Page 1: Battery fault Transfer Fault Charger fault Emergency Lamp ...€¦ · One blink ON/pause Battery not connected Two blinks ON/pause Battery fault Three blinks ON/pause Charger fault

TROUBLE SHOOTING•“EXIT” legend does not illuminate • Check wiringconnections.

•Emergency circuit does not work • Batteriesareshippedunchargedanddisconnected.Connectpowerpackleadsandchargebeforetesting. • Makesurechargerboardisproperlyseated. • Checkwiringconnections.

MAINTENANCESignsshouldbetestedandmaintainedinaccordancewithNationalElectricalCodeandNFPA101LifeSafetyCoderequirements.Itisrecommendedthatemergencyexitsignsbetestedfor30secondsonceamonthandfor90minutesonceayear.

RECYCLING INFORMATION Allthermoplasticpartsarerecyclable.Allcartonscontainrecycledmaterials.Pleaserecycleresponsibly.

NOTICE:Emergency model exit signs contain rechargeable nickel-cadmium batteries which must be recycled or disposed of properly.

LX SeriesThermoplastic LED Exit Sign

Installation, Operation and Maintainance Instructions

Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.comCopyright©HubbellLighting,Inc.,AllRightsReserved•Specificationssubjecttochangewithoutnotice.•PrintedinU.S.A. 93028841B 6/10

IMPORTANT SAFEGUARDSWhenusingelectricalequipment,basicsafetyprecautionsshouldalwaysbefollowedincludingthefollowing.

READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1.Donotuseoutdoors. 2.Donotletpowersupplycordstouchhotsurfaces. 3.Donotmountneargasorelectricheaters. 4.Equipmentshouldbemountedinlocationsandatheightswhereitwillnotreadilybesubjecttotamperingby unauthorizedpersonnel. 5.Theuseofaccessoryequipmentnotauthorizedbythemanufacturermaycauseanunsafecondition. 6.Donotusethisequipmentforotherthanitsintendedpurpose. 7.Servicingofthisequipmentshouldbeperformedbyqualifiedservicepersonnel. 8.Testcycling:theLifeSafetyCode(NFPA101)requirestestingofemergencyexitsignsonceamonthfora minimumof30secondsandonceayearforaminimumof90minutes.

INSTALLER: •SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS

•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT

WARNING–ThisproductcontainschemicalsknowntotheStateofCaliforniatocausecancer,birthdefectsand/orotherreproductiveharm.Thoroughlywashhandsafterinstalling,handling,cleaning,orotherwisetouchingthisproduct.

93028961

OPERATION“ACON”LEDisiluminatedwhenACpowerispresent.NOTE:AllmodelsaresuppliedwithanACLockoutcircuit,whichpreventsthe“EXIT”legendfromilluminatingwhenthebatteryisconnectedandnoACpowerispresent.NOTE:AllmodelsaresuppliedwithaLowVoltageDisconnectcircuit,whichpreventsdamagetothebatteryfromdeepdischargeduringprolongedemergencyoperation.NOTE:Batteriesareoftenshippedinadischargedstate–thisisnormal.Thebatterywillrequirecharging.Allowseveralhoursofchargebeforetestingtheunit.

ModelsWithSPECTRON®Self-Testing/Self-DiagnosticCircuitryModelsequippedwiththeSpectronself-testing/self-diagnosticelectronicssystemprovide:

■ Visual indication of AC power status ■ Visual indication of self-diagnostic test cycle —Visual indication of any unit malfunctions including— ■ Battery fault ■ Transfer Fault ■ Charger fault ■ Emergency Lamp faultSpectron equipped units also include:Brownoutprotection:unitwillautomaticallytransfertoemergencyoperationupondetectionoflowACpower(approximately80%ofnominalline).TimeDelayRetransfer:uponreturnofnormalACpower,unitwillremainintheemergencymodeforanadditional15minutestoallowACpowertostabilize.

LED Status IndicatorAbicolorLED(green/red)isprovidedonthecontrolpanelofallmodelsequippedwiththeSpectronoption.

Red Status Indicator Code Description

OneblinkON/pause Batterynotconnected

TwoblinksON/pause Batteryfault

ThreeblinksON/pause Chargerfault

FourblinksON/pause Transfercircuitfault

FiveblinksON/pause EmergencyLampfault

Automatic TestsTheunitwillautomaticallyinitiateaself-test/self-diagnosticcyclebasedonthefollowingtable:

Testing Period Duration of Test

Onceamonth 1minute

Onceevery6months Alternating:30minutesor60minutes

Manual TestsUsingtheunittestswitch,userscaninitiatedifferentdurationtestcyclesbasedonthefollowingtable:

Initiating Action Test Cycle

Presstestswitchonce 1minute

Presstestswitchtwice 90minutes

Pressingthetestswitchatanytimeafteratestcyclehasbeguncancelstheremainderofthetestandreturnstheunittonormaloperation.

RedServiceAlertIndicatorUndernormaloperatingconditions,theredServiceAlertIndicatorwillremain“off”.IntheeventtheSpectroncontrollerdetectsamalfunction,theredServiceAlertIndicatorwillblinkata1Hz.rate,basedonthefollowingtable:

GreenOperatingStatusIndicatorThegreenOperatingStatusIndicatorservesasbothanACpowerandaself-testindicator.Duringnormaloperation,thegreenOperatingStatusIndicatorwillbeilluminated,indicatingthepresenceofACpower.Duringallautomaticormanualself-testcycles,thegreenOperatingStatusIndicatorwillblinkata1Hz.rate.

MAINTENANCE

930289619302896393029014930290199302902593029029

Page 2: Battery fault Transfer Fault Charger fault Emergency Lamp ...€¦ · One blink ON/pause Battery not connected Two blinks ON/pause Battery fault Three blinks ON/pause Charger fault

END MOUNT Makeconnectionsusingquickconnectorsprovidedandinsertconnectorsincaptureslots.(SeedetailA)

IMPORTANT:Routewiresthroughtopopeningincanopyforeaseofwiring.

Usepre-tinnedpigtailleadsprovidedforACinputtosign.

ACtransformer.120VAC-connectblackandwhiteleads277VAC-connectredandwhiteleads

Storeunusedleadintransformercompartment.

*Foremergencymodels- plug2-pinbattery connectorintoPCboard.

Chargerboardand

batterypack.(Emergencymodelsonly*)

93029014

Routewiresinchannelasshown.

INSTALLATION INSTRUCTIONS

IMPORTANT:Optionconnectionwiresmustberunbeforesignhousingisattachedtocanopy.FIRE ALARM PANEL (-FAP) OPTIONFAPoptionconnectsto24voltACorDC(purplewires).FlashRate:.5secondson,.5secondsoff.DC REMOTE (-DC) OPTION DCRemoteoptionconnectsto6-24voltDC[yellow(–),blue(+)].FLASHER MODULE (-FM) OPTION EmergencyModeFlashRate:.5secondson,.5secondsoff.AUDUBLE/FLASHER MODULE (-AF) OPTION EmergencyModeBeep/FlashRate:.5secondson,.5secondsoff.

Connectoptionwires(-FAPor-DC)togreyconnectoronoptionboard.

Routewiresthroughtransformercompartmentandoutcanopyorbackplate.

93029029

DUAL CIRCUIT (-2C) OPTION

Dual-circuittransformersecondarywiresconnecttoinputconnectoronoptionboard.

Connectdual-circuitprimarytransformerwirestoutilitysource.120VAC-connectblackandwhiteleads.277VAC-connectredandwhiteleads.

93029025

WALL MOUNT

Routewiresinchannelasshown.

Storeunusedleadintransformercompartment.

Makeconnectionsusingquickconnectorsprovidedandinsertconnectorsincaptureslots.(SeedetailA)

Selectappropriateknockoutsforwallbox.

ACtransformer.120VAC-connectblackandwhiteleads.277VAC-connectredandwhiteleads

Usepre-tinnedpigtailleadsprovidedforACinputtosign.

Chargerboardand

batterypack.(Emergencymodelsonly*)

*Foremergencymodels- plug2-pinbattery connectorintoPCboard.

93028963

CEILING MOUNT

ACtransformer.120VAC-connectblackandwhiteleads.277VAC-connectredandwhiteleads

Usepre-tinnedpigtailleadsprovidedforACinputtosign.

Routewiresthroughlargeholeatsnap.

Makeconnectionsusingquickconnectorsprovidedandinsertconnectorsincaptureslots.(SeedetailA)

Routewiresinchannelasshown.

Storeunusedleadsintransformercompartment.

Chargerboardand

batterypack.(Emergencymodelsonly*)

IMPORTANT: Routewiresthroughtopopeningincanopyforeaseofwiring.

*Foremergencymodels- plug2-pinbattery connectorintoPCboard.

93029019

93029019