BK SERIESYEAR ROUND MAXIMUM CONDENSING BOILER
burning diesel oil, kerosene, natural gas or liquid petroleum gas
OPERATING & MAINTENANCE MANUALBK50 - BK70 - BK100
90% and above A A
86% - 90% B
82% - 86% C
78% - 82% D
74% - 78% E
70% - 74% F
Below 70% G
1
Contents
1 Overview – laws, regulations and standards 2
2 Information 42.1 Identification(label) ���������������������������� 42.2 Warningsymbols �������������������������������� 42.3 Importantinformation ������������������������� 5
2.3.1 Updatingservice �����������������������������52.3.2 Actuality �������������������������������������������52.3.3BKFullyCondensingBoiler ����������52.3.4 Abouttheseoperatinginstructions ��5
2.4 Validity ������������������������������������������������ 52.5 Applicability ���������������������������������������� 52.6 Liabilitylimitations ������������������������������ 5
3 Safety instructions 73.1 Generalinformation ���������������������������� 73.2 Safetyguidelines �������������������������������� 7
3.2.1 Riskoffrostdamage �����������������������83.2.2 Corrosion,boilerdamage ����������������8
3.3 Norms,regulations ����������������������������� 83.4 Operationandmonitoring ������������������� 8
3.4.1 Burnerfaults/remoteunlocking �������93.4.2 Maintenance(servicing) ������������������9
3.5 Safetyinstallations ����������������������������� 93.5.1 Water-sidesafetyinstallations���������93.5.2 Gas-sidesafetyinstallations �����������93.5.3 Labelandoperatinginstructions �����93.5.4 Additionalsafetyinstallations ����������9
3.6 Wastedisposalandenvironmentalprotection ����������������������������������������� 10
4 Function and description 114.1 Functionandoperatingprinciple ������ 114.2 Boilerdescriptionanddimensions ��� 11
4.2.1 Trialrun,productioncontrol,qualityassurance ��������������������������11
4.2.2 Operatingcharacteristics,adjust-ment ����������������������������������������������11
4.2.3 Materials ��������������������������������������� 124.2.4 Safetyinstallations ����������������������� 124.2.5 Fluegassystem ��������������������������� 124.2.6 Combustionair ����������������������������� 124.2.7 Reservoir–servicewaterheater � 13
4.3 Unintendeduse �������������������������������� 134.4 Technicaldata ���������������������������������� 14
5 Delivery – transportation to installation site 16
5.1 Safetyinstructions ���������������������������� 165.2 Unloading,useofhoist ��������������������� 165.3 Completenessofdelivery ����������������� 16
6 Installation and connection 176.1 FullyCondensingBoiler ������������������� 176.2 Electricalconnection ������������������������ 176.3 Condensatedrainage ����������������������� 186.4 Handingoverandservicing
instructions ��������������������������������������� 18
7 Cleaning 207.1 Cleaningofcombustionchamber
andboiler ����������������������������������������� 207.2 Cleaningoffluegaspasses ������������� 217.3 Cleaningoffluegaspassesbox
(open) ����������������������������������������������� 217.4 Wetcleaning–neutralizationbox
andplasticheatexchanger �������������� 23
8 Terminal assignment and le-gend to Conform 6.0 26
9 Spare parts BK50, BK70 and BK100 28
10 ECconformitycertification 32
11 Guarantee 33
12 Notes 34
BK50/BK70 BK100
2
Overview–laws,regulationsandstandards
1 Overview – laws, regulations and standards
General information:Transportation,installation,mountingandelectri-calconnectionsshouldbedonebyacompetentperson.Hebearsresponsibilityforaproperimplementationoftheseworks.
BeforeinstallationoftheFullyCondensingBoiler,itisnecessarytoobtainpermissionofthelocalheatingequipmentinspectionboardorothercompetentauthorities.
Inordertopreventpenetrationofoxygenintotheclosedheatingsystem,itisadvisabletoperformasystemdivisionbetweenthefloorheatingandtheheatingsystembymeansofaheatexchanger.Itisadvisabletoinstallatemperaturesensorforthefloorheatingsystem,inordertoprotectpipesandfloorcoveringfromoverheating.
Sincecorrespondingregulationsvaryindifferentfederallands,werecommend,beforeboilerins-tallation,toconductconsultationswithcompetentauthoritiesandthelocalheatingequipmentins-pectionboard.Combustionairsupplyshouldbeperformedinsuchawayastoexcludesuctionoffluegasesfromheatingsystemsworkingonliquidorsolidfuels.
Thecombustionairsuppliedtotheunitshouldbefreefromchemicalsubstancessuchasfluorine,chlorineorsulphur.Thesesubstancesarecon-tainedinsprays,solventsandcleaningagents.Theymaycause,inspecificcases,corrosionofsomeunitcomponentsparticularlyinchimneys.Beforetheunitisputintooperation,itisneces-sarytocheckwithcompetentauthoritieswhethercondensateneutralizationisrequired.
Ifanychangesinthecontrolsystemoritssepa-rateitemsaremade,thentheguarantee,incaseofpossiblesubsequentdamages,shallbeinva-lid.Itisrecommendedtoinstallasafetyvalvewith“H”identificationintotheheatingcircuit.Themaximumpressureofthedischargepipeis3bars.Ifthedischargepipeofthesafetyvalveflowsintotheseweragenetwork,itisnecessarytointegrateadraintrap.
92/42/EWGEfficiencyguidelines
2006/95/EGElectricalequipmentdesignedforusewithincer-tainvoltagelimits
DIN EN 267:2011-02Fan-assistedoilburner
DIN EN 676:2003 + A2:2008Automaticforceddraughtburnersforgaseousfuels
DIN EN 677:1998-08Gas-firedcentralheatingboilers
DIN EN 14 471:2005Chimneys–systemchimneyswithplasticflueliners
DIN EN 15 034:2007-01Chapters 4.3.1 and 4.4Heatingboilers–condensingheatingboilersforfueloil
DIN EN 15 035:2007-05Chapters 6.1, 6.3.1, 6.3.3.1Heatingboilers–specialrequirementsforoilfiredroomsealedunits
DIN 18 160-1 Supplement 3Chimneys
DIN EN 12 828:2003Safety-relatedequipmentofheatingsystems
2006/42/EGMachineguidelines
DIN EN 303-1:2003-12Chapters 4.1.5.10 to 4.1.5.12Condensingheatingboilerswithfan-assistedburner
DIN EN 303-2:2003/12Chapters 3.2 to 3.5 andAppendices A and B
DIN EN 303-3:2004-10Chapters 5.4 to 5.5
3
Overview–laws,regulationsandstandards
DIN EN 304:2004/01Condensingheatingboilers–testcodeforhea-tingboilerswithfan-assistedoilburners
1 BImSchV (22.03.2010)Regulationonsmallfurnaces
ATV A 251Removalofcondensatefromchimneys
DIN EN 60 335-1:2010
DIN EN 60 335-2-102:2010Safetyofhouseholdandsimilarelectricalappli-ances
2004/108/EGElectromagneticcompatibility
Furthermore, for installation in Austria the following norms and regulations are valid:• ÖVE–Rulesandlocalrules
• Art.15aB-VG
• FAnlG–LawonfurnacesdatedJune12,2011
Switzerland:• Swissprovisions(BAFU)andcertificateofconformityforoilandgas(LRVArticle20)
• Environmentalprotectionlaw
• Waterprotectionact
• Waterprotectionordinance
• Recommendationforsewagedrainagefromcondensingheatingsystems
• SVGWgasguidelines
• SVGWwaterguidelines
• Recommendationconcerningtheminimumchimneyheight(aboveroof)
• VKFfireprotectionregulations
• SWKIguidelines
• SEVandESTIrulesI
BK50/BK70 BK100
4
Information
2 Information
2.1 Identification(label)
Product Id. Nr.Heating outputFlue gas temperatureMax. operation temperatureMax. operation overpressureWater contentElectrical connectionProtection classInstallation typeDegree of efficiencyCountry of destination
Unit category
Boiler number
0085
Oil
Giersch (G)Produkt ID-Nr.CE-0032BQ2719
CE0035CM10333 - 49 kW47°C / 54°C100°C3 bar110 l230 V~/50 Hz/350 WIP40C13/C33/C43/C53/C63/C8399%DE, AT, BE, CH, CZ, FR,GB, PL, SE, SK, LUsee identification plategasburnersee boiler base in front left
Giersch (GBZ)DIN CERTCO Reg.Nr.5G1049/11S
UNIT BK50 fully condensing boiler with fan
Gas
Weishaupt (WG) 33 - 49 kWWeishaupt (W)Produkt ID-Nr.CE-0036 0362/05
Produkt ID-Nr.CE-0085AU0353
MHG (M)Produkt ID-Nr.CE-0032BR2740
Firing capacity
33 kW 41 kW 49 kW Set on kW
Product Id. Nr.Heating outputFlue gas temperatureMax. operation temperatureMax. operation overpressureWater contentElectrical connectionProtection classInstallation typeDegree of efficiencyCountry of destination
Unit category
boiler number
Oil
CE0035CM10350 - 70 kW47°C / 54°C100°C3 bar110 l230 V~/50 Hz/410 WIP40C13/C33/C43/C53/C63/C8399%DE, AT, BE, CH, CZ, FR,GB, PL, SE, SK, LUsee identification plategasburnersee boiler base in front left
UNIT BK70 fully condensing boiler with fan
Gas
Weishaupt (WG) 50 - 70 kWWeishaupt (W)Produkt ID-Nr.CE-0036 0362/05
Produkt ID-Nr.CE-0085AU0353
MHG (M)Produkt ID-Nr.CE-0032BR2740
DIN CERTCO Reg.Nr.5G1034/08
Giersch (GL)
0085
50 kW 60 kW 70 kW Set on kW
Firing capacity
Product Id. Nr.Heating outputFlue gas temperatureMax. operation temperatureMax. operation overpressureWater contentElectrical connectionProtection classInstallation typeDegree of efficiencyCountry of destination
Unit category
Boiler number
Oil
CE0035CM10371 - 120 kW47°C / 54°C100°C4 bar200 l230 V~/50 Hz/480 WIP40C13/C33/C43/C53/C63/C8399%DE, AT, BE, CH, CZ, FR,GB, PL, SE, SK, LUsee identification plategasburnersee boiler base in front left
UNIT BK100 fully condensing boiler with fan
Gas
Weishaupt (WG) 71 - 120 kWWeishaupt (W)Produkt ID-Nr.CE-0036 0362/05
Produkt ID-Nr.CE-0085AU0353
MHG (M)Produkt ID-Nr.CE-0032BR2740
DIN CERTCO Reg.Nr.5G1034/08
Giersch (GL)
95 kW
0085
Firing capacity
71 kW 95 kW 120 kW Set on kW
2.2 WarningsymbolsIntheseoperatinginstructionsthefollowingwar-ningsymbolsareused:
Disregardingtheinstructionsmarkedwiththissymbolmayresultinadangerforpersonsandpropertydamage.
Attention
Thissymbolspecifiesinformationrelatedtoboileroperationaswellastocorrespondingorganizationalandtechnicalissues.
Information
5
Information
2.3 Important information
Careshouldbetakentoensurethat,depen-dingonthefuelandboilertype,theapprop-riateoperatingmodeisselected(SeeOpe-ratinginstructionforConform6.0andInitialcommissioningmanual).Failuretocomplywiththisprovisionwillresultinexpirationoftheguaranteeontheboilerbody!Withoutthesubmittedcommissioningreport,theguaranteeagreementwiththecompanyshallnotenterintoforce.
Information
Inordertopreventpenetrationofoxygenintotheclosedheatingsystem,itisrecommendedtoperformsystemseparationbetweenthefloorheatingandtheheatingsystem,bymeansofaheatexchanger.
2.3.1 Updating serviceTheseoperatinginstructionsarenotsubjecttomodifications!Themanufacturerreservestherighttomakeatanytimemodificationsandimprovementsintermsoffurthertechnicaldevelopment,toalltechnicaldata,informationandimages.AnyclaimsforafreemodificationorimprovementofalreadydeliveredFullyCondensingBoilersareexcluded.
2.3.2 ActualityAllreferencestolaws,regulations,guidelines,normsetc.mentionedintheseoperatinginstruc-tions,arecorrectasoftheperiodoftheinstruc-tions’drafting(may2012).
2.3.3 BK Fully Condensing BoilerThecopyrightfortheseoperatinginstructionsremainswiththecompany.
2.3.4 AbouttheseoperatinginstructionsForreasonsofclarity,theseoperatinginstruc-tionsdonotcontainalldetailedinformationwithregardtopossibleconstructionalandequip-mentversionsoftheFullyCondensingBoilerinquestion.Atthesametime,itisnotpossibletoforeseeeveryimaginablecaseofinstallation,configuration,operationand/ormaintenance.Intheeventyouwillrequireadditionalinformationorsomespecificproblemswillarisethatarenotaddressedindetailintheseoperatinginstruc-tions,pleasereferforinformationtoacompetentheatinginstallationcompanyordirectlyto thecompany.
2.4 ValidityTheseoperatinginstructionsarevalidonlywithrespecttotheFullyCondensingBoilermarkedwiththeproductionnumber(SeeLabel).Whenmakingrequestsandorderingspareparts,ple-asealwaysstatethesemodel(factory)numbers!TheseoperatinginstructionscontaininformationabouttheFullyCondensingBoileranditsitemsofequipment,insofarasthesebelongtothescopeofdelivery.Statementsaboutequipmentnotbelongingtothescopeofdeliveryareinten-dedpurelyforinformationalpurposes.Alegalclaimforthisequipment(options)isexcluded.Shouldmaterialsofthethird-partymanufacturersbeattachedtotheseoperatinginstructions(ope-ratinginstructionsofthirdparties),sothecompanycannotassumeanyliabilityfortheircorrectness,validity,technicaldataetc.
2.5 ApplicabilityAllinformationprovidedhereinwithrespecttotheworksafetyandenvironmentalprotectioncorrespondswithEU/ECregulationsand/orwiththeEquipmentSafetyAct(GSG)oftheFederalRepublicofGermany!Thecustomer/operatorshould,underhisorherownresponsibility• Considerthelaws,regulations,rules,gui-delines,technicalinstructionsetc.specifiedabove,asabasisforsafehandlingandmaintenance,
• Measuretheircompliancewiththelocalregulations,and
• independentlyinstallandadjustadditionalaccessoriesprescribedbythelocalcom-petentauthoritiesandcarryoutappropriateworksandmeasuresusingtheresourcesofaspecialistcompany.
2.6 LiabilitylimitationsThecompanytakesnoresponsibilityfordamagestothedeliveredFullyCondensingBoi-lercausedbythefollowingreasons:• Ignoranceoforfailuretocomplywiththeseoperatinginstructions.
• Insufficientlyqualifiedmaintenancestafforinadequatelyinstructedservicepersonnel.
• Naturalwearandtear!FordetailsseeDIN31051Part4,EN13306„Maintenanceterms“.
• FaultyornegligenthandlingoftheFullyCondensingBoilerand,inparticular,omis-sionoftakingmeasuresastosafeandproper
BK50/BK70 BK100
6
Information
◦ Installationandcommissioning, ◦ Operationandmonitoring,and ◦ Maintenance(servicing).
• Defectiveinstallationworksand/ordefectiveelectricalinstallation.
• Chemical,electrochemicalorelectricalinflu-ences.
• Forsubstantialthird-partyproducts,theliabilityofthecompanyislimitedtotheassignmentofliabilityclaimstowhichthecompanyisentitledagainstthesupplierofthethird-partyproducts.
Priortoeachcommissioningandmaintenancecycle,thefurnaceshouldbecheckedforgassidemalfunctionsandleakproofness.
Attention
7
Safetyinstructions
TheoperatinginstructionsshouldbepositionedvisiblyadjacenttotheFullyCondensingBoiler.Theconnectionandadjustmentoftheheatingsystemshouldbeperformedbyaqualifiedplum-ber.Theheatingtechnicianshouldfamiliarizetheoperator(s)oftheFullyCondensingBoilerwithitsfunctionsandservicing!IntheeventofanyfaultsordisturbancesintheoperationoftheFullyCondensingBoiler,pleasenotifytheheatingins-tallationcompany!
If you smell gas, there is a risk of explosion• Avoidopenfireandsparkformation(forexamplewhenturningonandoutlightsandelectricalappliances)
• Closetheshut-offgasvalveandnotifytheheatinginstallationcompany
If you smell exhaust fumes, there is a risk of poisoning• Switchofftheunit
• Opendoorsandwindows
• Notifytheheatinginstallationcompany
Ifthereisariskoffire• Immediatelyputoftheheatingemergencyswitch(incaseitisoutsidetheinstallationroom)
• Closetheshut-offgasvalve
• Intheeventofafire,usethesuitablefireextinguisher(fireclassBpursuanttoDIN14406)
Dimensionaldistancesfromtheboilertocom-bustibleitemsormaterialsshouldcorrespondtolocalfireprotectionnormsbuttheyshouldbeatleast200mm(seeFig.1).Otherwise,thereisdangerofafire.
3 Safety instructions
3.1 General informationTheseoperatinginstructionsarevalidexclusivelyforthetheFullyCondensingBoiler.Thestaffinchargeofinstallation,commissioningormain-tenanceshouldreadtheoperatinginstructionspriortostartingtheseworks.Therequirementscontainedintheseoperatinginstructionsmustbeadheredto.Intheeventofanon-compliancewiththeoperatinginstructions,theguaranteeclaimvis-à-visthecompanyshallexpire.
3.2 Safety guidelines
ForaproperandreliableoperationoftheFullyCondensingBoiler,itisnecessarytoobservethefollowingsafetyguidelines.
Attention
• Installation,commissioningandmainte-nanceoftheFullyCondensingBoilershouldbeperformedonlybyqualifiedandtrainedpersonnel.
• Workswithelectricalcomponents(forexample,adjustment)aretobeperformedonlybyqualifiedelectricians.
• Duringinstallationofelectricalequipment,theprovisionsofVDE(GermanAssociationforElectrical,Electronic&InformationTech-nologies)andofthelocalelectricitysupplycompanyarerelevant.
• TheFullyCondensingBoilermaybeope-ratedonlywithinthepowerrangeindicatedinthetechnicaldocumentationofthecom-panyandoftheburnermanufacturer.
• TheintendeduseoftheFullyCondensingBoilercomprisesitsexclusiveuseforhotwaterheatingsystemspursuanttoDINEN304andDINEN303-3.
• Itisstrictlyprohibitedtobypassorinanywayremoveorswitchoffcontrol,safetyandmonitoringequipment.
• TheFullyCondensingBoilermaybeopera-tedonlywhenitssystemsareintechnicallyperfectcondition.
• Malfunctionsanddefectswhichaffectsafety(ormayaffectit)shouldbefixedinapromptandexpertmanner.
• Defectivepartsandcomponentsmustbereplacedonlywithoriginalsparepartsofthecompany.
BK50/BK70 BK100
8
Safetyinstructions
combustion,underassistanceofaspecializedinstallingcompany.If,afteracleaning,repeateddustexposureshallstillbepossible,(forexample,duetospongychimneyjoints),taketheappropriatemeasures(forexample,cleanthechimney).
ModificationofthegasheatingsystemTheoperatormayundernocircumstancesmakechangesintheheater,pipesforgas,electricity,water,airsupplyandfluegas.Theseworksmaybeperformedonlybyahea-tingtechnician,toeliminatetheabovementionedhazards.
3.3 Norms, regulations• Theboilermustbeservicedinregularinter-vals.Werecommendtoconclude,forthispurpose,amaintenancecontract.
• TheFullyCondensingBoilersmaybeins-talledandoperatedonlyintheboilerandinstallationroomsasrequiredbylocalregu-lationsandguidelines(FeuAO)withrespecttofurnaces.
• ForAustriaarealsorelevanttheprovisionsoftheAustrianGasandWaterIndustryAssociationÖVGWTRGas(G1),BuildingregulationslawB-VG,Art.15AandalsotheLawonfurnacesFAnlG.
• Swissregulations(BAFU)andtheDeclara-tionofConformityforoilandgas(LRVArt.20)
BurnersFullyautomatedfan-assistedoilburnerspursu-anttoDINEN267.Fullyautomatedfan-assistedgasburnerspursuanttoDINEN676.Duringthecommissioningoftheburner,theappropriateoperatinginstructionsoftheburnerareessential.Astothecommissioningoftheburner,seecorre-spondingoperatingandassemblyinstructions.FuelELheatingoilpursuanttoDIN51603.NaturalgasinaccordancewiththeCodeofPracticeoftheGermanTechnicalAssociationforGasandWater(DVGW)G260/Iandalsopursu-anttolocalnorms.
3.4 Operation and monitoringPutintooperationtheFullyCondensingBoileronlyafterallworksrelatedtoinstallationandconnectionarecompletedand/oraftercomple-tionofpossiblepreventivemaintenancemeasu-res.Duringtheinitialcommissioningitisneces-sarytomonitortheautomaticprocessofcontrol
Fig. 1: Alateraldistanceofminimum600mmshouldbemaintainedeitherontheleftorontherightsideoftheboiler.
Aconnectinglineshouldbeleadtothechimneyasshortaspossibleandascending.Thisistheonlywaytoensuretheoptimumperformance.Thepipesshouldbecarefullysealed!Ifthefluepipesarenotproperlysealed,thefluegasmayescapeandcausetheriskofsuffocation.Itisadvisabletousethefluepipebendswithcleaningopenings,tobeabletocleanthefluepipes.
3.2.1 Risk of frost damageTheFullyCondensingBoilerandstoragewaterheaterarefrostprotectedthroughthecontrollingsystem.Sincetherisk(forexample,duringalong-lastingelectricalpoweroutage)offrostdamagecannotbeexcluded,theFullyConden-singBoilersandstoragewaterheatersshouldbeonlyinstalledinthefrost-protectedrooms.If,duringlongshutdownperiodsandwithinopera-tiveheatingsystem,theriskoffrostdangershallremain,aheatingtechnicianshouldemptytheFullyCondensingBoiler,reservoirandheatingsystem,inordertopreventwater-piperupturescausedbyfrost.
3.2.2 Corrosion,boilerdamageThecombustionairmustbefreefromdust(forexample,depositedsolidfuelsorconstructiondust)aswellasfromhalogenatedhydrocarbons(contained,forexample,inspraycans,solvents,washingandcleaningagents,paintsorglues).Otherwisepittingcorrosionoftheboilerbodyispossible.Ifthecombustionairisbeingsuckedinfrominoperativefireplaceorshaft,itisnecessarytoremoveresidualsofformeroilorsolidfuel
9
Safetyinstructions
thepowersupplyandonlybyaskilledelectri-cian.Beforecommencementofanyworksontheelectricalequipment,makesurethatthevoltageiscompletelyswitchedoff.Damaged,burned,frayedcablesaswellaslooseanduntightcableconnectionsmustbeimmediatelyreplacedbyaskilledelectrician.Intheeventofadefectivefuse,theymustbereplacedonlywiththeoriginalfuseswithprescri-bedamperage.
3.5 Safety installations
ThecommissioningoftheFullyCondensingBoilerwithoutaproperlyfunctioningsafetyinstallation(orwithanimproperlyfunctioningsafetyinstallation),isnotpermitted.
Attention
3.5.1 Water-side safety installationsSafetyinstallationspursuanttoDIN12828suchasthesafetyvalve,safetytemperaturelimiterandtemperaturecontrolleraredescribedindetail.
3.5.2 Gas-side safety installationsTothesesafetyinstallationsbelongsthefluegassafetytemperaturelimiter(STL).
3.5.3 LabelandoperatinginstructionsThelabelmustnotberemovedfromtheBKFullyCondensingBoiler;itshouldbekeptinawellreadablecondition.(Theoperatinginstruc-tionsmustbeplacedvisiblyinthesameroomwheretheboilerislocated).
3.5.4 Additional safety installationsThesesafetyinstallationsinclude,amongotherequipment.• Furnaceemergencyswitch
• Heatingoillockingdeviceinthefurnace
• Impermeablecovers/grillsinconformitywithDINEN294onthefluegassystem(uponarrangementasanoutdoorchimney)andontheairsupplyconnectionshouldbeinstalledbyatechnician,underhisownresponsibility,incompliancewithlocalregu-lationsandguidelines(FeuAO).
TheBKFullyCondensingBoilerservesexclu-sivelyforheatgenerationandalsoforwaterheatingpursuanttoDIN12828.Theflowtem-peratureismaximum80°C,thetechnicaldataofvariousboilertypesareindicatedonthecor-respondinglabels.Onlythoseliquidorgaseous
functionsandtocheckthetightnessoftheFullyCondensingBoileranditsconnections.
IntheeventofunusualoperatingperformanceinthefunctioningoftheFullyCondensingBoiler,forexample,malfunctionsorfaultsinenergysupply,theunitmustbeimmediatelyshutoff.
Attention
Determinethecauseoftheproblemorfaultandfixitinasafeandsecuremanner.Startre-commissioningonlyaftercompleteeliminationoffaults.
3.4.1 Burner faults/remote unlockingIncaseofaburnerdefectorfault,theredpushbuttoninthecontrolpanelwillflash.Pressthebuttonshortlytounlocktheburner.Shouldtheburnerfaultreappear,callaqualifiedspecialist.
Fig. 2: Donotpressthepushbuttonduringnormalburneroperation!
Pushbuttonofremoteunlocking
3.4.2 Maintenance (servicing)Itisstronglyrecommendedtoconsider,duringeachinspectionand/orscheduledmaintenanceworks,suggestionswithrespecttocausesoffaultsduetosuperfluousmeasuresand,inparti-cular,toboileropening,mostlyunnecessary.AllconnectionsattheFullyCondensingBoi-ler,burner,controlpaneletc.arepluggableorscrewable.WhenreplacingsafetyinstallationsmakesurethatthenewcomponentscorrespondtotheoriginalpartsandaretestedinconformitywithDINEN14597orDIN12828.Use only genuine components and parts deli-veredbythecompany!Duringanyoperations,refrainfromusingexces-siveforce–ifitgoesbeyondwhatisnecessarytoconnectordisconnectboltedconnections–thereisariskofmaterialdamage!Itisnotallowedtomoistentheplasticcompo-nents(secondaryheatexchanger,fluegassystem,hoses,sealsetc.)withoils,solvents,cleaningagentsorotherchemicalsubstances.Allworksontheelectricalequipmentshouldbeperformedonlyafterhavingdisconnecteditfrom
BK50/BK70 BK100
10
Safetyinstructions
non-recyclableresiduesshouldbedisposedofpursuanttotheGermanWasteManagementLaw(AbfG).Duringdisposalworks,usesafetygloves.
fuelsthatareindicatedintheorderconfir-mationmaybeusedasworkingmaterials.Thedefinitionismadeincompliancewith1.BImSchV(1stFederalGermanrulingonemissi-onscontrol)condensingboilers:theseareheatgeneratorswhichutilizebycondensation,asaresultoftheirdesign,theheatofvaporizationofwatervapourcontainedinfluegases.Thisdefini-tiondifferentiatestheheatgenerationwithutiliza-tionoftheheatofvaporizationofwatervapourinfluegasesfromtheheatgeneratorswithoutsuchutilization.
3.6 Waste disposal and environmen-tal protection
Thefollowingsubstanceswhichmayoriginateduringmaintenanceandrepairworksshouldbedisposedof–underpersonalresponsibilityoftheheatingtechnician:• Sediments,forexample,afterabreakdown
• Heatingoilrests
• Cleaningagentsandconsumables
• Solidwaste(replacedcomponents)ofalltypes
Alldisposalworksshouldbeconductedasprescribed,alsopursuantto1.BImSchVandGermanWasteManagementLaw(AbfG)andincompliancewiththeprovisionsoftheWaterResourcesAct(WHG)aswellaswithlocalandregionalregulations.Liquidwastesuchaspotentialtoxicsubstancescapableofendangeringgroundwater(WHG)shouldbecollectedinspecialclosedcontainersandallocatedfortheproperdisposal.Donotallowworkingmaterials(heatingoil)toinfiltrateintothegroundorseweragesystem.PotentialoilleakagesshouldbeimmediatelyboundinconformitywiththeAccidentpreventionregulations(UVV1.)orwipedout.Duringdisposal(dismantling/scrapping)oftheboiler,itscomponentsshouldbedividedinaccordancewiththeirmaterials.Aftercompletecleaningandemptyingoftheneu-tralizationboxandduringsubsequentdismant-ling,thefollowingmaterialsmayberecovered:• Metals,steel,malleableiron
• Insulationmaterials,mineralwool
• Plastics:polypropylene,PVC,cableinsula-tion
• electrical/electroniccomponentsThecomponentsshouldbecollectedsepa-rately,inaccordancewiththematerials;the
11
Functionanddescription
ofelectrical/electronicmeasuringandcontroldevices.Maximumambienttemperature: 40°CMinimumambienttemperature: 1°CTheinductedcombustionairshouldbedust-freeandofnormalquality(temperature,humidityetc.).TheBKFullyCondensingBoilerisoperativeandreliableprovidedthatitisusedproperly,theagreedoperationaldataareadheredtoandonlyprescribedfuelsareused.Itisnecessarytotakeintoconsiderationpossiblemalfunctions,if:• installation,adjustmentandsubsequenttrialoperationwerenotcarriedoutproperly.
• itisimpossibletomaintaintheover-pres-sureinthefurnace(resistanceinthefluegassystemorduringthefluegassuction).
• theheatexchangerwasnotfilledwithwateronthegassidepriortocommissioningorafteralongoperationalstandstill.
• thefueldoesnotcorrespondtotheusualspecifications.
• thesafetyinstallations,notwithstandingtheprohibitiononalterations,weremisplacedorbridged.
• theelectricalconnectiondataandnet-workconditionsdonotcorrespondtothemanufacturer’sdata.
• thefurnacewasputintooperationimmedi-atelyafterorduringfillingoftheheatingoilstoragetanks.
4.2 Boiler description and dimensi-ons
4.2.1 Trial run, production control, qua-lity assurance
TheinstallationoftheFullyCondensingBoilermustbeperformedbyaqualifiedstaff(aheatingtechnicianandanelectrician).Withoutthecom-missioningreport,theguaranteeagreementwiththecompanyshallnotcomeintoeffect.Thenintroductiontotheunit,trialrunandhando-vertotheoperatortakeplace.
4.2.2 Operating characteristics, adjust-ment
TheBKFullyCondensingBoilerisfittedwiththefullyautomaticelectroniccontrolsystemwhich
4 Function and description
4.1 Function and operating principleInthefurnaceoftheBK FullyCondensingBoiler,thecombustionheatfromoilorgasistransferredtothecombustionchamberwashedroundbytheboilerwaterandtotheprimaryheatexchangerwhichisconnectedtothecombustionchamberfromthewaterside.Thehotfluegasesarrivethen,undertemperaturesbelow85°C–thatis,abovethedewpoint–intothesecondaryheatexchangerandtheyarecooleddown,inaccordancewiththeexternalairtemperature,toabout30°C–48°C.Thedewpointofthefluegasistherebynotreachedandbothsensibleandlatent(hidden)heatisdelivered,throughsteamcondensation,tothesecondaryheatexchangerortothecombustionairpassingthroughitincounterflow.Thefluegasarrives,afterflowingthroughthesecondaryheatexchanger(counterflow)withverylowtemperaturetothefluegaspipe.Thefreshairnecessaryforcombustionissuckedinthroughtheannulargapoutsidethefluegaspipe(roomsealedoperation).Therequirednegativepressureisgeneratedbytheburnerfan.Priortoentryintothecombustionchamber,thecom-bustionairispreheatedinthesecondaryheatexchangeragainstthefluesgases,thuscontribu-tingtothehighefficiency.Thecondensateaccumulatedinthesecondaryheatexchangercontainsthemostpollutantsfromthecombustionfluegases.Itaccumulatesinthesecondaryheatexchangerandisthenfedthroughapipeconnectiontotheneutraliza-tionbox.Thecondensatepassesthroughthemineralgranulateandisthen,intheneutralizedcondition,dischargedintoawastewaterpipeorsewagesystem.Owingtotemperaturemonitoringwiththesafetytemperaturelimiter(STL)andtheimplementationofstandards,thefunctionoftheBKFullyCon-densingBoilerisself-retainingoverthewholecombustiongaspath.
Theworkswhicharenotdescribedintheseoperatinginstructionsarereservedtothestaffofthemanufacturer.
Information
Functional criteriaTheambientconditionsintheinstallationroomoftheBKFullyCondensingBoilermustnotexceedthenormalvaluesfortheoperation
BK50/BK70 BK100
12
Functionanddescription
• controlstheoperatingperformanceincon-formitywiththeheatdemandoftheheatinginstallation,and
• assafetycircuit,canshutdowntheintheeventofanymalfunctionsonthewaterorgasside.
• Thepressuretransmitterservesforthefunregulationandcontrol.
TheConform 6.0controlsystemisintegra-tedintheFullyCondensingBoiler.Whenstudyingtheinformationintheseoperatinginstructions,pleasealwayscomparetheindica-tedtypedesignationwiththedataonthecontrolpanelofthedeliveredboiler.
Thesystemhasintegratedfunctionsfor:Boiler temperatureTheboilertemperatureismaintainedbywayofswitchingtheburneron/off–atsome55°Cto80°C,butalways>55°C(seealsotheoperatinginstructionsofthecontrolsystem).HeatingcircuittemperatureThetemperatureattheheatingcircuitflowisregulatedthroughcontrolsystemtothepreselec-tedvalue.Itispossible,byvirtueoftheoperatingsoftware,atanytimetolowerortopredeterminetheheatingcircuittemperature(operatingmodeselection).Service water temperatureThewatertemperatureintheseparatereservoirforservicewaterheating(reservoiroption)ismaintainedbywayofswitchingon/offtherespec-tiveservicewaterpumpatthelevelpresetinthecontrolsystem.Thisprocessisinterruptedifthereturnboilertemperaturefallsbelow50°C(boilerprotection).Flue gas temperatureThefluegastemperatureismonitoredbytheSTL90°Clocatedinthesecondaryheatexchanger.AmbienttemperatureregulationTheambienttemperatureandthetemperatureoftheheatingcircuitflowarerecordedbysen-sorsanditiscompared,bymeansofthecontrolsystem,withthepredeterminedheatingcircuittemperatureandthesetbacktemperature;ifnecessary,itisbeingcorrected.
4.2.3 MaterialsThecomponentsofthe BK FullyCondensingBoilercorrespondtothematerialrequirementsandthetestprotocol.• Theprimaryheatexchanger
◦ SteelS235JR
◦ ConnectingpiecesofseamlesstubesinaccordancewithDIN1629
• Thesecondaryheatexchanger � PP/PP
• Thermalinsulation/outercover ◦ 3-sidedmineralwool80mm ◦ Front–mineralwool40mmwithcoatingintegratedintothefrontdoor
◦ Boilercasing–steelplate1,25mm,scre-wedtogetherandpowder-coated.
4.2.4 Safety installationsTheBK FullyCondensingBoilerisfittedpur-suanttoDINEN304andDINEN303withthefollowingsafetyinstallations.• Safetytemperaturelimiter(STL)boiler100°C.ThisSTLmonitorstheboilertempe-rature.
• Safetytemperaturelimiter,heatexchanger90°Cprotectsfromexcessivefluegastem-peraturetransfer.Whenapre-settempera-turethresholdisreached,thetemperaturelimitersshutdowntheheatgeneratorandlockit.Re-startingisonlypossiblewiththehelpofatool.
• ThesafetytemperaturelimitersaretestedandmarkedinaccordancewithDIN EN 14 597�
4.2.5 Flue gas systemThefluegassystemisusedtoremoveresiduallow-pollutionfluegaseswiththetemperatureof<60°C(monitoredbyatemperaturesensor)outsidethebuilding,overtheroof.Itismarkedwithitsownlabelcontaininginformationaboutthemanufacturerandtheapprovalnumber.Thefluegassystemshouldbeinstalledbyeffortsofalocallyapprovedheatinginstallercompany,withtheuseofpipesandfittingsmadeofplasticcerti-fiedforapplicationinconstructionandconnectedtothefluegasconnectingpieceoftheFullyCon-densingBoiler.Thecombustiongaspathoftheboilercorres-pondstothebasicstandards.
4.2.6 CombustionairThecombustionairistakendirectlyfromthefreeatmosphere;itispreheatinthesecondaryheatexchangerandsuppliedtotheburner.Ifthefluepipeisarrangedinaduct(unused,cleanedchimney),thentheremainingfreespaceinthisductisusedforcombustionairsupply.Inthecasethefreespacemaynotbeused,incompliancewiththelocalrequirements,sothe
13
Functionanddescription
4.3 Unintended useTheBKFullyCondensingBoilermaynotbeused:• forthefunctionsotherthanindicatedinChapter3.5.4.
• inothersystemconfiguration.
• withvaluesdifferentfromthoseindicatedonthelabel.
• withfuelsotherthanindicatedintheorderconfirmation(OC).
• withoutnegativepressureatthecombustiongaspathrequiredforoperatingpurposes.
Theriskforthepersons,theFullyCondensingBoilerandotherequipmentcarriestheheatingtechnicianortheoperatoroftheheatingsystem.
WithfluegasfanBoiler type BK50 BK70 BK100Fuel Heatingoil Gas Heatingoil Gas Heatingoil Gas
Fluegaspipe DN 80/125 80/125 80/125110/160
80/125110/160 110/160 110/160
Duct system
Pipelength(vertical) m 25 [28]28 [31]
15 [18]25 [28]
27 [40]30 [43]
27 [40]30 [43]
2030 [43] 20
30 [33]
Ductcross-section mm 135170
135170
135170
135170
170200
170200
Exterior wall system
Pipelength(vertical) m 25 [28]28 [31]
20 [23]30 [33]
40 [43]40 [43]
28 [31]40 [43] 40 [43] 30 [33]
AssessmentbasisConnectingpipeBK50,BK70,BK100: 100cmeffectiveheight,2,5moveralllength,3pipebends87°Exteriorwallsystem: AirsupplyoverconsolewithadditionalincomingairconnectionGeodeticinstallationheight: from1000mgenerallyonlywithfluegasfanWitheveryfurtherinstalledpipebend,thelengthofthefluegaswillbereducedby1m.ThistableisbasedonpracticalendurancetestsconductedbythecompanyandpartlyoncalculationsperformedbyCentrotecSystemtechnikGmbHcompany.
Flue gas pipe dimensions BK50, BK70 and BK100roomsealedheatingRSH[non-roomsealedheatingNRSH]
combustionairshouldbesuckedinthroughanopeningintheexternalwallandthecorrespon-dingpipeandthensuppliedtotheairinletofthesecondaryheatexchanger.Thecombustionairheatedfromcondensingfluegasesinthesecon-daryheatexchangercomesoutattheboilerfront-sidefromthesecondaryheatexchangerandpassesthroughaspiralhosetotheinletopeningoftherespectiveburner.
4.2.7 Reservoir – service water heaterTheconnectionoftheservicewaterheaterismadeattheinletandtheoutletoftheBKFullyCondensingBoiler.Aheatingtechnicianshouldinstallaservicewatercirculationpump.Therespectiveelectricalsocketsareavailableattheboilercontrolpanel(seecircuitdiagraminthedescriptionoftheConform6.0system).Asensorformeasuringtheservicewatertempera-tureisattachedtothecontrolsystem.
BK50/BK70 BK100
14
Functionanddescription
Fig. 3: Installationtypes(NRSH) B23,B33 (RSH) C13,C33,C43,C53,C63orC83pursuanttoDINEN15035
SupplyairFluegas
4.4 Technical dataTheoperatingdataforthedeliveredFullyCon-densingBoilermaybefoundonthelabelorintheorderconfirmation.ThepresentoperatinginstructionsareattachedtothedeliveredFullyCondensingBoilerinclu-dingtechnicaldata,dimensionsandinstructionswithregardtoinstallation,commissioningandmaintenance.
Boiler type BK50 BK70 BK100Fuel Heatingoil Natural
gasHeatingoil Natural
gasHeatingoil Natural
gasNominalheatoutput kW 33,0–49,0 33,0–49,0 50,0–70,0 50,0–70,0 71,0–120 71,0–120Firingcapacity kW 33,3–49,5 33,3–49,5 50,5–70,7 50,5–70,7 71,7–121 71,7–121CO2content* Vol.-% 13 9,5 13 9,5 13 9,5Fluegasmassflow g/s 14,9–22,1 13,9–20,6 22,5–31,5 21,0–29,4 32,0–54,0 29,8–50,4Fluegastemperature °C <48 <56 <48 <56 <48 <56Air-fluegas-systemØ mm 80/125 110/160 110/160Heatingwaterresis-tance(withΔT=20K) mbar 9,3 13,7 14
Residualconveyingpressureafterfan Pa 200 200 200
*CO2contentmeasuredinfurnace
Thethirdpartyoperatingmanualsand/orcir-cuitdiagramsoftheboilerequipment,controlsystems,supplementarydocumentation,expertassessmentsetc.shouldbetakenintoconsi-deration.Ifneeded,thesedocumentsmayberequesteddirectlyfromthe company.
15
Functionanddescription
Fig. 4: Boilerdimensions
Pos. Description BK50 BK70 BK100Watercapacity l 110 110 200Weight kg 470 470 746
1 Safetygroupconnection DN 25(1") 25(1") 25(1")2 heatinputpipe DN 32(5/4") 32(5/4") 50(2")3 heatoutputpipe DN 32(5/4") 32(5/4") 50(2")4 Fillinganddischargingcock DN 1/2" 1/2" 1/2"5 Expansiontankconnection DN 25(1") 25(1") 25(1")
7 Fluegasconnectionair-fluegas-system(AFGS)**
external-Ø mm 160 160 160internal-Ø mm 110 110 110
8 Condensatedrainage DN 40 40 40Allconnections-externalthread|**BK50:usereductionto125/80,BK70:ifnecessaryusereductionto125/80
Pos. Description BK50 BK70 BK100H1 Connectingdimensions,condensatedrainage mm 49 49 56H2 Connectingdimensions,AFGsystem mm 278 278 314H3 Connectiondimensionoptionalexpansiontank mm 471 471 576H4 Connectingdimensions,heatoutputpipe mm 1162 1162 1291H5 Connectingdimensions,heatinputpipe mm 1302 1302 1468H6 Overall height mm 1480 1480 1605
Overall height without casing mm 1480 1480 1605Overallheightwithoutcasing,withoutbase mm 1095 1095 1100
H7 Boilersupports(*height-adjustable) mm 20–40 20–40 20–40B1 Connectingdimensions,AFGsystem mm 232,5 232,5 335B2 Connectingdimensions,condensatedrainage mm 322,5 322,5 425B3 Connectiondimensions,filling/dischargingcock mm 452,5 452,5 580D1 Connectiondistanzposition4and5 mm 80 80 80B4 Connectingdimensions,safetygroup mm 322,5 322,5 425B5 Connectingdimensions,heatinputpipe mm 370,7 370,7 447D2 Connectiondistanzheater mm 140 140 177B6 Overall width mm 645 645 850
Overall width without casing mm 645 645 835L1 Connectingdimensions,AFGsystem mm 54 54 54L2 Connectingdimensions,safetygroup mm 377 377 339L3 Overall length mm 1520 1520 1710
Overall length without casing mm 1250 1250 1457Overalllengthwithoutcasing,withoutbase mm 1110 1110 1250
BK50/BK70 BK100
16
Delivery–transportationtoinstallationsite
5 Delivery – transportation to installation site
5.1 Safety instructionsDuringloadingorunloading,anytransportationtoinstallationsiteandalsoduringtemporarysto-rageorwarehousing,itisnecessarytocomplywithregulations,warningsandinstructionsrela-tedtosafetyguidelinesoftherespectivecountry.
5.2 Unloading, use of hoistTheBKFullyCondensingBoilerisbroughttoshippingcompletelyorpartiallyassembled.• Dangerofinjury!Manualunloadingortrans-portationofweights>35kg(ILO,Geneva)orone-timeliftingofmaximum>55kg(Acci-dentpreventionregulations/FederalMinistryofLabourandSocialAffairesofGermany)isforbidden.
• Foryourownsecurity,alwaysusesuitablehoistingdevicesand/orindustrialtrucksaswellasotherloadhandlingaccessorieswithadequateloadcapacity.BeforeloadingorunloadingtheFullyCondensingBoiler,takecaretoensuresufficientspaceforsecureplacingoftheboiler.
• Theloadhandlingaccessoriesmustbecarefullyattachedandsecured.Thereshouldbenodangerfromsuspendedloads!
• Fixingropesorstringstotheboilerequip-mentisforbidden!
• AlwayslifttheFullyCondensingBoileronlyvertically–neverpullitsidewards!
Neverstayorworkunderthesuspendedload.Mortaldanger!
Attention
TheBKFullyCondensingBoilershouldbehandled,duringunloading,transportationtoinstallationsiteortemporarystorage,withtheusualcareandprotectedagainstexternalroughtreatmentand/orfallingobjects.
5.3 Completeness of deliveryCheckthecompletenessofdeliveryimmediatelyuponitsreceipt(compareitwiththeorderconfir-mation/deliverynoteofthecompany).
Missingpartsshouldbepromptlyclaimedtothedeliveringtransportcompanyandthecompanynotified.
17
Installationandconnection
6.2 Electrical connectionThereliablemainsconnectionistobeperformedbyanexperiencedelectrician.
1� Thecharacteristicsofelectricalmainsshouldmeettherespectivelocalandnati-onallegalprovisions.
2� Aspowercables,chooseatleastonefle-xiblecablewithpolychloroprenecoating,inaccordancewith60245IEC45(forexample,NYM3x1,5m2).
3� Theearthwireshouldbelongerthanothercables.
Information
6 Installation and connection
6.1 Fully Condensing BoilerTheinstallationoftheFullyCondensingBoilershouldbecarriedoutunderconsiderationoftheactualinstallationguidelines.Inthiscase,itisnecessarytoinstallsafety-relatedequipmentinconformitywithDIN12828,forexample,asafetygroupmaximum3bar.Foroperationwithgasfanburners,thefollowingclassesofgasequipmentareutilized(pursuanttoDINEN437):
Thedistancesfromtheunittothewallsorcom-bustiblematerials(min.200mm)shouldmeetlocalfirepoliceregulations.Thelateraldistancesontheleftortherightsideoftheboilershouldbeminimum600mm,toensurethattheboilerdoorwiththeburnercouldbeeasilyswungout.Thefluegaspipemustbeleadtothechimneyasshortaspossibleandrising.Thefluegaspipesmustbecarefullysealedup!Itisrecommendedtousethefluegaspipeswithaninspectionope-ning,toenablecleaningandvisualinspectionofthefluegaspipes.TheFullyCondensingBoilerandthetankwaterheaterhavetostandhorizontallyorslightlyrisingtothebackinordertoensureacompletede-aeriation(usetheadjustablefeettolevelthem).
Country Classes of gas equip-ment
Gas connec-tion pressure
Germany I2ELL 20/25mbarAustria I2H 20mbarBelgium I2E+ 20/25mbarLuxembourg I2E 20mbarFrance I2E+ 20/25mbarSwitzerland I2H 20mbar
BK50/BK70 BK100
18
Installationandconnection
Fig. 6: Condensatetrap
siphon
siphon-likehopper
25mm
Boiler
6.4 Handingoverandservicing instructions
Itisessentialthattheinstallation,commissio-ningandmaintenanceoftheFullyCondensingBoilersarecarriedoutbyqualifiedandtrainedpersonnel.Duringtheinstallationandtrialrun,itisnecessarytocarefullychecktheconformityofsafetyinstallationswithDIN12828aswellasitsfunctioningandcorrectsettingandtoconfirmitinthecommissioningreport.Theheatingtechnicianshouldfamiliarizetheoperatorwiththeheatingunitanditsservicingandwithsafetyinstallationsandtheirfunctions!Theoperatormustplacetheoperatinginstruc-tionsfortheBK FullyCondensingBoilervisiblyinthesameroomwheretheboilerislocated�
Theoperatorisobligatedtoeliminatemal-functionsintheheatingunitand/oritssafety-relatedorelectricalequipmentonlybyqualifiedexperts.Moreover,hemustbeclearlyinformedabouttheinadmissibilityandpotentialdangerofimproperhandlingoftheunit.
Information
Theheatingtechnicianand/ortheoperatormustnotmakeduringinstallation,commissio-ningoroperationanychangesintheBKFullyCondensingBoiler,itssafety-relatedequip-mentorfactorysettings.
Attention
6.3 Condensate drainageThecondensateaccumulatedinthesecondaryheatexchangerisprocessedintheneutraliza-tionboxoftheBKFullyCondensingBoiler.Whendischargingthecondensateintosewageorwastewatersewer,itisnecessarytotakeintoaccountthewaterwayprescriptionsoftheres-pectivecountryandthestatutesoflocalwastedisposalcompanies!Theunitoperatormustobtaintheauthorization,bearinginmindtheAdvisoryleafletA-251„Condensationdisposalinchimneys”withpresentationoftheexpertassessment.Oninstallationofthesuppliedneu-tralizationbox,itisessentialtoannuallyloosenandrinsethegranulate.
Duringinstallationofthecondensatedrainagesystem,caremustbetakentoensurethatthecondensationwaterlevelof120mm(seeFig.5)isnotexceeded.Thecondensatedrainagesystemmaynotbealteredorclosed.ThesuppliedcondensatetrapDN40shouldbeplacedasclosetotheboileraspossible.Priortocommissioning,fillthesiphonwithwater.Ifinspecificsituationstheneutralizationboxisnotutilized,thecondensatedrainagesystemshouldbearrangedinsuchawaythatthesealingwaterheightisnotlessthan25mm(see.Fig.6).
Attention
Fig. 5: Condensatedrainage–thehighestlevel
120mm
19
Installationandconnection
Option 1 Neutralizationboxalignedwiththepermanentlycondensingboiler.
Option 2 Neutralizationboxatrightanglestothepermanentlycondensingboiler.
Option 3 Neutralizationboxparallelbeneaththepermanentlycondensingboiler(additionalHTtuberequired).
BK50/BK70 BK100
20
Cleaning
Step 2: Removethefasteningscrews/nuts(4pieces,widthacrossflats17)attheboilerdoorandopenthedoortogetherwiththeburner.Attention!Riskofburning–wearprotectivegloves!
Step 3: Removetheintakesocketattheplasticheatexchanger.
Step 4: Removethestainlesssteelinsert.Attention!Riskofburning–wearprotectivegloves!
7 Cleaning
Maintenanceandcleaningworksmayonlybecarriedoutbyauthorizedskilledpersonnel.
Attention
Ateachservicecheck-up,theFullyCondensingBoilershouldbeswitchedcurrentless(mainswitchoftheFullyCondensingBoilerandmainswitchoftheheatingsystem).Itisrecommendedtoplaceintheinstallationroom,asaprecautionarymeasure,asignboard:“Attention!Boilercleaning!Donotputonpower supply”.Pleaseuseduringtheseworksthepersonalsafetygeartoprotectyoureyes,breathingandhands.
7.1 Cleaningofcombustionchamberandboiler
Step 1: Removetheairintakehoseattheburnerandheatexchanger.Disconnecttheburnerplugandalsotheplug“Remoteunlocking“.
WhenopeningtheboilerdoorsduringthenextStep2,itisnecessarytoliftitovertheintakesocketoftheplasticheatexchanger!
Attention
21
Cleaning
7.3 Cleaningoffluegaspassesbox(open)
Step 1: Loosethethreescrewsontheinspectionlidattheleftorrightboilersideandremovethelid.
Step 2: Takeouttheinsulationinsert.
Step 3: Loosethetwowingnutsonthecleaningcover,donotunscrewthem.
Step 5: Cleanthecombustionchamberfromthetoptothebottomwiththespecialboilerbrush.Attention!Riskofburning–wearprotectivegloves!Sweepoutorvacuumawaytheresidues.
7.2 CleaningoffluegaspassesStep 1: RemovethetubulatorsfromthefluegaspassesonlywithBK50andBK70.Attention!Riskofburning–wearprotectivegloves!
Step 2: Cleaningofthefluegaspasseswithabrush.
BK50/BK70 BK100
22
Cleaning
Cleaningofthefluegaspassesbox(closing)Step 1: Closethecleaningcoveronthefluegaspas-sesbox.Putthethreadedpinwithaflatheadscrewdriverintoposition �
Step 2: Tightlyscrewthewingnut.
Step 3: Putintheinsulationinsert.Attachtheinspectionlidandcloseit.
Step 4: Putthethreadedpinswithaflatheadscrewdri-verintoposition andtakeoutthecleaningcover.
Step 5: Vacuumoutthefluegaspassesbox.Theabsor-berplateneedsnotberemoved.
23
Cleaning
Agranulateadditionwillberequiredattheear-liestafter1–2yearswhensome50%ofthegra-nulateareusedup.Afterapproximately4years,completereplacementofthegranulatewillberequired.Itisabsolutelyessentialtoloosenandrinsethegranulateannually.Cleaning
Fig. 8: overallviewoftheneutralizationboxwithsiphon
Step 1: Takeoffthesiphonbendandtheconnectiontubefromtheneutralizationboxandtheboiler.
Step 2: Rinsethesiphonbendandpipewithwater.
7.4 Wetcleaning–neutralizationboxand plastic heat exchanger
Whenthegranulatebecomescontaminatedorsolidified,theneutralizationeffectdrops(pollutantsinthecondensateareinsufficientlyreduced).Incertaincases,corrosiondamageonthewastewaterpipesystemcannotbeexcluded.
Information
Theneutralizationboxshouldberegularlymaintained(atleastonceinayear),particu-larlyiftheboilerisoil-fired.Washoutthefiltermaterialwithclearwater.Duringtheseworks,wearprotectiveglovesandsafetygoggles.Thecondensateresiduesmaybeetching.ObservetheprovisionsoftheattachedSafetydatasheet!
Attention
Fig. 7: neutralizationbox
1 Fill3kggranulateuniformlyintothemidd-lechamber.
2 Safetydischargedevice(limitsthewaterleveltomax.130mmintheeventofapumpfailure).Thereforeitisadvisabletoinstallcatchcontainerincombinationwithanelectronicalarmtransmitter(acces-sorieskit).Itwouldbepracticaltolayanattachedhosewithadownwardgradient.• Electricalfaultsensor036425• Condensatepump044958-01(notincludedindelivery)
12
BK50/BK70 BK100
24
Cleaning
Step 6: Pouroutthegranulateintoasuitablecontainer(atub).
Step 7: Cleantheneutralizationboxwithwater.
Step 9: Rinsethegranulatewithwater.
Step 3: Placeacontainerforcollectingrinsingwaterunderthecondensatedischargesystem.
Step 4: Rinsetheplasticheatexchangerwiththehelpofawaterhosewhiletheboilerdoorisopen,throughthefluegasopening.
Step 5: Opentheneutralizationbox.
25
Cleaning
Step 9: Refillthecleanedgranulateintotheneutraliza-tionbox.
Fillthegranulateonlyintothemiddlechamber(asshowninthepicture).
Information
Step 10: Againinstallthecoveroftheneutralizationbox
Step 11: Againconnecttheneutralizationboxtothecondensatedrainagesystem(bearinmindtheprovisionsofcl.6.4!).
Re-establishingofoperatingcondi-tion• Connectthecondensatedischargesystemwiththeneutralizationboxandthentothewastewatersystem.
• Filltheneutralizationboxwiththegranulateasdescribedabove(waterandgranulate).
• Mountthestainlesssteelcombustioncham-ber.
• Whenclosingthedoor,liftitovertheintakesockettightlysetupandfixitwiththenuts.
• Connecttheairintakehosetotheburnerandheatexchangerandplugtheconnec-torsoftheburnerandremoteunlocking.
Carryoutcleaningworksatleastonceayear.Whiledoingso,pleasekeepinmindtheappro-priateregulationsandnormsoftherespectivecountry,sewagewaterandwasteordinanceaswellasjobsafetyrulesandinstructions.
Information
Priortoeverycommissioningandduringeachmaintenanceinterval,pleasecheckthefurn-aceforpossiblegas-sidemalfunctionsandforleakproofness.
Attention
BK50/BK70 BK100
26
TerminalassignmentandlegendtoConform6.0
8 Terminal assignment and legend to Conform 6.0
01
23
45
67
89
Änderung Datum Name
Gepr.
Norm
Datum
Urspr.
Ers.d
Ers.f
Zust.
Bearb.
BU
Blatt
von
11
04.12.15
Regelung 6.0
40
41
42
47
48
49
50
43
44
45
46
51
52
53
54
55
5657
5859
0 - 10V
eBUS
eBUS
LN
N3
N4
N5
N6
14N
1615
N7
NL1
S3B4
T2T1
N
12
N
N
N
89
1011
1213
MP
1P
2P
3P
4P
5
+
-M1
+-M
2
+
-M3
T8T6
22
24 21
0 - 10V
P6
063936
A1
A2
12
14 11
Attention!Whenconnectinganexternalfeedingpump(P2),anadditionalrelay(Article060115)needtobeinterposed
27
TerminalassignmentandlegendtoConform6.0
Terminal as-signment
Standard assignment Designation
40 Nominalvalueoutput0–10V
41 eBus(controlpanel,servicetool,sequencecontroller,remotecontrol)
42Controlpanel Yes eBus(controlpanel,servicetool,sequencecontroller,remotecontrol)
43 Yes Servicewaterchargepump44 Yes Ambienttemperaturesensor
45 Buffertemperaturesensor,above(requiredforcascadeservice,buffermodeoperationandmixingcylinder)
46 Buffertemperaturesensor,centric/lower(Shutdownsensorfortricklecharging)
47 Yes* Secondarypre-flowsensor(*onlyforBK50–BK250)(notrequiredforcascadeservice,buffermodeoperationandmixingcylinder)
48 Yes Fluegastemperaturesensor49 Yes Boilertemperaturesensor50 Yes Boilerreturnflowtemperaturesensor51 Yes Flowtemperaturesensor,heatingcircuit152 Flowtemperaturesensor,heatingcircuit253 Collectorsensor54 Buffertemperaturesensor,lower/Collectorbuffersensor55 Nominalvalueinput0–10V
56/57 Yes 12VDCoutputpressuresensor(red/yellow/black)(notforBK20/BK30withoutfluegasfan)
59 Auxiliaryboilersensor
Terminal assignment Standard assignment Designation
L N Yes Mainsconnection1
(blue)(1)
2(brown)(3)
N(black)(2)
YesFluegasfan(notinthemodelBK20/BK30withoutfan)(Directconnection)(with4-poleWielandplug)
M
3 N Yes Servicewaterchargepump P1
4 N Yes FeedingpumpBK50–BK250electronic,constantspeed P2
5 N Yes CirculationpumpHC1 P36 N Yes Circulationpumpforservicewater P47 N CirculationpumpHC2 P5
8(black)
9(brown)
N(grey) Yes Internalmixer(8open+/9close-)
(BK50–BK250) M1
8 N Yes orinBK20/BK30solarpump/switchvalveoversolarpower
10 11 N Yes HC1mixer(10open+/11close-) M212 13 N HC2mixer(12open+/13close-) M3
14 N Yes Additionalrelay(Boilercirculationpump)(BK50–BK250)electronic,constantspeed P6
15 16 Yes STLboiler/fluegasL1 N T1 T2 S3 B4 Yes Burnerplug(1/2/gr/ye/3/4/5/6)
T8 T6 Burnerplugstage2(T6/T8)
(gr/ye)(gr/ye)
BK50/BK70 BK100
28
SparepartsBK50,BK70andBK100
9 Spare parts BK50, BK70 and BK100
29
SparepartsBK50,BK70andBK100
OrdernumberBK50 BK70 BK100
1 BoilerBoilermountedwithfluegasfan 037667-11Boilerpre-mountedwithoutfluegasfan 051705-11 051705-11 051707-11
1�1 Boiler 042868-10 042868-10 037667-101�2 Sealing 050773 050773 0507741�3 Cleaningcovercomplete 050627 050627 050628
2 Casingparts2�1 Inspectionlid 050650 050650 0506502.2a Lockingspigot 041535 041535 0415352.2b Fixationplate 041534 041534 0415342.2c Retainingcam 041533 041533 0415332�2 Sideelementleft,frontpart 041977-10 041977-10 037307-102�3 Sideelementleft,rearpart 041979-10 041979-10 037309-102�4 Sideelementleft,lowerpart 041978-02 041978-02 037308-032�5 Rearpanel,upperpart 037282-10 037282-10 037313-102�6 Rearpanel,middlepart 037283-10 037283-10 037314-102�7 Rearpanel,lowerpart 037284-10 037284-10 037315-102�8 Faceplate 037285-03 037285-03 037316-032�9 Mountingpanel 042855-11 042855-11 042854-112�10 Sideelementright,frontpart 041980-10 041980-10 037310-102�11 Sideelementright,rearpart 041982-10 041982-10 037312-102�12 Frontcover 036866-10 036866-10 036862-102�13 Sideelementright,lowerpart 041981-02 041981-02 037311-032�14 Boilerdoorcasing 036863-10 036863-10 036859-102�15 Doorinsulation2�16 Combustionchamberinsert2�17 Coveratthefront 037278-03 037278-03 037305-032�18 Coverattheback 037279-10 037279-10 037306-10
3 Baseparts3�1 U-formholder 040337-01 040337-01 039973-013�2 Basesidepartright 040331-01 040331-01 039967-013�3 Basesidepartleft 040332-01 040332-01 039968-013�4 Basecross-beamhead 040335-01 040335-01 039971-013�5 Basecross-beamrear 040336-01 040336-01 039972-013�6 Anglebracketright 040333-01 040333-01 039969-013�7 Anglebracketleft 040334-01 040334-01 039970-013�8 Absorberframe 050598 050598 050599
4 Othersheet-metalparts4�1 Mountingbracketleft 040330-01 040330-01 039966-014�2 Mountingbracketleft 040329-01 040329-01 039965-01
**:withoutpicture
BK50/BK70 BK100
30
SparepartsBK50,BK70andBK100
OrdernumberBK50 BK70 BK100
5 Component5�1 Heatexchanger 031662-02 031662-02 037420-025�2 Siliconsealstringforheatexchanger 044622 044622 0446245�3 Fluegasfanpre-assembled 031826-01 031826-01 031826-015�4 Protectivecoverformotoroffluegasfan 031124-01 031124-01 031124-015�5 Burner Seetheattachedburneroperating
instructions5�7 ConnectionpieceforAFGsystem 037340 037340 0373405�8 Boilersupports 035457 035457 0354575�10 Boilerdoor5�11 Collar 035459 035459 0354595�12 Collar 043462 043462 043462
6 Control,regulationelementsandsignallers6�1 Controlset** 041371-05 041371-05 041371-056�2 Control 042475-02 042475-02 042475-026�3 Frontpanel 042433-03 042433-03 042433-036�5 Safetytemperaturelimiter90°C 042314 042314 0423146�6 Safetytemperaturelimiter100°C 042315 042315 0423156�8 Powerbuttongreen0/1 042777 042777 0427776�9 Fuseholder(includingmicrofuseT10A5x20) 042776 042776 0427766�10 Controlunit 042476-01 042476-01 042476-016�11 Remoteunlockingpushbuttoncomplete 048252 048252 0482526�20 Differentialpressuretransmitterwithplug 042517 042517 0425176�21 Holdingbracket 042548 042548 0425486�22 Additionelrelay 060115 060115 0601156�23 Plug3/N(servicewaterchargepump)** 042576 042576 0425766�24 Plug4/N(feedingpump)** 042577 042577 0425776�25 Plug5/N(HC1circulationpump)** 042578 042578 0425786�26 Plug6/N(circulationpump)** 042579 042579 0425796�27 Plug8/9/N(internalmixer)** 042581 042581 0425816�28 Plug10/11/N(HC1mixer)** 042582 042582 0425826�29 Plug43(DHWtemperaturesensor)** 042623 042623 0426236�30 Plug44(ambienttemperaturesensor)** 042555 042555 0425556�31 Plug48(fluegastemperaturesensor)** 042626 042626 0426266�32 Plug49(boilertemperaturesensor)** 042627 042627 0426276�33 Plug50(boilerreturnsensor)** 042628 042628 0426286�34 Plug51(HC1sensor)** 042629 042629 0426296�35 DHWtemperaturesensor** 042474 042474 0424746�36 Fluegastemperaturesensor** 042474 042474 0424746�37 Boilertemperaturesensor** 042474 042474 0424746�38 Boilerreturntemperaturesensor** 042474 042474 042474**:withoutpicture
31
SparepartsBK50,BK70andBK100
OrdernumberBK50 BK70 BK100
6�39 HC1sensor** 042473 042473 0424736�40 ambienttemperaturesensor** 042471 042471 0424716�41 Burnercable** 042780 042780 0427806�42 Burnercablestage2** 046312 046312 0463126�43 eBusconnectionline** 042784 042784 0427846�44 Omegaconnectionspring** 038749 038749 038749
8 Otherconnectionelements8�2 AirplastPVCspiralhose 051948 051948 0410598�3 Fillinganddischargingcock** 037339 037339 037339
9 Accessories9�1 Neutralizationboxwithoutpump** 035314-01 035314-01 035314-019�5 Pumpforneutralizationbox** 044958-01 044958-01 044958-019�6 Connenctionsetformixer 049884 049884 0498849�7 4waymixer 050345 050345 0503449�8 Servomotor 037338 037338 0446239�9 Circulationpump 063319 063319 0633209�10 Hydrolitfiltermaterial,bundle3kg** 031278 031278 0312789�11 HTsiphonangleDN4090° 035710 035710 0357109�12 HTrubbernippleNW50x30forsiphonangle** 035981 035981 0359819�13 Fluegaspassesbrush** 050716 050716 0507169�14 Boilerbrush** 050717 050717 0507179�15 Brushhandle** 050727 050727 050727**:withoutpicture
BK50/BK70 BK100
32
ECconformitycertification
10 ECconformitycertificationEG-KonformitätserklärungDéclaration de conformité CE 0035
33
Guarantee
6� ExclusionofguaranteeNoguaranteeshallbegranted,regardlessofthecontributoryreasons,fordamageinconsequenceof:• Accident,wilfuldamage,unauthorizeduse,fie,storm,hail,lightningorexplo-sion,
• Useofunsuitablefuels
• Actsofwarofanykind,
• Confiscationorstateintervention.Noguaranteeisgrantedforconsumables(oiljets,ignitionandionizationelectrodes).
7� ScopeTheguaranteeisonlyvalidwithinEurope,ingeographicsense.
8� OtherprovisionsTheWarranteeisadvisedthatthelegalrightsoftheconsumersarenotaffectedbythisguarantee.
11 GuaranteeFully Condensing Boilers BK50, BK70 and BK100
1� Wegranttodealers/craftsmenandconsu-mersaguaranteefordurabilityofgoods,incompliancewiththefollowingconditions,forthefollowingparts:• Boilerbody 2years
• PlasticheatexchangerPP 5years
• Plasticparts 5years
• Conform6.0controlsystem 2years
• Rotatingelectricalcomponents 2years
• Oilandgasfanburner 2years
2� Theguaranteebeginswiththedateofput-tingintooperationbutnolaterthan4weeksafterdeliverytoadealer/craftsmanandendsafterexpirationoftheperiodspecifiedincl.1.Withoutthesubmittedcommissio-ningreport,theguaranteeagreementwiththecompanyshallnotenterintoforce.Asthepartsarereplacedwithinthescopeofguarantee,theguaranteeendsafterdismounting.Forthenewlyinstalledparts,theperiodmentionedincl.1,beginswiththeinstallation.
3� ScopeoftheguaranteeTheguaranteeincludesthereplacementofpartscoveredbytheguarantee.Labourandtransportationcostsrelatedtotheinstalla-tionaswellascostsofdisposalbearstheWarrantee,asfaraslegallypermissible.
4� GuaranteehandlingTheWarranteeshouldinformthemanu-factureraboutanydamagecoveredbytheguarantee,immediatelyupondiscovery,withanexactdescriptionofit.Thedefectivepartshouldbesenttothemanufactureralongwiththereturnsform.
5� Guaranteeisgranted• Ifthecommissioningwascarriedoutbyatrainedspecialiststaffandthesignedcommissioningreportwassenttothemanufacturerimmediatelyaftercommis-sioning.
• Ifmaintenancewasmadeaccordingtotherules,inthementionedtimescale.
BK50/BK70 BK100
34
Notes
12 Notes
Notes and particularities
35
Notes
Notes and particularities
BK50/BK70 BK100
36
Notes
Notes and particularities
Any use, installation, maintenance that is not effected in accordance with the rules specified in the operating instructions, or unauthorized modifications to
the factory-made equipment design shall result in expiration of every guarantee claim.Otherwise our “Conditions of Sale and Delivery” shall apply.
Subject to technical change in terms of product improvement without notice.