BECHTEL CORPORATION
POWER GLOBAL BUSINESS UNIT – CONTROL SYSTEMS ENGINEERING
ENGINEERING DESIGN GUIDETHERMOWELLS FOR POWER PROJECTReason for Revision: Issued for Incorporation of Lessons Learned
Prepared by:Checked by:Approved by:
INTRODUCTION
This design guide focuses on formulating a consistent approach to the selection anddesign of thermowells for power plant applications. Lessons learned and improvements in
thermowell design from past projects have been considered in the preparation of thisdesign guide. Thermowells that are not supplied by Bechtel, or are supplied as a part of mechanical supplier’s equipment, are generally not covered by this document. This guidediscusses both the selection and installation of the thermowell.
Additionally, the specification of isokinetic (constant velocity) sampling nozzles iscovered in this guide. Isokinetic sampling is a condition wherein the velocity of thesample entering the port or the ports of the sample nozzles is at the same velocity asthe velocity of the fluid in the main process pipe. This ensures the most representativesample is obtained for chemical analysis. These nozzles are very similar mechanicallyto a thermowell, and are typically procured as part of the thermowell purchase.
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 2/19
Electronic documents, once printed, are uncontrolled and may become outdated.Refer to the electronic documents in BecRef for current revisions.
Bechtel Confidential © Copyright Bechtel Corporation, 2002, 2007. All rights reserved.
3DG-J35G-00002-001 Page 2 of 20
TABLE OF CONTENTS
INTRODUCTION 1
1.0 LIST OF FIGURES 3
2.0 PURPOSE 4
3.0 CODES AND STANDARDS 4
4.0 APPLICATION 4
5.0 STANDARD THERMOWELLS 4
6.0 ISOKINETIC NOZZLES 5
6.1 SAMPLE CALCULATION 5
7.0 INSTALLATION DETAILS 7
8.0 STRESS ANALYSIS OF THERMOWELLS 7
9.0 MEASUREMENT CONSIDERATIONS 7
10.0 INSULATION 8
11.0 OTHER REQUIREMENTS 8
12.0 THERMOWELL FABRICATION NOTES 8
13.0 THERMOWELL MATERIAL SELECTION 9
14.0 REFERENCES 9
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 3/19
Page 3 of 20
1.0 LIST OF FIGURES
Figure 1 1” Threaded Thermowell Type T
Figure 2 1-1/4” Threaded Thermowell Type T
Figure 3 Machine Threaded Thermowell Type MT
Figure 4 Flanged Thermowell Type F
Figure 5 Weld-in Isokinetic Nozzle
Figure 6 MT Type Thermowell Installation
Figure 7 Thermowell Fittings Fabrication Details
Figure 8 T Type Thermowell Installation Detail
Figure 9 Thermowell Installation for 3” and Smaller Lines
Figure 10 Thermowell Installation for 2” and Smaller Lines
Figure 11 Typical Work Process Flow Diagram for Thermowells
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 4/19
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 5/19
Electronic documents, once printed, are uncontrolled and may become outdated.Refer to the electronic documents in BecRef for current revisions.
Bechtel Confidential © Copyright Bechtel Corporation, 2002, 2007. All rights reserved.
3DG-J35G-00002-001 Page 5 of 20
6.0 ISOKINETIC NOZZLES
Two types of isokinetic steam sample nozzles are recommended for Bechtel designedpiping. One is “MT” Type for line wall thicknesses more than 3/4-inch and the other isWeld-In type for line wall thicknesses equal to or less than 3/4-inch (refer to Figure 5).
Either type may be configured as multi-port isokinetic nozzles. These nozzles are to beinstalled at locations where the velocity profile across the pipe can be determined. Portsshall be located such that each port samples from an equal fraction of the cross-sectional area of the pipe being sampled. As the steam velocity varies across the pipesection, each port diameter must be sized to result in isokinetic sampling with theproper fraction of sample collected from each port. Sample ports shall be drilled cleanlyusing the standard drill size nearest to the calculated standard port diameter. The portinlet ends shall not be chamfered or rounded and the outlet ends shall be free of burrs.The smallest recommended port diameter is 1/8-inch. Port diameters less than this arenot recommended as they may be subject to plugging. Total port area shall bedetermined to maintain isokinetic sampling in the nozzle ports at the desired samplingrate. Following calculation per ASTM D1066 may be followed:
For determining port diameter, d = (a/0.7854N)1/2
For determining nozzle bore, b = (3a/1.5708)1/2
For determining Radii of port circles, r 1 = (D1/2) x (1/N)1/2
r 2 = (D1/2) x (3/N)1/2
r 3 = (D1/2) x (5/N)1/2
Where:
D1 = Pipe IDN = Total number of portsa = Total port area = Af/FA = Traverse area of Pipe = 0.7854 D1
2
F = Flow rate of fluid through pipef = Flow rate of total sample extracted
The number of sampling ports shall be four (4) for pipe ID 2 inches to 6 inches. Thenumber of sampling ports may be more for line sizes above 6 inches.
6.1 SAMPLE CALCULATION
Attachment on the following page is an example for determining the nozzle hole size for isokinetic samples. Note it is more accurate to use the center of equal area annuli to
determine port position.
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 6/19
Electronic documents, once printed, are uncontrolled and may become outdated.Refer to the electronic documents in BecRef for current revisions.
Bechtel Confidential © Copyright Bechtel Corporation, 2002, 2007. All rights reserved.
3DG-J35G-00002-001 Page 6 of 20
STEAM SAMPLE NOZZLE
Sample nozzle hole size for isokinetic flow
Pipe inside diameter inches 12Pipe area square inches 113.097
number of annuli needed 6
area /# of annuli + CC 16.157
Center circle "CC" diam. ins 4.536
Center of
annuli
Distance
ID to
center of
annuli
Annulus
OD ins
Total
annulus
area in^2
Fraction of
total area
in^2
Annulus
number
includes
circle
center next annuli 5.475 3.2625391 6.414 80.784 0.714
center next annuli 7.135 2.4324715 7.856 64.627 0.571
center next annuli 8.463 1.7682521 9.071 48.470 0.429
center next annuli 9.606 1.1967504 10.142 32.314 0.286center next annuli 10.626 0.6870769 11.110 16.157 0.143
center next annuli 11.555 0.2225397 12.000 0.000 0.000
Steam flow rate lbs/hr 83460
Pressure psia 82
Temperature °F 513
Specific Volume Ft^3/lb 6.9428083
Velocity feet per second 204.93738
Sample flow cc/min. 500Sample flow rate lbs/hr 65.956739
Insertion depth of nozzle 4.5
Number of sample nozzles 2
Pipe diam. at sample nozzle tip 3
By inspection # of holes 5
By inspection fraction of area 0.714
Considered steam flow lbs/hr 59590.44
Ratio steam flow to sample 903.47766
Covered area of pipe sq ins 80.751498
Area of each sample hole 0.0089379
Diameter of each sample hole 0.1066772
By inspection drill size #36 (.1065)
Mimimum nozzle center bore ins 0.337343
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 7/19
Electronic documents, once printed, are uncontrolled and may become outdated.Refer to the electronic documents in BecRef for current revisions.
Bechtel Confidential © Copyright Bechtel Corporation, 2002, 2007. All rights reserved.
3DG-J35G-00002-001 Page 7 of 20
7.0 INSTALLATION DETAILS
Refer to Figures 6 through 10 for installation of standard thermowells and isokineticnozzles. It is recommended that Type “MT” thermowells and isokinetic nozzles shouldbe installed in the pipe fabricator’s shop. Weld-in type isokinetic nozzles may be
installed in the field using half couplings. During installation of isokinetic nozzles, caremust be taken to ensure the ports face upstream. For installation details on “MT” and“T” type thermowells, refer to Figures 6 through 8. Figure 7 shows fabrication details for machine thread and NPT type thermowell fittings. For installation on line sizes 3-inchand smaller, install an expander to increase the line size to 4 inches as shown in Figure9 or install a tee at a 90 degree pipe bend as shown in Figure 10.
The location and installation details for thermowells and nozzles reside in Plant Designdocuments. Typical installations have been depicted in this guide for convenience.When feasible, the thermowells may be shipped directly to the piping fabricator. Shopinstallation by the fabricator is often more economical than field installation.
8.0 STRESS ANALYSIS OF THERMOWELLS
All thermowells must be analyzed and found to meet acceptable stress criteria prior tomanufacture. Current practice is to have the vendor provide the calculation of record.In-house assessment is also possible, normally using either the Brock or ASME PTC-19.3 methods. In-house verification of suspect applications is recommended to avoiditerating the design with the vendor, and to preclude later accidental installation of anunacceptable well.
While vendors routinely perform vibration analysis (vortex shedding frequency), thepressure boundary verification is sometimes omitted. For high pressure applications
(typical of supercritical plants), the pressure limit of the well must be verified. Confirmthe vendor includes this calculation prior to award.
Caution must be exercised regarding the location of thermowells. Normally, theaverage fluid velocity is entered into the data sheet, which is adequate for mostinstallations. However, vibration induced fatigue failures have occurred where the wellshave been located in a region of locally high velocity flows. For example, the well mustnot be placed downstream of a butterfly valve, where the fluid stream past the disc hasa higher than the average velocity (upon which the stress calculation is based).
9.0 MEASUREMENT CONSIDERATIONS
Bechtel experience has been generally successful using a minimum 3-inch immersionfrom pipe inner surface. PTC 19.3 provides equations for estimating measurementerror due to well conduction (“wall effect”), thermal radiation, low fluid velocity and
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 8/19
Electronic documents, once printed, are uncontrolled and may become outdated.Refer to the electronic documents in BecRef for current revisions.
Bechtel Confidential © Copyright Bechtel Corporation, 2002, 2007. All rights reserved.
3DG-J35G-00002-001 Page 8 of 20
aerodynamic heating. These effects usually require consideration only for unusualapplications.
10.0 INSULATION
Insulation thickness is project specific and is followed once released for project.Typically, the thermowell is dimensioned to extend about one inch beyond theinsulation.
11.0 OTHER REQUIREMENTS
Refer to the attached flow chart (Figure 11), which explains the typical work processfrom thermowell selection to preparation of data sheet and the requisition process.Refer to GBU Design Guide 3DG-J21-G0008 “User Instructions for Instrument DataSheets” for completion of data sheets.
12.0 THERMOWELL FABRICATION NOTES
Thermowell dimension and well material shall be specified on data sheet and surfacefinish shall be manufacturer’s standard. Tolerances are as follows:
Bore, “d” shall be 0.26 inch maximum to pass plug gauge of 0.254 inch OD.
Bore /OD eccentricity shall be +/- 10 percent of minimum wall thickness.
Bore depth shall be +/- 1/32 inch for depths to 30 inches.
Overall length, “L” shall be +/- 1/32 inch for lengths to 30 inches.
Insertion Length, “U” shall be +/- 1/16 inch for lengths to 12 inches and +/- 1/8 inch for lengths over 12 inches.
Head diameter shall be +/- 0.01 inch
Shank diameter shall be +/- 0.01 inch
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 9/19
Page 9 of 20
Tip diameter shall be +/- 1/32 inch
Tip thickness +/- 1/32 inch
Thermowells shall have the tag number and material on the well head. For testthermowells, provide 1/2-inch NPT brass plug with brass chain attached to head of wellby non-welding technique. Bore drilling may be performed either by twist drill or gundrill.
13.0 THERMOWELL MATERIAL SELECTION
Refer to Thermowell Fitting Material Selection Chart in Plant Design Standard 3DS-P72G-00009. The thermowell shall be of the same material as the fittings provided onthe pipe (e.g. threaded half coupling).
14.0 REFERENCES
1. Standard Practice for Sampling Steam ASTM D1066 – 97 (Re-approved 2001)
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 10/19
Page 10 of 20
1" THREADED THERMOWELL
TYPE T
1.375"
HEX
1/2" NPT
OR
NPSM
1" NPT
1" DIA.
SHANK
BORE= .260"
3/4" DIA.
1/4"
INSERTION
LENGTH= U
OVERALL
LENGTH= L
LAGGING
EXTENSION= T
3/4" WRENCH
FLATS
1"
Overall Length= U + T + 1.75"
FIGURE 1
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 11/19
Page 11 of 20
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 12/19
Page 12 of 20
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 13/19
Page 13 of 20
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 14/19
Page 14 of 20
1/4"1"
DIA.
U = 4 1/2 "
T=8"
1/2" SCH 160 x 6-1/2"END TO END
NIPPLE OF SAME MATERIAL OR
MACHINE END DOWN TO 0.840 O.D.
DRILL HOLES
TO
SPECIFIED
SIZE
CENTER BORE TO
SPECIFIED ID ±0.015"
SOCKET DIAMETER AND DEPTH TO ANSI
B-16.11
0.855± 0.010 DIA.
3.0" DEEPDIA
1.5" ±0.015"
WELD-IN ISOKINETIC NOZZLE
FIGURE 5
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 15/19
Page 15 of 20
SHOP INSTALL-
PROVIDE TEMPORARY PLUG AND TEMPORASHIPPING PROTECTION FOR THERMOWELL
SEAL WELD
PIPE THICKNESS
MORE THAN 3/4"
1 3/4" UN-8 MACHINE THREAD
1/2"
1/2"
1/8"
MT TYPE THERMOWELL INSTALLATION
FIGURE 6
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 16/19
Page 16 of 20
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 17/19
Page 17 of 20
NPT THREADS
FULL PENETRATION WELD, GAS TUNGSTEN.06
tn
tc
ARC WELDING (GTAW), NOT MANDATORY
tn = NOMINAL THICKNESS OF HALF-COUPLING WALL
tc = 0.7 tn OR 1/4 " WHICHEVER IS LESS
T TYPE THERMOWELL INSTALLATION DETAIL
FIGURE 8
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 18/19
Electronic documents, once printed, are uncontrolled and may become outdated.Refer to the electronic documents in BecRef for current revisions.
Bechtel Confidential © Copyright Bechtel Corporation, 2002, 2007. All rights reserved.
3DG-J35G-00002-001 Page 18 of 20
TYPE 1
FOR USE ON 3" AND SMALLER LINES
A
G
F
B
C
E
D
DESCRIPTION OF PARTS:
(A) STD THERMOWELL
(B) HALF-COUPLING
(C) ECCENTRIC OR CONCENTRICREDUCER 4" NPS TO RUN SIZE,BUTT WELDED, MATERIAL AS
PER PIPE CLASS SHEETS
(D) PIPE 4" NPS PER PIPE CLASS
(E) LINE PIPE, BUTT WELD
(F) SEAL WELD
(G) FULL PENETRATION WELD
PREFERRED ARRANGEMENT
1. VERTICAL LINES - CONCENTRIC
2. HORIZONTAL LINES - CONCENTRIC OR ECCENTRIC,
INSTALL WELL IN HORIZONTAL PLANE.
THERMOWELL INSTALLATION FOR 3" AND SMALLER LINES
FIGURE 9
8/8/2019 3DG-J35G-00002Thermowells for Power Project Test
http://slidepdf.com/reader/full/3dg-j35g-00002thermowells-for-power-project-test 19/19
BD
C
F
B
AE
TYPE 2
FOR USE ON 2" AND SMALLER LINES
DESCRIPTION OF PARTS:
(A) STD THERMOWELL
(B) BUSHING, THREADED TO SUIT
(C) THREADED TEE, MATERIAL ASPER PIPE CLASS SHEETS, SIZE2" NPS
(D) THREADED NIPPLE, USED IN
(E) REDUCING COUPLING
(F) INSERTION LENGTH (U = 3" MAX)
THERMOWELL OR LINE SIZE
CONJUNCTION WITH REQUIREDREDUCING COUPLING
THERMOWELL INSTALLATION FOR 2" AND SMALLER LINES
FIGURE 10