ZonePRO™ Modulating Thermostats. Technical Training July 10, 2006. Models and Features. Models with 1 output TB6980A1007 (Floating) TB7980A1006 (Analog 0-10V or 2-10V) Models with 3 outputs TB6980B1006 (1 st output is floating) TB7980B1005 (1 st output is analog 0-10V or 2-10V) - PowerPoint PPT Presentation

Citation preview

Page 1: ZonePRO™ Modulating Thermostats

ZonePRO™ Modulating Thermostats

Technical TrainingJuly 10, 2006

Page 2: ZonePRO™ Modulating Thermostats

2

Models and Features

• Models with 1 output- TB6980A1007 (Floating)

- TB7980A1006 (Analog 0-10V or 2-10V)

• Models with 3 outputs- TB6980B1006 (1st output is floating)

- TB7980B1005 (1st output is analog 0-10V or 2-10V)

- 2nd output can be configured for: Analog 0-10V Analog 2-10V 24V

- 3rd output is 24V only

• Features for all models- Automatic changeover (duct sensor required)

- Manual changeover (remote switch or relay required)

- Night setback

- Min and Max temperature setpoint stops

Page 3: ZonePRO™ Modulating Thermostats

3

Applications and Accessories

• Hydronic and pressure dependent VAV with or without reheat

• Non-programmable• Up to three outputs depending on model• Can be used for:

- Floating or Analog damper/valve actuator control

- Damper/valve actuator with duct reheat and aux heat (B models)

- Hydronic systems (room control, perimeter heating and cooling)

• Compatible accessories- R841 family of electromechanical relays

- 50014156-002 remote room sensor

- 50014157-001 duct temperature sensor

- 32004800-001 bare thermistor

Page 4: ZonePRO™ Modulating Thermostats

4

Terminal Connections

Terminal Description

12

24 VACCOM

Power supply

34

AN1COM Output 1

TB7980 models

34

OPENCLOSED

TB6980 models

56

T2/AN2T2/COM

Output 2 (TB6980B and TB7980B models)WARNING: Make sure SW6 is set to the proper setting (Triac or Analog)

78

T3T3

Output 3 (TB6980B and TB7980B models)

910

COMSENSOR

External sensor input. (For applications requiring an external sensor)

911

COMC-Over

Mode Changeover input (N.O contact).

912

COMNSB

Night Setback activation input (N.O. contact)

Page 5: ZonePRO™ Modulating Thermostats

5

Typical Applications

Damper control with electric reheat and auxiliary hot-water heating

TB6980B

Relay

24 VAC not COM

Page 6: ZonePRO™ Modulating Thermostats

6

Typical Applications

Damper control with electric reheat and auxiliary baseboard heating

TB7980B

Relay

Relay

Page 7: ZonePRO™ Modulating Thermostats

7

Typical Applications

Damper control with automatic changeover, electric reheat and central cooling

TB7980B

50014157-001

Relay

Page 8: ZonePRO™ Modulating Thermostats

8

Typical Applications

Temperature control of fresh air supply

TB6980B

Relay

50014157-001

Page 9: ZonePRO™ Modulating Thermostats

9

Typical Applications

Changeover and NSB inputs sharing the same 24-Vac transformer

TB7980B TB7980B TB7980B

Page 10: ZonePRO™ Modulating Thermostats

10

Modèle 1A2T

Application Default mode & output 1 type

Output 2 type Output 3 type Output 3 activation

NSB value Output 1 min.

opening

Maximum setpoint

Minimum setpoint

0 Internal sensor 0 Cool / 0-10V 0 Not used 0 Not used 0 100% 1 1°C (2°F) 0 0%

Can be set between 35°C (95°F) and "minimum setpoint + 1“

Default value is 35°C (95°F)

Can be set between 10°C (50°F) and “maximum setpoint -1“

Default value is 10°C (50°F)

1 Room 1 Heat / 0-10V 1 SSR 24 VAC

1 SSR 24 VAC 1 10% 2 2°C (4°F) 1 10%

2 Return 2 Cool / 2-10V 2 N.C. Valve 2 N.C. Valve 2 20% 3 3°C (6°F) 2 20%

3 Supply 3 Heat / 2-10 V 3 N.O. Valve 3 N.O. Valve 3 30% 4 4°C (8°F) 3 30%

4 Auto changeover

4 Mech. relay

4 Mech. Relay 4 40% 5 5°C (10°F) 4 40%

5 Limited cooling 5 SSR 3-32V 5 Contact 5 50% 6 6°C (12°F) 5 50%

6 SCR 0-10V 6 60% 7 7°C (14°F)

7 Act. 0-10V 7 70% 8 8°C (16°F)

8 Act. / 2-10V

8 80% 9 9°C (18°F)

9 90%

Default configuration

Configuration – TB7980B1005

Page 11: ZonePRO™ Modulating Thermostats

11

Modèle 1F2T

Application Default Mode Output 2 type Output 3 type Output 3 activation

NSB value Output 1 min.

opening

Output 1 opening

time

Maximum

setpoint

Minimum

setpoint

0 Internal sensor 0 Cool 0 Not used 0 Not used 0 100% 1 1°C (2°F) 0 0% 0 80

Can be set between 35°C (95°F) and “min setpoint + 1“

Default value is 35°C (95°F)

Can be set between 10°C (50°F) and “max setpoint -1“

Default value is 10°C (50°F)

1 Room 1 Heat 1 SSR 24 VAC

1 SSR 24 VAC

1 10% 2 2°C (4°F) 1 10% 1 90

2 Return 2 N.C. Valve 2 N.C. Valve 2 20% 3 3°C (6°F) 2 20% 2 100

3 Supply 3 N.O. Valve 3 N.O. Valve 3 30% 4 4°C (8°F) 3 30% 3 110

4 Auto changeover

4 Mech. relay 4 Mech. Relay

4 40% 5 5°C (10°F)

4 40% 4 120

5 Limited cooling 5 SSR 3-32V 5 Contact 5 50% 6 6°C (12°F)

5 50% 5 130

6 SCR 0-10V 6 60% 7 7°C (14°F)

6 140

7 Act. 0-10V 7 70% 8 8°C (16°F)

7 150

8 Act. / 2-10V 8 80% 9 9°C (18°F)

8 160

9 90%

Default configuration

Configuration – TB6980B1006

Page 12: ZonePRO™ Modulating Thermostats

12

Configuration menu TB6980B

output 1 default mode

Output 1 Activation

Page 13: ZonePRO™ Modulating Thermostats

13

Configuration menu TB6980BOutput 1 Modes

Menu setting TB7980 models TB6980 models

0 Cool / 0-10 V analog (max. of 10 min. refresh)

Cool(24 V tri-state floating)

1 Heat / 0-10 V analog (max. of 10 min. refresh)

Heat(24 V tri-state floating)

2 Cool / 2-10V analog (max. of 10 min. refresh)

3 Heat / 2-10 V analog (max. of 10 min. refresh)

Page 14: ZonePRO™ Modulating Thermostats

14

Configuration menu TB6980B

output 1 default mode Output 1 jumps at 100% if there is an instant 5°F difference

Output 2 Activation

Page 15: ZonePRO™ Modulating Thermostats

15

Configuration menu TB6980BOutput 2 Modes

Menu setting Description

0 Not used

1 24 VAC pulsed (triac) 1 sec. Cycle

2 24 VAC pulsed (triac) / 10 min. cycle / direct action (e.g., N.C. thermal valve)

3 24 VAC pulsed (triac) / 10 min. cycle / reverse action (e.g., N.O. thermal valve)

4 24 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical relay such as R841)

5 0-10 V pulsed / 1 sec. Cycle

6 0-10 V analog / 1 sec. Refresh (e.g., SCR controlled device such as re-heater)

7 0-10 V analog / max. of 10 min. refresh (e.g., valve)

8 2-10 V analog / max. of 10 min. refresh (e.g., damper)

Page 16: ZonePRO™ Modulating Thermostats

16

Configuration menu TB6980BOutput 3 Activation

output 1 default modeOutput 1 jumps at 100% if there is an instant 5°F difference

Output 2 jumps at 100% if there is an instant 11°F difference

Page 17: ZonePRO™ Modulating Thermostats

17

Configuration menu TB6980BOutput 3 Modes

Menu setting Description

0 Not used

1 24 VAC pulsed (triac) 1 sec. Cycle

2 24 VAC pulsed (triac) / 10 min. cycle / direct action (e.g., N.C. thermal valve)

3 24 VAC pulsed (triac) / 10 min. cycle / reverse action (e.g., N.O. thermal valve)

4 24 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical relay such as R841)

5 N.O. contact (The contact closes when output 1 reaches or exceeds set percentage)

Page 18: ZonePRO™ Modulating Thermostats

18

Configuration menu TB6980BOutput 3 Activation “Contact Mode”

output 1 default mode

Page 19: ZonePRO™ Modulating Thermostats

19

Configuration and Operation

• Configuration- Dip switches

Temperature display, F or C (SW1) Access mode (SW2) Output 2 type (SW6)

• This sets output 2 type (analog or triac)

• Operation- Backlight (on for 12 seconds)

- Temperature setting by 1° increments (2°F in changeover)

- Output display (Hold Override for 4 seconds)

Page 20: ZonePRO™ Modulating Thermostats

20

Operation (continued)

• Operation- Changeover

Manual changeover (contact) Automatic changeover (9°F differential between duct and room) Night setback

• Override (2 hours)

• Error codes- E1 (internal sensor defective)

- E2 (internal sensor shorted)

- E3 (external temperature sensor defective or not connected)

- E4 (external temperature sensor shorted)

Page 21: ZonePRO™ Modulating Thermostats

21

System Components

OS # Dimensions Compatible Valves and Actuators Sensors and Accessories Replaces

TB6980A1007

2.7 x 4.6 x 1.0 in. (69 x 118 x

27 mm)

VC6930, VC6934, VC6936, ML6984A1006, ML6420, ML6161B2024, MN6105A1011

R841 Series of electromechanical relays, 50014157-001 air duct sensor, 50014156-002 space sensor, ST6008A1003 and

ST7009A1003 time clocks, 209651A wall plate

T6984A1059

TB6980B1006

T6984D1046, T6984E1043

TB7980A1006 VC7930, VC7934, VC7936, ML7984A4009,

ML7420, ML7161A2008, MN7505A2001

T7984A1057, T7984A1065

TB7980B1005

T7984B1055, T7984C1053

ML6984

ZonePRO

MN7505

VC7930ST7009

Page 22: ZonePRO™ Modulating Thermostats

22

Literature and Point of Purchase Materials

TECHNICAL LITERATURE

62-0238 Installation Instructions

63-4370 Guide Specification

63-8563 Actuator Cross Reference

SALES LITERATURE

63-9555 Brochure

n/a Flyer

All ZonePRO sales, technical and PowerPoint materials can be downloaded at customer.honeywell.com/buildings