Upload
rebecca-murphy
View
216
Download
3
Embed Size (px)
Citation preview
WW
W.IN
ALA
.CO
.ZA
11
Product: ITMS2
Hardware Training
2
WWW.INALA.CO.ZA
INDEX
ITMS:
Network System Diagram. Mechanical Presentation of ITMS. Unit Capacity.
SAM2 ITMS (IP Controller)
ITMS System Components Installation Connections
33
WWW.INALA.CO.ZA
HARWAREITMS2
4
WWW.INALA.CO.ZA
NETWORK SYSTEM DIAGRAM
5
WWW.INALA.CO.ZA
MECHANICAL PRESENTATION
ECS2 unit is 2u High and 300mm deep and fits into a 19” Transmission Rack
A – SAM2 Main Controller Unit
B – Alarm Input Adaptor
C – Pix Alarm Output Adaptor
D – Utility Interface Module
E – GSM Modem
F – LCD and Key pad
G – E1 Controller Unit
H – Access Control Unit
6
WWW.INALA.CO.ZA
UNIT CAPACITY – SAM2
DC Ventilation Fan
SAM2 :SAM2 Main Controller 26 x General Purpose Digital inputs4 x Generator #1 Digital Inputs4 x Generator #2 Digital Inputs4 x Aircon Digital Inputs6 x Temp Analog Inputs1 x Analog Input 0-60vdc1 x Analog Input 0-20mA
3 x Relay outputs – Generator Ctrl4 x Aircon Drive Outputs24 x Pix Outputs (RBS)1 x DC Fan Output, Speed Ctrl
1 x RS485 Port – communication to E1 Controller
Expansion Modules Available:1 x GSM Modem1 x Generator Controller (2 x Gen Sets)2 x Fuel Management (RS485)1 x Battery Management (RS485)1 x Utility Management (RS485)1 x HEM (Hybrid Extension Module)
7
WWW.INALA.CO.ZA
UNIT CAPACITY – ITMS
DC Ventilation Fan
Remote Management Modules Available:
IP Communication Controller: 1 x RS232 Port – Unit Configuration Port2 x TCP/IP Ports1 x RS485 Port - Communication to SAM2 and Access Control Unit2 x RS232 Port – Virtual Port1 x Relay – Lock Failsafe Override
Expansion Modules Available:SP8 - 8 x RS232 portSP6 – 6 x RS232 port & 2 x RS485 PortLAN Card - 4 x TCP/IP Ports
ITMS Controller
SP6 - PCBSP8 - PCB
8
WWW.INALA.CO.ZA
SYSTEM COMPONENTS
Battery Current Probe
Main Control Unit
AC Mains Phase Frequency Monitor
Hybrid Extension Module
Aircon Control Switch
Door Switch
Smoke Room Temp & Humidity
Movement
Wiring Kit
9
WWW.INALA.CO.ZA
DVR COMPONENTS
4 Channel DVR
Indoor IR Dome Camera
Video Surveillance• TCP-IP Remotely managed DVR• Four channel CCTV DVR• Eight channel CCTV DVR• CCTV Indoor dome type cameras• CCTV Outdoor bullet type cameras• Indoor TCP-IP Web Cam
4 Channel DVR
1010
WWW.INALA.CO.ZA
INSTALLATIONITMS Components
11
WWW.INALA.CO.ZA
ITMS2 – RACK MOUNT UNIT
Alarm Input Module
ITMS2 Unit
12
WWW.INALA.CO.ZA
DOOR SWITCH
Door Switch
13
WWW.INALA.CO.ZA
MOVEMENT SENSOR
Movement Sensor
14
WWW.INALA.CO.ZA
SMOKE SENSOR
Smoke Sensor
15
WWW.INALA.CO.ZA
ROOM TEMP & HUMDITY SENSOR
Room Temp & Humidity Sensor
16
WWW.INALA.CO.ZA
AC MAINS PHASE MONITOR
AC Main Phase Frequency Monitor
17
WWW.INALA.CO.ZA
HYBRID EXTENSION MODULE
Hybrid Extension Module
18
WWW.INALA.CO.ZA
BATTERY CURRENT CLAMP
Battery Current Clamp 200A
200A Probe 500A Probe
Wire Lead Probe Termination Probe Termination
Blue GND Not Connected
Orange Positive (+) Positive (+)
White/Orange Negative (-) Negative (-)
White/Blue Not Connected Not Connected
Battery Current Clamp 500A
19
WWW.INALA.CO.ZA
Aircon Control Switch – Clipon Type
Aircon Control Switch
To Second Aircon
20
WWW.INALA.CO.ZA
Aircon Control Switch – Pearl Type
Aircon Control Switch
21
WWW.INALA.CO.ZA
Rectifier – Alarm wiring
22
WWW.INALA.CO.ZA
AC Mains & Generator on load Alarm
23
WWW.INALA.CO.ZA
Surge Protection Alarm
24
WWW.INALA.CO.ZA
Over/Under AC Voltage (Eskom) Alarm
Blue
25
WWW.INALA.CO.ZA
Over/Under AC Voltage (Eskom) Alarm
26
WWW.INALA.CO.ZA
Over/Under AC Voltage (Eskom) Alarm
27
WWW.INALA.CO.ZA
ITMS RS485 COMMS WIRING
2828
WWW.INALA.CO.ZA
SOFTWAREITMS
29
WWW.INALA.CO.ZA
SAM2 ECT
SAM2 ECT:
Current Version ECT – V2.17 ECT Version is viewed on the top left corner as indicated with the yellow circle
EG: “AIU 2 ECT V2.17”
Current Version Firmware – V2.17 Firmware Version is viewed on the top left corner as indicated with the Red circle
EG: “AIU Version: SAM205 V2.17”
Front Panel View:Room and Aircon Vent temps and run timesAlarm Input StatusOutput Status
# The “Front Panel” is a real-time information panel display
30
WWW.INALA.CO.ZA
ITMS ECT (IP Controller)
IP Controller (V2.1 - 2 Lan Port) ECT:
Current Version ECT – V2.12 ECT Version is viewed on the top left corner as indicated with the yellow circle
EG: “ITMS-C Ver 2.1.2”
Current Version Firmware – V3.0.0.9Firmware Version is viewed on the button left corner as indicated with the Red circle
EG: “S/W: 3.0.0.9”
WW
W.IN
ALA
.CO
.ZA
3131
THANK YOU