900 SERIES PANEL
SHEET INDEX
CI-DS-01-900 C & I DISCLAIMER
CI-PJ-01-900 PANEL JOINT
CI-PJ-02-900 INTERMEDIATE SUPPORT
CI-EL-01-900 ENDLAP
CI-EL-02-900 ENDLAP CONDITIONS
CI-EL-03-900 4-WAY INTERSECTION
CI-EL-04-900 CONTINUOUS MALE LEG AT
STAGGERED ENDLAP
CI-EL-05-900 STAGGERED MALE LEG AT ENDLAP
CI-EL-06-900 MALE LEG ENDLAP AT
CONTINUOUS FEMALE
CI-EL-07-900 ENDLAP INSTALLATION SEQUENCE
CI-EL-08-900 STAGGERED ENDLAP ASSEMBLY
CI-RD-01-900 RIDGE
CI-RD-02-900 RIDGE ASSEMBLY
CI-RD-03-900 RIDGE CLOSURE ASSEMBLY
CI-EV-01-900 LOW EAVE W/O GUTTER
CI-EV-02-900 LOW EAVE W/ GUTTER
CI-EV-03-900 HIGH EAVE
CI-RK-01-900 RAKE
CI-VL-01-900 VALLEY CONDITION
CI-VL-02-900 VALLEY ASSEMBLY
CI-WR-01-900 WALL TO ROOF HIGH EAVE
CI-WR-02-900 CONCRETE WALL TO HIGH EAVE
CI-WR-03-900 WALL TO RAKE
CI-WR-04-900 CONCRETE WALL TO ROOF
900 SERIES PANEL
COMMERCIAL/INDUSTRIAL
DISCLAIMER
DISCLAIMER:
THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED
COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES.
LOCATION OF VAPOR BARRIERS AND ASSOCIATED SEALANTS IN THESE DETAILS ARE BASED
ON TYPICAL DESIGN PRACTICES FOR MOST U.S. CLIMACTIC ZONES. (THE PRIMARY VAPOR
BARRIER IS PLACED ON THE "WARM" SIDE IN WINTER).
PROJECTS LOCATED IN SPECIFIC AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW
LOADS MAY REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL
SERVICES FOR SPECIFIC PROJECT RECOMMENDATIONS.
1
1
2
" - 6
"
1
1
2
"
39
3
8
" (1000mm)
EXTERIOR
INTERIOR
HIGH RIB PROFILE
V-GROOVE PROFILE
CORE DEPTHS:
1.5", 2", 2.5", 3", 4", 5", 6"
STEEL GAUGES:
EXTERIOR: 26, 24, 22
INTERIOR: 26, 24, 22
MODULE WIDTH:
39.375" (39
3
8
")
PANEL ORIENTATION:
ROOF
EMBOSSING:
EXTERIOR: STUCCO / SMOOTH
INTERIOR: STUCCO / SMOOTH
LENGTHS:
MINIMUM: 8'-0"
MAXIMUM: 53'-0"
900 ROOF
PANEL PROFILE
900 SERIES ROOF PANEL
DIRECTION OF INSTALLATION
FIELD APPLIED BUTYL
TAPE ENTIRE LENGTH
OF LAP JOINT
SIPHON GROOVE
1
4
" - 14 X
7
8
" LOW PROFILE TEK SCREWS
* FOR SLOPES ≥ 1:12 INSTALL AT
20" O.C. BETWEEN MAIN FASTENERS
* FOR SLOPES < 1:12 INSTALL AT 12"
O.C. BETWEEN MAIN FASTENERS
16 GA. PAINTED SADDLE CLIP
STAND ON THIS PANEL
WHEN FASTENING
HEAVY BEAD OF FIELD
APPLIED CONTINUOUS
BUTYL SEALANT
1
4
" - THROUGH
FASTENER WITH WASHER
ROOF SADDLE CLIPS WITH
1
4
" - THROUGH
FASTENER WITH WASHER LOCATED AT HIGH RIBS
AS REQUIRED FOR WIND LOADS
PATTERN NO. 3
PATTERN NO. 2
1
4
" - THROUGH
FASTENERS WITH
NEOPRENE WASHER
PANEL JOINT
900 SERIES ROOF PANEL
1
4
" - THROUGH FASTENERS
WITH NEOPRENE WASHER
PURLIN (BY OTHERS)
16 GA. PAINTED SADDLE CLIP
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
INTERMEDIATE
SUPPORT
900 SERIES ROOF PANEL
CONTINUOUS
BUTYL SEALANT W/
MARRIAGE BEAD TO
PANEL JOINT
3" X 4" CONTINUOUS ANGLE,
GAUGE TO MATCH PURLINS
(NOT BY KINGSPAN)
1
4
" - 14 X
7
8
" LOW PROFILE
TEK SCREWS FASTEN
BETWEEN EVERY MINOR RIB
CONTINUOUS HEAVY BEAD
BUTYL SEALANT
2
1
2
" WIDE BUTYL TAPE
CONTINUOUS ALONG
ENDLAP
1
4
" - THROUGH FASTENER
WITH NEOPRENE WASHER
FIELD REMOVE FOAM
AND INSIDE SKIN
FACTORY CUT
LINER SIDE
JOINT TO BE CENTERED
ON STRUCTURAL SUPPORT
6" E
ND
LA
P
1"
NOTE:
MIN. 5" WIDE SUPPORT
AT EACH ENDLAP FOR
PROPER PANEL
ATTACHMENT
6" LAP
MAX.
1
8
" ALLOWABLE "GAP"
BETWEEN PANELS FILLED
WITH EMSEAL BACKSEALER
ADDITIONAL CLIP
LOCATION FOR HIGH WIND
LOAD AREAS
16 GA. PAINTED SADDLE
CLIP
(USE VIBRATION RESISTANT/
ANTI-BACKOUT TYPE)
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
2
1
2
"
2
1
2
"
MIN
.
MIN
.
CONTINUOUS BUTYL
SEALANT TO SEAL
POTENTIAL GAP
BETWEEN STEEL
MEMBERS
CONTINUOUS BUTYL
SEALANT AT JOINT
LOCATIONS
ENDLAP
900 SERIES ROOF PANEL
PA
NE
L LE
NG
TH
*
3" C
UT
BA
CK
(M
OD
ES
TO
)
4
1
4
" C
UT
BA
CK
(D
ELA
ND
)
SIN
GLE
R
OO
F P
AN
EL LA
YO
UT
WIT
H N
O E
ND
LA
PS
TW
O P
AN
EL LA
YO
UT
WIT
H E
ND
LA
PS
TH
RE
E P
AN
EL LA
YO
UT
WIT
H E
ND
LA
PS
(*) A
DD
W
ALL P
AN
EL T
HIC
KN
ES
S T
O P
AN
EL LE
NG
TH
3" C
UT
BA
CK
(M
OD
ES
TO
)
4
1
4
" C
UT
BA
CK
(D
ELA
ND
)
3" C
UT
BA
CK
(M
OD
ES
TO
)
4
1
4
" C
UT
BA
CK
(D
ELA
ND
)
PA
NE
L LE
NG
TH
6" E
ND
LA
P
PA
NE
L LE
NG
TH
S*
PA
NE
L LE
NG
TH
6" E
ND
LA
P
PA
NE
L LE
NG
TH
6" E
ND
LA
P
PA
NE
L LE
NG
TH
S*
ENDLAP CONDITIONS
900 SERIES ROOF PANEL
BUTYL SEALANT FOR
VAPOR BARRIER
CONTINUOUS
BUTYL TAPE AT
LAP JOINT
REMOVE 6" MALE LEG ON THE LOWER
END OF THE UPPER PANEL, THEN ALIGN
INSTALL AND ALIGN UPPER COURSE,
FASTEN AND SEAL AS DETAILED
CONTINUOUS BUTYL
TAPE
1
2
NOTES:
1. SET LOWER COURSE ROOF PANEL IN PLACE. UPPER END OF PANEL AT THE ENDLAP MUST ALIGN
WITH THE WEB OF THE ENDLAP PURLIN AND REST ON THE 3" X 4" SUPPORT ANGLE.
2. CHECK PANEL MODULE, ADJUST IF NECESSARY BEFORE ATTACHING PANEL TO THE SUPPORT
ANGLE WITH FASTENING SYSTEM.
3. SET THE UPPER PANEL IN PLACE, FASTEN PANELS TO THE SUPPORT STRUCTURE USING A SINGLE
HEX HEAD FASTENER WITH PAINTED SADDLE CLIP WHICH MUST PASS THROUGH ALL FOUR PANELS.
4. KINGSPAN DOES NOT RECOMMEND INSTALLING ALL LOWER COURSE PANELS FIRST.
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD
CONTINUOUS BUTYL
SEALANT
CONTINUOUS BUTYL SEALANT TO
SEAL POTENTIAL GAP BETWEEN
STEEL MEMBERS
MAX.
1
8
" ALLOWABLE
"GAP" BETWEEN
PANELS FILLED WITH
EMSEAL BACKSEALER
EMSEAL BACKSEALER
CONTINUOUS BUTYL
SEALANT AT JOINT
LOCATIONS
4-WAY INTERSECTION
900 SERIES ROOF PANEL
BUTYL SEALANT FOR
VAPOR BARRIER
CONTINUOUS
BUTYL TAPE AT
LAP JOINT
REMOVE 6" MALE LEG ON THE LOWER
END OF THE UPPER PANEL, THEN ALIGN
INSTALL AND ALIGN UPPER COURSE,
FASTEN AND SEAL AS DETAILED
CONTINUOUS BUTYL
TAPE
1
2
NOTES:
1. SET LOWER COURSE ROOF PANEL IN PLACE. UPPER END OF PANEL AT THE ENDLAP MUST ALIGN
WITH THE WEB OF THE ENDLAP PURLIN AND REST ON THE 3" X 4" SUPPORT ANGLE.
2. CHECK PANEL MODULE, ADJUST IF NECESSARY BEFORE ATTACHING PANEL TO THE SUPPORT
ANGLE WITH FASTENING SYSTEM.
3. SET THE UPPER PANEL IN PLACE, FASTEN PANELS TO THE SUPPORT STRUCTURE USING A SINGLE
HEX HEAD FASTENER WITH PAINTED SADDLE CLIP WHICH MUST PASS THROUGH ALL FOUR PANELS.
4. KINGSPAN DOES NOT RECOMMEND INSTALLING ALL LOWER COURSE PANELS FIRST.
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD
CONTINUOUS BUTYL
SEALANT
CONTINUOUS BUTYL SEALANT TO
SEAL POTENTIAL GAP BETWEEN
STEEL MEMBERS
EMSEAL BACKSEALER
CONTINUOUS MALE LEG
AT STAGGERED ENDLAP /
FEMALE ENDLAP
900 SERIES ROOF PANEL
BUTYL SEALANT FOR
VAPOR BARRIER
CONTINUOUS
BUTYL TAPE AT
LAP JOINT
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD
CONTINUOUS BUTYL SEALANT TO
SEAL POTENTIAL GAP BETWEEN
STEEL MEMBERS
MAX.
1
8
" ALLOWABLE "GAP"
BETWEEN PANELS FILLED WITH
EMSEAL BACKSEALER
3" X 4" ANGLE, GAUGE TO MATCH
PURLINS
(NOT BY KINGSPAN)
CONTINUOUS BUTYL
SEALANT
NOTES:
1. SET LOWER COURSE ROOF PANEL IN PLACE. UPPER END OF PANEL AT THE ENDLAP MUST ALIGN
WITH THE WEB OF THE ENDLAP PURLIN AND REST ON THE 3" X 4" SUPPORT ANGLE.
2. CHECK PANEL MODULE, ADJUST IF NECESSARY BEFORE ATTACHING PANEL TO THE SUPPORT
ANGLE WITH FASTENING SYSTEM.
3. SET THE UPPER PANEL IN PLACE, FASTEN PANELS TO THE SUPPORT STRUCTURE USING A SINGLE
HEX HEAD FASTENER WITH PAINTED SADDLE CLIP WHICH MUST PASS THROUGH ALL FOUR PANELS.
4. KINGSPAN DOES NOT RECOMMEND INSTALLING ALL LOWER COURSE PANELS FIRST.
REMOVE 6" MALE LEG ON THE LOWER
END OF THE UPPER PANEL, THEN ALIGN
INSTALL AND ALIGN UPPER COURSE,
FASTEN AND SEAL AS DETAILED
1
2
STAGGERED MALE LEG AT
ENDLAP
900 SERIES ROOF PANEL
BUTYL SEALANT FOR
VAPOR BARRIER
CONTINUOUS
BUTYL TAPE AT
LAP JOINT
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD
CONTINUOUS BUTYL SEALANT TO
SEAL POTENTIAL GAP BETWEEN
STEEL MEMBERS
MAX.
1
8
" ALLOWABLE
"GAP" BETWEEN
PANELS FILLED WITH
EMSEAL BACKSEALER
3" X 4" ANGLE, GAUGE TO MATCH
PURLINS
(NOT BY KINGSPAN)
STAGGERED MALE LEG AT
ENDLAP / CONTINUOUS
FEMALE LEG
900 SERIES ROOF PANEL
12
46
35
78
EA
VE
R
A
K
E
RID
GE
PU
RL
IN
T
YP
E M
AY
V
AR
Y
DIR
EC
TIO
N O
F IN
ST
AL
LA
TIO
N
NO
TE
: IN
TE
RM
ED
IA
TE
R
IB
S A
RE
N
OT
S
HO
WN
F
OR
C
LA
RIT
Y
ENDLAP INSTALLATION
SEQUENCE
900 SERIES ROOF PANEL
1F
AS
TE
N A
T E
VE
RY
M
IN
OR
R
IB
V
AL
LE
Y
2S
TA
GG
ER
ED
E
ND
LA
PS
3S
EE
M
AL
E L
EG
E
ND
LA
P D
ET
AIL
4S
EE
C
ON
TIN
UO
US
M
AL
E L
EG
D
ET
AIL
5S
EE
F
EM
AL
E L
EG
E
ND
LA
P D
ET
AIL
15
43
ST
AG
GE
RE
D E
ND
LA
P A
SS
EM
BL
Y
(IS
OM
ET
RIC
V
IE
W - T
YP
IC
AL
)
STAGGERED ENDLAP
ASSEMBLY
900 SERIES ROOF PANEL
1
4
" - 14 X
7
8
" LOW PROFILE TEK
SCREWS AT EACH HIGH RIB AND
BETWEEN HIGH RIBS
FIELD FILL WITH COMPRESSIBLE
INSULATION OR FIELD FOAM WITH
2-PART URETHANE (NOT BY KINGSPAN)
OUTSIDE RIDGE TRIM
(SET IN BUTYL TAPE)
RIDGE CLOSURE TRIM
INSIDE RIDGE TRIM
900 FOAM CLOSURE SET IN
BUTYL TAPE TOP AND BOTTOM
1
4
" - THROUGH FASTENER
WITH NEOPRENE WASHER
(AS REQUIRED FOR WIND LOADS)
CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD TO PANEL JOINT
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
1
4
" - 14 X
7
8
" LOW
PROFILE TEK SCREWS
BETWEEN EVERY
MINOR RIB
CONTINUOUS
BUTYL TAPE
CONTINUOUS
BUTYL TAPE
CONTINUOUS BUTYL
SEALANT AT JOINT
LOCATIONS
RIDGE
900 SERIES ROOF PANEL
1
4
" - 14 X
7
8
" LOW
PROFILE TEK
SCREWS AT
EACH HIGH
RIB AN
BETWEEN HIGH
RIBS
OUTSIDE RIDGE TRIM
5
5
NOTE: SEE 900 CLOSURE
ASSEMBLY DETAIL
BUTYL TAPE
RIDGE CLOSURE TRIM W/
1
4
" - 14 x
7
8
" LOW PROFILE
TEK SCREWS BETWEEN EVERY MINOR RIB
900 FOAM CLOSURE
FOUR REQUIRED PER PANEL
5
4
3
3
3
2
2
1
FIELD FILL WITH COMPRESSIBLE
INSULATION OR FIELD FOAM WITH
2-PART URETHANE (NOT BY
KINGSPAN)
SET IN BUTYL TAPE
TOP AND BOTTOM
1
4
" - THROUGH FASTENER
WITH NEOPRENE WASHER
(AS REQUIRED FOR WIND
LOAD)
INSIDE RIDGE TRIM
NOTE: # 'S REFER TO SEQUENCE
OF INSTALLATION
SET IN CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEADS TO PANEL JOINT
RIDGE ASSEMBLY
900 SERIES ROOF PANEL
900 STANDARD ROOF CLOSURE SET
ROOF CLOSURE TO BE FIELD CUT FOR HIP AND VALLEY CONDITIONS
BUTYL TAPE
RIDGE CLOSURE TRIM (NOTCH AS NECESSARY AT HIGH RIB)
OUTSIDE CLOSURE
BUTYL TAPE
900 ROOF PANEL
COMPLETELY FILL
VOIDS AROUND FOAM
CLOSURE AT BATTEN
RIB WITH SEALANT
(NOT BY KINGSPAN)
BUTYL TAPE
BUTYL SEALANT
COMPLETELY FILL
VOIDS AROUND FOAM
CLOSURE AT BATTEN
RIB WITH SEALANT
(NOT BY KINGSPAN)
BUTYL TAPE
RIDGE CLOSURE
ASSEMBLY
900 SERIES ROOF PANEL
CONTINUOUS
BUTYL SEALANT W/
MARRIAGE BEAD TO PANEL
JOINT
(2)
1
4
" - HEX HEAD
FASTENERS PER PANEL
CLIP
CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD TO VERTICAL
PANEL JOINT
POP RIVETS @ 8" O.C.
14 GA. GALVANIZED
HIDDEN CLIP
(1 PER PANEL, PER GIRT)
(SET CLIP IN BED OF BUTYL
SEALANT)
CONTINUOUS
BUTYL TAPE
16 GA. PAINTED SADDLE CLIP
INSIDE FOAM CLOSURE W/
BUTYL TAPE TOP, BOTTOM
AND SIDES
1
4
" - 14 X
7
8
" LOW PROFILE
TEK SCREWS @ 8" O.C.
LOW EAVE TRIM
1
4
" - THROUGH FASTENER
WITH NEOPRENE WASHER
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
HEAVY BEAD OF BUTYL
SEALANT AT LAP JOINT TO
MARRY BUTYL TAPE AND
SEALANT AT PANEL JOINT
BUTYL TAPE AT
LAP JOINT
COMPRESSIBLE
INSULATION OR FIELD
FOAM WITH 2-PART
URETHANE (NOT BY
KINGSPAN)
LOW EAVE W/O
GUTTER
900 SERIES ROOF PANEL
12"
1
2
"
4"
CONTINUOUS
BUTYL TAPE
GUTTER TRIM
EAVE CLOSURE TRIM
(PRE-ASSEMBLED TO GUTTER)
1
4
" - 14 X
7
8
" LOW
PROFILE TEK SCREWS @ 8" O.C.
GUTTER HANGER*
INTERMEDIATE
GUTTER HANGERGUTTER
HANGER
FOR SNOW LOAD AREAS, ADD
INTERMEDIATE GUTTER
HANGERS, TWO PER PANEL
MAXIMUM / AS REQUIRED
(LOCATE AT HIGH RIBS)
* LOCATE GUTTER HANGER AT EACH
"LAPPING" RIB
NOTE: STANDARD EAVE CUTBACK IS
3" MODESTO, 4
1
4
" DELAND
INSIDE FOAM
CLOSURE
CONTINUOUS
BUTYL TAPE
BUTYL TAPE AT
LAP JOINT
POP RIVETS @ 8" O.C.
CONTINUOUS
BUTYL SEALANT W/
MARRIAGE BEAD TO
PANEL JOINT
CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD TO VERTICAL
PANEL JOINT
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
COMPRESSIBLE
INSULATION OR FIELD
FOAM WITH 2-PART
URETHANE (NOT BY
KINGSPAN)
1
4
" - THROUGH
FASTENER
WITH
NEOPRENE
WASHER
HEAVY BEAD OF BUTYL SEALANT
AT LAP JOINT TO MARRY BUTYL
TAPE AND SEALANT AT PANEL
JOINT
(2)
1
4
" - HEX HEAD
FASTENERS PER
PANEL CLIP
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
(SET CLIP IN BED OF BUTYL
SEALANT)
LOW EAVE W/ GUTTER
900 SERIES ROOF PANEL
HIGH EAVE TRIM
RIDGE CLOSURE TRIM WITH
OUTSIDE FOAM CLOSURE SET IN
BUTYL TAPE TOP AND BOTTOM
W/
1
4
" - 14 X
7
8
" LOW PROFILE TEK
SCREWS BETWEEN EVERY
MINOR RIB
1
4
" - 14 X
7
8
" LOW PROFILE
TEK SCREWS @ EACH HIGH
RIB AND BETWEEN HIGH RIB
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
1
4
" - THROUGH FASTENER WITH
NEOPRENE WASHER
HEAVY BEAD OF BUTYL SEALANT
AT LAP JOINT TO MARRY BUTYL
TAPE AND SEALANT AT PANEL
JOINT
OUTSIDE FOAM CLOSURE
SET IN BUTYL TAPE TOP
AND BOTTOM
COMPRESSIBLE
INSULATION OR FIELD
FOAM WITH 2-PART
URETHANE (NOT BY
KINGSPAN)
(2)
1
4
" - HEX HEAD FASTENERS
PER PANEL CLIP
CONTINUOUS BUTYL SEALANT
W/ MARRIAGE BEAD TO PANEL
JOINT
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
(SET CLIP IN BED OF BUTYL
SEALANT)
POP RIVETS @ 8" O.C.
BUTYL TAPE AT
LAP JOINT
CONTINUOUS
BUTYL TAPE
HIGH EAVE
900 SERIES ROOF PANEL
1
4
" - 14 THROUGH FASTENER
WITH 1
1
8
" BONDED WASHER
RAKE FASCIA
1
4
" - 14 X
7
8
" LOW PROFILE
TEK SCREWS @ 8" O.C.
BUTYL TAPE
CONTINUOUS BUTYL SEALANT
SHEETING OR RAKE ANGLE
REQUIRED (NOT BY KINGSPAN)
POP RIVETS @ 8" O.C.
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
COMPRESSIBLE
INSULATION OR FIELD
FOAM WITH 2-PART
URETHANE (NOT BY
KINGSPAN)
(2)
1
4
" - HEX HEAD FASTENERS
PER PANEL CLIP
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
(SET CLIP IN BED OF BUTYL
SEALANT)
CONTINUOUS BUTYL SEALANT
W/ MARRIAGE BEAD TO PANEL
JOINT
RAKE
900 SERIES ROOF PANEL
FIE
LD
CU
T
BA
CK
*
UPPER VALLEY FLASHING
(FIELD BREAK FROM FLATSTOCK)
1
4
" - 14 X
7
8
" LOW PROFILE
TEK SCREWS 4" O.C.
(IN LOWS)
1
4
" - 14 X
7
8
" LOW PROFILE
TEK SCREWS W/O WASHER
SEE BELOW FOR
ADDITIONAL INFO.
1
4
" - 14 X
7
8
" LOW
PROFILE TEK SCREWS
W/O WASHER 18" O.C
COMPLETELY FILL
VOID W/ COMPRESSIBLE
INSULATION (NOT BY
KINGSPAN)
LOWER VALLEY
FLASHING (NOT BY
KINGSPAN) GAUGE TO
MATCH PURLIN
1
4
" - THROUGH
FASTENER WITH
NEOPRENE WASHER
VALLEY SUPPORT ("Z"
SHAPE) SET IN
BUTYL SEALANT
6
7
5
4
3
12
SEQUENCE OF INSTALLATION:
1 LOWER VALLEY PAN
2 "Z" SHAPED VALLEY SUPPORT
3 FILL VOID W/ INSULATION
4 INSTALL SECONDARY & UPPER VALLEY PAN
5 APPLY TAPE MASTIC TO TOP OF UPPER VALLEY PAN
6 CUT ROOF PANELS. REMOVE CUT BACK & FOAM AT HIGH RIB
7 FASTEN ASSEMBLY
* FIELD CUT ROOF PANELS FOR 4
1
4
" OR 3" CUTBACK. CUTBACK SIZE
TO MATCH THE EAVE CONDITION
FIE
LD
CU
T
BA
CK
FIELD CUT PANEL FOAM AT HIGH
RIB INSIDE FOAM CLOSURE AS
NECESSARY TO FIT HIGH RIB
LOCATIONS
16 GA. PAINTED
SADDLE CLIP
FIELD CUT INSIDE
FOAM CLOSURE SET
IN BUTYL TAPE TOP
AND BOTTOM
CONTINUOUS
BUTYL SEALANT
VALLEY CONDITION
900 SERIES ROOF PANEL
PURLIN
AND FLASHINGS
VALLEY SUPPORT STEEL
GUTTERS
AT VALLEY CONDITION
FIELD CUTBACK
HIGH RIB AT
PANEL JOINT
ROOF VALLEY PLAN
TO MATCH FACTORY
CUTBACK AT EAVE
CONDITION
4
1
4
" CUTBACK (DELAND)
3" CUTBACK (MODESTO)
V
A
L
L
E
Y
SL
OP
E
SLOPE
VALLEY ASSEMBLY
900 SERIES ROOF PANEL
CONTINUOUS BUTYL
SEALANT BOTH
SIDES OF TRIM W/
MARRIAGE BEAD TO
VERTICAL PANEL
JOINT
RIDGE CLOSURE TRIM WITH
OUTSIDE FOAM CLOSURE SET IN
BUTYL TAPE TOP AND BOTTOM
BASE TRIM W/ POP RIVETS
@ 8" O.C.
TRANSITION FLASHING
1
4
" - 14 X
7
8
" LOW PROFILE TEK
SCREWS AT EACH HIGH RIB AND
BETWEEN HIGH RIB
FIELD FILL WITH
COMPRESSIBLE
INSULATION (NOT BY
KINGSPAN)
KINGSPAN TO SUPPLY
FLAT STOCK MATERIAL
(FIELD BREAK BY OTHERS)
CONTINUOUS BUTYL SEALANT
WITH MARRIAGE BEAD TO
PANEL JOINT
16 GA. PAINTED SADDLE CLIP
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
STRUCTURAL FRAMING
W/ MIN. 3" BEARING
SURFACE FOR PANEL
FASTENING
(NOT BY KINGSPAN)
FOAM CLOSURE W/
BUTYL TAPE TOP
AND BOTTOM
(2)
1
4
" - HEX HEAD FASTENERS
PER PANEL CLIP
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
(SET CLIP IN BED OF BUTYL
SEALANT)
1
4
" - THROUGH FASTENER WITH
NEOPRENE WASHER
1
4
" - 14 X
7
8
" LOW PROFILE TEK
SCREWS BETWEEN EVERY
MINOR RIB
CONTINUOUS BUTYL
TAPE
CONTINUOUS BUTYL SEALANT
AT JOINT LOCATIONS
WALL TO ROOF
HIGH EAVE
900 SERIES ROOF PANEL
RIDGE CLOSURE TRIM WITH
OUTSIDE FOAM CLOSURE SET IN
BUTYL TAPE TOP AND BOTTOM
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO PANEL JOINT
FASTENERS TO CONCRETE
(NOT BY KINGSPAN)
POURABLE SEALANT
(NOT BY KINGSPAN)
FIELD CUT MASONRY FOR INSTALLATION OF FLASHING,
FILL VOID WITH SEALANT (NOT BY KINGSPAN)
COUNTER FLASHING
TRANSITION FLASHING
1
4
" - 14 X
7
8
" LOW PROFILE TEK
SCREWS AT EACH HIGH RIB AND
BETWEEN EACH HIGH RIB
1
4
" - THROUGH FASTENER
WITH NEOPRENE WASHER
FILL WITH
COMPRESSIBLE
INSULATION
(NOT BY KINGSPAN)
16 GA. PAINTED SADDLE CLIP
KINGSPAN TO SUPPLY
FLAT STOCK MATERIAL
(FIELD BREAK BY OTHERS)
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
FOAM CLOSURE W/
BUTYL TAPE TOP
AND BOTTOM
CONCRETE
MASONRY WALL
(NOT BY KINGSPAN)
1
4
" - 14 X
7
8
" LOW
PROFILE TEK
SCREWS BETWEEN
EVERY MINOR RIB
CONTINUOUS BUTYL
TAPE
CONTINUOUS BUTYL
SEALANT AT JOINT
LOCATIONS
CONCRETE WALL
TO HIGH EAVE
900 SERIES ROOF PANEL
CONTINUOUS BUTYL
SEALANT BOTH SIDES
OF TRIM WITH
MARRIAGE BEAD
TO VERTICAL
PANEL JOINT
BASE TRIM W/ POP RIVETS @ 8"-12" O.C.
TRANSITION FLASHING
FILL WITH
COMPRESSIBLE
INSULATION
(NOT BY KINGSPAN)
1
4
" - 14 X
7
8
" LOW
PROFILE TEK SCREWS
@ 8" O.C.
CONTINUOUS BUTYL TAPE
CONTINUOUS BUTYL SEALANT
1
4
" - THROUGH FASTENER
WITH 1
1
8
" BONDED WASHER
(AS REQUIRED FOR WIND LOAD)
RAKE ANGLE WITH
UP-TURNED LEG FOR
PANEL ATTACHMENT
(NOT BY KINGSPAN)
CONTINUOUS BUTYL
SEALANT AT PANEL
JOINT
(2)
1
4
" - HEX HEAD FASTENERS
PER PANEL CLIP
14 GA. GALVANIZED HIDDEN CLIP
(1 PER PANEL, PER GIRT)
(SET CLIP IN BED OF BUTYL
SEALANT)
WALL TO RAKE
900 SERIES ROOF PANEL
FASTENERS TO CONCRETE
(NOT BY KINGSPAN)
POURABLE SEALANT
(NOT BY KINGSPAN)
FIELD CUT MASONRY FOR INSTALLATION OF FLASHING,
FILL VOID WITH SEALANT (NOT BY KINGSPAN)
COUNTER FLASHING
TRANSITION FLASHING
1
4
" - 14 X
7
8
" LOW
PROFILE TEK SCREWS
@ 8" O.C.
BUTYL TAPE
1
4
" - THROUGH FASTENER WITH 1
1
8
" BONDED WASHER
(AS REQUIRED FOR WIND LOAD)
CONTINUOUS BUTYL SEALANT AT RAKE ANGLE TO
MASONRY WALL
CONTINUOUS BUTYL SEALANT
CONCRETE
MASONRY WALL
(NOT BY KINGSPAN)
FILL WITH
COMPRESSIBLE
INSULATION
(NOT BY
KINGSPAN)
RAKE ANGLE FOR
PANEL ATTACHMENT
AND FASTENER
(NOT BY KINGSPAN)
CONCRETE WALL TO
ROOF
900 SERIES ROOF PANEL