POWER NOTE
REFER TO ELECTRICAL DRAWINGS FOR CIRCUIT WITING AND PRECISE LOCATION DETAILS.
CONDUIT NOTE
ALL CONDUITS TO BE 1" EMT UNLESS OTHERWISE NOTED (UON). ALL CONDUITS TO BE SUPPLIED WITH NYLON PULL STRING. ALL STUBS TO BE SUPPLIED WITH PLASTIC BUSHING.
GENERAL NOTES
1. THE SYMBOLS AND DETAILS ON THIS SHEET ARE TYPICAL AND MAY NOT APPLY TO THE SYSTEMS DESIGNED IN THIS DRAWING SET.
2. QUANTITIES SHOWN IN DRAWINGS TO SUPERCEDE QUANTITIES SHOWN IN WRITTEN SPECIFICATIONS. REFER TO THE SPECIFICATION FOR ADDITIONAL DETAILS.
DESC
EQUIP ID
LOCATION
1
2
1
2
DESC
EQUIP ID
LOCATION
1
2
1
2
DESC
EQUIP ID
LOCATION
1
2
1
2
DESCEQUIP ID
LOCATION
1
2
1
2
DESCEQUIP ID
LOCATION
1
2
1
2
DESC
EQUIP ID
LOCATION
INPUT 1 OUTPUT 1
R
G
B
H
V
R
G
B
H
V
DESCEQUIP IDLOCATION
DESCEQUIP IDLOCATION
#
70V VCDESC
LOCATION
2-WAY LOUDSPEAKEREQUIP ID
LOCATION
HF
LF
3-WAY LOUDSPEAKEREQUIP ID
LOCATION
HF
MF
LF
1-WAY LOUDSPEAKEREQUIP ID
LOCATION
SPK
DESCEQUIP ID
LOCATION
1
2
1
2
EQUIP IDDESC
LOCATION
EQUIP IDDESC
LOCATION
MICROPHONEEQUIP ID
LOCATION
SOURCEOUTPUT
SOURCEOUTPUTSHEET
DESTINATION INPUT
DESTINATION INPUT SHEET
TYPELABEL
TYPELABEL
OUT IN
OUT IN
OUT IN
OUT IN
OUT IN
TYPELABEL
TYPELABEL
CONE LOUDSPEAKER w/70V TRANSFORMER.WATTAGE/TAP VALUE AS NOTED.
CONE LOUDSPEAKER.
SCHEMATIC DEVICE LEGEND
CONNECTORS & JACKS LEGEND
PLATE/PANEL CONNECTOR OUTPUT
FEATHER INPUT - SAME SHEET
FEATHER OUTPUT - SAME SHEET
PLATE/PANEL CONNECTOR INPUT
STANDARD DEVICE BLOCK. I/O AS NOTED.
STANDARD AMPLIFIER BLOCK. I/O AS NOTED.
SPLIT BLOCK - TOP SECTION. I/O AS NOTED.
SPLIT BLOCK - BOTTOM SECTION. I/O AS NOTED.
RGBHV BLOCK. I/O AS NOTED.
1-WAY LOUDSPEAKER ENCLOSURE.
2-WAY LOUDSPEAKER ENCLOSURE.
3-WAY LOUDSPEAKER ENCLOSURE.
70 VOLT VOLUME CONTROL.WATTAGE VALUE AS NOTED.
FEATHER INPUT - OTHER SHEET
FEATHER OUTPUT - OTHER SHEET
JACK TERMINAL - NON NORMAL
JACK TERMINAL - NORMAL
JACK TERMINAL - HALF NORMAL
JACK TERMINAL - INLINE DISCONNECT
JACK TERMINAL - RJ-45
SPLIT BLOCK - MIDDLE SECTION. I/O AS NOTED.
OWNER FURNISHED OR EXISTING BLOCK. I/O AS NOTED.
STANDALONE CONNECTOR OUTPUT(CONNECTOR AS NOTED)
STANDALONE CONNECTOR INPUT(CONNECTOR)
ANTENNA
TERMINATOR
MICROPHONE
WIRE TYPES LEGEND
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:09
:45 P
M
TA001
LEGEND AND GENERAL NOTES -
AV SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
SHEET INDEX
ID DESCRIPTION REV
TA001 LEGEND AND GENERAL NOTES - AV SYSTEMS
TA002 LEGEND AND GENERAL NOTES - AV SYSTEMS
TA101 FIRST LEVEL FLOOR PLAN - AV SYSTEMS
TA102 SECOND LEVEL FLOOR PLAN - AV SYSTEMS
TA111 FIRST LEVEL REFLECTED CEILING PLAN - AV SYSTEMS
TA112 SECOND LEVEL REFLECTED CEILING PLAN - AV SYSTEMS
TA501 TYPICAL DETAILS - AV SYSTEMS
TA502 SECTIONS & ELEVATIONS - AV SYSTEMS
TA503 STORAGE 210 - DETAILED VIEWS - AV SYSTEMS
TA601 FUNCTIONAL DIAGRAMS 1/2 - AV SYSTEMS
TA602 FUNCTIONAL DIAGRAMS 2/2 - AV SYSTEMS
XT EXTRON XTP EXTRON XTP DTP 24 PLUG XTP DTP 24 JACK EXTRON XTP
DM DIGITAL MEDIA NEUTRIK - NE8FDY-C6-B CRESTRON DIGITAL MEDIA CHASSIS MOUNT
DM DIGITAL MEDIA CRESTRON DM-8G-CONN-WG - CRESTRON DIGITAL MEDIA CABLE MOUNT
DT12m DT12 MALE GEP CO G37M G37MP 37 PIN, 12 CHANNEL AUDIO
DT12f DT12 FEMALE GEP CO G37F G37FP 37 PIN, 12 CHANNEL AUDIO
W6 W5 MASS WHIRLWIND W6IRP W6CRP 84 PIN, 28 CHANNEL AUDIO
W5 W5 MASS WHIRLWIND W5IRP W5CRP 48 PIN, 16 CHANNEL AUDIO
W4 W4 MASS WHIRLWIND W4IRP W4CRP 176 PIN, 58 CHANNEL AUDIO
W3 W3 MASS WHIRLWIND W3IRP W3CRP 122 PIN, 40 CHANNEL AUDIO
PC POWERCON 20A NEUTRIK NAC3FCA NA3MPA-1 POWER
EC ETHERCON NEUTRIK NE8MC NE8FDV-Y110-B DATA
RJ45 RJ45 PANDUIT SP688-C CJ688TP (##) TX6 PLUS, "##" = JACK COLOR
F FMALE LIBERTY CM-RG6C-F N/A 75Ω CATV, RG-6 CUB "P" FOR "C" FOR PLENUM
F F MALE LIBERTY CM-RG59C-F N/A 75Ω CATV, RG-59, SUB "P" FOR "C" FOR PLENUM
F F FEMALE CANARE N/A FJ-JR 75ΩCATV, PROVIDE ISO BUSHING
BNC BNC MALE LIBERTY CM-RG6C-BNC N/A 75Ω VIDEO, RG-6, SUB "P" FOR "C" FOR PLENUM
BNC BNC MALE LIBERTY CM-RGB59-BNC N/A 75Ω VIDEO, RG-59, SUB "P" FOR "C" FOR PLENUM
BNC BNC MALE LIBERTY CM-RGB25-BNC N/A 75Ω VIDEO, 25 AWG SOLID
BNC BNC FEMALE CANARE N/A BCJ-RJ 75Ω VIDEO, COLOR MATCH ISO BUSHING
RCAm RCA MALE LIBERTY CM-RG6C-RCA N/A 75Ω VIDEO, RG-6, SUB "P" FOR "C" FOR PLENUM
RCAm RCA MALE LIBERTY CM-RG59C-RCA N/A 75Ω VIDEO, RG-59, SUB "P" FOR "C" FOR PLENUM
RCAm RCA MALE LIBERTY CM-RGB25-RCA N/A 75Ω VIDEO, 25 AWG SOLID
RCAf RCA FEMALE CANARE N/A RJ-BCJRU 75Ω BIDEO, COLOR MATCH INSULATOR
RCAm RCA MALE NEUTRIK NF2C-B2 N/A UNBAL AUDIO
RCAf RCA FEMALE NEUTRIK N/A NF2D-B-(#) UNBAL AUDIO, "#" = COLOR
NL8 SPEAKON 8 NEUTRIK NL8FC NL8MP 8C LOUDSPEAKER
NL4... SPEAKON 4 NEUTRIK NL4FC NL4MP 4C LOUDSPEAKER
NL2 SPEAKON 2 NEUTRIK NL2FC NL2MP 2C LOUDSPEAKER
mTRS 3.5" MINI SWITCHCRAFT 35HDBAU N/A 3.5MM (1/8") MINI STEREO AUDIO
TRSm 1/4" PHONE NEUTRIK NP3X-B N/A 1/4" TIP RING SLEEVE
TSm 1/4" PHONE NEUTRIK NJFC6B N/A 1/4" TIP SLEEVE
TRSf 1/4" PHONE NEUTRIK NJFC6-B NJ3FP6C-B 1/4" TIP RING SLEEVE
TSf 1/4" PHONE NEUTRIK NJFC6-B NJ3FP6C-B 1/4" TIP SLEEVE
XLRmx XLR MALE NEUTRIK NC3MXX-EMC N/A RF HOSTILE ENVIRONMENT
XLRx XLR FEMALE NEUTRIK NC3FXX-EMC NC3FDX-EMC-SPEC RF HOSTILE ENVIRONMENT
XLRm XLR MALE NEUTRIK NC3MX-B NC3MD-L-1-B LINE/MIC LEVEL AUDIO
XLRf XLR FEMALE NEUTRIK NC3FX-B NC3FD-L-1-B LINE/MIC LEVEL AUDIO
ID LABEL MAKE CABLE MOUNT CHASSIS MOUNT NOTES
PROJECT CABLE CONNECTOR SCHEDULE
12 THE MALE END OF ALL PORTABLE CABLES SHALL BE SUPPLIED WITH VELCRO TIE WRAPS.
11 ALL EQUIPMENT MUST BE PROVIDED WITH SIGNAL AND/OR CONTROL CABLING, WHETHER OR NOT SPECIFICALLY SHOWN ON THE CONDUIT ANDWIRING DRAWINGS.
10. MOLDED CABLE/CONNECTORS ARE NOT ACCEPTABLE FOR AUDIO, VIDEO, OR CONTROL CIRUITS EXCEPT COMPUTER SIGNAL INTERCONNECTION ORAC POWER CORDS.
9. FOIL SHIELDED CABLES ONLY PROVIDED WITH A DRAIN WIRE MUST USE THE DRAIN WIRE FOR SHIELD TERMINATION.
8. CABLES WITH WIRE SHIELDS, BRAID OR WOUND, MUST USE ALL THE WIRE CONDUCTORS FOR SHIELD TERMINATION, AND NOT JUST A DRAIN WIREOR SOME OF THE SHIELD STRANDS. CONNECTIONS NOT FOLLOWING THIS REQUIREMENT WILL BE REJECTED.
7. ALL CABLE FOR A GIVEN WIRING CATEGORY SHALL BE CONSISTENT UNLESS SPECIFIED OTHERWISE; (I.E. IF WEST PENN (X)45 IS CHOSEN FOR FIXEDLINE LEVEL WIRING, ALL FIXED LINE LEVEL WIRING SHALL BE DONE WITH THIS CABLE).
6. NO SUBSTITUTIONS ARE ALLOWABLE WITHOUT SPECIFIC WRITTEN APPROVAL.
5. NO SPLICES OR INTERMEDIATE CONNECTION POINTS ARE PERMITTED UNLESS SPECIFICALLY CALLED FOR IN THE SPECIFICATION OR DRAWINGS.
4. INSTALL IN METALLIC CONDUIT, WIRE-WAY, OR FLEXIBLE CONDUIT, UNLESS OTHERWISE NOTED OR INSTRUCTED.
3. INSULATION DIELECTRIC SHALL BE APPROPRIATE TO SIGNAL AND CODE REQUIREMENTS.
2. HIGH PURITY COPPER CABLE ONLY.
1. NOT ALL ACCEPTABLE CABLES LISTED ABOVE MAY BE EMPLOYED IN THE SYSTEM.
CABLE NOTES
6. ALL XLR CONNECTORS, PER IEC-268 STANDARD, WITHIN EQUIPMENT OR OUT, SHALL BE WIRED PIN 2 HOT (HIGH), PIN 3 LOW, AND PIN 1 SCREEN(SHIELD). AT NO TIME CONNECT THE XLR CASE OR BODY TO PIN 1 ON A CONNECTOR NOT PART OF EQUIPMENT CONSTRUCTED OF METAL SHELLS...
5. ALL AUDIO, VIDEO, AND CONTROL CONNECTORS NOT A PART OF MANUFACTURED EQUIPMENT (BNC, XLR, PHONO, VIDEO PATCH, CARD EDGE,MULTIPIN, SPADE LUG ETC.) SHALL HAVE GOLD PLATED CONTACTS. ONLY EXCEPTIONS SHALL BE 1/4" PHONE JACKS, AUDIO PATCH PLUGS, ANDLOUDSPEAKER CONNECTORS.
4. CONNECTORS SHALL TYPICALLY BE KEYED TO PREVENT MIS-INSERTION, AND INCLUDE STRAIN RELIEF MECHANISMS THAT FIRMLY GRIP THE CABLEJACKET.
3. DO NOT MOUNT CONNECTORS IN INACCESSIBLE LOCATIONS, OR EMPLOY TO SPLICE CABLES.
2. EMPLOY ONLY NEW FIRST QUALITY CONNECTORS, ASSEMBLED,WIRED, AND INSTALLED ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS.
1. NOT ALL ACCEPTABLE CONNECTORS LISTED ABOVE MAY BE EMPLOYED IN THE SYSTEM.
CONNECTOR NOTES
Z DIG AUDIO WEST PENN DA2401 DA252401 AES/EDU DIGITAL AUDIO
Y FIBER TBD TBD TBD FIBER OPTIC
XT EXTRON XTP EXTRON XPT DTP 24 XTP DTP 24P XTP DIGITAL DISTRIBUTION
X2 COM BELDEN 8760 N/A >500' PRODUCTION COMMUNICATIONS
X1 COM BELDEN 8762 N/A <500' PRODUCTION COMMUNICATIONS
V3 VIDEO RG-6 WEST PENN 6350 256350 >200'' 75Ω VIDEO (ANALOG OR DIGITAL)
V2 VIDEO RG-59 WEST PENN 819 25819 <50' OR <200' 75Ω HD VIDEO (ANALOG OR DIGITAL)
V1 VIDEO WEST PENN HD825 HD25825 IN RACK OR <50' 75Ω VIDEO (ANALOG OR DIGITAL)
U2 UTP WEST PENN 4246AF 254246AF AV/HDBaseT OVER CAT 6A F/UTP
U1 UTP WEST PENN 4246 254246 A/V OVER CAT6 U/UTP
S4 SPEAKER 12#/ 4C WEST PENN 248 25248B >25' OR <150' 8Ω BIAMP LOUDSPEAKER
S3 SPEAKER 16#/ 2C WEST PENN 225 25225B <500' 70V LOUDSPEAKER
S2 SPEAKER 12#/ 2C WEST PENN 227 25227B >25' OR <150' 8Ω LOUDSPEAKER
S1 SPEAKER 10#/ 2C WEST PENN C210 25210 >150' 8Ω LOUDSPEAKER/SUBWOOFER
R RGBHV MINI HR WEST PENN WP8255 WP258255 IN RACK OR <60' RGBHV
P POWER 18#/ 2C WEST PENN 224 25224B LOW VOLTAGE POWER
M MICROPHONE WEST PENN 454 D25454 MICROPHONE LEVEL AUDIO
L2 LAN WEST PENN 4246AF 254246AF CAT 6A SHEILDED (10G) F/UTP
L1 LAN WEST PENN 4246 254246 ETHERNET/CAT 6 (1G) U/UTP
I RG-58A/U WEST PENN 812 25812 50Ω FOR ASSISTIVE LISTENING SYSTEMS
H3 RF RG-213/U WEST PENN 810 25810 <100'' 50Ω ANTENNA FOR WIRELESS SYSTEMS
H2 RF RG-8X/U WEST PENN 807X N/A >25' OR <100' 50Ω ANTENNA FOR WIRELESS SYSTEMS
H1 RF RG-58A/U WEST PENN 812 25812 <25' 50Ω ANTENNA FOR WIRELESS SYSTEMS
F2 RF RG-11 WEST PENN 821 25821 75Ω CATV/SATELLITE TRUNK
F1 RF RG-6 WEST PENN 841 25841 75Ω CATV/SATELLITE DROP
E CONTROL WEST PENN 291 25291B RELAY/CONTACT CLOSURE
DX DX LINK WEST PENN 4246AF 25 42 46AF AMD DX LINK CABLE
DM DIGITAL MEDIA CRESTRON DM-CBL-8G-NP DM-CBL-8G-P CRESTRON DIGITAL MEDIA CABLE
D DATA WEST PENN D2404 D252404 DATA/RS-232/422/485
C CONTROL WEST PENN 77350 D25350 MEDIA CONTROL CABLE
A AUDIO WEST PENN 454 D25454 LINE LEVEL AUDIO
ID LABEL MAKE MODEL PLENUM NOTES
PROJECT CABLE TYPES SCHEDULE
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
SYMBOL DESCRIPTION
DEVICE LEGEND
INFRASTRUCTURE
MXS
##"
ROUGH-IN FOR FUTURE PROPOSED LOUDSPEAKER LOCATION BASED ON 90° CONICAL COVERAGE PATTERN
M INDICATES MOUNTING TYPE AS PER MOUNTING TYPE SCHEDULE
X INDICATES ROUGH-IN BOX AS PER ROUGH-IN BOX SCHEDULE
INFRASTRUCTURE AS SPECIFIED ON PLANS
ROUGH-IN FOR FUTURE FLAT PANEL DISPLAY WHERE ##" INDICATES DIAGONAL MEASUREMENT OF IMAGE
RE: TA501 DETAIL #1
##"ROUGH-IN FOR FUTURE DIGITAL SIGNAGE FLAT PANEL DISPLAY WHERE ##" INDICATES DIAGONAL MEASUREMENT OF IMAGE
RE: TA501 DETAIL #3SIGN
ROUGH-IN FOR FUTURE AV CREDENZA EQUIPMENT RACKMIDDLE ATLANTIC CFR SERIES
AV BOX: EC TO PROVIDE AND FLUSH MOUNT 12X12X4" NEMA 1 SCREW COVER BOX BELOW COUNTER HEIGHT COORDINATED TO BE BEHIND CREDENZA. EC TO PROVIDE QTY 4 1" EMT STUBS TO ACCESSIBLE CEILING.
PSCHED
ROUGH-IN FOR FUTURE ROOM SCHEDULING PANEL
FLOOR BOXFOR FLOOR BOX DETAILRE: TA501 DETAIL #4FB
##"ROUGH-IN FOR FUTURE FUTURE FLAT PANEL DISPLAY WITH INFRASTRUCTURE FOR AV CONTROL PANEL AND AV INPUT
WHERE ##" INDICATES DIAGONAL MEASUREMENT OF IMAGE
RE: TA501 DETAIL #2POD
BROUGH-IN FOR FUTURE BUTTON CONTROL EC SHALL PROVIDE AND FLUSH MOUNT 3-GANG BOX; 3-1/4" DEEP AT SWITCH
HEIGHT. RACO 263 OR EQUAL. EC SHALL COORDINATE RING WITH OWNER TO ACCOMODATE THEIR PREFERRED BUTTON CONTROLLER (RECOMMEND 3-GANG FOR COMPATIBILITY WITH CRESTRON MPC3-302-B). PROVIDE 1 1" EMT STUB TO ACCESSIBLE CEILING.
1
FOR GYP CONDITIONEC SHALL PROVIDE AND FLUSH MOUNT 3-GANG BOX; 3-1/4" DEEP AT SWITCH HEIGHT. RACO 263 OR EQUAL. EC SHALL COORDINATE RING WITH OWNER TO ACCOMODATE THEIR PREFERRED SCHEDULING PANEL (RECOMMEND 2-GANG OR 3-GANG FOR COMPATIBILITY WITH CRESTRON TSW-760-B-S). PROVIDE 1 1" EMT STUB TO NEAREST CABLE TRAY.
FOR MULLION CONDITIONSCC SHALL PLACE DATA DROP ABOVE CEILING PLANE WHERE POSSIBLE. FUTURE AVC SHALL COORDINATE PATCH CABLE THROUGH MULLION AND GLASS MOUNT OF ROOM SCHEDULING PANEL.
1
ROUGH-IN FOR FUTURE 10K LUMEN PROJECTOR MOUNTED TO STRUCTUREAS PER DETAIL #1 ON TA502
FOR POSITION OF ROUGH-IN RELATIVE TO CONCRETE DOUBLE T STRUCTURE SEE TA502 DETAIL #1.
120VAC DUPLEXADJACENT
2
AV BOX: 2-GANG SURFACE MOUNT BOX WITH GROMMET PASSTHROUGH MOUNTED TO STRUCTURE AS PER TA502 DETAIL #1 & 2. CONDUIT AS PER RCP.
##" PAINT FUTURE PROJECTED IMAGE ON PAINTED WALL SURFACE.
PAINTED WALL SURFACE BY OWNER'S FUTURE AV CONTRACTOR.
VW
ROUGH-IN FOR FUTURE VIDEO INPUTEC SHALL PROVIDE AND FLUSH MOUNT 3-GANG BOX; 3-1/4" DEEP AT OUTLET HEIGHT. RACO 263 OR EQUAL. EC SHALL PROVIDE 2-GANG MUD RING. PROVIDE (1) 1-1/4" EMT STUB TO ACCESSIBLE CEILING.
10KLM
120VAC QUADADJACENT
4
DUPLEX RECEPTACLESTANDARD, COUNTER, CEILING HEIGHT
QUAD RECEPTACLESTANDARD, COUNTER, CEILING HEIGHT
MISCELLANEOUS PORT - PORTS AS NOTEDNOT PART OF A/V SCOPE U.O.N.
PHONE DROP - PORTS AS NOTEDNOT PART OF A/V SCOPE
PHONE AND DATA PORT - PORTS AS NOTEDNOT PART OF A/V SCOPE
DATA PORT - PORTS AS NOTEDNOT PART OF A/V SCOPE
AUDIOVISUAL
TMXT2
MXT2
FLOOR OR WALL MOUNTED AV DEVICE
T = PRIMARY TECHNOLOGYM = MOUNTING TYPEX = SCHEDULE REFERENCET2 = SECONDARY TECHNOLOGY
MXT2
T CEILING MOUNTED AV DEVICE
T = PRIMARY TECHNOLOGYM = MOUNTING TYPEX = SCHEDULE REFERENCET2 = SECONDARY
EMT CONDUIT CALLOUT - 3/4" EMT SHOWN
EMT CONDUIT CALLOUT - DUAL 1" EMT SHOWN
AGENERAL NOTE CALLOUT - REFER TO SCHEDULE ON SHEET FOR DETAILS
1 EMT STUB TO ACCESSIBLE AREA ABOVE CEILING CALLOUT- 1" EMT SHOWN
MARGINAL VIEWING THRESHOLD BASED ON 6X THE IMAGE HEIGHT
FLAT PANEL DISPLAY - WIDTH CORRESPONDS TO ACTUAL DISPLAY WIDTH UNLESS OTHERWISE NOTED. ##" IS NOMINAL DIAGONAL IMAGE SIZE.
PROJECTOR
PROJECTION SCREEN. WIDTH CORRESPONDS TO ACTUAL DIMENSIONS UNLESS OTHERWISE NOTED. ###" IS DIAGONAL IMAGE SIZE.
AV RACK - WIDTH AND DEPTH CORRESPOND TO ACTUAL DIMENSIONS UNLESS OTHERWISE NOTED.
PRIMARY TECHNOLOGY (T)SECONDARY TECHNOLOGY (T2)
C CAMERAD – DOCUMENT IP – IP CAM PTZ – PAN/TILT/ZOOM
E OTHER EQUIPMENTWAP – WIRELESS ACCESS POINT
J JUNCTION BOXWP – WEATHER PROOF#X#X# – NEMA 1 SCREW COVER BOX #
INCHES HIGH, #INCHES WIDE, #INCHES DEEPB BUTTON CONTROLLER
M – MASTER NUM – NUMERIC R – REMOTE WLS – WIRELESS
M MICROPHONEB – BOUNDARY LAV – LAVALIER GNK – GOOSENECK HH – HANDHELDHW – HEADWORN SGN – SHOTGUN WLS – WIRELESS
S SPEAKERBAR – SOUND BAR LAR– LINE ARRAY SPEAKER CAR - COLUMN ARRAY M – MONITOR P – POWEREDS – SUBWOOFER
T TOUCH PANELFT – FLIP TOP T – TABLE TOP WLS – WIRELESS (CRADLE LOCATION
SHOWN)W WALL PLATE
A – AUDIOV – VIDEOC – CONTROLL – LIGHTING[A][V][C][L] – COMBO
BRACKETS INDICATE OPTIONAL$ SWITCH
NOT SPECIFIED – SINGLE PROJECTION SCREEN UP/DOWN
CONTROLK – KEY OPERATED T – TIMER OPERATED2G - DUAL PROJECTION SCREEN UP/DOWN CONTROL
INFRASTRUCTURE
A/V SYMBOLS LEGEND
MOUNTING TYPE (M)
NOT SPECIFIED SEE WAC ABOVE COUNTERAFF ABOVE FINISHED FLOORC CEIILINGD DESKF FLUSHFL FLOORG GROUNDH HIDDENM MULLIONO OUTDOORP PENDANTPE PEDESTALR RECESSEDRF ROOFRK RACKS SURFACESW WALL AT PRJECT'S STANDARD SWITCH HEIGHTW WALL AT PROJECT'S STANDARD OUTLET HEIGHTW## WALL AT ##" AFF MEASURED
TO TOP OF BOX OR EQUIPMENTW##OC WALL AT ##" AFF MEASURED
ON CENTER OF BOX OR EQUIPMENTW##U WALL AT ##" AFF MEASURED
TO UNDERSIDE OF BOX OR EQUIPMENTX##[OC][U] X REPRESENTS ANY MOUNTING TYPE
E.G. P96U MEANS PENDENT MOUNT;96" AFF MEASURED TO UNDERSIDE OF EQUIPMENT
SECONDARY TECHNOLOGY (T2)NOT SPECIFIED – STANDARD OR LONG THROW LENSST – SHORT THROW
SECONDARY TECHNOLOGY (T2)NOT SPECIFIED – GENERIC COMMERICAL-GRADENTS – NOT TO SCALETV – INCLUDES TUNERTP – TRANSPARENTWP – WEATHERPROOF#X# – VIDEO WALL (#DISPLAYS WIDE X # DISPLAYS HIGH) E.G. 3X3
SECONDARY TECHNOLOGY (T2)NOT SPECIFIED – MOTORIZEDF – FIXEDIWB – INTERACTIVE WHITEBOARDNTS – WIDTH NOT TO SCALEPD – PULL-DOWN (MANUAL)PU – PULL-UP (MANUAL)R – REAR
SECONDARY TECHNOLOGY (T2)CB – CASTER BASEGF – GANGABLE FLOOR-STANDINGLM – LAMINATEMBL – MOBILE ROAD CASESO – SLIDE OUTWM – WALL MOUNT
MXT2
TYPICAL ATTRIBUTE TAGM = MOUNTING TYPEX = SCHEDULE REFERENCET2 = SECONDARY
MXT2
MXT2
MXT2
MXT2
MXT2
MXT2
WIRELESS COMMUNICATIONS DEVICE
SECONDARY TECHNOLOGY (T2)CR – CELLULAR REPEATER IR – IR EMITTERRX – RECEIVER TR – TRANSCEIVER TX – TRANSMITTER WMT – WIRELESS MICROPHONE TRANCEIVER
ANTENNA
SECONDARY TECHNOLOGY (T2)AM – AMFM – FMM – MICROPHONE WITH FREQUENCY BASED ON SITE SURVEYU – UHFV – VHF
NO
TE
NO
TE
NO
TE
NO
TE
##"
###"
1 1
¾
REFER TO ELECTRICAL DRAWINGS FOR ALL ELECTRICAL POWER CIRCUITING AND ASSOCIATED CONDUIT REQUIREMENTS.
DOWEL WIDTH
MAX CASE WIDTH
DEVICE ROUGH-IN BOX SCHEDULE (X)
J-HOOK TO NEAREST CABLE TRAY
1-GANG DIECAST; RACO DIECAST ALUMINUM 2-5/8" DEEP. SURFACE MOUNT.SAME AS S1, BUT HIDDEN MOUNT ABOVE CEILING PLANE AS PER TA501 #6.2-GANG DIECAST; RACO DIECAST ALUMINUM 2-5/8" DEEP. SURFACE MOUNT.SAME AS S2, BUT HIDDEN MOUNT ABOVE CEILING PLANE AS PER TA501 #6.3-GANG DIECAST; RACO DIECAST ALUMINUM 2-5/8" DEEP. SURFACE MOUNT.SAME AS S3, BUT HIDDEN MOUNT ABOVE CEILING PLANE AS PER TA501 #6.4-GANG DIECAST; RACO DIECAST ALUMINUM 2-5/8" DEEP. SURFACE MOUNT.SAME AS S4, BUT HIDDEN MOUNT ABOVE CEILING PLANE AS PER TA501 #6.
1-GANG 4" SQUARE RACO STEEL BOX, 2-1/8" DEEP WITH 1-GANG COVER. COVER EDGE TO BE FLUSH WITH FINISHED WALL. PROVIDE EXTENSION RING FOR A MINIMUM OF 2-1/2" DEEP BEFORE TRIM RING.
2-GANG 4" SQUARE RACO STEEL BOX, 2-1/8" DEEP WITH 2-GANG COVER. COVER EDGE TO BE FLUSH WITH FINISHED WALL. PROVIDE EXTENSION RING FOR A MINIMUM OF 2-1/2" DEEP BEFORE TRIM RING.
3-GANG RACO STEEL BOX, 2-1/8" DEEP WITH 3-GANG COVER. COVER EDGE TO BE FLUSH WITH FINISHED WALL.PROVIDE EXTENSION RING FOR A MINIMUM OF 2-1/2" DEEP BEFORE TRIM RING.
4-GANG RACO STEEL BOX, 2-1/8" DEEP WITH 4-GANG COVER. COVER EDGE TO BE FLUSH WITH FINISHED WALL. PROVIDE EXTENSION RING FOR A MINIMUM OF 2-1/2" DEEP BEFORE TRIM RING.
1-GANG MASONRY; RACO STEEL MASONRY BOX, NO LESS THAN 2-1/2” IN 6" CMU,BRICK OR CONCRETE AND 3-1/2” DEEP IN 8” CMU. COVER EDGE TO BE FLUSH WITH FINISHED WALL.
2-GANG MASONRY; RACO STEEL MASONRY BOX, NO LESS THAN 2-1/2” IN 6" CMU,BRICK OR CONCRETE AND 3-1/2” DEEP IN 8” CMU. COVER EDGE TO BE FLUSH WITHFINISHED WALL.
3-GANG MASONRY; RACO STEEL MASONRY BOX, NO LESS THAN 2-1/2” IN 6" CMU,BRICK OR CONCRETE AND 3-1/2” DEEP IN 8” CMU. COVER EDGE TO BE FLUSH WITH FINISHED WALL.
4-GANG MASONRY; RACO STEEL MASONRY BOX, NO LESS THAN 2-1/2” IN 6" CMU, BRICK OR CONCRETE AND 3-1/2” DEEP IN 8” CMU. COVER EDGE TO BE FLUSH WITH FINISHED WALL.
N/A
S1S1HS2S2HS3S3HS4S4H
F1
F2
F3
F4
M1
M2
M3
M4
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:09
:46 P
M
TA002
LEGEND AND GENERAL NOTES -
AV SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
FD FD
FD
187"
60"
Ae
2e 3e 4e 6e5e 7e 8e 9e
Be
Ce
De
Fe
Ge
He
E.1e
C.1e
D.1e
Ee
F.1e
H.1e
10e 11e 12e
11.1e10.1e
D.2e
H.2e
1e
?
?
OFFICE
106
WAREWASH
111
DINING
110SERVERY
105
FAMILY
RESTROOM
102
FOOD PREP
115
COOLER
113
OFFICE
116
HALL
120
FREEZER
114
?
?
LOBBY
100
VESTIBULE
100A
2e 3e 4e 6e5e 7e 8e 9e 10.1e1e
TA502
1
TA502
2
SIG
N
STORAGE
117
STORAGE
119
?
?
WOMENS
123
MENS
122
BSW
VW
NEAREST VIEWER RECOMENDATION.
THIS MAY BE MOVED CLOSER TO THE
PROJECTED IMAGE, BUT WILL REQUIRE
DESTRUCTIVE KEYSTONE
CORRECTION.
PAINT
FURTHEST VIEWER RECOMENDATION BASED ON
4% MINIMUM ELEMENT HEIGHT
EQ EQ
TA GENERAL NOTE
AV SYSTEMS ARE SHOWN FOR REFERENCE ONLY. ROUGH-IN IS IN CONTRACT. ALL AV EQUIPMENT, SYSTEMS AND PROGRAMMING IS N.I.C. BY OWNER'S FUTURE AV CONTRACTOR.
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:09
:57 P
M
TA101
FIRST LEVEL FLOOR PLAN - AV
SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
4' 16'2' 8' TA1011/8" = 1'-0"
1FIRST LEVEL FLOOR PLANTRUE NORTH
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
60"
187"
75"
60"
60"
Ae
2e 3e 4e 6e5e 7e 8e 9e
Be
Ce
De
Fe
Ge
He
E.1e
C.1e
D.1e
Ee
F.1e
H.1e
10e 11e 12e
11.1e10.1e
D.2e
H.2e
1e
(E)
ELECTRICAL
262
(E) MENS
E104
(E) STAIR
E152
(E)
VESTIBULE
E121
(E)
VESTIBULE
E122
NORTH
STAIR
E-204
(E) MENS
E
(E)
WOMENS
E(E)
CUSTODIAL
E
(E)
WOMENS
E101
FUTURECLINIC
SUPPORT
E102
FUTURECLINIC
SUPPORT
E100
FUTURECLINIC
SUPPORT
E103
(E) HALL
E108
(E) LOUNGE
E107
DINING
110
STUDENT
LOUNGE
270
READING
ROOM
240
DINING
200
CORRIDOR
265
?
?
READING
ROOM
245
2e 3e 4e 6e5e 7e 8e 9e 10.1e1e
TA502
FB
PSCHED
A
SIG
N
1
TA502
2
1% OPENNESS OR BLACKOUT SHADES REQUIRED FOR
PROJECTION PERFORMANCE
PAINT
NEAREST VIEWER RECOMENDATION.
THIS MAY BE MOVED CLOSER TO THE
PROJECTED IMAGE, BUT WILL REQUIRE
DESTRUCTIVE KEYSTONE
CORRECTION.
FURTHEST VIEWER RECOMENDATION BASED ON
4% MINIMUM ELEMENT HEIGHT
FURTHEST VIEWER RECOMENDATION BASED ON
3% MINIMUM ELEMENT HEIGHT
7' - 0" 5' - 6" 2' - 0" 4' - 6"
FB
PO
DP
OD
(E) OFFICE
SUITE
E
(E) OFFICE
E
(E) OFFICE
E(E) OFFICE
E(E) OFFICE
E
(E) OFFICE
E
(E) OFFICE
E
(E) OFFICE
E
(E) OFFICE
E
Room
250N
Room
250O
Room
250P
STORAGE
210
ELEC
205
FAMILY
RESTROOM
215
EXECUTIVE
DINING
225
FUTURE OWNER FURNISHEDAV EQUIPMENT RACK
TA5031
ROUGH-IN LOCATED ON THIS WALL
VW
B
SHEET NOTES
REGION INDICATES ALTERNATE NO. 7 FOR AV ROOM SCHEDULING INFRASTRUCTURE
A
TA GENERAL NOTE
AV SYSTEMS ARE SHOWN FOR REFERENCE ONLY. ROUGH-IN IS IN CONTRACT. ALL AV EQUIPMENT, SYSTEMS AND PROGRAMMING IS N.I.C. BY OWNER'S FUTURE AV CONTRACTOR.
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:10
:04 P
M
TA102
SECOND LEVEL FLOOR PLAN - AV
SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
4' 16'2' 8' TA1021/8" = 1'-0"
1SECOND LEVEL FLOOR PLAN TRUE NORTH
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
Ae
2e 3e 4e 6e5e 7e 8e 9e
Be
Ce
De
Fe
Ge
He
E.1e
C.1e
D.1e
Ee
F.1e
H.1e
10e 11e 12e
11.1e10.1e
D.2e
H.2e
1e
OFFICE
106
WAREWASH
111
DINING
110SERVERY
105
FAMILY
RESTROOM
102
FOOD PREP
115
STORAGE
119
COOLER
113
OFFICE
116
HALL
120
FREEZER
114
?
?
LOBBY
100
VESTIBULE
100A
2e 3e 4e 6e5e 7e 8e 9e 10.1e1e
CS1HS
CS1HS
1"
CS1HS
CS1HS
1"
BB
B B
STUB CONDUITS TO ACCESSIBLE CEILING AT DINING 200 ABOVE
?
?1"
A
CS1S
CS1S
CS2S
CS1S
CS1S
¾"
¾"
¾" ¾"
¾"
SHEET NOTES
GENERAL NOTE: OWNER'S FUTURE AV CONTRACTOR TO PROVIDE J-HOOKS ABOVE CEILING AS NECESSARY FOR SUPPORTING LOUDSPEAKER CABLES.
REGION INDICATES ALTERNATE NO. 8 BUILDING WIDE PA SYSTEM INFRASTRUCTURE.
FUTURE PA SYSTEM SHOWN AS BASIS OF INFRASTRUCTURE DESIGN
FOR GYP CEILING CONDITION EC SHALL PROVIDE ROUGH-IN AS PER TA501 DETAIL #6.
A
B
TA GENERAL NOTE
AV SYSTEMS ARE SHOWN FOR REFERENCE ONLY. ROUGH-IN IS IN CONTRACT. ALL AV EQUIPMENT, SYSTEMS AND PROGRAMMING IS N.I.C. BY OWNER'S FUTURE AV CONTRACTOR.
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:10
:06 P
M
TA111
FIRST LEVEL REFLECTED
CEILING PLAN - AV SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
4' 16'2' 8' TA1111/8" = 1'-0"
1FIRST LEVEL REFLECTED CEILING PLAN TRUE NORTH
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
187"
SS
SS
SS
Ae
2e 3e 4e 6e5e 7e 8e 9e
Be
Ce
De
Fe
Ge
He
E.1e
C.1e
D.1e
Ee
F.1e
H.1e
10e 11e 12e
11.1e10.1e
G
D.2e
H.2e
1e2e 3e 4e 6e5e 7e 8e 9e 10.1e
G
1e
TA502
(E)
ELECTRICAL
262
(E) MENS
E104
NORTH
STAIR
E-204
(E) MENS
E
(E)
WOMENS
E(E)
CUSTODIAL
E
DINING
110
STUDENT
LOUNGE
270
STORAGE
210
READING
ROOM
240
DINING
200
EXECUTIVE
DINING
225
CORRIDOR
265
FAMILY
RESTROOM
215
ELEC
205
READING
ROOM
245
1
TA502
2
CN/A
CN/A
10KLM
PAINT
14' - 2 15/16" 15' - 0 5/16"
CN/A
CN/AS
CN/AS
CN/AS
CN/AS
12' - 11 31/32"
CN/AS
CN/AS
PS1S
PS1S
PS1S
PS1S
PS1S
CN/AS
CN/A S
1
A
CN/AS
1 1 1
11
CS1HS
1
1
B
TA503 2
3
120 VAC
2
FLUSH MOUNTED CEILING POWER AND DATA FOR FUTURE PROJECTOR
8' - 11 31/32"
8' - 5 31/32"
EQ
EQ
EQ
EQ
12' - 11 31/32"
20' - 8 23/32" 13' - 1 25/32"
13' - 1 29/32"
13' - 1 23/32"
20' - 8 19/32"
20' - 8 25/32"
SHEET NOTES
GENERAL NOTE: OWNER'S FUTURE AV CONTRACTOR TO PROVIDE J-HOOKS ABOVE CEILING AS NECESSARY FOR SUPPORTING LOUDSPEAKER CABLES.
REGION INDICATES ALTERNATE FOR BUILDING WIDE PA SYSTEM INFRASTRUCTURE.
FUTURE PA SYSTEM SHOWN AS BASIS OF INFRASTRUCTURE DESIGN
FOR GYP CEILING CONDITION EC SHALL PROVIDE ROUGH-IN AS PER TA501 DETAIL #6.
A
B
TA GENERAL NOTE
AV SYSTEMS ARE SHOWN FOR REFERENCE ONLY. ROUGH-IN IS IN CONTRACT. ALL AV EQUIPMENT, SYSTEMS AND PROGRAMMING IS N.I.C. BY OWNER'S FUTURE AV CONTRACTOR.
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:10
:09 P
M
TA112
SECOND LEVEL REFLECTED
CEILING PLAN - AV SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
4' 16'2' 8' TA1121/8" = 1'-0"
1SECOND LEVEL REFLECTED CEILING PLAN TRUE NORTH
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
DETAIL ASCALE 1 : 1.5
DETAIL BSCALE 1 : 2
EC TO PROVIDE (1) 1" EMT TO ACCESSIBLE AREA ABOVE CEILING. COUPLE DIRECTLY TO IN-WALL STORAGE BOX UON.
EC TO PROVIDE (1) 1-1/4" EMT TO ACCESSIBLE AREA ABOVE CEILING. COUPLE DIRECTLY TO IN-WALL STORAGE BOX UON.
EC TO PROVIDE CHIEF PAC526FCW IN-WALL STORAGE BOX WITH WHITE FLANGE AND COVER.EC TO INSTALL AS NOTED IN AV INFRASTRUCTURE LEGEND.
CEILING
FINISHED FLOOR
GC TO PROVIDE STRUCTURAL BLOCKING AT EACH DISPLAY LOCATION, TO SUPPORT UP TO 350 LBS. COORDINATE BLOCKING WITH AVC TO COMPLY WITH DISPLAY SIZE, POSITION AND MOUNT REQUIREMENTS.
OWNER'S FUTURE AVC TO PROVIDE DISPLAY AS SPECIFIED PER LOCATION. DIFFERING SIZES SHOWN FOR REFERENCE ONLY.
ABBREVIATIONS
AVC: AUDIO VISUAL CONTRACTOR
SCC: STRUCTURED CABLING CONTRACTOR
EC: ELECTRICAL CONTRACTOR
GC: GENERAL CONTRACTOR
UON: UNLESS OTHERWISE NOTED
RE: REFER TO
EG: FOR EXAMPLE
CONDUIT SIZING
AV: 1-1/4" C. UON. ALL CONDUIT SHOWN IS DEDICATED FOR AV.
DATA: AS NOTED IN T DRAWINGS
POWER: CONDUIT AS REQUIRED
CONDUIT NOTES
ROUTE CONDUIT TO ACCESSIBLE CEILING IN DIRECTION OF CABLE TRAY WITH J-HOOK SUPPORTS TO CABLE TRAY OR AV RACKS AS APPROPRIATE.PROVIDE PULL STRING AND NYLON BUSHING AT END OF CONDUIT.
PROVIDE NO MORE THAN (2) 90-DEGREE BENDS.
CATV NOTE
SCC SHALL PROVIDE CATV CONNECTION WHEN SHOWN ON FLOOR PLAN OR IN INFRASTRUCTURE SCHEDULE.
CMU, FIRE RATED, AND OTHER NON-DRYWALL & STUD CONSTRUCTION WALLS
REPLACE IN-WALL STORAGE BOX WITH (3) SEPARATE ROUGH-IN BOXES ALL ADJACENT WITHIN 16" OF EACH OTHER:
AV: STEEL CITY 82181T-1-114-CV SQUARE TELECOMMUNICATION BOX WITH APPROPRIATE 2-GANG MUDRING AND (1) 1-1/4" CONDUIT.
DATA: STEEL CITY 82181T-1-114-CV SQUARE TELECOMMUNICATION BOX WITH APPROPRIATE 2-GANG MUDRING AND (1) 1" CONDUIT.
POWER: QUAD AC ELECTRICAL OUTLET - ROUGH-IN BOX AND CONDUIT AS REQUIRED.
COLORS AND COVER PLATES:
WHERE WALL COLOR IS WHITE NO EXCEPTIONS
WHERE WALL COLOR IS BLACK PROVIDE BLACK FLANGE INSTEAD OF WHITE.
WHERE WALL COLOR IS OTHER THAN BLACK OR WHITE, GC TO PAINT FLANGE AND COVER PLATE TO MATCH WALL.
WHERE DISPLAY INDICATED AS 'FUTURE' ON DRAWINGS, EC TO PROVIDE COVER PLATE (CHIEF #PAC526CVR[X]-KIT) TO MATCH FLANGE COLOR AND OBSCURE OPENING.
DETAIL GENERAL NOTES
40" 16:960" 16:9
AS SHOWN ONELEVATIONS
80" 16:90' - 4"
EC TO PROVIDE 1-GANG BOX COUPLED DIRECTLY TO IN-WALL STORAGE BOX. PROVIDE CONDUIT IN ACCORDANCE WITH PROJECT STANDARDS UON.
SCC TO PROVIDE DROP QUANTITY NOTED IN INFRASTRUCTURE SCHEDULE IN ACCORDANCE WITH PROJECT STANDARDS UON.
EC TO PROVIDE 1-GANG BOX COUPLED DIRECTLY TO IN-WALL STORAGE BOX. PROVIDE CONDUIT IN ACCORDANCE WITH PROJECT STANDARDS UON.
EC TO PROVIDE 120VAC IN DUPLEX RECEPTACLE.
14.25
362.0
6.08
154.5
14.25
362.0
1.25
31.8
4.63
117.5
4.63
117.5
1.25
31.8
3.88
98.4
2.88
73.0
8.44
214.3
1.31
33.2
1.66
42.2
5.63
142.9
1.66
42.2
5.63
142.9
2.38
60.3
2.38
60.3
1.31
33.2
∅ 1.73
44.0
TRADE CONDUIT SIZE 1-1/4"METRIC CONDUIT SIZE 35mm
∅ 1.38
34.9
TRADE CONDUIT SIZE 1"METRIC CONDUIT SIZE 27mm
∅ 0.88
22.2
TRADE CONDUIT SIZE 1/2"METRIC CONDUIT SIZE 16mm
3.73
94.9
1.13
28.6
3.43
87.1
2.09
53.1
R0.25
6.4
∅ 0.11
2.9
AB
RECOMMENDED ELECTRICAL BOX:RACO 560 3" X 2" BOX, 2 3/4" DEEPGANGABLE OR EQUIVALENT.
RECOMMENDED ELECTRICAL BOXCOVER: RACO 864 SINGLE DUPLEX
CEILING
FINISHED FLOOR
DETAIL GENERAL NOTESALL NOTES IDENTICAL TO DETAIL #1 WITH EXCEPTIONS NOTED
OMIT 1" AND 1-1/4" AV CONDUIT TO ACCESSIBLE CEILING
1-1/4" EMT STUBBED TO ACCESSIBLE AREA ABOVE CEILING FOR AV CABLES
3 1-GANG COMPARTMENTS DEDICATED FOR AUDIO VISUAL CABLES. CUSTOM PLATES BY OWNER'S FUTURE AVC
1-GANG DEDICATED FOR:FUTURE LOW VOLTAGE
1-GANG DEDICATED FOR:STRUCTURED CABLING DROPS
1-1/4" EMT CONDUIT DEDICATED FOR STRUCTURED CABLING STUBBED TO NEAREST ACCESIBLE CEILING WITH DIRECT ACCESSIBLE PATHWAY TO CABLE TRAY
GENERAL NOTES
A. PROVIDE FIRESTOPPING AS REQUIRED FOR ALL PENETRATIONS.
B. ALL LOW VOLTAGE CONDUITS TO BE SUPPLIED WITH NYLON BUSHING AND PULL STRING.
C. PROVIDE CLEAR PERMANENT MARKING WITHIN UNFINISHED PORTION OF FLOOR BOX TO IDENTIFY WHETHER GANG IS RESERVED FOR AV, IT OR POWER
(1) X 20 AMP DUPLEX ELECTRICAL OUTLETS. REFER TO ELECTRICAL PLANS FOR CIRCUITING AND CONDUIT REQUIREMENTS
AV AV AV
AC DATA (FUT)
1" EMT STUBBED TO ACCESSIBLE AREA ABOVE CEILING FOR AV CABLES
TUNNEL LOCATION. NOTE THAT AV GANG CONNECT TO 1-GANG DEDICATED FOR FUTURE AV CABLING
CEILING
FINISHED FLOOR
DETAIL GENERAL NOTESALL NOTES IDENTICAL TO DETAIL #1 WITH EXCEPTIONS NOTED
OU
TLE
TH
EIG
HT
1-1/4" EMT CHASE
1-1/4" EMT CHASE
FUTURE AV CONTROL PANELEC SHALL PROVIDE AND FLUSH MOUNT 3-GANG BOX; 3-1/4" DEEP AT SWITCH HEIGHT. RACO 263 OR EQUAL WITH 3-GANG RING.EC SHALL CONFIRM MUD RING SIZE WITH OWNER PRIOR TO INSTALL.
FUTURE AV INPUTEC SHALL PROVIDE AND FLUSH MOUNT 2-GANG BOX; 3-1/4" DEEP AT SWITCH HEIGHT. RACO 260 OR EQUAL WITH 2-GANG RING.EC SHALL CONFIRM MUD RING SIZE WITH OWNER PRIOR TO INSTALL.
0' -
4"
BRACKET
PA LOUDSPEAKER ELECTRICAL BOX
CONDUIT TO PREVIOUS PA LOUDSPEAKER LOCATION
CONDUIT TO NEXT PA LOUDSPEAKER LOCATION
PROVIDE PULL STRINGTO NEXT PA LOUDSPEAKER LOCATION
PROVIDE PULL STRINGTO PREVIOUS PA LOUDSPEAKER LOCATION
ATTACH BRACKET TO CEILING WITH DRYWALL SCREWS
GYPSUM CEILING
PROVIDE HOLE IN GYP CEILING - SIZE AS NEEDED;HOLE NOT TO EXCEED 3" DIAMETER.
ATTACH COVER TO BRACKET
SECURE PULL STRING TO BRACKET
PROVIDE COVER ASSEMBLY, ARLINGTON CP3540 OR EQUAL;PROVIDE FASTENERS AS NEEDED.
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:10
:10 P
M
TA501
TYPICAL DETAILS - AV SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
1 1/2" = 1'-0"1
WALL MOUNT DISPLAY - A/V ROUGH-IN DETAIL1
1 1/2" = 1'-0"5
PAC526 COORDINATION DETAIL1/2" = 1'-0"
3WALL MOUNT SIGNAGE DISPLAY - A/V ROUGH-IN DETAIL
N.T.S.4
WIREMOLD EFB6S-OG FLOOR BOX
1/2" = 1'-0"2
DETATCHED-FROM-WALL POD DISPLAY - A/V ROUGH-IN DETAIL
N.T.S.6
PA ROUGH-IN GYP CEILING CONDITION
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
LEVEL ONE100' - 0"
T.O. PARAPET124' - 0"
LEVEL TWO108' - 0"
MEZZANINE LEVEL112' - 0"
T.O. PARAPET - SOUTH126' - 0"
2e3e 1e
LEVEL ONE100' - 0"
T.O. PARAPET124' - 0"
LEVEL TWO108' - 0"
MEZZANINE LEVEL112' - 0"
T.O. PARAPET - SOUTH126' - 0"
1
TA502
IMAGE HEIGHT MAY BE REDUCED, BUT PROJECTOR WILL NEED TO MOVE DOWN THE SAME DISTANCE.
ALTERNATIVELY DESTRUCTIVE IMAGE PROCESSING KNOWN AS "KEYSTONE CORRECTION" MAY BE EMPLOYED. THIS PROCESS CAUSES VARIANCE IN BRIGHTNESS & FOCUS AND LOSS OF RESOLUTION ACROSS THE IMAGE.
LEVEL ONE100' - 0"
T.O. PARAPET124' - 0"
T.O. PARAPET - OLD
GYM126' - 8"
LEVEL TWO108' - 0"
MEZZANINE LEVEL112' - 0"
T.O. PARAPET - SOUTH126' - 0"
CeDeFeGe Ee
LEVEL ONE100' - 0"LEVEL ONE100' - 0"
T.O. PARAPET124' - 0"
T.O. PARAPET - OLD
GYM126' - 8"
LEVEL TWO108' - 0"
MEZZANINE LEVEL112' - 0"
T.O. PARAPET - SOUTH126' - 0"
29' - 8"
WALL SURFACE BY OTHERSRECOMMEND USING GOO BASIC GREY BY ALTERNATIVE SCREEN SOLUTIONS
11' -
2 9
/16"
75.00°
75.00°
75.00°
AS PER GENERAL NOTE: PROJECTOR IS FUTURE BY OWNER. BASE BID TO INCLUDE POWER AND DATA AT CEILING FOR THIS USE.
TA GENERAL NOTE
AV SYSTEMS ARE SHOWN FOR REFERENCE ONLY. ROUGH-IN IS IN CONTRACT. ALL AV EQUIPMENT, SYSTEMS AND PROGRAMMING IS N.I.C. BY OWNER'S FUTURE AV CONTRACTOR.
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:10
:14 P
M
TA502
SECTIONS & ELEVATIONS - AV
SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
1/4" = 1'-0"2
DINING 110 - SOUTH ELEVATION
1/4" = 1'-0"1
DINING 110 - SECTION WEST
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
Ae
4e
Be
TA503 2
STORAGE
210
0' -
10"
3FUTURE OWNER FURNISHEDAV EQUIPMENT RACK
ROUGH-IN LOCATED ON THIS WALL
OPEN DOOR POSITION SHOWN FOR REFERENCE
T.O. PARAPET124' - 0"
Ae
T.O. PARAPET - OLD
GYM126' - 8"
MEZZANINE LEVEL112' - 0"
T.O. PARAPET - SOUTH126' - 0"
Be
T.O. PARAPET124' - 0"
T.O. PARAPET - OLD
GYM126' - 8"
MEZZANINE LEVEL112' - 0"
T.O. PARAPET - SOUTH126' - 0"
STORAGE
210
MEZZANINE LEVEL112' - 0"
4e
MEZZANINE LEVEL112' - 0"
2' - 4"
3' -
0"
PROVIDE AV ROUGH-IN WITHIN SPACE INDICATED BY DASHED LINES
1' -
6"
APPROXIMATE STUD LOCATION
EC SHALL PROVIDE AND FLUSH MOUNT NEMA 121204 TYPE 1 SCRE COVER BOX
EC SHALL PROVIDE FLUSH MOUNT DATA ROUGH-IN.SCC SHALL PROVIDE (4) DATA DROPS.
EC SHALL PROVIDE FLUSH MOUNT QUAD RECEPTACLE WITH 120VAC/20A DEDICATED CIRCUIT.
EC SHALL PROVIDE (4) 1-1/4" EMT STUBS TO ACCESSIBLE CEILING
STORAGE
210
TA GENERAL NOTE
AV SYSTEMS ARE SHOWN FOR REFERENCE ONLY. ROUGH-IN IS IN CONTRACT. ALL AV EQUIPMENT, SYSTEMS AND PROGRAMMING IS N.I.C. BY OWNER'S FUTURE AV CONTRACTOR.
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:10
:15 P
M
TA503
STORAGE 210 - DETAILED VIEWS -
AV SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
1/2" = 1'-0"1
STORAGE 210 - ENLARGED FLOOR PLAN1/2" = 1'-0"
2STORAGE 210 - EAST ELEVATION
1/2" = 1'-0"3
STORAGE 210 - SOUTH ELEVATION
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
NC NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
TO CMC LAN
AV RACK (STORAGE 210)
CEILING (EXECUTIVE DINING 225)
DISPLAY LOCATION (EXECUTIVE DINING 225)
TO CMC LAN
UNDER DISPLAY (EXECUTIVE DINING 225)
NORTH SIDE OF TABLE (EXECUTIVE DINING 225)
SOUTH SIDE OF TABLE (EXECUTIVE DINING 225)
OUTLET HEIGHT UNDER DISPLAY (EXECUTIVE DINING 225)
ROUGH-IN AVAILABLENO AV SYSTEMS
PLANNED
ROUGH-IN AVAILABLENO AV SYSTEMS
PLANNED
TO CMC LAN
AV RACK (STORAGE 210)
CEILING (DINING 110)
DISPLAY LOCATION (EXECUTIVE DINING 225)
TO CMC LAN
SW WALL LEVEL 1 (DINING 110)
TO CMC LAN
CEILING (DINING 200)
AV RACK (STORAGE 210)
SCALE: N.T.S.1
EXECUTIVE DINING (225) - FUNCTIONAL DIAGRAM
SCALE: N.T.S.3
DINING (110 & 200) - FUNCTIONAL DIAGRAM
SCALE: N.T.S.2
SHARED AUDIO DSP - FUNCTIONAL DIAGRAM
75" LED DISPLAY
TV75
FRONT WALL
HDMI
RS232
VIDEO RECEIVER
DM-RX
BEHIND DISPLAY
DM HDMI
RS232
COORDINATE WITH OWNER:
* EXACT FLIP TOP CONNECTIVITY
* COMPATIBILITY WITH SELECTED FURNITURE
DIGITAL MEDIA PRESENTATION SWITCHER
DMPS-150-01DM
HDMI 1
HDMI 2
HDMI 3
MIC
DM OUT
HDMI OUT
LAN
AUDIO LEFT
AUDIO RIGHT
AUDIO AMPLIFIERAMP1
1
2
1
2
CEILING LOUDSPEAKERSPK1
8Ω CEILING LOUDSPEAKERSPK1
8Ω
BUTTON CONTROLLER/ROOM CONTROLLER
BTN
ON CONFERENCER ROOM WALL
COM
LAN PoE
RELAY
FLOOR BOX
TOP OF LECTERN
VIDEO TRANSMITTER
DM-TX3
UNDER TABLE
HDMI 1
HDMI 2
DP
DM
TABLE BOX
FT-2
TABLE SURFACE
COMMUNICATE WITH DMPS USING EISC(ETHERNET INTERSYSTEM COMMUNICATION)
PROJECTOR
PROJ1
CEIILING
HDMI
RS232
VIDEO RECEIVER
DM-RX
BEHIND DISPLAY
DM HDMI
RS232
DIGITAL MEDIA PRESENTATION SWITCHER
DMPS-150-02DM
HDMI 1
HDMI 2
HDMI 3
MIC
DM OUT
HDMI OUT
LAN
AUDIO LEFT
AUDIO RIGHT
BUTTON CONTROLLER/ROOM CONTROLLER
BTN
SWITCH HEIGHT
COM
LAN PoE
RELAY
COMMUNICATE WITH DMPS USING EISC(ETHERNET INTERSYSTEM COMMUNICATION)
WIRELESS MICROPHONE RECEIVER
WLESSANT A
ANT B
AUD OUT
REMOTE ANTENNAS IF NECESSARY
VIDEO TRANSMITTER
DM-TX1
OUTLET HEIGHT
HDMI IN DM
8X6 AUDIO DSP
DSPMIC/LINE 1
MIC/LINE 2
MIC/LINE 3
MIC/LINE 4
MIC/LINE 5
MIC/LINE 6
MIC/LINE 7
MIC/LINE 8
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
LAN
CEILING LOUDSPEAKERSPK2
60W CEILING LOUDSPEAKERSPK2
60W CEILING LOUDSPEAKERSPK2
60W
CEILING LOUDSPEAKERSPK1
30W CEILING LOUDSPEAKERSPK1
30W
CEILING LOUDSPEAKERSPK1
30W CEILING LOUDSPEAKERSPK1
30W
AUDIO AMPLIFIER (200W@70V)AMP2
1 1
AUDIO AMPLIFIER (200W@70V)AMP2
1 1
HDMI
mDP
DSP MIC/LINE 5
WLESSAUD OUT
DM INDM
DSP MIC/LINE 1
DSP MIC/LINE 2
DMPS-150-01LEFT
DMPS-150-01RIGHT
DMPS-150-02LEFT
DMPS-150-02RIGHT
DSPOUT 1
DSPOUT 2
DSPOUT 3
DSPOUT 4
AMP1 1
AMP1 2
AMP2-01 1
AMP2-02 1
DSP MIC/LINE 3
DSP MIC/LINE 4
PA HEAD ENDAUDIO OUTTA602
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:10
:15 P
M
TA601
FUNCTIONAL DIAGRAMS 1/2 - AV
SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College
1. SYSTEM SHALL MEET OR EXCEED ANSI/AVIXA A102.01:2017 AUDIO COVERAGE
UNIFORMITY IN LISTENER AREAS FOR A COVERAGE ENVELOPE OF 12dB
MEASURED OVER 6 OCTAVES CENTERED AT 250HZ, 500HZ, 1000HZ, 2000HZ,
4000HZ AND 8000HZ. THE "LISTENER AREAS" ARE LOOSELY DEFINED AS ALL
PUBLIC AREAS IN THE BUILDING.
2. SYSTEM SHALL BE CAPABLE OF EXCEEDING AMBIENT NOISE LEVEL BY 15 dB AT
EACH OCTAVE TESTED.
3. RECOMMENDED HEADEND IS QSYS CORE 110f TO ALLOW FOR A VARIETY OF
PAGING FUNCTIONALITY INCLUDING LIVE PAGING, ZONING, SCHEDULED
MESSAGES AND OTHER ADVANCED PROGRAMMING FEATURES.
4. K2 EXPECTS ALL LOUDSPEAKERS TO BE IN A SINGLE ZONE. VERIFY WITH OWNER
AT TIME OF BID.
5. CONTRATOR SHALL TAP LOUDSPEAKERS TO ENSURE APPROPRIATE LEVEL FOR
THE SPACE IN WHICH EACH LOUDSPEAKERS IS LOCATED. E.G. A RESTROOM
WITH LOW AMBIENT NOISE LEVELS WILL BE TAPPED MUCH LOWER THAN A
COMPARABLE LOUDSPEAKER IN A BUSY CIRCULATION AREA. STRIVING TO
EXCEED AMBIENT NOISE LEVEL BY 15-20dB WILL REDUCE THE LIKELIHOOD OF
STARTLING OCCUPANTS.
PA SYSTEM ALTERNATE BASIS OF DESIGN NOTES:
TO CMC LAN
TO CMC LAN
OUTLET HEIGHT ON COLUMN (STUDENT LOUNGE 270)
ROUGH-IN AVAILABLEFOR FUTURE AV SYSTEMS
CEILING (STUDENT LOUNGE 270)
ROUGH-IN AVAILABLEFOR FUTURE AV SYSTEMS
SCALE: N.T.S.1
DINING 110 SIGNAGE - FUNCTIONAL DIAGRAM
SCALE: N.T.S.2
STUDENT LOUNGE 270 - FUNCTIONAL DIAGRAM (TYPICAL OF 2 SYSTEMS)
SCALE: N.T.S.4
PA SYSTEM ALTERNATE
DINING 200 SIGNAGE - FUNCTIONAL DIAGRAM
SCALE: N.T.S.3
STUDENT LOUNGE 270 FUTURE PROJECTION - FUNCTIONAL DIAGRAM
65" LED DISPLAY
TV65
WALL
HDMI
RS232
DIGITAL SIGNAGE PLAYER
PLAYER
BEHIND DISPLAY
LAN HDMI
RS232
60" LED DISPLAY
TV60
WALL
HDMI
RS232
SCALING AUTO SWITCHER RECEIVER
SCALER-RX
BEHIND DISPLAY
FROM TX HDMI
SCALING AUTO SWITCHER TRANSMITTER
SCALER-TV
ON WALL UNDER DISPLAY
HDMI TO RX
BUTTON CONTROLLER/ROOM CONTROLLER
B-CTRL
ON WALL UNDER DISPLAY
COM
LAN PoE
SCHEDULE DISPLAY OFF TIME IN ACCORDANCEWITH MANUFACTURER RECOMMENDATIONS
AMPLIFIERSELECTION BY CONTRACTOR
MDF 277
1 1TYPICAL PA LOUDSPEAKERSELECTION BY CONTRACTORGYMNASIUM BUILDING
TAP
TAP VALUES WIL VARY BY SPACE
AND LOUDSEAKER TYPE.
CONNECT ALL LOUDSPEAKERS IN
PARALLEL.
ADDITIONAL AMPLIFIERS ASNECESSARY TO ACHIEVE POWER
AND ZONING REQUIREMENTS
PROCESSOR SHALL BE CAPABLE OF REMOTE LIVE PAGING
STATIONS, BUT NOT ARE ASSUMED FOR BASIS OF DESIGN.
PROCESSOR SHALL BE CAPABLE OF MULTIPLE ZONES, BUT
ONE 1 IS ASSUMED FOR BASIS OF DESIGN. VERIFY BASIS OF
DESIGN ASSUMPTIONS WITH OWNER AT TIME OF BID.
PA HEAD END
LAN AUDIO OUT
AUDIO OUT
PROVIDE PAGES TO DININGLOUDSPEAKER SYSTEMS. AUDIOSIGNAL SHOWN, BUT NETWORKDELIVERY MAY BE SIMPLER TOCOORDINATE.
DSP MIC/LINE 8 TA601
CMC LAN
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
AndersonMasonDale Architects, P.C.3198 Speer Boulevard
Denver, CO, 80211Telephone: 303-294-9448
Architect
Sopris Engineering502 Main Street, Suite A-3
Carbondale, CO 81623Telephone: 970-704-0311
Civil Engineer
Lime Green Design900 E. Louisiana Ave, Suite 289
Denver, CO 80210Telephone: 303-733-7558
Landscape Architect
KL&A Engineers215 N. 12th Street, Unit E
Carbondale, CO 81623Telephone: 970-927-5174
Structural Engineer
Cator Ruma and Associates, Co896 Tabor Street
Lakewood, CO 80401Telephone: 303-232-6200
MEP Engineer
K2 Audio, LLC5777 Central Ave, Suite 225
Boulder, CO 80301Telephone: 303-865-5500
AV / IT / Security / Acoustics
Jedrziewski Designs1537 East Yale Avenue
Salt Lake City, UT 84105Telephone: 801-582-9747
Food Service
2/2
0/2
01
9 5
:10
:16 P
M
TA602
FUNCTIONAL DIAGRAMS 2/2 - AV
SYSTEMS
17.061.00
RT
NH
N/A
CMC Student Commons
17.061.00
Colorado Mountain College
12/14/2018100% Design Development
02/01/201950% CD Coordination Set
02/22/2019Construction Documents
E
Y
E
Spring Valley at Glenwood Springs Campus3000 County Road 114
Glenwood Springs, CO 81601
CMC Student Commons
& Campus Improvements
17-061
Colorado Mountain College