In case of DP3...operation efficiency UP!Since the threshold level can be automatically changedby the auto-reference function, two suction nozzles canbe used, alternately, with one sensor.

Till now...one sensor was required for each suctionnozzleSince the threshold level differs with the suction nozzle, asensor was required for each suction nozzle, increasingthe cost significantly.

Incorporates Auto-reference Function

DP3LED Display High Functionality Digital Pressure Sensor

High Accuracy Sensingat All Times with Auto-reference Function

710

SERIES

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

MarkedConforming to EMC Directive

• Unaffected by changes in reference pressureBy an external signal, the set (threshold) values are corrected by being shifted by an amount equal to thepressure change. Hence, judgement by the sensor is as accurate as before the reference pressure change.This function is extremely suitable in places havingintense variations in the reference pressure or wherefine settings are required.

• Total cost reduction

For chip components

For trimmers

Example of air-leak test

OK NG

NG? NG OK NG

Threshold level

Reference pressure

Auto-reference function follows reference pressure changes

Pressure sensor not incorporatingauto-reference function DP3 series

Before reference pressure change After reference pressure change

Referencepressure

Reference pressure

change

Referencepressure

Referencepressure

Referencepressure

Referencepressure

Referencepressure

Suction OK Suction NG Suction over

Suction nozzle for trimmersAtmosphericpressure( )

Vacuum

Suction nozzle for chip components

Threshold level for suction nozzle for trimmers

Threshold levelfor suction nozzle for chip components

Before suction

Aut

o-re

fer-

ence

inpu

t

Electromagnetic valve

DP3-80

MODE

Page 2: Bottle Filling Circuit Diagram

The pressure unit can be selected fromsix different systems to suit yourrequirement.

The selectable pressure units differwith the sensor type. When the pres-sure unit is changed, the measuredpressure value and the set valuesare automatically converted.

Pressure changes can also be dis-played in an analog fashion using LEDbars. Hence, sudden pressure changescan be recognized at a glance.

LED bars indicate the pressure levelin steps of 10% F.S., regardless ofthe pressure unit.

711

DP3

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

Two Outputs with Four Independent Settings and Four Output Modes Enable Control as per Your Requirement

Selection from Six Pressure UnitsAnalog Bar Display Peak Hold/Bottom Hold Display

A Wide Variety of Models

High Accuracy • High Resolution • High Speed

Hysteresis modeThe hysteresis of the comparative outputs can be set, as desired, with theset values.

Window comparator modeThe comparative outputs can be madeON or OFF by a pressure within the setrange.Since Comparative Output 1 can be usedas a self-diagnosis output, it is possibleto specify the auto-reference input range.

Note: The auto-reference function acts only on Set Value 3 (P3) and Set Value 4 (P4) of Comparative Output 2.

Forced output modeThe comparative outputs are forciblymaintained in the OFF state in thesensing mode, irrespective of the setvalues.Also, since the comparative outputs can be forcibly made ON or OFF withkey operation, without actually applyingpressure, this mode is suitable for anoperation check or a start-up check.

Leak test modeThis mode is optimally suitable for aleak test since Comparative Output 1can be set to the hysteresis mode andComparative Output 2 can be set to thewindow comparator mode.

It achieves a 2.5ms, or less, responsetime at a high resolution of 1/1,000.It enables highly accurate sensing with itsexcellent repeatability and temperaturecharacteristics.

The peak value or the bottom value ofthe varying pressure can be displayed.This function is convenient for findingthe pressure variation range or fordetermining a reference for pressuresettings.

Selection can be made according tomounting method or place of use.

Note: The response time is 7.5ms, or less, at thetime of auto-reference input.

1 2

3 4

ON

OFF

ON

OFF0

Comparative Output 1

Comparative Output 2

Hysteresis

High pressure(Positive pressure type)High vacuum(Vacuum pressure type)

Hysteresis

Set Value 1 Set Value 2 Set Value 3 Set Value 4(P1)

(Note)

(P2) (P3) (P4)

ON

OFF

ON

OFF0

Comparative Output 1

Comparative Output 2

Hysteresis Hysteresis

Hysteresis Hysteresis

Set Value 1 Set Value 3(P1)

(Note)

(P2) (P3) (P4)Set Value 2 Set Value 4

High pressure(Positive pressure type)High vacuum(Vacuum pressure type)

ON

OFF

ON

OFF0

Comparative Output 1

Comparative Output 2

Hysteresis(Variable)

Hysteresis(Fixed)

Hysteresis(Fixed)

Set Value 1 Set Value 2 Set Value 3 Set Value 4(P1)

(Note)(P2) (P3) (P4)

High pressure(Positive pressure type)High vacuum(Vacuum pressure type)

ON

OFFON

OFF

MODE MODEPress key

Sensing mode Forced output mode

ComparativeOutput 1

ComparativeOutput 2

Sensing mode

Press key

Hysteresis: 1 digit (2 digits when using psi unit)

Response time2.5ms or less

RepeatabilityWithin50.2% F.S.51 digit

Temperature characteristicsWithin51% F.S.

Optimum for leak test Suitable for start-up check

: Positive pressure type: Vacuum pressure type

inHg kPa

mmHg psi bar

(Note) kgf/cm2

International System of Units (SI)

DP3-41 100kPa

OUT2OUT1

MODE

0-ADJ

Peak value

Bottom value

Peak value is displayed if key is pressed continuously.

Bottom value is displayed if key is pressed continuously.

DP3-41 100kPa

OUT2OUT1

MODE

0-ADJ

Pre

ssur

e

Time

Analog bar display Digital display

Note: ‘MPa’ in case of DP3-22 and DP3-42.Note: The above graph is for a positive pressuretype sensor.

Hysteresis (fixed): 1 digit (2 digits when using psi unit)

Note: The auto-reference function acts only on Set Value 3 (P3) and Set Value 4 (P4) of Comparative Output 2.

Note: The auto-reference function acts only on Set Value 3 (P3) and Set Value 4 (P4) of Comparative Output 2.

Standard type/DP3-2 M

Flat type/DP3-4 M Light weight type/DP3-80

MODE

Direct piping

Direct mounting on a wall

Mounting on apanel

DP2-20

–101.3kPa

OUT2

OUT1

MODE

0-ADJ

DP2-20

–101.3kPa

OUT2

OUT1

MODE

0-ADJ

Total weight70g approx.

The sensorcan bemounted onthe suctionhead of a chipmounter.

( ) ( )

Page 3: Bottle Filling Circuit Diagram

DP3

712

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

Type Appearance Rated pressure range Model No. Pressure port

APPLICATIONS

ORDER GUIDE

Confirmation of chip component suctionThe auto-reference function can com-pensate for the difference in suctionlevels due to suction nozzle separationdistance. The vacuum type can bemounted close to the chip mountersuction head since it weighs only 70g.

Air-leak test for PET bottlesLeak test mode, which is an outputmode optimally suitable for an air-leaktest, has been incorporated. It can reli-ably detect even a small air- leak.Because of the auto-reference func-tion, it is safe even if the filling pressurevaries.

IC

IC tray

DP3-80

MODE

DP3-41

100kPa

OUT2

OUT1MODE

0-ADJ

DP3-41

0 to1101.3kPa

0 to 1.000MPa

0 to 100.0kPa

0 to1101.3kPa

0 to 100.0kPa

0 to 1.000MPa

DP3-80

DP3-22

DP3-21

DP3-20

DP3-41

DP3-42

M5 female thread

Rc (PT) 1/8female thread

Rc (PT) 1/8female thread

Vac

uum

pre

ssur

e

Ligh

t wei

ght

Pos

itive

pre

ssur

e

Sta

ndar

d

Vac

uum

pres

sure

110

1kP

a ty

pe1M

Pa

type

100k

Pa

type

110

1kP

a ty

pe

Pos

itive

pre

ssur

e

Fla

t

1MP

a ty

pe10

0kP

a ty

pe

Page 4: Bottle Filling Circuit Diagram

713

DP3

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

OPTIONS

Designation

Sensor mountingbracket(For standard type)

Mounting bracket for standard typeTwo M4 (length 6mm) pan head screws and two spring washersare attached.

Changes the pressure port from female thread [Rc (PT) 1/8] tomale thread [R (PT) 1/8].

It can be used for mounting on a panel (1 to 3.2mm thick).

It protects the sensor’s adjustment panel.(It can be fitted when the panel mounting bracket is used.)

MS-DPX

DPX-03

MS-DPX-2

DPX-04

Straight bush

Panel mountingbracket(For standard type)

Front protectioncover(For standard type)

Model No. Description

Panel mounting bracket, Front protection cover

Sensor mountingbracket

Straight bush

DP2-20

–101.3kPa

OUT2

OUT1

MODE

0-ADJ

Front protectioncover DPX-04

Panel mounting bracketMS-DPX-2 Suitable for 1 to 3.2mm thick panel( )

Straightbush

Two M4 (length 6mm) panhead screws and two springwashers are attached.

[ ]

Page 5: Bottle Filling Circuit Diagram

Type of pressure

Rated pressure range

Set pressure range(Note 1)

Settable range(Note 2)

Pressure withstandability

Applicable fluid

Selectable units

Supply voltage

Current consumption

Comparative outputsComparative Output 1Comparative Output 2

Utilization category

Output modes

Hysteresis

Repeatability

Response time

Short-circuit protection

Auto-reference input

Display

Displayable pressure range

Analog bar display

Comparative Output 1

Comparative Output 2

Pollution degree

Protection

Ambient temperature

Ambient humidity

EMC

Voltage withstandability

Insulation resistance

Vibration resistance

Shock resistance

Temperature characteristics

Pressure port

Material

Cable

Cable extension

Weight

Accessories

DP3

714

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

Env

ironm

enta

l res

ista

nce

SPECIFICATIONS

Gauge pressure

0 to1101.3kPa 0 to 100.0kPa 0 to 1.000MPa

5.1 to1101.3kPa15.0 to 100.0kPa 10.050 to 1.000MPa

101.3 to1101.3kPa1100.0 to 100.0kPa 11.000 to 1.000MPa

490kPa 1.47MPa

Non-corrosive gas

kPa, kgf/cm2, bar, psi, mmHg, inHg kPa, kgf/cm2, bar, psi MPa, kgf/cm2, bar, psi

12 to 24V DC % Ripple P-P 10% or less

50mA or less

NPN open-collector transistor• Maximum sink current: 100mA• Applied voltage: 30V DC or less (between comparative output and 0V)• Residual voltage: 1V or less (at 100mA sink current)

0.4V or less (at 16mA sink current)

DC-12 or DC-13

Equipped with 4 types of modes: hysteresis mode, window comparator mode, leak test mode, forced output mode(selectable by key operation)

1 digit (however, variable in hysteresis mode, variable for Comparative Output 1 only when using leak test mode, and 2 digits when using psi unit)

Within50.2% F.S.51 digit

2.5ms or less [7.5ms or less with auto-reference input (Note 3)]

Incorporated

Input signal condition: NPN non-contact input [operates in Low (fall) state]High...5 to 30V or openLow...0.4V or less (0.5mA, or less, source current)Low level input time...1ms or moreReference pressure duration...1ms or more

31/2 digit red LED display (Sampling rate: 4 times/sec. approx.)

5.1 to1101.3kPa15.0 to 100.0kPa 10.050 to 1.000MPa

LED bar display in steps of 10% F.S. approx.

Orange LED (lights up when Comparative Output 1 is ON)

Green LED (lights up when Comparative Output 2 is ON)

3 (Industrial environment)

IP40 (IEC)

110 to`507C (No dew condensation or icing allowed), Storage: 110 to`607C

35 to 85% RH, Storage: 35 to 85% RH

Emission: EN50081-2, Immunity: EN50082-2

1,000V AC for one min. between all supply terminals connected together and enclosure

50MΩ, or more, with 500V DC megger between all supply terminals connected together and enclosure

10 to 150Hz frequency, 0.75mm amplitude in X, Y and Z directions for two hours each

100m/s2 acceleration (10G approx.) in X, Y and Z directions for three times each

Over ambient temperature range 110 to`507C: within51% F.S. of detected pressure at 207C

Standard type: Rc (PT) 1/8 female thread, Flat type: Rc (PT) 1/8 female thread, Light weight type: M5 female thread

Front case: ABS, Rear case: PPS (glass fiber reinforced), Display surface: AcrylicPressure port attachment: Die-cast zinc alloy [Light weight type: POM (glass fiber reinforced), pressure port is brass (nickel plated)]

0.15mm2 5-core oil resistant cabtyre cable, 2m long

Extension up to total 100m is possible with 0.3mm2, or more, cable.

Standard type: 95g approx., Flat type: 120g approx., Light weight type: 70g approx.

DPX-02 (Hexagon-socket-head plug for pressure port): 1 No. (Standard type only), Pressure unit label: 1 No.

Vacuum pressure Positive pressure 1101kPa type 100kPa type 1MPa type

Standard Light weight Standard Flat Standard Flat

DP3-20 DP3-80 DP3-21 DP3-41 DP3-22 DP3-42

Type

Item Model No.

0.052 to11.033kgf/cm2, 0.051 to11.013bar0.74 to114.70psi, 38 to1760mmHg1.5 to129.9inHg

10.051 to 1.020kgf/cm2, 10.050 to 1.000bar10.72 to 14.50psi

10.51 to 10.20kgf/cm2, 10.50 to 10.00bar17.2 to 145.0psi

1.033 to11.033kgf/cm2, 1.013 to11.013bar14.70 to114.70psi, 760 to1760mmHg29.9 to129.9inHg

11.020 to 1.020kgf/cm2, 11.000 to 1.000bar114.50 to 14.50psi

110.20 to 10.20kgf/cm2,110.00 to 10.00bar1145.0 to 145.0psi

0.052 to11.033kgf/cm2, 0.051 to11.013bar0.74 to114.70psi, 38 to1760mmHg1.5 to129.9inHg

10.051 to 1.020kgf/cm2,10.050 to 1.000bar10.72 to 14.50psi

10.51 to 10.20kgf/cm2,10.50 to 10.00bar17.2 to 145.0psi

Operationindicators

Notes: 1) The set pressure range is the settable pressure range for Set Value 1 (P1) and Set Value 2 (P2).2) The settable range is the settable pressure range for Set Value 3 (P3) and Set Value 4 (P4). It caters to the auto-reference function and is much wider

than the rated pressure range.3) Refer to ‘Time chart ’ under ‘Auto-reference function’ on P.718.

`10115

( )

Page 6: Bottle Filling Circuit Diagram

715

DP3

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

I/O CIRCUIT AND WIRING DIAGRAMS

PRECAUTIONS FOR PROPER USE

I/O circuit diagram

Note: If you do not use the auto-reference input (pink),always connect it to `V (brown).

Symbols ... D: Reverse supply polarity protection diodeZD1, ZD2: Surge absorption zener diodeTr1, Tr2 : NPN output transistor

Wiring diagram

Tr2

Tr1

ZD1

ZD2

D

12 to 24V DC`10115 %

`

1

Sen

sor

circ

uit

Color code

(Brown)`V

LoadLoad

100mA max.

100mA max.(Blue) 0V

(White) Comparative Output 2

(Black) Comparative Output 1

(Pink) Auto-reference (Pink) input (Note)

Users’ circuitInternal circuit

Blue

Brown

White

Pink

BlackLoad

12 to 24V DC`10115 %

`

1

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

Load

• This product is not a safety sensor. Its use is notintended or designed to protect life and preventbody injury or property damage from dangerousparts of machinery. It is a normal pressuredetection sensor.

• The DP3 series is designed for use with non-corrosive gas. It cannot be used with liquid or cor-rosive gas.

Others• Use within the rated pressure range.• Do not apply pressure exceeding the pressure with-standability value. The diaphragm will get damaged andcorrect operation shall not be maintained.

• Do not use during the initial transient time (0.5 sec.) afterthe power supply is switched on.

• Avoid dust, dirt, and steam.• Take care that the sensor does not come in direct contactwith water, oil, grease, or organic solvents, such as,thinner, etc.

• Do not insert wires, etc., into the pressure port. Thediaphragm will get damaged and correct operation shallnot be maintained.

• Do not operate the keys with pointed or sharp objects.

Wiring• Make sure to carry out the wiring in the power supply offcondition.

• Verify that the supply voltage variation is within the rating.• If power is supplied from a commercial switching regulator,ensure that the frame ground (F.G.) terminal of the powersupply is connected to an actual ground.

• In case noise generating equipment (switching regulator,inverter motor, etc.) is used in the vicinity of this sensor,connect the frame ground (F.G.) terminal of the equipmentto an actual ground.

• Do not run the wires together with high-voltage lines orpower lines or put them in the same raceway. This cancause malfunction due to induction.

All models

Page 7: Bottle Filling Circuit Diagram

DP3

716

All models

PRECAUTIONS FOR PROPER USE

Displays measured pressure, settings, errormessages and key-protect status.

Lights up when Comparative Output 1 is ON.

Lights up when Comparative Output 2 is ON.

• Each press of the key changes the selectedmode to sensing mode, Set Value 1 (P1) lSet Value 4 (P4) set mode.

• In the sensing mode, if the key is pressedcontinuously for about 3 sec., key-protect canbe set/released.

• In the sensing mode, if the mode selection key is pressed while pressing the incrementkey( ), the initial setting mode is obtained.

• In the initial setting mode, pressing thekey changes the settable digit.

• In the Set Value 1 to 4 modes, press-ing the key changes the set value tothe high pressure side in case ofpositive pressure type sensor and tothe high vacuum side in case ofvacuum pressure type sensor.

• In the sensing mode, if the key ispressed continuously for 4 sec. or more, the display shows peak hold value.

• In the initial setting mode, pressing thekey changes the set conditions.

• In the Set Value 1 to 4 modes, press-ing the key changes the set value tothe low pressure side in case ofpositive pressure type sensor and tothe low vacuum side in case ofvacuum pressure type sensor.

• In the sensing mode, if the key ispressed continuously for 4 sec. or more,the display shows bottom hold value.

31/2 digit LEDdisplay (Red)

Comparative Output1 operation indicator(Orange)

Comparative Output2 operation indicator(Green)

4

5

6

1

2

3

Increment key ( )

Mode selection key ( )

Decrement key ( )

In th

e se

nsin

g m

ode,

if b

oth

the

keys

are

pre

ssed

si

mul

tane

ousl

y, z

ero-

poin

t adj

ustm

ent i

s do

ne.

Functional description

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

1

23

64

5

Label for change in pressure unit• When a pressure unit other than ‘kPa’ ( ) or ‘MPa’ ( ) has

been selected in the initial setting mode, the label (suppliedas accessory) which corresponds to the selected unit should be stuck at the position shown in the figure below.

Pressure unit label (accessory)

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

Conversion of pressure units• In the DP3 series, the conversionto different units is automaticallydone on changing the setting ofthe pressure unit. However, thisconversion can also be obtainedby multiplying the values by thecoefficients given in the table onthe right.

Conversion procedure

• For example, if 2kPa is to be expressedin kgf/cm2,

since 1kPa41.0197221012kgf/cm2,2kPa becomes 221.0197221012c0.020kgf/cm2.

Description Function

Stick the pressure unit labelat the position shown.

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

MODE

Error message Cause Corrective action

00

00

00

00

Overcurrent due to short-circuit.

Pressure is being appliedduring zero-point adjust-ment.

Applied pressureexceeds the upperlimit of displayablepressure range.

Applied pressureexceeds the lowerlimit of displayablepressure range.

Applied pressureexceeds the lowerlimit of displayablepressure range.

Applied pressureexceeds the upperlimit of displayablepressure range.

Switch off the power supplyand check the load.

Applied pressure at thepressure port should bebrought to atmospheric pres-sure and zero-point adjust-ment should be done again.

Applied pressure should bebrought within the ratedpressure range.

Error messages• When an error occurs, take the following corrective action.

Pos

itive

pres

sure

type

Vac

uum

pres

sure

type

Pos

itive

pres

sure

type

Vac

uum

pres

sure

type

kPa MPa kgf/cm2 bar psimmHg

inHg atm(Torr)

1kPa 1 121013 1.0197221012 121012 1.4503821011 7.50062 0.2953 9.8692321013

1MPa 12103 1 1.01972210 1210 1.450382102 7.500622103 0.29532103 9.86923

1kgf/cm2 9.80665210 9.8066521012 1 9.8066521011 1.42234210 7.355592102 2.8959210 9.6784121011

1bar 12102 121011 1.01972 1 1.45038210 7.500622102 2.953210 9.8692321011

1psi 6.89473 6.8947321013 7.0306521012 6.8947321012 1 5.17147210 2.036 6.8045721012

1mmHg1.3332221011 1.3332221014 1.3595121013 1.3332221013 1.9336821012 1 3.937021012 1.3157921013

(1Torr)

1inHg 3.3864 3.386421013 3.453121012 3.386421012 0.4912 2.5400210 1 3.34221012

1atm 1.013252102 1.0132521011 1.03323 1.01325 1.46960210 7.600002102 2.9921210 1

Conversion table for pressure units

Page 8: Bottle Filling Circuit Diagram

717

DP3PRECAUTIONS FOR PROPER USE

Setting

• If key-protect has been set, make sure to release key-protect before operating the keys. (Please refer to ‘Key-protect function ’ on P.719 for the procedure.)

• Set Value 1 to 4 (P1 to P4) can be made common for all the output modes.• In the positive pressure type sensor, Set Value 2 (P2) and Set Value 4 (P4) can be set only towards the high pressure side

with respect to Set Value 1 (P1) and Set Value 3 (P3), respectively.In the vacuum pressure type sensor, Set Value 2 (P2) and Set Value 4 (P4) can be set only towards the high vacuum sidewith respect to Set Value 1 (P1) and Set Value 3 (P3), respectively.

• Auto-reference function acts on Set Value 3 (P3) and Set Value 4 (P4) only.• Set Value 5 (P5) is the auto-reference input value. If auto-reference input is not applied, Set Value 5 (P5) is zero.• The conditions which are set are stored in an EEPROM. Kindly note that the EEPROM has a life span and its guaranteedlife is 100,000 write operation cycles. However, since the auto-reference input value [Set Value 5 (P5)] is not written intothe EEPROM, it is not included in the number of write operation cycles.

Setting procedure

1 Zero-point adjustment

Adjust zero-point

2 Initial setting

Set ‘Display’, ‘Output mode’,and ‘Unit’

3 Pressure value setting

Enter Set Value 1 to 4(P1 to P4)

Measurement

Commence measurement on completion of setting

1 Zero-point adjustment

• The displayed pressure when the pressure port is leftopen is adjusted to zero.

• The sensor will automatically enter the sensingmode when power is supplied.

• Let the pressure port be at atmospheric pressure(i.e., no applied pressure condition), and press,simultaneously, the increment and decrement keys continuously.

• is displayed and, when the fingers arereleased, zero-point adjustment is completed andthe sensor returns to the sensing mode.

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

3 Pressure value setting

• Set Value 1 to 4 (P1 to P4) of the comparative outputs are set.• At each press of key, the mode changes, in rotation, to Set Value 1 (P1) set mode, Set Value 2(P2) set mode, Set Value 3 (P3) set mode, Set Value4 (P4) set mode, Set Value 5 (P5) display mode andsensing mode.

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

2 Initial setting• Pressure ‘Unit’, ‘Display’ and ‘Output mode’ of thecomparative outputs are set.

• In the sensing mode, press key while press-ing key.

• Initial setting is displayed.• If sensor is being used for the first time, is displayed.

MODEDP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

3rd digit 2nd digit

Change with key

1st digit

Unit Output mode Display

: kPa or MPa

: kgf/cm2

: bar

: psi

: Hysteresis mode

: Window comparator mode

: Digital display

: Analog bar display

: Leak test mode

: Forced output mode

: mmHg

: inHg

Pos

itive

pr

essu

re ty

peV

acuu

m

pres

sure

type

• If the output mode has been set to the window comparatormode ( ), set the pressure values so that there is a differenceof 3 digits, or more, between Set Value 1 (P1) and Set Value 2(P2) and between Set Value 3 (P3) and Set Value 4 (P4). Also, if the output mode has been set to the leak test mode ( ), setthe pressure values so that there is a difference of 3 digits, or more,between Set Value 3 (P3) and Set Value 4 (P4). However, when unitis set to ‘psi’ ( ), the difference should be 6 digits, or more.

• The pressure values can be set only when the output mode hasbeen set to hysteresis mode ( ), window comparatormode ( ) or leak test mode ( ). If the output mode has been setto the forced output mode ( ), pressure values cannot be set.

MODE

Sensing mode1’ • At the time of auto-reference input, is displayed, and the sensed pressure value is recorded in Set Value 5 (P5).

Sensing mode1 • Sensed pressure value is displayed.

Set Value 5 (P5) display mode6 • Auto-reference input value is displayed.

In case auto-reference input has not been applied, zero is displayed.

Set Value 1 (P1) set mode2 • Enter Set Value 1 (P1) using key and key.

Set Value 4 (P4) set mode5 • Enter Set Value 4 (P4) using key and key.

Set Value 2 (P2) set mode3 • Enter Set Value 2 (P2) using key and key.

Set Value 3 (P3) set mode4 • Enter Set Value 3 (P3) using key and key.

MODEPress key MODEPress key

MODEPress key

MODEPress key MODEPress key

MODEPress key

Aut

o-re

fere

nce

inpu

t

• The settable digit blinks.• The settable digit changes when key is pressed.• The setting is changed when key is pressed.

All models

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

Page 9: Bottle Filling Circuit Diagram

1. Pressure is increased in the PET bottle, and when Set Value 2(P2) is reached, Comparative Output 1 is turned ON and the filling is tightly shut off.

2. After shutting off the filling pressure, the auto-reference input ismade ‘Low’. The filled pressure is recorded in Set Value 5 (P5)as the reference value, and Set Value 3 (P3) and Set Value 4(P4) are corrected.

3. The leakage is measured by Comparative Output 2, 7.5ms, ormore, after the application of the auto-reference input.If the leakage is OK, Comparative Output 2 is ON, and if it isNG, Comparative Output 2 is OFF.

1. By making the auto-reference input ‘Low’ when the PCB mountcomponents are not being sucked, the reference pressure valueis recorded in Set Value 5 (P5), and Set Value 3 (P3) and SetValue 4 (P4) are corrected.

2. Suction confirmation is done by Comparative Output 2, 7.5ms,or more, after the application of the auto-reference input.If suction is OK, Comparative Output 2 is ON, and if it is NG,Comparative Output 2 is OFF.

3. Error due to suction nozzle clogging is detected by the setting ofComparative Output 1. If the nozzle is OK, Comparative Output 1 is OFF, and if it is NG,Comparative Output 1 is ON.

DP3

718

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

PRECAUTIONS FOR PROPER USE

Auto-reference functionPrinciple

• Auto-reference function corrects Set Value 3 (P3) and Set Value 4(P4) of Comparative Output 2 by taking the pressure measured atthe time of auto-reference input as the reference pressure.

<Before auto-reference input >

ComparativeOutput 2

ON

OFF

Atmospheric pressure P3 P4Pressure

<After auto-reference input >

ON

OFF

Atmospheric pressure

Auto-reference input

Pressure change

P3’

P3’4P3`P5

P4’4P4`P5

P5 P4’

ComparativeOutput 2

Pressure

• When there is no auto-reference input, the atmospheric pressureis taken as the reference pressure for Set Value 3 (P3) and SetValue 4 (P4).

• At the time of auto-reference input, the pressure value detected atthat instant is temporarily recorded as Set Value 5 (P5) andbecomes the reference pressure.

• With Set Value 5 (P5) as the reference pressure, Set Value 3 (P3)and Set Value 4 (P4) are automatically corrected to ‘Set Value 3(P3)`Set Value 5 (P5)’ and ‘Set Value 4 (P4)`Set Value 5(P5)’, respectively.

Settable range and set pressure range after correction

• The settable range of Set Value 3 (P3) and Set Value 4 (P4) is widerthan the rated pressure range to cater to the auto-reference function.

• At the time of auto-reference input, if the corrected set valueexceeds the set pressure range, the set value is automaticallycorrected to be within the set pressure range. Hence, pleasesee that the set pressure range is not exceeded.

2101kPa type

100kPa type

1MPa type

Lo

101.3

2100.0

21.000

101.2

299.9

20.999

zzzzzzzzz

zzzzzzzzz

zzzzzzzzz

5.1

25.0

0

0

0

20.1

0.1

0.001

zzzzzzzzzzz

zzzzzzzzzzz

zzzzzzzzzzz

2101.2

99.9

0.999

2101.3

100.0

1.000

UP

Settable range (P3, P4)

Rated pressure range

Set pressure range (P3 and P4 after correction)

zzzzzzzzzzz

zzzzzzzzzzz

zzzzzzzzzzz 20.050

Time chart

Auto-reference input

Comparative Output 2(ON/OFF)

High

Low

Output response time at the time of auto-reference input

Low levelinput time

1ms or more

7.5ms or less

• Maintain the pressure at a constant level for at least 1ms after theauto-reference input is made Low. If used in a transient state, itwill result in wrong operation.

• Use Comparative Output 2 at least 7.5ms after the auto-referenceinput is made low.

• At the time of auto-reference input, is displayed on the 31/2digit LED display for 1 sec. approx., the pressure at that instant isstored temporarily in Set Value 5 (P5), and Set Value 3 (P3) andSet Value 4 (P4) are corrected.

• Since Set Value 5 (P5) and the corrected Set Value 3 (P3’) andSet Value 4 (P4’), after the auto-reference input, are not stored inan EEPROM, they are erased when the power is switched off.

• When the power supply is switched on again, the auto-referenceinput value [Set Value 5 (P5)] is set to zero.

• Although it is not possible to display the corrected Set Value 3(P3’) and Set Value 4 (P4’), it is possible to display the auto-reference input value [Set Value 5 (P5)].

• In case the auto-reference input (pink) is not used, make sure toconnect it to `V (brown).

Application examples

(2) Air-leak test for PET bottles (Using leak test mode)

• Pressure judgement errors due to suction nozzle type, suctionnozzle clogging, reference pressure changes, etc., are eliminatedby the auto-reference function.

• The confirmation of PCB mount component suction is done withComparative Output 2, which is acted upon by the auto-referencefunction, and error due to nozzle clogging is simultaneouslydetected by Comparative Output 1.

0

P5

P2

P1

P4

P3

Auto-reference input

Suction level can be specified with respect to the atmospheric pressure

Suction nozzle clogging error range

P4’4P4`P5P3’4P3`P5

Time

ba

ba

OK product

NG productPre

ssur

e

<Sensing method >

(1) Confirmation of PCB mount component suction (Using hysteresis mode)

• The effect of dispersion in the filling pressure of the PET bottle iseliminated by using the auto-reference function.

• Comparative Output 1 is used to detect the filling pressure, whileComparative Output 2 is used to detect the leakage. SinceComparative Output 1 is not affected by the auto-reference inputfunction, the filling pressure is detected with reference to theatmospheric pressure.

0

P1

P5P2

P3

P4

Auto-reference input

Leakage can be specified with respect to the atmospheric pressure

P4’4P4`P5

P3’4P3`P5

b

a

OK product

NG product

ba

Time

Pre

ssur

e

<Sensing method >

If it is a simple air-leak test, it can be done by directly applyingthe Comparative Output 1 signal (falling signal) to the auto-reference input.

All models

( )

( )

( )

Page 10: Bottle Filling Circuit Diagram

719

DP3

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

• In the sensing mode, press key continuouslyfor about 3 sec. and release it immediatelywhen is displayed.• Key-protect is set and the sensor returns to the

sensing mode.

PRECAUTIONS FOR PROPER USE

Peak hold & bottom hold functions Forced output mode

Key-protect function

• Peak hold and bottom hold functions enable the display ofthe peak value (maximum pressure value in case of thepositive pressure type sensor and maximum vacuum pres-sure value in case of the vacuum pressure type sensor)and the bottom value (minimum pressure value in case ofthe positive pressure type sensor and minimum vacuumpressure value in case of the vacuum pressure type sen-sor) of the varying measured pressure.

• These functions are convenient for finding the pressurevariation range or for determining the reference for pres-sure settings.

• Please note that the peak value and the bottom value data iserased when it is no longer displayed.

• The response time of the comparative outputs becomes slowerduring the peak hold and bottom hold display.

Peak hold display

Initiating peak hold displayDP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

Displayedalternately

• In the sensing mode, keep key pressed untilis displayed. (4 sec. approx.)

• When the finger is released after is dis-played, the peak value and are displayedalternately.• If the applied pressure exceeds the displayable

pressure range, error message ( or )and are displayed alternately. In this case,bring back the applied pressure to within the ratedpressure range.

• The figure on the left shows the display of avacuum type sensor when the pressure unit hasbeen set to ‘kPa’ ( ).

Ending peak hold displayDP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

• Press key.[• Sensor returns to sensing mode.]

Bottom hold display

Initiating bottom hold displayDP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

Displayedalternately

• In the sensing mode, keep key pressed untilis displayed. (4 sec. approx.)

• When the finger is released after is displayed, the bottom value and are displayed alternately.• If the applied pressure exceeds the displayable

pressure range, error message ( or )and are displayed alternately. In this case,bring back the applied pressure to within the ratedpressure range.

• The figure on the left shows the display of avacuum type sensor when the pressure unit hasbeen set to ‘kPa’ ( ).

Ending bottom hold displayDP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

• Press key.[• Sensor returns to sensing mode.]

• In the initial setting, if the output mode is set to the forced outputmode ( ), Comparative Output 1, 2 are forcibly maintained atOFF level in the sensing mode, irrespective of Set Value 1 to 4(P1 to P4). Hence, this mode is useful when it is desired to onlydisplay the pressure value without using the comparativeoutputs.Further, if the keys are operated as per the procedure givenbelow, Comparative Output 1, 2 can be forcibly switched eitherON or OFF without applying pressure at the pressure port. Thisis convenient for an operation check of Comparative Output 1, 2or for an inspection before commencing work.The figure below is for a vacuum pressure type sensor with theunit set to ‘kPa’ ( ).

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

DP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

Forced output mode

Blinking display of measured pressure

Sensing mode

MODEPress key

[• Sensor returns to sensing mode.]

Each time key is pressed, Comparative Output 2 switches between ON and OFF.(Operation indicator also lights up, turns off.)

Each time key is pressed, Comparative Output 1 switches between ON and OFF.(Operation indicator also lights up, turns off.)

MODEPress key

Time chart

ON

OFF

ON

OFF

Sensing mode Forced output mode Sensing mode

MODEPress key MODEPress key

ComparativeOutput 1

ComparativeOutput 2

• The comparative outputs are held at the OFF level from thetime a change is made to the forced output mode ( ) from theother modes.

• Even if a comparative output is held at the ON level in theforced output mode, it is forcibly brought to the OFF level at thetime the sensor returns to the sensing mode.

• Key-protect is a function which prevents any unintentional changein the conditions which have been entered in each setting modeby making the sensor not to respond to the key operations.

Setting of key-protectDP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

MODE

• In the sensing mode, press key continuouslyfor about 3 sec. and release it immediatelywhen is displayed.• Key-protect is released and the sensor returns to

the sensing mode.

Release of key-protectDP3-80 –101.3kPa

OUT2OUT1

MODE

0-ADJ

MODE

All models

Page 11: Bottle Filling Circuit Diagram

DP3

720

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

PRECAUTIONS FOR PROPER USE

Setting of pressure lead direction• The pressure lead direction can be changed bydismantling the pressure port attachment and changingthe mounting direction. The tightening torque of thehexagon-socket-head bolt (length: 9mm or less) should be0.29Nzm or less.

Note: Make sure to close any unused pressure port with the hexagon-socket-head plug supplied as accessory.

Piping• When connecting a hexagon-socket-head plug or couplingto the pressure port, hold the hexagonal part of thepressure port with a 12mm spanner and make sure thatthe tightening torque is 9.8Nzm or less. Also, in order toprevent any leakage, wind a sealing tape on the couplingwhen connecting.

Standard type

Main body

Hexagon-socket-head bolts

Pressure portattachment

Pressureports

Hexagon-socket-head plug

12mm spanner

Setting of pressure lead direction• The pressure lead direction can be changed bydismantling the pressure port attachment and changingthe mounting direction. The tightening torque of thehexagon-socket-head bolt (length: 9mm or less) should be0.29Nzm or less.

Piping• When connecting a coupling to the pressure port, hold thepressure port attachment with a 16mm (light weight type:10mm) spanner and make sure that the tightening torqueis 9.8N z m or less (light weight type: 1.47N z m or less).Also, in order to prevent any leakage, wind a sealing tapeon the coupling when connecting.

Pressure port attachment

Hexagon-socket-head bolts

2-"4.3mm mounting holes

Pressure port

Main body

16mm(light weight type: 10mm)spanner

Flat type Light weight type

Page 12: Bottle Filling Circuit Diagram

721

DP3

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

DIMENSIONS (Unit: mm)

DP3-80 Light weight type

MODE

30

(11)30

(15.7)(10.8)

6.2

(23.7)41

2-"8, 4.4 deep

2-"4.3 mounting holes

33.5

5

10

18"3.7 cable 2m long

Pressure portM5 female thread 4 deep

23.5(25.8)

Comparative Output 2operation indicator (Green)

Increment key

Decrement key

Comparative Output 1operation indicator (Orange)

Mode selection key

(2.1)

20

(9)

(18)

31/2 digit LED display (Red)

DP3-20 DP3-21DP3-22 Standard type

MODE

(11)30 31.6

(25.8)(2.1)

30

31.6

(6)

(18.9)(10.9)

Increment key

Decrement key Mode selection key

Comparative Output 2operation indicator (Green)

Comparative Output 1operation indicator (Orange)

23.5 5

38.5

Pressure portRc (PT) 1/8 female thread

8

14

13

"3.7 cable 2m long

20

20

12

2-M3 hexagon-socket-head bolts

2-M4

31/2 digitLED display (Red)

(9)

(18)

DP3-41DP3-42 Flat type

MODE

30

(25.8)

(11)30

(15)

44.7

5.7

(19.9)

20

Comparative Output 2 operation indicator (Green)

Increment key

Decrement key

Comparative Output 1 operation indicator (Orange)

Mode selection key

2-"8, 4.4 deep

31/2 digit LED display (Red)

2-"4.3 mounting holes

35

8.2

19.5

16

"3.7 cable 2m long

Pressure portRc (PT) 1/8 female thread

23.5

(27.9)

(2.1)

(9)

(18)

Page 13: Bottle Filling Circuit Diagram

25

40

1120

12.5

20

31.5

5.8

45.5

20

20

5.8

3.6

8

t 1.6

30

2-"4.2 mounting holes

2-"4.2 mounting holes

DP3

722

PRES

SURE

SEN

SORS

DP

2D

P-Y

LED

Bar D

ispla

yD

P-M

PE

LED

Dig

ital D

ispl

ayD

P3

DIMENSIONS (Unit: mm)

MS-DPX Sensor mounting bracket for standard type (Optional)

MS-DPX-2DPX-04 Panel mounting bracket, front protection cover for standard type (Optional)

Material: Cold rolled carbon steel (SPCC) (Uni-chrome plated)

Two M4 (length 6mm) pan head screwsand two spring washers are attached.

Assembly dimensions

Assembly dimensions

MODE

25

30

28.5

11

48.539.5

31.6

14.2

45.8

40

38.5

30

24

2-"4.2 mounting holes

MODE

30

40

40 30

42.7

3

349.7

43.7

42.7

4.5

56

80

36 0.5 0

36 0.5 0

Panel cut-out dimensions

portion shows the front protection cover.Material: Polycarbonate (Front protection cover)

Nylon 6, Stainless steel (SUS304) (Panel mounting bracket)

Note: The panel thickness should be 1 to 3.2mm.


Recommended