8/20/2019 Comp Carly Scre Refrig 2004
1/52
1
CARLYLE 104 MM SCREW COMPRESSORS
06N CARLYLE SEMI-HERMETIC COMPRESSORS
8/20/2019 Comp Carly Scre Refrig 2004
2/52
8/20/2019 Comp Carly Scre Refrig 2004
3/52
1
CARLYLE REFRIGERATION COMPRESSORS
05T (74 mm) SCREW COMPRESSOR
Design Duty: Commercial Refrigeration
Qualified For: HCFC Refrigeration Duty
HFC Refrigeration Duty
R-22/407C Water Cooled Duty
R-134a Air Cooled Duty
Capacities: cfm @ 60 Hz 33 39 44 49 54 65 78 88
m3 /hr @ 50 Hz
Economizer: Optional on all modelsVi: Dual Vi Option
Configuration: Open Drive
Check Valve: Integral
Oil Filter: External
Motor Type: External
P3036
8/20/2019 Comp Carly Scre Refrig 2004
4/52
134
CARLYLE REFRIGERATION COMPRESSORS
OPEN DRIVE MODELS - For All Temperature Ranges With Service Valves
NOTE: APPLICATION LIMITS.
R-134a - Medium temperature
- Air Condition
R-22 - Low temperature
- Medium temperature
- Air Conditioning
R-404A/R-507 - Low temperature
- Medium temperature
ACCESSORIES FOR 05T MODELS
05T COUPLING PACKAGE
05T C-FLANGE PACKAGE
MODEL NO.
DISPLACEMENT (CFM)MOTOR
HP
APPROX.
SHIP. WEIGHT
(kg)1750 RPM
Motor (4 pole)
3500 RPM
Motor (2 pole)
05TRQ033Z3EA-A00 33 65 N/A 91
05TRQ039Z3EA-A00 39 78 N/A 91
05TRQ044Z3EA-A00 44 88 N/A 91
05TRQ048Z3EA-A00 48 N/A N/A 91
05TRQ054Z3EA-A00 54 N/A N/A 91
COUPLING
PKG
MOTOR SHAFT
DIAMETER
(in.)
4 POLE MOTOR
1750 Rpm @ 60 Hz
1450 Rpm @ 50 Hz
2 POLE MOTOR
3500 Rpm @ 60 Hz
3000 Rpm @ 50 Hz
APPROX.
SHIP. WT
(kg)Hp NEMA Frame Size Hp NEMA Frame Size
8TA0868B 1 5/8 15, 20 254TC, 256TC 30 286TC 5
8TA0869B 1 7/8 25, 30 284TC, 286TC 40, 50
60, 75
324TSC, 326TSC,
364TSC, 365TSC 5
8TA0870B 2 1/8 40, 50 324TC, 326TC N/A N/A 5
C-FLANGE
PKG
4 POLE MOTOR1750 Rpm @ 60 Hz
1450 Rpm @ 50 Hz
2 POLE MOTOR3500 Rpm @ 60 Hz
3000 Rpm @ 50 Hz
APPROX.
SHIP. WT
(kg)Hp NEMA Frame Size Hp NEMA Frame Size
0TA0929 15, 20,
35, 30
254TC, 256TC,
284TC, 286TC N/A N/A 25
0TA0930 25, 30 284TC, 286TC N/A
60, 75 N/A 25
0TA0931 N/A N/A 40, 50
60, 75
286TC, 324TSC,
226TSC, 364TSC,
365TSC
25
8/20/2019 Comp Carly Scre Refrig 2004
5/52
1
CARLYLE REFRIGERATION COMPRESSORS
06T SCREW COMPRESSOR
†Economized (°F).
06T Model Number Significance
CAPACITY (Btu/Hr) @ 60 HzRefrigerant R-22 R-507/404A R-22 R-507/404A R-134a
Conditions† - 25/110/65 -25/110/65 20/110/65 20/110/65 45/130/65
06T**033 51,000 70,900 131,500 143,100 127,900
06T**039 62,700 86,100 161,000 175,000 156,800
06T**044 72,100 98,900 182,800 199,000 177,700
06T**048 80,100 11,000 203,100 221,100 194,300
06T**054 91,900 126,100 233,100 253,700 222,800
06T**065 113,900 156,400 292,500 318,400 284,100
06T**078 140,200 192,000 354,300 385,700 342,400
06T**088 159,800 218,700 400,900 436,300 387,500
P3035
8/20/2019 Comp Carly Scre Refrig 2004
6/52
136
CARLYLE REFRIGERATION COMPRESSORS
COMPRESSOR PHYSICAL DIMENSIONS
P3031 P3032
P3033
8/20/2019 Comp Carly Scre Refrig 2004
7/52
1
CARLYLE REFRIGERATION COMPRESSORS
LOW TEMPERATURE DUTY - Semi-Hermetic With Service Valves
NOTE: APPLICATION LIMITS.
R-134a - Medium temperature
- Air Conditioning
R-22 - Low temperature
R-404A/R-507 - Low temperature
06TRK model satisfactory for use on high temp, medium temp and low temp applications.
MODEL NO.
VOLTAGE
3 PHASE MOTOR
HP
APPROX.
SHIP. WEIGHT
(kg)60 HZ 50 HZ
06TRC033B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
15 166
06TRD039B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
20 172
06TRD044B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
20 172
06TRE048B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
25 177
06TRE054B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
25 177
06TRF065B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
30 181
06TRG078B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
35 184
06TRH088B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
40 184
06TRK108B2EA-A00
NOTE: 50Hz Applications Only n/a 400 50 186
8/20/2019 Comp Carly Scre Refrig 2004
8/52
138
CARLYLE REFRIGERATION COMPRESSORS
MEDIUM/HIGH TEMPERATURE DUTY - Semi-Hermetic With Service Valves
NOTE: APPLICATION LIMITS.
R-22 - Low temperature
- Air Conditioning (High Temperature)
R-404A/R-507 - Medium temperature
MODEL NO.
VOLTAGE
3 PHASE MOTOR
HP
APPROX.
SHIP. WEIGHT
(kg)60 HZ 50 HZ
06TAD033B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
20 164
06TAE039B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
25 171
06TAF044B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
30 171
06TAF048B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
30 176
06TAG054B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
35 176
06TAG065B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
35 180
06TAH078B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
40 182
06TAK088B2EA-A00
F2EA-A00
C2EA-A00
460
208/230
575
400
200
-
50 187
8/20/2019 Comp Carly Scre Refrig 2004
9/52
1
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIESELECTRONIC PHASE MONITOR (REVERSE ROTATION PROTECTION)
(See Notes Below)
NOTES:
1. Protects screw compressor from reverse rotation by monitoring 3-phase input power to compressor motor. Will not allow compressor to start ifsequence is incorrect.
2. This phase monitor will not operate with a variable speed drive inverter.
3. May be used in place of reverse rotation switch; (1) per compressor.
RUBBER ISOLATION MOUNTS
(1 Package Per Compressor Recommended)
MUFFLERS
(1 Per Compressor Required)
OIL SEPARATORS
(1 Per Rack Required)
NOTES:
1. Oil Separators supplied with multiple sight glasses to view oil level.2. Oil Separators has adapter fitting at bottom to connect KH13LB004 Oil Level Float Switch.
PART NO. QTY/PKG WEIGHT (kg) USAGE
P251-0090 1 1.5 ALL 05/6T compressors
PART NO. QTY/PKG WEIGHT (kg) USAGE
KA75KR002 4 0.5 ALL 05/6T compressors
PART NO. QTY/PKG WEIGHT (kg) INLET/OUT LENGTH USAGE
LM10HH162 1 3 1-5/8” 9-3/4″ All 05/6T
compressor
PART NO. MOUNTING LINE SIZE (0. WT (kg) DIA. USAGE
KH31ZZ340
KH31ZZ212
VERTICAL
VERTICAL
2-1/8″
2-5/8″
66
120
12″
14″
Single Comp.
Multiple Comp.
8/20/2019 Comp Carly Scre Refrig 2004
10/52
140
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIESOIL LEVEL SWITCH
(1 Per Oil Separator Required)
NOTE:
1. Protects compressor against loss of oil in Oil Separator. Screws into bottom.
HEATER FOR OIL SEPARATOR / OIL RESERVOIR
(2 Per Oil Separator Recommended)
NOTE:
1. Heater applied to oil separator to keep refrigerant from accumulating in it during off cycles.
See application guide for application requirements.
AIR-COOLED OIL COOLERS
(See Application Guide for Requirements)
OIL FILTER HOUSING ASSEMBLY
(2 Per Rack Required)
NOTES:
1. Oil Housing which allows replacement of filter cartridge.
2. Filter Housing assembly includes (1) 3 micron filter cartridge.
3. (2) per rack recommended.
PART NO. QTY/PKG WEIGHT (kg) USAGE
HK13LB004 1 0.5 On vertical oil separators
PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL CHARACTERISTICS
VOLTS WATTS
HK38KN007 1 0.5 115/230 500
PART NO. NO. OF COMPS.
@ LOAD WEIGHT (kg)
ELECTRICAL CHARACTERISTICS
VOLTS/1 PH HZ
KH51ZZ181 2 23 115/230 V - 1 PH 60/50 HZ
KH51ZZ182 3 57 115/230 V - 1 PH 60/50 HZ
KH51ZZ183 4 91 115/230 V - 1 PH 60/50 HZ
KH51ZZ184 5 98 115/230 V - 1 PH 60/50 HZ
PART NO. QTY/PKG WEIGHT (kg) CONNECTION TYPE USAGEKH18MG002 1 4 7/8″ Sweat All 05/6T Compressors
8/20/2019 Comp Carly Scre Refrig 2004
11/52
1
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIESOIL FILTER CARTRIDGE
NOTE:
1. Carlyle recommends (3) cartridges be left at the job site per oil filter housing. Several changeouts will be necessary before the system is free
of contaminant. If the job is a remodel, more changeouts may be necessary.
2. Each cartridge is supplied with (1) filter housing O ring.
PART NO. QTY/PKG WEIGHT (kg) USAGE
KH39MG002 1 0.5 Replacement Cartridge for KH18MG002 housing
DESUPERHEATING
(1 Per Compressor for R-22
8/20/2019 Comp Carly Scre Refrig 2004
12/52
142
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIES5K THERMISTOR
(1 Per Compressor Required)
NOTE: One required per compressor for use with CEM to monitor discharge temperature.
PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE
HH79NZ065 1 0.5 115/240-1-60 All 05/6T Compressors
MOTOR COOLING VALVES
(1 Per Compressor Required)
NOTE: Used for motor and discharge gas cooling of screw compressors.
PART NO. QTY/PKG WEIGHT (kg) EVRP SIZE USAGE
EF28BZ007 1 0.5 1.4 All 05/6T Compressors
SOLENOID COILS FOR MOTOR COOLING VALVES
(1 Per Compressor Required)
PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE
P510-XV120D 1 0.5 120-1-50/60All 05/6T Compressors
P510-XV208D 1 0.5 208/240-1-50/60
P510-XV024D 1 0.5 24-1-50/60
REVERSE ROTATION PROTECTION SWITCH
(1 Per Compressor Required)
NOTE: Protects screw compressor from reverse rotation.
PART NO. QTY/PKG WEIGHT (kg) USAGE
HK01CB002 1 1 All 05/6T Compressors
8/20/2019 Comp Carly Scre Refrig 2004
13/52
1
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
05T/06T REFRIGERATION COMPRESSOR ACCESSORIESOIL PRESSURE DIFFERENTIAL SWITCH(1 Per Compressor Required)
NOTES:
1. Senses oil differential between discharge pressure and oil feed to the compressor.
2. Switch setting is for cutout when differential pressure above (45 psid) and has a 30 second time delay.
PART NO. QTY/PKG WEIGHT (kg) CONNECTION VOLTAGE
INPUT USAGE
HK06ZB006 1 2 1/4″ FLARE 115 or 230 ALL 05/6T compressors
OIL FILTER DIFFERENTIAL SWITCH
(1 Per Oil System Recommended)
NOTES:
1. Senses oil differential across filters.
2. Switch setting is for cutout when differential pressure exceeds 45 psid and has a 30 second time delay.
PART NO. QTY/PKG WEIGHT (KG) CONNECTION VOLTAGE
INPUT USAGE
HK06CA051 1 2 1/4″ FLARE 115 or 230 ALL 05/6T compressors
SUCTION AND DISCHARGE SERVICE VALVE PACKAGES
NOTES:
1. (2) 06TA660001 packages are supplied with each compressor.
2. All service Valve are 4 bolt, 2-1/2″ square bolt spacing. Service Valve Package contains (1) service valve (1) gasket, and (4) metric hex
head cap screws (M12 x 1,75 x 60mm).3. These Service Valve packages (except 06TA68005) are the same as the respective 06D/E packages except the mounting bolts have
metric threads.
PART NO. SIZE ODF QTY/PKG WEIGHT (kg) USAGE
06TA660001 1-5/8″ 1 2
ALL 05/6T compressors
05T/06T 65, 78, 88 CFM
06TA660002 1-3/8″ 1 2
06TA660003 1-1/8″ 1 2
06TA680005 1-5/8″ 1 2
ECONOMIZER SERVICE VALVE
(See Notes Below)
NOTES:
1. (1) 06TA660004 package is supplied with each compressor.2. All Economizer Service Valve contain (1) Rotalock * valve, (1) O-ring, (1) seal, and (1) connection fitti ng.
PART NO. SIZE ODF QTY/PKG WEIGHT (kg) USAGE
06TA660004 7/8″ 1 2 ALL 05/6T compressors
8/20/2019 Comp Carly Scre Refrig 2004
14/52
144
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
06T REFRIGERATION COMPRESSOR ACCESSORIES
CALIBRATED CIRCUIT BREAKERS
(1 Per 06T Compressor)
NOTES:
1. Circuit breaker selections are based on across-the-line start.
2. Overcurrent protection required per General Note.
3. Heinemann circuit breaker not required with 05T compressor.
COMPRESSOR
MODULE USAGE
VOLTAGE
3 PHASE QTY/PKG WEIGHT (kg) CIRCUIT BREAKER
06TRC033B2EA-A00
F2EA-A00C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50575-3-60
1
2
22
HH83XA463
HH83XB356HH83XA460
06TRD039B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
2
2
2
HH83XA424
HH83XB336
HH83XA461
06TRD044B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
2
2
2
HH83XA424
HH83XB336
HH83XA461
06TRE048B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
2
3
2
HH83XA426
HH83XC509
HH83XA469
06TRE054B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
2
3
2
HH83XA426
HH83XC509
HH83XA469
06TRF065B2EA-A00
F2EA-A00C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50575-3-60
1
2
32
HH83XA474
HH83XC573HH83XB617
06TRG078B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
2
3
2
HH83XA476
HH83XC574
HH83XB618
06TRH088B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
2
3
2
HH83XA476
HH83XC575
HH83XB619
06TRK108B2EA-A00 400-3-50 1 2 HH83XA477
8/20/2019 Comp Carly Scre Refrig 2004
15/52
1
CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES
06T REFRIGERATION COMPRESSOR ACCESSORIESCALIBRATED CIRCUIT BREAKERS
(1 Per 06T Compressor)
*These breakers are supplied without compression lugs. Customer must provide connectors or use our Power Terminal Parts Connectors for
HH83XB Circuit Breakers shown below.
NOTES:
1. Circuit breakers selections are based on across-the-line start.
2. Overcurrent protection required per General Note.
3. Heinemann circuit breaker not required with 05T compressor.
COMPRESSOR
MODULE USAGE
VOLTAGE
3 PHASE QTY/PKG WEIGHT (kg) CIRCUIT BREAKER
06TAD033B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
4
4
4
HH83XA424
HH83XB336* orHH83XB625
HH83XA461
06TAE039B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
4
4
4
HH83XA426
HH83XC509
HH83XA469
06TAF044B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
4
4
4
HH83XA425
HH83XC539
HH83XA430
06TAF048B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
4
4
4
HH83XA425
HH83XC539
HH83XA430
06TAG054B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
4
4
4
HH83XA547
HH83XC532
HH83XA453
06TAG065B2EA-A00F2EA-A00
C2EA-A00
460-3-60 & 400-3-50230-3-60 & 200-3-50
575-3-60
146
4
HH83XA475HH83XC574
HH83XB618
06TAH078B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
4
6
4
HH83XA476
HH83XC575
HH83XB619
06TAK088B2EA-A00
F2EA-A00
C2EA-A00
460-3-60 & 400-3-50
230-3-60 & 200-3-50
575-3-60
1
4
6
4
HH83XA477
HH83XC576
HH83XB610
POWER TERMINAL PARTS CONNECTORS FOR HH83XB CIRCUIT BREAKER
HH83XB series circuit breakers require customer supplied power wire connections at circuit breaker.
Kit includes ring terminal, cap screws and lock washers. Not required for XA, XC, C or B series circuit breakers.
PART NO. USAGE SHIP WEIGHT (kg)
06EA660152 #1 - #2 Wire 0.5
06EA660153 #4 Wire 0.5
TERMINAL PARTS PACKAGES
Package Contents: (6) Ring Terminal to connect power wiring to compressor terminal studs, plus (3) spare (2-hole) jumper bars.
PART NO. QTY/PKG WEIGHT (kg) USE WITH USAGE
06EA900132 1 0.5 #6 Wire
All 06T
Compressors
06EA900102 1 0.5 #4 Wire
06EA900112 1 0.5 #2 Wire
06EA900122 1 0.5 #1/0 Wire
8/20/2019 Comp Carly Scre Refrig 2004
16/52
146
CARLYLE REFRIGERATION COMPRESSORS
GUIDE TO 06D PART NUMBERING SYSTEM:NOTES:1. SPECIAL ORDER SERVICE COMPRESSORS FOR BRYANT
MAY BE PROCESSED AS “9” NAMEPLATED “6” (8TH DIGIT).2. SERVICE MODELS WITH “C” IN THE 10th DIGIT REPLACE
ALL “A”, “C” AND “E” ORIGINAL EQUIPMENT MODELS AND“D” SERVICE MODELS REPLACE “8” & “F” MODELS.TERMINAL BOXES AND OVERLOADS ARE TO BE RE-USEDOR REPLACED IF DAMAGED.
3. “09” IN THE 11TH & 12TH DIGITS HAS BEEN USED IN THEPAST FOR 400-3-50 MOTORS AND IS NO LONGER USED,
SO AS TO AVOID CONFUSION IN SERVICE THESE DIGITSARE TO BE LEFT ON THIS CHART BUT ARE NOT TO BERE-USED.
PRODUCT
SERIES
U N L O A D E R
V A R I A T I O N S
M O T O R
S I Z E
C F M
D I S P L A C E M E N T
K E Y N U M B E R
VARIABLES
E L E C T R I C A L
C H A R A C T E R I S T I C
V A R I A T I O N S
F U T U R E D E S I G N
V A R I A B L E S
P A C K A G I N G
V A R I A T I O N S
S U C T I O N V A L U E & M . E .
C O V E R O R I E N T A T I O N
V O R E L O A D S & I N T E R N A L
T H E R M O S T A T
MODEL 0 6 D A 3 1 6 0 0 A 3 2 0 0
VARIABLE DIGIT I 2 3 4 5 6 7 8 9 10 11 12 13 14
13TH
DIGIT
FUTURE DESIGN
VARIABLES
0 ORIGINAL DESIGN A/C & REFRIG.
1 2ND GENERATION REFRIG,
CPRSR. W/NEW VALVE PLATE
2 MED. RANGE A/C CPRSR. WITH
REFRIG. CHARACTERISTICS
3 LOW CLEARANCE VOLUME
4 SUCTION CUT-OFF
ELECTRIC UNLOADERS
1 STEP
5 OILLESS
6
7
14THDIGIT
PACKAGING VARIATIONS
0 SERVICE UNIT SINGLE PACK -
BASE UNIT UNPACKAGES
I SINGLE PACK - DOMESTIC
LESS SERVICE VALVE
2 MULTI-PACK - DOMESTIC
3 EXPORT - I UNIT
4 MULTI-PACK
5 PALLETIZED
6 GOVERNMENT PACK
7 SINGLE PACK - DOMESTIC
WITH SERVICE VALVE
8
MATCHED COMPONENTS -
CONSISTS OF SEPARATEEXPORT PACKAGE PIECES
9 DOMESTI C MULTI-PACK &
MCMINNVILLE
1ST, 2ND, 3RD DIGITS
SIGNIFY 06D HERMETIC
RECIP. COMPRESSOR
4TH DIGIT UNLOADER VARIABLE
L
E
T
T
E
R
S
T
A
N
D
A
R
D
S
E
R
V
I
C
E
B
O
T
H
DESCRIPTION
A X NO HOT GAS BY-PASS UNLOADERS
B X ELECT RIC UNLOADERS 1 STEP
C X 2 STEP
D X P RE SSU RE U NLOA DER S 1 ST EP
E X 2 STEP
F X SUCT ION CUT-OFF
ELECTRIC UNLOADERS
1 STEP
G X 2STEP
M X MED. TEMPERATURE, REPLACES
ALL “A’s” IN SERVICE
N X 2 SHAVED HDS. - SPECIAL ORDER
R X REFRIGERATION
W X AIC - 2 PLUGGED HDS. REPLACES
ALL C&E SERVICE SPEC. ORDERS
X X 1 PLUGGED HEAD - REPLACES ALL
B, C, D & E PROD. MODELS IN
SERVICE
Y X REFR. - 2 PLUGGED HDS. SERVICE
SPEC. ORDER
S X HI-EFF SERVICE MOD. w/I BLOCKED
UNLD’R HD - REPLACES F, G, H & J
H X S UC TON C UT- OF F P RE S-
SURE UNLOADERS!
1 STEP
J X 2 STEP
5TH DIGIT
VARIABLE
MOTOR SIZES
2 CYL 4 CYL 6 CYL
0 3 HP
1 2 HP 5 HP
2 24 LBFT
3 5 HP 27 LBFT
4 31 / 2 HP
5 51 / 2 H P 3 8 L BF T
6
7 5 HP 20 LBFT
8 3 HP 20 LBFT 24 LBFT
9
10TH
DIGIT
OVERLOAD & T’STAT. VARIABLE SEE NOTE 2
EXTL.
OVLDS.
INTL.
T’RAT. DESCRIPTION
A Y ES YES
B YES NO
C NO YES
D NO NO
E YES YES 1ST OVERLOAD VARIATION
F YES NO 1ST OVERLOAD VARIATION
G YES YES MANUAL RESET OVERLOADS
T NO YES TECUMSEH SERVICE MODELS
9TH
DIGIT
SUCTION SERVICE VALVE VARIABLES
LOC. OF VALVE M.E.COV. DESC. VALVE ORIENTATION
A MOTOR END 2 BOLT 30°
B MOTOR END 4 BOLT 30°
C MOTOR END 2 BOLT 90°
D MOTOR END 4 BOLT 90° OR 180°
E MOTOR END 2 BOLT 150°
F PUMP END PLAIN 270°
G PUMP END PLAIN 225°
0°
270° 90°
180°
8TH
DIGIT KEY NO. SIGNIFICANCE
0 PROD. MOD. W/T-BOX
1 PKG. CPRSR. & CONTROL BOX
2 OEM A/C CPRSR.
3 TYLER MODELS
4 TECUMSEH OEM MODELS
5 FUTURE USE
6 REMAN. SERVICE CPRSR.
7 NEWMAN SERVICE GPRSR.
6 SPECIAL ORDER ONLY
9 SERV. SPEC. OR SEE NOTE 1
6TH & 7TH
DIGITS
CRANKCASE
ASSEMBLY
NO.
CYL
BORECFM
07 6 D2 0- 24 9 1 -13 / 1608 6D23-249 2
09 6D23-249 2
13 6D48-249 2
16 6D48-249 2
18 6D48-249 2
20 6D48-249 2
24 6D68-259 2
28 6D75-249 2
37 6D75-249 2
11TH
& 12TH
DIGITS
ELECTRICAL
CHARACTERISTICS
VOLTS-PHASE-HERT
Z
START
00 XL
01 575 - 3 - 60 XL
02 200 - 1 - 60 XL
03 230 - 1 - 60 XL
04 200 - 3 - 60 XL
05 230 - 3 - 60 XL
06 400/460 - 3 - 50/60 XL
07 230 - 1 - 50 XL
08 220 - 3 - 50 XL
09 SEE NOTE 3 XL10 230 - 2 - 60 XL
11 480 - 3 - 60 XL
12 2081230 - 3 - 60 XL
13 380 - 3 - 60 XL
14 200 - 3 - 60 P/W
15 230 - 3 - 60 P/W
18 220 - 3 - 50 P/W
19 230/ 460 - 3 - 60 XL
21 575 - 3 - 60 XL
26 400/460 - 3 - 50/60 XL
31 575 - 3 - 60 XL
32 208/ 230 - 3 - 60 XL
36 400/460 - 3 - 50/60 XL
38 415 - 3 - 50 P/W
39 415 - 3 - 50 XL
33 208/ 230 - 1 - 60 XL
34 220 - 3 - 50 XL
8/20/2019 Comp Carly Scre Refrig 2004
17/52
1
CARLYLE REFRIGERATION COMPRESSORS
06D REFRIGERATION AND MEDIUM TEMPERATURE DUTY COMPRESSORAPPLICATION DATA
P912
For mounting configuration,
dimensions and weight refer to
outline drawings on previous
pages.
MODEL
NO. HP
NO.
OF
CYL.
CFM
@
1750
RPM
SUCTION TEMP. RANGE*
(°F)
*
Condensing temperature range 80°to 120°F.
CAPACITY (000 BTUH)
-25°SST
110°SCT
65°SGT
0°SC
20°SST
120°SCT
65°SGT
0°SC
15°SST
110°SCT
65°SGT
0°SC
40°SST
120°SCT
60°SGT
0°SC
R-502 R-12 R-22 R-502 R-502 R-12/R134a R-22
06DR109 2 2 8.7 -40 to 0**
**Cylinder Head Cooling Fan is required to operate at minimum suction temperatures.
-10 to 40 - 9.9 - 14.6/ - -
06DM808 3 2 8.0 -10 to 40 - -10 to 50 - 23.1 - 35.6
06DR013 3 4 13.1 -40 to 0** -10 to 40 - 11.7 - 22.7/19.5 -
06DM313 5 4 13.1 -10 to 40 -10 to 40 -10 to 50 - 35.1 20.4/ - 55.6
06DR316 5 4 15.9 -40 to 10** -10 to 40 - 16.2 - 29.1/26.9 -
06DM316 5 4 15.9 -10 to 40 -10 to 40 -10 to 50 - 45.0 26.6/ - 69.0
06DR718 5 4 18.3 -40 to 10** -10 to 40 - 20.4 - 33.7/31.9 -
06DR820 6-1/2 4 20.0 -40 to 40** -10 to 40 -10 to 50 22.3 - 37.4/35.6 92.5
06DR724 6-1/2 6 23.9 -40 to 40** -10 to 40 -10 to 50 25.6 - 43.7/40.1 109.6
06DR228 7-1/2 6 28.0 -40 to 40** -10 to 40 -10 to 50 31.0 - 51.3/49.2 128.2
06DR337 10 6 37.1 -40 to 10** -10 to 40 - 42.7 - 69.3/67.7 -
06DM337 10 6 37.1 -10 to 30 -10 to 40 -10 to 35 - 111.1 65.6/ - 165.9
06D COMPRESSOR DATA - SINGLE PHASEMED. TEMP - NO UNLOADING
COMPRESSOR
MODEL NO. VOLT HP CFM
OIL
CHG.
PINTS
MAX.
WATTS
MAX.
RLA MTA LRA
2 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM8086-0350 230 3 8 3.5 2800 17.0 22.0 70.0
06DM1096-0350 230 2 8.7 3.5 2800 12.5 15.6 50.0
4 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM3136-0350 230 5 13.1 5 6600 28.0 35.0 100.0
06DM3166-0350 230 5 15.9 5 6600 28.0 35.0 100.0
06DM3186-0350 230 5 18.3 7 6600 28.0 35.0 100.0
06DM5186-0350 230 5.5 18.3 7 7700 36.8 46.0 148.0
06DM7186-0350 230 5 18.3 7 6600 28.0 35.0 100.0
8/20/2019 Comp Carly Scre Refrig 2004
18/52
148
CARLYLE REFRIGERATION COMPRESSORS
06D COMPRESSOR DATA - THREE PHASEMED. TEMP. - NO UNLOADING
COMPRESSOR
MODEL NO. VOLT HP CFM
OIL
CHG.
PINTS
MAX.
WATTS
MAX.
RLA*
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much
lower RLA values.
MTA LRA
2 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM8086-3150 575 3 8 3.5 4,100 5.6 7.0 28.4
06DM8086-3250 208/230 3 8 3.5 4,100 14.0 17.4 71.006DM8086-3650 460 3 8 3.5 4,100 7.0 8.7 35.5
2 CYLINDER... MEDIUM TEMP ... 50 HZ
06DM8086-3650 400 3 6.7 3.5 3,400 7.0 8.7 35.5
4 CYLINDER... MEDIUM TEMP ... 60 HZ
06DM3136-3150 575 5 13.1 5 6,250 8.6 10.8 40.0
06DM3136-3250 208/230 5 13.1 5 6,250 21.5 27.0 100.0
06DM3136-3650 460 5 13.1 5 6,250 10.8 13.5 50.0
06DM3166-3150 575 5 15.9 5 6,250 8.6 10.8 40.0
06DM3166-3250 208/230 5 15.9 5 6,250 21.5 27.0 100.0
06DM3166-3650 460 5 15.9 5 6,250 10.8 13.5 50.0
4 CYLINDER...MEDIUM TEMP ... 60 HZ
06DM3136-3650 400 5 11 5 5,200 10.8 13.5 50.0
06DM3166-3650 400 5 13 5 5,200 10.8 13.5 50.0
6 CYLINDER...MEDIUM TEMP ... 60 HZ
06DM3376-3150 575 10 37.1 10 16,500 17.9 25.0 91.0
06DM3376-3650 460 10 37.1 10 16,500 22.1 31.0 114.0
06DM3376-3250 208.230 10 37.1 10 16,500 44.3 62.0 228.0
6 CYLINDER...MEDIUM TEMP ... 50 HZ
06DM3376-3650 400 8 31.0 10 13,700 22.1 31.0 114.0
06D COMPRESSOR DATA - SINGLE PHASELOW TEMP REFRIGERATION
COMPRESSOR
MODEL NO. VOLT HP CFM
OIL
CHG.
PINTS
MAX.
WATTS
MAX.
RLA* MTA LRA
2 CYLINDER... LOW TEMP REFRIGERATION ... 60 HZ
06DR1096-3350 208/230-1 2 8.7 3.5 3,400 17.0 24.0 110.0
4 CYLINDER... LOW TEMP REFRIGERATION ... 60 HZ
06DR0136-3350 208/230-1 3 13.1 5 4,800 23.3 32.6 100.0
06DR3166-3350 208/230-1 5 15.9 5 6,400 28.6 40.0 150.0
06DR7186-3350 208/230-1 5 18.3 7 6,400 28.6 40.0 150.0
8/20/2019 Comp Carly Scre Refrig 2004
19/52
1
CARLYLE REFRIGERATION COMPRESSORS
06D COMPRESSOR DATA - THREE PHASE
LOW TEMP REFRIGERATION
COMPRESSOR
MODEL NO. VOLT HP CFM
OIL
CHG.
PINTS
MAX.
WATTS
MAX.
RLA*
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much
lower RLA values.
MTA LRA
2 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR1096-3150 575 2 8.7 3.5 3,100 3.1 4.4 21.3
06DR1096-3250 280/230 2 8.7 3.5 3,100 8.8 12.1 53.3
06DR1096-3650 460 2 8.7 3.5 3,100 3.8 5.5 26.6
2 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR109-3650 400 2 7.5 3.5 2,600 3.8 5.5 26.6
4 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR0136-3150 575 3 13.1 5 4,300 5.6 7.0 28.4
06DR0136-3250 208/230 3 13.1 5 4,300 14.0 17.4 71.0
06DR0136-3650 460 3 13.1 5 4,300 7.0 8.7 35.5
06DR3166-3150 575 5 15.9 5 6,250 8.6 10.8 40.0
06DR3166-3250 208/230 5 15.9 5 6,250 21.5 27.0 100.0
06DR3166-3650 460 5 15.9 5 6,250 10.8 13.5 50.0
06DR7186-3150 575 5 18.3 7 6,250 8.6 10.8 40.0
06DR7186-3250 208/230 5 18.3 7 6,250 21.5 27.0 100.0
06DR7186-3650 460 5 18.3 7 6,250 10.8 13.5 50.0
06DR8206-3150 575 6.5 20 7 9,800 12.6 17.6 64.0
06DR8206-3250 208/230 6.5 20 7 9,800 31.5 44.0 160.0
06DR8206-3650 460 6.5 20 7 9,800 15.7 22.0 80.0
4 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR013-3650 400 3 11 5 3,400 7.0 8.7 35.5
06DR316-3650 400 5 13 5 5,200 10.8 13.5 50.0
06DR718-3650 400 5 15 7 5,200 10.8 13.5 50.0
06DR820-3650 400 6.5 16.7 7 8,200 31.5 44.0 160.0
6 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06DR7246-3150 575 6.5 23.9 10 9,800 12.6 17.6 64.0
06DR7246-3250 208/230 6.5 23.9 10 9,800 31.5 44.0 160.0
06DR7246-3650 460 6.5 23.9 10 9,800 15.7 22.0 80.0
06DR2286-3150 575 7.5 28 10 12,800 15.9 22.2 79.0
06DR2286-3250 208/230 7.5 28 10 12,800 39.7 55.5 198.0
06DR2286-3650 460 7.5 28 10 12,800 19.9 27.8 99.0
06DR3376-3150 575 10 37.1 10 1,6500 17.9 25.0 91.0
06DR3376-3250 208/230 10 37.1 10 16,500 44.3 62.0 228.0
06DR3376-3650 460 10 37.1 10 16,500 22.1 31.0 114.0
6 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ
06DR724-3650 400 6.7 20 10 8,200 15.7 22.0 80.0
06DR228-3650 400 8 23.3 10 10,700 19.9 27.8 99.0
06DR337-3650 400 9 31 10 13,700 22.1 31.0 114.0
8/20/2019 Comp Carly Scre Refrig 2004
20/52
150
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06D ... 60 HZ (REF. DUTY)
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06DR1096-3100 HH83XB498
06DR1096-3200 HH83XB492
06DR1096-3600 HH83XB495
06DR0136-3100 HH83XB496
06DR0136-3200 HH83XB490
06DR0136-3600 HH83XB494
06DR3166-3100 HH83XB497
06DR3166-3200 HH83XB415
06DR3166-3600 HH83XB443
06DR7186-3100 HH83XB497
06DR7186-3200 HH83XB415
06DR7186-3600 HH83XB443
06DR8206-3100 HH83XB450
06DR8206-3200 HH83XB306
06DR8206-3600 HH83XB419
06DR7246-3100 HH83XB450
06DR7246-3200 HH83XB306
06DR7246-3600 HH83XB419
06DR2286-3100 HH83XB419
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06DR2286-3200 HH83XB307
06DR2286-3600 HH83XB438
06DR3376-3100 HH83XB451
06DR3376-3200 HH83XB305
06DR3376-3600 HH83XB452
06DM8086-030 0 HH83XB480
06DM1096-030 0 HH83XB481
06DM8096-030 0 HH32XB480
06DM3136-030 0 HH83XB483
06DM3166-030 0 HH83XB483
06DM3186-030 0 HH83XB483
06DM5186-030 0 HH83XB484
06DM7186-030 0 HH83XB483
06DM8086-320 0 HH83XB490
06DM8086-360 0 HH83XB494
06DM3136-310 0 HH83XB497
06DM3136-320 0 HH83XB316
06DM3136-360 0 HH83XB443
06DM3166-310 0 HH83XB497
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06DM3 166-3200 HH83XB316
06DM3 166-3600 HH83XB443
06DM8 186-0100 HH83XB450
06DM8 186-0600 HH83XB419
06DM8 186-1200 HH83XB306
06DM8 246-0100 HH83XB419
06DM8 246-0600 HH83XB400
06DM8 246-1200 HH83XB423
06DM3 376-3100 HH83XB451
06DM3 376-3600 HH83XB452
06DM3 376-3200 HH83XB305
06DM3 376-1400 HH83XE630
06DM3 376-1500 HH83XE604
06DM5 376-0100 HH83XB440
06DM5 376-0600 HH83XB422
06DM5 376-1200 HH83XB311
06DM5 376-1400 HH83XE633
06DM5 376-1500 HH83XE643
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06DR109-3600 HH83XB495
06DR013-3600 HH83XB49406DR316-3600 HH83XB443
06DR718-3600 HH83XB415
06DR820-3600 HH83XB419
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06DR724-3600 HH83XB419
06DR228-3600 HH83XB43806DR337-3600 HH83XB452
06DM808-3600 HH83XB494
06DM313-3600 HH83XB443
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06DM316-3600 HH83XB443
06DM818-0600 HH83XB41906DM824-0600 HH83XB400
06DM337-3600 HH83XB452
06DM537-0600 HH83XB422
REQUIRED CIRCUIT BREAKERS: 06D ... 50 HZ
8/20/2019 Comp Carly Scre Refrig 2004
21/52
1
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06D
OPTIONAL ACCESSORIES
COMPRESSORMODEL NO.
TERMINALBOX KIT
SUCTIONSERVICE
VALVE KIT
ALTERNATESUCTIONSERVICE
VALVE KIT
DISCHARGESERVICE
VALVE KIT
ALTERNATEDISCHARGE
SERVICE VALVEKIT
SUSPENSION KIT MOUNTING
PLATE KIT
06DR109 06DA660075 0 6DA660061 - 06DA660060 06DA660059 06DA660058 06EA660096
- - 06DA660061
013 06DA660078 06DA660064 - 06DA660056
316 06DA660064 - 06DA660056
718 0 6DA660065 06EA660090 06DA660056
820 0 6DA660065 06EA660090 06DA660056
724 06DA660065 06EA660090 06DA660062 06DA660064 06DA660057
228 06EA660090 - 06DA660062 06DA660064 06DA660057
337 06EA660090 - 06DA660062 06DA660064 06DA660057
06DM808 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058
- - 06DA660061
809 06DA660061 - 06DA660058
( )313 06DA660078 06DA660064 - 06DA660056
( )316 06DA660078 06DA660062 06DA660064 06DA660056
518 06DA660078 06DA660064 - 06DA660061 - 06DA660056 06EA660096
( )818 06DA660064 - 06DA660061 - 06DA660056
06D( )724 06DA660063** 06DA660065** 06DA660062 06DA660064 06DA660057
- 06EA660090** - -
06DA660064* - - -
( )824 06DA660063** 06DA660065** 06DA660062 06DA660064
- 06EA660090** - -
06DA660064* - - -
( )337 06DA660065 06EA660090 06DA660064 -
* -- 2 BOLT ** -- 4 BOLT
• KIT CONSISTS OF:
SERVICE VALVE, GASKET AND BOLTS
NOTE: Service Valve contained in kits cannot be ordered separately.
P419
NR= Not Required.
NA = Vendor part number available upon request.
VALVESIZE(in.)
VALVEMOUNTING
(BOLT HOLECENTER-IN)
MUELLER - SERVICE VALVE HENRY - SERVICE VALVE
ADAPTER/TAILPIECE
P/N
KITP/N
VALVEP/N
CAPP/N
ADAPTER/TAILPIECE
P/N
KITP/N
VALVEP/N
CAPP/N
5/8 FLARE 2 BOLT (1-5/8) NR 06DA660059 EN26AA211 EN99ZA001 - - - -
5/8 SWEAT 2 BOLT (1-5/8) NR 06DA660060 EN32AA250 EN99ZA001 - - - -
7/8 SWEAT
2-BOLT (1 -5/8)NR
06DA660061 EN07AA271
EN99ZA006 NR
06DA660061 EN07AA271NA
2 BOLT (1 -3/4) 06DA660062 EN07AA284 06DA660062 EN07AA284
2 BOLT (2-3/4) EN99ZC027 - EN07AA390 - - - -
1-1/8 SWEAT
4 BOLT (2-1/2) NR 06DA660063 EN07EA033
EN99ZA006 NR
06DA660063 EN07EA033
EN99ZA0132 BOLT (1 -3/4) 06DA660064 EN07AA348 06DA660064 EN07AA348
2 BOLT (2-3/4) EN99ZC033 - EN07AA395 NA - EN07EC341
1-3/8 SWEAT 4 BOLT (2-1/ 2) NR 06DA660065 EN07EA039 EN99ZA006 NR - - -
1-5/8 SWEAT4 BOLT (2-1/2) NR 06EA660090 EN07EA041 EN99ZA006 NR 06EA60090 EN07EA041
EN99ZA013NR - EN13HA045 NA NA - EN13HA045
2-1/8 SWEAT 4 BOLT (3-1/16) EM99AA516 - EM13FE051
EN99ZA009 EP29VC540 06EA660091 EM13FE051 EN99ZA022- EM13FA516
2-5/8 SWEAT 4 BOLT (3-1/16) EM99AA518 - EM13FA518 - - - - -
3-1/8 SWEAT 4 BOLT (3-7/8) EM99AA520 - EM13FA520 EN99ZA011 EP29VC660 - EM13FE520 EN99ZA018
4-1/8 SWEAT 4 BOLT (4-13/16) NA - EM13FA524 NA NA - EM13FES24 EN99ZA025
COMPRESSOR SERVICE VALVE KITS BY VALVE SIZE
8/20/2019 Comp Carly Scre Refrig 2004
22/52
152
CARLYLE REFRIGERATION COMPRESSORS
GUIDE TO 06E PART NUMBERING SYSTEM:
PRODUCT
SERIES
D
E S I G N V A R I A B L E S
U S A G E
SIZE
E L E C T R I C A L
C
H A R A C T E R I S T I C S
F U T U R E D E S I G N
M O D E L A N D
P A C K A G I N G
CFM
CPRSRS
HOM.H.P.
CPRSR
UNITS
MODEL 0 6 E A 1 5 0 3 4 0
DIGIT 1 2 3 4 5 6 7 8 9 10
1ST, 2HD, 3RD DIGITS
O6E HERMETIC COMPRESSOR
9TH DIGIT SERVICE DESIGN VARIABLE1 THERMOTECTOR PROTECTION OLD STYLE
CRANKCASE
2 NEW MANUFACTURE SERVICE COMPRESSOR
3 FUTURE USE
4 REMANUFACTURED SERVICE COMPRESSOR
LOW TEMP
5 OLD STYLE CRANKCASE ROBERTSHAW SEN-
SORS & TAPPED CYL. H DS. MOTOR PROTEC-
TION KIT REQ’D. FOR THERMOTECTOR
APPLICATION
6 REMANUFACTURED SERVICE COMPRESSOR
7 REMANUFACTUREO SERVICE COMPRESSOR
MED. TEMP.
9TH DIGIT PROD. DESIGN VARIABLE
0 OEM MODEL
1 ELECTRICAL REDESIGN
23 FIRST REDESIGN
LONG STROKE CRANKCASE
4 SECOND DESIGN
ROBERTSHAW MOTOR PROTECTION
5
6 CPRSR. MODEL LESS MOTOR PROTECTION
7 MEDIUM TEMP. ROBERTSHAW MOTOR PRO-
TECTION
8
9 CEMAK MODEL
10TH DIGIT PACKAGING
0 MODEL
NO.
4MULTI PACK EXP
1SINGLE PACK
LESS
VALVE
5PALLETIZED LESS VALVE
2 MULTI PACK DOM 7 PALLETIZED WITH VALVE
3SINGLE PACK
WITH
VALVE
9 MULTI PACK MC MINN
SYMBOLS:
= SAMPLE PART NO. 06E215O36O
NOTES:
4. 220-3-60 UNIT DESIGNED FOR USE ON 198 to 242 V
380-3-60 342 418 V
575-3-60 518 660 V
460-3-60 414 529 V
230-3-60 198 264 V
230-3-50 198 264 V
400-3-50 342 457 V
200-3-60 180 229 V
5. RVS HD CPRSR -- ORIGINAL DESIGN NO. 4TH DIGIT A, B, C, D, CRF
9TH DIGIT
REDESIGNNO. 4TH DIGIT F, J, K. L OR N
9TH DIGIT SAME AS
STANDARD
5TH DIGIT USAGE
0 LIGHT DUTY CPRSR. OR
CPRSR. UNIT TONNAGE
5
6
1 MEDIUM DUTY CPRSR. 7
2 H EAV Y D UT Y C PR SR . 8 S PEC IAL OR DE R
3 OILLESS 9
4
6TH & 7TH DIGIT COMPRESSOR SIZE
NO. ST D. LONG STROKE LONG STROKE SHORT
CYL. PROD. STD. CLEARANCE HI CLEARANCE STROKE
4 50 CFM 66 CFM 60 CFM --
6 75 CFM 99 CFM -- 65 CFM
COMPRESSOR UNITS (CAC USAGE)
NO
CYL. STD. PROD. CPRSR. LONG STROKE CPRSR.
4 22 (NOM TONS) --
6 33 (NOM TONS) 44 (NOM TONS)
8TH DIGIT ELECT
1 575 - 3 - 60
2 200 - 1 - 60
3 208/230/460 - 3 - 60
4 200 - 3 - 60
5 230 - 3 - 60
6 400 - 3 - 50
460 -3 - 60
7 230 - 1 - 50
8 230 - 3 - 50
9 220/380 - 3 - 60
0 208/230 - 3 - 60
A 415 - 3 - 50
4TH DIGI T 4T H DIGIT UHLDADER VARIABLE
SUCTION
CUTOFF
UNLOADING
L
E
T
T
E
R
S
T
A
N
D
A
R
D
S
E
R
V
I
C
E
B
O
T
H
DESCRIPTION
A X NO UNLOADERS
2 B X ON E U NL OAD ER - E LE CT RI C
3 C X TWO UNLOADERS - ELECTRIC
4 D X ON E U NL OAD ER - PR ES SU RE
5 E X TWO UNLOADERS - PRESSURE
F X NO UNLOADERS
R E V E R S E D
H E A D 6 C Y L .
S E E N O T E 2
6 J X ON E U NL OAD ER - E LE CT RI C
7 K X TWO UNLOADERS - ELECTRIC
8 L X ON E U NL OAD ER - PR ES SU RE
9 N X TWO UNLOADERS - PRESSURE
G X N O U NLOA DER S - PR ES SU RE
C P R S R W I T H
C O N T B O X
U S E D B Y C A C
F O R U N I T SP X ON E U NL OAD ER - E LE CT RI C
U X TWO UNLOADERS - ELECTRIC
V X ON E U NL OAD ER - PR ES SU RE
W X TWO UNLOADERS - PRESSURE
M X MEDIUM TEMP. - NO UNLOADERS
R X REFRIGERATION - NO UNLOADERS
T X
SERVICE CMPRSR. w/
(1) BLOCKED SUCTION CUT-
OFF UNLOADER HEAD
REPLACES 2,
3,4, 5, 6, 7, 8 & 9
X X SERVICE COMPRESSOR -
AIR CONDITION.
REPLACES A,
B,C, D, E, F J, K,
L & N
Y X SVC. CPRSR. - REFRIG. REPLACES R
8/20/2019 Comp Carly Scre Refrig 2004
23/52
1
CARLYLE REFRIGERATION COMPRESSORS
06E REFRIGERATION AND MEDIUM TEMPERATURE DUTY COMPRESSORAPPLICATION DATA
P52
For mounting configuration,
dimensions and weight refer to
outline drawings on previous
pages.
MODEL
NO. HP
NO.
OF
CYL.
CFM
@
1750
RPM
SUCTION TEMP. RANGE*
(°F)
*Condensing temperature range 80°to 120°F.
CAPACITY (000 BTUH)
-25°SST
110°SCT
65°SGT
0°SC
20°SST
120°
SCT
65°SGT
0°SC
15°SST
110°SCT
65°SGT
0°SC
40°SST
120°SCT
60°SGT
0°SC
R-502 R-12 R-22 R-502 R-502 R-12 R-22
06EY150 15 4 50.3 -40 to 10** -10 to 40 - 54.5 - 92.1 -
06EZ150 15 4 50.3 -10 to 40 -10 to 40 -10 to 40 - 139.0 82.6 219.7
06EY166 20 4 66.0 -40 to 10** -10 to 40 - 68.0 - 109.0 -
06EZ266 25 4 66.0 -10 to 40 - -10 to 50 - 180.0 - 277.0
06EY165 20 6 65.0 -40 to 10** -10 to 40 - 68.3 - 121.7 -
06EY175 20 6 75.4 -40 to 1**
**Cylinder Head Cooling Fan is required to operate at minimum suction temperatures.
-10 to 40 - 78.6 - 135.7 -
06EZ175 25 6 75.4 -10 to 40 -10 to 40 -10 to 50 - 207.5 121.0 323.8
06EY099 30 6 99.0 -40 to 10** -10 to 40 - 104.0 - 172.4 -
06EZ199 35 6 99.0 -10 to 40 -10 to 40 -10 to 50 - 280.0 163.4 422.6
8/20/2019 Comp Carly Scre Refrig 2004
24/52
154
CARLYLE REFRIGERATION COMPRESSORS
06E COMPRESSOR DATA - THREE PHASELOW TEMP. & MED. TEMP. REFRIGERATION
COMPRESSOR
MODEL NO. VOLT HP CFM
OIL
CHG.
PINTS
MAX.
WATTS
MAX.
RLA*
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much
lower RLA values.
MTA LRA
4 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06EY150-140 575 15 50.3 14 22,000 31 38 98
06EY150-340 208-230/460 15 50.3 14 22,000 72/36 90/45 283/14206EY166-140 575 20 66 14 25,300 36 45 120
06EY166-340 208-230/460 20 66 14 25,300 87/44 108/54 345/173
06EY166-640 **
**Order the discrete 400/460-3-50/60 volt compressor for part wind start applications only. When ordering, place the letters PW after the model num-
ber, (i.e., 06EX299660PW)
460 20 66 14 25,300 45 56 150
4 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06EY150-340 200/400 15 41.7 14 18,300 72/36 90/45 283/142
06EY166-340 200/400 20 55 14 28,000 87/44 108/54 345/173
06EY166-640 ** 400 20 55 14 28,000 45 56 150
6 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ
06EY165-140 575 20 65 19 25,300 36 45 120
06EY165-340 208-230/460 20 65 19 25,300 87/44 108/54 345/173
06EY165-640 ** 460 20 65 19 25,300 44 54 173
06EY175-140 575 20 75.4 19 25,300 36 45 120
06EY175-340 208-230/460 20 75.4 19 25,300 87/44 108/54 345/173
06EY175-640 ** 460 20 75.4 19 25,300 45 56 15006EY099-140 575 30 99 19 39,100 52 65 176
06EY099-340 208-230/460 30 99 19 39,100 135/68 168/84 506/253
06EY099-640 ** 460 30 99 19 39,100 65 81 220
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06EY165-340 200/400 20 54 19 21,100 87/44 108/54 345/173
06EY165-640 ** 400 20 54 19 21,100 44 54 173
06EY175-340 200/400 20 62.5 19 21,100 87/44 108/54 345/173
06EY175-640 ** 400 20 62.5 19 21,100 45 56 150
06EY099-340 200/400 30 82.5 19 32,600 135/68 168/84 506/253
06EY099-640 ** 400 30 82.5 19 32,600 65 81 220
4 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 60 HZ
06EZ150-170 575 15 50.3 14 22,000 31 38 98
06EZ150-370 208-230/460 15 50.3 14 22,000 72/36 90/45 283/142
06EZ266-170 575 25 66 14 33,600 46 57 16406EZ266-370 208-230/460 25 66 14 33,600 112/56 140/170 446/223
06EZ266-670 ** 460 25 66 14 33,600 57 71 205
4 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 50 HZ
06EZ150-370 200/400 15 41.7 14 18,300 72/36 90/45 283/142
06EZ266-370 200/400 25 55 14 28,000 112/56 140/170 446/223
06EZ266-670 ** 400 25 55 14 28,000 57 71 205
6 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 60 HZ
06EZ175-170 575 25 75.4 19 33,600 46 57 164
06EZ175-370 208-230/460 25 75.4 19 33,600 112/56 140/70 446/223
06EZ175-670 ** 460 25 75.4 19 33,600 57 71 205
06EZ199-170 575 35 99 19 47,600 65 82 212
06EZ199-370 208-230/460 35 99 19 47,600 155/77 193/96 610/305
06EZ199-670 ** 460 35 99 19 47,600 82 102 265
6 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 50 HZ06EZ175-370 200/400 25 62.5 19 28,000 112/56 140/170 446/223
06EZ175-670 ** 400 25 62.5 19 28,000 57 71 205
06EZ199-370 200/400 35 82.5 19 39,700 155/77 193/96 610/305
06EZ199-670 ** 400 35 82.5 19 39,700 82 102 265
Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.
8/20/2019 Comp Carly Scre Refrig 2004
25/52
1
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06E ... 60 HZ
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06EY150-140 HH83XA460
06EY150-340
HH83XE633†
HH83XB360††
HH83XA463†††
06EY166-140 HH83XA461
06EY166-340
HH83XE622†
HH83XB336††
HH83XA424†††
06EY166-640 HH83XE626
06EY165-140 HH83XA461
06EY165-340
HH83XE622†
HH83XB336††
HH83XB437†††
06EY165-640 HH83XE626
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06EY175-140 HH83XA461
06EY175-340
HH83XE622†
HH83XB336††
HH83XA424†††
06EY175-640 HH83XE626
06EY099-140 HH83XA430
06EY099-340
HH83XE652†
HH83XC439††
HH83XA425†††
06EY099-640 HH83XE642
06EZ150-170 HH83XA460
06EZ150-370
HH83XE633†
HH83XB356††
HH83XA463†††
06EZ266-170 HH83XA469
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06EZ266-370
HH83XE621†
HH83XC409††
HH83XA426†††
06EZ266-670 HH83XE630
06EZ175-170 HH83XA469
06EZ175-370
HH83XE621†
HH83XC409††
HH83XA426†††
06EZ175-670 HH83XE630
06EZ199-170 HH83XA453
06EZ199-370
HH83XE609†
HH83XC432††
HH83XA547†††
06EZ199-670 HH83XE623
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06EY150-340
HH83XE633†
HH83XB360††
HH83XA463†††
06EY166-340
HH83XE622†
HH83XB336††
HH83XA424†††
06EY166-640 HH83XE626
06EY165-340
HH83XE622†
HH83XB336††
HH83XB437†††
06EY165-640 HH83XE626
06EY175-340
HH83XE622†
HH83XB336††
HH83XA424†††
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06EY175-640* HH83XE626
06EY099-340
HH83XE652†
HH83XC439††
HH83XA425†††
06EY099-640 HH83XE642
06EZ150-370
HH83XE633†
HH83XB356††HH83XA463†††
06EZ266-370
HH83XE621†
HH83XC409††
HH83XA426†††
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06EZ266-670 HH83XE630
06EZ175-370
HH83XE621†
HH83XC409††
HH83XA426†††
06EZ175-670 HH83XE630
06EZ199-370
HH83XE609†
HH83XC432††HH83XA547†††
06EZ199-670 HH83XE623
REQUIRED CIRCUIT BREAKERS: 06E ... 50 HZ
NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.
†This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.††This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.
†††This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.
Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers)
.
Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.
8/20/2019 Comp Carly Scre Refrig 2004
26/52
156
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06E
OPTIONAL ACCESSORIES
COMPRESSOR
MODEL NO.
TERMINAL
BOX KIT
SUCTION
SERVICE
VALVE KIT
ALTERNATE
SUCTION
SERVICE
VALVE KIT
DISCHARGE
SERVICE
VALVE KIT
ALTERNATE
DISCHARGE
SERVICE
VALVE KIT
SUSPENSION
KIT
MOUNTING
PLATE KIT
06EY150 06EA660095 06EA660091 - 06DA660064 - 06EA660089 06EA660096
166 - 06DA660064 -175 - 06DA660065 06EA660090
099 - 06DA660065 06EA660090
06EZ150 - 06DA660064 -
266 - 06DA660064 -
175 - 06DA660065 06EA660090
199 - 06DA660065 06EA660090
8/20/2019 Comp Carly Scre Refrig 2004
27/52
1
VALVES
COMPRESSOR SERVICE VALVE KITS BY VALVE SIZE
• KIT CONSISTS OF:
SERVICE VALVE, GASKET AND BOLTS
NOTE: Service Valve contained in kits cannot be ordered separately.
P419
NR= Not Required.
NA = Vender part number available upon request.
VALVE
SIZE
(in.)
VALVE
MOUNTING
(BOLT HOLE
CENTER-IN)
MUELLER - SERVICE VALVE HENRY - SERVICE VALVE
ADAPTER/
TAILPIECE
P/N
KIT
P/N
VALVE
P/N
CAP
P/N
ADAPTER/
TAILPIECE
P/N
KIT
P/N
VALVE
P/N
CAP
P/N
5/8 FLARE 2 BOLT (1-5/8) NR 06DA660059 EN26AA211 EN99ZA001 - - - -
5/8 SWEAT 2 BOLT (1-5/8) NR 06DA660060 EN32AA250 EN99ZA001 - - - -
7/8 SWEAT
2-BOLT (1 -5/8)NR
06DA660061 EN07AA271
EN99ZA006 NR
06DA660061 EN07AA271NA
2 BOLT (1 -3/4) 06DA660062 EN07AA284 06DA660062 EN07AA284
2 BOLT (2-3/4) EN99ZC027 - EN07AA390 - - - -
1-1/8 SWEAT4 BOLT (2-1/2) NR 06DA660063 EN07EA033
EN99ZA006 NR 06DA660063 EN07EA033
EN99ZA0132 BOLT (1 -3/4) 06DA660064 EN07AA348 06DA660064 EN07AA348
2 BOLT (2-3/4) EN99ZC033 - EN07AA395 NA - EN07EC341
1- 3/ 8 SWE AT 4 BOLT ( 2-1/ 2) NR 06DA660065 EN07EA039 EN99ZA006 NR - - -
1-5/8 SWEAT 4 BOLT (2-1/2) NR 06EA660090 EN07EA041 EN99ZA006 NR 06EA60090 EN07EA041
EN99ZA01NR - EN13HA045 NA NA - EN13HA045
2-1/8 SWEAT 4 BOLT (3-1/16) EM99AA516 - EM13FE051
EN99ZA009 EP29VC540 06EA660091 EM13FE051 EN99ZA02- EM13FA516
2-5/8 SWEAT 4 BOLT (3-1/16) EM99AA518 - EM13FA518 - - - - -
3-1/8 SWEAT 4 BOLT (3-7/8) EM99AA520 - EM13FA520 EN99ZA011 EP29VC660 - EM13FE520 EN99ZA01
4-1/8 SWEAT 4 BOLT (4-13/16) NA - EM13FA524 NA NA - EM13FES24 EN99ZA02
8/20/2019 Comp Carly Scre Refrig 2004
28/52
158
CARLYLE REFRIGERATION COMPRESSORS
TOTALINE COMPRESSOR OILS - FOR CARLYLE ANDTOTALINE COMPRESSORS
COMPRESSOR
MODEL
REFRIGERANT R-12, R-22
(L & H TEMP.)
REFRIGERANT R-507,
R-404A
(MED. TEMP)
REFRIGERANT R-507,
R-404A (LOW. TEMP
REFRIGERANT R-134A
(M & H TEMP)
OIL MODEL TOTALINE
PART NO. OIL MODEL
TOTALINE
PART NO. OIL MODEL
TOTALINE
PART NO. OIL MODEL
TOTALINE
PART NO.
Carlyle 06D, E
semi-hermetic
Zerol 150P903-2001
P903-2005
P903-2025
SW68P903-1001
P903-1025
P903-1005
E68
(Do not use
SW-68 for Low
Temp)
P903-1725
P903-1701
P903-1705
SW68P903-1001
P903-1025
P903-1005
RO 15 P903-0101
P903-0105
P903-0155
Carlyle 5F/H open Zerol 150P903-2001
P903-2005
P903-2025
SW68P903-1001
P903-1025
P903-1005
E68
(Do not use
SW-68 for Low
Temp)
P903-1725
P903-1701
P903-1705
SW 68P903-1001
P903-1025
P903-1005
RO 15 P903-0101P903-0105
P903-0155
Carlyle 05T/06T
Screw (74)
E-100 P903-1501
P903-1505
P903-1525
E-100 P903-1501
P903-1505
P903-1525
E-100 P903-1501
P903-1505
P903-1525
E-100 P903-1501
P903-1505
P903-1525
Carlyle 06N Screw
(104 mm Global Chiller)
N/A N/A N/A N/A N/A N/A SW-220
(R-134a Only)
P903-1201
P903-1225
P903-1205
Millennium Scroll
Technologies
Zerol 150 P903-2001
P903-2005
P903-2025
N/A N/A N/A N/A Mobil Arctic 68
Model now
obsolete
8/20/2019 Comp Carly Scre Refrig 2004
29/52
1
OILS
TOTALINE®OILSVACUUM PUMP OIL
A highly purified purpose vacuum
pump oil that cleans and lubri-
cates. The quart bottle (9.5 liters)
has a convenient flip-top-cap.
P894
P/N SIZE
P903-0632 1 QT (.95 liters)
P903-0601 1 GAL (3.8 liters
P903-0605 5 GAL (18.9 liters)
P903-0655 55 GAL (208.2 liters)
MINERAL REFRIGERATION OILS
POLYOL-ESTER OILS
This is a refined oil used specifically
for air conditioning and refrigera-
tion. The low moisture content
means less failure. A non-foaming,
wax-free oil to prevent plugged cap-illaries and sticking expansion
valves. OEM approved by most
manufacturers.
P/N SIZE VISCOSITY
P903-0101 1 GAL (3.8 liters) 150
P903-0105 5 GAL (18.9 liters) 150
P903-0155 55 GAL (208.2 liters) 150
P903-0201 1 GAL (3.8 liters) 300
P903-0205 5 GAL (18.9 liters) 300
P903-0255 55 GAL (208.2 liters) 300
P903-0301 1 GAL (3.8 liters) 500
P903-0305 5 GAL (18.9 liters) 500
P903-0355 55 GAL (208.2 liters) 500
P893
P/N SIZE TYPE
P903-1025 1 QT (.95 liters) SW68
P903-1001 1 GAL (3.8 liters) SW68
P903-1005 5 GAL (18.9 liters) SW68
P903-1125 1 QT (.95 liters) SW32
P903-1101 1 GAL (3.8 liters) SW32
P903-1105 5 GAL (18.9 liters) SW32
P903-1225 1 QT (,95 liters) SW220
P903-1201 1 GAL (3.8 liters SW220
P903-1205 5 GAL (18.9 l iters) SW220
P1544
These environmentally friendly products are specifically for-
mulated to use with the non-CFC refrigerant R-134a. The
base fluids have been engineered to be totally miscible with
R134a over a very wide temperature range while maintain-
ing excellent lubricating properties.
The Z-Series are high quality synthetic Alkylbenzene Refriger
ation fluids for us with HCFC, CFC and ammonia refrigerants
in refrigeration and air conditioning applications.
Due to superior miscibility, Totaline Z-Series lubricants are
excellent for systems utilizing environmentally sound refriger-
ants MP39, MP60, HP80 or HP81. Totaline Z-Series are supe
rior products for all R-22, R-123 and R-502 Systems,
particularly at low temperatures.
Z-200TD is formulated with a unique additive package provid-
ing extreme pressure (EP) lubricity and foam control at operating conditions.
P/N SIZE TYPE
P903-2025 1 QT (.95 liters) Z-150
P903-2001 1 GAL (3.8 liters) Z-150
P903-2005 5 GAL (18.9 liters) Z-150
P903-2125 1 QT (.95 li ters) Z-200TD
P903-2101 1 GAL (3.8 l iters) Z-200TD
P903-2105 5 GAL (18.9 liters) Z-200TD
P903-2225 1 QT (.95 liters) Z-300
P903-2201 1 GAL (3.8 liters Z-300
P903-2205 5 GAL (18.9 liters) Z-300
ALKYLBENZENE REFRIGERATION OILS
P1545
8/20/2019 Comp Carly Scre Refrig 2004
30/52
160
CARLYLE REFRIGERATION COMPRESSORS
06CY REFRIGERATION DUTY COMPRESSOR APPLICATION DATA
P53
CARLYLE COMPOUND COOLINGTM ...
An innovative approach to low temperature refrigeration from Carlyle.
TWO-STAGE COMPRESSION IN A SINGLE COMPRESSOR USES R-22 WITH THE
EFFICIENCY AND RELIABILITY OF R-502
• LOW COMPRESSION RATIOS• TWO-STAGE BOOSTER
PERFORMANCE
• SAME CAPACITIES AS R-502COMPRESSORS
• EASY APPLICATION OFSUBCOOLING
• SUBCOOLING CONTROL ALLOWSCONSTANT CAPACITY OVER AWIDE OPERATING RANGE
• CONSTANT CAPACITY REDUCESSTRESS RESULTING FROM SHORTCYCLING
• IDENTICAL OIL CONTROL TO R-502RACK SYSTEMS
• LOW OIL CIRCULATION RATES
• SIMILAR DIMENSIONS TO OTHERCARLYLE MODELS FOR EASY FIT
HOW COMPOUND COOLINGTM WORKS
A variation of the two-stage booster system, the internally compounded compressor has both the high and low stages built into
one compressor body. In this arrangement, compression is accomplished in two stages, safely and economically.
All nine Compound Cooling models have six cylinders. Four cylinders, acting as the low stage, “boost” the suction pressure from
the refrigeration load to the intermediate pressure. The remaining two cylinders, acting as the high stage, complete the compres-
sion to normal condensing temperatures. The result is lower internal losses and a compressor that delivers more capacity in the
same displacement. The lower losses also produce operating efficiencies that are substantially higher than the competition.
For mounting configuration, dimen-
sions and weight refer to outline
drawings on following page.
MODEL NO. HP
NO.
OF
CYL.
CFM
@
RPM
SUCTION TEMP. RANGE*
(DEGREES °F)
R-22
*Condensing temperature range 60°to 130°F Cylinder Head Cooling Fans recommended for all applications.
R-22 CAPACITY
(000 BTUH)OIL
CHARGE
(PINTS)
-25°SST
110°SCT
65°SGT
40°LIQUID
06CY016 5.0 6 16 -40 to -15 17.6 1006CY018 5.0 6 18 -40 to -15 22.6 10
06CY124 6.5 6 24 -40 to -15 24.6 10
06CY228 7.5 6 28 -40 to -15 29.5 10
06CY337 10.0 6 37 -40 to -15 39.9 10
06CY550 15.0 6 50 -40 to -15 56.3 19
06CY665 20.0 6 65 -40 to -15 71.4 19
06CY675 20.0 6 75 -40 to -15 80.6 19
06CY899 30.0 6 99 -40 to -15 103.4 19
8/20/2019 Comp Carly Scre Refrig 2004
31/52
1
CARLYLE REFRIGERATION COMPRESSORS
06CY OUTLINE DRAWINGSNOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS.
06CC COMPRESSORS
* 4 FIRST STAGE, 2 SECOND STAGE.
0 6CY01 6 0 6CY0 18 0 6CY2 28 0 6CY3 37
MOTOR HORSEPOWER 5 5 7.5 10
NO. OF CYLINDERS 6* 6* 6* 6*
BORE AND STROKE (in.) 2.0 x 2.0 x 2.0 x 1.47 2.0 x 1.94
DISPLACEMENT CFM AT 1750 RPM 16 18 28 37OIL, CHARGE, PINTS CPP33-2 10 10 10 10
DRY WEIGHT LESS SERVICE VALVES 340 LBS 340 LBS 340 LBS 345 LBS
06CC COMPRESSORS
* 4 FIRST STAGE, 2 SECOND STAGE.
0 6CY5 50 06 CY6 65 0 6CY6 75 0 6CY8 99
MOTOR HORSEPOWER 15.0 20.0 50.0 30.0
NO. OF CYLINDERS 6* 6* 6* 6*
BO RE AND STROKE (in.) 2. 69 x 2. 16 2.69 x 1.96 2.6 9 x 2.19 2. 69 x 2.87
DISPLACEMENT CFM AT 1750 RPM 50 65 75 99
OIL, CHARGE, PINTS CPP33-2 19 19 19 19
DRY WEIGHT LESS SERVICE VALVES 545 LBS 555 LBS 555 LBS 580 LBS
8/20/2019 Comp Carly Scre Refrig 2004
32/52
162
CARLYLE REFRIGERATION COMPRESSORS
06CY COMPRESSOR DATA - THREE PHASELOW TEMP. REFRIGERATION - COMPOUND COOLING™ MODELS
COMPRESSOR
MODEL NO. VOLT HP CFM
OIL
CHG.
PINTS
MAX.
WATTS
MAX.
RLA*
*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much
lower RLA values.
MTA LRA
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 60 HZ
06CY016-D103 208/230 5.0 16 10 4,600 19.3 27.0 100
06CY016-G103 460 5.0 16 10 4,600 9.6 13.5 50.006CY016-J103 575 5.0 16 10 4,600 7.7 10.8 40.0
06CY018-DI03 208/230 5.0 18 10 5,000 19.3 27.0 100
06CY018-G103 460 5.0 18 10 5,000 9.6 13.5 50.0
06CY018-J103 575 5.0 18 10 5,000 7.7 10.8 40.0
06CY124-D103 208/230 6.5 24 10 6,500 23.6 33.0 160
06CY124-G103 460 6.5 24 10 6,500 11.8 16.5 80.0
06CY124-J103 575 6.5 24 10 6,500 9.4 13.2 64.0
06CY228-D103 208/230 7.5 28 10 7,600 29.7 41.6 198
06CY228-G103 460 7.5 28 10 7,600 14.9 20.9 99.0
06CY228-J103 575 7.5 28 10 7,600 11.9 16.7 79.0
06CY337-D103 208/230 10 37 10 10,000 33.2 46.5 228.0
06CY337-G103 460 10 37 10 10,000 16.6 23.3 114.0
06CY337-J103 575 10 37 10 10,000 13.4 18.8 91.0
06CY550-E103 208-230/460 15 50 19 13,000 37.1/18.6 52/26 283/142
06CY550-F103 460 15 50 19 13,000 18.6 26.0 142
06CY550-J103 575 15 50 19 13,000 15.0 21.0 98.0
06CY665-E103 208-230/460 20 65 19 16,800 60.7/30.0 85/42 345/173
06CY665-F103 460 20 65 19 16,800 30.0 42.0 173
06CY665-J103 575 20 65 19 16,800 23.6 33.0 120
06CY675-E103 208-230/460 20 75 19 19,000 60.7/30.0 85/42 345/173
06CY675-F103 460 20 75 19 19,000 30.0 42.0 173
06CY675-J103 575 20 75 19 19,000 26.4 33.0 120
06CY899-E103 208-230/460 30 99 19 26,000 92.9/46.4 130/65 506/253
06CY899-F103 460 30 99 19 26,000 46.4 65.0 253
06CY899-J103 575 30 99 19 26,000 37.1 52.0 175
6 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ
06CY016-G103 400 5 13.2 10 3,800 9.6 13.5 50.0
06CY018-G103 400 5 15.0 10 4,200 9.6 13.5 50.0
06CY124-G103 400 6.5 20.0 10 5,400 11.8 16.5 80.0
06CY228-G103 400 7.5 23.3 10 6,300 14.9 20.9 99.0
06CY337-G103 400 10 30.8 10 8,300 16.6 23.3 114.0
06CY550-E103 200/400 15 41.7 19 11,000 37.1/18.6 52.0/26.0 283/142
06CY550-F103 400 15 41.7 19 11,000 18.6 26.0 142
06CY665-E103 200/400 20 54 19 14,000 60.7/30.0 85.0/42.0 345/173
06CY665-F103 400 20 54 19 14,000 30.0 42.0 173
06CY675-E103 200/400 20 62.5 19 14,000 60.7/30.0 85.0/42.0 345/173
06CY675-F103 400 20 62.5 19 14,000 30.0 42.0 173
06CY899-E103 200/400 30 82.5 19 2,1700 92.9/46.4 130/65.0 506/253
06CY899-F103 400 30 82.5 19 21,700 46.4 65.0 253
Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.
8/20/2019 Comp Carly Scre Refrig 2004
33/52
1
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED CIRCUIT BREAKERS: 06CY ... 60 HZ
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06CY550-E100 HH83XB560††
HH83XB548†††
06CY550-F100 HH83XB548
06CY550-J100 HH83XB547
06CY665-E100 HH83XB376††
HH83XB447†††
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06CY665-F100 HH83XB447
06CY665-J100 HH83XB555
06CY675-E100
HH83XB376††
HH83XB559†††
06CY675-F100 HH83XB559
06CY675-J100 HH83XB430
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06CY899-E100 HH83XB346††
HH83XB402†††
06CY899-F100 HH83XB402
06CY899-J100 HH83XB437
REQUIRED CIRCUIT BREAKERS: 06CY ... 50 HZ
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06CY550-E100 HH83XB560††
HH83XB548†††
06CY550-F100 HH83XB548
06CY665-E100 HH83XB376††
HH83XB447†††
06CY665-F100 HH83XB447
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06CY675-E100 HH83XB376††
HH83XB559†††
06CY675-F100 HH83XB559
COMPRESSOR
MODEL NO.
CIRCUIT
BREAKERS
P/N
06CY899-E100 HH83XB346††
HH83XB402†††
06CY899-F100 HH83XB402
NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.
†This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.††This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.
†††This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.
Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers).
Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.
8/20/2019 Comp Carly Scre Refrig 2004
34/52
164
CARLYLE REFRIGERATION COMPRESSORS
REQUIRED ACCESSORIES - 06CY
REQUIRED ACCESSORIES - 06CY OPTIONAL ACCESSORIES
COMPRESSOR
MODEL NO.
SUCTION
SERVICE
VALVE KIT
P/N
ALTERNATE
SUCTION
SERVICE
VALVE KIT
P/N
DISCHARGE
SERVICE
VALVE KIT
P/N
ALTERNATE
DISCHARGE
SERVICE
VALVE KIT
P/N
SUSPENSION
KIT
P/N
MOUNTING
PLATE KIT
P/N
06CY016 06DA660063 06DA660065 06DA660062 06DA660064 06DA660057 06EA660096
06EA660090 - -
06CY018 06DA660065 06EA660090 06DA660062 06DA660064
06DA660063 - -
06CY124 06DA660065 06EA660090 06DA660062 06DA660064
06DA660063 - -
06CY228 06DA660065 06EA660090 06DA660062 06DA660064
06DA660063 - -
06CY337 06DA660090 06EA660065 06DA660064 06DA660062
06DA660063 - -
06CY550 06EA660090 - 06DA660065 06EA660090 06EA660089
06CY665 06EA660090 - 06DA660065 06EA660090
06CY675 06EA660090 - 06DA660065 06EA660090
06CY899 06EA660090 - 06DA660065 06EA660090
8/20/2019 Comp Carly Scre Refrig 2004
35/52
1
COPELAND SEMI-HERMETIC COMPRESSORS
REMANUFACTURED COPELAND COMPRESSORS FROM CARLYLE
X X X X X X X X X X X
COMPRESSORFAMILY SERIES
Either a number or a letter estab-lished for each product model.
MODEL VARIATION
A number assigned to indicate majorvariations within one family series.
COMPRESSOR MOTOR TYPES
Phase Description Code
3 Three Phase T
3 Wye (Star) Delta E
3 6 Lead Part Winding or Across-the-Line except 575 V F
ELECTRICAL CODES
60 Hz 50 Hz Cod
460-3 380/420-3 D
575-3 500-3 E
208/230/460-3 200/380/
400-3 K
- 210/240/
380/4 L
- 380/420-3 M
230/460-3 200/400/3 N
200/3 - U
200/220/380-3 200/380-3 8
DISPLACEMENT AND VALVE PLATE
A letter only, arbitrarily assigned for each dif-ferent displacement valve plate combinationwithin any one family series.
Code Description
R Standard Refrigerant-Cooled
A Air Cooled
D Discus (Refrig. Cooled)
COMPRESSOR MOTORRATING
Nominal (HP) Code
1/2 005
3/4 007
1 010
1-1/2 015
5 050
7-1/2 076
10 10020 200
25 250
30 300
35 350
40 400
TYPE OF OIL
Type Code
Mineral O
Alki A
POE E
COMPRESSOR MOTORPROTECTION
Type Protection Code
Internal ThermalProtectors - ElectricalSensors; and Control“Module External Use withContactor
S
8/20/2019 Comp Carly Scre Refrig 2004
36/52
166
CARLYLE REMANUFACTURED COPELAND COMPRESSORS
PERFORMANCE DATA — Air Cooled Models (60 Hz)
R-12
MODEL NOM.
HP
CONDTEMP
°F
CAPACITY, Btu/ hr x 1000POWER INPUT, Watts x 1000
Evaporating Temperature, °F
55 45 35 25 15 5 0 -5 -10 -20 -30 -40
KEAB 005AIAA 1/2
90 5450
6354350585
3420540
2990520
2580500
130 3960
7303100640
2380565
2040530
1730495
KGAB005AIAAKAGB005EIAA
1/290
3575605
3150575
2375515
1710460
1175405
130 2325
6552030600
1430510
860420
KAA2007AIAAKAAB007ACAVKABB007AIAA
KABB007ECAA
3/490
4360835
3250680
2370545
1600450
130 3100
8702180715
1460580
850475
KAMB007ECAAKAMB007ACAVKAMB007EIAA
3/4
90 13400
79011150
7709030740
7200715
5620680
4250650
3670630
130 9970
112081601060
6550980
51400900
3920820
2900740
2470685
KAGA007ATAC
KAGB007ACAV
3/490
78307200
6190675
4830620
4200595
3600560
130 5600875 4350780 3300685 2830635 2400595
KAJA010ATACKAJB010ECAV
1.090
17000920
14100905
11550880
9300850
7350815
5700770
5000750
130 12550
1295103001220
83001140
66001045
5100950
3900840
8400785
KAKA010ATACKAKB011ACAVKAKB011ECAV
1.0
90 10700
9308560880
6800830
6030800
5300765
130 7700
114560801015
4700890
4070835
3500785
KALB010ACAVKALB010ECAV
1.090
7400950
6440880
5600810
4190680
3030565
2040480
130 5300
111546001030
3930950
2830800
1900670
1150560
KATB01 0ACAV 1 .090
79201135
69001060
5200920
3840790
2700680
130 5775
1360
4970
1240
3630
1010
2550
815
1680
650
KALB015ECAVKALA016ETAC
1.5
90 24250
1370202001340
164501300
132001250
104001190
80501120
70501090
130 18300
1860152501790
123501685
97501560
74001430
56001280
48001210
KATA015ETACKATB015ECAV
1.590
161501510
127001390
101001275
89701220
79001165
130 12000
180094001595
73001410
63601325
55001255
R-502
KAMB007ECAAKAMB007ACAVKAMB007EIAA
3/4
90 5920
8705180810
3880710
2840615
2030540
130 3620
9403120865
2230725
1500590
960480
KAJA010ATACKAJB010ECAV
1.090
78201050
6840980
5200855
3830740
2700640
130 4900
116042801065
3150885
2200720
1360570
KAL B01 5ECAV 1 .590
97501480
73501300
54001145
41001030
130 4300
133030001110
2100950
8/20/2019 Comp Carly Scre Refrig 2004
37/52
1
CARLYLE REMANUFACTURED COPELAND COMPRESSORS
TECHNICAL DATA — Air Cooled Models (60 Hz)
MODEL NOM.
HP CYL
BORE
(in.)
STROKE
(in.)
CFH
(60 Hz)
OIL
CHARGE
(oz)
DIMENSIONS (in.) MOUNTING
CENTERS (in.)
RECOMMENDED
SERVICE VALVES
WEIGH
(lb)
Length Width Height Length Width Suction
(in.)
Disch.
(in.) Net Sh
KAEB005AIAA 1/2 2 1-1/2 5/8 134.2 22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 1/2 FL 3/8 FL 81 8
KAGB005AIAAKAGB005EIAA 1/2 2 1-7/16 15/16 184.9 22(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 1/2 FL 3/8 FL 81 8
KAA2007AIAA
KAAB997ACAV
KAAB007AIAA
KAAB007ECAA
3/4 2 1-11/16 15/16 255.0 22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/6 FL 3/8 FL 89 9
KAMB007ECAA
KAMB007ACAV
KAMB007EIAA
3/4 2 1-3/8 15/16 169.0 22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 3/8 FL 89 9
KAGA007ATAC
KAGB007ACAV 3 /4 2 1-7/16 15/16 184.9
22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 3/8 FL 89 9
KAJA010ATAC
KAJB010ECAV 1 2 1-9/16 15/16 218.4
22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 1/2 FL 89 9
KAKA010ATAC
KAKB011ACAV
KAKB011ACAV
1 2 1-11/16 15/16 255.0 22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 1/2 FL 89 9
KALB010ACAVKALB010ECAV
1 2 1-7/8 15/16 313.0 22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 1/2 FL 89 9
KATB010ACAV 1 2 1-7/8 1-5/32 389.0 22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 1/2 FL 89 9
KALB015ECAV 1-1/2 2 1-7/8 15/16 313.0 22
(20) 14-3/8 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 1/2 FL 94 9
KATA015ETAC
KATB015ECAV 1-1/2 2 1-7/8 1-5/32 389.0
22
(20) 14-3/8 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 1/2 FL 94 9
KAMB007ECAA
KAMB007ACAV
KAMB007EIAA
3/4 2 1-3/8 15/16 169.0 22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 3/8 FL 89 9
KAJA010ATAC
KAJB010ECAV 1 2 1-9/16 15/16 218.4
22
(20) 14 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 1/2 FL 89 9
KALB015ECAV 1-1/2 2 1-7/8 15/16 313.0 22
(20) 14-3/8 7-7/8 9-3/4 8-3/16 6-3/8 5/8 FL 1/2 FL 94 9
8/20/2019 Comp Carly Scre Refrig 2004
38/52
168
CARLYLE REMANUFACTURED COPELAND COMPRESSORS
PERFORMANCE DATA — Refrigerant Cooled Models (60 Hz)
R-12
MODEL NOM.
HP
COND
TEMP
°F
CAPACITY, Btu/hr x 1000
POWER INPUT, Watts x 1000
Evaporating Temperature, °F
55 45 35 25 15 5 0 -5 -10 -20 -30 -40
9RA1050ATFC 5
90 52.5
4.76
42.3
4.47
33.6
4.00
29.5
3.71
25.7
3.42
130 37.0
5.44
28.4
4.87
21.2
4.28
17.8
3.97
14.6
3.66
9RBI050ATFC 5
90 32.2
4.70
28.1
4.36
21.3
3.68
15.4
3.08
10.2
2.60
130 23.2
5.25
19.9
4.83
14.5
4.06
9.0
3.36
6.0
2.80
9RB1076ATFC
9RB1076ATFD 7.5
90 65.7
6.04
53.0
5.47
42.7
4.94
37.8
4.69
33.3
4.44
130 48.9
7.00
39.4
6.27
31.5
5.56
27.7
5.22
24.2
4.89
9RC1076ATFC 7.5
90 116.4
7.45
96.5
6.97
78.3
6.47
61.4
5.95
47.5
5.42
36.4
4.90
32.1
4.62
130 86.3
9.33
71.5
8.66
57.4
7.92
44.7
7.10
34.0
6.23
25.2
5.32
22.0
4.86
9RS2076ATFC96S3076ATFC
9RS3076ATFD
7.5
90 76.3
7.80
63.3
7.00
51.4
6.24
46.1
5.88
41.3
5.50
36.8
5.40
28.0
5.14
20.0
4.77
13.4
4.37
130 57.2
9.35
47.6
8.56
38.3
7.53
33.8
6.95
29.3
6.36
25.3
5.80
17.4
4.60
10.3
3.34
4.20
2.10
4 RA3 100 ATSK 1 0
90 165.6
9.78
140.88
9.23
117.9
8.66
97.6
8.06
79.4
7.45
63.7
6.81
56.5
6.49
130
126.6
12.51
11.78
106.0
11.78
97.3
10.43
71.0
9.93
56.8
8.82
45.0
7.59
39.7
6.94
4 RH115 0ATSK 1 5
90 214.2
12.70
182.3
12.88
153.1
12.76
127.9
12.29
105.7
11.57
87.3
10.54
79.0
9.95
130 180.3
18.25
148.9
17.05
120.4
15.73
96.1
14.27
75.0
12.69
57.9
10.99
50.3
10.10
R-22
9RJ1076ATFC 7.5
90 111.6
8.34
88.8
7.64
69.6
6.97
53.5
6.34
130 83.210.51
66.09.40
51.48.40
39.17.51
9RC1101ATFC
9RC1101ATFD 10
90 189.9
10.50
155.0
9.90
127.2
9.25
103.6
8.60
82.6
7.95
63.8
7.26
130 146.7
13.44
120.0
12.50
96.9
11.90
77.5
10.35
59.2
9.23
42.5
8.08
9RS1150ATFD
9RS1150ATSC 15
90 265.3
12.20
212.5
12.40
171.0
12.05
137.2
11.40
106.6
10.40
67.7
9.25
130 191.5
17.70
156.0
17.00
125.7
15.80
98.2
14.35
72.9
12.65
45.00
10.40
R-502
9RJ1076A-TFC 7.5
90 115.0
9.07
95.4
8.74
77.7
8.12
61.6
7.33
54.5
6.90
48.8
6.52
42.7
6.14
32.5
5.40
23.9
4.64
16.9
3.86
130 84.0
11.46
68.9
10.44
55.3
9.35
43.2
8.25
38.2
7.71
31.9
7.16
27.4
6.59
19.5
5.45
12.9
4.29
7.9
3.05
9RS2076ATFC9RS3076ATFC
9RS3076ATFD
7.590
62.6
9.30
49.5
8.12
37.5
6.87
26.2
5.60
130 39.5
10.00
29.5
8.40
21.1
6.70
13.4
5.00
9RC1101ATFC
9RC1101ATFD 10
90 111.5
9.80
89.2
9.12
71.2
8.40
65.0
8.00
130 78.0
11.95
61.0
10.74
47.2
9.50
42.0
8.85
4 RA3 100 ATSK 1 0
90 97.9
12.42
87.3
11.61
77.3
10.85
58.8
9.42
42.7
8.14
28.9
7.00
130 64.5
13.70
57.0
12.77
50.0
11.85
37.4
9.99
27.6
8.13
17.8
6.26
8/20/2019 Comp Carly Scre Refrig 2004
39/52
1
CARLYLE REMANUFACTURED COPELAND COMPRESSORS
PERFORMANCE DATA — Refrigerant Cooled Models (60 Hz) (cont)
R-502 (cont
MODEL NOM.
HP
COND
TEMP
°F
CAPACITY, Btu/hr x 1000
POWER INPUT, Watts x 1000
Evaporating Temperature, °F
55 45 35 25 15 5 0 -5 -10 -20 -30 -40
4RL1150ATSK4RL3150ATSK
15 90
115.4
15.58
103.0
14.61
91.4
13.68
71.1
11.95
54.5
10.41
41.6
9.04
130 78.0
17.14
68.2
16.36
59.3
15.08
43.9
12.67
31.8
10.47
22.9
8.46
6RA4200ATSK 20
90 139.2
17.99
124.1
16.83
109.7
15.72
83.6
13.65
60.7
11.79
41.0
10.14
130 91.6
19.85
81.0
18.51
71.1
17.17
53.2
14.48
37.9
11.78
25.4
9.07
6RL1250ATSK 25
90 165.5
21.00
149.0
20.49
133.3
19.84
104.9
18.12
80.3
15.84
59.4
13.00
130 114.4
26.03
101.9
24.34
90.1
22.65
68.7
19.23
50.3
15.78
34.9
12.28
6RT1300ATSK 30
90 179.5
27.00
160.5
25.65
145.5
24.25
118.5
21.55
94.5
18.95
72.0
16.40
130 125.0
32.40
111.5
29.90
99.0
27.50
76.5
22.75
55.0
18.20
34.5
13.85
9RB1076ATFD 7.5
90 63.08.18
55.77.90
49.47.57
39.26.85
30.86.08
23.45.24
130 41.5
9.68
36.0
9.03
31.2
8.37
23.6
7.04
17.7
5.64
12.9
4.27
8/20/2019 Comp Carly Scre Refrig 2004
40/52
170
CARLYLE REMANUFACTURED COPELAND COMPRESSORS
TECHNICAL DATA — Refrigerant Cooled Models (60 Hz)
MODEL NOM.
HP CYL
BORE
(in.)
STROKE
(in.)
CFH
(60 Hz)
OIL
CHARGE
(oz)
DIMENSIONS (in.)
MOUNTING
CENTERS
(in.)
RECOMMENDED
SERVICE VALVES
WEIGHT
(lb)