    Product Specification

    03248E

    MFR 2Multi Function Relay

    Mains & GeneratorProtection & Control

    Generator and mainsprotection

    Synchronization fortwo breakers

    Frequency andvoltage matching

    Real power control

    Power factor control

    Load/var sharing

    Counters for kWh,operating hours,maintenance call

    Programmable relayoutputs

    PC and front panelconfigurable

    CAN bus basedcommunication

    Microprocessortechnology forflexible and reliableoperation

    CE marked

    UL/cUL Listed

    APPLICATIONS

    Based on micro-controller technology,Woodward's MFR 2 Multi FunctionRelay incorporates functions andfeatures for multiple applications (e.g.gensets, hydropower, etc.) in isolatedor parallel utility operation. The MFR 2is designed for generators andswitchgear equipment that requireindependent protection.

    The ability for the MFR 2 to quicklydecouple from the mains whenworking in parallel with the mainsgives complete generator protectionfor frequency, voltage, and real and re-active power control allowing load/varsharing between as many as eightunits.

    DESCRIPTIONThe Series of MFR 2 Multi FunctionRelays consists of the modelMFR 2S/PSVA.

    Features Battery voltage monitoring kWh/oper.hours/start/maintenance

    counter 4 configurable discrete alarm inputs 4 configurable relays Two-line LC display Synchroscope Multi level password protection Configuration directly or via PC CAN bus communication

    DESCRIPTION (continued)

    Protection ANSI #Mains Over-/undervoltage (59/27) Over-/underfrequency (81O/U) Voltage asymmetry (47)

    Phase/vector shift (MFR 2S only) (78)Generator Over-/undervoltage (59/27) Over-/underfrequency (81O/U) Overload (32) Reverse/reduced power (32R/F) Unbalanced load (46) Re-active power monitoring Loss of excitation (40Q) Time-overcurrent (50)

    Controller Synchronizer for 2 CB

    Discrete raise/lower for n/f/V/P/Q Speed/frequency/real power Voltage/power factor Isolated operation Mains parallel operation Load/var sharing (up to 8 units) (MFR 2S only) Dead bus operation

    MFR 2S/PSVAThe PSVA package additionally includes: df/dt (ROCOF) (81RL) 2 conf. analog outputs (20 mA) 2 conf. pulse outp. for kWh/kvarh

    Real power set-point input (20 mA)

  • 8/11/2019 Woodward - Not According to ANSI Guidelines - 03248_E

    2/4

    SPECIFICATIONS

    Accuracy .......................................................................................... Class 1Power supply ..................................................................... 24 Vdc (+/-30 %)Intrinsic consumption .................................................................. max. 15 W

    Ambient temperature ................................................................ -20 to 70 C Ambient humidity ...................................................... 95 %, non-condensingVoltage ........... Rated value / D: [1] 66/115 Vac or [4] 230/400 Vac

    Maximum value (V max): [1] 150 Vac or [4] 300 VacRated voltage V ph-ground : [1] 150 Vac or [4] 300 Vac

    Rated surge voltage: [1] 2.5 kV or [4] 4.0 kVMeasuring frequency ................................................ 50/60 Hz (40 to 70 Hz)Linear measuring range up to ....................................................... 1.3V rated Input resistance ..................................................... [1] 0.21 M W, [4] 0.7 M WMax. power consumption per path ................................................... 0.15 WCurrent (Irated ) .............................................................. [1] ../1 A or [5] ../5 ALinear measuring range up to ............................................... I gen = 3.0I rated

    Imains = 1.5I rated Load ............................................................................................. < 0.15 VARated short-time current (1 s) ................................. [1] 50I rated , [5] 10I rated Discrete inputs .............................................................................. isolatedInput range .................................................................... 18 to 250 Vac or dcInput resistance ..................................................................... approx. 68 k W

    Pulse outputs ................................................................... transistor outputRated gate voltage ............................................................................ 24 VdcMaximum gate voltage ...................................................................... 32 VdcMinimum gate current .................................................................... 10 mAdcMaximum gate current ................................................... 30 mAdc (0.5 Vdc)Relay outpu ts ................................................................................ isolatedContact material ............................................................................... AgCdOLoad (GP) ................................................. 24 Vdc@2 Adc, 250 Vac@2 Aac

    Pilot duty (PD) ...................................................................... 24 Vdc@1 Adc Analog o utp ut ................................................................................ isolatedType ............................................................. 0/4 to 20 mA, freely scaleableResolution .................................................... 8/12 Bit (depending on model)Max. load 0/4 to 20 mA ..................................................................... 500 W Insulating voltage ......................................................................... 3,000 VdcHousing ...................................................... Type APRANORM DIN 43 700Dimensions ....................................................................... 14472122 mmFront cutout ............................................................................... 13867 mmConnection ................................................ screw/plug terminals depending

    on connector 1.5 mm or 2.5 mmFront ................................................................................. insulating surfaceProtection system ................................................................................ IP 21Weight ............................................ depending on version, approx. 1,000 g

    Disturbance test (CE) .................................................. tested according toapplicable EN guidelines Listings ............................................... UL/cUL listed for ordinary locations

    DIMENSIONS

    Bottom view

    7 2

    DIN rail mountoption (please order

    brackets P/N 8923-1023)

    8

    116 50

    1 3 9

    1 7 9

    6 5

    2 7

    3 5

    Back view withconnecting terminals

    Front view

    X1 X5

    6570 6075 5450

    0 24

    48 25

    2004-11-11 | MFR 2 Dimensions r2ww-4604-ab.skf

    1 4 4

    80 87

    Configuration portConfiguration port

  • 8/11/2019 Woodward - Not According to ANSI Guidelines - 03248_E

    3/4

    WIRING DIAGRAM (MFR 2S/PSVA; refer to manual for other units)

    D r i v e raise

    lower 1 0

    9

    8

    0 V

    I A

    Analog output0/4 to 20 mA

    7 0

    7 1

    7 2

    Subject totechnical modifications.

    G

    s2 (l) 2 5

    s1 (k)

    s2 (l)

    s1 (k) 2 6

    2 9

    3 0

    2 0

    s1 (k)

    s2 (l) 3 1

    3 2

    2 1 2 2

    Alarminput 2 6 2

    N

    0 Vdc

    24 Vdc

    Switching set point 1 2

    Enable GCB

    0

    2005-09-13 | MFR2WiringDiagramr2ww-0537-ap.skf

    2

    1

    3

    5

    Isolated operation ON

    Common

    Common (terminal 3/4/5/6/53/54)

    Release monitoring

    Not used

    External acknowledgment

    3 52

    3 3

    6

    7

    3 4

    Alarminput 1

    Blocking of mains protection 4

    3 3 6

    6 0

    6 1

    Relay 3

    Ready for operation

    Relay 4

    Common

    Alarminput 4

    Alarminput 3

    1 8

    6 3

    6 4

    6 5

    1 9

    3 7

    3 8

    4 3

    Relay 1

    Relay 2 4 6

    4 4

    4 5

    4 7 4 8

    8 0

    8 1

    8 2

    8 3

    0 V

    I A

    Analog output0/4 to 20 mA

    8 4

    8 5

    Impulse output kvarhOpen Collector

    8 6

    8 7

    Impulse output kWhOpen Collector

    1

    Analog input0/4 to 20 mA- Setpoint value: Real power kW

    X 1

    X 2

    X 3

    X 4

    X 5

    InterfaceCANbus

    P S V A

    Generator current L1

    Generator current L2

    Generator current L3

    SPEED/ POWERThree-position controller

    P S V A

    Battery#2

    #2Battery

    #1NO/NC

    #1NO/NC

    #2Battery

    #1NO/NC

    #1NO/

    NC

    #1NO/NC

    #1NO/NC

    #1NO/NC

    c o n f

    i g u r a b

    l e d u r i n g s e

    t u p

    ( N O / N C )

    # 1 B a t

    t e r y o r a n o t

    h e r p o w e r s u p p

    l y ; t e r m

    i n a l

    7 / 3 3 / 6 5 i s p o s . o r n e g . s i g n a l

    # 2

    T h e s o c k e t

    f o r t h e

    P C c o n f

    i g u r a t

    i o n

    i s s i t u a

    t e d o n

    t h e

    s i d e o f

    t h e u n

    i t . T h i s i s w h e r e

    t h e

    D P C h a s

    t o b e p l u g g e

    d i n

    .

    u p t o 7 a d

    d i t i o n a

    l g e n e r a t o r s

    ( e a c

    h v i a o n e

    M F R 2 )

    G A T E W A Y

    G W 4

    C o n

    t r o l r o o m

    S P S

    P CGND

    CAN-H

    CAN-L

    Termination

    5

    6

    7

    8

    M F R 2 S / P S V A ( M u l

    t i F u n c

    t i o n R e l a y )

    4 1

    M C B

    3

    3

    5 0

    5 2

    5 1

    s2 (l)

    s1 (k)

    2 7

    2 8

    Mains voltage L1Mains voltage L2

    Mains voltage L3

    5 3

    3 9

    1 6

    4 0

    1 7

    5 4

    Enable MCB

    Command: open MCB

    Command: close MCB

    Busbar voltage

    Reply: MCB is open

    G C B

    3

    4 2

    1 4

    1 5

    4 Reply: GCB is open

    Command: close GCB

    Command: open GCB

    raise

    lower

    1 1

    1 2

    1 3

    Generator voltage L1

    Generator voltage L2Generator voltage L3

    Mains current L1

    VOLTAGE / POW.FACTThree-position controller

    2 3

    2 4 L2

    L1

  • 8/11/2019 Woodward - Not According to ANSI Guidelines - 03248_E

    4/4

    InternationalWoodwardPO Box 1519Fort Collins CO, USA80522-15191000 East Drake RoadFort Collins CO 80525Ph: +1 (970) 498-3634Fax: +1 (970) 498-3058email:[email protected]

    EuropeWoodward GmbHHandwerkstrasse 2970565 Stuttgart, GermanyPh: +49 (0) 711 789 54-510Fax: +49 (0) 711 789 54-101email:[email protected]

    Distributors & ServiceWoodward has an internationalnetwork of distributors andservice facilities. For yournearest representative, call theFort Collins plant or see the

    Worldwide Directory on ourwebsite.

    Corporate HeadquartersRockford IL, USAPh: +1 (815) 877-7441

    www.woodward.com

    Subject to technicalmodifications.

    This document is distributed forinformational purposes only. It is notto be construed as creating orbecoming part of any WoodwardGovernor Company contractual orwarranty obligation unless expresslystated in a written sales contract.

    We appreciate your comments aboutthe content of our publications.Please send comments including thedocument number below [email protected]

    Woodward GovernorCompany

    All Right s Reser ved

    03248E - 12/6/S

    TYPICAL APPLICATIONS

    52

    52

    MFR 2

    CAN

    RS232

    0/4..20mA

    I / O

    G

    81RL

    78

    90

    79

    47

    81U81O

    59

    27

    25

    25

    27

    59

    81O50

    79

    32 81U

    32R

    32F

    40Q

    4639

    38

    12

    49 55

    90

    74

    MFR 2S

    ANSIPSVA

    ControlBreaker 2Synchronization 25

    Isolated single-unit operation

    Mains parallel operation Accessor ieskWh counter kvarh counter Operat. hours/start/mainten. counter Configuration via PC #1 ProtectionGen.: Over-/undervoltage 59/27 Mains: over-/undervoltage 59/27 Gen.: Over-/underfrequency 81O/U Mains: over-/underfrequency 81O/U Mains: Voltage asymmetry 47 Mains: phase/vector shift 78 Mains: df/dt (ROCOF) 81RL Gen.: Overload 32 Gen.: Reverse power 32R Gen.: Reduced power 32F/37 Gen.: Unbalanced load 46 Gen.: Re-active power Gen.: Loss of excitation 40Q Gen.: Time-overcurrent 50/51* ControllerDiscrete raise/lower: n/f & P Discrete raise/lower: V & Q

    Active power setp.: 0/4 to 20 mA Load/var sharing

    I/O'sDiscrete alarm inputs (config.) 4Relay outputs (config.) 74 4

    Analog inputs 0/4 to 20 mA (conf.) 2 Analog outp. 0/4 to 20 mA (conf.) 2Impulse output for kWh/kvarh CAN bus communication #2 Listings/ApprovalsUL/cUL listed Product Number P/N Language

    Measuring inputs 100 Vac, ../5 AEnglish 8440-1287German 8440-1733

    Measuring inputs 400 Vac, ../5 A English 8440-1735

    German 8440-1323

    * not according to ANSI guidelines (two-step protection instead of inverse time characteristic)#1 Cable incl. software necessary (DPC, Product Number P/N 5417-557)#2 Remote monitoring, control, configuration (GW 4 could be used for several interfaces)