7/30/2019 Concealed Upright Sprinkler
http://slidepdf.com/reader/full/concealed-upright-sprinkler 1/8
General Description The Model CC1 Combustible Con-cealed Sprinklers are fast response,
upright, specific application sprinklersdesigned to provide protection of lighthazard combustible, as well as non-combustible, concealed spaces requir-ing sprinkler protection. The CC1Sprinklers comply with the criterion forthe protection of combustible con-cealed spaces as described in NFPA13.
The Model CC1 Sprinklers can insome cases allow for the use of Blaze-Master® CPVC piping within con-cealed spaces requiring automaticsprinkler protection. At one time, thelisting of CPVC piping for fire protec-tion systems did not allow the use ofCPVC piping in combustible con-cealed spaces requiring automaticsprinkler protection. With the extensivefull scale fire testing of the Model CC1Combustible Concealed Space Sprin-klers, performed at UL, BlazeMasterCPVC may now be used in the speci-fied combustible concealed spaces re-quiring automatic sprinkler protection,when installed in accordance with thisTechnical Data Sheet.
The effectiveness of the Model CC1Sprinklers, in the combustible con-cealed spaces invest igated, wasclearly evident during the full scale fire
testing for this product. Concealedspaces between floors, as well as lowpitch attics are inherently shallow.Standard spray sprinklers, by design,have an umbrella like spray patternthat poses a difficult challenge whentrying to achieve effective coverage
within a shallow space. The ModelCC1 Combustible Concealed SpaceSprinklers have addressed this difficultfire challenge.
WARNING The Model CC1 Combustible Con- cealed Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso- ciation, in addition to the standards of any other authorities having jurisdic- tion. Failure to do so may impair the performance of these devices.
The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition.The installing contractor or manufac- turer should be contacted with any questions.
Sprinkler Identification Number TY1189 - Upright, 2.8 K
TY1189 is a redesignation for C1189.
Technical Data ApprovalsUL and C-UL Listed.(Listings and approvals only apply tothe service conditions indicated in theDesign Criteria sections.)
Maximum Working Pressure175 psi (12,1 bar)
Pipe Thread Connection1/2 inch NPT or ISO 7-R3/4
Discharge CoefficientK = 2.8 GPM/psi1/2
(40,3 LPM/bar1/2)
Temperature Rating175°F/79°C
FinishNatural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . BrassButton . . . . . . . . . . . . BronzeSealing Assembly . . . . . . . . . .
. . . . . . Stainless Steel w/Teflon†Bulb . . . . . . . Glass (3 mm dia.)Compression Screw . . . . . . BrassDeflector . . . . . . . . . . . Bronze† DuPont Registered Trademark
Page 1 of 8 TFP630JULY, 2004
Model CC1 — 2.8 K-factor Combustible Concealed Space Sprinklers TM
Specific Application, Upright
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
7/30/2019 Concealed Upright Sprinkler
http://slidepdf.com/reader/full/concealed-upright-sprinkler 2/8
Operation The glass bulb contains a fluid thatexpands when exposed to heat. Whenthe rated temperature is reached, thefluid expands sufficiently to shatter theglass bulb allowing the sprinkler to ac-tivate and flow water.
Design Criteria - CPVC Pipe (Fig. 2 & 3) Area Of Use:Horizontal (slope not exceeding 2 in12) combustible concealed spaces of
• Wood truss construction or bar joistconstruction (Fig. 2).
• Non-combustible insulation filledsolid wood or composite wood joistconstruction (Fig. 3).
NOTE In order to be considered “non-com- bustible insulation filled solid wood or composite wood joist construction”,the insulation (including insulation pro-
vided with a combustible vapor bar- rier), must completely fill the pockets between the joists to the bottom of the
joists, and the insulation must be se- cured in place with metal wire netting.The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the op- eration of the CC1 Sprinklers in the event of a fire.
Concealed Space Area:The area of the concealed space is notlimited; however, for both Fig. 2 andFig. 3, where CPVC pipe is being util-
ized, draft-curtains or full height wallsmust be provided at 1000 ft2 (93 m2)areas. This draft curtain shall be atleast 1/3 the depth of the concealedspace or 8 inches (200 mm), which-ever is greater, and be constructedusing a material which will not allowheat to escape through or above thedraft curtain.
Concealed Space Size:The depth of the concealed space is36 inches (915 mm) maximum to 12inches (305 mm) minimum.
SystemType:Light hazard, wet pipe system.
Minimum Distance Between CC1Sprinklers:6 feet (3,1 m). Minimum spacing does not apply to any additional sprinklers required for protection of BlazeMaster CPVC that is offset over an obstruc- tion.
Maximum Distance Between CC1Sprinklers:10 feet (3,1 m).
Maximum Coverage Area:100 ft2 (9,3 m2).
Deflector Position:1-1/2 to 4 inches (40 to 100 mm) belowupper deck for wood truss constructionor bar joist construction (Fig. 2).
1-1/2 to 2 inches (40 to 50 mm) belowsolid wood or composite wood joists(Fig. 3).
Minimum Distance Away FromTrusses:4-1/2 inches (114 mm).
Remote Area:The remote area is 1000 ft2 (93 m2).
The remote area does not include any additional sprinklers required for pro- tection of BlazeMaster CPVC that is offset over an obstruction.
Required Density:0.10 gpm/ft2 (4,1 mm/min).
Minimum Operating Pressure:10 psi (0,7 bar).
Obstructions:All obstruction criteria per NFPA forstandard spray sprinklers apply (Ref.Figure 8), unless modified by thisTechnical Data Sheet.
UL Listed Use Of BlazeMaster CPVCPiping With Model CC1 Sprinklers:Only BlazeMaster CPVC product maybe used in concealed spaces requiringautomatic sprinklers, when used inconjunction with Model CC1 Sprin-klers. In order to use the BlazeMasterCPVC product for wood truss or bar
joist construction,the horizontal run of
pipe must be a maximum of 6 inches(150 mm) above the ceiling or non-combustible ceiling insulation, or 1/3the depth of concealed space (asmeasured from the top surface of theceiling to the bottom of the deckabove), whichever is smaller (Fig. 2).For insulation filled solid wood or com-posite wood joist construction, thehorizontal run of pipe must be a maxi-mum of 6 inches (150 mm) above ceil-ing or non-combustible ceiling insula-tion, or 1/3 the depth of concealedspace (as measured from the top sur-face of theceiling to the bottomsurfaceof the joist insulation above), which-
ever is smaller (Fig. 3). The CPVC pip-ing can then be used to supply theModel CC1 Sprinklers, as well as thesprinklers below the ceiling. Unlessmodified by this Technical Data Sheet,all other guidelines of the “BlazeMas-ter — Installation Instructions & Tech-nical Manual” must be met. When us-ing 1 inch (DN25) or larger pipe, ahanger must be located at the trussnearest a sprig for purposes of re-straint. If using 3/4 inch (DN19) piping,all sprigs over 12 inches (305 mm)must be laterally braced using meth-ods described in the NFPA standards.
Where the CPVC must be offset upand over an obstruction and the pipeexceeds the allowed horizontal posi-tioning requirements specified aboveas well as shown in Figure 2 and 3,additional Model CC1 Sprinklers are tobe installed as shown in Figure 2 and3 to protect the BlazeMaster CPVCproduct.
A minimum lateral distance of 18inches (460 mm) must be maintainedbetween the CPVC pipe and heatpumps, fan motors, and heat lamps.
Page 2 of 8 TFP630
FIGURE 1MODEL CC1 SPRINKLER
CROSSSECTION
-1 Frame
Button
Sealing
Deflector
BulbCompression
Assembly
Screw-6
-3
54
-
2
-
-
2
1
3
4
Components:5
6
FRAME
THREAD
1/2" NPT
RELIEF
FLATSWRENCH
ARMS
FRONTELEVATION
7/16" (11,1 mm)NOMINAL MAKE-IN
SPRINKLER
(27,0 mm)1-1/16"
2-1/4"(57,2 mm)
7/30/2019 Concealed Upright Sprinkler
http://slidepdf.com/reader/full/concealed-upright-sprinkler 3/8
TFP630 Page 3 of 8
FIGURE 2 WOOD TRUSS CONSTRUCTION OR COMBUSTIBLE BAR JOIST CONSTRUCTION (CPVC PIPE)
CROSS SECTION ELEVATION VIEW
FIGURE 3 NON-COMBUSTIBLE INSULATION FILLED UPPER DECK
SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION (CPVC PIPE) CROSS SECTION ELEVATION VIEW
WHEN OFFSETTING CPVC PIPE OVERAN OBSTRUCTION,A CC1 SPRINKLER
MUST BE INSTALLED DIRECTLY ON THE
CEILING
4-1/2" (114 mm) MINIMUMFROM FACE OF WOOD TRUSSOR TOP CHORD OF BAR JOIST
6" (150 mm)MAXIMUM FOR
CPVC PIPE
UPPER DECK
OBSTRUCTION
MAXIMUM
12" (450 mm)
36" (915 mm)
MINIMUM
6" (150 mm) MAXIMUM ABOVE CEILING ORNON-COMBUSTIBLE CEILING INSULATION,
OR 1/3 THE DEPTH OF CONCEALED SPACE
MAXIMUM
1-1/2" (40 mm)
4" (100 mm)
MINIMUM
CPVC PIPE OVER THE OBSTRUCTION (AS MEASURED FROM TOP SURFACE OFCEILING TO BOTTOM OF DECKABOVE),
BOTTOMOF PIPE
WHICHEVER IS SMALLER
CC1SPRINKLER
PARALLEL WITH
FRAMEARMS OFSPRINKLER MUST
BE INSTALLED
TRUSSES OR JOISTS,NOT NECESSARILY
WITH PIPE
UPPERDECK
NON-COMBUSTIBLEINSULATION
OBSTRUCTION
MAXIMUM
12" (450 mm)
36" (915 mm)
MINIMUM
MAXIMUM
1-1/2" (40 mm)
2" (50 mm)
MINIMUM6" (150 mm)
MAXIMUM FORCPVC PIPE
COMPOSITEWOOD JOISTS
SOLID WOODJOISTS
CEILING
WHEN OFFSETTING CPVC PIPE OVERAN OBSTRUCTION, A CC1 SPRINKLER
MUST BE INSTALLED DIRECTLY ON THE
6" (150 mm) MAXIMUMABOVE CEILING ORNON-COMBUSTIBLE CEILING INSULATION,OR 1/3 THE DEPTH OF CONCEALED SPACE
CPVC PIPE OVER THE OBSTRUCTION (AS MEASURED FROM TOP SURFACEOF CEILING TO BOTTOM SURFACE
BOTTOMOF PIPE
OF JOIST INSULATION ABOVE),WHICHEVER IS SMALLER
CC1SPRINKLER
NOT NECESSARILY WITH PIPE
FRAME ARMS OF SPRINKLERMUST BE INSTALLED PARALLEL
WITH TRUSSES OR JOISTS,
7/30/2019 Concealed Upright Sprinkler
http://slidepdf.com/reader/full/concealed-upright-sprinkler 4/8
Design Criteria - Steel Pipe (Fig. 4, 5 ,& 6) Area Of Use: Horizontal (slope not
exceeding 2 in 12) combustible con-cealed spaces of
• Wood truss construction or bar joistconstruction (Fig. 4).
• Solid wood joist construction (Fig. 5)where the upper deck and ceiling
joists may have a maximum depth of12 inches (300 mm) and typical oncenter joist spacing of minimum 16inches (400 mm).
• Non-combustible insulation filledsolid wood joist or wood composite
joist construction (Fig. 6).
NOTE In order to be considered “non-com- bustible insulation filled solid wood
joist or composite wood joist construc- tion”, the insulation (including insula- tion provided with a combustible vapor barrier), must completely fill the pock- ets between the joists to the bottom of the joists, and the insulation must be secured in place with metal wire net- ting. The metal wire netting is intended to hold the insulation in place should the insulation become wetted by the operation of the CC1 Sprinklers in the event of a fire.
Concealed Space Area:
The area of the concealed space is notlimited; however,
• for wood truss construction or con-cealed spaces of non-combustiblebar joist construction (Fig. 4) draft-curtains or full height walls must beprovided at 1000 ft2 (93 m2) areas.This draft curtain shall be at least 1/3the depth of the concealed space or8 inches (200 mm), whichever isgreater, and be constructed using amaterial which will not allow heat toescape through or above the draftcurtain.
• for solid wood joist construction (Fig.
5), blocking must be provided ineach upper deck and ceiling joistchannel at a maximum 32 feet (9,75m) intervals. This blocking shall beinstalled to the full depth of the joistsand be installed so as to not allowheat to escape through or above theblocking. The blocking must be con-structed using a non-combustiblematerial or the joist construction ma-terial.
Solid wall construction or draft cur-tains must protrude below the joist aminimum of 6 inches (150 mm) or
1/3 the space, whichever is smallestand run lateral ly with the joistspaced at 25 feet (7,6 m) width maxi-mum to limit the area to a maximumof 1000 ft2 (93 m2). The draft curtainmay be constructed of 1/4 inch (6,4mm) plywood to prevent heat fromescaping beyond the area.
• for non-combustible insulation filledsolid wood joist or composite wood
joist construction (Fig. 6), the re-quirement for draft curtains or block-ing does not apply.
Concealed Space Size:The minimum and maximum con-cealed space depth is as follows:
For wood truss construction or con-cealed spaces of non-combustible bar
joist construction (Fig.4) the depth ofthe concealed space is 36 inches (915mm) maximum to 12 inches (305 mm)minimum.
For solid wood joist construction (Fig.5) or for non-combustible insulationfilled solid wood or composite wood
joist construction (Fig. 6), the maxi-mum depth of the concealed space is54 inches (1372 mm) from bottom ofupper deck to top of ceiling, and theminimum depth is 6 inches (150 mm)from the bottom of the upper deck
joists to the top of the ceiling joists.
SystemType:Light hazard, wet pipe system.
Minimum Distance Between CC1Sprinklers:6 feet (1,8 m).
Maximum Distance Between CC1Sprinklers:10 feet (3,1 m)
Maximum Coverage Area:100 ft2 (9,3 m2).
Deflector Position:1-1/2 to 4 inches (40 to 100 mm) belowupper deck for wood truss constructionor concealed spaces of non-combusti-ble bar joist construction (Fig. 4).
1-1/2 to 2 inches (40 to 50 mm) belowsolid wood joists (Fig. 5).
1-1/2 to 2 inches (40 to 50 mm) below
non-combustible insulation filled solidwood joists or composite wood joists(Fig. 6).
Remote Area:The remote area for wood truss con-struction or bar joist construction (Fig.4) or solid wood joist construction (Fig.5) is 1000 ft2 (93 m2).
The remote area for non-combustibleinsulation filled solid wood joist orwood composite joist construction(Fig. 6) is to be calculated per the re-quirements of NFPA 13.
Required Density:0.10 gpm/ft2 (4,1 mm/min).
Minimum Operating Pressure:10 psi (0,7 bar).
Obstructions:All obstruction criteria per NFPA forstandard spray sprinklers apply (Ref.Figure 8), unless modified by thisTechnical Data Sheet.
Page 4 of 8 TFP630
7/30/2019 Concealed Upright Sprinkler
http://slidepdf.com/reader/full/concealed-upright-sprinkler 5/8
TFP630 Page 5 of 8
FIGURE 5 SOLID WOOD JOIST CONSTRUCTION (STEEL PIPE)
CROSS SECTION ELEVATION VIEW
54" (1372 mm)MAXIMUM
2" (51 mm) MAXIMUM1-1/2" (38 mm) MINIMUM
CC1 SPRINKLER
WOOD JOISTS2x FLOOR SOLID
DECKUPPER
CEILINGFRAMINGCEILING
FRAME ARMS OF SPRINKLER MUST BEINSTALLED PARALLEL WITH WOOD JOISTS,
6" (152 mm)TO
36" (914 mm)
NOT NECESSARILY WITH PIPE
FIGURE 4 WOOD TRUSS CONSTRUCTION OR NON-COMBUSTIBLE BAR JOIST CONSTRUCTION (STEEL PIPE)
CROSS SECTION ELEVATION VIEW
CEILING
4-1/2" (114 mm) MINIMUMFROM FACE OF WOOD TRUSSOR TOP CHORD OF BAR JOIST
CC1
SPRINKLERUPPER DECK
PARALLEL WITH
FRAME ARMS OFSPRINKLER MUST
BE INSTALLED
TRUSSES OR JOISTS,NOT NECESSARILY
WITH PIPE
MAXIMUM
1-1/2" (40 mm)
4" (100 mm)
MINIMUM
MAXIMUM
12" (450 mm)
36" (915 mm)
MINIMUM
7/30/2019 Concealed Upright Sprinkler
http://slidepdf.com/reader/full/concealed-upright-sprinkler 6/8
Installation The Model CC1 Sprinklers must be
installed in accordance with the follow-ing instructions:
NOTES The CC1 Sprinklers are to be installed upright and with their frame arms (ref.Figure 2, 3, 4, 5, or 6 as applicable) parallel with the wood trusses, top chord of the bar joist, or wood joists,as opposed to being necessarily par- allel with the pipe.
Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 175°F/79°C tempera- ture rating.
A leak tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- mum of 20 ft.lbs. (28,5 Nm) of torque is to be used to install sprinklers.Higher levels of torque may distort the sprinkler inlet with consequent leak- age or impairment of the sprinkler.
The Model CC1 Sprinklers must onlybe installed in the upright position with
the deflector parallel to the upper deck.With pipe thread sealant applied tothe pipe threads, use only the W-Type20 (End B) Sprinkler Wrench (Figure
7) for installation of the Model CC1Sprinklers by applying the wrench tothe sprinkler wrench flats only.
Page 6 of 8 TFP630
FIGURE 6 NON-COMBUSTIBLE INSULATION FILLED UPPER DECK
SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION (STEEL PIPE) CROSS SECTION ELEVATION VIEW
NON-COMBUSTIBLE
INSULATION
FRAME ARMS OF SPRINKLER MUST BEINSTALLED PARALLEL WITH WOOD JOISTS,
NOT NECESSARILY WITH PIPE
54" (1372 mm)MAXIMUM
6" (152 mm)
TO36" (914 mm)2" (51 mm) MAXIMUM
1-1/2" (38 mm) MINIMUM
FRAMINGCEILING CEILING
WOOD JOISTS2x FLOOR SOLID
SPRINKLERCC1
DECK
UPPER
WOOD JOISTSCOMPOSITE
FIGURE 7 W-TYPE 20 SPRINKLER
WRENCH
WRENCH RECESS(USE END "B" FOR
MODEL CC1)
7/30/2019 Concealed Upright Sprinkler
http://slidepdf.com/reader/full/concealed-upright-sprinkler 7/8
Care and Maintenance The Model CC1 Sprinklers must bemaintained and serviced in accord-ance with the following instructions:
NOTE Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must be obtained from the proper authorities and all personnel who may be affected by this action must be no- tified.
Sprinklers that are found to be leakingor exhibiting visible signs of corrosionmust be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwisealtered after leaving the factory. Modi-f ied sprinklers must be replaced.Sprinklers that have been exposed tocorrosive products of combustion, buthave not operated, should be replacedif they cannot be completely cleanedby wiping the sprinkler with a cloth orby brushing it with a soft bristle brush.
Care must be exercised to avoid dam-age to the sprinklers - before, during,and after installation. Sprinklers dam-aged by dropping, striking, wrenchtwist/slippage, or the like, must be re-placed. Also, replace any sprinkler thathas a cracked bulb or that has lostliquid from its bulb. (Ref. InstallationSection).
The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-tion Association (e.g., NFPA 25), inaddition to the standards of any otherauthorities having jurisdiction. The in-stalling contractor or sprinkler manu-facturer should be contacted relativeto any questions.
It is recommended that automaticsprinkler systems be inspected,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcodes.
TFP630 Page 7 of 8
OBSTRUCTION
CC1SPRINKLER
C
D
A
OBSTRUCTION
UPPERDECK
LOWERDECK
A
CC1SPRINKLER
CC1SPRINKLER
UPPERDECK
LOWERDECK
A
B
OBSTRUCTION
CC1
SPRINKLER
A
UPPER DECKOR BOTTOM OF
NON-COMUSTIBLEINSULATION
B
Centerline ofSprinkler to Side
of Obstruction
Maximum AllowableDistance of Deflector
Above Bottom of
Obstruction(A) (B)
Distance from
<12" 0"<(304,8 mm)
12" to <18"
(304,8 mm to <457,2 mm)
2-1/2"
(63,5 mm)18" to <24"(457,2 mm to <609,6 mm)
3-1/2"(88,9 mm)
24" to <30"(609,6 mm to <762,0 mm)
5-1/2"(139,7 mm)
30" to <36"(762,0 mm to <914,4 mm)
7-1/2"(190,5 mm)
36" to <42"(914,4 mm to <1066,8 mm)
9-1/2"(241,3 mm)
42" to <48"(1066,8 mm to <1219,2 mm)
12"(304,8 mm)
48" to <54"(1219,2 mm to <1371,6 mm)
14"(355,6 mm)
54" to <60"
(1371,6 mm to <1524,0 mm)
16-1/2"
(419,1 mm)
(0 mm)
HorizontalDistance
MinimumVertical DistanceBelow Deflector
(A)(B)
6" 3"( 152,4 mm)
>6" to 9"(>152,4 to 228,6 mm)
4"(101,6 mm)
>9" to 12"(>228,6 mm to 304,8 mm)
6"(88,9 mm)
>12" to 15"(>304,8 mm to 381,0 mm)
8"(203,2 mm)
>15" to 18"(>381,0 to 457,2 mm) 9-1/2"(241,3 mm)
>18" to 24"(457,2 mm to 609,6 mm)
12-1/2"(317,5 mm)
>24" to 30"(>609,6 mm to 762,0 mm)
15-1/2"(393,7 mm)
>30"(>762,0 mm)
18"(457,2 mm)
(76,2 mm)
ELEVATION VIEW PLAN VIEWA 3C or 3DA 24" (609,6 mm)
(Use dimension C or D, whichever is greater)
C
D
OBSTRUCTION
NOTE:WEB MEMBERS AND GUSSETS
OBSTRUCTIONS PROVIDED THEMINIMUM 4-1/2 INCH LATERALDISTANCE (FIG. 2 & 4) REQUIREDBY THE SPECIFIC APPLICATIONLISTING IS MAINTAINED.
SHALL NOT BE CONSIDERED
FIGURE 8 NFPA 13 OBSTRUCTION TO WATER DISTRIBUTION CRITERIA
(REFERENCE)
7/30/2019 Concealed Upright Sprinkler
http://slidepdf.com/reader/full/concealed-upright-sprinkler 8/8
Limited Warranty Products manufactured by Tyco FireProducts are warranted solely to theoriginal Buyer for ten (10) years
against defects in material and work-manship when paid for and properlyinstalled and maintained under normaluse and service. This warranty will ex-pire ten (10) years from date of ship-ment by Tyco Fire Products. No war-ran ty i s g iven for p roducts orcomponents manufactured by compa-nies not affiliated by ownership withTyco Fire Products or for products andcomponents which have been subjectto misuse, improper installation, corro-sion, or which have not been installed,maintained, modified or repaired in ac-cordance with applicable Standards ofthe National Fire Protection Associa-
tion, and/or the standards of any otherAuthorities Having Jurisdiction. Mate-rials found by Tyco Fire Products to bedefective shall be either repaired orreplaced, at Tyco Fire Products’ soleoption. Tyco Fire Products neither as-sumes, nor authorizes any person toassume for it, any other obligation inconnection with the sale of products orparts of products. Tyco Fire Productsshall not be responsible for sprinklersystem design errors or inaccurate orincomplete information supplied byBuyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIREPRODUCTS BE LIABLE, IN CON-TRACT, TORT, STRICT LIABILITY ORUNDER ANY OTHER LEGAL THE-ORY, FOR INCIDENTAL, INDIRECT,SPECIAL OR CONSEQUENTIALDAMAGES, INCLUDING BUT NOTLIMITED TO LABOR CHARGES, RE-GARDLESS OF WHETHER TYCOFIRE PRODUCTS WAS INFORMEDABOUT THE POSSIBILITY OF SUCHDAMAGES, AND IN NO EVENTSHALL TYCO FIRE PRODUCTS’ LI-ABILITY EXCEED AN AMOUNTEQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESSOR IMPLIED,INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT- NESS FOR A PARTICULAR PUR- POSE.
Ordering Procedure Contact your local distributor for avail-ability.
Sprinkler Assemblies with NPTThread Connections:Specify: TY1189, 2.8 K-factor, ModelCC1, 175°F/79°C, Upright, SpecificApplication, Combustible ConcealedSpace Sprinkler, P/N 50-300-1-175.
Sprinkler Wrench:Specify: W-Type 20 Sprinkler Wrench,P/N 56-000-1-106.
Page 8 of 8 TFP630
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446