ZONES SOFTWARE What needs to happen? Intelligent devices with intelligent control panels, allow almost unlimited flexibility through the use of Software
Intelligent devices with intelligent control panels, allow
almost unlimited flexibility through the use of Software
Zones!
Slide 5
WHAT IS A SOFTWARE ZONE? FIRST LETS DISCUSS WHAT ITS NOT! A
software zone is not a group of devices specifically wired together
to form a WIRED ZONE A software zone is not a geographical zone
such as a BUILDING OR A FLOOR ZONE
Slide 6
A SOFTWARE ZONE IS: A function within the control panel that
allows the programming of a variety of output responses based on
various initiating events known as: CBEs (Control By Event)
Slide 7
Word Association HOT TRUE ON HIGH ONE (1) ACTIVE COLD FALSE OFF
LOW ZERO (0) INACTIVE
Slide 8
A SOFTWARE ZONE HAS JUST TWO STATES: ACTIVE or INACTIVE
Slide 9
The control panel operates CBEs through Lists of ZONES.
Slide 10
A ZONE becomes listed when it is added to a device points ZONE
map through POINT PROGRAMMING
Slide 11
These lists are associations between INPUTS and OUTPUTS.
Slide 12
A zone (ZONE 47) mapped to a smoke detectors CBE list and the
same zone (ZONE 47) mapped to a NACs CBE list constitute an
association. BASIC EXAMPLE
Slide 13
Now, lets assume that the detectors goes into alarm. ZONE
47
Slide 14
The control panel during its polling cycle determines that the
detector is in alarm. ZONE 47
Slide 15
THE ZONE(s) IN THE DETECTORS CBE LIST NOW BECOME ACTIVE.
ZONE47
Slide 16
The control panel checks to see if there are any devices that
have ZONE (Z47) mapped to their CBE lists. The control panel
identifies the NAC as having ZONE (Z47) in its CBE list.
Slide 17
The control panel activates the NAC. 47 ZONE
Slide 18
(Note: The ZONE (Z47) did not activate the NAC)
Slide 19
Please note: THE DETECTOR AND THE NAC DO NOT HAVE TO BE ON THE
SAME (SIGNALING LINE CIRCUIT) SLC!!!!
Slide 20
INPUT / OUTPUT ASSOCIATION -- -- -- -- -- 01
Slide 21
Slide 22
9901
Slide 23
GENERAL ZONES THE NFS2-640 SUPPORTS 100 GENERAL ZONES
Slide 24
THE NFS2-3030 SUPPORTS 1000 GENERAL ZONES GENERAL ZONES
Slide 25
ZONE 00 GENERAL ALARM ZONE -- -- -- -- -- 0003
Slide 26
0003
Slide 27
HOW MANY ZONES CAN BE PLACED IN A POINTS CBE LIST?
Slide 28
NFS2-640 = FIVE NFS2-3030 = TEN
Slide 29
CBE LIST 5 POSITIONS NFS2-640
Slide 30
CBE LIST - 10 POSITIONS NFS2-3030
Slide 31
CBE List Activation! -- -- -- -- -- 90030925030834
Slide 32
NFS2-640 10 SPECIAL ZONES
Slide 33
ZF0INPUT OR OUTPUT PRESIGNAL (TIME) ZF1OUTPUT - SYS TROUBLE
(NOT AC LOSS) ZF2OUTPUT - SYS TRBL AC LOSS OR BROWNOUT ZF3OUTPUT -
SECURITY INPUT ACTIVE ZF4OUTPUT SUPERVISORY INPUT ACTIVE ZF5INPUT
SWITCHES TO OCCUPIED LEVEL ZF6 ZF7HOLIDAY LIST ZF8OUTPUT MARCH OR
TEMPORAL CODE ZF9PRE-ALARM
Slide 34
NFS2-3030 13 SPECIAL ZONES
Slide 35
ZF0INPUT OR OUTPUT PRESIGNAL (TIME) ZF1OUTPUT - SYS TROUBLE
(NOT AC LOSS) ZF2OUTPUT - SYS TRBL AC LOSS OR BROWNOUT ZF3OUTPUT -
SECURITY INPUT ACTIVE ZF4OUTPUT SUPERVISORY INPUT ACTIVE ZF5INPUT
SWITCHES TO OCCUPIED LEVEL ZF9PRE-ALARM (ALERT/ACTION) ZF10ALARM
VERIFICATION ZF11DRILL ACTIVE NORMAL AFTER RESET ZF12ACKNOWLEDGE 2
SECONDS NORMAL ZF13SIGNAL SILENCE 2 SECONDS NORMAL ZF14SYSTEM RESET
10 SECONDS NORMAL ZF15DISABLED EVENTS NORMAL AFTER ALL CLEARED