propeller
130
44.8
65
70
880X798X310
1,023X889X413
6.35X4
9.52X2+12.70X2
70
15
-5~43
-15~24
MH080FXEA4B*5)
1/220~240/50
HP
4
3.0
8.0
27,296
9.3
31,732
51/51
10.5
10.1
2,300
2,200
16.6
TWIN BLDC INV.
25.18
7.77
POE
700
R410A
2.8
Propeller
130
45.4
65
70
880X798X310
1,023X889X413
6.35X4
9.52X2+12.70X2
70
15
-5~43
-15~24
Notes
*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Model
Specification | Outdoor Units
Specification | Indoor Units
Notes*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power SupplyMode *1)
Performance
SoundPower
Piping
Set Size
Accessories
Cooling *2)
Heating *3)
Sound Pressure (High/Low) *4)
Fan
Running CurrentPower InputConnecting Pipe
Net WeightShipping WeightNet Dimensions (WxHxD)Shipping Dimensions (WxHxD)PanelFilterDrain Pump
Model
Ø/V/Hz
kWBtu/hkWBtu/hdB(A)-m3/min
mmAq
AWØ,mmØ,mmØ,mmkgkgmmmm---
MH020FNEA MH026FNEA MH035FNEA MH052FNEA
1/220~240/50HP2.6
8,8712.9
9,89532/23 *5)
Cross Flow Fan8.31/8.56
-
0.18/0.1830/306.359.52 ID 187.89.4
825X285X189900X349X252
---
1/220~240/50HP3.5
11,9423.8
12,96636/23 *5)
Cross Flow Fan9.54/9.93
-
0.19/0.1935/356.359.52 ID 187.8 9.4
825X285X189900X349X252
---
1/220~240/50HP5.2
17,7425.6
19,10740/30 *5)
Cross Flow Fan13.21/14.22
-
0.3/0.350/506.3512.70 ID 1813.0 16.0
1,099X315X2171,137X377X299
---
1/220~240/50HP2
6,8242.2
7,50632/23 *5)
Cross Flow Fan7.73/8
-
0.18/0.1830/306.359.52 ID 187.89.4
825X285X189900X349X252
---
TypeAirflow Rate(Cool/Heat)External StaticPressure(Standard/High)Cooling/HeatingCooling/HeatingLiquid(Flare)Gas(Flare)Drain
Neo Forte
Power SupplyMode *1)
Performance
SoundPower
Piping
Set Size
Accessories
Cooling *2)
Heating *3)
Sound Pressure (High/Low) *4)
Fan
Running CurrentPower InputConnecting Pipe
Net WeightShipping WeightNet Dimensions (WxHxD)Shipping Dimensions (WxHxD)PanelFilterDrain Pump
Model
Ø/V/Hz-kWBtu/hkWBtu/hdB(A)-m3/min
mmAq
AWØ,mmØ,mmØ,mmkgkgmmmm---
MH020FVEA MH026FVEA MH035FVEA MH052FVEA
1/220~240/50HP2.6
8,8712.9
9,89531/21 *5)
Cross Flow Fan8.5/8.3
-
0.18/0.1830/306.359.52 ID 188.5 11.5
825X285X189900X349X252
---
1/220~240/50HP3.5
11,9423.8
12,96635/21 *5)
Cross Flow Fan10/10.4
-
0.19/0.1935/356.359.52 ID 188.5 11.5
825X285X189900X349X252
---
1/220~240/50HP5.2
17,7425.6
19,10740/30 *5)
Cross Flow Fan14.8/14.8
-
0.3/0.350/506.3512.70 ID 1812.0 15.0
1,065X298X2141,137X377X299
---
1/220~240/50HP2
6,8242.2
7,50631/21 *5)
Cross Flow Fan7.5/8.1
-
0.18/0.1830/306.359.52 ID 188.5 11.5
825X285X189900X349X252
---
TypeAirflow Rate(Cool/Heat)External StaticPressure(Standard/High)Cooling/HeatingCooling/HeatingLiquid(Flare)Gas(Flare)Drain
Vivace
Notes*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Outdoor Units - Free Joint Multi 50 51
Outdoor U
nits
2008 SAMSUNG DVM Air Conditioners Outdoor Units
1Way Cassette
MB
Power SupplyMode *1)
Performance
SoundPower
Piping
Set Size
Accessories
Cooling *2)
Heating *3)
Sound Pressure (High/Low) *4)
Fan
Running CurrentPower InputConnecting Pipe
Net WeightShipping WeightNet Dimensions (WxHxD)Shipping Dimensions (WxHxD)PanelFilterDrain Pump
Model
Ø/V/Hz-kWBtu/hkWBtu/hdB(A)-m3/min
mmAq
AWØ,mmØ,mmØ,mmkgkgmmmm---
MH026FBEA MH035FBEA MH052FBEA
1/220~240/50HP3.5
11,9423.8
12,96635/21 *5)
Cross Flow Fan9.16/9.46
-
0.19/0.1935/356.359.52 ID 1810.2 11.5
900X304X185963X349X247
---
1/220~240/50HP5.2
17,7425.6
19,10740/30 *5)
Cross Flow Fan14.98/14.49
-
0.3/0.350/506.3512.70 ID 1813.016.0
1,100X307X2251,157X381X292
---
1/220~240/50HP2.6
8,8712.9
9,89531/20 *5)
Cross Flow Fan8.14/8.23
-
0.18/0.1830/306.359.52 ID 1810.2 11.5
900X304X185963X349X247
---
TypeAirflow Rate(Cool/Heat)External StaticPressure(Standard/High)Cooling/HeatingCooling/HeatingLiquid(Flare)Gas(Flare)Drain
Console
Power SupplyMode *1)
Performance
SoundPower
Piping
Set Size
Accessories
Cooling *2)
Heating *3)
Sound Pressure (High/Low) *4)
Fan
Running CurrentPower InputConnecting Pipe
Net WeightShipping WeightNet Dimensions (WxHxD)Shipping Dimensions (WxHxD)PanelFilterDrain Pump
Model
Ø/V/Hz
kWBtu/hkWBtu/hdB(A)-m3/min
mmAq
AWØ,mmØ,mmØ,mmkgkgmmmm---
MH026FJEA MH035FJEA
1/220~240/50HP3.5
11,9423.8
12,966-
Turbo Fan-
-
--
6.359.52
-14.5 18.5
720x620x199810x710x295
---
1/220~240/50HP2.6
8,8712.9
9,895-
Turbo Fan-
-
--
6.359.52
-14.5 18.5
720x620x199810x710x295
---
TypeAirflow Rate(Cool/Heat)External StaticPressure(Standard/High)Cooling/HeatingCooling/HeatingLiquid(Flare)Gas(Flare)Drain
MH026FKEA MH035FKEA
1/220~240/50HP3.5
11,9003.8
12,90038/35
Cross Flow Fan7.5/8.0
-
0.23/0.2345/456.359.52
VP:20 (OD:26, ID:20)15.0 18.0
970x180x3901,168x302x467Option (P1SMA)
Built-inBuilt-in
1/220~240/50HP2.6
8,8002.9
9,80036/33
Cross Flow Fan7.0/7.5
-
0.20/0.2040/406.359.52
VP:20 (OD:26, ID:20)15.0 18.0
970x180x3901,168x302x467Option (P1SMA)
Built-inBuilt-in
Specification | Indoor Units
Notes*1) Mode - HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Outdoor Units - Free Joint Multi 52 53
Outdoor U
nits
2008 SAMSUNG DVM Air Conditioners Outdoor Units
Mini 4Way Cassette
Power SupplyMode *1)
Performance
Soundpower
Piping
Set Size
Accessories
Cooling *2)
Heating *3)
Sound Pressure (High/Low) *4)
Fan
Running CurrentPower InputConnecting Pipe
Net WeightShipping WeightNet Dimensions (WxHxD)Shipping Dimensions (WxHxD)PanelFilterDrain Pump
Model
Ø/V/Hz
kWBtu/hkWBtu/hdB(A)-m3/min
mmAq
AWØ,mmØ,mmØ,mmkgkgmmmm---
MH030FMEA MH035FMEA MH052FMEA
1/220~240/50HP3.5
11,9003.8
12,90040/37
Turbo Fan10.8/11.7
-
0.37/0.3785/856.359.52
VP:25 (OD:32, ID:25)17.0 20.0
575x242x575660x310x635
PMSMABuilt-inBuilt-in
1/220~240/50HP5.2
17,7005.6
19,10044/40
Turbo Fan12.1/13.6
-
0.52/0.52120/120
6.3512.70
VP:25 (OD:32, ID:25)17.0 20.0
575x242x575660x310x635
PMSMABuilt-inBuilt-in
1/220~240/50HP3.0
10,2003.4
11,60040/37
Turbo Fan10.8/11.7
-
0.37/0.3785/856.359.52
VP:25 (OD:32, ID:25)17.0 20.0
575x242x575660x310x635
PMSMABuilt-inBuilt-in
TypeAirflow Rate(Cool/Heat)External StaticPressure(Standard/High)Cooling/HeatingCooling/HeatingLiquid(Flare)Gas(Flare)Drain
Specification | Pack Multi Split (Forte Type)
Capacity(Cooling/Heating)
Energy Efficiency
Moisture removalAirflow Rate(Max.)
Sound Pressure(Max.)
Power SupplyPower Input(Cooling/Heating)
Running Current(Cooling/Heating)
Net Dimensions(WxHxD)
Net Weight
Shipping Weight
Loading Q’ty(40ft)
SVC Valve
Piping Length
Piping HeightQuantity of RefrigerantAdditional Refrigerant
Good Sleep IISilver Coated Health System
Pure and Clean Air
Operating Mode
Convenience
Etc.Operating Temp. Range
1Unit(A)1Unit(B or C)2Unit[A+(B or C)]1Unit(A)
1Unit(B or C)
2Unit[A+(B or C)]
1Unit(A)1Unit(B or C)Indoor (A-Unit)Indoor (B-Unit or C-Unit)Outdoor Unit
1Unit(A)1Unit(B or C)2Unit[A+(B or C)]1Unit(A)1Unit(B or C)2Unit[A+(B or C)]
Indoor (A-Unit)Indoor (B-Unit or C-Unit)Outdoor UnitIndoor (A-Unit)Indoor (B-Unit or C-Unit)Outdoor UnitIndoor (A-Unit)Indoor (B-Unit or C-Unit)Outdoor Unit
Liquid(A)Gas(A)Liquid(B or C)Gas(B or C)StandardMaxMax
Silver Coated FilterSilver Coated EvaporatorDNA FilterPure Filter(HAF Filter)Catechin FilterDeodorizing FilterDigital i PlusDehumidificationTurbo ModeTimerEnergy Saving ModeAuto RestartAuto ChangeoverAuto WindAirflow Control Steps(Cool/Fan)Air Direction Control(Up/Down)Air Direction Control(Left/Right)Auto GrilleRemote ControllerAuto Clean(Self cleaning)Compressor TypeCoolingHeating
Outdoor unit
Indoor unit
MH18VF1XMH18VF1-09MH18VF1-09
Model
Electrical Data
Dimensions and Loading Q’ty
Technical Information
Features
kWkWkWEERCOPEERCOPEERCOPl/hm3/minm3/mindB(A)dB(A)dB(A)
Ø/V/HzWWWAAA
mmmmmmkgkgkgkgkgkgW/O PipeW/Pipe
Ø,mmØ,mmØ,mmØ,mmmmmkgg/m
°C°C
2.6/2.92.6/2.93.9/4.4
3.47 3.44 3.47 3.443.363.791.68.38.34343
51/52
1/220-240/50750/900750/900
1,160/1,1603.4/4.13.4/4.15.3/5.3
825x285x189825x285x189548x790x285
8.48.441
10.610.644153
-
6.359.526.359.527.5307.51.310
●
●
●
●
●
●
●
●
●
●
4/3AUTO
MANUAL
●
Rotary(BLDC)-5~43-15~24
MH19VF1XMH19VF1-07MH19VF1-12
2.1/2.43.5/3.83.9/4.4
3.893.003.023.283.363.791.67.739.54343
51/52
1/220-240/50540/800
1,160/1,1601,160/1,160
2.5/3.75.3/5.35.3/5.3
825x285x189825x285x189548x790x285
8.48.441
10.610.644153
-
6.359.526.359.527.5307.51.310
●
●
●
●
●
●
●
●
●
●
4/3AUTO
MANUAL
●
Rotary(BLDC)-5~43
-15~24
Power SupplyMode *1)
Performance
Soundpower
Piping
Set Size
Accessories
Cooling *2)
Heating *3)
Sound Pressure (High/Low) *4)
Fan
Running CurrentPower InputConnecting Pipe
Net WeightShipping WeightNet Dimensions (WxHxD)Shipping Dimensions (WxHxD)PanelFilterDrain Pump
Model
Ø/V/Hz
kWBtu/hkWBtu/hdB(A)-m3/min
mmAq
AWØ,mmØ,mmØ,mmkgkgmmmm---
TypeAirflow Rate(Cool/Heat)External StaticPressure(Standard/High)Cooling/HeatingCooling/HeatingLiquid(Flare)Gas(Flare)Drain
MH026FEEA MH035FEEA
1/220~240/50HP3.5
11,9003.8
12,90032/27
Sirocco Fan9.8/10.3
2/4
0.4/0.480/806.350.92
VP:25 (OD:32, ID:25)26.0 31.0
900x199x6001,133x333x722
-Built-in
MDP-E075SEE
1/220~240/50HP2.6
8,8002.9
9,80031/26
Sirocco Fan8.6/9.0
2/4
0.4/0.480/806.359.52
VP:25 (OD:32, ID:25)26.0 31.0
900x199x6001,133x333x722
-Built-in
MDP-E075SEE
MH052FUEA
1/220~240/50HP5.2
17,7425.6
19,107-
Sirocco Fan-
6/10
--
6.3512.70
-29.5 34.5
900x242x4801,146x363x584
--
MSP-M075SGU3
Slim Duct MSP Duct
Outdoor Units - Free Joint Multi 54 55
Outdoor U
nits
2008 SAMSUNG DVM Air Conditioners Outdoor Units
MH040FXEA2BIndoor Unit Combination
Numberof Unit
1 Unit
2 Unit
2 Unit
Cooling Capacity(W) Capacity CurrentPower Consumption
ACOP EG
20002600350020002000200026002600
20002600
B
---
20002600350026003500
35002600
C
--------
--
D
--------
--
%
51%67%90%103%118%141%133%156%
141%133%
Total Total
20002600350040004600550052006100
55005200
A
21002600350019501696141819501662
14181950
B
---
19502204248219502238
24821950
C
--------
--
Min.W
12801280130013501500150015001500
15001500
Nom.W
21002600350039003900390039003900
39003900
Max.Ml
25203120420042004200420042004200
42004200
Min.W
400400400420420440440440
440440
Nom.W
540750116011601140116011601140
11601160
Max.W
630880124012501250125012501250
12501250
D
--------
--
21002600350039003900390039003900
39003900
Min.A
2.22.22.22.32.32.42.42.4
2.42.4
Nom.A
2.53.45.35.35.25.35.35.2
5.35.3
Max.A
2.94
5.75.75.75.75.75.7
5.75.7
3.893.473.023.363.423.363.363.42
3.363.36
AABAAAAA
AA
Capacity Combination
Multi Split (Wall Mounted Type)
Indoor Unit CombinationNumberof Unit
1 Unit
2 Unit
2 Unit
Heating Capacity(W) Capacity CurrentPower Consumption
ACOP EG
22002900380022002200220029002900
22002900
B
---
22002900380029003800
38002900
C
--------
--
D
--------
--
%
50%66%86%100%116%136%132%152%
136%132%
Total Total
22002900380044005100600058006700
60005800
A
24003100380022001898161322001904
16132200
B
---
22002502278722002496
27872200
C
--------
--
Min.W
13001300130015001500150015001500
15001500
Nom.W
24003100380044004400440044004400
44004400
Max.Ml
29903450437047004700470047004700
47004700
Min.W
280280280300300300300300
300300
Nom.W
800900116011601160116011601120
11601160
Max.W
9101080142013901420149014901490
14901490
D
--------
--
24003100380044004400440044004400
44004400
Min.A
1.51.51.51.61.61.61.61.6
1.61.6
Nom.A
3.74.15.35.35.35.35.35.1
5.35.3
Max.A
4.24.96.56.46.56.86.86.8
6.86.8
3.003.443.283.793.793.793.793.93
3.793.79
DBCAAAAA
AA
Multi Split (Wall Mounted Type)
MH050FXEA2BIndoor Unit Combination
Numberof Unit
1 Unit
2 Unit
Cooling Capacity(W) Capacity CurrentPower Consumption
ACOP EG
200026003500520020002000200020002600260026003500
B
----
20002600350052002600350052003500
C
------------
D
------------
%
40%52%70%104%80%92%110%144%104%122%156%140%
Total Total
200026003500520040004600550072005200610078007000
A
240026003500500020002000181813892500213116672500
B
----
20002600318236112500286933332500
C
------------
Min.W
128012801280130013501350135015001500150015001500
Nom.W
240026003500500040004600500050005000500050005000
Max.Ml
288031204200520048005200540054005400540054005400
Min.W
400400400400420420420440440440440440
Nom.W
7308001090166012451430149013801500150013301500
Max.W
8809601310174014901720178018001780178018001780
D
------------
240026003500500040004600500050005000500050005000
Min.A
1.91.91.91.9222
2.12.12.12.12.1
Nom.A
3.33.75
7.65.76.56.86.36.96.96.16.9
Max.A
44.468
6.87.98.18.28.18.18.28.1
3.293.253.213.013.213.223.363.623.333.333.763.33
AAABAAAAAAAA
CoolingCooling
Cooling
Heating
Heating
Heating
MH060FXEA3BIndoor Unit Combination
Numberof Unit
1 Unit
2 Unit
3 Unit
Cooling Capacity(W) Capacity CurrentPower Consumption
ACOP EG
2000
2600
3500
5200
2000
2000
2000
2000
2600
2600
2600
3500
3500
2000
2000
2000
2000
2000
2000
2600
2600
B
-
-
-
-
2000
2600
3500
5200
2600
3500
5200
3500
5200
2000
2000
2000
2600
2600
3500
2600
2600
C
-
-
-
-
-
-
-
-
-
-
-
-
-
2000
2600
3500
2600
3500
3500
2600
3500
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
%
34%
44%
59%
88%
68%
78%
93%
122%
88%
103%
132%
119%
147%
102%
112%
127%
122%
137%
153%
132%
147%
Total Total
2000
2600
3500
5200
4000
4600
5500
7200
5200
6100
7800
7000
8700
6000
6600
7500
7200
8100
9000
7800
8700
A
2400
2600
3500
5200
2000
2000
1909
1528
2600
2259
1967
2725
2374
1760
1636
1573
1528
1457
1311
1967
1763
B
-
-
-
-
2000
2600
3341
3972
2600
3041
3933
2725
3526
1760
1636
1573
1986
1894
2294
1967
1763
C
-
-
-
-
-
-
-
-
-
-
-
-
-
1760
2127
2753
1986
2549
2294
1967
2374
Min.W
1280
1280
1280
1300
1300
1300
1300
1380
1300
1300
1380
1300
1380
1500
1500
1500
1500
1500
1500
1500
1500
Nom.W
2400
2600
3500
5200
4000
4600
5250
5500
5200
5300
5900
5450
5900
5280
5400
5900
5500
5900
5900
5900
5900
Max.Ml
2880
3120
4200
5800
4800
5520
6290
6600
5800
6400
6800
6560
6800
6380
6490
6800
6600
6800
6800
6800
6800
Min.W
400
400
400
400
420
420
430
430
420
430
430
430
440
430
430
440
430
440
440
440
440
Nom.W
730
790
1070
1620
1240
1410
1550
1580
1620
1550
1610
1570
1620
1550
1560
1610
1580
1610
1610
1600
1600
Max.W
930
1010
1370
1900
1480
1680
1820
1850
1800
1840
1880
1850
1880
1840
1850
1880
1850
1880
1880
1880
1880
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2400
2600
3500
5200
4000
4600
5250
5500
5200
5300
5900
5450
5900
5280
5400
5900
5500
5900
5900
5900
5900
Min.A
2.2
2.2
2.2
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.4
2.3
2.3
2.4
2.3
2.4
2.4
2.4
2.4
Nom.A
3.3
3.6
4.9
7.4
5.7
6.5
7.1
7.2
7.4
7.1
7.4
7.2
7.4
7.1
7.1
7.4
7.2
7.4
7.4
7.3
7.3
Max.A
4.3
4.6
6.3
8.7
6.8
7.7
8.3
8.5
8.2
8.4
8.6
8.5
8.6
8.4
8.5
8.6
8.5
8.6
8.6
8.6
8.6
3.29
3.29
3.27
3.21
3.23
3.26
3.39
3.48
3.21
3.42
3.66
3.47
3.64
3.41
3.46
3.66
3.48
3.66
3.66
3.69
3.69
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Indoor Unit CombinationNumberof Unit
1 Unit
2 Unit
3 Unit
Heating Capacity(W) Capacity CurrentPower Consumption
ACOP EG
2200
2900
3800
5600
2200
2200
2200
2200
2900
2900
2900
3800
3800
2200
2200
2200
2200
2200
2200
2900
2900
B
-
-
-
-
2200
2900
3800
5600
2900
3800
5600
3800
5600
2200
2200
2200
2900
2900
3800
2900
2900
C
-
-
-
-
-
-
-
-
-
-
-
-
-
2200
2900
3800
2900
3800
3800
2900
3800
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
%
35%
46%
60%
89%
70%
81%
95%
124%
92%
106%
135%
121%
149%
105%
116%
130%
127%
141%
156%
138%
152%
Total Total
2200
2900
3800
5600
4400
5100
6000
7800
5800
6700
8500
7600
9400
6600
7300
8200
8000
8900
9800
8700
9600
A
2500
2900
3800
5600
2200
2200
2053
1692
2900
2510
2149
2950
2547
1933
1778
1690
1650
1557
1414
2100
1903
B
-
-
-
-
2200
2900
3547
4308
2900
3290
4151
2950
3753
1933
1778
1690
2175
2053
2443
2100
1903
C
-
-
-
-
-
-
-
-
-
-
-
-
-
1933
2344
2920
2175
2690
2443
2100
2494
Min.W
1300
1300
1300
1350
1400
1400
1500
1500
1400
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
Nom.W
2500
2900
3800
5600
4400
5100
5600
6000
5800
5800
6300
5900
6300
5800
5900
6300
6000
6300
6300
6300
6300
Max.Ml
2990
3340
4370
6300
5060
5870
6440
6900
6300
6770
7300
6880
7300
6760
6840
7300
6920
7300
7300
7300
7300
Min.W
350
350
350
350
350
350
350
350
350
350
350
350
350
350
350
350
350
350
350
350
350
Nom.W
880
1030
1350
1820
1220
1490
1640
1660
1700
1700
1740
1730
1740
1590
1610
1660
1590
1630
1560
1650
1400
Max.W
1110
1270
1660
1920
1510
1830
1860
1860
1910
1900
1830
1860
1830
1840
1840
1830
1840
1830
1830
1830
1830
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2500
2900
3800
5600
4400
5100
5600
6000
5800
5800
6300
5900
6300
5800
5900
6300
6000
6300
6300
6300
6300
Min.A
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
Nom.A
4
4.7
6.2
8.3
5.6
6.8
7.5
7.6
7.8
7.8
8
7.9
8
7.3
7.4
7.6
7.3
7.5
7.1
7.6
6.4
Max.A
5.1
5.8
7.6
8.8
6.9
8.4
8.5
8.5
8.7
8.7
8.4
8.5
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
2.84
2.82
2.81
3.08
3.61
3.42
3.41
3.61
3.41
3.41
3.62
3.41
3.62
3.65
3.66
3.80
3.77
3.87
4.04
3.82
4.50
D
D
D
D
A
B
B
A
B
B
A
B
A
A
A
A
A
A
A
A
A
Indoor Unit CombinationNumberof Unit
1 Unit
2 Unit
Heating Capacity(W) Capacity CurrentPower Consumption
ACOP EG
220029003800560022002200220022002900290029003800
B
----
22002900380056002900380056003800
C
------------
D
------------
%
39%51%67%98%77%89%105%137%102%118%149%133%
Total Total
220029003800560044005100600078005800670085007600
A
250029003800540022002200209016082850246719452850
B
----
22002900361040922850323337552850
C
------------
Min.W
130013001300145014501450150015001500150015001500
Nom.W
250029003800540044005100570057005700570057005700
Max.Ml
299033404370560047505460630064006300630064006300
Min.W
320320320340350350350350350350350350
Nom.W
88010301300181012201410152014401550148014001470
Max.W
101012901620206013901610195018302060194018301890
D
------------
250029003800540044005100570057005700570057005700
Min.A
1.71.71.71.81.91.91.91.91.91.91.91.9
Nom.A
44.75.98.35.66.57
6.67.16.86.46.7
Max.A
4.65.97.49.46.47.48.98.49.48.98.48.6
2.842.822.922.983.613.623.753.963.683.854.073.88
DDDDAAAAAAAA
NoteSpecifications are subject to change without prior notice for product improvement.
NoteSpecifications are subject to change without prior notice for product improvement.
Outdoor Units - Free Joint Multi 56 57
Outdoor U
nits
2008 SAMSUNG DVM Air Conditioners Outdoor Units
Capacity CombinationCoolingMH070FXEA4B
Indoor Unit CombinationNumberof Unit
1 Unit
2 Unit
3 Unit
4 Unit
Cooling Capacity(W) Capacity CurrentPower Consumption
ACOP EG
2000
2600
3500
5200
2000
2000
2000
2000
2600
2600
2600
3500
3500
5200
2000
2000
2000
2000
2000
2000
2000
2000
2000
2600
2600
2600
2600
3500
2000
2000
2000
2000
2000
2000
2000
2600
B
-
-
-
-
2000
2600
3500
5200
2600
3500
5200
3500
5200
5200
2000
2000
2000
2000
2600
2600
2600
3500
3500
2600
2600
2600
3500
3500
2000
2000
2000
2000
2000
2600
2600
2600
C
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2000
2600
3500
5200
2600
3500
5200
3500
5200
2600
3500
5200
3500
3500
2000
2000
2000
2600
2600
2600
2600
2600
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2000
2600
3500
2600
3500
2600
3500
2600
%
29%
37%
50%
74%
57%
66%
79%
103%
74%
87%
111%
100%
124%
149%
86%
94%
107%
131%
103%
116%
140%
129%
153%
111%
124%
149%
137%
150%
114%
123%
136%
131%
144%
140%
153%
149%
Total Total
2000
2600
3500
5200
4000
4600
5500
7200
5200
6100
7800
7000
8700
10400
6000
6600
7500
9200
7200
8100
9800
9000
10700
7800
8700
10400
9600
10500
8000
8600
9500
9200
10100
9800
10700
10400
A
2400
2600
3500
5200
2000
2000
2000
1944
2600
2600
2333
3500
2816
3500
2000
2000
1781
1522
1847
1664
1429
1516
1308
2240
2029
1750
1896
2330
1680
1577
1474
1522
1386
1429
1308
1750
B
-
-
-
-
2000
2600
3500
5056
2600
3500
4667
3500
4184
3500
2000
2000
1781
1522
2401
2163
1857
2652
2290
2240
2029
1750
2552
2330
1680
1577
1474
1522
1386
1857
1701
1750
C
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2000
2600
3118
3957
2401
3119
3714
2652
3120
2240
2732
3121
2552
2330
1680
1577
1474
1978
1802
1857
1701
1750
Min.W
1350
1350
1350
1400
1500
1690
1770
1900
1750
1820
1900
1900
1900
1900
1810
1870
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
Nom.W
2400
2600
3500
5200
4000
4600
5500
7000
5200
6100
7000
7000
7000
7000
6000
6600
6680
7000
6650
6740
7000
6820
7000
6720
6790
7000
7000
6990
6720
6780
7000
7000
7000
7000
7000
7000
3000
3480
4200
6240
4800
5520
6600
8400
6240
7320
8400
8400
8900
8900
7200
7920
8020
8900
7980
8080
8900
8180
8900
8050
8150
8900
8900
8900
8070
8140
8900
8900
8900
8900
8900
8900
Max.Ml
Min.W
380
390
400
420
410
420
430
580
420
440
580
580
580
580
440
440
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
Nom.W
780
840
1130
1520
1240
1430
1710
2180
1660
1880
2130
2120
2110
2000
1800
1830
1835
1850
1830
1840
1880
1850
1930
1840
1850
1880
1880
1900
1850
1880
1900
1880
1900
1900
1930
1900
Max.W
950
1100
1580
2160
1490
1720
2050
2520
2000
2260
2540
2530
2540
2540
2280
2460
2410
2460
2410
2460
2460
2510
2510
2420
2460
2510
2460
2510
2460
2460
2460
2460
2510
2460
2550
2550
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1680
2050
2579
1978
2426
1857
2290
1750
2400
2600
3500
5200
4000
4600
5500
7000
5200
6100
7000
7000
7000
7000
6000
6600
6680
7000
6650
6740
7000
6820
7000
6720
6790
7000
7000
6990
6720
6780
7000
7000
7000
7000
7000
7000
Min.A
1.7
1.8
1.8
1.9
1.9
1.9
2
2.7
1.9
2
2.7
2.7
2.7
2.7
2
2
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
Nom.A
3.6
3.8
5.2
7
5.7
6.5
7.8
10
7.6
8.6
9.7
9.7
9.7
9.2
8.2
8.4
8.4
8.5
8.4
8.4
8.6
8.5
8.8
8.4
8.5
8.6
8.6
8.7
8.5
8.6
8.7
8.6
8.7
8.7
8.8
8.7
Max.A
4.3
5
7.2
9.9
6.8
7.9
9.4
11.5
9.2
10.3
11.6
11.6
11.6
11.6
10.4
11.3
11
11.3
11
11.3
11.3
11.5
11.5
11.1
11.3
11.5
11.3
11.5
11.3
11.3
11.3
11.3
11.5
11.3
11.7
11.7
3.08
3.10
3.10
3.42
3.23
3.22
3.22
3.21
3.13
3.24
3.29
3.30
3.32
3.50
3.33
3.61
3.64
3.78
3.63
3.66
3.72
3.69
3.63
3.65
3.67
3.72
3.72
3.68
3.63
3.61
3.68
3.72
3.68
3.68
3.63
3.68
B
B
B
A
A
A
A
A
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
HeatingMH070FXEA4BIndoor Unit Combination
Numberof Unit
1 Unit
2 Unit
3 Unit
4 Unit
Heating Capacity(W) Capacity CurrentPower Consumption
ACOP EG
2200
2600
3800
5600
2200
2200
2200
2200
2900
2900
2900
3800
3800
5600
2200
2200
2200
2200
2200
2200
2200
2200
2200
2900
2900
2900
2900
3800
2200
2200
2200
2200
2200
2200
2200
2900
B
-
-
-
-
2200
2900
3800
5600
2900
3800
5600
3800
5600
5600
2200
2200
2200
2200
2900
2900
2900
3800
3800
2900
2900
2900
3800
3800
2200
2200
2200
2200
2200
2900
2900
2900
C
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2200
2900
3800
5600
2900
3800
5600
3800
5600
2900
3800
5600
3800
3800
2200
2200
2200
2900
2900
2900
2900
2900
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2200
2900
3800
2900
3800
2900
3800
2900
%
26%
30%
44%
65%
51%
59%
70%
91%
67%
78%
99%
88%
109%
130%
77%
85%
95%
116%
93%
103%
124%
114%
135%
101%
112%
133%
122%
133%
102%
110%
121%
119%
129%
127%
137%
135%
Total Total
2200
2600
3800
5600
4400
5100
6000
7800
5800
6700
8500
7600
9400
11200
6600
7300
8200
10000
8000
8900
10700
9800
11600
8700
9600
11400
10500
11400
8800
9500
10400
10200
11100
10900
11800
11600
A
2500
2900
3800
5600
2200
2200
2200
2200
2900
2900
2729
3800
3283
4250
2200
2200
2200
1892
2200
2042
1768
1872
1631
2750
2516
2188
2375
2867
2063
1927
1819
1855
1705
1736
1603
2150
B
-
-
-
-
2200
2900
3800
5600
2900
3800
5271
3800
4837
4250
2200
2200
2200
1892
2900
2691
2331
3234
2817
2750
2516
2188
3112
2867
2063
1927
1819
1855
1705
2288
2114
2150
C
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2200
2900
3800
4816
2900
3119
4501
3234
3120
2750
3297
3121
3112
2867
2063
1927
1819
2445
2247
2288
2114
2150
Min.W
1790
1820
1930
2080
1980
2040
2110
2200
2100
2170
2200
2200
2200
2200
2170
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
Nom.W
2500
2900
3800
5600
4400
5100
6000
7800
5800
6700
8000
7600
8120
8500
6600
7300
8200
8600
8000
8260
8600
8340
8600
8250
8330
8600
8600
8600
8250
8320
8600
8600
8600
8600
8600
8600
3220
3680
4600
6440
5060
5870
6900
9130
6670
8040
9600
9120
9740
10200
7590
8400
9590
10300
9360
9670
10300
9760
10300
9650
9740
10300
10300
10300
9660
9730
10300
10300
10300
10300
10300
10300
Max.Ml
Min.W
580
590
600
610
600
610
610
620
610
610
620
620
620
620
610
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
Nom.W
950
1100
1250
1670
1220
1410
1760
2150
1600
1940
2210
2100
2250
2250
1830
1880
1930
1960
1900
1930
1970
1950
2000
1930
1950
1980
1980
2000
1930
1950
2000
1970
2000
2000
2000
2000
Max.W
1330
1500
1810
2370
1530
1700
2110
2700
1930
2330
2650
2510
2700
2740
2530
2590
2660
2700
2620
2660
2720
2690
2760
2660
2690
2730
2730
2760
2660
2690
2760
2720
2760
2760
2760
2760
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2063
2540
3142
2445
2944
2288
2769
2150
2500
2900
3800
5600
4400
5100
6000
7800
5800
6700
8000
7600
8120
8500
6600
7300
8200
8600
8000
8260
8600
8340
8600
8250
8330
8600
8600
8600
8250
8320
8600
8600
8600
8600
8600
8600
Min.A
2.7
2.7
2.7
2.8
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
Nom.A
4.3
5
5.7
7.6
5.6
6.5
8.1
9.8
7.3
8.9
10.1
9.6
10.3
10.3
8.4
8.6
8.8
9
8.7
8.8
9
8.9
9.2
8.8
8.9
9.1
9.1
9.2
8.8
8.9
9.2
9
9.2
9.2
9.2
9.2
Max.A
6.1
6.9
8.3
10.8
7
7.8
9.7
12.4
8.8
10.7
12.1
11.5
12.4
12.5
11.6
11.9
12.2
12.4
12
12.2
12.4
12.3
12.6
12.2
12.3
12.5
12.5
12.6
12.2
12.3
12.6
12.4
12.6
12.6
12.6
12.6
2.63
2.64
3.04
3.35
3.61
3.62
3.41
3.63
3.63
3.45
3.62
3.62
3.61
3.78
3.61
3.88
4.25
4.39
4.21
4.28
4.37
4.28
4.30
4.27
4.27
4.34
4.34
4.30
4.27
4.27
4.30
4.37
4.30
4.30
4.30
4.30
E
E
D
C
A
A
B
A
A
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
NoteSpecifications are subject to change without prior notice for product improvement.
NoteSpecifications are subject to change without prior notice for product improvement.
Outdoor Units - Free Joint Multi 58 59
Outdoor U
nits
2008 SAMSUNG DVM Air Conditioners Outdoor Units
Capacity CombinationCoolingMH080FXEA4B
Indoor Unit CombinationNumberof Unit
1 Unit
2 Unit
3 Unit
4 Unit
Cooling Capacity(W) Capacity CurrentPower Consumption
ACOP EG
2000
2600
3500
5200
2000
2000
2000
2000
2600
2600
2600
3500
3500
5200
2000
2000
2000
2000
2000
2000
2000
2000
2000
2600
2600
2600
2600
2600
3500
3500
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2600
2600
2600
B
-
-
-
-
2000
2600
3500
5200
2600
3500
5200
3500
5200
5200
2000
2000
2000
2000
2600
2600
2600
3500
3500
2600
2600
2600
3500
3500
3500
3500
2000
2000
2000
2000
2000
2000
2000
2000
2600
2600
2600
2600
2600
2600
C
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2000
2600
3500
5200
2600
3500
5200
3500
5200
2600
3500
5200
3500
5200
3500
5200
2000
2000
2000
2000
2600
2600
2600
3500
2600
2600
3500
2600
2600
3500
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2000
2600
3500
5200
2600
3500
5200
3500
2600
3500
3500
2600
3500
3500
%
25%
33%
44%
65%
50%
58%
69%
90%
65%
76%
98%
88%
109%
130%
75%
83%
94%
115%
90%
101%
123%
113%
134%
98%
109%
130%
120%
141%
131%
153%
100%
108%
119%
140%
115%
126%
148%
138%
123%
134%
145%
130%
141%
153%
Total Total
2000
2600
3500
5200
4000
4600
5500
7200
5200
6100
7800
7000
8700
10400
6000
6600
7500
9200
7200
8100
9800
9000
10700
7800
8700
10400
9600
11300
10500
12200
8000
8600
9500
11200
9200
10100
11800
11000
9800
10700
11600
10400
11300
12200
A
2400
2600
3500
5200
2000
2000
2000
2000
2600
2600
2400
3500
2957
3825
2000
2000
2000
1663
2000
1864
1573
1698
1495
2510
2274
1940
2083
1841
2667
2295
1888
1767
1617
1429
1663
1531
1356
1455
1573
1495
1379
1940
1841
1705
B
-
-
-
-
2000
2600
3500
5200
2600
3500
4800
3500
4393
3825
2000
2000
2000
1663
2600
2423
2046
2971
2617
2510
2274
1940
2804
2478
2667
2295
1888
1767
1617
1429
1663
1531
1356
1455
2046
1944
1793
1940
1841
1705
C
-
-
-
-
-
-
-
-
-
-
-
-
-
2000
2600
3500
4324
2600
3262
4091
2971
3888
2510
3061
3880
2804
3681
2667
3410
1888
1767
1617
1429
2162
1990
1763
2545
2046
1944
2414
1940
1841
2295
Min.W
1470
1520
1600
1750
1640
1690
1770
1900
1750
1820
1900
1900
1900
1900
1810
1870
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
Nom.W
2400
2600
3500
5200
4000
4600
5500
7200
5200
6100
7200
7000
7350
7650
6000
6600
7500
7650
7200
7550
7710
7640
8000
7530
7610
7760
7690
8000
8000
8000
7550
7600
7680
8000
7650
7730
8000
8000
7710
8000
8000
7760
8000
8000
3000
3480
4200
6240
4800
5520
6600
8640
6240
7320
8640
8400
8820
9180
7200
7920
9000
9180
8640
9060
9250
9160
9300
9030
9130
9300
9230
9300
9300
9300
9050
9120
9220
9300
9180
9280
9300
9300
9250
9300
9300
9300
9300
9300
Max.Ml
Min.W
380
390
400
420
410
420
430
580
420
440
580
580
580
580
440
440
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
580
Nom.W
780
840
1130
1520
1240
1430
1710
2240
1660
1900
2240
2180
2290
2380
1850
2000
2220
2190
2150
2150
2190
2190
2260
2110
2140
2210
2180
2260
2260
2300
2140
2140
2180
2300
2190
2200
2300
2280
2190
2260
2300
2220
2300
2300
Max.W
950
1100
1580
2160
1490
1720
2050
2690
2000
2260
2690
2620
2750
2860
2310
2500
2780
2730
2680
2690
2730
2730
2820
2640
2690
2780
2730
2870
2820
2910
2690
2690
2730
2870
2730
2780
2870
2870
2730
2820
2870
2780
2870
2910
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1888
2298
2829
3714
2162
2679
3525
2545
2046
2617
2414
1940
2478
2295
2400
2600
3500
5200
4000
4600
5500
7200
5200
6100
7200
7000
7350
7650
6000
6600
7500
7650
7200
7550
7710
7640
8000
7530
7610
7760
7690
8000
8000
8000
7550
7600
7680
8000
7650
7730
8000
8000
7710
8000
8000
7760
8000
8000
Min.A
1.7
1.8
1.8
1.9
1.9
1.9
2
2.7
1.9
2
2.7
2.7
2.7
2.7
2
2
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
Nom.A
3.6
3.8
5.2
7
5.7
6.5
7.8
10.3
7.6
8.7
10.3
10
10.5
10.9
8.5
9.2
10.2
10
9.8
9.8
10
10
10.3
9.7
9.8
10.1
10
10.3
10.3
10.5
9.8
9.8
10
10.5
10
10.1
10.5
10.4
10
10.3
10.5
10.2
10.5
10.5
Max.A
4.3
5
7.2
9.9
6.8
7.9
9.4
12.3
9.2
10.3
12.3
12
12.6
13.1
10.6
11.4
12.7
12.5
12.3
12.3
12.5
12.5
12.9
12.1
12.3
12.7
12.5
13.1
12.9
13.3
12.3
12.3
12.5
13.1
12.5
12.7
13.1
13.1
12.5
12.9
13.1
12.7
13.1
13.3
3.08
3.10
3.10
3.42
3.23
3.22
3.22
3.21
3.13
3.21
3.21
3.21
3.21
3.21
3.24
3.30
3.38
3.49
3.35
3.51
3.52
3.49
3.54
3.57
3.56
3.51
3.53
3.54
3.54
3.48
3.53
3.55
3.52
3.48
3.49
3.51
3.48
3.51
3.52
3.54
3.48
3.50
3.48
3.48
B
B
B
A
A
A
A
A
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Indoor Unit CombinationNumberof Unit
1 Unit
2 Unit
3 Unit
4 Unit
Heating Capacity(W) Capacity CurrentPower Consumption
ACOP EG
2200
2900
3800
5600
2200
2200
2200
2200
2900
2900
2900
3800
3800
5600
2200
2200
2200
2200
2200
2200
2200
2200
2200
2900
2900
2900
2900
2900
3800
3800
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2900
2900
2900
B
-
-
-
-
2200
2900
3800
5600
2900
3800
5600
3800
5600
5600
2200
2200
2200
2200
2900
2900
2900
3800
3800
2900
2900
2900
3800
3800
3800
3800
2200
2200
2200
2200
2200
2200
2200
2200
2900
2900
2900
2900
2900
2900
C
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2200
2900
3800
5600
2900
3800
5600
3800
5600
2900
3800
5600
3800
5600
3800
5600
2200
2200
2200
2200
2900
2900
2900
3800
2900
2900
3800
2900
2900
3800
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2200
2900
3800
5600
2900
3800
5600
3800
2900
3800
3800
2900
3800
3800
%
24%
31%
41%
60%
47%
55%
65%
84%
62%
72%
91%
82%
101%
120%
71%
78%
88%
108%
86%
96%
115%
105%
125%
94%
103%
123%
113%
132%
123%
142%
95%
102%
112%
131%
110%
119%
139%
129%
117%
127%
137%
125%
134%
144%
Total Total
2200
2900
3800
5600
4400
5100
6000
7800
5800
6700
8500
7600
9400
11200
6600
7300
8200
10000
8000
8900
10700
9800
11600
8700
9600
11400
10500
12300
11400
13200
8800
9500
10400
12200
10200
11100
12900
12000
10900
11800
12700
11600
12500
13400
A
2500
2900
3800
5600
2200
2200
2200
2200
2900
2900
2729
3800
3283
4250
2200
2200
2200
1896
2200
2109
1785
1931
1764
2840
2595
2226
2392
2193
2910
2677
2130
1987
1830
1677
1864
1726
1586
1610
1754
1633
1611
2188
2158
2013
B
-
-
-
-
2200
2900
3800
5600
2900
3800
5271
3800
4837
4250
2200
2200
2200
1896
2900
2779
2353
3335
3047
2840
2595
2226
3134
2873
2910
2677
2130
1987
1830
1677
1864
1726
1586
1610
2312
2153
2124
2188
2158
2013
C
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2200
2900
3800
4827
2900
3642
4543
3335
4490
2840
3400
4298
3134
4234
2910
3945
2130
1987
1830
1677
2456
2276
2091
2780
2312
2153
2783
2188
2158
2637
Min.W
1790
1820
1930
2080
1980
2040
2110
2200
2100
2170
2200
2200
2200
2200
2170
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
2200
Nom.W
2500
2900
3800
5600
4400
5100
6000
7800
5800
6700
8000
7600
8120
8500
6600
7300
8200
8620
8000
8530
8680
8600
9300
8520
8590
8750
8660
9300
8730
9300
8520
8580
8650
9300
8640
8710
9300
8780
8690
8760
9300
8750
9300
9300
3220
3680
4600
6440
5060
5870
6900
9130
6670
7710
9360
8740
9500
9950
7590
8400
9590
10090
9360
9980
10150
10070
10900
9960
10050
10900
10130
10900
10220
10900
9970
10040
10120
10900
10100
10190
10900
10270
10170
10250
10900
10240
10900
10900
Max.Ml
Min.W
580
590
600
610
600
610
610
620
610
610
620
620
620
620
610
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
620
Nom.W
950
1110
1250
1670
1220
1410
1760
2150
1600
1940
2210
2090
2250
2340
1830
1950
2150
2140
2080
2100
2140
2140
2150
2090
2100
2140
2140
2150
2150
2180
2100
2100
2140
2200
2140
2140
2200
2180
2140
2180
2200
2140
2180
2200
Max.W
1330
1500
1810
2370
1530
1700
2110
2580
1930
2330
2600
2510
2650
2750
2220
2340
2570
2610
2500
2690
2740
2740
2750
2680
2690
2740
2740
2750
2750
2790
2690
2690
2740
2820
2740
2740
2820
2790
2740
2790
2820
2740
2790
2820
D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2130
2619
3161
4269
2456
2982
4037
2780
2312
2821
2783
2188
2827
2637
2500
2900
3800
5600
4400
5100
6000
7800
5800
6700
8000
7600
8120
8500
6600
7300
8200
8620
8000
8530
8680
8600
9300
8520
8590
8750
8660
9300
8730
9300
8520
8580
8650
9300
8640
8710
9300
8780
8690
8760
9300
8750
9300
9300
Min.A
2.7
2.7
2.7
2.8
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
Nom.A
4.3
5.1
5.7
7.6
5.6
6.5
8.1
9.8
7.3
8.9
10.1
9.6
10.3
10.7
8.4
8.9
9.8
9.8
9.5
9.6
9.8
9.8
9.8
9.6
9.6
9.8
9.8
9.8
9.8
10
9.6
9.6
9.8
10.1
9.8
9.8
10.1
10
9.8
10
10.1
9.8
10
10.1
Max.A
6.1
6.9
8.3
10.8
7
7.8
9.7
11.8
8.8
10.7
11.9
11.5
12.1
12.6
10.2
10.7
11.8
11.9
11.4
12.3
12.5
12.5
12.6
12.3
12.3
12.5
12.5
12.6
12.6
12.8
12.3
12.3
12.5
12.9
12.5
12.5
12.9
12.8
12.5
12.8
12.9
12.5
12.8
12.9
2.63
2.61
3.04
3.35
3.61
3.62
3.41
3.63
3.63
3.45
3.62
3.64
3.61
3.63
3.61
3.74
3.81
4.03
3.85
4.06
4.06
4.02
4.33
4.08
4.09
4.09
4.05
4.33
4.06
4.27
4.06
4.09
4.04
4.23
4.04
4.07
4.23
4.03
4.06
4.02
4.23
4.09
4.27
4.23
E
E
D
C
A
A
B
A
A
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
HeatingMH080FXEA4B
NoteSpecifications are subject to change without prior notice for product improvement.
NoteSpecifications are subject to change without prior notice for product improvement.
Different types of air conditioners are required depending on different types of buildings andresidential space. Searching for the right air conditioner for your commercial and residentialspace is over. You’ll be able to find the one you need from Samsung’s variety of indoor units instyle. Perfect fit, just the way you need it.
Indoor Units
>> 62_ Wall-mounted Type >64_ MB >66_ Vivace >68_ Neo Forte >> 70_ Cassette Type >72_ Slim 1Way Cassette
>76_ 2Way Cassette >78_ Mini 4Way Cassette >80_ 4Way Cassette >> 84_ Duct Type >86_ Slim Duct >90_ MSP Duct
>> 92_ Floor & Convertible >94_ Console >98_ Ceiling >> 100_ ERV System >> 104_ Accessories
imaginethe perfect fit
60 61
Indoor Units
Indoor Units
Indoor Units - Wall-mounted type
2008 SAMSUNG DVM Air Conditioners Indoor Units
62 63
Indoor Units
Wall-mounted typeAir conditionersSamsung’s brand new wall-mounted type air conditioners have more than just afeature of comfortable cooling. New wall-mounted air conditioners will be part ofyour interior design and protect your health with built-in health care system.Breathe cooler and healthier air every second of your life.
MPI Zone (Optional)
● Creation of an Intensely Purified Zone
● Protection against disease
● Safe from allergy-causing agents
● Controls active oxygen which can cause disease,cancer, and accelerated aging
Do you know that harmful substances andviruses breed in the space you live in?
How Micro Plasma Ion Systemtechnology Works
Health Care System 5-Step Air Purifying System
Micro Plasma Ion improves yourIndoor Air Quality and eliminatesall your worries.
Active hydrogen /Oxygen ions
Active hydrogen and oxygen ionsare generated
Harmful substancesCombines with
Harmful substancesOH radical, Harmfulviruses and bacteria.
Harmlesswater
Turns into harmless water
Health Care System (Optional)
Good’sleep II (MB/Forte)
Best Temperature for deep sleepAccording to the stage of sleep, temperatures are adjusted so you fall into deep sleep faster and get up morerefreshed in the morning for a great start to your day.
1. Falling asleep stage: Eases you into sleep by dropping the temperature.2. Sound sleep stage: Relaxes your body and raises your temperature slightly.3. Wake up stage: Allows you to wake up from comfortable intermittent air and it makes you feel refresh.
MPI Zone (Optional)
Stage 1
Stage 1 Auto Roof Shutter(MB)
Stage 3
Stage 2
Step 5
Deodorizing filterStep 4
DNA or Catechin FilterStep 3
Silver Coated Evaporator(Optional)
Step 2
Silver Coated FilterStep 1
The Samsung air conditioner is all what you needto keep your air consistently clean and fresh.
The Auto Roof Shutter keeps dirt from gettinginside.
Stage 2 MPI (Micro Plasma Ion )Biological contaminants and various pathogenssuch as bacteria, viruses, and molds are removed.
Stage 3 DNA filter & 5 step filterExogenous endocrine-disrupting chemicals, hazardous materials, and other harmful chemicals are removed.
Indoor Units - Wall-mounted type
2008 SAMSUNG DVM Air Conditioners Indoor Units
64 65
Indoor Units
••• Unique and Innovative•••
MB
Blue Light Pearl Color Auto Roof Shutter
Auto Roof Shutter (2.8/3.6kW)This unique air conditioner automatically seals off to preventdirt infiltration when not in operation.
DNA FilterIt is a new technology that screens selectively for only toxicagents. This enables a smarter and effective air managementcompared to other filters.
MPI (Micro Plasma Ion)The world's first technology that generates active hydrogenatoms together with oxygen ions to improve your Indoor AirQuality. It protects you from harmful particles and virusesexisting in the air.
Good’sleep IIInnovative technology developed to control the air temperatureduring your sleep and maintain optimum skin temperature toenjoy a comfortable sleep and also a refreshed wake up.
Deodorizing filterIncorporated with activated carbon, the Deodorizing Filterefficiently adsorbscigarette smoke, pet odors and other unpleasant odors.
Design
Silver Coated EvaporatorThe fins of the evaporator are triple coated with environmen-tally friendly materials (2 years of chrome-free silica, 1 layer ofSilver coating) to ensure efficient removal of condensation andto guarantee the production of clean and fresh air.
OptionalAccessories
Individual Controllers
MR-BH01MWR-WS00
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.*6) Optional Accessory
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Wireless Remote Controller
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
AVXWBH028EE AVXWBH036EE AVXWBH056EE AVXWBH071EE
1/220~240/50
HP/HR
3.6
12,200
4.0
13,600
30
0.19
35 / 21 *5)
Cross Flow Fan
9.16 *5)
9.46 *5)
R410A
EEV *6)
6.35
12.70
ID 18 hose
10.2 *5)
11.5 *5)
900x304x185
963x349x247
Filter (Washable)
ARH-1364
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
50
0.3
40 / 30 *5)
Cross Flow Fan
14.98 *5)
14.49 *5)
R410A
EEV *6)
6.35
12.70
ID 18 hose
13.0 *5)
16.0 *5)
1,100x307x225
1,157x381x292
Filter (Washable)
ARH-1364
1/220~240/50
HP/HR
6.8
23,200
7.0
23,800
50
0.3
41 / 30 *5)
Cross Flow Fan
-
-
R410A
EEV *6)
9.52
15.88
ID 18 hose
13.0 *5)
16.0 *5)
1,100x307x225
1,157x381x292
Filter (Washable)
ARH-1364
1/220~240/50
HP/HR
2.8
9,500
3.2
10,900
30
0.18
31 / 20 *5)
Cross Flow Fan
8.14 *5)
8.23 *5)
R410A
EEV *6)
6.35
12.70
ID 18 hose
10.2 *5)
11.5 *5)
900x304x185
963x349x247
Filter (Washable)
ARH-1364
Cooling *2)
Heating *3)
Specification | MB
MWR-TH01 MWR-SH00
Indoor Units - Wall-mounted type
2008 SAMSUNG DVM Air Conditioners Indoor Units
66 67
Indoor Units
••• Chic and Graceful•••
Vivace (Shadow Mirror)
Shadow Mirror Hidden Display Trim-less Design
MPI (Micro Plasma Ion)The world's first technology that generates active hydrogenatoms together with oxygen ions to improve your Indoor AirQuality. It protects you from harmful particles and virusesexisting in the air.
Good’sleep IIInnovative technology developed to control the air temperatureduring your sleep and maintain optimum skin temperature toenjoy a comfortable sleep and also a refreshed wake up.
Catechin filterCatechin, extracted from green tea, is contained in the filterand deactivates captured bacteria and unpleasant odors.
Deodorizing filterIncorporated with activated carbon, the Deodorizing Filterefficiently adsorbscigarette smoke, pet odors and other unpleasant odors.
Design
Silver Coated EvaporatorThe fins of the evaporator are triple coated with environmen-tally friendly materials (2 years of chrome-free silica, 1 layer ofSilver coating) to ensure efficient removal of condensation andto guarantee the production of clean and fresh air.
OptionalAccessories
Individual Controllers
Specification | Vivace
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.*6) Optional Accessory
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Wireless Remote Controller
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
AVXWVH022EE
1/220~240/50
HP/HR
2.2
7,500
2.5
8,500
30
0.13
31 / 21 *5)
Cross Flow Fan
8.82
6.11
R410A
EEV *6)
6.35
12.70
ID 18 hose
8.5
11.5
825x285x189
900x349x252
Filter (Washable)
ARH-1364
AVXWVH028EE
1/220~240/50
HP/HR
2.8
9,500
3.2
10,900
30
0.18
31 / 21
Cross Flow Fan
7.0
7.3
R410A
EEV *6)
6.35
12.70
ID 18 hose
8.5
11.5
825x285x189
900x349x252
Filter (Washable)
ARH-1364
AVXWVH036EE
1/220~240/50
HP/HR
3.6
12,200
4.0
13,600
35
0.19
35 / 21
Cross Flow Fan
8.2
8.8
R410A
EEV *6)
6.35
12.70
ID 18 hose
8.5
11.5
825x285x189
900x349x252
Filter (Washable)
ARH-1364
AVXWVH056EE
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
50
0.30
40 / 30
Cross Flow Fan
13.3
14.0
R410A
EEV *6)
6.35
12.70
ID 18 hose
12.0
15.0
1,065x298x218
1,137x377x299
Filter (Washable)
ARH-1364
AVXWVH071EE
1/220~240/50
HP/HR
6.8
23,200
7.0
23,800
50
0.30
41 / 30
Cross Flow Fan
13.3
14.0
R410A
EEV *6)
9.52
15.88
ID 18 hose
12.0
15.0
1,065x298x218
1,137x377x299
Filter (Washable)
ARH-1364
Cooling *2)
Heating *3)
MR-BH01MWR-WS00MWR-TH01 MWR-SH00
Indoor Units - Wall-mounted type
2008 SAMSUNG DVM Air Conditioners Indoor Units
68 69
Indoor Units
Indoor Units
••• Clean and Fashionable•••
Neo Forte
Clean-Cut Front Panel Silver Accent Line Bottom Opening Front Panel
Good’sleep IIInnovative technology developed to control the air temperatureduring your sleep and maintain optimum skin temperature toenjoy a comfortable sleep and also a refreshed wake up.
Catechin filterCatechin, extracted from green tea, is contained in the filterand deactivates captured bacteria and unpleasant odors.
Deodorizing filterIncorporated with activated carbon, the Deodorizing Filterefficiently adsorbscigarette smoke, pet odors and other unpleasant odors.
Design
Silver Coated EvaporatorThe fins of the evaporator are triple coated with environmen-tally friendly materials (2 years of chrome-free silica, 1 layer ofSilver coating) to ensure efficient removal of condensation andto guarantee the production of clean and fresh air.
OptionalAccessories
Individual Controllers
Specification | Neo Forte
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.*6) Optional Accessory
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Wireless Remote Controller
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø/mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
AVXWNH022EE AVXWNH028EE AVXWNH036EE AVXWNH056EE AVXWNH071EE
1/220~240/50
HP/HR
2.8
9,500
3.2
10,900
25
0.16
32/23
Cross Flow Fan
8.31 *5)
8.56 *5)
R410A
EEV *6)
6.35
12.70
ID 18 hose
8.5 *5)
11.5 *5)
825x285x189
900x349x252
Filter (Washable)
ARH-1364
1/220~240/50
HP/HR
3.6
12,200
4.0
13,600
30
0.18
36/23 *5)
Cross Flow Fan
9.54 *5)
9.93 *5)
R410A
EEV *6)
6.35
12.70
ID 18 hose
8.5 *5)
11.5 *5)
825x285x189
900x349x252
Filter (Washable)
ARH-1364
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
45
0.27
40/30 *5)
Cross Flow Fan
13.21 *5)
14.22 *5)
R410A
EEV *6)
6.35
12.70
ID 18 hose
12.0 *5)
15.0 *5)
1,065x298x218
1,137x377x299
Filter (Washable)
ARH-1364
1/220~240/50
HP/HR
6.8
23,200
7.0
23,800
50
0.30
41/30 *5)
Cross Flow Fan
14.45 *5)
14.94 *5)
R410A
EEV *6)
9.52
15.88
ID 18 hose
12.0 *5)
15.0 *5)
1,065x298x218
1,137x377x299
Filter (Washable)
ARH-1364
1/220~240/50
HP/HR
2.2
7,500
2.5
8,500
25
0.16
32/23 *5)
Cross Flow Fan
7.73 *5)
8.00 *5)
R410A
EEV *6)
6.35
12.70
ID 18 hose
8.5 *5)
11.5 *5)
825x285x189
900x349x252
Filter (Washable)
ARH-1364
Cooling *2)
Heating *3)
MR-BH01MWR-WS00MWR-TH01 MWR-SH00
Indoor Units - Cassette type
2008 SAMSUNG DVM Air Conditioners Indoor Units
70 71
Cassette typeAir conditionersThis year's new cassette type air conditioner still boasts its slim and compact size,but is now equipped with more advanced features. The cassette type air conditionernot only has stronger airflow to cool and heat every inch of space efficiently, but isalso designed to be quiet and to purify. Expect more with Samsung.
Cassette type Icon
WIDE BLADE
FRESH AIR INTAKE
SUB DUCTQUICK CONNECTION OF DRAIN PIPE
CEILING SOILINGPREVENTION
HIGH LIFT-UP DRAIN PUMPWIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH
FRESHFRESHFRESHFRESH SUB DUCTSUB DUCTSUB DUCTSUB DUCT QUICKQUICKQUICKQUICK
Wide BladeThe new cassette type air conditioner is equipped with uniquely designed blades that are wider to provide even cooling andheating power throughout the room.
WIDEWIDEWIDEWIDE
64mm
46mm
WIDER
Airflow is directed towards theceiling which cause ceilingsoiling.
Airflow is directed downwardswithout having contact with theceiling.
Ceiling Soiling PreventionNewly designed panel will control the air direction to avoid having contactwith the ceiling. This new design will prevent the ceiling soiling and keep yourinterior cleaner than ever even, after long period of operation.
Conventional Blade
Ceiling Ceiling
New Blade
600(mm) 650
Lift-up Range
700 750
750mm
700mm
High Lift-up Drain PumpThe lift-up drain pump lifts condensed water up to 750mm,compared to the competitor’s 700mm, allowing for flexibleand convenient installation.
Fresh Air IntakeWith optional installation of an air intake motor, fresh air canenter through the cassette unit so you have fresher air in theroom.
Sub DuctThe Sub Duct lets you use the same air conditioner unit tocool another smaller space nearby. (The cassette unit is fitted with a knock-out component to accommodate this.)
Quick Connection of Drain PipeSamsung's unique drain pipe prevents leaks and is easier toinstall with no need to use tape or adhesives.
FRESHFRESHFRESHFRESH
SUB DUCTSUB DUCTSUB DUCTSUB DUCT QUICKQUICKQUICKQUICK
HIGHHIGHHIGHHIGH
Company A
Fresh air
Office Fitting room
Motor
Samsung
Indoor Units
2008 SAMSUNG DVM Air Conditioners Indoor Units
Indoor Units - Cassette type 72 73
Individual Controllers
Panel
PSSMA
OptionalAccessories
WIDE BLADEQUICK CONNECTION OF DRAIN PIPE
CEILING SOILINGPREVENTION
HIGH LIFT-UP DRAIN PUMPWIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH QUICKQUICKQUICKQUICK
Slim and Compact Design
Slim 1Way CassetteWant a cassette type air conditioner, but have limited space? Samsung's new Slim 1Way cassette type air conditioner is the answer.
10.5kg
17kg
38% Down
4kW R410A model Weight
Only 135mm thickSamsung introduces the world's slimmest indoorair conditioner unit. Only 135mm thick, the slim 1Way Cassette air conditioner can be installedpractically anywhere.
Lighter indoor unitThe first to apply ABS cabinets into its indoorunits, Samsung has achieved the lightest unitson the market. Its slim lightweight design makesinstallation and maintenance a breeze.
135mm
Ensure that there is sufficient installation space. Allow at least170mm for the installation.
NOTE
Min. 170mm
Quiet OperationSamsung's new blade design drastically reduces noise levels, so you can relax in peace and quiet.
25dB
35dB
30dB
43dB
Low
High
Fan speed Noise level
Check Valve Inside Drain PumpFaulty drainage installation or power failures can cause condensed water to flow back into the unit, causingleakage and odors. Samsung's air conditioners are equipped with a check valve built directly into the drainpump to prevent water from flowing backward.
Check Valve
••• Stylish and Slim •••
Slim 1Way Cassette
Indoor Units
MR-AH01MR-BH01MWR-WS00MWR-TH01 MWR-SH00
2008 SAMSUNG DVM Air Conditioners Indoor Units
Indoor Units - Cassette type 74 75
Specification | Slim 1Way Cassette
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Indoor Units
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Panel Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Model
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Drain Pump (Pumping speed / lift)
AVXCSH022EEModel
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
kg
kg
mm
mm
-
l/h /mm
1/220~240/50
HP/HR
2.2
7,500
2.5
8,500
40
0.20
30/25 *5)
Cross Flow Fan
5.4 *5)
7.6 *5)
R410A
EEV
6.35
12.70
VP20(OD 25,ID 20)
10.5
13.5
970x135x410
1,164x212x478
PSSMA
3.0
5.0
1,180x25x460
1,259x144x539
Filter (Washable)
24/750
Cooling *2)
Heating *3)
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Panel Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Model
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Drain Pump (Pumping speed / lift)
AVXCSH028EEModel
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
kg
kg
mm
mm
-
l/h /mm
1/220~240/50
HP/HR
2.8
9,500
3.2
10,900
45
0.23
30 / 25 *5)
Cross Flow fan
6.0 *5)
8.6 *5)
R410A
EEV
6.35
12.70
VP20(OD 25,ID 20)
10.5
13.5
970x135x410
1,164x212x478
PSSMA
3.0
5.0
1,180x25x460
1,259x144x539
Filter (Washable)
24/750
AVXCSH036EE
1/220~240/50
HP/HR
3.6
12,200
4.0
13,600
50.5
0.25
32 / 27 *5)
Cross Flow fan
7.5 *5)
9.7 *5)
R410A
EEV
6.35
12.70
VP20(OD 25,ID 20)
10.5
13.5
970x135x410
1,164x212x478
PSSMA
3.0
5.0
1180x25x460
1259x144x539
Filter (Washable)
24/750
Cooling *2)
Heating *3)
2008 SAMSUNG DVM Air Conditioners Indoor Units
Indoor Units - Cassette type 76 77
Individual Controllers
PanelOptionalAccessories
••• Slim and Compact •••
2Way CassetteSpecification | 2Way Cassette
QUICK CONNECTION OF DRAIN PIPE
HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH QUICKQUICKQUICKQUICK
Small Size Big PerformanceThe 2Way cassette air conditioner is now 45% smaller thancompetitor’s models, so it's even easier to incorporate intobuilding design.
Twin Cross Flow FanThe 2Way cassette type unit is perfect fit for long and narrowrectangular type of space. Twin Cross Flow Fan inside of the2Way cassette will spread cool or warm air even further andwider with less noise.
Standard Formula for Easy InstallationThe dimensions of the 2Way cassette air conditioner allows for easyinstallation into standard ceiling grids (600Wx600H), so everythingjust falls into place.
230mm
890mm575mm
45%Decreased
305mm
1,180mm600mm
P2SMA
Indoor Units
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Panel Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Model
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Drain Pump (Pumping speed / lift)
AVXC2H056EEModel
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
kg
kg
mm
mm
-
l/h /mm
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
70
0.38
36 / 28
Cross Flow Fan
14.0
16.0
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
21.0
25.0
890x230x575
1,077x299x642
P2SMA
4.0
8.0
1,030x25x650
1,103x151x727
Filter (Washable)
24/750
AVXC2H071EE
1/220~240/50
HP/HR
7.1
24,200
8.0
27,200
75
0.40
38 / 28
Cross Flow Fan
14.0
16.0
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
21.0
25.0
890x230x575
1,077x299x642
P2SMA
4.0
8.0
1,030x25x650
1,103x151x727
Filter (Washable)
24/750
Cooling *2)
Heating *3)
MR-AH01MR-BH01MWR-WS00MWR-TH01 MWR-SH00
600mm
600mm
Cross flow fans
2008 SAMSUNG DVM Air Conditioners Indoor Units
Indoor Units - Cassette type 78 79
Individual Controllers
OptionalAccessories
••• Compact and Efficient •••
Mini 4Way Cassette
FRESH AIR INTAKE
QUICK CONNECTION OF DRAIN PIPE
HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH FRESHFRESHFRESHFRESH QUICKQUICKQUICKQUICK
Fan Speed AdjustmentFan speed can be adjusted according to ceiling height byadjusting dip switch of indoor unit’s PCB.
Ideal Compact SizeThe Mini 4Way cassette air conditioner can be installed in one standardceiling tile (600Wx600H), which can save installation time.
3~3.5m 2.7m
High Ceiling
On : Increased fan speed Off : Standard fan speed
Unit : mm
Standard Ceiling
Specification | Mini 4Way Cassette
PMSMA
Indoor Units
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Panel Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Model
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Drain Pump (Pumping speed / lift)
AVXCMH028EEModel
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
kg
kg
mm
mm
-
l/h /mm
1/220~240/50
HP/HR
2.8
9,500
3.2
10,900
90
0.50
30 / 25
Turbo Fan
10.1
11.9
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
17.0
20.0
575x260x575
660x310x635
PMSMA
3.5
6.2
670x35x670
717x93x717
Filter / Safety Grille
24/750
AVXCMH036EE
1/220~240/50
HP/HR
3.6
12,200
4.0
13,600
90
0.50
34 / 27
Turbo Fan
10.1
11.9
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
17.0
20.0
575x260x575
660x310x635
PMSMA
3.5
6.2
670x35x670
717x93x717
Filter / Safety Grille
24/750
AVXCMH056EE
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
95
0.52
41 / 33
Turbo Fan
10.6
12.6
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
17.0
20.0
575x260x575
660x310x635
PMSMA
3.5
6.2
670x35x670
717x93x717
Filter / Safety Grille
24/750
AVXCMH060EE
1/220~240/50
HP/HR
6.0
20,400
6.8
23,200
100
0.55
41 / 33
Turbo Fan
12.2
14.5
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
17.0
20.0
575x260x575
660x310x635
PMSMA
3.5
6.2
670x35x670
717x93x717
Filter / Safety Grille
24/750
Cooling *2)
Heating *3)
MR-AH01MR-BH01MWR-WS00MWR-TH01 MWR-SH00
Panel
2008 SAMSUNG DVM Air Conditioners Indoor Units
Indoor Units - Cassette type 80 81
New Turbo Fan
Stylish Panel DesignThe stylish panel is well harmonized with any interior design.
WIDE BLADE
FRESH AIR INTAKE
SUB DUCTQUICK CONNECTION OF DRAIN PIPE
CEILING SOILINGPREVENTION
HIGH LIFT-UP DRAIN PUMPWIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH
FRESHFRESHFRESHFRESH SUB DUCTSUB DUCTSUB DUCTSUB DUCT QUICKQUICKQUICKQUICK
Individual Controllers
PanelOptionalAccessories
Quiet OperationImagine a room of cool calmness. The aerodynamicallydesigned ‘Turbo Fan' minimizes noise from the turbulence of blade movement. Therefore noise isless than conventional models.
Uniform DistributionThe new 'Turbo Fan' with wide blades providesextreme cooling and heating power from 4 separate outlets so the entire room gets cool orwarm faster. Now, every nook and cranny is comfortable.
Easy LevelingEach corner portion of the panel is detachable, which gives easieraccess to adjust the height, therefore leveling and installation ismuch easier and quicker than before.
Compact SizeThe 4Way cassette type unit has gotten even slimmer. Nowonly 218mm thick (5.2/7.0/9.0kW), 24% slimmer compare tocompetitor’s 288mm (9.0kW). It's still the industry leader in compactness and is even easier to install in tight spaces.
Efficient Cooling3-dimensional blade, which has the world wide patent, is able to spread cool or warm air further and evenly toall corners of the space.
Conventional 4Way
Conventional 4Way
New 4Way
New 4Way
‘A’ View
‘B’ View
‘C’ View
Detachable corners make installationand height adjustments much easier.
Air distribution
Detaching the whole panel tookmore time.
218mm
••• Powerful and Silent •••
4Way Cassette
P4SMA
Indoor Units
Air distribution
MR-AH01MR-BH01MWR-WS00MWR-TH01 MWR-SH00
Outlet1
Outlet2
Outlet3
Outlet4
2008 SAMSUNG DVM Air Conditioners Indoor Units
Indoor Units - Cassette type 82 83
Specification | 4Way Cassette
Indoor Units
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Panel Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Model
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Drain Pump (Pumping speed / lift)
AVXC4H045EEModel
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
kg
kg
mm
mm
-
l/h /mm
1/220~240/50
HP/HR
4.5
15,300
5.0
17,000
40
0.19
34/29
Turbo Fan
14.5
16.5
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
25.0
31.0
840x218x840
926x280x926
P4SMA
7.0
10.3
950x35x950
1,042x103x1,042
Filter / Safety Grille
24/750
AVXC4H056EE
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
40
0.19
34/29
Turbo Fan
14.5
16.5
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
25.0
31.0
840x218x840
926x280x926
P4SMA
7.0
10.3
950x35x950
1,042x103x1,042
Filter / Safety Grille
24/750
AVXC4H071EE
1/220~240/50
HP/HR
7.1
24,200
8.0
27,200
45
0.21
36/30
Turbo Fan
17.0
18.5
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
25.0
31.0
840x218x840
926x280x926
P4SMA
7.0
10.3
950x35x950
1,042x103x1,042
Filter / Safety Grille
24/750
AVXC4H090EE
1/220~240/50
HP/HR
9.0
30,700
10.0
34,100
50
0.23
39/32
Turbo Fan
19.5
21.5
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
25.0
31.0
840x218x840
926x280x926
P4SMA
7.0
10.3
950x35x950
1,042x103x1,042
Filter / Safety Grille
24/750
Cooling *2)
Heating *3)
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Panel Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Model
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Drain Pump (Pumping speed / lift)
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
kg
kg
mm
mm
-
l/h /mm
AVXC4H112EE AVXC4H128EE AVXC4H140EE
1/220~240/50
HP/HR
11.2
38,200
12.5
42,600
50
0.23
40 / 33
Turbo Fan
23.0
26.5
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
29.0
35.0
840x298x840
926x360x926
P4SMA
7.0
10.3
950x35x950
1,042x103x1,042
Filter / Safety Grille
24/750
1/220~240/50
HP/HR
12.8
43,600
13.8
47,000
65
0.30
41 / 35
Turbo Fan
25.0
29.5
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
29.0
35.0
840x298x840
926x360x926
P4SMA
7.0
10.3
950x35x950
1,042x103x1,042
Filter / Safety Grille
24/750
1/220~240/50
HP/HR
14.0
47,700
16.0
54,500
80
0.36
45 / 38
Turbo Fan
26.5
32.0
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
29.0
35.0
840x298x840
926x360x926
P4SMA
7.0
10.3
950x35x950
1,042x103x1,042
Filter / Safety Grille
24/750
Cooling *2)
Heating *3)
Indoor Units - Duct type
2008 SAMSUNG DVM Air Conditioners Indoor Units
84 85
Duct typeAir conditionersSamsung's new duct type air conditioners offer flexible installation benefits with its slim,compact size and the option to set up the air inlet either on the bottom or rear of theunit. Its Smart Pressure Control System also provides consistent cool and warm airregardless of the surrounding environment, and the filtering options give you cleaner,healthier air. Enjoy more with Samsung.
Duct type Icon
ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA
EASY FILTER CLEANING
HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH
SMART PRESSURECONTROL
Clean Filter SystemThe anti-bacteria filter and the filter cleaning indicator provide you with cleaner, healthier air. You deserve to breathe fresh air everyday.
Anti-bacteria FilterThe anti-bacteria filter not only traps dust particles, butsuppresses proliferation of molds and bacteria.
BACTERIABACTERIABACTERIABACTERIA Easy Filter CleaningAfter 1,000 hours of operation the filter clean indicatorwill inform you that the filter should be cleaned. The filter can be easily removed from the bottom, left, or rightof the unit. (1,000 hours is the default set time, whichcan be adjusted to 2,000 hours on the internal PCB.)
High Lift-up Drain Pump (optional)The lift-up drain pump lifts condensed water up to 750mm, compared to the competitor’s 700mm, allowing for flexible and convenient installation.
HIGHHIGHHIGHHIGH
Smart Pressure ControlThe Smart Pressure Control System adjusts fan speed according toE.S.P(External Static Pressure), so the air conditioner always givesyou consistent cooling and heating power regardless of the surrounding environment.
E.S.P Control
Air v
olum
e
Static pressure (mmAq)Minimum Maximum
H
H
M
M
L
L
Air volume 1mmAq Air volume 3mmAq
Indoor Units
Slim DesignOnly 199mm thick, this slim design makes installation, maintenance,and repair easy.
Easy to MaintainParts are easily accessible by simply opening the bottompanel, which reduces time and maintenance costs.
199mm
••• Slim and Flexible •••
Slim Duct
Indoor Units - Duct type
2008 SAMSUNG DVM Air Conditioners Indoor Units
86 87
Indoor Units
ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA
EASY FILTER CLEANING
HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH
SMART PRESSURECONTROL
Flexible InstallationThe air inlet can be set up on either the bottom or rearof the unit, so there is more flexibility in installation.
Individual Controllers
OptionalAccessories
Specification | Slim Duct type
Drain Pump
MDP-E075SEE / MDP-E075SEE1
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Optional
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
External Static Pressure
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Duct Receiver Kits
Drain Pump
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
mmAq
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
-
-
Cooling *2)
Heating *3)
Standard(Min.~Max.)
Receiver
Receiver Wire
AVXDSH022EE
1/220~240/50
HP/HR
2.2
7,500
2.5
8,500
80
0.40
31 / 26
Sirocco Fan
8.0
9.0
2 (0~4)
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
26.0
31.0
900x199x600
1,133x333x722
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE
AVXDSH028EE
1/220~240/50
HP/HR
2.8
9,500
3.2
10,900
80
0.40
32 / 27
Sirocco Fan
9.0
10.0
2 (0~4)
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
26.0
31.0
900x199x600
1,133x333x722
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE
AVXDSH036EE
1/220~240/50
HP/HR
3.6
12,200
4.0
13,600
80
0.40
32 / 27
Sirocco Fan
10.0
12.0
2 (0~4)
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
26.0
31.0
900x199x600
1,133x333x722
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE
MR-AH01MR-BH01MWR-WS00MWR-TH01 MWR-SH00
Rear side air inlet Bottom side air inlet
Suction DuctSuction Duct
TexTexDiffuser
Diffuser
199mm
220mm
225mm
160 180 200 220210 230
Indoor Units - Duct type
2008 SAMSUNG DVM Air Conditioners Indoor Units
88 89
Indoor Units
Specification | Slim Duct type
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Optional
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
External Static Pressure
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Duct Receiver Kits
Drain Pump
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
mmAq
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
-
-
Cooling *2)
Heating *3)
Standard(Min.~Max.)
Receiver
Receiver Wire
AVXDSH045EE
1/220~240/50
HP/HR
4.5
15,300
5.0
17,000
90
0.60
33 / 30
Sirocco Fan
14.5
16.5
2 (0~4)
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
31.0
39.0
1,100x199x600
1,330x330x730
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE
AVXDSH056EE
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
100
0.60
33 / 30
Sirocco Fan
15.5
18.0
2 (0~4)
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
31.0
39.0
1,100x199x600
1,330x330x730
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE
AVXDSH071EE
1/220~240/50
HP/HR
7.1
24,200
8.0
27,200
120
0.60
36 / 32
Sirocco Fan
16.5
20.0
2 (0~4)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
31.0
39.0
1,100x199x600
1,330x330x730
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Optional
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
External Static Pressure
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Duct Receiver Kits
Drain Pump
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
mmAq
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
-
-
Cooling *2)
Heating *3)
Standard(Min.~Max.)
Receiver
Receiver Wire
AVXDSH090EE
1/220~240/50
HP/HR
9.0
30,700
10.0
34,100
170
0.96
40 / 36
Sirocco Fan
29.0
34.0
3 (0-6)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
43.0
51.5
1,300x295x690
1,600x444x831
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE1
AVXDSH112EE
1/220~240/50
HP/HR
11.2
38,200
12.5
42,600
170
0.96
40 / 36
Sirocco Fan
31.2
34.0
3 (0~6)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
43.0
51.5
1,300x295x690
1,600x444x831
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE1
AVXDSH128EE
1/220~240/50
HP/HR
12.8
43,600
13.8
47,000
200
1.13
41 / 38
Sirocco Fan
34.0
36.0
3 (0~6)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
46.0
54.5
1,300x295x690
1,600x444x831
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE1
AVXDSH140EE
1/220~240/50
HP/HR
14.0
47,700
16.0
54,500
220
1.24
41 / 38
Sirocco Fan
36.0
38.0
3 (0~6)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
46.0
54.5
1,300x295x690
1,600x444x831
Filter (Washable)
MRK-A00
MRW-10A
MDP-E075SEE1
••• Flexible and Silent•••
MSP Duct
Indoor Units - Duct type
2008 SAMSUNG DVM Air Conditioners Indoor Units
90 91
Indoor Units
Individual Controllers
OptionalAccessories
Specification | MSP Duct type
Drain Pump
Easy to MaintainReduce time and maintenance costs by keeping parts easilyaccessible.
Flexible InstallationSamsung's MSP Duct air conditioners offer different solutionsfor any shape room allowing for specific airflow requirements.
L-shaped area Y-shaped areaAreas far apart
Silent Operation with the static pressure controlThe external static pressure control makes it easy to design duct work to ensure efficiency and silent operation.
Narrow Width (5.6kW) Middle Static Pressure
900mmSlim Duct
mmAq
2
4
6
8
10
MSP Duct
0~10mmAq
0~6mmAq
ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA
EASY FILTER CLEANING
HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH
SMART PRESSURECONTROL
WIRED REMOTE CONTROLLERWiredWiredWiredWired
MDP-M075SGU1 / MDP-M075SGU2 /MDP-M075SGU3
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Optional
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
External Static Pressure
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Duct Receiver Kits
Drain Pump
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
mmAq
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
-
-
Cooling *2)
Heating *3)
Standard(Min.~Max.)
Receiver
Receiver Wire
AVXDUH056EE
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
240*5)
1.2*5)
39 / 35
Sirocco Fan
14.5
15.5
4 (0~6)
R410A
EEV
6.35
12.70
VP25 (OD 32,ID 25)
31.0
36.0
900x260x480
1,146x345x584
Filter
(Washable)
MRK-A00
MRW-10A
MDP-M075SGU3
AVXDUH071EE
1/220~240/50
HP/HR
7.1
24,200
8.0
27,200
240*5)
1.2*5)
39 / 35
Sirocco Fan
18.5
20.0
4 (0~6)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
31.0
36.0
900x260x480
1,146x345x584
Filter
(Washable)
MRK-A00
MRW-10A
MDP-M075SGU3
AVXDUH112EE
1/220~240/50
HP/HR
11.2
38,200
12.5
42,600
260
1.17
39 / 35
Sirocco Fan
27.0
27.0
8 (6~10)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
39.0
46.0
1,150x320x480
1,390x420x584
Filter
(Washable)
MRK-A00
MRW-10A
MDP-M075SGU1
AVXDUH090EE
1/220~240/50
HP/HR
9.0
30,700
10.0
34,100
240*5)
1.2*5)
39 / 35
Sirocco Fan
19.5
21.5
6 (4~8)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
35.0
41.0
1,150x260x480
1,390x345x584
Filter
(Washable)
MRK-A00
MRW-10A
MDP-M075SGU1
AVXDUH128EE
1/220~240/50
HP/HR
12.8
43,600
13.8
47,000
370
1.67
39 / 35
Sirocco Fan
32.0
31.0
8 (6~10)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
52.0
60.0
1,200x360x650
1,447x425x769
Filter
(Washable)
MRK-A00
MRW-10A
MDP-M075SGU2
AVXDUH140EE
1/220~240/50
HP/HR
14.0
47,700
16.0
54,500
410
1.86
43 / 38
Sirocco Fan
37.0
36.0
8 (6~10)
R410A
EEV
9.52
15.88
VP25 (OD 32,ID 25)
52.0
60.0
1,200x360x650
1,447x425x769
Filter
(Washable)
MRK-A00
MRW-10A
MDP-M075SGU2
❊ Width measured without control box.
MR-AH01MR-BH01MWR-WS00MWR-TH01 MWR-SH00
Indoor Units - Floor & Convertible type
2008 SAMSUNG DVM Air Conditioners Indoor Units
92 93
Indoor Units
Floor & Convertible typeAir conditionersSamsung introduces a new elegance in air conditioners. This year's new console andceiling type air conditioners have the style to complement any decor. The flexibility ofdrain pipe placement also gives you more options in where you want to place the airconditioner. Staying cool has never been more stylish.
Floor & Convertible type Icon
INTERIORDESIGNINTERIORINTERIOR
DESIGNDESIGNINTERIORINTERIORDESIGNDESIGN
ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA
LIGHT WEIGHT UNIT
LIGHTLIGHTLIGHTLIGHT
SILENTMODE
FLEXIBLE PIPE INSTALLATIONFlexible PipeFlexible Pipe
InstallationInstallationFlexible PipeFlexible PipeInstallationInstallation
WIRELESS REMOTECONTROLWirelessWirelessWirelessWireless
I Interior DesignNow with more flexibility in placement, the air conditionercan add a stylish element to your room.
INTERIORINTERIORDESIGNDESIGN
INTERIORINTERIORDESIGNDESIGN
Silent ModeIndoor units operate quietly with the least possible noise.
Anti-bacteria FilterThe anti-bacteria filter not only traps dust particles, butsuppresses proliferation of molds and bacteria.
BACTERIABACTERIABACTERIABACTERIA
Light Weight UnitThis extremely lightweight design makes maintenanceand installation easy.
LIGHTLIGHTLIGHTLIGHT
Flexible Pipe InstallationThe drain pipe can be installed in 6 different places, so youhave more options in where to place your air conditioner.
Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation
Indoor Units - Floor & Convertible type
2008 SAMSUNG DVM Air Conditioners Indoor Units
94 95
Indoor Units
OptionalAccessories
Elegant Design
••• Slim and Elegant •••
Console
INTERIORDESIGNINTERIORINTERIOR
DESIGNDESIGNINTERIORINTERIORDESIGNDESIGN
ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA
LIGHT WEIGHT UNIT
LIGHTLIGHTLIGHTLIGHT
SILENT MODEFLEXIBLE PIPEINSTALLATIONFlexible PipeFlexible Pipe
InstallationInstallationFlexible PipeFlexible PipeInstallationInstallation
Individual Controllers
MWR-WS00
Clean PanelStay clean with the smartly designed Clean Panel. This uniquepanel keeps dust from being accumulated so the unit and theroom stays cleaner.
Slim DesignIt can't get any slimmer. This newly introduced console type airconditioner is only 199mm thick, the slimmest on the market.Its slim design easily integrates the unit into your decor.
Silent Operation (23dB)The silent, yet powerful and efficient cooling and heating system keeps things morecomfortable. Silent mode is available in 4 different operating modes: High / Medium /Low / Silence.
2Way air outletsThere are two separate air outlets for cooling and heating. Having warmer air comingout from the bottom part of the air outlet will spread the warm air evenly throughout theroom. Stay cooler and warmer in every corner of your room.
Slim & Smart DesignThis extremely slim design with Clean Panel adds aesthetic value to any interior.
199mm
Black DisplayFunctional art, the touch screen display is elegant while itmaximizes the convenience of control.
MWR-TH01
WIRELESS REMOTECONTROLWirelessWirelessWirelessWireless
MWR-SH00 ARH-1379
2008 SAMSUNG DVM Air Conditioners Indoor Units
Indoor Units - Floor & Convertible type 96 97
Specification | Console
Indoor Units
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Wireless Remote Controller
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
AVXTJH028EE
1/220~240/50
HP/HR
2.8
9,500
3.2
10,900
30
0.25
38 / 23 *5)
Turbo Fan
7.8*5)
7.2*5)
R410a
EEV
6.35
12.70
ID 18 hose
15.0
19.0
720x620x199
810x710x295
Filter (Washable)
AHR-1379
Cooling *2)
Heating *3)
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Wireless Remote Controller
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
AVXTJH036EE
1/220~240/50
HP/HR
3.6
12,200
4.0
13,600
35
0.29
39 / 24 *5)
Turbo Fan
8.7*5)
8.9*5)
R410a
EEV
6.35
12.70
ID 18 hose
15.0
19.0
720x620x199
810x710x295
Filter (Washable)
ARH-1379
Cooling *2)
Heating *3)
Compact but PowerfulSamsung’s ceiling type air conditioner boasts a slim, compactdesign, half the size of its competitors, with cooling powercomparable to competitor’s larger products.
2way InstallationDepending on the space availability and the purposeof the air conditioner, the indoor unit can be installedunder the ceiling or on the floor.
••• Slim and Compact•••
Ceiling
Indoor Units - Floor & Convertible type
2008 SAMSUNG DVM Air Conditioners Indoor Units
98 99
Indoor Units
OptionalAccessories
INTERIORDESIGNINTERIORINTERIOR
DESIGNDESIGNINTERIORINTERIORDESIGNDESIGN
ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA
LIGHT WEIGHT UNIT
LIGHTLIGHTLIGHTLIGHT FLEXIBLE PIPEINSTALLATIONFlexible PipeFlexible Pipe
InstallationInstallationFlexible PipeFlexible PipeInstallationInstallation
MR-AH01
Individual Controllers
MR-BH01MWR-WS00
Specification | Ceiling
Notes
*1) Mode: HP: Heat Pump, HR: Heat Recovery*2) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,
Equivalent refrigerant piping: 7.5m, Level differences: 0m*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Specifications are subject to change without prior notice for product improvement.*6) Optional Accessory.
Power Source
Mode *1)
Performance
power
Sound
Fan
Airflow Rate
Refrigerant
Piping
Connections
Weight
Set Size
Standard
Accessories
Capacity
Input
Running Current
Sound Pressure (High/Low) *4)
Type
Cooling (High)
Heating (High)
Type
Control Method
Liquid (Flare)
Gas (Flare)
Drain (Quick Lock)
Net Weight
Shipping Weight
Net Dimensions (WxHxD)
Shipping Dimensions (WxHxD)
Filter / Safety Grille
Wireless Remote Controller
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
W
A
dB(A)
-
m3/min
m3/min
-
-
Ø,mm
Ø,mm
Ø,mm
kg
kg
mm
mm
-
-
AVXTFH056EE AVXTFH071EE
1/220~240/50
HP/HR
5.6
19,100
6.3
21,400
72
0.33
38 / 32
Sirocco Fan
14.0
14.5
R410a
EEV *6)
6.35
12.70
ID 18 hose
22.0
26.0
1,000x650x200
1,074x726x294
Filter (Washable)
-
1/220~240/50
HP/HR
7.1
24,200
8.0
27,200
80
0.35
41 / 36
Sirocco Fan
18.0
18.5
R410a
EEV *6)
9.52
15.88
ID 18 hose
22.0
26.0
1,000x650x200
1,074x726x294
Filter (Washable)
-
Cooling *2)
Heating *3)
Under Ceiling Floor Standing
MWR-TH01
200%
100%
136%
118% 123%
100%
Size
7.1kW Model
Weight
Smaller Lighter
MWR-SH00
2008 SAMSUNG DVM Air Conditioners Indoor Units
100 101
Indoor Units
Indoor Units
Indoor Units - ERV System
How it Works
Key Technology
New Diamond Type● Optimized Airflow Design
● High Efficiency Element
● Compact size
Automatic Refresh System (CO2 Sensor) : Optional● ERV is automatically operated to give fresh air into room by sensing CO2 Level.
High Efficiency Motor (BLDC)● Constant air volume by BLDC motor.
Intelligent Operating System (-15˚C) Without Heater
ERV SystemEnergy Recovery Ventilator
WinterIt reduces the costs of heating ventilated air by transferring heatfrom the warm inside air being exhausted to the fresh (but cold)supply air.
SummerThe inside air cools the warmer supply air to reduce ventilationcooling costs.
Samsung’s ERV System has applied the cross flow ventilating method whichassure you efficient ventilation and energy saving. Furthermore, ERV System hasadopted total heat exchange (sensible heat + latent heat) as a heat recoveryprocess that helps maintaining indoor temperature and humidity and minimizingindoor heat loss caused by ventilation
Heat
Heat
HeatHeat
Heat
Heat
Cool
Cool Cool
Cool Cool
CoolCool
IndoorOutdoor
Element
Rectangular Type
Diamond Type
Hexagonal Type
Indoor Units - ERV System
2008 SAMSUNG DVM Air Conditioners Indoor Units
102 103
Indoor Units
Indoor Units
Energy Saving Operation (Auto Mode)
Extreme Climates (Winter & Summer)When temperature and humidity level difference between indoor andoutdoor is big, it operates as ERV.
Mild Climates (Spring & Fall)When temperature and humidity level difference between indoor andoutdoor is small, it operates as conventional ventilation fan.
It automatically changes operation mode depending on temperature difference between indoorand outdoor to save energy.
Element
EA
OA
EA
OA
RA
SA
RA
SA
Element
Damper
Damper
Specification | ERV System
Line-upRHF025EE
250
RHF035EE350
RHF050EE500
RHF080EE800
RHF100EE1,000
Voltage
Frequency
Withstand Voltage
Insulation Resistance
Air Volume
External Static Pressure
Leakage Rate
Power Input
Current
Temperature Exchange
Efficiency
Effective Enthalpy
Exchange Efficiency
Sound Level
Dust Collection Method
Dimensions (Net)
Dimensions (Gross)
Weight (Net/Gross)
Duct Diameter
Cooling
Heating
Cooling
Heating
WxHxD
WxHxD
Model
V
Hz
-
-
m3/hr
Pa
%
W
A
%
%
%
%
dB(A)
-
mm
mm
kg
Ø,mm
RHF025EE
220~240
50/60
AC1500V, 1min
30MG
250
110
10
115
0.7
70
70
50
70
38
High efficiency filter(PP)
600X350X660
760X400X807
25.5/30
150
→
→
→
→
RHF035EE
220~240
50/60
AC1500V, 1min
30MG
350
155
10
115
0.7
70
70
50
70
40
High efficiency filter(PP)
1,012X270X1,000
1,299X337X1,183
42.5/53.5
200
RHF050EE
220~240
50/60
AC1500V, 1min
30MG
500
165
10
175
1.1
70
70
50
70
42
High efficiency filter(PP)
1,012X270X1,000
1,299X337X1,183
42.5/53.5
200
RHF080EE
220~240
50/60
AC1500V, 1min
30MG
800
155
10
330
2.1
70
70
50
70
46
High efficiency filter(PP)
1,220X340X1,135
1,475X 440 X1,330
67/75.5
250
RHF100EE
220~240
50/60
AC1500V, 1min
30MG
1,000
155
10
450
2.9
70
70
50
70
48
High efficiency filter(PP)
1,220X340X1,135
1,475X440X1,330
67/75.5
250
→
→
→
→
→
→
Compact Size & Flexible Installation● Compact and Slim in Size by High Efficiency Diamond Element.
Ex.) Model No. RHF-035~050
Indoor Units - Accessories
2008 SAMSUNG DVM Air Conditioners Indoor Units
104 105
Indoor Units
MXJ-YA1509K
MXJ-YA2512K
MXJ-YA2812K
MXJ-YA2815K
MXJ-YA3119K
MXJ-YA3819K
MXJ-YA4422K
MXJ-HA2512K
MXJ-HA3115K
MXJ-HA3819K
MXJ-YA1500K
MXJ-YA2500K
MXJ-YA3100K
MXJ-YA3800K
MXJ-T3819K
MXJ-T4422K
MXJ-T3100K
MXJ-T3800K
MCU-4EAE1
MCU-4EAEV1
MCU-6EAE1
15.0kW and below
Over 15.0 ~ 40.6kW and below
Over 40.6 ~ 46.4kW and below
Over 46.4 ~ 69.6kW and below
Over 69.6 ~ 98.6kW and below
Over 98.6 ~ 139.2kW and below
Over 139.2kW
Below 46.4kW
46.5 ~ 69.6kW
Over 69.7kW
23.2kW and below
Over 23.2 ~ 63.9kW and below
Over 69.6 ~ 139.2kW and below
Over 139.3kW
Below 48HP
Over 50HP
Below 48HP
Over 50HP
Below 4 indoor units
Below 4 indoor units *1)
Below 6 indoor units
Requisite
Option
Requisite
Requisite
Requisite
Requisite(HR only)
DVM PLUS II,
DVM PLUS II HR
DVM PLUS III,
DVM PLUS III HR
DVM PLUS II,
DVM PLUS II HR
DVM PLUS III,
DVM PLUS III HR
DVM PLUS II, DVM PLUS
II HR, DVM PLUS III, DVM
PLUS III HR (Module)
DVM PLUS III HR
DVM PLUS III HR
(Module)
DVM PLUS II HR,
DVM PLUS III HR
Y-Joint
Header Joint
Y-Joint(Only for DVM PLUS IIIHR in high pressure gasconnection)
Outdoor Joint for DVM PLUS III / HR (Outdoor Connection)
Outdoor Joint only for DVM PLUS III HR Module(High Pressure GasConnection)
MCU Kits
ModelFeatureClassification Description Relevant Unit Remark
MXD-A13K116A
MXD-A13K200A
MXD-A16K200A
MXD-A22K200A
MXD-A13K216A
MXD-A13K300A
MXD-A16K213A
MXD-A16K300A
MEV-A13SA
MEV-A16SA
MDP-E075SEE
MDP-E075SEE1
MDP-M075SGU1
MDP-M075SGU2
MDP-M075SGU3
PSSMA
P2SMA
P4SMA
PMSMA
Below 3.6kW (1 Room) +
5.6 kW~9.0kW (1Room)
Below 3.6kW (2 Rooms)
5.6 kW~9.0kW (2Rooms)
5.6 kW~7.1kW (2Rooms)
Below 3.6kW (2 Rooms) +
5.6 kW~9.0kW (1Room)
Below 3.6kW (3 Rooms)
Below 3.6kW (1 Room) +
5.6 kW~9.0kW (2Rooms)
5.6 kW~9.0kW (3Rooms)
Below 3.6kW (1 Room)
5.6 kW~9.0kW (1Room)
Slim Duct (2.2~7.1) kW
Slim Duct (9.0~14.0) kW
M.S.P Duct (9.0, 11.2) kW
M.S.P Duct (12.8, 14.0) kW
M.S.P Duct (5.6, 7.1) kW
Slim 1 Way Cassette
2 Way Cassette
4 Way Cassette
Mini 4 Way Cassette
Option
Option
Option
Option
Requisite
EEV Kits
Drain PumpDrain Pump
Front Panel
ModelFeatureClassification Description Relevant Unit Remark
Accessories
Wall-mounted &
Ceiling indoor unit
(For 2 indoor units)
Wall-mounted &
Ceiling indoor unit
(For 3 indoor units)
Wall-mounted &
Ceiling indoor unit
(For single unit)
-
-
Notes
*1) MCU-4EAEV1 is the product that includes built in EEV to connect the indoor unit (wall-mounted type and ceiling type) that does notinclude EEV.
Effective and complete control systems are here. Samsung’s control systems are easy tocontrol, simple and user-friendly. These effective and convenient control systems will not onlycontrol but also monitors, manages and maintain all the information of your air conditioner.Complete control, in your hands.
Control Systems
>> 108_ Integrated Management System >> 116_ Centralized Control System >> 118_ Individual Control System
>> 120_ Building Management System >> 123_ Accessories
imaginethe complete control
106 107
ControlSystems
Control S
ystems
Control Systems - Integrated Management System
2008 SAMSUNG DVM Air Conditioners Control Systems
108 109
Control S
ystems
IntegratedManagement SystemSamsung’s Integrated Management System provides the
easiest and most convenient way to manage a large number
of air conditioning units at once. This Integrated Management
System will help you control, monitor, manage and maintain
every little detail of your air conditioning needs.
Samsung's Data Management Server (DMS) lets you monitor and control your on-site air conditioningneeds remotely. It's the easiest and most convenient way to manage a large number of air conditioningunits at once.
Data Management Server
DMS
Easy Control & Monitoring
Web Server Function
Schedule Control Function
Power Distribution System
Building Management System
MIM-D00• Built-in web server for PC-independent management and remote access control
• Multiple upper-layer control access (S-NET 3, S-NET Mini, Web-client)
• Individual/Group control of up to 256 indoor units and heat exchange units
• Error history management
• Weekly/Daily schedule control
• Power distribution function
• 2 digital inputs, 2 digital outputs
• Current time management even during power failure (for 24 hours)
• Data storage in non-volatile memory
• Emergency stop function with simple contact interface
CentralizedController
DMS
Interface Module
Interface Module
Interface Module
CentralizedController
SIM Watt HourMeter
Control Systems - Integrated Management System 110 111
Main Features
Easy Control & Monitoring• Individual/Group control and monitoring up to 256 indoor units.
• Operation mode, temperature setting, airflow direction and
fan speed.
• Wireless/wired remote control restriction.
• Easy multiple/full indoor unit selection.
• Full room temperature display.
• Error history query based on date.
Web Server Function• Built-in web server.
• Multiple upper-layer control access with prioritized management.
• Remote access control with the static IP address.Internet
Anytime, Anywhere Control
2008 SAMSUNG DVM Air Conditioners Control Systems
360kWh
460kWh
140kWh
610kWh
180kWh
Cooling Schedule Setup
Power Distribution System• Power distribution to up to 256 indoor units.
• Data query for watt-hour, use time and use ratio.
• File save in Microsoft Excel format.
• 93 days worth of power distribution data storage.
08:00 AM On 10:00 PM Off
External Contact Interface• Full indoor unit control with simple contact input. (Emergency/Lock)
• State output (Operation/Error) for synchronous control.
Schedule Control Function
DMS System
• Up to 256 schedule settings.
• Weekly, Daily or 1-Day schedule control.
• Exception date setting.
History Management• Easy service and management with error history.
• Occurrence date, error details, current state.
Building Control System
Rapid Service Response
Error History Monitoring
Fire Control System Error Status Indicator
Operation Restriction
Service
Control S
ystems
Control Systems - Integrated Management System 112 113
Control S
ystems
Control and Monitoring• Control & monitoring of up to 4,096 indoor units
• Heat exchange unit management
• Wireless/wired remote control restriction
• Temperature limit setting
• Multiple/full indoor unit selection
• Icon-based indoor unit display mode
Schedule Control• Graphical schedule settings
• Weekly, Daily schedule control
• Exception date setting
Main Features
• Fully integrated PC management software.
• Up to 16 DMSs connection through the Ethernet.
• Centralized management up to 4,096 indoor/heatexchange units.
• Schedule/Zone control.
• Error/Operation history management.
• Power distribution management and analysis.
• Automatic update through the Internet.
S-NET 3
S-NET 3
Supports 16 DMSs ▼
Max. 16 units
Smart Net Control SystemS-NET is a complex management program that controls and monitors a complete air conditioner networksystem. The S-NET series provides flexible and complete control for a variety of applications.
Zone Management• Management structure customization regardless of installation structure• Control zone creation/edition/deletion• Tree structure zone management control
Power Distribution Management• Data query for power distribution and operation time
• Power distribution report generation and print
• Time section setting for different electricity rates
• Group setting for power distribution summation
History Management• Error/Event history management
• Indoor unit operation history management
• Report generation and print
Cycle monitoring• Monitoring outdoor / indoor unit cycle data
(Supported for specific outdoor unit models)
2008 SAMSUNG DVM Air Conditioners Control Systems
2008 SAMSUNG DVM Air Conditioners Control Systems
Control Systems - Integrated Management System 114 115
Control S
ystems
• Dynamic compatibility options (DMS, centralized controller, interface module)• Control and monitoring of up to 256 indoor units• Detailed cycling information monitoring• Schedule function (Weekly, Daily)• USB keyboard supported • Error display • 7-inch wide LCD restriction • Temperature limit setting • Touch screen• Zone control• Child-lock setting
S-NET mini
Supports 16
InterfaceModules
▼
Supports 4 DMSs ▼
Supports 16
CentralizedControllers
▼
Control and monitoring
Dynamic Compatibility Option
• Control & Monitor up to 256 indoor units• Operation control and monitoring• Detailed operation cycling information monitoring• Wireless/wired remote control restriction setting
Schedule Control• Maximum 256 Weekly, Daily schedule control
• Schedule repetition, exception date setting
• Schedule edit (add, edit, delete)
• Detailed operation schedule setting
• Remote control restriction option setting
Main Features
Zone Management• Management structure customization regardless of installation structure • Control zone creation/edition/deletion
Temperature Limit Setting• Upper/Lower temperature limit setting
Cycle Monitoring• Outdoor/Indoor unit cycling information monitoring
(supported for specific outdoor unit models)
Error Management• Error history management• Error management information query• Detailed error information query
2008 SAMSUNG DVM Air Conditioners Control Systems
Control Systems - Centralized Control System 116 117
Control S
ystems
CentralizedControl SystemSamsung's advanced technology has come up with the centralized
control that is convenient and efficient. Samsung's centralized control
system can control and monitor 4,096 individual indoor units and 256
groups of indoor units simultaneously.
Function Icon
ON/OFF, OPERATION MODE, FAN SPEED,AIRFLOW, TEMPERATURE SETTING
OperationOperationOperationOperation INDIVIDUAL AND GROUP CONTROL (MAXIMUM 16 INDOOR UNITS)
GroupGroupGroupGroup
ERROR DISPLAYErrorErrorErrorError
FILTER REPLACEMENT ALARM RESETFilterFilterFilterFilter
MCM-A202A
• Maximum 16 group controls (Maximum 256 Indoor units)• Unified/Individual indoor unit control (On/Off)• Wireless/wired remote control restriction• Cooling/Heating mode control• Indoor unit error display
Centralized ControllerMCM-A100
• Control and monitoring of up to 16 indoor unit groups
Function Controller
• Communicator between indoor/outdoor units andthe centralized controller
Interface ModuleMIM-B13A
• Operation mode selection (Cooling, Heating or Auto) • Mixed operation mode protection
Operation Mode Selection SwitchMCM-C200
MIM-B04A
To use Function Controller, it requires to be connected to MCM-A202A
OperationOperationOperationOperation ErrorErrorErrorError FilterFilterFilterFilter
S-NET II Plus• Indoor unit control of up to 256 groups• Extensive individual control of up to 4096 indoor units• Weekly and Daily schedule function• Zone setting and control• Dynamic exchange to Permitted and Prohibited wireless/wired remote control• Full/Group/Individual indoor unit display
256 group 4096 indoor units controls Zone controlSchedule controlIndividual control
Max. 16 units
RS232-RS485Converter
S-NET II Plus
2008 SAMSUNG DVM Air Conditioners Control Systems
Control Systems - Building Management System 120 121
Control S
ystems
BuildingManagement SystemBMS (Building Management System) makes it possible to control and
monitor the air conditioning network using the remote control and
monitoring function.
Optimum control keeps the air conditioning system efficient, saves energy,
reduces maintenance costs, and extends the life cycle of the units.
MIM-B07• Interface for Lon-Connection to Lonworks management system
• Quick and easy installation
• Up to 12 indoor units can be controlled
• Communication : 485 to Lonworks
• Upper physical layer : FTT-10A
BMS Control Function
• On/Off control• Temperature setting• Operation mode• Fan speed
Monitoring Function
• On/Off• Operation mode• Room temperature• Error information
Guest Room Management System
External Contact Interface Module
The Guest Room Management System is asmart way to save energy and money.When the Key Tag is in place, the air conditioneris activated. When the Key Tag is removed,the air conditioner turns off. Now you canavoid cooling an unoccupied room and saveenergy.
ON OFF
MIM-B14• Direct indoor unit control by external contact signal
• Window-synchronized indoor unit control
• Emergency control with simple contact input
• Indoor unit operation/error state output through relay contacts
MIM-B02• Indoor unit control by external contact signals
• Individual/Group control of up to 16 indoor units
• Combinational use with sensor/timer/emergency inputs
Room 501
Key-Holder
Room 502
Key-Holder
Room 503
Key-Holder
Room 504
Key-Holder
2008 SAMSUNG DVM Air Conditioners Control Systems
Control Systems - Individual Control System 118 119
Control S
ystems
IndividualControl SystemThere are many ways to control your air conditioner, but one
smart controller is all you need. Samsung provides several
different control options that can control one indoor unit to a
group of indoor units with one system.
Function Icon
ON/OFF, OPERATION MODE, FAN SPEED,AIRFLOW, TEMPERATURE SETTING
OperationOperationOperationOperation INDIVIDUAL AND GROUP CONTROL (MAXIMUM 16 INDOOR UNITS)
GroupGroupGroupGroup
ERROR DISPLAYErrorErrorErrorError
FILTER REPLACEMENT ALARM RESETFilterFilterFilterFilter
MWR-WS00 (Premium)
• Weekly schedule setting (Maximum 70 schedules)• Exception date setting• Built-in room temperature sensor• Clear and bright screen with LCD backlight• Temperature limit setting• Wireless remote control restriction• Automatic Stop mode • Sleep and Silent mode• Child lock
• Mode selection protection
MWR-TH01
Wired Remote Controller
MWR-SH00
Simplified wired remote controller
• Individual and group control (Maximum 16ERVs)
• On/Off control• Operation mode (By-Pass, Heat Exchange),
fan speed• Simple schedule control• Error display• Synchronous operation with indoor units
MWR-VH01
ERV Wired remote controller
• Simple schedule control• Wireless remote control restriction
OperationOperationOperationOperation GroupGroupGroupGroup ErrorErrorErrorError FilterFilterFilterFilter
OperationOperationOperationOperation GroupGroupGroupGroup ErrorErrorErrorError FilterFilterFilterFilter
• ON/OFF control• Operation indication• Error Indication• Filter replacement sign• Use with receiver wire, MRW-10A
MRK-A00
Wireless Signal Receiver (for Duct-type indoor unit)
• Up to 100 weekly and daily schedulesettings
• Schedule setting based on 1-minutetime units
• Digital clock display• Permanent schedule setting storage• Current time protection from blackout
(maximum 3 days)• Use with wired remote controller, or
centralized controller.(MWR-TH01, MCM-A202A)
MWR-BS00
7-day Scheduler
OperationOperationOperationOperation GroupGroupGroupGroup ErrorErrorErrorError FilterFilterFilterFilter
• Compact size• Simple schedule control• Soft touch button
MR-BH01 MR-AH01
• Simple schedule control• Wide display• Soft touch button
Wireless Remote Controller
OperationOperationOperationOperation FilterFilterFilterFilter OperationOperationOperationOperation FilterFilterFilterFilter
Room01(60kWh)
Room04(210kWh) 600kWh
Room03(210kWh)
Room02(120kWh)
RS 485
RS 485
Power Supply
2008 SAMSUNG DVM Air Conditioners Control Systems
Control Systems - Building Management System
Control S
ystems
Power Distribution Unit
MCM-B102• Real-time power distribution for one indoor/outdoor system.
• Power distribution to maximum 48 indoor units.
• Communication error display.
• Total system power consumption display.
• Power consumption display of individual indoor units.
• Data storage even during a power failure.
• Consult with Samsung Electronics for watt-hour meter interface
= x
Room01
Room02
Room03
Room04
40%
30%
20%
10%
0%Room01 Room02 Room03 Room04
20% 19.4%
35.0%35.3% 35.0%35.1%
Actual Usage Rate
Displayed Rate
10.2% 10.2%
Room 01 electric powerconsumption
Total powerconsumption
Demand capacityof Room 01
Total demand capacityof indoor units
• Exclusive use for DMS power distribution.• Connection with up to 8 watt-hour meters.• RS485 interface with watt-hour meters.• Power consumption display for each watt-hour meter.• Automatic detection of specified watt-hour meters.
MIM-B12
Watt-hour meter Interface Module
Classification Product Model Image Application Model
IntegratedManagementSystem
Controller
InterfaceModule
DMS MIM-D00 DVM Series, FJM, CAC, ERV
DVM Series, FJM, CAC, ERV
DVM Series, FJM, CAC
S-NET 3 MST-P3P
S-NET mini MST-S3W
DVM Series, FJMSiM MIM-B12
CentralizedControlSystem
InterfaceModule
S-NET II Plus MSP-S1P DVM, DVM HR, DVM PLUS II, DVM PLUS II HR, FJM, CAC
DVM Series, FJM, CAC, ERV
DVM Series, FJM, CAC
Mini DVM(R410A), DVM PLUS II, DVM PLUSII HR, DVM PLUS III, DVM PLUS III HR, FJM,ERV
MCM-A202A
Controller
Centralized Controller
MCM-A100Function Controller
MIM-B13ACentralized Control Interface Module
DVM, DVM PLUS, DVM HR, CACMIM-B04A
Accessories
DVM SeriesMCM-C200Operation Mode Selection Switch
DVM Series, FJMPower Distribution Unit
DVM Series : Mini DVM, DVM, DVM PLUS, DVM HR, DVM PLUS II, DVM PLUS IIHR, DVM PLUS III, DVM PLUS IIIHR
MCM-B102
Mini DVM(R410A), DVM PLUS II, DVM PLUS II HR, DVM PLUS III, DVM PLUS III HR (Non RAC/Console)
External Contact Interface Module MIM-B14
Building ManagementSystem
Lonworks Interface Module MIM-B07 DVM Series, FJM
Power Distribution
DVM Series, FJM Key-tag Interface Module MIM-B02Guest RoomManagementSystem
IndividualControlSystem
Controller Wireless Remote Controller MR-AH01MR-BH01
Cassette, Ceiling, Duct (Receiverneeded), Console (Included)
Cassette, Wall Mounted, Ceiling, Duct, Console
Cassette, Wall Mounted, Ceiling, Duct, Console
Duct (For Wireless Remote Controller)
Duct (For Wireless Remote Controller)
Cassette, Wall Mounted, Ceiling, Duct
Wired Remote Controller (Premium) MWR-WS00
Wired Remote Controller MWR-TH01
Cassette, Wall Mounted, Ceiling, Duct, Console
Simplified Wired Remote Controller MWR-SH00
ERVERV Wired Remote Controller MWR-VH01
Wireless SignalReceiver Kit
MRK-A00Wireless Signal Receiver
Receiver Wire MRW-10A
7-day Scheduler MWR-BS00