Previous Issue: 28 January 2004 Next Planned Update: 16 December 2014 Page 1 of 25 Primary contact: Anizi, Salamah Salem on 966-3-8760203
Copyright©Saudi Aramco 2009. All rights reserved.
Materials System Specification
32-SAMSS-029 16 December 2009
Manufacture of Fired Heaters
Heat Transfer Equipment Standards Committee Members Anizi, Salamah Salem, Chairman Bagawi, Jamil Jarallah, Vice Chairman Anezi, Mohammed Ali Dossary, Musfir Abdullah Fernandez, Gabriel Thomas Gahtani, Moraya Saif Guthami, Mohammed Mohsen Hamam, Ibrahim Hassan Harbi, Abdullah Mohammed Saeed Mansour, Khalid Mohammad Naffaa, Mahmoud Youniss Rumaih, Abdullah Mohammad
Saudi Aramco DeskTop Standards Table of Contents 1 Scope............................................................. 2 2 Normative References.................................... 2 3 Terms and Definition...................................... 4 5 Proposals....................................................... 4 6 Design Considerations................................... 5 7 Tubes............................................................. 6 8 Headers.......................................................... 7 9 Piping, Terminals and Manifolds.................... 7 10 Tube Supports................................................ 8 11 Refractory and Insulation............................... 8 12 Structures and Appurtenances....................... 9 13 Stacks, Ducts, and Breechings.................... 11 14 Burners and Auxiliary Equipment................. 13 15 Instrument and Auxiliary Connections.......... 16 16 Shop Fabrication and Field Erection............ 17 17 Inspection, Examination and Testing........... 19 18 Life Cycle Cost Evaluation........................... 22
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 2 of 25
Table of Contents
Appendix E – Centrifugal Fans for Fired Heater Systems..................... 24 Appendix F – Air Preheat Systems for Fired Process Heaters.................... 25
The following paragraph numbers refer to API STD 560, Fourth Edition, August 2007,
which is part of this specification. The text in each paragraph below is an addition,
deletion or exception to API STD 560 as noted. Paragraph numbers not appearing in
API STD 560 are newly added paragraphs inserted in numerical order.
1 Scope
(Exception) The scope of this specification covers the minimum requirements for the
process design, mechanical design, materials, shop and field fabrication, shop and field
testing, preparation for shipment, and field erection of direct-fired and pyrolysis
excluding radiant section fired heaters.
1.1 Any conflicts between this specification and other applicable Saudi Aramco
Materials System Specifications, (SAMSSs), Standard Drawings (SASDs),
or industry standards, codes, and forms shall be resolved in writing by Saudi
Aramco or it’s Representative through the Manager, Consulting Services
Department of Saudi Aramco, Dhahran.
1.2 Direct all requests to deviate from this specification in writing to Saudi
Aramco or its Representative, who shall follow internal company procedure
SAEP-302 and forward such requests to the Manager, Consulting Services
Department of Saudi Aramco, Dhahran
2 Normative References
Materials or equipment supplied to this specification shall comply with the latest edition
of the references listed below, unless otherwise noted.
2.1 Saudi Aramco References
Saudi Aramco Engineering Procedures
SAEP-302 Instructions for Obtaining a Waiver of a
Mandatory Saudi Aramco Engineering
Requirement
SAEP-1142 Qualification of Non-Saudi Aramco Personnel
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 3 of 25
Saudi Aramco Engineering Standards
SAES-A-112 Meteorological and Seismic Design Data
SAES-A-206 Positive Material Identification
SAES-B-054 Access, Egress and Materials Handling for Plant
Facilities
SAES-H-100 Painting Requirements for Industrial Facilities
SAES-N-100 Refractory Systems
SAES-N-110 Installation Requirements - Castable Refractory
SAES-N-130 Installation Requirements - Fireclay Bricks
SAES-N-140 Installation Requirements - Refractory Ceramic
Fiber
SAES-W-011 Welding Requirements for On-plot Piping,
Saudi Aramco Forms and Data Sheets
175-323700 Manufacture of Fired Heaters
7305-ENG Equipment Noise Data Sheet
NMR-7900 Non-Material Requirements for Fired Heaters
American Society of Mechanical Engineers/Boiler and Pressure Vessel
Codes
ASME B16.20 Metallic Gaskets Ring Joint and Spiral Wound
ASME B16.21 Non-Metallic Gaskets for Pipe Flanges
ASME B16.5 Pipe Flanges and Flanged Fittings
ASME B31.1 Power Piping
American Society for Testing and Materials
ASTM A297 Standard Specification for Steel Castings, Iron-
Chromium, and Iron-Chromium-Nickel, Heat
Resistant for General Application
American Institute of Steel Construction
AISC 325 Manual of Steel Construction
AISC 326 Detailing for Steel Construction
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 4 of 25
3 Terms and Definition
3.85 Design Engineer: The Engineering Company responsible for specifying on
the data sheet the thermal and mechanical design requirements for heaters.
3.86 Direct-Fired Heaters: Heaters used to provide heat primarily by
conductive heat by flame impingement used for heating asphalt or bunker oil
for loading or mixing.
3.87 Engineering Company: The company responsible for specifying the
design requirements for Heaters on the data sheet.
3.88 Heater fabricator: The Company responsible for manufacturing heaters in
accordance with the design requirements specified by the heater designer.
3.89 Heater supplier: the Company responsible for the design, materials,
fabrication, testing, preparation for shipment, of fired heaters in accordance
with this specification.
3.90 Hydrocarbon Service: Process streams of liquid or gaseous hydrocarbon
materials.
3.91 Pyrolysis Heaters: Heaters that provide heat for chemical reactions inside
heater tubes for cracking and have service descriptions of ethylene crackers
3.92 Reformer Heaters: to provide heat for catalytic chemical reaction and have
process description such as: steam (hydrogen) reformer.
3.93 Saudi Aramco Engineer: The chairman of standard committee, Consulting
Services Department, Dhahran.
3.94 Saudi Aramco Inspector: The person or company authorized by the Saudi
Aramco Inspection Department to inspect heaters to the requirements of this
specification.
5 Proposals
5.1 Purchaser’s Responsibilities
5.1.4 (Exception) The number of copies of drawings, data sheets, specifications,
data reports, operating manuals and installation instructions shall be in
accordance with Form NMR-7900, Nonmaterial Requirements.
5.2 Vendor’s Responsibilities
The Heater supplier is to supply the following additional information with
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 5 of 25
the proposal. This information is necessary and will be used to complete the
technical evaluation of the quotation. The quotation will be technically
unacceptable if any of the information required is not included.
(e) (Exception) A completed noise data sheet (Form 7305-ENG) with a
detailed description of acoustical design.
(k) Energy conservation recommendations including: use of air-preheats,
high-efficiency burners, etc.
5.3 Documentation
5.3.1 to 5.4 (Exception) Documentation shall be in accordance with Form NMR-7900.
5.5 Performance Guarantees
The following shall be guaranteed when heaters are operated at 100% of
design heat release and design excess air, with the feeds and fuels specified
on the data sheet and at the process and ambient conditions specified. These
requirements are in addition to any other guarantees detailed in the purchase
order or contractual documents.
(a) Flue gas emission levels at normal and design conditions
(b) Sound levels at all specified operating conditions shall not exceed
85 dBA one meter from the source.
(c) Efficiency as specified in the data sheet based on the procedures of
API STD 560.
(d) Maximum pressure drop as specified in the data sheet.
6 Design Considerations
6.1 Process design
6.1.6 The values of average heat flux densities shall be in accordance with process
licensor specified by the Engineering Company.
6.3 Mechanical design
6.3.13 A minimum 30 inch diameter manway shall be provided to heater/furnace
areas such as radiant section, convection tube banks and passes, areas of flue
gas breaching and stack, and air ducts or breaching.
6.4 Environmental
6.4.1 All fired heaters and their associated equipment shall be suitably designed
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 6 of 25
for outdoor operations in a desert climate where the atmosphere is salt laden
and highly corrosive and in accordance with the climatic data specified in
SAES-A-112.
6.4.2 Accessories provided for the heater which are exposed to direct sunlight
shall be designed for a temperature of 70°C.
6.5 Noise
6.5.1 The Engineering Company shall specify limits for the sound pressure levels
(SPL) at the designated locations, on Form 7305-ENG.
6.6 Emissions
6.6.1 Heaters shall be designed to operate in compliance with local environmental
regulations as detailed by the Engineering Company.
6.6.2 The Heater supplier shall calculate and guarantee emission rates of Nitrogen
oxides. The emission rates shall be expressed in PPMv at 3% O2 dry basis
when the heater is operated at its design rate firing the fuels specified. Flue
gas emissions (NOx, CO, particulates, hydrocarbons, etc.) will not exceed
the specified levels.
6.7 Decoking
6.7.2 A recommended procedure including steam and air rates shall be provided
by the Heater Supplier as part of the operating procedures.
7 Tubes
7.1 General
7.1.1 (Exception) Tube wall thickness for coils shall be determined in accordance
with the procedures set forth in API STD 530. Minimum design tube life
shall be 100,000 hours.
7.1.8 Heater coils and piping that contain steam and water shall be designed in
accordance with the Boiler and Pressure Vessel Code, ASME SEC VIII.
7.1.9 Where allowable stresses are not covered by the ASME Code or API RP 530,
data from a reliable published source may be used subject to approval of the
Saudi Aramco Engineer.
7.1.10 Minimum rupture coil design pressure shall be the maximum operating inlet
pressure plus 10% or plus 345 kPa (50 psig), whichever is greater.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 7 of 25
7.1.11 The radiant tubes shall be located with two nominal diameters minimum
spacing between centerlines of adjacent tubes.
7.1.12 spacing between the convection section walls or corbelling ends and the
closest tube centerline shall be one half of the horizontal tube spacing.
7.1.13 Provision shall be made to facilitate the removal and reinstallation of radiant
and convection tubes. A description of the removal and replacement
procedures shall be provided.
7.1.14 All crossovers, manifolds, and external piping shall be arranged so that they
do not interfere with tube removal.
7.2 Extended Surfaces
7.2.4 The method of protecting carbon steel and fins from corrosion, prior to
startup shall be specified by the Heater Supplier.
8 Headers
8.3 Return Bends
8.3.5 Inside diameter of fittings shall match that of the heater tube.
9 Piping, Terminals and Manifolds
9.1 General
9.1.9 Unless otherwise specified in the data sheet, Process coil inlets and outlets
shall be flanged. Minimum flange rating shall be ASME Class 300.
9.1.10 Terminal connections on steam and water coils shall be beveled for welding,
unless stated on the data sheet.
9.1.11 Swages shall be schedule 160 minimum taper bored.
9.1.12 Manifolds and associated piping shall be furnished as required to provide a
single outlet connection for each heating service.
9.1.13 Manifold thickness shall not be less than standard thickness.
9.1.14 Manifolds shall be sized so that the dynamic head in the manifold at the
point of maximum velocity is not more than 10% of the individual pass
pressure drop.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 8 of 25
10 Tube Supports
10.1 General
10.1.7 Keepers shall be provided on horizontal tube supports as required to prevent
tubes from becoming dislodged from the support.
10.1.8 Supports for horizontal tubes maximum straight tube overhang shall not be
more than six outside diameters.
10.1.9 Start-up, shutdown, and part-load operation shall be considered when setting
the design temperature.
10.3 Materials
10.3.3 Bolting used to tie tube support brackets or hangers to the structure shall be
stainless steel type 304H, as a minimum.
10.3.4 Carbon steel end tube supports shall be protected on the flue gas side by
castable insulation. Minimum thickness shall be 100 mm for convection
end-tube supports and 150 mm for radiant supports.
11 Refractory and Insulation
11.1 General
(Exception) The design temperature of the outside casing surfaces of radiant
and convection sections shall be determined in accordance with SAES-N-100.
11.1.5 (Exception) The design of refractory for heater floors shall be in accordance
with SAES-N-100.
11.1.13 The design and material selection of refractory systems shall be in
accordance with SAES-N-100.
11.1.14 Burner blocks shall be high-duty refractory laid in high temperature bonding
cement.
11.1.15 Expansion joints shall be provided around each burner.
11.2 Brick and Tile Construction
11.2.10 The design of brick and tile construction shall be in accordance with
SAES-N-100.
11.2.11 Burner tile for floor-mounted burners shall extend at least 2 inches above
floor refractory.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 9 of 25
11.3 Castable Construction
11.3.1 to 11.3.11 (Exception) The construction of castable refractory shall be in
accordance with SAES-N-100.
11.4 Ceramic Fiber Construction
11.4.1 to 11.4.21 (Exception) The design of refractory ceramic fiber insulation shall be
in accordance with SAES-N-100.
11.5 Multi-component Lining Construction
11.5.1 to 11.5.9 (Exception) Multi-component Lining shall be in accordance
withSAES-N-100.
11.6 Materials
11.6.1 & (Exception) Material selection for refractory and refractory anchors
11.6.2 shall be in accordance with SAES-N-100.
12 Structures and Appurtenances
12.1 General
12.1.1 (Exception) Structural steel shall be designed and detailed in accordance
with AISC M016 and AISC 326.
12.1.2 (Exception) Heaters shall be designed for wind and earthquake loads in
accordance with ASCE 7.
With reference to ASCE 7, the wind Category Classification to be used in
the calculations of wind loads shall be Category III, and the Seismic Hazard
Exposure Group to be used in calculations of earthquake loads shall be
Group III.
Wind pressures shall be assumed to act on the projected surface area of the
heater and shall include due allowances for platforms, ladders, piping,
insulation, and equipment supported from the heaters.
12.1.5 (Exception) The design metal temperatures of structures shall be the
calculated metal temperature plus 56°C, based on the maximum flue gas
temperature expected for all operating modes with an average ambient
temperature specified in accordance with SAES-A-112.
12.1.8 Additional structure shall be provided at the convection section ends above
the base platform level to support temporary scaffolding for maintenance.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 10 of 25
12.1.9 All removable panels and access doors shall be provided with an eye or
lifting lug suitable for use with a crane or cable lifting hook.
12.1.10 Designs shall provide for adequate ventilation of enclosed or partially
enclosed areas of the heater structure.
12.2 Structures
12.2.7 (Exception) The extent and thickness of fireproofing shall be specified by
the engineering contractor.
12.2.11 Heater structures which contain more than one heater shall be designed to
accommodate differential thermal expansion when one heater is operating
and the adjacent heater(s) is out of service.
12.2.12 All bolted connections for ducts, plenums, and header boxes shall be
provided with suitable gaskets to prevent air or flue gas leakage.
12.3 Header Boxes, Doors, and Ports
12.3.1 Header Boxes
(Exception) Housings shall have bolted removable sections or header box
doors. All removable panels are to be provided with an eye or lifting lug
suitable for use with a crane or cable lifting hook. Header box doors shall be
equipped with hinges, latches, and handles. Handles shall be designed so
that their external temperature does not exceed 50°C
12.3.1.6 Header boxes containing plug fittings shall be provided with threaded
couplings for drains and smothering steam connections.
12.3.1.7 Removable header box panels at ends of convection section shall be lined
with ceramic fiber blanket held in place by appropriate anchoring system as
internal insulation.
12.3.1.8 If return bends are located outside fireboxes, they shall be enclosed in steel-
plate housings.
12.3.1.9 Return header housings shall be internally insulated as required to meet the
casing temperature limitation.
12.3.2 Doors and Ports
12.3.2.7 Access doors shall be an airtight design.
12.3.2.8 Two explosion doors shall be furnished to relieve each combustion chamber
of a multi-cell heater with a common convection section having tubes
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 11 of 25
oriented parallel to the radiant tubes.
12.3.2.9 For radiant sections over 6 m high, a second elevation set of peep doors shall
be installed.
12.3.2.10 Peep doors shall be located so that tubes and burners are clearly observable.
12.3.2.11 Clear access shall be provided to the return headers without interfering with
working platforms or piping.
12.4 Ladders, Platforms, and Stairways
12.4.1 Additional Platforms shall be provided at the following locations:
(g) All access doors, observation and instrument connections
(h) All stack sampling connections
(i) All analyzer and analyzer connections
12.4.12 Walkways shall be provided to inter-connect platforms at each level.
12.4.13 Unless otherwise specified by the Engineering Company, stairways shall be
provided from grade to burner operating platforms as follows:
12.4.14 Heater coil vents, drains, sample, instrument, and chemical cleaning
connections shall be accessible from heater platforms or grade.
12.4.15 Stairs, ladders and access platforms shall be in accordance with SAES-B-054.
13 Stacks, Ducts, and Breechings
13.1 General
13.1.3 A pneumatically operated flue gas control damper shall be provided at the
base of each natural draft stack.
13.1.4 Maintenance blinds shall be provided in ducts to isolate air preheaters.
13.1.5 In order to avoid inversion and downwash, the flue gas stack exit velocity
under heater turndown conditions shall not be less than 4.5 m/sec.
13.1.6 Sections of ducts which must be removed for maintenance shall be flanged
and bolted.
13.1.7 All stacks shall be provided with a painter's rail, trolley, and halyard.
13.1.8 Insulation required for noise attenuation and weatherproofing for air ducts
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 12 of 25
and windboxes shall be included.
13.1.9 Duct fittings shall be provided with turning vanes as required for proper air
distribution and minimum pressure loss.
13.1.10 Air ducts shall be of welded steel plate construction.
13.1.11 Provision shall be made for expansion between air preheaters and connecting
ductwork.
13.1.12 Hanger and bracket supports for ducts are to be included.
13.1.13 If a forced draft fan is used, combustion air ductwork including forced draft
fan inlet and discharge ductwork, air ducts, and any additional features
required for operation shall be provided.
13.2 Design Considerations
13.2.14 (Exception) Heater stacks, ducts and breechings shall be designed for wind
and earthquake loads in accordance with ASCE 7.
With reference to ASCE 7, the wind Category Classification to be used in
the calculations of wind loads shall be Category III, and the Seismic Hazard
Exposure Group to be used in calculations of earthquake loads shall be
Group III.
Wind pressures shall be assumed to act on the projected surface area of the
heater and shall include due allowances for platforms, ladders, piping,
insulation, and equipment supported from the heaters.
Minimum design loads shall be in accordance with ASCE 7. All structural
steel shall be designed and detailed in accordance with AISC M016 and
AISC M013.
13.2.18 (Exception) The design metal temperatures of stacks, ducts and breechings
shall be the calculated metal temperature plus 50°C, based on the maximum
flue gas temperature expected for all operating modes with an average
ambient temperature specified in accordance with SAES-A-112.
13.5 Wind-Induced Vibration Design
13.5.3 (Exception) Spiral or staggered vertical plates shall be provided as required
by the design.
13.6 Materials
13.6.1 The top edge of the stack lining shall be protected with a Type 316L
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 13 of 25
stainless steel internal angle or other suitable means to prevent water
penetration between steel and lining.
13.6.2 The top 600 mm of the stack shall be Type 316L stainless steel.
13.6.3 As a minimum, the cable for trolley tracks and halyard shall be 18%
Chrome-8% Nickel stainless steel.
14 Burners and Auxiliary Equipment
14.1 Burners
14.1.23 Burners in natural draft heaters shall be specified to permit firing at burner
design heat release at 10% excess air for fuel gas and 20% excess air for fuel
oils and any fuel/oil gas combinations.
Forced draft burners shall be specified to permit firing at burner design heat
release at 10% excess air for fuel gas and 15% excess air for fuel oil or any
combination of fuel oil/fuel gas.
14.1.24 The selection of burners shall be based on verification of satisfactory
performance in the same or a similar service.
14.1.25 Burners shall be designed to fire all fuels with fuel combinations specified
on the data sheet.
14.1.26 A pilot for each burner shall be provided. The pilots shall burn continuously
while the heater is in operation.
14.1.27 Bottom fired heaters shall be arranged to provide sufficient head room,
consistent with easy operation of the burners. Sight holes shall be positioned
accordingly.
14.1.28 Burners shall be supported from the heater structure and burner blocks shall
be independent of the heater wall.
14.1.29 Burner tips shall be easily removable for maintenance during heater
operation.
14.1.30 Lighting ports shall be provided so that burners may be manually lighted.
14.1.31 Burner fuel and air controls shall be accessible from grade or platforms.
Means to view the burner and pilot flame during light-off and operating
adjustment shall be provided.
14.1.32 The weight of burner assemblies shall be stated on the burner assembly
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 14 of 25
drawing.
14.1.33 When a flame detector is specified, the detector mount shall be adjustable
for sighting, and be lockable.
14.1.34 Burner air registers shall be externally adjustable and removable during
heater operation. External position indicators shall be provided for burner
registers.
14.1.35 Burners gas rings or tips and oil guns shall be removable while the heater is
in operation.
14.2 Sootblowers
14.2.7 Soot-blowers shall be fully automatic with selected sequential control and
manual override capabilities for individual soot-blowers.
14.2.8 Each soot-blower shall be easily maintainable, with readily accessible
lubrication fittings at all required lubrication points.
14.2.9 The soot-blower manufacturers design shall be substantiated by at least two
years of experience in comparable service.
14.2.10 Soot-blower pipe work shall be arranged so that condensate buildup drains
away from the soot-blower head. Drain valves shall be interlocked with the
steam valve to ensure that upstream condensate is drained during warm-up
and prior to the operation of soot-blowers.
14.2.11 Pipe work and associated fittings shall be in accordance with ASME B31.3.
14.2.12 Automatic control shall be obtained via a programmable logic controller
(PLC) as designed and specified by the Engineering Company in accordance
with 34-SAMSS-830.
14.2.13 Automatic mode of operation shall incorporate the following functions:
(1) Enable the lockout of any soot-blower from the normal operating
sequence.
(2) Enable the sequence to be held at any point in the sequence by operator
intervention, and allow soot-blowers to operate in the manual or local
mode during that hold period. On reselection of the automatic mode,
the soot-blower sequence shall continue from where it was interrupted.
(3) On the initiation of any emergency stop signal, automatically retract
any operating retractable soot-blower and shut down the system to a
safe condition.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 15 of 25
14.2.14 The following are the minimum indications of system status that shall be
provided:
(1) The mode of operation selected
(2) When the system is running under automatic sequential control
(3) Individual sootblower in operation
(4) The direction of travel for individual retractable sootblower during
operation
(5) Steam system warm-up period is in progress
(6) Steam system warm-up period is completed
(7) Any sootblower(s) locked out of the normal operating sequence
(8) Open/closed positions of main supply valve
(9) Open/closed positions of individual heater steam supply shutoff valves
14.2.15 The following are the minimum indications of alarm status:
(1) Elapsed time
(2) Motor overload
(3) Steam pressure
(4) Out of sequence
14.2.16 The following shall be provided in the control rooms:
(1) Alarm and status indications
(2) Automatic and manual mode pushbuttons
(3) Soot-blower selector switches
14.4 Damper Controls
14.4.1 Include pneumatically operated dampers as required to control combustion
air and flue gas flows on heater arrangements with air preheaters and forced
or induced draft fans.
14.4.2 Pneumatically operated stack damper shall have an alternate means of
manual operation from grade level.
14.4.3 Stack damper shall be designed with a counterweight to prevent closing if
the cable breaks or the operating mechanism otherwise fails.
14.4.4 Stack dampers for natural draft shall be designed for clearance of 25 mm in
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 16 of 25
fully closed position. The damper controls shall be designed to prevent
automatic closure beyond 85% closed.
14.4.5 For installations where tight shut-off is required as in bypasses to air heaters,
etc. dampers shall close against seal.
14.4.6 Damper positioners, shall be included for all pneumatically operated
dampers. The necessary mechanical linkages shall be included between
dampers and positioners and limit switches.
14.4.7 All pneumatically operated dampers shall have the facility to vent the motive
air from the actuator and bypass the controller so that the damper can be
manually positioned.
15 Instrument and Auxiliary Connections
15.1 Flue Gas and Air
15.1.1 Flue-gas and Combustion-air Temperature
15.1.2.8 A metering venturi, airfoil section or multi-point mass flowmeters located in
the forced draft fan inlet or discharge duct, with taps suitable for airflow
measurement shall be provided. The device shall be located upstream of any
air heater. The system proposed shall be provided with sufficient upstream
and downstream straight lengths of duct to ensure accuracy of airflow
measurement.
15.1.3 Flue-gas Sampling
15.1.3.6 Sample connections shall be provided for oxygen and combustible analyzers
at the furnace exit, boiler, economizer, and air preheater outlet.
15.1.3.7 Multiple sampling connections shall be provided in the flue gas duct at the
convection outlet and air preheater to obtain flue gas analysis. Each
connection shall consist of a stainless steel nipple, valve, and plug with
provision for purging. The vendor shall identify the purging media and
submit the purging procedure in the proposal.
15.1.3.8 Connections for the measurement of opacity, particulate matter, sulfur
dioxide, nitrogen oxides, oxygen, and carbon monoxide shall be provided.
15.2 Process Fluid Temperature
15.2.1 (Exception) Thermowell connections on each pass at the outlets of
convection and radiant sections shall be provided.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 17 of 25
15.3 Auxiliary Connections
15.3.1 Purge-steam Connections
15.3.1.2 (Exception) Snuffing and purge steam connections shall be 2 inch NPS
minimum for combustion chambers and 1 inch NPS minimum for header
housings.
15.3.1.6 Additional connections for the following shall be provided by the heater
manufacturer.
(1) Connections for flame monitoring and scanning shall be provided.
(2) Connections for draft gages at fan inlet and discharge air outlet of the
air preheater, windbox, furnace, outlet, flue gas outlet of the air
preheater, and stack entry.
(3) Six equally spaced connections installed around the periphery of forced
draft fan outlet ducts for pitot tube traverse of airflow.
(4) High point's vents, low point drains, and test connections shall be
provided, as required, on all manifolds and piping.
15.4 Tube Skin Thermocouples
15.4.3 Tube Skin Thermocouples
Exception) As a minimum, provide four tube skin thermocouples per pass.
For the arbor type heater four tube thermocouples per cell. Thermocouple
locations shall be determined by the heater.
15.5 Burner Management Systems
All nozzles and instrument connections of the instrumentation system shall
be supplied by the Heater supplier if the burner management system is
supplied by others.
16 Shop Fabrication and Field Erection
16.1 General
16.1.5 The manufacturer shall shop-install sufficient braces, struts, and lifting lugs
to permit handling at the construction site with conventional slings or hooks
without damage to the equipment.
16.1.6 Temporary bracing shall be clearly identified as such.
16.1.7 The Heater supplier shall submit plans for handling and shipping heaters for
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 18 of 25
review and approval.
16.1.8 Each part of a heater which is shipped as separate pieces or shop assembly
shall be identified. This includes steel and refractory parts which must be set
in a specific location in the heater.
16.1.9 Drawings which show the location of each piece and the sequence of
erection shall be included.
16.1.10 Piece marks may be stenciled or painted on according to the manufacturer's
standard procedure except as follows:
(1) Paints containing lead, zinc, or any other metals which are detrimental
to pressure parts operating at elevated temperatures shall not be used
for marking.
(2) Acceptability of marking paint must be established by prior
satisfactory experience of the heater supplier.
(3) Die stamping of parts which will contain process fluids under pressure
or temperature is prohibited.
16.1.11 All austenitic stainless steel material shall be protected against salt water
spray during ocean shipment.
16.1.12 Heater structures shall be designed such that outside columns do not
interfere with the lift and setting of convection sections while maintaining
structural integrity.
16.1.13 Convection sections shall be fully preassembled before delivery to the
jobsite including complete box assembly, refractory, tube supports, and
tubes.
16.1.14 Mating flanges of boxed pieces shall be match punched for proper field fit up.
16.1.15 Crossover piping shall be prefabricated to minimize field welding.
16.1.16 Platforms shall be shipped in maximum frame sizes allowed by shipping
limitations.
16.1.17 Stack sections shall be shipped with lifting lugs.
16.2 Structural-Steel Fabrication
16.2.1 General Requirements
m) (Exception) Attachment of refractory anchors and tie-backs shall be in
accordance with SAES-N-110.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 19 of 25
16.3 Coil Fabrication
16.3.8 Fabrication of steam or water coils shall be in accordance with Boiler and
Pressure Vessel Code, ASME SEC VIII.
16.4 Painting and Galvanizing
16.4.1 (Exception) The type of coating and painting systems to be used shall be in
accordance with the data sheet and SAES-H-100.
16.4.5 Gasket contact surfaces shall not be painted.
16.5 Refractories and Insulation
13.5.8 (Exception) Refractory materials shall be installed in accordance with
SAES-N-110, SAES-N-130 and SAES-N-140 as applicable,
16.6 Preparation for Shipment
16.6.17 Prior to shipping coils are to be completely and thoroughly dried and cleaned.
16.6.18 Markings shall be done with water-soluble materials that contain no harmful
substances that would attack or harmfully affect coils at both ambient and
operating temperature. The marking materials shall be free of Lead, Sulfur,
Zinc, Cadmium, Mercury, Chlorine, or any other Halogens.
16.6.19 Flanged connections and all other machined surfaces shall be protected by a
coating, which is easily removed in the field. Flanges shall be fitted with a
steel or wood cover, 3 mm thick and neoprene gaskets.
16.6.20 Covers shall be securely attached by a minimum of four bolts equally
spaced. For ocean shipment, flanged connections shall also be covered with
heavy duty plastic bags securely taped to the nozzles.
16.7 Field Erection
16.7.7 Stainless coil material shall be covered, packaged for off-the-ground storage,
and plugged to prevent moisture from entering.
16.7.8 Heater radiant and convection sections shall be protected from atmospheric
moisture with all coil openings sealed.
17 Inspection, Examination and Testing
17.1 General
17.1.5 The responsibility for inspection rests with the Heater supplier in accordance
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 20 of 25
with the applicable Industry Standards and the requirements of this
specification.
17.1.6 Heaters manufactured in accordance with this specification are subject to
verification by the Saudi Aramco Inspector in accordance with Saudi
Aramco Inspection Requirements Form 175-323700.
17.1.7 All Nondestructive Testing (NDT) shall be performed in accordance with the
Heater Supplier’s written procedure prepared in accordance with
ASME SEC V with the scope of NDT and acceptance/rejection criteria as
defined by the referencing Code section and this specification.
17.1.8 Inspection procedures shall be established in accordance with ASME SEC V.
A written procedure for each inspection method and technique, including
acceptance criteria, to be used shall be submitted to the Saudi Aramco
Inspector for approval. Qualification of the procedure by the Heater supplier
may be required, as determined by the Saudi Aramco Inspector. Inspection
procedures in conformance with other standards are acceptable only with the
approval of the Saudi Aramco Inspector.
17.1.9 Written reports and evaluations of all inspections performed by the Heater
supplier shall be made and submitted to the Saudi Aramco Inspector, at a
frequency to be determined by the Saudi Aramco Inspector.
17.1.10 The Saudi Aramco Inspector shall have free access to the work at all times.
17.1.11 Saudi Aramco shall have the right to inspect the fabrication at any state and
to reject material or workmanship which does not conform to the specified
requirements.
17.1.12 Saudi Aramco reserves the right to inspect, photograph, and/or videotape all
material, fabrication, coating, and workmanship and any materials, equipment,
or tools used or to be used for any part of the work to be performed.
17.1.13 Saudi Aramco may reject the use of any materials, equipment, or tools that
do not conform to the requirements of this specification, jeopardize safety of
personnel, or impose hazard of damage to Saudi Aramco property.
17.1.14 All of the rights of Saudi Aramco and their designated representatives for
access, documentation, inspection, and rejection shall include any work done
by sub-contractors or sub-vendors.
17.1.15 The Heater Fabricator shall furnish, install, and maintain in a safe operating
condition all necessary scaffolding, ladders, walkways, and lighting for a
safe and thorough inspection.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 21 of 25
17.1.16 Additional inspection of any weld joint at any stage of the fabrication may
be requested by the Saudi Aramco Inspector, including re-inspection of
previously inspected joints. The Saudi Aramco Inspector also has the right
to request or conduct independent NDT of any joint. If such testing should
disclose non-conformance to the requirements of the applicable Code or this
specification, all repair and NDT costs shall be at the Heater Supplier’s
expense.
17.1.17 All NDT performed in the field shall be by personnel certified in accordance
with SAEP-1142. Personnel responsible for interpretation of NDT results
shall be certified in accordance with SAEP-1142.
17.1.18 All NDT on heater coils which are to be postweld heat treated shall be made
after postweld heat treatment.
17.1.19 All pressure and non-pressure welds shall be visually inspected where
accessible.
17.1.20 Prior to final inspection and pressure testing, the inside and outside of the
heater shall be thoroughly cleaned of all slag, scale, dirt, grit, weld spatter,
paint, oil, etc.
17.1.21 All appropriate safety precautions shall be taken for each inspection method.
17.1.22 All materials required to be other than, carbon steels, shall be alloy verified
in accordance with SAES-A-206.
17.2 Weld Examination
17.2.2.1 a) (Exception) Root and cover passes of all welds on austenitic alloy parts
shall be liquid penetrant examined.
17.3 Castings Examination
17.3.2 a) & b) (Exception) Radiographic testing of tube support castings shall be given
to any cracks or other indications exposed by liquid penetrant inspection that
exceed the quality requirements of ASME SEC I, PG-25.
17.3.2 c) (Exception) Areas of stress concentration in corners of castings, especially
at support lugs, shall be radiographically inspected. At least two spot
radiographs shall be taken of the lower flanges of each cast tube support
section.
17.4 Examination of other Components
17.4.2 (Exception) Refractory linings shall be inspected in accordance with
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 22 of 25
SAES-N-110, SAES-N-130, and SAES-N-140.
17.4.7 One random spot radiograph shall be made for each girth weld and one
random radiograph for each two vertical welds of a stack shell. In addition,
each vertical and circumferential welds intersection shall be radiographed in
the circumferential direction.
17.5 Testing
17.5.1 Pressure Testing
17.5.1.5 Coil assemblies shall be completely drained and dried immediately upon
completion of hydrotesting. If coil assemblies are not drainable,
demineralized water containing 1% Na2 CO3 (Sodium Carbonate) plus 0.5%
Na NO2 shall be used for hydrotesting. For tube coils manufactured from
stainless steel, the water shall not contain more than 50-ppm chlorides.
17.5.2 Refractory Testing
(Exception) Refractory materials shall be tested in accordance with
SAES-N-110, SAES-N-130, and SAES-N-140 as applicable.
17.5.4 Positive Material Identification
14.5.4.2 (Exception) All materials, except carbon steel, shall be alloy verified in
accordance with SAES-A-206.
17.6 Burner Testing
A production model of each burner type shall be test fired prior to shipment.
Test firing may be witnessed by the Saudi Aramco Inspector. A certified
test report indicating the test firing shall be provided.
18 Life Cycle Cost Evaluation
Unless otherwise approved by the Coordinator, Mechanical Engineering Division,
Consulting Services Department, Quotations for heaters shall be evaluated on the basis
of Life Cycle Cost (LCC) as explained in SAEP-341. This cost is composed of the
initial purchase cost of the heater(s) plus the present worth of the fuel consumption over
an assumed operating period of 15 years. The Life Cycle Cost of the Heater(s) shall be
determined using the following Life Cycle Cost spreadsheets:
LCC-024, Single Fuel Heaters
LCC-024A, Dual Fuel Heaters
The efficiency of the heater at 100% of the design heat releases shall be guaranteed. If
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 23 of 25
the actual efficiency during performance tests is found to be less than the guaranteed
efficiency, then the cost of the heater(s) shall be reduced by an amount equal to the
difference in fuel consumption (MMBTU/hr) for not meeting the guaranteed efficiency,
multiplied by the Evaluation Factor $-hr/MMBTU as given in the provided Life Cycle
Cost spreadsheets included with heater data sheet. The maximum reduction shall not
exceed 15% of the initial cost of the process heater(s).
Mathematically:
Single Fuel:
Efficiency Penalty = [actual efficiency – (guaranteed efficiency-0.01)] * L * EF
Commentary Note:
Efficiency values are in decimal representation. 0.01 in the equation is a 1% test tolerance allowed.
EF = PV * EC * AH
Dual Fuel:
Efficiency Penalty = Sum of Efficiency Penalty of all fuels
For each type of fuel the evaluation factor is defined by
EF = PV * EC * T
Where;
L = Heater Load (Duty) @ normal condition (MMBTU/hr) will be show
on the data sheet.
EF = Evaluation Factor ($-hr/MMBTU) will be shown on the data sheet
that goes with the quotation request
EC = Energy cost in $/MMBTU for each fuel
AH = Annual operating hours
= OF * 8760
OF = Operating Factor, equal 1
PV = Present value factor = 5.85 based on 15% discount rate expressed as a
decimal number and operating period of 15 years.
T = Operating time for each fuel type, in hours
Revision Summary
16 December 2009 Major revision.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 24 of 25
Appendix E – Centrifugal Fans for Fired Heater Systems
E.1 General
E.2 Design
E.2.1 General
E.2.1.2d Should the fouling characteristics of the fuel(s) demand a more stringent
design, the Fan Manufacturer shall submit the fan design criteria with
proposal.
E.2.1.15 Fans shall be designed for not less than the following conditions:
1) Mass flow rate at heater design case plus 10 %.
2) Static pressure through the heater plus 21%.
All the above are based on the average ambient temperature for FD fan
and stack temperature for ID fan.
E.2.1.16 Forced draft fans shall be located at ground level and designed to permit
easy access to the interior of fan casings and to allow easy removal of rotors.
E.2.1.17 Fans shall be supported on a common base plate with the fan driver.
E.2.1.18 Air intakes of fans located outdoors shall be provided with bird screen and
with means to avoid pickup of wind-driven sand. The inlet shall also be
designed to avoid wind effects on combustion airflow measuring devices.
E.2.1.18 Air intake and discharge ducts shall be provided with silencers as required
E.2.2 Fan Housing
E.2.2.4 The housing shall be of all-welded construction and shall be equipped with a
cleanout door and a 2 inch NPS drain. Housings shall be constructed with a
split-flanged bolted joint to allow for rotor removal.
E.2.5 Rotating Elements
E.2.5.9 Fans shall be furnished with inlet guide vanes/dampers and with a vane drive
arm for connection to operator. The drive arm connections shall be of the
ball-and-socket design (or approved equivalent) to minimize lost motion.
Document Responsibility: Heat Transfer Equipment 32-SAMSS-029
Issue Date: 16 December 2009
Next Planned Update: 16 December 2014 Manufacture of Fired Heaters
Page 25 of 25
E.3 Accessories
E.3.2 Drivers
E.3.2.11 Turbine drivers shall conform to the requirements of 32-SAMSS-009.
Motor drivers shall conform to the requirements of 17-SAMSS-503.
E.3.2.12 Drivers shall be as specified on the data sheet and shall be in accordance
with the specified electric power supply and steam conditions.
E.3.2.13 Geared drives shall be separately coupled units with a minimum service
factor of 1.5.
E.4 Examination, Testing and Preparation for Shipment
E.4.2 Fan Testing
E.4.2.4 Fans shall be tested by the Fan Manufacturer in accordance with
ANSI/AMCA 210-85 and no load, mechanical run test.
Appendix F – Air Preheat Systems for Fired Process Heaters
F.1 Scope
F.1.1 The Engineering Company together with the Heater supplier must evaluate
the need for air-preheating systems based on energy conservation in
accordance with the requirements of this Appendix. The design and
proposal will be technically unacceptable if an evaluation of a preheat
system based on energy conservation has not been provided.