  • Date :Time: 14-Sep-2013 23:32:05Prepared By :Site: AJ Wunut StationClient :Tag Number: KEIL FE-4001A

    :Data ReferenceDescription : Metering Strea"A"

    AGA3 - 1992 Orifice Metering

    MFRUnitsSVFRUnits

    Input Data

    Standard Volume Flow Rate Calculation

    314.73 psiaPf1Upstream Static Pressure

    Developed from Real Gas Relative Density

    80 FTfTemperature

    5.761 inchesDrPipe BoreFTrPipe Bore Calibration Temperaturein/in-FTemperature Coefficient for Pipe

    0.0116 lbm/ft-secDynamic Viscosity Cp/CvSpecific Heat Ratio

    Calculated ResultsMeter Tube Internal Diameter at Operating Temperature D 5.761429 inchesOrifice Plate Bore at Operating Temperature d 2.194052 inchesDiamater Ratio at Operating Temperature 0.380817Expansion Factor Y1 0.999126Velocity of Approach Factor Ev 1.010684Coefficient of Discharge Cd(FT) 0.684148

    Solve For : Flow

    680.0000062

    Orifice BoreOrifice Bore Calibration TemperatureTemperature Coefficient for Orifice

    drtr

    2.19380868

    0.00000925Differential Pressure hw 25 in H2O @ 60F

    1.369

    Fin/in-F

    inches

    Compressibility Factor At Base ConditionsCompressibility Factor of Air At Base Conditions

    0.9979690.99959

    ZbZbair

    Compressibility Factor At Upstream Flowing ConditionsReal Gas Relative DensityBase TemperatureBase Pressure

    Zf1GrTbPb

    0.9487860.69720

    6014.73

    Fpsia

    Calorific Value CV Btu/Sft1020.2

    14-Sep-2013Kelton FLOCALC v2.1 Printed on:Kelton Engineering Ltd

    The MacKenzie Building, 168 Skene Street, Aberdeen, AB10 1PE

    Tel: +44 (0) 1224 630000 Fax: +44 (0) 1224 630004email: [email protected] http://www.kelton.co.uk

    Page 1 of 2 at 11:43:49PM

  • Date :Time: 14-Sep-2013 23:32:05Prepared By :Site: AJ Wunut StationClient :Tag Number: KEIL FE-4001A

    :Data ReferenceDescription : Metering Strea"A"

    AGA3 - 1992 Orifice Metering

    MFRUnitsSVFRUnitsReynolds Number ReD 407.441884

    Mass Flow Rate Qm 0.00000000Standard Volume Flow Rate Qb 2.88598149Energy Flow Rate Qe 2944278312.737020 MMBtu/day

    lb/hrMMSft/day

    Notes

    14-Sep-2013Kelton FLOCALC v2.1 Printed on:Kelton Engineering Ltd

    The MacKenzie Building, 168 Skene Street, Aberdeen, AB10 1PE

    Tel: +44 (0) 1224 630000 Fax: +44 (0) 1224 630004email: [email protected] http://www.kelton.co.uk

    Page 2 of 2 at 11:43:49PM