1GENERAL INTRODUCTION
ipe Shields Inc. pioneered the first insulated pipe support, in 1971, for use on HVAC and plumbing lines. These supports were designed because fiberglass pipe insulation is not strong enough to carry
the load at the point of support without crushing. The various methods contractors employed to compensate for this weakness were inconsistent, non-uniform and labor intensive, often resulting in damage to the vapor barrier and/or pipe insulation. The insulated pipe support filled the need for an energy efficient, economical and practical support. Pipe Shields Inc. has developed a large and growing family of insulated pipe supports, using its standard concept of incorporating materials strong enough to carry the load while insulating the pipe at the same time. No welding to the pipe is required (except for insulated positive anchors and insulated pipe riser clamps) and no direct metal-to-metal heat path exists. Insulated pipe supports meet an assortment of requirements, including:
Pipe supported on: o Flat Surface o Pipe Roll o Clevis Hanger
Gas Steam Super Heated Steam Chilled Water Styrene Guide Supports Sliding Supports Restrained Supports
Anchors Pipe Hangers Pipe Riser Clamps Thermal Growth Small or Large Maximum Support Spacing Light, Medium or Heavy Loads Ultra-High Temperatures Minimum Overhead Clearance Minimum Horizontal Clearance Minimum Field Labor Minimum Friction Loads Easy Installation
Other products designed, manufactured and supplied not included in this catalog are:
1. Cryogenic supports 2. Seismic pipe restraints 3. Heat-traced pre-insulated pipe supports 4. Pipe supports used in computer chip, styrene plants and oil refineries 5. Pipe supports for solar energy projects to accommodate expansion travels in excess of 5- 0
Our highly sophisticated products are a direct result of years of research, engineering and design to develop cost efficient products for the power, petrochemical, chemical and commercial markets. We work closely with engineering firms and in-house engineering departments of owners to provide working solutions to meet their engineering challenges. We have established proprietary specifications that have now become an industry standard used by owners, engineers and contractors throughout the world markets. If you have a pipe support need not met by any of the items described in this catalog, please contact us at
713-731-0030 or 1-800-787-5914.
P
FRONEK GROUP
CATALOG PS-2004
2TEMPERATURE, DIMENSIONAL AND MATERIAL VARIANCES
Temperature Ranges Pipe Shi elds Inc. str ongly recommen ds the foll owing temper ature range s for our stan dard insulati on material: Material Temperature Calcium Silicate +40oF to + 1200 oF Urethane -275 oF to +275 oF Foamglas -450 oF to +900 oF Material Variances Our standard paint finish is SP150 Red Oxide Primer which meets full EPA and California safety regulations. Other paint finished are available upon request:
Hot dipped galvanized In-organic zinc (CZ11HS) Dupont (Corlar) 25P epoxy SP145 grey oxide Carbothane 134HG Carbozinc 859
Slide plate material and other field welded material are coated with deoxaluminate (silver coating) Model Designation for Alternate Insulation Materials Polyurethane Add U after Catalog Model Number Example: B1000U Urethane/Foamglas - Add UF after Catalog Model Number Example: B1000UF Calcium Silicate/Foamglas - Add CF after Catalog Model Number Example: B1000CF
FRONEK GROUP
CATALOG PS-2004
3INSULATED PIPE SUPPORT SELECTION GUIDEFRONEK GROUP
CATALOG PS-2004
1.A. WaterB. Steam, Gas, or Air
2. APPLICATIONA. Pipe supported from below
a. On flat surfaceb. On pipe roll
B. Pipe supported from abovea. In clevis or 2-bolt hanger
The product data sheets describing each model refer to other models in the catalog with features such as load rating, axial or lateral travel, or restraint, etc. which you may have an interest.
USE OF THE INSULATED PIPE SUPPORT SELECTION GUIDE
XX
OR AIR
TABLE 6 X
TABLE 3
TABLE 1TABLE 2
XX
XTABLE 4TABLE 5
X
XX
X
XX
ONPIPE ROLL
ON FLATSURFACE
APPLICATIONPIPE SUPPORTED
FROM ABOVEFROM BELOW
If you have a pipe support need not met by any of the items described in this catalog, please contact us at 713-731-0030 or 1-800-787-5914.
SERVICE
These Selection Guide Tables are organized by:
The table on the following pages will assist you in making a selection of the proper and most economicinsulated pipe support for your application.
WATER
SERVICE
STEAMGAS IN CLEVIS OR
2-BOLT HANGER
4INSULATED PIPE SUPPORT SELECTION GUIDEFRONEK GROUP
CATALOG PS-2004
WATERPIPE SUPPORTED FROM BELOW ON FLAT SURFACE
B1000 B1100 B1200 B1300B2000 B2100 B2200 B2300B3000 B3100 B3200 B3300B4000 B4100 B4200 B4300
ASME A1000 A3000 A5000 A7000 A7200 A7400 B5000 B5100 B5200 B5300 B7000 B7100 B7200 B7300B31.1 A2000 A4000 A6000 B6000 B6100 B6200 B6300 B8000 B8100 B8200 B8300
PipeSize (Ref)1/2 7 11 123/4 7 12 131 7 13 14
1 1/2 9 15 162 10 15 17
2 1/2 11 12 14 16 213 12 12 13 17 20 35 45 55 32 45 55
3 1/2 13 12 13 16 19 35 45 55 33 45 554 14 13 14 17 19 35 45 55 35 45 555 16 12 14 16 17 35 45 55 33 45 556 17 10 12 13 14 26 34 45 55 30 45 558 19 7 8 11 12 21 29 45 55 26 45 5510 22 6 6 7 10 18 25 24 45 55 21 42 5512 23 8 14 20 31 20 40 55 65 17 36 54 6514 25 8 13 22 31 20 40 55 65 18 35 53 6516 27 12 21 28 19 37 55 65 16 34 50 6518 28 10 19 26 17 34 52 65 15 30 46 6120 30 9 17 23 15 31 46 62 14 27 41 5524 32 14 18 12 24 36 48 10 21 32 4330 33 10 12 11 21 32 43 9 19 29 3936 35 9 18 28 37 8 16 24 3342 36 8 16 24 32 7 14 21 28
Note:
Pipe Diameter: 8" standard weightWater20' - 0Insulated pipe support model number
support spacing. In this case, Model A7200 is selected since it is capable of handling 21'-0 supportspacing. The Index Sheets to Sections "A" & "B" indicate some of the differences between models.Check Product Data Sheet for description before making a final selection. In this example, if thesupport is required to handle +/-4 1/2" of axial travel, Model B2000 would be selected (Section "B"Index & Product Data Sheet B2000).
The maximum hanger spacing s hown in Table 1 are derived from load ratings (see Product Data Sheets) of Pipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should be guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or res traint, etc.
In table 1, for 8" pipe size, find the model(s) rated for handling 20'- 0 or greater
Service:
Determine:Support Spacing:
Method:
Example: Given:
TABLE 1SERVICE:APPLICATION:
MAXIMUM HANGER SUPPORT SPACING - FEETFOR VARIOUS PIPE SH IELDS, INC.INSULATED PIPE SUPPORT MODELS
CommercialLight Industrial
w/ Load Distribution PlateHeavy Industrial
on Slide PadRated for Combined
Lateral and Vertical Loads
5INSULATED PIPE SUPPORT SELECTION GUIDEFRONEK GROUP
CATALOG PS-2004
STEAM, GAS OR AIRPIPE SUPPORTED FROM BELOW ON FLAT SURFACE
B1000 B1100 B1200 B1300B2000 B2100 B2200 B2300B3000 B3100 B3200 B3300B4000 B4100 B4200 B4300
ASME A1000 A3000 A5000 A7000 A7200 A7400 B5000 B5100 B5200 B5300 B7000 B7100 B7200 B7300B31.1 A2000 A4000 A6000 B6000 B6100 B6200 B6300 B8000 B8100 B8200 B8300
PipeSize (Ref)1/2 8 11 123/4 9 12 131 9 14 15
1 1/2 12 17 192 13 18 20
2 1/2 14 15 16 20 253 15 15 17 21 26 40 50 60 40 50 60
3 1/2 16 16 18 21 25 40 50 60 40 50 604 17 17 19 23 26 40 50 60 40 50 605 19 17 20 22 25 40 50 60 40 50 606 21 16 18 20 22 40 40 50 60 40 50 608 24 12 14 17 19 35 40 50 60 40 50 6010 26 10 10 13 17 31 40 40 50 60 36 50 6012 30 9 9 15 26 37 45 36 50 60 70 32 50 60 7014 32 8 9 15 25 40 45 38 50 60 70 34 50 60 7016 35 8 8 14 24 40 45 39 50 60 70 25 50 60 7018 37 14 24 40 45 38 50 60 70 34 50 60 7020 39 14 22 40 45 36 50 60 70 32 50 60 7024 42 11 20 36 45 32 50 60 70 28 50 60 7030 44 10 18 32 39 33 50 60 70 30 50 60 7036 48 9 15 27 33 50 60 70 29 50 60 7042 50 12 23 31 50 60 70 28 50 60 70
Note:
Pipe Diameter: 8" standard weightSteam30' - 0Insulated pipe support model number
The maximum hanger spac ing shown in Table 2 are derived from load ratings (see Product Data Sheets) of Pipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc.
w/ Load Distribution PlateHeavy Industrial
on Slide PadRated for Combined
Lateral and Vertical Loads
support spacing. In this case, Model A7200 is selected since it is capable of handling 35'-0 supportspacing. The Index Sheets to Sections "A" & "B" indicate some of the differences between models.Check Product Data Sheet for description before making a final selection. In this example, if thesupport is required to handle +/-4 1/2" of axial travel, Model B2000 would be selected (Section "B"Index & Product Data Sheet B2000).
Example: Given:
TABLE 2SERVICE:APPLICATION:
MAXIMUM HANGER SUPPORT SPACING - FEETFOR VARIOUS PIPE SH IELDS, INC.INSULATED PIPE SUPPORT MODELS
CommercialLight Industrial
In table 2, for 8" pipe size, find the model(s) rated for handling 30'- 0 or greater
Service:
Determine:Support Spacing:
Method:
6INSULATED PIPE SUPPORT SELECTION GUIDEFRONEK GROUP
CATALOG PS-2004
WATERPIPE SUPPORTED FROM ABOVE IN CLEVIS OR 2-BOLT HANGER
D1000D2000
ASME A1000 A3000 D4000 D3000 D3100 D3200 D3300B31.1 A2000 A4000 A9000 D5000 D6000 D6100 D6200 D6300
PipeSize (Ref)1/2 7 11 12 133/4 7 12 13 151 7 14 15 17 19
1 1/2 9 16 18 19 222 10 17 18 21 29
2 1/2 11 16 18 21 243 12 17 18 20 25
3 1/2 13 16 17 19 224 14 16 18 19 225 16 15 16 19 21 406 17 14 15 16 21 408 19 13 13 15 22 3210 22 12 13 14 24 2812 23 11 12 13 22 2614 25 11 12 13 20 2316 27 10 11 12 21 26 4018 28 9 10 11 18 22 3320 30 9 9 10 16 18 28 3724 32 8 9 15 19 29 3830 33 11 13 19 26
Note:
Pipe Diameter: 8" standard weightWater20' - 0Insulated pipe support model number
MAXIMUM HANGER SUPPORT SPACING - FEET
In table 3, for 8" pipe size, find the model(s) rated for handling 20"- 0 or greatersupport spacing. In this case, Model D3000 is selected since it is capable of handling 22'-0 support spacing.The Index Sheets to Sections "A" & "D" indicate some of the differences between models. Check ProductData Sheet for description before making a final selection. In this example, if the clearance is above thesupport limited, Model D6000 might be selected (Section "D" Index & Product Data Sheet D6000).
Service:
Determine:Support Spacing:
Method:
Example: Given:
The maximum hanger spacing shown in Table 3 are derived from load ratings (see Product Data Sheets) ofPipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should beguided by the hanger spacings allowed by the applicable code or the project engineers' specifications before makingaection. Refer to the appropriate Product Data Sheets for additional information such as load rating,compensation for temperature, axial or lateral travel, or res traint, etc.
TABLE 3SERVICE:APPLICATION:
Clevis Hanger 2-Bolt Hanger
FOR VARIOUS PIPE SH IELDS, INC.PRE-INSULATED PIPE SUPPORT MODELS
7INSULATED PIPE SUPPORT SELECTION GUIDEFRONEK GROUP
CATALOG PS-2004
STEAM, GAS OR AIRPIPE SUPPORTED FROM ABOVE IN CLEVIS OR 2-BOLT HANGER
D1000D2000
ASME A1000 A3000 D4000 D3000 D3100 D3200 D3300B31.1 A2000 A4000 A9000 D5000 D6000 D6100 D6200 D6300
PipeSize (Ref)1/2 8 11 12 133/4 9 12 13 151 9 15 16 19 21
1 1/2 12 19 20 22 262 13 20 22 25 36
2 1/2 14 20 22 25 293 15 21 24 26 32
3 1/2 16 21 23 25 294 17 23 24 26 315 19 22 24 28 30 556 21 22 23 24 32 558 24 21 22 25 25 5210 26 20 22 24 40 4512 30 20 21 24 40 4514 32 21 23 25 38 55 6016 35 21 22 25 40 55 6018 37 21 22 25 40 49 6020 39 21 22 25 38 44 60 6524 42 20 21 24 40 50 60 6530 44 34 51 60 65
Note:
Pipe Diameter: 8" standard weightSteam24' - 0Insulated pipe support model number
TABLE 4SERVICE:APPLICATION:
Clevis Hanger
FOR VARIOUS PIPE SH IELDS, INC.PRE-INSULATED PIPE SUPPORT MODELS
2-Bolt Hanger
MAXIMUM HANGER SUPPORT SPACING - FEET
The maximum hanger spacing shown in Table 4 are derived from load ratings (see Product Data Sheets) oPipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided bythe hanger spacings allowed by the applicable code or the project engineers' specifications before making aselection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensationfor temperature, axial or lateral travel, or restraint, etc.
support spacing. In this case, Model A9000 is selected since it is capable of handling 25'-0 support spacing.The Index Sheets to Sections "A" & "D" indicate some of the differences between models. Check ProductData Sheet for description before making a final selection. In this example, if the clearance is above thesupport limited, Model D6000 might be selected (Section "D" Index & Product Data Sheet D6000).
Service:
Determine:Support Spacing:
Method: In table 4, for 8" pipe size, find the model(s) rated for handling 24'- 0 or greater
Example: Given:
8INSULATED PIPE SUPPORT SELECTION GUIDEFRONEK GROUP
CATALOG PS-2004
WATERPIPE SUPPORTED FROM BELOW ON PIPE ROLL
ASME A5000B31.1 A6000 A8000 A8200 A8400
PipeSize (Ref)1/2 73/4 71 7
1 1/2 92 10
2 1/2 11 15 183 12 15 17
3 1/2 13 12 164 14 15 165 16 14 156 17 12 13 248 19 9 10 1910 22 10 16 2212 23 12 23 3114 25 11 21 2816 27 10 19 2518 28 9 17 2320 30 8 15 2024 32 12 1630 33 9 12
Note:
Pipe Diameter: 8" standard weightWater18' - 0Insulated pipe support model number
The maximum hanger spacing shown in Table 5 are derived from load ratings (see Product Data Sheets) ofPipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should beguided by the hanger spacings allowed by the applicable code or the project engineers' specifications before makinga selection. Refer to the appropriate Product Data Sheets for additional information such as load rating,compensation for temperature, axial or lateral travel, or res traint, etc.
13
15121212
Service:
Determine:Support Spacing:
Method: In table 5, for 8" pipe size, find the model(s) rated for handling 18'- 0 or greatersupport spacing. In this case, Model A8200 is selected since it is capable of handling 19'-0 support spacing.The Index Sheet to Section "A" indicates some of the differences between models. Check Product DataSheet for description before making a final selection. If greater support spacings are desired, see Section "B"(Base Mounted Supports).
Example: Given:
TABLE 5SERVICE:APPLICATION:
A3000A4000
1315
Commercial1213
Light Insutrial w/Load Distribution Plate
MAXIMUM HANGER SUPPORT SPACING - FEETFOR VARIOUS PIPE SH IELDS, INC.PRE-INSULATED PIPE SUPPORT MODELS
9INSULATED PIPE SUPPORT SELECTION GUIDEFRONEK GROUP
CATALOG PS-2004
STEAM, GAS OR AIRPIPE SUPPORTED FROM BELOW ON PIPE ROLL
ASME A5000B31.1 A6000 A8000 A8200 A8400
PipeSize (Ref)1/2 83/4 91 9
1 1/2 122 13
2 1/2 14 18 223 15 19 21
3 1/2 16 19 214 17 20 235 19 20 226 21 18 20 368 24 15 17 3110 26 11 17 27 3812 30 13 23 40 5014 32 13 22 40 5016 35 13 22 39 5018 37 12 21 38 5020 39 12 20 36 4924 42 11 18 33 4430 44 9 16 29 3936 48 8 13 2442 50 11 20
Note:
Pipe Diameter: 8" standard weightSteam25' - 0Insulated pipe support model number
Light Industrial w/ Load Distribution Plate
15
Example: Given:
151617
The maximum hanger spacing shown in Table 6 are derived from load ratings (see Product Data Sheets) of Pipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided bythe hanger spacings allowed by the applicable code or the project engineers' specifications before making aselection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensationfor temperature, axial or lateral travel, or restraint, etc.
TABLE 6SERVICE:APPLICATION:
A3000
MAXIMUM HANGER SUPPORT SPACING - FEETFOR VARIOUS PIPE SH IELDS, INC.PRE-INSULATED PIPE SUPPORT MODELS
A4000
141718
Commercial1213
Service:
Determine:Support Spacing:
Method: In table 6, for 8" pipe size, find the model (s) rated for handling 25'-0 or greatersupport spacing. In this case, Model A8200 is selected since it is capable of handling 25'-0 or 31'-0 supportspacing. The Index Sheet to Section "A" indicates some of the differences between models. Check ProductData Sheet for description before making a final selection. If greater support spacings are desired, seeSection "B" (Base Mounted Supports).
FRONEK GROUP
INTRODUCTION SECTION A
INTRODUCTION
SECTION A
PRE-INSULATED PIPE SUPPORTS APPLICATION Commercial and Light Industrial Most Commercial applications are well served by Models A1000 and A2000, which are recommended for use on common 10-0 hanger space for small bore pipe sizes (see Selection Guide). However, should the need arise, because of increased hanger spacing or the manner in which the insulated support is mounted, heavier duty supports are available. As is readily seen in the Section Index on the following page, some models are meant for installation only in a clevis hanger, on a flat surface, or on a pipe roll. Other models may be installed in any two or all three mounting methods. The load ratings (see Product Data Sheets) reflect consideration for the manner in which each of these models will be mounted. Note that in the A7000 through A7400 Series and the A8000 through A8400 Series, the higher the model number, the higher the load rating. We are committed to providing the most economical and appropriate insulated pipe support to satisfy the requirements of the piping system.
If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at 713-731-0030 or 1-800-787-5914.
Please acquaint yourself with the selection guide at the front of this catalog and the section index on the page following this introduction, for assistance in determining the most
appropriate support for your application.
FRONEK GROUP
CATALOG PS-2004
PIPESIZE FLAT CLEVIS PIPE
MODEL RANGE HOT COLD SURFACE HANGER ROLL DUTY
A1000 1/2 - 24 X X X LIGHTA2000 1/2 - 24 X X X LIGHTA3000 1/2 - 24 X X X MEDIUMA3000 1/2 - 4 X X MEDIUMA4000 1/2 - 24 X X X MEDIUMA4000 1/2 - 4 X X MEDIUM
A5000 2 1/2 - 42 X X X MED/HEAVYA6000 2 1/2 - 42 X X X MED/HEAVYA7000 2 1/2 - 42 X X X HEAVYA7200 6 - 42 X X X HEAVIERA7400 10 - 30 X X X HEAVIESTA8000 2 1/2 - 42 X X X HEAVYA8200 6 - 42 X X X HEAVIERA8400 10 - 30 X X X HEAVIEST
A9000 1/2 - 24 X X X HEAVY
PRE-INSULATED PIPE SUPPORTSCOMMERCIAL AND LIGHT INDUSTRIAL
PRIMARYAPPLICATION
INSTALLED ON
SECTION A INDEX
TO ORDER, specify:1. Quantity 202. Pipe Size & Type 2 IPS3. Insulation Thickness 2-1/24. Model Number A1000
EXAMPLE: (20) 2 x 2-1/2 A1000
FRONEK GROUP
CATALOG PS-2004
MODEL A1000 Insulated Pipe Support Regular Duty
A1
Features:
Compact Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Minimizes heat-loss and/or condensation Copper tubing sizes available Other I.D.'s and/or O.D.'s available on request Clamps available (see G-series) Performance Test Results on File: Available upon request.
Material Data:
A1000: Applicable PSI spec. doc.: No. 205.Insulation: Calcium Silicate asbestos-free,
treated with water repellant.Jackets: Galvanized Steel ASTM A-527.Glue: Industrial contact adhesive
Formal Submittal Sheets available
Application:
Model A1000 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces Band, ring or clevis pipe hanger
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
Hardware sold separately
A B A B A B A B A B A B A B A B A B4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 246 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 246 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 206 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 1612 16 12 16 12 16 12 16 12 16 12 1618 16 18 16 18 16 18 16 18 16 18 16
200
TABLE III1200
0.750.500.30
7501000
350450
Mult.
CopperTubing
Size O.D.
250
5501000750
1200
300
Oper.Temp.
oF
To develop maximum load rating, use band, ring or clevis hanger with manufacturer'sload rating equal to or greater than values shown in Table I.
To develop maximum load rating, width of support surface should be at least 1/2 ofdimension "A" in Table II.
The load ratings represent average values obtained in accordance with acceptedmethods and are subject to normal manufacturing variations. Dimensions and ratingsare subject to change without notice.
Factor"F"
500 0.90
MAXIMUM LOAD
Pipe On Flat In Clevis
1 1/2Iron
Contact factory for other dimensions, temperatures, and loads.
Available in all insulation thicknesses.Insulation Thickness
2 2 1/2
To obtain load ratings for operating temperatures of 500 F and higher, multiply loadrating by factor "F" in Table III.
1/2 3/4 1
8 1/8 -10 1/812 1/8
5/8 - 1 5/8
4
2 1/82 5/8 - 4 1/8
550350
6580110140
150180225270
400450
3
8
56
141618
2420
160018002000
3 1/2
TABLE I750
600625675
TABLE II "B" = gauge of sheet metal jacket
PipeSize
1/2 - 1 1/2
6 - 78 - 1012 - 18
52 1/2 - 4
3
2 1/2
2
20 - 24
5 1/86 1/8
2300
10
1400575
500
Note: For higher load ratings, see A3000, A9000.
12
3 1/24
70100125
1 1/41 1/2
2
1
1/24060
Size
3/4
RATING (LBS)
Hanger(b) (c)
40
Surface(a) (c)
3545
A2
MODEL A2000 Insulated Pipe Support Regular Duty w/Extended Insulation
Application:
Model A2000 is designed for use on: Cold Water Chilled Water
Intended for installation on: Flat Surfaces Band, ring or clevis pipe hangers
Temperature Range: F to +1200F +40Note: Up to 1700F available upon request.
Features:
Compact Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Minimizes heat-loss and/or condensation Calcium silicate insulation extends 1'' beyond the galvanized sheet metal jacket providing for an easier vapor barrier joint with the pipe insulation Copper tubing sizes available Other I.D.'s and/or O.D.'s available on request Clamps available see (G-series) Performance Test Results on File: Available upon request.
Material Data:
A2000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive
Formal Submittal Sheets available
FRONEK GROUP
CATALOG PS-2004
Hardware sold separately
A B A B A B A B A B A B A B A B A B6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 246 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 246 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 206 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 1612 16 12 16 12 16 12 16 12 16 12 1618 16 18 16 18 16 18 16 18 16 18 16
0.750.50
TABLE III1200 0.30
FactorTemp.
The load ratings represent average values obtained in accordance with acceptedmethods and are subject to normal manufacturing variations. Dimensions and ratingsare subject to change without notice.
oF "F"
Note: For higher load ratings, see A4000, A9000.
5007501000
0.90
10
3 1/2
1214
4568
To obtain load ratings for operating temperatures of 500F and higher, multiply loadrating by factor "F" in Table III.
182024
To develop maximum load rating, width of support surface should be at least 1/2 ofdimension "A" in Table II.
To develop maximum load rating, use band, ring or clevis hanger with manufacturer'sload rating equal to or greater than values shown in Table I.
Contact factory for other dimensions, temperatures, and loads.
Available in all insulation thicknesses.
16
2000675
140016001800625
575
1 1/22
2 1/23
1/23/41
1 1/4
12 1/8
750
5/8 - 15/8
CopperTubing
Size O.D.4
2300
6 1/88 1/8 -10 1/8
110140200250
450
7501000
550
70
600
500
150
400450
550
MAXIMUM LOAD
On Flat
1200
Pipe
225270
100125
300350
3 1/2
RATING (LBS)In Clevis
40456580
354060
Oper. Mult.
2 2 1/2Insulation ThicknessIron
Pipe
180
350
TABLE II "B" = gauge of sheet metal jacket
3/4 1 1 1/2
20 - 24
56 - 7
2 1/82 5/8 - 4 1/8
5 1/8
1/2 - 1 1/2
1/2
8 - 10
Size
12 - 18
Size
TABLE I
Hanger(b) (c)
Surface(a) (c)
2 1/2 - 4
3
2
MODEL A3000 Insulated Pipe Support
A3
Extra HeavyBottom Jacket
Features:
Compact Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Minimizes heat-loss and/or condensation Double thickness bottom jacket for added structural strength and abrasive wear resistance Copper tubing sizes available Other I.D.'s and/or O.D.'s available on request Clamps available (see G-series) Performance Test Results on File: Available upon request.
Material Data:
A3000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A3000 is designed for use on: Hot Water Steam Cold Water Air Chilled Water Gas Dual Temperature Vacuum
Intended for installation on: Flat Surfaces . Pipe Rolls Band, ring or clevis pipe hanger
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
PipeSize
1/23/41
1 1/41 1/2
2Hardware sold separately 2 1/2
33 1/2
456810121416182024
A B A B A B A B A B A B A B A B A B4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 246 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 246 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 206 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 1612 16 12 16 12 16 12 16 12 16 12 1618 16 18 16 18 16 18 16 18 16 18 16
TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket)
12 - 18 12 1/820 - 24
6 - 7 6 1/88 - 10 8 1/8 -10 1/8
2 1/2 - 4 2 5/8 - 4 1/85 5 1/8
1/2 - 1 1/2 5/8 -1 5/82 2 1/8
3 1/2 4 TubingSize Size O.D.
1 1/2 2 2 1/2 3Pipe
To develop maximum load rating, use band, ring or clevis hanger with manufacturer'sload rating equal to or greater than values shown in Table I. TABLE I
1/2 3/4 1
Contact factory for other dimensions, temperatures, loads.
Available in all insulation thicknesses.To obtain load ratings for operating temperatures of 500oF and higher, multiply loadrating by factor "F" in Table III.
Iron Insulation Thickness Copper
700 2100775 2400
Divide "A" in Table II by 6 to find maximum allowable travel on pipe roll (+/- fromcentered position). 650 1900
600 1500625 A5000 1700
To develop maximum load rating, width of support surface should be at least 1/2 ofdimension "A" in Table II. 575 1300
500 800525 See 1100
300 270 375The load ratings represent average values obtained in accordance with acceptedmethods and are subject to normal manufacturing variations. Dimensions and ratingsare subject to change without notice.
400 475450 575
Note: For higher load ratings, see A5000, A9000.250 225 325200 180
155
TABLE III165 150 2201200 0.30140 125
275
120750 0.7580
1000 0.50110 100
50
500 0.9065 60 70
70 90
(b) (d) (c) (d)
Temp. Factor40 35 45Oper. Mult.
40
(a) (d)
oF "F"45
Surface Roll or ClevisHanger
MAXIMUM LOADRATING (LBS)
On Flat On Pipe In Ring
A4
MODEL A4000 Insulated Pipe Support Extra Heavy BottomJacket w/ext. Insulation
Material Data:
A4000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Features: Compact Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Double thickness bottom jacket for added structural strength and abrasive wear
Minimizes heat-loss and/or condensation Calcium silicate insulation extends 1'' beyond the galvanized sheet metal jacket providing for an easier vapor barrier joint with the pipe Copper tubing sizes available Other I.D.'s and/or O.D.'s available on request Clamps available (see G-series)
Performance Test Results on File: Available upon request.
resistance
Application:
Model A4000 is designed for use on: Cold Water Chilled Water
Intended for installation on: Flat Surfaces . Pipe Rolls Band, ring or clevis pipe hanger
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
PipeSize
1/23/41
1 1/41 1/2
2Hardware sold separately 2 1/2
33 1/2
456810121416
182024
A B A B A B A B A B A B A B A B A B6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 246 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 246 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 206 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 1612 16 12 16 12 16 12 16 12 16 12 1618 16 18 16 18 16 18 16 18 16 18 16
3540
12 1/8
5/8-1 5/8
2 5/8 - 4 1/8
6 1/88 1/8 -10 1/8
See
270
6070100125
80110140165
Surface
404565
On Pipe In Ring
(c) (d)
or ClevisRoll
Temp.Oper. Mult.
Factor
12 - 18
2 1/2 - 4
TABLE III
2 2 1/2Iron PipeSize
1/2
21/2 - 1 1/2
TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket)
3/4 1 1 1/2
20 - 24
56 - 78 - 10
220275200
250
150180225 325
1200
0.900.750.500.30
500"F"
7501000
oF 7090120155
MAXIMUM LOAD
On Flat
375475
45
Hanger(b) (d)
RATING (LBS)
(a) (d)
50
575
3 1/2
1700190021002400
4Insulation Thickness
700
300400450
650
500
625
525575600
5 1/8
CopperTubing
Size O.D.
1500
775
2 1/8
TABLE I
3
A6000
Note: For higher load ratings, see A6000, A9000
To obtain load ratings for operating temperatures of 500F and higher, multiply loadrating by factor "F" in Table III.
Contact factory for other dimensions, temperatures, loads.
Available in all insulation thicknesses.
The load ratings represent average values obtained in accordance with acceptedmethods and are subject to normal manufacturing variations. Dimensions and ratingsare subject to change without notice.
To develop maximum load rating, width of support surface should be at least 1/2 ofdimension "A" in Table II.
Divide "A" in Table II by 6 to find maximum allowable travel on pipe roll (+/- fromcentered position).
To develop maximum load rating use band, ring or clevis hanger with manufacturer'sload rating equal to or greater than values shown in Table I.
80011001300
A5
MODEL A5000 Insulated Pipe Support With loaddistribution plate
Features:
Compact Easy Installation Eliminates welding to pipe Copper tubing sizes available Overlapping galvanized sheet metal jacket Minimizes heat-loss and/or condensation Load distribution plate integral with bottom jacket Other I.D.'s and/or O.D.'s available upon request
Performance Test Results on File: Available upon request.
Material Data:
A5000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Load distribution Plate: Carbon steel
ASTM A-36 Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A5000 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces Pipe Rolls
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 1/49 6 1/49 6 1/49 6 1/49 6 1/49 6 1/49 6 1/49 6 1/412 9 3/812 9 3/812 9 1/212 9 1/212 9 1/212 9 3/412 9 3/412 9 3/412 9 3/4
Hardware sold separatelyNote: For higher load ratings, see A7000
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturingvariations. Dimensions and ratings are subject to change without notice. Contact fac tory for current information.
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.To obtain load ratings for operating temperatures of 500 oF and higher, multiply maximum load rating by factor "F" in Table II.
Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses.1200 0.30
TABLE II
750 0.751000 0.50
1350 3500 0.90 TABLE I
oF "F" 42 1500
1350 3Temp. Factor 36 1500 1350 3Oper. Mult. 30 1500
24 1400 1250 320 1300 1150 318 1200 1075 316 1100 975 314 1000 900 312 925 825 310 650 575 28 625 550 26 500 450 25 450 400 24 350 315 2
3 1/2 300 270 23 250 225 2
2 1/2 200 180 2
Pipe Roll(a) (b) (b) +/-
Size Surface Roll on Pipe On Flat On Pipe (inches)
MAXIMUM LOAD Max. AxialRATING (LBS) Travel
With load distributionplate w/ext. InsulationMODEL A6000 Insulated Pipe Support
A6
Features:
Compact Easy Installation Eliminates welding to pipe Copper tubing sizes available Overlapping galvanized sheet metal jacket Minimizes heat-loss and/or condensation Load distribution plate integral with bottom jacket Calcium silicate insulation extends 1'' beyond the galvanized sheet metal jacket providing for an easier vapor barrier joint with the pipe Other I.D.'s and/or O.D.'s available on request
Performance Test Results on File: Available upon request.
Material Data:
A6000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant.Jackets: Galvanized Steel ASTM A-527.Load distribution Plate: Carbon steel
ASTM A-36 Coating : Primer coated or hot-dip galvanized.
Other coatings available upon request.Glue: Industrial contact adhesive
Formal Submittal Sheets available
Application:
Model A6000 is designed for use on: Cold Water Chilled Water
Intended for installation on: Flat Surfaces Pipe Rolls
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 1/49 6 1/49 6 1/49 6 1/49 6 1/49 6 1/49 6 1/49 6 1/412 9 3/812 9 3/812 9 1/212 9 1/212 9 1/212 9 3/412 9 3/412 9 3/412 9 3/4
Hardware sold separately
MAXIMUM LOAD Max. AxialRATING (LBS) Travel
Pipe On Flat On Pipe (inches)Size Surface Roll on
Pipe Roll(a) (b) (b) +/-
2 1/2 200 180 23 250 225 2
3 1/2 300 270 24 350 315 25 450 400 26 500 450 28 625 550 210 650 575 212 925 825 314 1000 900 316 1100 975 318 1200 1075 3
1250 320 1300 1150 3
30 150024 1400
1350 3Temp. Factor 36 1500 1350 3Oper. Mult.
1350 3500 0.90 TABLE I
oF "F" 42 1500
750 0.751000 0.50 Contact factory for other dimensions, temperatures, and loads . Available
in all insulation thicknesses.1200 0.30TABLE II
Note: For higher load ratings, see A7000
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturingvariations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.To obtain load ratings for operating temperatures of 500 oF and higher, multiply maximum load rating by factor "F" in Table II.
A7
MODEL A7000 Insulated Pipe Support Heavy Duty withload bearing plate
Features:
Compact Easy Installation Eliminates welding to pipe Copper tubing sizes available Minimizes heat-loss and/or condensation Insulating structural inserts for load transfer Overlapping galvanized sheet metal jacket Other I.D.'s and/or O.D.'s available on request Load distribution plate integral with bottom jacket
Performance Test Results on File: Available upon request.
Material Data:
A7000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Structural Inserts: High-density calcium silicate asbestos-free, treated with water
Load Distribution Plate: Carbon steel ASTM A-36 Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
repellant.
Application:
Model A7000 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces Pipe rolls, see A8200 Clevis hangers, see A9000
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
A B C
6 3 1/46 3 1/46 3 1/46 3 1/46 3 1/46 3 1/46 3 1/49 6 3/89 6 3/89 6 3/89 6 1/29 6 1/29 6 1/29 6 3/49 6 3/49 6 3/49 6 3/4
Surface
350
Pipe (LBS)
(a)
3
TABLE I
MAXIMUMLOAD RTG.
2 1/2 250300
1850
8
3 1/2
2500
6
45
2000
400
101214 1650
500
16182024
25002500
3036
On FlatSize
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normalmanufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
5507008751600
42
21002300
To develop maximum load rating, width of support sur face should be at least 1/2 of dimension "B" in Table I.
Contact factory for other dimensions, temperatures, and loads. Available in all
insulation thicknesses.
Note: For higher load ratings, see A7200
A8
MODEL A7200 Insulated Pipe Support Heavy Duty withload bearing plate
Features:
Compact Easy Installation Eliminates welding to pipe Copper tubing sizes available Minimizes heat-loss and/or condensation Insulating structural inserts for load transfer Overlapping galvanized sheet metal jacket Other I.D.'s and/or O.D.'s available on request Load distribution plate integral with bottom jacket
Performance Test Results on File: Available upon request
Material Data:
A7200: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free,
treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Structural Inserts: High-density calciumsilicate asbestos-free, treated with water
Load distribution Plate: Carbon steel ASTM A-36 Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
repellant.
Application:
Model A7200 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Chilled Water Dual Temperature
Intended for installation on: Flat Surfaces Pipe rolls, see A8200 Clevis hangers, see A9000
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 1/29 6 1/29 6 5/89 6 5/89 6 5/89 6 3/49 6 3/49 6 3/49 6 19 6 19 6 19 6 1
MAXIMUMLOAD RTG.
Pipe (LBS)Size On Flat
Surface(a)
6 10008 125010 155012 225014 278016 330018 360020 380024 410030 4500
Contact factory for other dimensions, temperatures, and loads. Available in all
insulation thicknesses.
TABLE I
36 450042 4500
Note: For higher load ratings, see A7400, B1100
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normalmanufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
To develop maximum load rating, width of support sur face should be at least 1/2 of dimension "B" in Table I.
A9
MODEL A7400 Insulated Pipe Support Heavy Duty withload bearing plate
Features:
Compact Easy Installation Eliminates welding to pipe Copper tubing sizes available Minimizes heat-loss and/or condensation Insulating structural inserts for load transfer Overlapping galvanized sheet metal jacket Other I.D.'s and/or O.D.'s available on request Load distribution plate integral with bottom jacket
Performance Test Results on File: Available upon request.
Material Data:
A7400: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
Load distribution Plate: Carbon steel ASTM A-36 Coating : Primer coated or hot-dip galvanized. Other coatings available upon request. Glue: Industrial contact adhesive
Formal Submittal Sheets available
repellant.
Application:
Model A7400 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Chilled Water Dual Temperature
Intended for installation on: Flat Surfaces Pipe rolls, see A8400 Clevis hangers, see A9000
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 3/49 6 3/49 6 3/49 6 19 6 19 6 19 6 19 6 1
MAXIMUMLOAD RTG.
Pipe (LBS)Size On Flat
Surface(a)
10 210012 340014 390016 440018 480020 510024 550030 5500
Table I
Contact factory for other dimensions, temperatures, and loads. Available in all
insulation thicknesses.
Note: For higher load ratings, see B1200
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normalmanufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
To develop maximum load rating, width of support sur face should be at least 1/2 of dimension "B" in Table I.
A10
MODEL A8000 Insulated Pipe Support Heavy Duty withload bearing plate
Features:
Compact Easy Installation Eliminates welding to pipe Copper tubing sizes available Minimizes heat-loss and/or condensation Insulating structural inserts for load transfer Overlapping galvanized sheet metal jacket Other I.D.'s and/or O.D.'s available on request Load distribution plate integral with bottom jacket
Performance Test Results on File: Available upon request.
Material Data:
A8000: Applicable PSI spec. doc. No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Structural Inserts: High-density calcium silicate asbestos-free, treated with water repellant. Load Distribution Plate: Carbon steel ASTM A-36 Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A8000 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Chilled Water Dual Temperature
Intended for installation on: Flat Surfaces Pipe rolls, see A7000 Clevis hangers, see A9000
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 1/49 6 1/49 6 1/49 6 1/49 6 1/49 6 1/49 6 1/412 9 3/812 9 3/812 9 3/812 9 1/212 9 1/212 9 1/212 9 3/412 9 3/412 9 3/412 9 3/4
Hardware sold separately
MAXIMUM Max. AxialLOAD RTG. Travel
Pipe (LBS) (Inches)Size On on
Pipe Pipe RollRoll
2 1/2 225 23 250 2
3 1/2 300 24 350 25 450 26 500 28 625 210 875 412 1400 414 1475 416 1650 418 1800 420 1875 424 2050 4
436 2250 430 2250
4TABLE I
42 2250
Contact factory for other dimensions, temperatures , and loads. Available in all insulation thicknesses.
Note: For higher load ratings, see A8200
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normalmanufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
A11
MODEL A8200 Insulated Pipe Support Heavy Duty withload bearing plate
Features:
Compact Easy Installation Eliminates welding to pipe Copper tubing sizes available Minimizes heat-loss and/or condensation Insulating structural inserts for load transfer Overlapping galvanized sheet metal jacket Other I.D.'s and/or O.D.'s available on request Load distribution plate integral with bottom jacket
Performance Test Results on File: Available upon request.
Material Data:
A8200: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Structural Inserts: High-density calcium silicate asbestos-free, treated with water repellant. Load distribution Plate: Carbon steel ASTM A-36 Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A8200 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Chilled Water Dual Temperature
Intended for installation on: Pipe rolls Flat surface, see A7200 Clevis hangers, see A9000
Note: Up to 1700F available upon request.Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
A B C
12 9 1/212 9 1/212 9 5/812 9 5/812 9 5/812 9 3/412 9 3/412 9 3/412 9 112 9 112 9 112 9 1
Hardware sold separatelyNote: For higher load ratings, see A8400, B1100
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normalmanufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
TABLE I
Contact factory for other dimensions, temperatures , and loads. Available in all insulation thicknesses.
36 4050 342 4050 3
24 3675 330 4050 3
18 3200 320 3375 3
14 2650 316 2950 3
10 1375 312 2550 3
6 900 38 1125 3
Pipe Pipe RollRoll
Pipe (LBS) (Inches)Size On on
MAXIMUM Max. AxialLOAD RTG. Travel
A12
MODEL A8400 Insulated Pipe Support Heavy Duty withload bearing plate
Features:
Compact Easy Installation Eliminates welding to pipe Copper tubing sizes available Minimizes heat-loss and/or condensation Insulating structural inserts for load transfer Overlapping galvanized sheet metal jacket Other I.D.'s and/or O.D.'s Available on request Load distribution plate integral with bottom jacket
Performance Test Results on File: Available upon request.
Material Data:
A8400: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Structural Inserts: High-density calcium silicate asbestos-free, treated with water
Load distribution Plate: Carbon steel ASTM A-36 Coating : Primer coated or hot-dip galvanized. Other coatings Available upon request. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
repellant.
Application:
Model A8400 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Chilled Water Dual Temperature
Intended for installation on: Pipe rolls Flat surface, see A7400 Clevis hangers, see A9000
Note: Up to 1700F available upon request. Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
A B C
12 9 112 9 112 9 112 9 112 9 112 9 112 9 112 9 1
Hardware sold separately
MAXIMUM Max. AxialLOAD RTG. Travel
Pipe (LBS) (Inches)Size On on
Pipe Pipe RollRoll
10 1875 2 1/412 3400 2 1/414 3500 2 1/416 3950 2 1/418 4300 2 1/420 4550 2 1/424 4950 2 1/430 5450 2 1/4
TABLE I
Contact factory for other dimensions, temperatures, and loads. Available in all
insulation thicknesses.
Note: For higher load ratings, see B1200
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normalmanufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
A13
MODEL A9000 Insulated Pipe Support Heavy Duty for usewith rod hangers
Features:
Compact Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Minimizes heat-loss and/or condensation Insulating structural inserts for load transfer Copper Tubing available Other I.D.'s and/or O.D.'s available on request
Performance Test Results on File: Available upon request.
Material Data:
A9000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Structural Inserts : High-density calcium silicate asbestos-free, treated with water repellant. Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A9000 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Chilled Water Dual Temperature
Intended for installation on: Band, ring or clevis pipe hangers Flat surfaces, see A7000 Pipe rolls, see A8000
Note: Up to 1700F available upon request. Temperature Range: F to +1200F +40
FRONEK GROUP
CATALOG PS-2004
Hardware sold separately
A B A B A B A B A B A B A B A B A B4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 246 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 246 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 206 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 1612 16 12 16 12 16 12 16 12 16 12 1618 16 18 16 18 16 18 16 18 16 18 1620 - 24
TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket)
8 - 10 8 1/8 -10 1/812 - 18 12 1/8
5 5 1/86 - 7 6 1/8
5/8-1 5/82 2 1/8
2 1/2 - 4 2 5/8 - 4 1/8
1/2 3/4 1
1/2 - 1 1/2
3 1/2 4 TubingSize Size O.D.
1 1/2 2 2 1/2 3Pipe
TABLE I
Iron Insulation Thickness Copper
Contact factory for other dimensions, temperatures, loads.
Available in all insulation thicknesses.To develop maximum load rating use band, ring or clevis hanger with manufacturer's loadrating equal to or greater than values shown in Table I.
20 240024 2750
Note: For higher load ratings, see D1000, D3000
The load ratings represent average values obtained in accordance with accepted methodsand are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice.
6 6008 900
1618
12001450
4 4005 550
3 3003 1/2 350
2 1752 1/2 250
1 1/4 1001 1/2 130
1/2 505580
3/41
or ClevisHanger
(a)
Size
MAXIMUM
(LBS)In RingPipe
LOAD RTG.
165019002150
101214
FRONEK GROUP
INTRODUCTION SECTION B
INTRODUCTION
SECTION B
PRE-INSULATED PIPE SUPPORTS - Base Mounted APPLICATION Heavy Industrial and Large HVAC Distribution Systems Features:
Accommodation of thermal movement Provision or lateral guide or restraint Minimization of side friction loads Wide range of maximum load requirements for each pipe size
In each model number series (for example: B1000 through B1300 Series), the higher the model number, the higher the load rating. Models B1000 - B1300 Sliding supports free to travel axially and laterally. Models B2000 - B2300 Same as B1000 - B1300 except can accommodate greater axial travel. Models B3000 - B3300 Sliding supports with lateral guides. Models B4000 - B4300 Same as B3000 - B3300 except can accommodate greater axial travel. Models B5000 - B5300 Same as B1000 - B1300 except can accommodate greater lateral travel. Models B6000 - B6300 Same as B2000 - B2300 except can accommodate greater lateral travel. Models B7000 - B7300 Same as B3000 - B3300 except with reduced vertical load ratings to
allow greater lateral loads. Minimum side friction is assured by the addition of lateral slide pads.
Models B8000 - B8300 Same as B4000 - B4300 except with reduced vertical load ratings to
allow greater lateral loads. Minimum side friction is assured by the addition of lateral slide pads.
To meet special thermal movement requirements, Pipe Shields Inc. has provided supports that have accommodated axial travels in excess of five (5) feet. By modifying our standard pipe support concept with combinations of structural insulation materials, steel base and strap design, and slide plate configuration, we can readily and economically respond to virtually any pipe support requirement.
If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at 713-731-0030 or 1-800-787-5914.
Please acquaint yourself with the selection guide at the front of this catalog and the section index on the page following this introduction, for assistance in determining the most
appropriate support for your application.
FRONEK GROUP
CATALOG PS-2004
PIPESIZE LATERAL
MODEL RANGE AXIAL LATERAL GUIDE DUTY
B1000 1/2 - 42 1.5 1.5 NO MEDIUMB1100 1/2 - 42 1.5 1.5 NO HEAVYB1200 1/2 - 42 1.5 1.5 NO HEAVIERB1300 1/2 - 42 1.5 1.5 NO HEAVIEST
B2000 1/2 - 42 4.5 1.5 NO MEDIUMB2100 1/2 - 42 4.5 1.5 NO HEAVYB2200 1/2 - 42 4.5 1.5 NO HEAVIERB2300 1/2 - 42 4.5 1.5 NO HEAVIEST
B3000 1/2 - 42 1.5 0 YES MEDIUMB3100 1/2 - 42 1.5 0 YES HEAVYB3200 1/2 - 42 1.5 0 YES HEAVIERB3300 1/2 - 42 1.5 0 YES HEAVIEST
B4000 1/2 - 42 4.5 0 YES MEDIUMB4100 1/2 - 42 4.5 0 YES HEAVYB4200 1/2 - 42 4.5 0 YES HEAVIERB4300 1/2 - 42 4.5 0 YES HEAVIEST
PRE-INSULATED PIPE SUPPORTSHEAVY INDUSTRIAL - BASE MOUNTED
TRAVEL(INCHES) +/-
SECTION B INDEXFRONEK GROUP
CATALOG PS-2004
PIPESIZE LATERAL
MODEL RANGE AXIAL LATERAL GUIDE DUTY
B5000 1/2 - 42 1.5 1.5 - 4.5 NO MEDIUMB5100 1/2 - 42 1.5 1.5 - 4.5 NO HEAVYB5200 1/2 - 42 1.5 1.5 - 4.5 NO HEAVIERB5300 1/2 - 42 1.5 1.5 - 4.5 NO HEAVIEST
B6000 1/2 - 42 4.5 1.5 - 4.5 NO MEDIUMB6100 1/2 - 42 4.5 1.5 - 4.5 NO HEAVYB6200 1/2 - 42 4.5 1.5 - 4.5 NO HEAVIERB6300 1/2 - 42 4.5 1.5 - 4.5 NO HEAVIEST
B7000 1/2 - 42 1.5 0 W/SLIDE PADS MEDIUMB7100 1/2 - 42 1.5 0 W/SLIDE PADS HEAVYB7200 1/2 - 42 1.5 0 W/SLIDE PADS HEAVIERB7300 1/2 - 42 1.5 0 W/SLIDE PADS HEAVIEST
B8000 1/2 - 42 4.5 0 W/SLIDE PADS MEDIUMB8100 1/2 - 42 4.5 0 W/SLIDE PADS HEAVYB8200 1/2 - 42 4.5 0 W/SLIDE PADS HEAVIERB8300 1/2 - 42 4.5 0 W/SLIDE PADS HEAVIEST
PRE-INSULATED PIPE SUPPORTSHEAVY INDUSTRIAL - BASE MOUNTED
TRAVEL(INCHES) +/-
SECTION B INDEXFRONEK GROUP
CATALOG PS-2004
SECTION B INDEX
TO ORDER, specify:1. Quantity 202. Pipe Size & Type 18 IPS3. Insulation Thickness 24. Model Number B1000
EXAMPLE: (20) 18 x 2 B1000
FRONEK GROUP
CATALOG PS-2004
PIPESIZE 3 1/2 4 1/2 5 1/2 6 1/2
3 6 6 8 83 1/2 6 6 8 8
4 6 6 8 85 6 6 8 86 6 6 8 88 6 8 8 1010 6 8 8 1012 6 8 8 1014 6 8 8 1016 6 8 8 1018 6 8 8 1020 6 8 8 1024 6 8 8 1030 8 8 10 1036 8 8 10 1042 8 8 10 10
The Table above provides Bottom-of-Pipe to Top-of Steel dimensions ("B" dimensions) for3 1/2", 4 1/2", 5 1/2" and 6 1/2 " insulation thicknesses. Check with your salesperson if yourequire a "B" dimension other than those shown in this table.
INSULATION THICKNESS
THE FOLLOWING TABLE ILLUSTRATESBOTTOM-OF-PIPE TO TOP-OF STEEL DIMENSIONS
(DIMENSION "B") FOR "B" MODEL PIPE SUPPORTS AND "C" MODEL PIPE ANCHORSFOR INTERMEDIATE INSULATION THICKNESS
B1
Application:
Model B1000 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces
Temperature Range: +40F to +1200FNote: Up to 1700 F available upon request.
Features:
All pipe sizes Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Insulating structural inserts for load transfer Stainless steel to UHMW polyethylene slide Other I.D.'s and/or O.D.'s available on request Factory mounted polyethylene slide pad on steel mounting plate
Performance Test Results on File: Available upon request.
Material Data:
B1000: Applicable PSI spec. doc.: No. 209. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. Steel Straps/Base: Carbon Steel ASTM A-36. Fasteners: ASTM A-307 plated. Slide Pad: UHMW Polythylene (Teflon Optional). Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets available.
Heavy Duty,Base Mounted MODEL B1000 Sliding Insulated Pipe Support FRONEK GROUP
CATALOG PS-2004
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.Dimensions and ratings are subject to change without notice.Note: For higher load ratings, see: B1100 - For greater axial travel, see: B2000 - For lateral restraint, see: B3000 - For lateral travel, see: B5000
Pipe Vert.Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 140 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 175 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.1251 225 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 325 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.252 375 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 460 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.53 530 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.6254 840 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.6255 1050 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.8756 1275 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.8758 1700 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.12510 2000 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.12512 2200 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.12514 2500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.12516 2900 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.37518 3200 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.37520 3400 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.37524 3600 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.37530 4700 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.62536 5500 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.12542 6200 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B2
Heavy Duty,Base Mounted MODEL B1100 Sliding Insulated Pipe Support
Application:
Model B1100 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces
Temperature Range: +40F to +1200FNote: Up to 1700 F available upon request.
Features:
All pipe sizes Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Insulating structural inserts for load transfer Stainless steel to UHMW polyethylene slide Other I.D.'s and/or O.D.'s available on request Factory mounted polyethylene slide pad on steel mounting plate
Performance Test Results on File: Available upon request.
Material Data:
B1100: Applicable PSI spec. doc.: No. 209. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. Steel Straps/Base: Carbon Steel ASTM A-36. Fasteners: ASTM A-307 plated. Slide Pad: UHMW Polythylene (Teflon Optional). Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.Dimensions and ratings are subject to change without notice.Note: For higher load ratings, see: B1200 - For greater axial travel, see: B2100 - For lateral restraint, see: B3100 - For lateral travel, see: B5100
Pipe Vert.Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 280 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 350 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.251 450 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 650 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.252 750 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 920 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.53 1060 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.6254 1680 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.6255 2100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.8756 2550 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.8758 3400 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.12510 4000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.12512 4400 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.12514 5000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.12516 5800 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.37518 6400 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.37520 6800 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.37524 7200 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.37530 9400 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.62536 11000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.12542 12400 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B3
Heavy Duty,Base Mounted MODEL B1200 Sliding Insulated Pipe Support
Application:
Model B1200 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces
Temperature Range: +40F to +1200FNote: Up to 1700 F available upon request.
Features:
All pipe sizes Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Insulating structural inserts for load transfer Stainless steel to UHMW polyethylene slide Other I.D.'s and/or O.D.'s available on request Factory mounted polyethylene slide pad on steel mounting plate
Performance Test Results on File: Available upon request.
Material Data:
B1200: Applicable PSI spec. doc.: No. 209. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. Steel Straps/Base: Carbon Steel ASTM A-36. Fasteners: ASTM A-307 plated. Slide Pad: UHMW Polyethylene (Teflon Optional). Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.Dimensions and ratings are subject to change without notice.Note: For higher load ratings, see: B1300 - For greater axial travel, see: B2200 - For lateral restraint, see: B3200 - For lateral travel, see: B5200
Pipe Vert.Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 400 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 500 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.251 650 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 950 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.252 1100 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1350 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.53 1600 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.6254 2500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.6255 3100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.8756 3800 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.8758 5100 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.12510 6000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.12512 6600 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.12514 7500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.12516 8700 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.37518 9600 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.37520 10200 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.37524 10800 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.37530 14100 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.62536 16500 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.12542 18600 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B4
Heavy Duty,Base Mounted MODEL B1300 Sliding Insulated Pipe Support
Application:
Model B1300 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces
Temperature Range: +40F to +1200FNote: Up to 1700 F available upon request.
Features:
All pipe sizes Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Insulating structural inserts for load transfer Stainless steel to UHMW polyethylene slide Other I.D.'s and/or O.D.'s available on request Factory mounted polyethylene slide pad on steel mounting plate
Performance Test Results on File: Available upon request.
Material Data:
B1300: Applicable PSI spec. doc.: No. 209. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. Steel Straps/Base: Carbon Steel ASTM A-36. Fasteners: ASTM A-307 plated. Slide Pad: UHMW Polyethylene (Teflon Optional). Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.Dimensions and ratings are subject to change without notice.Note: For greater axial travel, see: B2300 - For lateral restraint, see: B3300 - For lateral travel, see: B5300
Pipe Vert.Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 550 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 3/4 700 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.251 900 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 1300 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.252 1500 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1800 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.6253 2100 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.6254 3350 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.6255 4200 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.8756 5100 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.8758 6800 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.12510 8000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.12512 8800 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.12514 10000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.12516 11600 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.37518 12800 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.37520 13600 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.37524 14400 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.37530 18800 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.62536 22000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.12542 24800 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B5
Heavy Duty,Base Mounted MODEL B2000 Sliding Insulated Pipe Support
Application:
Model B2000 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces
Temperature Range: +40F to +1200FNote: Up to 1700 F available upon request.
Features:
All pipe sizes Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Insulating structural inserts for load transfer Stainless steel to UHMW polyethylene slide Other I.D.'s and/or O.D.'s available on request Factory mounted polyethylene slide pad on steel mounting plate
Performance Test Results on File: Available upon request.
Material Data:
B2000: Applicable PSI spec. doc.: No. 209. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. Steel Straps/Base: Carbon Steel ASTM A-36. Fasteners: ASTM A-307 plated. Slide Pad: UHMW Polyethylene (Teflon Optional). Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.Dimensions and ratings are subject to change without notice.Note: For higher load ratings, see: B2100 - For lesser axial travel, see: B1000 - For lateral restraint, see: B4000 - For lateral travel, see: B6000
Pipe Vert.Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 140 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 175 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.1251 225 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 325 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.252 375 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 460 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.53 530 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.6254 840 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.6255 1050 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.8756 1275 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.8758 1700 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.12510 2000 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.12512 2200 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.12514 2500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.12516 2900 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.37518 3200 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.37520 3400 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.37524 3600 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.37530 4700 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.62536 5500 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.12542 6200 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B6
Heavy Duty,Base Mounted MODEL B2100 Sliding Insulated Pipe Support
Application:
Model B2100 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces
Temperature Range: +40F to +1200FNote: Up to 1700 F available upon request.
Features:
All pipe sizes Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Insulating structural inserts for load transfer Stainless steel to UHMW polyethylene slide Other I.D.'s and/or O.D.'s available on request Factory mounted polyethylene slide pad on steel mounting plate
Performance Test Results on File: Available upon request.
Material Data:
B2100: Applicable PSI spec. doc.: No. 209. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. Steel Straps/Base: Carbon Steel ASTM A-36. Fasteners: ASTM A-307 plated. Slide Pad: UHMW Polyethylene (Teflon Optional). Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.Dimensions and ratings are subject to change without notice.Note: For higher load ratings, see: B2200 - For lesser axial travel, see: B1100 - For lateral restraint, see: B4100 - For lateral travel, see: B6100
Pipe Vert.Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 280 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 350 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.251 450 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 650 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.252 750 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 920 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.53 1060 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.6254 1680 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.6255 2100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.8756 2550 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.8758 3400 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.12510 4000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.12512 4400 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.12514 5000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.12516 5800 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.37518 6400 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.37520 6800 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.37524 7200 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.37530 9400 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.62536 11000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.12542 12400 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B7
Heavy Duty,Base Mounted MODEL B2200 Sliding Insulated Pipe Support
Application:
Model B2200 is designed for use on: Hot Water Vacuum Gas Cold Water Steam Air Dual Temperature Chilled Water
Intended for installation on: Flat Surfaces
Temperature Range: +40F to +1200FNote: Up to 1700 F available upon request.
Features:
All pipe sizes Easy Installation Eliminates welding to pipe Overlapping galvanized sheet metal jacket Insulating structural inserts for load transfer Stainless steel to UHMW polyethylene slide Other I.D.'s and/or O.D.'s available on request Factory mounted polyethylene slide pad on steel mounting plate
Performance Test Results on File: Available upon request.
Material Data:
B2200: Applicable PSI spec. doc.: No. 209. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTM A-527. Glue: Industrial contact adhesive Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. Steel Straps/Base: Carbon Steel ASTM A-36. Fasteners: ASTM A-307 plated. Slide Pad: UHMW Polyethylene (Teflon Optional). Coating: Primer coated or hot dipped galvanized. Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.Dimensions and ratings are subject to change without notice.Note: For higher load ratings, see: B2300 - For lesser axial travel, see: B1200 - For lateral restraint, see: B4200 - For lateral travel, see: B6200
Pipe Vert.Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 400 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 500 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.251 650 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 950 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.252 1100 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1350 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.53 1600 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.6254 2500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.6255 3100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.8756 3800 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.8758 5100 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.12510 6000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.12512 6600 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.12514 7500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.12516 8700 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.37518 9600 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.37520 10200 4 15.