Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
November 2018
D-WAVE InstallationLoren A. Serna & Ron R. Velarde, LANL
Presented by Josip Loncaric, LANLLA-UR-18-30711
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Introduction
§ Ising: LANL’s D-Wave 2X system– Quantum annealing computer, and– A physics experiment which operates at 10 mK,
300 times cooler than interstellar space§ Tight facility requirements
– Low vibration & other disturbances– Highly reliable power and cryogenic cooling– …at much lower power than HPC
§ Installation steps
Slide 2
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Slide 3
Vibration Isolation Concrete Pad Installation and Prep
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Slide 4
Sump Pump Installation
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Slide 5
Wall Prep for D-WAVE Enclosure
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
UPS & Sheet Metal Installation
Slide 6
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Slide 7
Make-Up Water Piping to Closed Loop System
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Slide 8
Installed PDU & UPS
125 KVA PDU
250 KVA UPS
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Slide 9
Closed Loop Piping, Refrigerant Piping and Pumps. N+1 Pumps
3ea. 0.75 HP Closed Loop Pumps Running @ 3GPM
Chemical Pot Feeder
CRAC Refrigerant Piping
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Generator Transfer Switch & Mechanical Equipment Controls
Slide 10
Generator Transfer Switch Mechanical Equipment Controls
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Installed Outdoor Condensers, Indoor Chillers, & Indoor CRAC Units. All Are N+1
Slide 11
4 Ton & 8 Ton Condenser Units
4 Ton CRAC
8 Ton CRAC
2ea. 3 Ton Closed Loop Chillers
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Sump Pump and 120 Gallon Closed Loop Tank
Slide 12
120 Gallon Storage Tank For The Closed Loop
Sump Pump, Electrical & Mechanical Piping
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
Liquid Nitrogen Dewars. N+1Dewars
Slide 13
2ea. Liquid Nitrogen Dewars
Operated by Los Alamos National Security, LLC for the U.S. Department of Energy's NNSA
UNCLASSIFIED
D-WAVE Electrical & Mechanical Infrastructure
Slide 14