We are pleased to highlight some of the USP of DETECTOMAT Fire Alarm System as such,
√ DETECTOMAT, Germany is one of the most qualified manufacturer for a complete Fire Detection and Alarm System which has built over 600,000 industrial detectors, installed at many countries as because sensor alarming system and the fire-fighting system is “more sensitive, more accurate and more intelligent." √ The DETECTOMAT detectors are famous for their robust engineering design, stylish look and daily prove their quality and efficiency. It has highly touted VdS mark – and complies EN 54 Standard & LPCB approved.
√ Intelligent Detectors – Detectors with inbuilt - microprocessor √ DETECTOMAT Addressable Fire Alarm System has the capacity for 126 devices per loop with an overall loop length of 3,500 meters. √ DETECTOMAT Network devices can configure networks with up to 20 control panels. √ DETECTOMAT Detectors have Integrated T-branch and short circuit isolator √ DETECTOMAT Conventional Fire Alarm System has the capacity for 25- 30 devices per zone. √ Redundant host processor , Redundant loop card , Redundant Power Supply √ Detectors with Ambient Temperature of 60 Deg. C √ German is world known for its meteorology. √ We can provide After Sales Support as having trained man power for the Installation, Testing, Commissioning & Programming, as training is provided by DETECTOMAT. √ In house Product demonstration & training center for Programming and Installation, After sales service support. √ Product protocol matches to APOLLO protocol
DETECTOMAT Fire Alarm System & Equipments are Approved By - BHEL, NTPC- ANTA, RRVUNL, MAHAGENCO, Reliance, ADANI,
KPCL, ABB, VA Tech, DCPL, Desein, Fichtner , GSPL , NTPC- KAWAS
DETECTOMAT FIRE ALARM SYSTEM INSTALLATIONS IN INDIA
INDUSRIAL & POWER PLANT PROJECTS
• AREVA T&D LTD. - Kotambi, Baroda.
• AREVA RRVPNL- Indiranagar substation. • NTPC-Anta, Rajasthan.
• MAHAGENCO’s 1x 250 MW Paras TPS ( Unit 2)
• RRVUNL’s 1x250 MW Suratgarh Super Thermal power
Project • ADANI Power LTD - 4 x 330 MW Mundra, TPS.
• KPTCL’s 2 x 115 MW Varahi Hydroelectic Power Project
• Tata Nano Project-Sanand , Gujarat through ABB-Baroda
• MAHAGENCO’s 1X500 MW Khaperkheda TPS through BGR
-Chennai
• HI-TECH SILONG-Meghalaya State Electricity Board
COMMERCIAL PROJECT
• Reliance Industries Ltd.
Reliance PCS Center Naroda,Ahmedabad &
Reliance PCS Center Gurgoan , Delhi. • GSPL – Paguthan Terminal – Bharuch
• K. RAHEJA – Aquiline Properties – IT SEZ at KOBA , near
Gandhinagar
• NTPC-KAWAS
EXPORT PROJECTS
• Addressable Fire Alarm system for Anjelique Internation – Delhi for their Anjelique Internation – Zambia office.
• Conventional Fire Alarm system for Areva T & D – Noida for their client Kenya Electricity Board – Kenya
editing status: 2009-07-16
Properties:
� In accordance to EN 61000 - 6 - 3 class B for emissions, so suitable for the use in sensitive areas.
� Programming options for different alarm modes.
� Event log memory of up to 500 messages.
� Programming of control logics and time dependent functions for the components of series Loop 3000.
� Customized customer texts allowing up to a maximum of 20 characters.
� Simple menu structure in accordance to EN 54 - 2 A1 2006.
� Software controlled disablements for zones and individual detectors via external inputs.
� Connections for a fire brigade interface for controlling the panels outputs, key deposit and transmission units.
Product-Information Sheet
Type detect 3004plus
M GB Order No. 32551
Description:
Microprocessor controlled modular fire control panel
for the use with the Loop 3000 fire detection system
components. Approved according to EN 54 - 2 A1
2006, EN 54 - 4 A1 2002, A2 2006 and VdS for the
use according to VdE 0833.
Fire control panel detect 3004plus
, deep housing, language kit English
� Large LCD, 160 x 80 with backlight.
� Integrated display and control panel according to DIN EN 54 - 2 A1 2006.
126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m.
� Option for 2 conventional interface cards for controlling up to 16 conventional zones.
� Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to
EN 12094.
� 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of
� Integrated interface connection for up to 63 additional network components.
� Integrated control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
� Incl. English language kit for control and programming.
� Different access levels with password protection.
� Integrated "one-man-revision mode" with clear protocols and a revision counter.
� Visual diagnostics and remote-control operations via the visualization software "Visual detect".
� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.
� Integrated RS 232 - interface for the dpt software and the connection of printers and other
peripheral equipment.
� Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA.
� Monitored power supply unit and battery charging according to EN 54-4 A1 2002 and A2 2006
via the MC 3004 monitoring card.
� 1 external output 24 V / 400 mA monitored for sounding/signalling devices.
� 3 potential free relais for fire and fault.
� 3 inputs for collective signals.
� Ability to change and edit inspection and reaction times along with all delays.
� Emergency power supply via 2 batteries 12 V / up to 26 Ah.
� Integrated ground fault monitoring.
� Segmented front door allowing the quick assembly of LED indicator modules and printers.
� Option for customised front logos.
� Possibility for complete system redundancy with the CPU and loop interfaces.
� Up to 128 programmable detector zones.
� Up to 42 T-branches per loop possible.
� Integrated alarm buffer and 2 detector / zone dependencies.
� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes.
Supply voltage
Emergency supply
Quiescent current
Alarm current
Inputs
Ambient temperature
Humidity
Protection class
Colour
Material
Dimensions (H x W x D)
Weight
VdS approval
System approval
CPD-Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
3 inputs for collective signal
S 295054
1 x 24 V / 400 mA monitored for sounding/signalling devices
up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each
3 relais outputs 250 V / 5 A for alarm and fault
8 open collector outputs 30 V DC / 90 mA
- Subject to alterations and errors -
490 mm x 420 mm x 210 mm
230 V AC (-15%/+10%)
Technical data
LC-Display 160 x 80 points, backlight
20 LED-displays for status signal Display
400 mA
2 x 12 V / 26 Ah
250 mA
24 V DC / 72 W / 3,5 A
1 output 24 V DC / 800 mA for external devices Power supply
RS 232
Bitbus (RS 485 based)Interfaces
Outputs
-5°C bis +40°C
5 - 95 % (non-condensing)
IP 30
EN 54-2:1997 A1:2006
EN 54-4:1997 A1:2002 A2:2006Standards
light grey, RAL 7035
sheet steel
12,5 kg, without batteries
EN 12094 for 1 area extinguishing systems
international approvals on request Further approvals
Scope of delivery without loop cards, network interfaces and batteries utilization of
integrated standard extinguishing interface requires 1 optional LED indicator
module in the front to ensure the indication according to EN 54 - 2.
G 203068
General remarks
0786-CPD-20817
editing status: 2009-07-16
Properties:
� Ability to change and edit inspection and reaction times along with all delays.
� Emergency power supply via 2 batteries 12 V / up to 12 Ah.
� Integrated ground fault monitoring.
� Segmented front door allowing the quick assembly of LED indicator modules and printers.
� Option for customised front logos.
� Possibility for complete system redundancy with the CPU and loop interfaces.
� Up to 128 programmable detector zones.
� Up to 42 T-branches per loop possible.
� Integrated alarm buffer and 2 detector / zone dependencies.
� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes.
via the MC 3004 monitoring card.
� 1 external output 24 V / 400 mA monitored for sounding/signalling devices.
� 3 potential free relais for fire and fault.
� 3 inputs for collective signals.
� Integrated RS 232 - interface for the dpt software and the connection of printers and other
peripheral equipment.
� Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA.
� Monitored power supply unit and battery charging according to EN 54-4 A1 2002 and A2 2006
� Different access levels with password protection.
� Integrated "one-man-revision mode" with clear protocols and a revision counter.
� Visual diagnostics and remote-control operations via the visualization software "Visual detect".
� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.
� Integrated display and control panel according to DIN EN 54 - 2 A1 2006.
126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m.
� Option for 2 conventional interface cards for controlling up to 16 conventional zones.
� Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to
EN 12094.
� 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of
� Integrated interface connection for up to 63 additional network components.
� Integrated control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
� incl. English language kit for control and programming.
� Connections for a fire brigade interface for controlling the panels outputs, key deposit and transmission units
Product-Information Sheet
Type detect 3004plus
S GB Order No. 32553
Description:
Microprocessor controlled modular fire control panel
for the use with the Loop 3000 fire detection system
components. Approved according to EN 54 - 2 A1
2006, EN 54 - 4 A1 2002, A2 2006 and VdS for the
use according to VdE 0833.
Fire control panel detect 3004plus
, shallow housing, language kit English
� Large LCD, 160 x 80 with backlight.
� In accordance to EN 61000 - 6 - 3 class B for emissions, so suitable for the use in sensitive areas.
� Programming options for different alarm modes.
� Event log memory of up to 500 messages.
� Programming of control logics and time dependent functions for the components of series Loop 3000.
� Customized customer texts allowing up to a maximum of 20 characters.
� Simple menu structure in accordance to EN 54 - 2 A1 2006.
� Software controlled disablements for zones and individual detectors via external inputs.
Supply voltage
Emergency supply
Quiescent current
Alarm current
Inputs
Ambient temperature
Humidity
Protection class
Colour
Material
Dimensions (H x W x D)
Weight
VdS approval
System approval
CPD-Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
EN 12094 for 1 area extinguishing systems
international approvals on request Further approvals
Scope of delivery without loop cards, network interfaces and batteries utilization of
integrated standard extinguishing interface requires 1 optional LED indicator
module in the front to ensure the indication according to EN 54 - 2.
G 203068
0786-CPD-20817
General remarks
EN 54-2:1997 A1:2006
EN 54-4:1997 A1:2002 A2:2006Standards
light grey, RAL 7035
sheet steel
12,5 kg, without batteries
Outputs
-5°C bis +40°C
5 - 95 % (non-condensing)
IP 30
24 V DC / 72 W / 3,5 A
1 output 24 V DC / 800 mA for external devices Power supply
RS 232
Bitbus (RS 485 based)Interfaces
LC-Display 160 x 80 points
backlight
20 LED-displays for status signal
Display
400 mA
2 x 12 V / 12 Ah
250 mA
230 V AC (-15%/+10%)
Technical data
- Subject to alterations and errors -
490 mm x 420 mm x 150 mm
3 inputs for collective signal
S 295054
1 x 24 V /400 mA monitored for sounding/signalling devices
up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each
3 relais outputs 250 V / 5 A for alarm and fault
8 open collector outputs 30 V DC / 90 mA
editing status: 2009-12-15
Properties:
� Possibility for complete system redundancy with the CPU and loop interfaces.
� Up to 128 programmable detector zones.
� Up to 42 T-branches per loop possible.
� Integrated alarm buffer and 2 detector / zone dependencies.
� Emergency power supply via 2 batteries 12 V / up to 26 Ah.
� Integrated ground fault monitoring.
� Segmented front door allowing the quick assembly of LED indicator modules and printers.
� Option for customised front logos.
� 1 external output 24 V / 400 mA monitored for sounding/signalling devices.
� 3 potential free relais for fire and fault.
� 3 inputs for collective signals.
� Integrated RS 232 - interface for the dpt software and the connection of printers and other
peripheral equipment.
� Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA.
� Different access levels with password protection.
� Visual diagnostics and remote-control operations via the visualization software "Visual detect".
� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.
� Integrated display and control panel according to DIN EN 54
126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m.
� Option for 2 conventional interface cards for controlling up to 16 conventional zones.
� Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to
EN 12094.
� 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of
� Integrated interface slot for the connection for up to 63 additional network components.
� Option for control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
� Incl. English language kit for control and programming.
� Connection option for a fire brigade interface for controlling the panels outputs, key deposit; transmission units.
Product-Information Sheet
Type detect 3004 M GB Order No. 32421
Description:
Microprocessor controlled modular fire control panel
for the use with the Loop 3000 fire detection system
components. Approved according to EN 54 and VdS
for the use according to VdE 0833.
Fire control panel detect 3004, deep housing, language kit English
� 4 alphanumeric lines LC-displaywith backlight
� Programming options for different alarm modes.
� Event log memory of up to 500 messages.
� Programming of control logics and time dependent functions for the components of series Loop 3000.
� Customized customer texts allowing up to a maximum of 20 characters.
� Software controlled disablements for zones and individual detectors via external inputs.
� Ability to change and edit inspection and reaction times along with all delays.
� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes.
Supply voltage
Emergency supply
Quiescent current
Alarm current
Inputs
Ambient temperature
Humidity
Protection class
Colour
Material
Dimensions (H x W x D)
Weight
VdS approval
System approval
CPD-Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
EN 12094 for 1 area extinguishing systems
international approvals on request Further approvals
Scope of delivery without loop cards, network interfaces and batteries
G 203068
General remarks
0786-CPD-20817
S 295054
EN 54-2:1997
EN 54-4:1997 Standards
light grey, RAL 7035
sheet steel
12,5 kg, without batteries
Outputs
-5°C bis +40°C
5 - 95 % (non-condensing)
IP 30
3 inputs for collective signal
1 x 24 V / 400 mA monitored for sounding/signalling devices
up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each
3 relais outputs 250 V / 5 A for alarm and fault
8 open collector outputs 30 V DC / 90 mA
24 V DC / 72 W / 3,5 A
1 output 24 V DC / 800 mA for external devices Power supply
RS 232
RS485 and Bitbus as option for networkInterfaces
4 alphanueric lined LC-Display
Backlight 7 20 LED Displays for status signal Display
146 mA
2 x 12 V / 26 Ah
86 mA
230 V AC (-15%/+10%)
Technical data
- Subject to alterations and errors -
490 mm x 420 mm x 210 mm
editing status: 2009-12-15
Properties:
� Programming options for different alarm modes.
� Event log memory of up to 500 messages.
� Programming of control logics and time dependent functions for the components of series Loop 3000.
� Customized customer texts allowing up to a maximum of 20 characters.
� Software controlled disablements for zones and individual detectors via external inputs.
� Connection option for a fire brigade interface for controlling the panels outputs, key deposit, transmission units.
Product-Information Sheet
Type detect 3004 S GB Order No. 32424
Description:
Microprocessor controlled modular fire control panel
for the use with the Loop 3000 fire detection system
components. Approved according to EN 54 and VdS
for the use according to VdE 0833.
Fire control panel detect 3004, shallow housing, language kit English
� 4 alphanumeric lines LC-display with backlight
� Integrated display and control panel according to DIN EN 54
126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m.
� Option for 2 conventional interface cards for controlling up to 16 conventional zones.
� Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to
EN 12094.
� 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of
� Integrated interface slot for the connection for up to 63 additional network components.
� Option for control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
� Incl. English language kit for control and programming.
� Different access levels with password protection.
� Visual diagnostics and remote-control operations via the visualization software "Visual detect".
� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.
� 1 external output 24 V / 400 mA monitored for sounding/signalling devices.
� 3 potential free relais for fire and fault.
� 3 inputs for collective signals.
� Integrated RS 232 - interface for the dpt software and the connection of printers and other
peripheral equipment.
� Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA.
� Ability to change and edit inspection and reaction times along with all delays.
� Emergency power supply via 2 batteries 12 V / up to 12 Ah.
� Integrated ground fault monitoring.
� Segmented front door allowing the quick assembly of LED indicator modules and printers.
� Option for customised front logos.
� Possibility for complete system redundancy with the CPU and loop interfaces.
� Up to 128 programmable detector zones.
� Up to 42 T-branches per loop possible.
� Integrated alarm buffer and 2 detector / zone dependencies.
� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes.
Supply voltage
Emergency supply
Quiescent current
Alarm current
Inputs
Ambient temperature
Humidity
Protection class
Colour
Material
Dimensions (H x W x D)
Weight
VdS approval
System approval
CPD-Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
- Subject to alterations and errors -
490 mm x 420 mm x 150 mm
230 V AC (-15%/+10%)
Technical data
4 alphanumeric lined LC-Display
Backlight / 20 LED-displays for status signal Display
146 mA
2 x 12 V / 12 Ah
86 mA
24 V DC / 72 W / 3,5 A
1 output 24 V DC / 800 mA for external devices Power supply
RS 232
RS485 and Bitbus as option for networkInterfaces
Outputs
-5°C bis +40°C
5 - 95 % (non-condensing)
IP 30
3 inputs for collective signal
1 x 24 V / 400 mA monitored for sounding/signalling devices
up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each
3 relais outputs 250 V / 5 A for alarm and fault
8 open collector outputs 30 V DC / 90 mA
EN 54-2:1997
EN 54-4:1997 Standards
light grey, RAL 7035
sheet steel
12,5 kg, without batteries
EN 12094 for 1 area extinguishing systems
international approvals on request Further approvals
Scope of delivery without loop cards, network interfaces and batteries
G 203068
General remarks
0786-CPD-20817
S 295054
editing status 20.01.2010
Properties:
� Integrated display and control panel according to DIN EN 54
� Programming options for different alarm modes
� Integrated interface slot for the connection for up to 63 additional network components
� Connection option for a fire brigade interface for controlling the panels outputs, key deposit and
transmission units
� Integrated RS 232 - interface for the DPT programming software and the connection of printers and
other peripheral equipment
� Option for 8 conventional interface cards for controlling up to 64 conventional zones
Product-Information Sheet
Order No. 32422 - Type detect 3016 XL GB
Description:
Microprocessor controlled modular fire control panel for
the use with the Loop 3000 fire detection system
components approved according to EN 54 and VdS for
the use according to VdE 0833
Fire control panel detect 3016, wall mounted housing, language kit English
� 4 alphanumeric lines LC-display with backlight
� Software controlled disablements for zones and individual detectors via external inputs
� Ability to change and edit inspection and reaction times along with all delays.
� Basic version with 5 slots for 2 redundant loop-interfaces for the connection of up to 10 loops with a
maximum of 126 loop 3000 devices per loop and a maximum loop lenght of 3500m
� Option for up to 11 slots for extension boards and the connection of up to 16 loops with 126 loop 3000
devices per loop
� Extinguishing interface option for controlling extinguishing and gas suppression systems for 6
extinguishing areas in accordance to EN12094
� Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes
� Customized customer texts allowing up to a maximum of 20 characters
� 1 external output 24 V / 400 mA monitored for sounding/signalling devices
� 3 potential free relais for fire and fault
� 3 inputs for collective signals
� Programming of control logics and time dependent functions for the components of series Loop 3000
� Integrated power supply 192 W according to EN 54 with 2 outputs for external devices rated
at 24V DC/ 800mA
� Emergency power supply via 2 batteries 12V / up to 45 Ah
� Segmented front door allowing the quick assembly of LED indicator Modules and printers.
� Option for customised front logos
� Possibility for complete system redundancy with redundant CPU and redundant loop interfaces
� Up to 196 programmable detector zones
� Additional up to 42 T-branches per loop possible
� Event log memory of up to 500 messages
� Integrated alarm buffer and 2 detector / zone dependencies
� Different access levels with password protection
� Visual diagnostics and remote-control operations via the visualization software "Visual detect"
� Commissioning and service tool for analyzing and fault finding functions with "I-check" software.
� incl. English language kit for control and programming
Supply voltage
Emergency supply
Quiescent current
Alarm current
Inputs
Ambient temperature
Humidity
Protection class
Colour
Material
Dimensions (H x W x D)
Weight
VdS approval
System approval
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
General remarks
- Subject to alterations and errors -
Sheet steel
750 mm x 600 mm x 240 mm
13,5 kg, without batteries
Scope of delivery without loop cards, network interfaces and batteries
Ground fault montoring via module EM (Art.Nb. 30927)
Utilization of integrated standard extinguishing interface requires 1 optional LED
indicator module in the front to ensure the indication according
to EN 54 - 2
Technical data
230 V AC (-15%/+10%)
2 x 12 V / 45 Ah
ca. 190 mA
ca. 250 mA
G 203067
S295054
4 alphanumeric lines LC-display
Backlight
20 LED - displays for status signal
Display
3 inputs for collective signal
- 5°C up to + 40°C
1 x 24 V /400 mA monitored for sounding/signalling devices
up to 16 loops 140 mA / 3500 m for up to 126 Loop 3000 elements each
3 relais outputs 250 V / 5 A for alarm and fault
8 open collector outputs 30 V DC / 90 mA
24 V DC / 192 W / 8 A
1 output 24 V DC / 800 mA for external devicesPower supply
2 x RS 232
RS485 and Bitbus as option for networkInterfaces
Outputs
EN 54-2: 1997
EN 54-4: 1997Standards
EN 12094
EN 12094 for 1 area extinguishing systems Further approvals
IP 30
Light grey, RAL 7035
5 - 95 % (non-condensing)
editing status: 2009-08-26
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensitivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD-Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
ABS, metal mesh
42 mm x 95 mm
DIN EN 54–7
max. 93 % (+/-2%)
IP 40
15 to 30 V loop powered
silver
- Subject to alterations and errors -
5 mA
5 levels adjustable
� Detector sensitivities automatically calibrated and freely programmable.
� Periodic sensor test.
� Automatic and manual addressing on the loop 3000.
� Integrated isolator and T-branch option.
� Fault monitoring of the measurement chamber signal and loop 3000-electronics.
<20 m/s
� Disable and enable modes with individually adjustable sensitivities.
� Alarm output for the triggering of a LED indicators.
� Functions completely integrated via loop 3000 protocol.
Product-Information Sheet
Order No. 30488 - Type PL 3301 silver
Description:
Optical smoke detector for loop 3000 with 2 optical
and 1 thermal sensor for earliest fire detection and
indication and with bidirectional isolator according to
DIN EN 54-7.
Silver mesh design.
Optical smoke detector, with isolator, mesh design, silver
� Exact pollution recognition by an additional independent measuring chamber.
� Storage of last maintenance date.
max. 10 mA for LED-indicator or piezo buzzer
-10°C to +60°C
280 µA
Technical data
� Self learning modes for the ambient conditions.
� Display of the temperature environments of the fire detection system by a second temperature measurement.
� Multicolour-LED for alarm- (red) and fault (yellow).
� Delivery including protective cover for installation phase.
G 205046
S 295054 and S 208123
on request
0786-CPD-20037
Date: 03.08.2010 TINr.: 0016
Description;
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg
Product information
Brief description :
Design changes to the PL 3300/3200 O outer casing, reduced 6mm in height
- Subject to change (without notice); -
The Standard design of proven PL - series was in the wake of mechanical revision to be adapted to better
accommodate today’s market. With the 6mm reduction in height, we and users alike are able to optimise the
detectors handling and storage.These advantages apply to internal production and testing along with the installation
and commissioning by the end user. The original modern design has not been affected and only a slight change is
noticeable. The following detector types are to be modified:
Part No. Description
30011 PL 3300 O
32248 PL 3300 O
30009 PL 3200 O
32519 PL 3200 O
The changes made to the outer casing, in no way effect the operation of the detector or the detector base.
The design changes have been approved by the VdS and the respective approvals for this detector series have been
amended.
All dust covers for this detector range have also been changed to fit this new design.
These changes will come into effect during the middle of August 2010.
Questions or queries
We will be happy to answer any questions you my have regarding this or any other detectomat products.
1: New PL 3300/3200 O with detector base
2 : New PL 3300/3200 O without detector base
editing status: 2009-08-25
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensitivity
Ambient Temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD-Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
� Disable and enable modes with individually adjustable sensitivities.
� Storage of last maintenance date.
� Self learning modes for the ambient conditions.
� Display of the temperature environments of the fire detection system by a second temperature
measurement.
� Automatic and manual addressing on the loop 3000.
� Periodic sensor test.
� Alarm output for the triggering of a LED indicators.
� Functions completely integrated via loop 3000 protocol.
Product-Information Sheet
Order No. 30007 - Type PL 3200 OT
Description:
Optical and thermal multi sensor detector
for loop 3000 with 2 optical and 2 thermal
sensors for earliest fire detection and
indication in all environments with difficult
ambient conditions according to DIN EN
54-5/7 and CEA 4021.
Multi sensor detector optical - heat, without isolator
� Highest reliability by intelligent combination of thermal and optical sensor signals with via
algorithms.
< 20m/s
� Fault monitoring of the measurement chamber signal and loop 3000-electronics.
Technical data
280 µA
� Integrated temperature measurement as differential procedure and maximum value
in accordance to EN 54-5 1A.
� Exact pollution recognition by an additional independent measuring chamber.
� Detector sensitivities automatically calibrated and freely programmable.
5 mA
max. 10 mA for LED-indicator or piezo buzzer
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2%)
5 levels adjustable
IP 40
white (similar to RAL 9003)
ABS
52 mm x 100 mm
LPCB, BOSEC, PT (GOST), UNIVERZA V LJUBLJANI, EMI, Bahrain
0786-CPD-20197
� Multicolour-LED for alarm- (red) and fault (yellow).
� Delivery including protective cover for installation phase.
G 205052
15 to 30 V DC loop powered
DIN EN 54–7, EN 54-5, CEA 4021
S 295054 and S 208123
editing status: 2009-10-05
Properties:
Operation voltageQuiescent currentAlarm currentOC-outputsSensitivityAmbient temperatureHumidityAir speedProtection classColour housingMaterialDimensions (H x Ø)StandardsVdS approvalSystem approvalFurther approvalsCPD-Number
detectomat GmbHAn der Strusbek 5D-22926 Ahrensburg / Germany
Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670
[email protected] www.detectomat.com
on request0786-CPD-20043
15 to 30 V DC loop powered
G 203038S 295054 and S 208123
Automatic and manual addressing on the loop 3000. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date.
Delivery including protective cover for installation phase.
Product-Information Sheet
Order No. 30008 - Type PL 3200 T
Description:Heat detector with fixed and rate of rise temperature settings for loop 3000 with 1 thermal sensor for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN 54-5.
Heat detector with fixed and rate of rise temperature settings, without isolator
Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A.
< 20m/s
Technical data
280 μA
Periodic sensor test. Detector sensitivities automatically calibrated and freely programmable.
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Display of the temperature environments of the fire detection system by a second temperature measurement.
Multicolour-LED for alarm- (red) and fault (yellow).
- Subject to alterations and errors -
-10°C to +60°Cmax. 93 % (+/-2%)
5 levels adjustable
IP 40white (similar to RAL 9003)ABS52 mm x 100 mmDIN EN 54-5
Stand: 2009-10-05
Properties:
measurement.
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions ( H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD-Number
detectomat GmbH
An der Strusbek 5
D-22926 Ahrensburg / Germany
15 to 30 V DC loop powered
IP 40
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2%)
5 levels adjustable
white (similar to RAL 9003)
ABS
� Exact pollution recognition by an additional independent measuring chamber.
< 20m/s
� Fault monitoring of the measurement chamber signal and loop 3000-electronics.
Technical data
280 µA
� Detector sensitivities automatically calibrated and freely programmable.
5 mA
max. 10 mA for LED-indicator or piezo buzzer
� Multicolour-LED for alarm- (red) and fault (yellow).
� Delivery including protective cover for installation phase.
Product-Information Sheet
Order No. 30009 - Type PL 3200 O
Description:
Optical smoke detector for loop 3000 with
2 optical and 1 thermal sensor for earliest
fire detection and indication according to
DIN EN 54-7.
Optical smoke detector, without isolator
� Automatic and manual addressing on the loop 3000.
� Periodic sensor test.
� Alarm output for the triggering of LED indicators.
� Functions completely integrated via loop 3000 protocol.
� Disable and enable modes with individually adjustable sensitivities.
� Storage of last maintenance date.
� Self learning modes for the ambient conditions.
� Display of the temperature environments of the fire detection system by a second temperature
on request
0786-CPD-20677
44 mm x 100 mm
DIN EN 54–7
G 202003
S 295054 and S 208123
Tel. +49(0)4102/2114-60
Tel. +49(0)4102/2114-670
www.detectomat.com
Stand: 2009-08-25
Properties:
Operation voltage Quiescent currentAlarm current OC-outputs Sensivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x Ø)Standards VdS approval System approval Further approvalsCPD-Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670D-22926 Ahrensburg / Germany
52 mm x 100 mm DIN EN 54-5G 203037
Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol.
IP 40
Multicolour-LED for alarm- (red) and fault (yellow).
Storage of last maintenance date.
Automatic and manual addressing on the loop 3000. Periodic sensor test.
Product-Information Sheet
Order No. 30010 - Type PL 3300 T
Description:Heat detector with fixed and rate of rise temperature settings for loop 3000 with 1 thermal sensor for earliest fire detection and indication in all environments with difficult ambient conditions and with bidirectional isolator according to DIN EN 54-5.
Heat detector with fixed and rate of rise temperature settings, with isolator
Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A.
< 20m/s
Technical data
280 μA
Detector sensitivities automatically calibrated and freely programmable.
5 mAmax. 10 mA for LED-indicator or piezo buzzer
Disable and enable modes with individually adjustable sensitivities.
15 to 30 V DC loop powered
Display of the temperature environments of the fire detection system by a second temperature measurement.
Delivery including protective cover for installation phase.
- Subject to alterations and errors -
-10°C to +60°Cmax. 93 % (+/-2%)
5 levels adjustable
white (similar to RAL 9003)
S 295054 and S 208123on request0786-CPD-20044
ABS
Stand: 2009-08-25
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD-Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
15 to 30 V DC loop powered
G 202002
� Disable and enable modes with individually adjustable sensitivities.
� Storage of last maintenance date.
� Display of the temperature environments of the fire detection system by a second temperature
measurement.
IP 40
Product-Information Sheet
Order No. 30011 - Type PL 3300 O
Description:
Optical smoke detector for loop 3000 with
2 optical and 1 thermal sensor for earliest
fire detection and indication and with
bidirectional isolator according to DIN EN
54-7.
Optical smoke detector, with isolator
� Automatic and manual addressing on the loop 3000.
� Periodic sensor test.
� Integrated isolator and T-branch option.
0786-CPD-20679
ABS
� Functions completely integrated via loop 3000 protocol.
� Alarm output for the triggering of a LED indicators.
44 mm x 100 mm
DIN EN 54-7
� Delivery including protective cover for installation phase.
� Exact pollution recognition by an additional independent measuring chamber.
< 20m/s
Technical data
280 µA
� Detector sensitivities automatically calibrated and freely programmable.
5 mA
max. 10 mA for LED-indicator or piezo buzzer
� Multicolour-LED for alarm- (red) and fault (yellow).
� Fault monitoring of the measurement chamber signal and loop 3000-electronics.
� Self learning modes for the ambient conditions.
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2%)
5 levels adjustable
white (similar to RAL 9003)
S 295054 and S 208123
on request
Stand: 2009-10-05
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD-Number
detectomat GmbH
An der Strusbek 5
D-22926 Ahrensburg / Germany
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2%)
5 levels adjustable
white (similar to RAL 9003)
S 295054 ans S 208123
on request
0786-CPD-20198
ABS
� Highest reliability by intelligent combination of thermal and optical sensor signals with via
algorithms.
< 20m/s
Technical data
280 µA
� Exact pollution recognition by an additional independent measuring chamber.
5 mA
max. 10 mA for LED-indicator or piezo buzzer
� Disable and enable modes with individually adjustable sensitivities.
� Delivery including protective cover for installation phase.
15 to 30 V DC loop powered
Product-Information Sheet
Order No. 30021 - Type PL 3300 OT
Description:
Optical and thermal multi sensor detector
for loop 3000 with 2 optical and 2 thermal
sensors and bidirectional isolator for
earliest fire detection and indication in all
environments with difficult ambient
conditions according to DIN EN 54-5/7 and
CEA 4021.
Multi sensor detector optical - heat, with isolator
� Self lerning modes for the ambient conditions.
� Multicolour-LED for alarm- (red) and fault (yellow).
� Detector sensitivities automatically calibrated and freely programmable.
� Integrated temperature measurement as rate of rise procedure and
maximum value in accordance to EN54-5 1A.
� Fault monitoring of the measurement chamber signal and loop 3000-electonics.
� Automatic and manual addressing on the loop 3000.
� Periodic sensor test.
52 mm x 100 mm
DIN EN 54–7, EN 54-5, CEA 4021
G 205051
� Integrated Isolator and T-branch option.
� Alarm output for the triggering of LED indicators.
� Functions completely integrated via loop 3000 protocol.
IP 40
� Display of the temperature environments of the fire detection system by a second temperature
measurement.
� Storage of last maintenance date.
Tel. +49(0)4102/2114-60
Tel. +49(0)4102/2114-670
www.detectomat.com
Stand: 2009-08-25
Properties:
CO-Sensor lifetime
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensitivity
Ambient temperature
Humidity
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD - Number
General remarks
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
� Alarm evaluation with professional CO-sensor technology.
CO - Alarm at 30 ppm, heat accord. to EN 54 - 5 1A
� Automatic and manual addressing on the loop 3000.
� Periodic sensor test.
� Integrated isolator and T-branch option.
� Functions completely integrated via loop 3000 protocol.
� Alarm output for the triggering of a LED indicators.
� Disable and enable modes with individually adjustable sensitivities.
� Display of the temperature environments of the fire detection system by a second temperature
measurement.
Product-Information Sheet
Order No. 30079 - Type PL 3300 COBT
Description:
Intelligent multi sensor detector for the loop
3000 series featuring sensor technology for
carbon monoxide detection in combination
with two thermal detectors and an
integrated isolator for all environments with
difficult ambient conditions, in accordance
to EN 54-5/7.
For the earliest detection of smouldering
fires of all kinds including electrical. The PL
3300 COBT continously monitors the
temperature and the CO-concentration.
Multisensor carbon monoxide gas and heat, with isolator
max. 10 mA for LED-indicator or piezo buzzer
� Integrated acoustic indication for CO-pre alarm and CO-alarm.
� Highest reliability by intelligent combination of thermal and CO sensor via algorithm.
� Integrated temperature measurement as differential procedure and maximum value in
accordance to EN 54-5 1A.
5 mA
� Multicolour-LED for alarm- (red) and fault (yellow).
� Delivery including protective cover for installation phase.
5 years
Technical data
15 to 30 V DC loop powered
� Measurement of carbon monoxid with 2 alarm thresholds:
Prealarm: 15 ppm in 15 min.
Alarm: 30 ppm in 60 min.
600 µA
G 207005
S 295054 and S 208123
ABS
IP 40
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2%)
The Carbon Monoxide detector requires calibrating once a year to ensure the
high detection levels is maintained.
white (similar to RAL 9003)
Bulgaria
0786-CPD-20582
52 mm x 100 mm
DIN EN 54-5
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VDS-Approval
System approval
Further approvals
CPD-Number
Technical data
44 mm x 100 mm
IP 40
15 to 30 V DC loop powered
< 20m/s
max. 10 mA for LED-indicator or piezo buzzer
5 mA
280 µA
-10°C to +60°C
max. 93 % (+/-2%)
5 levels adjustable
white (similar to RAL 9003)
S 295054 and S 208123
DIN EN 54–7
G 202107
on request
0786-CPD-20036
ABS
Stand: 2009-08-27
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensitivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD - Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2%)
max. 10 mA for LED-indicator or piezo buzzer
silver
on request
0786-CPD-20041
47 mm x 110 mm
DIN EN 54-7
� Exact pollution recognition by an additional independent measuring chamber.
IP 40
Technical data
15 to 30 V DC loop powered
� Detector sensitivities automatically calibrated and freely programmable.
280 µA
5 mA
� Multicolour-LED for alarm- (red) and fault (yellow).
� Delivery including protective cover for installation phase.
� Fault monitoring of the measurement chamber signal and loop 3000-electronics.
Product-Information Sheet
Order No. 30568 - Type PL 3305 O silver
Description:
Optical smoke detector for loop 3000 with
2 optical and 1 thermal sensor for earliest
fire detection and indication and with
bidirectional isolator according to DIN EN
54-7.
Round glass design, silver colour.
Optical smoke detector, with isolator, round glass-design, silver
G 204089
S 295054 and S 208123
� Disable and enable modes with individually adjustable sensitivities.
� Storage of last maintenance date.
� Self learning modes for the ambient conditions.
� Display of the temperature environments of the fire detection system by a second temperature
measurement.
<20 m/s
� Periodic sensor test.
Glass, ABS
5 levels adjustable
� Automatic and manual addressing on the loop 3000.
� Integrated isolator and T-branch option.
� Functions completely integrated via loop 3000 protocol.
� Alarm output for the triggering of a LED indicators.
Stand: 2009-08-27
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensitivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD - Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2%)
max. 10 mA for LED-indicator or piezo buzzer
white (similar to RAL 9003)
on request
0786-CPD-20037
42 mm x 95 mm
DIN EN 54-7
� Exact pollution recognition by an additional independent measuring chamber.
IP 40
Technical data
15 to 30 V DC loop powered
� Detector sensitivities automatically calibrated and freely programmable.
280 µA
5 mA
� Multicolour-LED for alarm- (red) and fault (yellow).
� Delivery including protective cover for installation phase.
� Fault monitoring of the measurement chamber signal and loop 3000-electronics.
Product-Information Sheet
Order No. 30956 - Type PL 3301 O white
Description:
Optical smoke detector for loop 3000 with
2 optical and 1 thermal sensor for earliest
fire detection and indication and with
bidirectional isolator according to DIN EN
54-7.
White mesh design.
Optical smoke detector, with isolator, mesh design, white
G 205046
S 295054 and S 208123
� Disable and enable modes with individually adjustable sensitivities.
� Storage of last maintenance date.
� Self learning modes for the ambient conditions.
� Display of the temperature environments of the fire detection system by a second temperature
measurement.
<20 m/s
� Periodic sensor test.
ABS, metal mesh
5 levels adjustable
� Automatic and manual addressing on the loop 3000.
� Integrated isolator and T-branch option.
� Functions completely integrated via loop 3000 protocol.
� Alarm output for the triggering of a LED indicators.
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
further apporvals
CPD-number
Sensivity
detectomat GmbH [email protected]
An der Strusbek 5 www.detectomat.com
D-22926 Ahrensburg / Germany
G 208095
on request
52 mm x 100 mm
< 20m/sIP 40white (similar to RAL 9003)ABS
� Functions completely integrated via loop 3000 protocol
5 levels adjustble -10°C to +60°Cmax. 93% (+/-2%)
0786-CPD-20580
Tel. +49(0)4102/2114-670
� Integrated temperature measurement as rate of rise procedure and max. value in accordance to EN54-5 1A
250 µA5mAmax. 10 mA for LED-indicator or piezo buzzer
� Detector sensitivities automatically calibrated and freely programmable � Fault monitoring of the measurement chamber signal and loop 3000-electronics
� Integrated Isolator and T-branch option � Alarm output for the triggering of LED indicators
Product-Information Sheet
Order No. 32149 - Typ PL 3300 OTi Fusion
Description:
Intelligent optical and thermal multi sensor detector for loop 3000 with 2
optical and 2 thermal sensors and a bidirectional Isolator for earliest fire
detection and indication in all enviroments with difficult ambient conditions,
according to EN 54-5/7 and CEA 4021. Fusion®-Technology for the
detection of the smallest smoke particles and fires in the early stage by
using the wavelengthsof the wide-band white light spectrum.
Multi sensor optical - heat - intelligent Fusion
editing status: 2009-10-05
� Integrated measurement-System and algorithm for condensation recognition (Humitec®)
� Automatic and manual adressing on the loop 3000
- Subject to alterations and errors -
DIN 54-7, EN 54-5, CEA 4021
S 295054 and S 208123
� Intelligent analysis and disruption mode für the elimination of false alarm (e.g. cigarette smoke)
� Exact pollution recognition by an additional independent measuring chamber � Highest reliability by intelligent combination of thermal and optical sensor signals via algorithms
� Periodic sensor test
Tel. +49(0)4102/2114-60
� Disable and enable modes with individually adjustable sensitivities � Storage of last maintenance date � Self learning modes for the ambient conditions � Display of the temperature envirements of the fire detection system by a second temperature measurement � Multicolour-LED for alarm- (red) and fault (yellow) � Delivery including protective cover for installation phase
15 to 30 V DC loop powered Technical data
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensitivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material ABS
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD-Number
Sensitivity
detectomat GmbH [email protected]
An der Strusbek 5 www.detectomat.comD-22926 Ahrensburg / Germany
� Functions completely integrated via loop 3000 protocol.
� Disable and enable modes with individually adjustable sensitivities.
� Storage of last maintenance date.
� Self learning modes for the ambient conditions.
� Periodic sensor test.
� Automatic and manual adressing on the loop 3000.
� Integrated isolator and T-branch option.
� Alarm output for the triggering of LED indicators.
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2 %)
max. 10 mA for LED-indicator or piezzo buzzer5 levels adjustable
on request0786-CPD-20578
IP 40
white (similar to RAL 9003)
Tel. +49(0)4102/2114-60
� Exact pollution recognition by an additional independent measuring chamber.
� Integrated temperature measurement as rate of rise procedure and maximum value in
accordance to EN 54-5 1A.
� Detector sensitivities automatically calibrated and freely programmable.
� Fault monitoring of the measurement chamber signal and loop 3000-electronics.
� Highest reliability by intelligent combination of thermal and optical sensor signals with via
algorithms.
Product-Information Sheet
Order No. 32150 - Type PL 3300 OTi
Description:
Intelligent optical and thermal multi sensor detector for loop 3000
with 2 optical and 2 thermal sensors and a bidirectional isolator for
earliest fire detection and indication in all environments with difficult
ambient conditions, according to EN 54-5/7.
Multi sensor detector optical - heat - intelligent
� Integrated measurement-system and algorithm for condensation recognition (Humitec®).
� Intelligent analysis and disruption mode for the elimination of false alarms (e.g. cigarette smoke).
Stand: 2009-10-05
� Display of the temperature environments of the fire detection system by a second temperature
measurement.
� Multicolour-LED for alarm- (red) and fault (yellow).
� Delivery including protective cover for installation phase.
<20 m/s
250 µA
5 mA
Technical data
15 to 30 V DC loop powered
Tel. +49(0)4102/2114-670
S 295054 and S 208123
52 mm x 100 mm)
DIN EN 54-7, EN 54-5, CEA 4021
G 208096
Stand: 2009-08-26
Properties:
Operation voltage
Quiescent current
Alarm current
OC-outputs
Sensitivity
Ambient temperature
Humidity
Air speed
Protection class
Colour housing
Material
Dimensions (H x Ø)
Standards
VdS approval
System approval
Further approvals
CPD - Number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
� Periodic sensor test.
ABS, metal mesh
5 levels adjustable
� Automatic and manual addressing on the loop 3000.
� Integrated isolator and T-branch option.
� Functions completely integrated via loop 3000 protocol.
� Alarm output for the triggering of a LED indicators.
G 205046
S 295054 and S 208123
� Disable and enable modes with individually adjustable sensitivities.
� Storage of last maintenance date.
� Self learning modes for the ambient conditions.
� Display of the temperature environments of the fire detection system by a second temperature
measurement.
<20 m/s
Product-Information Sheet
Order No. 30525 - Type PL 3301 O black
Description:
Optical smoke detector for loop 3000 with
2 optical and 1 thermal sensor for earliest
fire detection and indication and with
bidirectional isolator according to DIN EN
54-7.
Optical smoke detector, with isolator, mesh design, black
� Exact pollution recognition by an additional independent measuring chamber.
IP 40
Technical data
15 to 30 V DC loop powered
� Detector sensitivities automatically calibrated and freely programmable.
280 µA
5 mA
� Multicolour-LED for alarm- (red) and fault (yellow).
� Delivery including protective cover for installation phase.
� Fault monitoring of the measurement chamber signal and loop 3000-electronics.
- Subject to alterations and errors -
-10°C to +60°C
max. 93 % (+/-2%)
max. 10 mA for LED-indicator or piezo buzzer
black
on request
0786-CPD-20037
42 mm x 95 mm
DIN EN 54-7
editing status 13.04.2010
Properties:
Supply voltage Power supplyEmergency supplyQuiescent current Alarm current Short circuitConventional line broken wire/ fault
Ambient temperature Humidity Stock temperature Protection class Colour MaterialDimensions (H x W x D) Weight
Further approvals
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670D-22926 Ahrensburg / Germany
Standards
21 LEDs for status display, thereof 11 LEDs masked6 keys for operation2 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC /3A for alarm and fault
2 to 10 mA 10 to 110 mA ≥110 mA0 to 2 mA
-20°C to +60°C
Grey (similar to RAL 7035)
-5°C to +40°C
ABS
2,30 kg, without batteryEN 54-2:1997/A1:2006EN 54-4:1997/A2:2006
Connection possibility for 2 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone
230 V AC ±10 %24 V DC/300 mA1 x 12 V/7 Ah
2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 7 Ah
Product-Information Sheet
Order No. 32638 - Type DCC 2
Description:Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1 2006 and EN 54-4:1997/A2:2006.
Fire Control Panel, 2 Zones, Conventional, English
Clear display and easy operation with LED displays and operation keys
Integrated "one-man-revision mode"
- Subject to alterations and errors -
0 - 95 % (non condensing)
IP 30
Integrated power supply accord. to EN 54-4:1997/A2:2006 with 1 output for external devices rated at 24V DC 2 monitored outputs with 300 mA each for signalling devices
288 mm x 340 mm x 98 mm
Independent connection of detector and signalling device zones
1293-CPD-0132
2 access levels via key switch
Display
Outputs
Manual control of signalling devices via seperate input Internal selftest for 8 potential faults Incl. programming option, e.g. alarm delay, fast modus
Technical data
editing status 13.04.2010
Properties:
Supply voltage Power supplyEmergency supplyQuiescent current Alarm current Short circuitConventional line broken wire/ fault
Ambient temperature Humidity Stock temperature Protection class Colour MaterialDimensions (H x W x D) Weight
Further approvals
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670D-22926 Ahrensburg / Germany
2 access levels via key switch
Display
Outputs
Manual control of signalling devices via seperate input Internal selftest for 8 potential faults
Technical data
Clear display and easy operation with LED displays and operation keys
Integrated "one-man-revision mode"
- Subject to alterations and errors -
0 - 95% (non condensing)
IP 30
Integrated power supply accord. to EN 54-4:1997/A2:2006 with 1 output for external devices rated at 24 V DC 2 monitored outputs with 300 mA each for signalling devices
288 mm x 340 mm x 98 mm
Independent connection of detector and signalling device zones
1293-CPD-0132
Product-Information Sheet
Order No. 32639 - Type DCC 4
Description:Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1:2006 and EN 54-4:1997/A2:2006.
Fire Control Panel, 4 Zones, Conventional, English
ABS
2,30 kg, without batteryEN 54-2:1997/A1:2006EN 54-4:1997/A2:2006
Connection possibility for 4 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone
230 V AC ±10 %24 V DC/300 mA1 x 12 V/7 Ah
2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 7 Ah
Standards
25 LEDs for status display, thereof 11 LEDs masked6 keys for operation2 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC /3A for alarm and fault
2 to 10 mA 10 to 110 mA ≥110 mA0 to 2 mA
-20°C to +60°C
Grey (similar to RAL 7035)
-5°C to +40°C
editing status 28.04.2010
Properties:
Supply voltage Power supplyEmergency supplyQuiescent current / ZoneAlarm current / Zone Short circuitConventional line broken wire/ fault
Ambient temperature Humidity Stock temperature Protection class Colour MaterialDimensions (H x W x D) Weight
Further approvals
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670D-22926 Ahrensburg / Germany
Standards
16 LED-displays for status display (+ 8 LEDs in case of extension)6 keys for operation and programming4 x 24 V/300 mA monitored for signalling devices2 relay outputs 60 V DC/120 V AC/3A for alarm and fault
2 to 10 mA 10 to 110 mA ≥110 mA0 to 2 mA
-20°C to +60°C
Grey (similar to RAL 7035)
-5°C to +40°C
Connection possibility for 8 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone
230 V AC ±10 %24 V DC/1 A1 x 12 V/18 Ah
2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 18 Ah
32654 - 4 alarm zones extension Type SE 4 32655 - Relay-module, 8 Relays 1 A/12 V Type RM 8
Technical data
1293-CPD-0133
ABS
4,26 kg, without batteryEN 54-2:1997/A1:2006EN 54-4:1997/A2:2006
Product-Information Sheet
Order No. 32640 - Type DCC 8 plus
Description:Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1:2006 and EN 54-4:1997/A2:2006.
Fire Control Panel, 8 - 16 Zones, Conventional, English
Clear display and easy operation with LED displays and operation keys
Integrated "one-man-revision mode"
- Subject to alterations and errors -
0 - 93% (non condensing)
IP 30
Extension option via 4 zone modules for up to 16 conventional zones for CT 3000 fire detection components Integrated power supply accord. to EN 54-4:1997/A2:2006 4 monitored outputs with 300 mA each for signalling devices
Outer dimensions 345 mm x 455 mm x 128 mm
Independent connection of detector and signalling device zones
Display
Outputs
Manual control of signalling devices via seperate input Internal selftest for 8 potential faults Incl. programming option, e.g. alarm delay, fast modus Panel network of max. two fire control panels
Accessories: 32653 - 4 zone extension module Type GE 4
www.detectomat.com
39
8. Conventional System
Multisensor detector optical/thermal CT 3000 OTNo. 30022
Conventional multisensor detector optical/thermal according to EN 54-7:
• intelligent analysis of the thermal sensor• intelligent analysis of the measuring chamber signal
Technical data
operating voltage 9 up to 33 V DCquiescent current 100 µAalarm current 20 mAopen collector output 15 mA for LED indicatorssensitivity < 0,15 dB/m 60°C rate of riseoperation temperature -10°C up to +60°Chumidity max. 95 %/RH/40°Cprotection class IP 30colour housing whitematerial ABSEN 54-7approvals further on request
Heat detector CT 3000 TNo. 30014
Conventional heat detector according to EN 54-7:
• highly functional detection-system• intelligent analysis of the thermal sensor
Technical data
operating voltage 9 up to 33 V DCquiescent current 80 µAalarm current 20 mAopen collector output 15 mA for LED indicatorssensitivity 60°C rate of riseoperation temperature -10°C up to +60°Chumidity max. 95 %/RH/40°Cprotection class IP 30colour housing whitematerial ABSEN 54-7approvals further on request
Detector base standard SDB 3000 whiteNo. 30301
Standard base for all conventional:
• including LED indicator connection• space for additional modules
Technical data
operation temperature -10°C up to +60°Cmaterial ABScolour whitedimensions (H x ø) 20 mm x 95 mm
www.detectomat.com
38
8. Conventional System
Fire control panel FCP 6No. 30941
Fire control panel FCP 4No. 32143
Conventional fire control panel with (FCP 4) 4 detector zones:
• 2 monitored outputs for signalling devices (300 mA)• 1 programmable output for telephone operators• 4 quiescent current monitored detector zones• max. 30 automatic detectors each zone• 4 relay outputs for alarm and fault• space for battery (1 x 12 V/7 Ah)
Conventional fire control panel with 4 or 6 detector zones:
• 2 monitored outputs for signalling devices (250 mA)• max. 30 automatic detectors each zone• 6 quiescent current monitored detector zones• 6 relay outputs for alarm and fault• space for battery (1 x 12 V/7 Ah)
Technical data
system voltage 220 up to 240 V ACoperating voltage 24 V DCquiescent current 190 mAalarm current 160 mAfrequency 50/60 Hzemergency power 12 V/7 Ahoperation temperature 0°C up to +60°Coutput relay 1 relay per zonesounder output 2 x 24 V/300 mA monitoreddisplay LCD displayhumidity max. 95 %protection class IP 20colour housing greymaterial ABS
EN:FCP 54-2, 54-4
dimensions (H x D x W) 240 mm x 325 mm x 80 mmweight 2 kg without battery
Optical smoke detector CT 3000 O VdS G203036No. 30015
Conventional optical smoke detector according to EN 54-7:
• highly functional detection-system• intelligent analysis of the measuring chamber signal
Technical data
operating voltage 9 up to 33 V DCquiescent current 40 mAalarm current 20 mAopen collector output 15 mA for LED indicatorssensitivity < 0,15 dB/moperation temperature -10°C up to +60°Chumidity max. 95 %/RH/40°Cprotection class IP 30colour housing whitematerial ABSDIN EN 54-7dimensions (H x Ø ) 44 mm x 100 mmapprovals further on request
editing status: 2009-08-27
Properties:
Colour housing
Material
Dimensions (H x Ø)
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
white (similar RAL 9003)
Technical data
- Subject to alterations and errors -
21 mm x 95 mm
ABS
� Integrated connectors for LED indicator (Art. 31193) or piezo buzzer (Art. 32091).
� Space for additional connectors Type WAGO 243.
� Mounting space for the piezo buzzer (Art 32091) and the detector labelling clip (Art 30479).
� Including transparent seal cover to protect the base against contaminents.
� Integrated connectors for the connection of one spur for the loop extension (T-branch).
Product-Information Sheet
Order No.32242 Type SDB 3000
Description:
Detector Base for all detectors of series CT and loop
3000.
Detector standard base, white
editing status 20.01.2010
Properties:
Operation voltage
Current consumption
Input
Ambient temperature
Humidity
Weight
Protection class
Colour housing
Material
Dimensions (H x W x D)
Standards
VdS approval
System approval
CPD - number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
Approx.20g
Technical data
Low active monitored
-10°C to +60°C
max. 93% (+/-2%)
� Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel
� Completely encapsulated module for the integration in special applications with control by the loop 3000
- Subject to alterations and errors -
Blue
27 mm x 73 mm x 15 mm
� Programming of different switching variants of input and output also with time control
� Monitoring of the operating status via Loop 3000
� Independent programming of Input and Output
S 295054 and S 208123
� Functions completely integrated via loop 3000 protocol
Product-Information Sheet
Order No. 31640 - Type OMS 3301 mini
Description:
Intelligent Input- / Output module mini for the Loop 3000
for the control of external optical and acoustic signalling
devices with bidirectional isolator for the integration in
externally connected modules according to DIN EN 54-
18 including one monitored fault input and one open
collector output for signalling devices
Input- / Output module, single I/O, signalling devices,with isolator
ABS
DIN EN 54-18, 17
IP 30
G 206047
0786-CPD-20530
� Connecting module with one freely programmable fault input and one output for the connection of
signalling devices
15 to 30 V DC loop powered
380 µA
1 Open Collector 500 mA
1 10 mAparallelfor LED-status indicationOutput
� Automatic and manual addressing on the loop 3000
� Integrated Isolator
editing status 20.01.2010
Properties:
Operation voltage
Quiescent current
Alarm current
Output
Input
Ambient temperature
Humidity
Weight
Protection class
Colour housing
Material
Dimensions (H x W x D)
Standards
VdS approval
System approval
CPD - number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
-10°C to +60°C
460 µA
460 µA, 5 mA if alarm-LED is active
Relay 1 change over contact 30 V DC/ 1A
Low active monitored
Accessories:
� Possibility for monitoring of the output with UBW 3311 (Order No. 32073)
15 to 30 V DC loop powered
Technical data
- Subject to alterations and errors -
ABS
DIN EN 54-18, 17
� Programming of different switching variants of input and output also with time control
� Independent programming of Input and Output
� Automatic and manual addressing on the loop 3000
� Integrated Isolator and T-branch option
� Monitoring of the operating status via Loop 3000
0786 - CPD-20459
� Aestethical robust wall mounted housing according with IP 54
� Functions completely integrated via loop 3000 protocol
� Multicolour-LED for alarm (red) and fault (yelow)
Product-Information Sheet
Order No. 30200 - Type IOM 3311
Description:
Intelligent Input- / Output Module for the Loop 3000 with
bidirectional isolator according to DIN EN 54-18 with one
monitored input and one potentialfree relay output
Input- / Output module, single I/O, Relay, with Isolator
� Connecting module with one freely programmable Input and one freely programmable output
G 205029
grey (similar to RAL 7035)
S 295054 and S 208123
max. 93% (+/-2%)
Approx. 185 g
IP 54
93 mm x 93 mm x 55 mm
editing status 16.12.2009
Properties:
Quiescent current
Alarm current
Input
Ambient temperature
Humidity
Weight
Portection class
Colour housing
Material
Dimensions (H x W x D)
Standards
VdS approval
System approval
CPD-Nummer
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
max. 93% (+/-2%)
Approx. 190g
IP 54
� Voltage selection for the detector zone supply via "jumper" on the module board
- Subject to alterations and errors -
grey (similarto RAL 7035)
93 mm x 93 mm x 55 mm
� Possibility for parametrization of short-circuit, wire break, prealarm and alarm thresholds
� Automatic and manual adressing on the loop 3000
� Integrated Isolator and T-branch option
S 295054 and S 208123
� Aesthetical robust wall mounted housing according with IP 54
Technical data
Product-Information Sheet
Order No. 30205 - Type TCM 3300
Description:
Intelligent Input module for the connection of one
conventional detector zone to the loop 3000 with
vidirectional isolator according to DIN EN 54-18 and for
the connection of conventional detectors with 12V or 24V
technology
Input module, 1 conventional zone,with Isolator
-10°C to +60°C
� Functions completely integrated via loop 3000 protocol
� Multicolour-LED for alarm (red) and fault (yellow)
ABS
DIN EN 54-18, 17
G 206048
0786-CPD-20373
� External supply of conventional detector zones for the flexible use of different current consumptions
and operation voltages
560 µA
560 µA ; 5 mA if alarm-LED is active
1 monitored detector zone with up to 65 mA
15 to 30 V DC loop powered
External supply output 12V or 24V DCOperation voltage
editing status 20.01.2010
Properties:
Operation voltage
Current consumption
Input
Output
Ambient temperature
Humidity
Weight
Protection class
Colour housing
Material
Dimensions (H x W x D)
Standards
VdS approval
System approval
CPD - number
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
Low active monitored
-10°C to 60°C
� Aestethical robust wall mounted housing according with IP 54
General remarks
� The fault input can be used for the monitoring module UBW 3311
Accessories:
� Possibility for monitoring of the output with UBW 3311 (Art.Nb. 32073)
� Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel
� Programming of different switching variants ofa input and output also with time control
- Subject to alterations and errors -
93 mm x 93 mm x 55 mm
G 205030
� Monitoring of the operating status via Loop 3000
� Independent programming of Input and Output
� Automatic and manual addressing on the loop 3000
� Multicolour-LED for alarm (red) and fault (yellow)
Product-Information Sheet
Order No. 30211 - Type OMS 3301
Description:
Intelligent Input- / Output module for the Loop 3000 for
the control of external optical and acoustic signalling
devices with bidirectional isolator according to DIN EN
54-18 including one monitored fault input and one
potentialfree relay output for signalling devices
Input- / Output module, single I/O, signalling devices, with isolator
DIN EN 54-18, 17
S 295054 and S 208123
ABS
07786-CPD-20460
� Connecting module with one freely programmable fault input and one output for the connection of
signalling devices
15 to 30 V DC loop powered
460 µA
Relay 1 change over contact 30 V DC / 1A
� Integrated Isolator and T-branch option
� Functions completely integrated via loop 3000 protocol
Technical data
max. 93% (+/-2%)
Approx. 190 g
IP 54
Grey (similar to RAL 7035)
editing status 14.12.2009
Properties:
Operation voltage
Quiescent current
Alarm Current
Input
Ambient temperature
Humidity
Weight
Protecting class
Colour Housing
Material
Dimensions (H x W x D)
Standards
VdS approval
System approval
CPD-Nummer
detectomat GmbH [email protected] Tel. +49(0)4102/2114-60
An der Strusbek 5 www.detectomat.com Tel. +49(0)4102/2114-670
D-22926 Ahrensburg / Germany
DIN EN 54-1, 18
380 µA
G 206047
076-CPD-20530
max. 93% (+/-2%)
� Functions completely integrated via loop 3000 protocol
Product-Information Sheet
Order No. 30513 - Type AMD 3311
Description:
Intelligent Input- / Output module mini for the Loop 3000
with bidirectional isolator for the integration in special
detectors and externally connected modules according
to DIN EN 54-18 including one monitored input and one
open collector output
Input- / Output module, single I/O, Open Collector with Isolator
� Connecting module with one freely programmable Input and one freely programmable output
- Subject to alterations and errors -
Blue
� Additional parallel alarm output (blinking) for the control of a status indicator (without series resistor)
� Monitoring of the operating status via Loop 3000
� Independent programming of Input and Output
� Automatic and manual addressing on the loop 3000
� Programming of different switching variants of input and output also with time control
S 295054 and S 208123
� Completely encapsulated module for the integration in special applications with control by the loop 3000
� Integrated Isolator
15 to 30 V DC loop powered
Technical data
380 µA ; 5 mA if alarm-LED is active
27 mm x 73 mm x 15 mm
low active monitored
-10°C to +60°C
ABS
Approx. 20g
IP 30
Output 1 Open Collector 500 mA
1 10 mA parallel for LED-Status indication