43
Copyright 2012 HVAC Systems at Y2E2 CEE 243 Y2E2 HVAC sequence of operation (controls) Week 3

Y2E2 – HVAC sequence of operation (controls)

  • Upload
    doliem

  • View
    237

  • Download
    3

Embed Size (px)

Citation preview

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Y2E2 – HVAC sequence of operation

(controls)

Week 3

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Big idea

• Modern energy management systems include a

combination of passive and active control of energy

distribution

– Passive: constant (volume/flow)

– Active: variable (volume/flow) under computer

control

• Based on If-then conditional control rules of

general form

If setpoint value out of range and

Other conditions met

Then adjust control variable value

2

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Jargon

• Active beam

• AHU

• CAV

• Cfm

• Condition

• Diffuser

• Diff pressure

• Fabric loss

• Fan coil

• Heat exchanger

• JK-1

• Natural ventilation

• Radiant slab

• Setpoint

• Tempered hot/cold

water

• U value

• VAV

• Zone

• Zone splitter

3

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Control basics

• Typically active response components have a setpoint,

i.e., operating functional objective value

– E.g., room temperature setpoint = 73 +- 3oF

• Under computer control, the HVAC building management

system (BMS) adjusts value of active control components

to maintain the setpoint of response components

– e.g., flow rate damper position = 0 – 100% open

• BMS rules “tell” control system how to reach setpoint

• BMS is linked to input sensors and output control signals

4

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Active beams provide efficient conditioned

fresh air to spaces: mostly passive

5

(Chilled) water passes through "beam"

heat exchanger

beam chills air

air becomes denser

(cool) air falls to floor

Convection & room cooling

• Heating similar

Reason for efficiency: heat capacity of

water >> that of air: 1 cubic foot

• Air: heat capacity 37 JK-1

• Water: heat capacity 20,050 JK-1.

heat/cool with much lower pumped

volume in smaller components

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Simple control example – Active beam

6

constant

Cool if SP > 75 F

Heat if SP < 71 F

Deadband +/- 2 F

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Deadband control

7

0

20

40

60

80

100

120

0

100

200

300

400

500

600

700

800

900

1000

65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85

Valv

e P

osit

ion

perc

en

t

Air

flo

w C

FM

Temperature degrees F

Air Flow

Cooling Valve

Heating Valve

Setpoint

Control

variable

(Direct)

Response

variable

Deadband

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Active beams

• Active (control) components: Cold and hot water valves, air flow damper

• Temperature control examples: – Occupied room air temperature setpoint user adjustable +/- 3F

– Unoccupied setpoints: cooling =78F; heating = 65F

– Control cold and/or hot water active beam valve position to achieve room air temperature setpoint

– Temperature control deadband of +/- 2F

– User override can extend occupied hours by 2 hours

• Active beam air flow control: – Air flow rate constant on during occupied hours (basement 24/7);

off during unoccupied hours

– CAV boxes modulate flow to achieve constant air flow during occupied hours only, except during night setback and warmup (compensating for different air pressures)

8

Copyright 2012

HVAC Systems at Y2E2

CEE 243

North facing spaces contain radiators to

balance fabric heat losses

9

Fabric heat loss through materials w/ temperature

difference, e.g., walls, windows, floor, roof.

Heat loss Q = ‘U’ * Area * Delta-temperature

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Baseboard radiators

• Active components: hot water control valve

• Temperature control examples:

– Occupied temperature setpoint adjustable by user +/- 3F

– Unoccupied heating temperature setpoint: 65F

– Control hot water valve position of baseboard heater to achieve room air temperature setpoint

– If outside air temperature > 78F close valve at all times

– User override extends occupied hours 2 hours

10

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Conference rooms

• Active beam control as in other rooms

• Active component: inline supply fan

• Additional CO2 level control

– If CO2 concentration > max CO2 setpoint

open inline supply fan

– Max CO2 setpoint = 500 ppm above outside

air CO2 concentration

11

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Laboratories

• Active components: damper, water coil valves

• Air flow control

– The greater of: • The required air changes (6 air changes/hr)

• Amount needed for cooling

• Sufficient makeup air for fume hoods (supply ~ exhaust)

– For heating air flow is set to minimum

– For cooling air flow is set to maximum

• Temperature control

– +/- 2F deadband

12

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Radiant floor

13

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Radiant floor

• Active components: Pump and valve

• Pump off if outside air temperature > 78F

• Otherwise – Turn on pump

– To reach steady state: • Increase valve position by 10% (every 10 min) until

temperature setpoint of 71F is met

• Decrease valve position by 5% (every 10 min) until temperature setpoint of 71F is met

– After reaching steady state • Adjust valve position by 1% (every 10 min) only

• During unoccupied hours temperature setpoint = 66F

14

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Fan Coil Units

15

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Fan coil units

• Active components: chilled water control valve

• On 24/7

• Temperature control:

– Modulate chilled water valve position to achieve temperature setpoint if space temperature is above setpoint

– If two spaces are controlled by one unit, control using higher space temperature

16

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Main chilled water loop

17

Serves:

• Tempered water loop

• Cooling coils

(AHU, FC, CVs, VAVs)

• Server Rack

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Chilled water system

• Active components: Control valve and booster pump

• Normal operation: Valve is used to control differential pressure to setpoint (if not enough booster pump helps out)

• If water return temp < 58F (for > 5 min) reset down differential pressure setpoint

• If water return temp < 55F (for > 5 min), start pump and recirculate water – If water supply temp < 48F go back to normal

18

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Tempered chilled water

loop

19

Serves:

• Active beams

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Tempered chilled water system

• Active components: Two pumps

• On/off speed control

– Lead/lag operation (weekly)

– Pumps are controlled to meet differential pressure setpoint

• lead pumps first

• If pressure difference too small, lag pump starts in addition

• If both run slow (< 25Hz), turn off lag pump

– Pumps should be off during unoccupied hours (expect overrides)

• Temperature control

– Maintain supply water temperature at 60F by opening and

closing control valve

• Supply Temp Reset (to prevent condensation on active beams)

– If outside dewpoint temperature > 58F

-> supply temperature setpoint = dewpoint temperature + 2F

20

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Main hot water loop

21

Serves:

• Tempered water loop

• Heating coils

(AHU, CVs)

• Radiators

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Hot water system

• Active components: Two pumps, heat exchanger valve

• On/Off speed control – Same as for tempered chilled water system

– If no hot water is needed close heat exchanger valve

• Temperature control – Maintain supply water temperature at 180F by

opening and closing value 1 (1/3 of flow) and valve 2 (2/3 of flow)

22

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Main hot water loop

23

Serves:

• Tempered water loop

• Heating coils

(AHU, CVs)

• Radiators

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Tempered hot water system

• Active components: Two pumps, valve

• On/Off speed control

– Same as for hot water system

• Temperature control

– Maintain supply water temperature at 110F

by opening and closing value

24

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air handling unit

25

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air handling unit

26

Sequence of Operations - Cooling

if 1. Cooling coil valve position (219) > 0

And 2. if the outside air temperature (1123) >

exhaust air temperature (1128),

then 3. heat pipe bypass damper (221) will modulate

closed forcing air to pass over the heat pipe &

avoid precooling.

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air Handling Units (1)

• Active components: fans, heating and cooling coil water valve, heat recovery bypass valve, cooling coil bypass valve

• 24/7 because of labs in the basement

• Maintain static pressure setpoint by modulating fan speed

• Supply air to be maintained at 65F (max DewPoint 60F)

• Cooling, Heating, Dehumidification, Morning Warm-up

27

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air Handling Units (2) - cooling

• Active components: heat recovery bypass damper, cooling coil

bypass damper, cooling coil valve

• Heat recovery

– If outside air temperature > exhaust air temperture -> heat

recovery bypass damper closed (heat recovery “on”) otherwise

open

– Heat recovery bypass damper modulates to set supply air

temperature to setpoint

• Cooling

– If no heating and supply air temperature > setpoint

-> cooling coil bypass damper closed and cooling coil valve

modulates to achieve setpoint

– If no heating and supply air temperature < setpoint

-> first close valve then close bypass damper 28

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air Handling Units (3) - heating

• Active components: heat recovery bypass damper, cooling coil

bypass damper, cooling coil valve

• Heat recovery

– If outside air temperature < heat recovery leaving temperature

& exhaust air temperature > heat recovery leaving temperature

-> heat recovery bypass damper closed (heat recovery “on”)

otherwise open

– Heat recovery bypass damper modulates to set supply air

temperature to setpoint

• Heating

– If no cooling and supply air temperature < setpoint

-> heating coil bypass damper closed and heating coil valve

modulates to achieve setpoint

– If no cooling and supply air temperature > setpoint

-> first close valve then close bypass damper 29

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air Handling Units (4) - dehumidification

• If leaving air dewpoint temperature > 60 F

then maintain dewpoint setpoint in

addition to temperature setpoint with

additional heating to lower moisture

content in air

30

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air Handling Units (5) – Morning

warmup

• Only if daytime temperature does not

exceed 68F

– 2-6 am air supply temperature setpoint is set

to 69F

– After 6am everything is set to normal

31

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air handling unit

• Apply the rule to lots of data

32

('DateTime',

M2_AHU

1_Outsid

eAirTem

p_1123',

'M2_AHU

1_HeatRe

cExhaust

ExitTemp

_1105',

M2_AHU

1_HeatRe

cExhaust

Temp_

1128',

'M2_AHU

1_Exhaus

tAirFlow

Rate_

1127'

,

'M2_AHU

1_CoolCo

ilValvePo

s_ 219',

'M2_AHU

1_HeatRe

cBypassD

amperPo

s_ 221') OAT>EAT

Intended

HP bypass

damper

position

HP

damper

position

OK?

HP

damper

position

always

OK?

3/27/2009 11:25 22 22 22 9 47.6 0 closed OK Ok

3/27/2009 11:30 22 22 22 9 48 0 closed OK

3/27/2009 11:35 22 22 22 9 48 0 closed OK

3/27/2009 11:40 22 22 22 9 49 0 closed OK

3/27/2009 11:45 23 22 22 9 49 0 closed OK

3/27/2009 11:50 23 22 22 9 49 0 closed OK

3/27/2009 11:55 23 22 22 9 49.8 0 closed OK

3/27/2009 12:00 23 22 22 9 50 0 closed OK

3/27/2009 12:05 23 22 22 9 50 0 closed OK

3/27/2009 12:10 23 22 22 9 51 0 closed OK

3/27/2009 12:15 23 22 22 9 51 0 closed OK

Cooling if 1. Cooling coil valve position (219) > 0And 2. if the outside air temperature (1123) > exhaust air temperature (1128),

then 3. heat pipe bypass damper (221) will modulate closed the heat pipe & avoid precooling.

Sequence of Operations - Cooling

if 1. Cooling coil valve position (219) > 0

And 2. if the outside air temperature (1123) >

exhaust air temperature (1128),

then 3. heat pipe bypass damper (221) will modulate

closed forcing air to pass over the heat pipe &

avoid precooling.

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air handling unit

• Apply the rule to lots of data

33

('DateTime',

M2_AHU

1_Outsid

eAirTem

p_1123',

'M2_AHU

1_HeatRe

cExhaust

ExitTemp

_1105',

M2_AHU

1_HeatRe

cExhaust

Temp_

1128',

'M2_AHU

1_Exhaus

tAirFlow

Rate_

1127'

,

'M2_AHU

1_CoolCo

ilValvePo

s_ 219',

'M2_AHU

1_HeatRe

cBypassD

amperPo

s_ 221') OAT>EAT

Intended

HP

bypass

damper

position

HP

damper

position

OK?

HP

damper

position

always

OK?

3/27/2009 12:20 23 22 22 9 52 40 closed bad problem

3/27/2009 12:30 23 22 22 9 53 20 closed bad

3/27/2009 12:35 24 23 22 9 53.2 40 closed bad

3/27/2009 12:40 23 22 22 9 54 40 closed bad

3/27/2009 12:45 24 23 22 9 54 60 closed bad

3/27/2009 12:50 23 22 22 9 54 40 closed bad

3/27/2009 12:55 24 23 22 9 54 40 closed bad

3/27/2009 13:00 24 23 22 9 54 80 closed bad

3/27/2009 13:05 24 23 22 9 54.6 99.8 closed bad

3/27/2009 13:10 24 23 22 9 54 100 closed bad

3/27/2009 13:15 24 23 22 9 54 49.75 closed bad

Cooling if 1. Cooling coil valve position (219) > 0And 2. if the outside air temperature (1123) > exhaust air temperature (1128),

then 3. heat pipe bypass damper (221) will modulate closed the heat pipe & avoid precooling.

Sequence of Operations - Cooling

if 1. Cooling coil valve position (219) > 0

And 2. if the outside air temperature (1123) >

exhaust air temperature (1128),

then 3. heat pipe bypass damper (221) will modulate

closed forcing air to pass over the heat pipe &

avoid precooling.

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Mechanical ventilation

34

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Building pressurization control

• Basement:

– Labs: Negative pressure: 5-10% more

exhaust air than supply

– Offices: Positive pressure: 5-10% more

supply air than exhaust

• Above Grade levels:

– If static pressure rises above 0.03” w.c. atria

dampers open to keep pressure below 0.03”

35

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Natural ventilation

36

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Natural ventilation

• Active components: Operable windows, atria damper

• Initial range for natural ventilation outside air temperature 68 – 85F

• If outdoor temperature is within range & average space

temperature > 70F -> open dampers

– For each zone where temperature > 70F open operable

windows

– If zone temperature < 70F for at least 5 min close windows

– If all windows around one atrium are closed close

corresponding atrium damper

• Night purge (if daytime outside air temperature exceeds 75F)

– During unoccupied hours open windows if Outside air

temperature < 65F and space temperature > 65F Close

windows if space temperature < 63F

37

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Representative offices in Y2E2

2 offices on the North side with radiant

heating and ceiling fans

38

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Representative offices in Y2E2

2 offices on the South side with active

beams (heating and cooling)

39

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Workflow to interpret building energy monitoring data

• Functional intent

• Measured data (x 2400

points @ 1x/minute)

• Work flow

• Summary assessment

40

Select system & points for analysis

Synthesize functional intent and data context

Access and graph data

Assess data conformance to functional intent

Identify potential causes

Document and discuss findings

Step 1

Step 4

Step 2

Step 3

Step 5

Step 6

End

All Ok

All Ok

All Ok

All Ok

All Ok

All Ok

Steps 1-5 to Clarify

Else

ElseSteps 1-4 for

satisfactory fault diagnosis

Steps 1-3 for additional

clarity

Else

Else repeat Step 3 for additional clarity

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Reading

• ACCO engineered systems, HVAC Sequences of

Operation for Stanford SEQ2 Environment and Energy

Building, 2007

• Abram, T., J. Kunz, J. O’Donnell, and M. Garr, Energy

Performance Analyses of a Santa Clara County Facility

by CEE243 Student Groups, CIFE Technical Report

#TR204, 2011

41

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Homework

• For an assigned system, compare

patterns between different years (2008,

2009, 2010)

• Classify pattern (red/yellow/green) re

assumed functional intent

42

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Big idea

• Modern energy management systems include a

combination of passive and active control of energy

distribution

– Passive: constant (volume/flow)

– Active: variable (volume/flow) under computer

control

• Based on If-then conditional control rules of

general form

If setpoint value out of range and

Other conditions met

Then adjust control variable value

43