FOR WALLS

SLIMLINE

FOR FLOORS

BASELINE

FOR ROOFS

TOPLINE

Specify for the future

2013

with EcoTherm Insulation

Insulation

Page 2: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

Application Product

Single Ply

Cavity wall

Internallining

Eco-Cavity p12

Eco-Liner p10

Eco-Versal p8

Eco-UFH p9

PitchedRoofs

FlatRoofs

Eco-Versal p13

Mastic asphalt

Eco-Taper p19Eco-Metre p14Eco-Felt p15Eco-Deck p18

Eco-Taper p19Eco-Metre p14Eco-Felt p15Eco-Deck p18

Torch on

Roll & pour

Eco-Taper p19Eco-Metre p14Eco-Felt p15Eco-Deck p18

Eco-Taper p19Eco-Metre p14Eco-Felt p15Eco-Deck p18

Mechanically fixed

Adhered

Bitumencompatible

Eco-Deck p18Eco-Fix p17

Eco-Taper p19Eco-Bond p16Eco-Deck p18

Felt

FOR WALLS

SLIMLINE

FOR FLOORS

BASELINE

FOR ROOFS

TOPLINE

www.ecotherm.co.uk tel: 01702 5201662 32013

FOR WALLS

SLIMLINE

FOR FLOORS

BASELINE

FOR ROOFS

TOPLINE

Keeping heat in and cold out – EcoTherm has it covered

Contents

Products selector 3

PIR board – meeting Building Regulations 4

Environment – dedicated to responsibility 6

Baseline – for floors

Eco-Versal 8

Eco-UFH 9

Slimline – for walls

Eco-Liner 10

Eco-Cavity 12

Topline – for roofs

Eco-Versal 13

Eco-Metre 14

Eco-Felt 15

Eco-Bond 16

Eco-Fix 17

Eco-Deck 18

Eco-Taper 19

Technical support 20

EcoTherm develops, manufactures and markets

Polyisocyanurate Rigid Thermal Insulation Boards.

In addition to our standard range of products we

also produce speciality products.

EcoTherm rigid insulation boards are produced in both the UK and The Netherlands

for the UK market. Rigorous quality control procedures are in place in both

production facilities.

EcoTherm products are recognised for their compressive strength and dimensional

stability which makes them ideally suited to flat and pitched roof construction, wall

insulation and for floors and ceilings.

All these applications are supported at every stage with comprehensive technical

advice and customer service.

PIR foam insulation materials may be considered to be the most sustainable, in that they do not affect the ozone layer and they perform for the life of the building without loss of performance. See page 6.

Select your productThe future of insulation

Insulation

Page 3: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

Meeting the insulation demands of Building Regulations

In the past, understanding how to meet the

requirements of Building Regulations for thermal

insulation was relatively straightforward. A table

would tell you the U-value that needed to be

achieved for a particular floor, wall or roof and the

manufacturer could then tell you what thickness

of insulation you needed to achieve that value.

As green issues and the threat of global warming

have come to the top of the agenda, however,

the approach has changed and the requirements

have not only become tougher, but also harder to

put into a simple formula.

The current Part L of the Building Regulations

(Conservation of Fuel and Power) came into effect

in 2006 and represents the Government’s response

to the EU’s Energy Performance of Buildings

Directive. It applies to all new buildings – dwellings

and commercial – as well as building work on

existing buildings.

The new requirements mean developers have to

use more energy saving insulation, more efficient

boilers and low or zero carbon systems to

demonstrate compliance.

PIR based insulation boards offer many advantages

in meeting these requirements as they have a high

thermal insulation factor per unit mass and an

extremely long performance life.

Their light weight means they can be easily

used with modern construction methods,

while their durability means that the building

performs to the required level of energy efficiency

throughout its life – without the need for resource-

consuming replacements.

On new buildings Part L sets overall performance

standards rather than laying down particular ways

of achieving them. The old Elemental Method and

Target U-Value approach of determining whether a

building is compliant are no longer allowed.

Every new building now has to achieve a Target CO2

Emission Rate (TER) expressed in mass of CO2 per

unit floor area emitted by all the internal heating,

hot water, ventilation and fixed lighting. This is

calculated using either the Government’s Standard

Assessment Procedure (SAP 2005) for dwellings

smaller than 450m2, or the Simplified Building

Energy Model (SBEM) for non-domestic buildings.

EcoT herm appreciates that the removal of the old

step-by-step approach means that it is much harder

to know how to comply. To help our customers

meet these new requirements we are pleased to

offer our technical advice.

FOR WALLS

SLIMLINE

FOR FLOORS

BASELINE

FOR ROOFS

TOPLINE

For new buildings (England and Wales)

Likely required values and thicknesses to achieve TER

For new dwellings, in accordance with Building Regulations Approved

Document L1A, April 2006, the Dwelling CO2 Emission Rate (DER) must

be no more than the defined Target CO2 Emission Rate (TER). DER and

TER may be calculated by the Standard Assessment Procedure (SAP).

To achieve the most cost-effective DER will generally require 10 – 20

iterations to calculate the permissible U-values for each element of

roof, wall, and floor. Experience shows that it is sensible to start with

the insulation thicknesses shown above in order to minimise the

number of SAP iterations required.

For new buildings and work to existing buildings (Scotland)

For work under Scottish Regulations U-values for each wall, floor or

roof element must be no more than those in the illustration adjacent,

subject to certain other factors (i.e. the total area of doors, windows

and rooflights must be less than 25% of the total floor area and the

boiler or heating appliance must have an efficiency not less than 78%

by SEDBUK calculations).

For all buildings (Scotland) and for work in existing buildings (England and Wales)

Required thicknesses to achieve elemental U-values

For work to existing buildings in accordance with Building Regulations

Approved Document L1B and L2B, U-values for each wall, floor or roof

element must be no more than those in the illustration adjacent.

www.ecotherm.co.uk tel: 01702 5201664 5

PIR board

BBA CertificationEcoTherm Insulation boards

are fully supported with a

British Board of Agrément

Certificate.

U-value = 0.25Thickness = 50 – 80mm dependent on floor P/A

U-value = 0.16Thickness = 130mm

U-value = 0.20Thickness = 100mm

England and Wales existing walls

U-value = 0.35

England and Wales new extension walls

U-value = 0.30

England and Wales new existing walls

U-value = 0.30

U-value = 0.35Thickness = 50mmUnheated space e.g. garage

U-value = 0.25Thickness = 80 – 110mm

U-value = 0.20 – 0.22Thickness = 50 – 80mm dependent on floor P/A

For new buildings other than dwellings (England and Wales)

To comply with ADL2A the Building CO2 Emission Rate (BER) must be

no more than the Target CO2 Emission Rate (TER). Experience shows

that the insulation thicknesses shown above are likely to be acceptable

in a Simplified Building Energy Model (SBEM) calculation.

Sensible starting point for calculations to meet TER

Element U-value (W/m2K) Thickness (mm)

Wall 0.25 – 0.30 50 – 70

Floor 0.20 – 0.22 50 – 80*

Roof 0.16 – 0.20 110 – 130

*Dependent on floor perimeter/area measurement

U-value = 0.20 – 0.22Thickness = 50 – 80mm dependent on floor P/A

U-value = 0.16Thickness = 130mm

U-value = 0.16 – 0.18Thickness = 120 – 130mm

U-value = 0.25 – 0.30Thickness = 50 – 70mm

U-value = 0.25 – 0.30Thickness = 65 – 70mmUnheated space e.g. garage

U-value = 0.18 – 0.20Thickness = 110 – 130mm

U-value = 0.20 – 0.22Thickness = 50 – 80mm dependent on floor P/A

For all buildings (Scotland) and for work in existing buildings

(England and Wales)

For new buildings (England and Wales)

FOR FREE TECHNICAL ADVICE Call: 01268 597 212/213Email: [email protected]

Insulation

2013

Page 4: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

BRE Green guide 'A' ratedEcoTherm is fundamentally dedicated to environmental responsibility by minimising energy consumption.

Our polyisocyanurate (PIR) products are among the most efficient and effective means of minimising

energy loss from buildings.

EcoTherm has achieved ISO 14001 accreditation; a reflection of the entire organisations commitment to

sustainability through their Environmental Management System.

All our insulation boards are manufactured from CFC- and HCFC-free grades of material which ensure zero ozone

depletion potential (ZERO ODP) and a global warming potential (GWP) factor of 3 which comfortably surpasses the

target of 5 and is BRE Green Guide A rated.

Whenever we use timber, such as in our Eco-Deck laminated roof decking, it is Forest Stewardship Council (FSC)

certified, which gives assurance that it is legal and sustainable at every stage of its chain of custody.

Wide experience supported by accelerated lab tests have proved that PIR insulation boards are among the most

durable construction products.

They will not rot, shrink, absorb moisture, or decay as some fibre board or organic insulation materials may, and so

they will deliver design insulation values throughout the full life of the building. And of course all our products are

recyclable. In practice PIR products have one of the highest ratings for successful recycling.

" Within 8 months users will

have recouped the energy

required to produce the

EcoTherm product in

energy savings."

FOR WALLS

SLIMLINE

FOR FLOORS

BASELINE

FOR ROOFS

TOPLINE

Environment

www.ecotherm.co.uk tel: 01702 5201666 7

"1m3 of PIR saves 40km3 of CO2. That’s 60kg of CO2 over 75yrs –

50% more than traditional insulation."

FOR FREE TECHNICAL ADVICE Call: 01268 597 212/213Email: [email protected]

EMS 564550

Insulation

2013

Page 5: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

IT’S THINsuperior rigid

insulation

BUILT IN MEMBRANEno need for a polythene

overlay

SUPERB CLIPRETENTIONheavy duty facing holds clips tight

www.ecotherm.co.uk tel: 01702 5201668 9

FOR FLOORS

BASELINE

FOR FLOORS

BASELINE

Eco-Versal formerly Floor-Therm

Cert 99/3569Benefits

■ Maximum insulation

performance for

minimum thickness

■ Good compressive strength

(140kpa for Eco-Versal and

160kpa for Eco-UFH)

■ High resistance to

compressive creep

■ Adaptability in

modern constructions

■ Flexibility to insulate

most floors

■ Meets NHBC

recommendations

■ Meets UK Building

Regulation standards

Dimensions

Width (mm): 1200

Length (mm): 2400

Thickness (mm): 25 – 200

Design considerations

BRE Good Building Guide 45,

Insulating ground floors.

CP 102:1973 Code of Practice for

protection of buildings against

water from the ground.

Compressive strength

Typical compressive strength

exceeds 140kPa for Eco-Versal

and 160kPa for Eco-UFH, when

tested to BS EN 826: 1996.

U-values

The calculation of U-Values

for floors depends on the

substructure and perimeter/

area. Therefore, it is not possible

to give accurate values.

Thermal conductivity

The thermal conductivity,

λ value is 0.022W/mK.

Thermal insulation for floors

Description: Rigid PIR core with an aluminium foil facing on both sides

Purpose: Solid concrete floors, suspended hollow pot floors, suspended timber

floors, foundations and perimeters, remedial overlay floors

Thermal insulation for underfloor heating

Description: Rigid PIR foam core with tough woven aluminium grid

Purpose: Insulating under floor heating systems and providing

a mechanism for servicing water pipes

Eco-UFH formerly Underfloor Heating

Benefits

■ Eco-UFH Board has a rigid PIR

foam core which gives the

highest thermal performance

for the minimum thickness

■ It has a tough woven grid and

aluminium facing which holds

clips tight and reduces the

number of clips required

■ Its high compressive strength

(160kPa) means it stands up

to foot traffic

■ Eco-UFH Board ensures the

performance of the system

by preventing heat loss

penetrating the floor; it saves

energy and money by

distributing heat evenly

Dimensions

Width (mm): 1200

Length (mm): 2400

Thickness (mm): See below

Design considerations

BRE Good Building Guide 45, Insulating ground floors. CP 102:1973

Code of Practice for protection of buildings against water from

the ground.

Thermal conductivity

The thermal conductivity, λ value, of EcoTherm Eco-UFH is typically

0.022W/mK. The thermal resistance 'R' varies with the thickness as

shown in the table below.

Solid and Suspended Block & Beam = UFH

All calculations based on a P/A ratio of 0.5

PRINTED GRIDmakes it easier

to align the pipes

Thickness Length Width R-value Typical Typical U-value Typical U-value (mm) (mm) (mm) (m2k/W) U-value Suspended Suspended Solid Concrete B&B Timber Floor (W/m2k) (W/m2k) (W/m2k)

25 2400 1200 1.14 0.36 0.40 0.39

30 2400 1200 1.36 0.33 0.37 0.36

35 2400 1200 1.59 0.31 0.34 0.34

40 2400 1200 1.82 0.28 0.31 0.32

45 2400 1200 2.05 0.27 0.30 0.30

50 2400 1200 2.27 0.25 0.27 0.29

60 2400 1200 2.73 0.22 0.24 0.26

65 2400 1200 2.96 0.21 0.23 0.25

70 2400 1200 3.18 0.20 0.22 0.25

75 2400 1200 3.41 0.19 0.21 0.24

80 2400 1200 3.64 0.19 0.20 0.23

90 2400 1200 4.09 0.17 0.18 0.22

100 2400 1200 4.55 0.16 0.17 0.21

110 2400 1200 5.00 0.15 0.16 0.20

120 2400 1200 5.46 0.14 0.15 0.19

130 2400 1200 5.91 0.13 0.14 0.18

140 2400 1200 6.36 0.12 0.13 0.18

150 2400 1200 6.82 0.12 0.12 0.17

160 2400 1200 7.27 0.11 0.12 0.15*

170 2400 1200 7.73 0.11 0.11 0.15*

180 2400 1200 8.18 0.10 0.10 0.14*

190 2400 1200 8.64 0.10 0.10 0.14*

200 2400 1200 9.09 0.09 0.10 0.14*

Thickness Length Width R-value Typical U-value Typical U-value

(mm) (mm) (mm) (m2k/W) Solid (W/m2k) Suspended B&B (W/m2k)

25 2400 1200 1.14 0.36 0.40

30 2400 1200 1.36 0.33 0.37

35 2400 1200 1.59 0.31 0.34

40 2400 1200 1.82 0.28 0.31

50 2400 1200 2.27 0.25 0.27

60 2400 1200 2.73 0.22 0.24

75 2400 1200 3.41 0.19 0.21

80 2400 1200 3.64 0.19 0.20

90 2400 1200 4.09 0.17 0.18

100 2400 1200 4.55 0.16 0.17

FOR FREE TECHNICAL ADVICE Call: 01268 597 212/213Email: [email protected]

BASELINE BASELINE

All calculations based on a P/A ratio of 0.5 * 200mm deep timbers

Insulation

2013

Page 6: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

Benefits

■ Insulate and dry line in one

■ Thin insulation solution

where space matters

■ Quick and cost effective

Dimensions

Width (mm): 1200

Length (mm): 2400

Thickness (mm): 37.5 – 112.5

Design considerations

Cut using a fine tooth saw,

ensuring accurate trimming to

achieve close butt joints and

continuity of insulation.

Follow BS 8212: 1995 Code

of Practice for dry lining and

partitioning using gypsum

plasterboard and BS 8000-Part 8:

1994 Workmanship on building

sites. Code of practice for

plasterboard partitions and dry

linings. If required for acoustics

and air tightness apply a suitable

parge coat prior to lining.

Compressive strength

Typical compressive strength

for the foam exceeds 140 kPa

when tested to BS EN 826: 1996

Thermal Insulating Products

for Building Applications –

Determination of

Compression Behaviour.

U-values

The calculation of U-values

for walls depends on the

substructure. Therefore, it is not

possible to give accurate values.

Thermal conductivity

The thermal conductivity

(λ value) of the foam is

0.022W/mK with inherent

vapour control resistance.

The 12.5mm gypsum

plasterboard element has a

thermal conductivity (λ) of

0.19W/mK. The thermal

resistances of the Eco-Liner

range of laminates are shown in

the table on the opposite page.

Thermal insulation for dry lined internal walls

Description: Polyisocyanurate foam core faced on one side with

12.5mm tapered edge gypsum plaster board.

Composite insulated panel comprising PIR foam

bonded to 12.5mm tapered edge gypsum

plasterboard for internal dry lining applications

for solid walls.

Purpose: Dab and mechanically fixed dry lining applications for

improving thermal performance

Figure 1

Figure 2

FOR WALLS

SLIMLINE

www.ecotherm.co.uk tel: 01702 52016610 11

Eco-Liner

FOR WALLS

SLIMLINE

FOR FREE TECHNICAL ADVICE Call: 01268 597 212/213Email: [email protected]

NEWSLIMLINE

Eco

-Lin

er • NEW

Eco-Liner • NEW

Insulation

Eco-Liner - Mechanically Fixed to Timber Battens

Eco-Liner - Dot & Dab Application

Insulation Total R-value U-value

thickness (mm) thickness (mm) (m2K/W) (W/m2K)

25 37.5 1.212 0.55

30 42.5 1.440 0.49

35 47.5 1.667 0.44

40 52.5 1.894 0.40

45 57.5 2.121 0.37

50 62.5 2.349 0.34

55 67.5 2.576 0.31

60 72.5 2.803 0.30

65 77.5 3.031 0.28

70 82.5 3.258 0.26

75 87.5 3.485 0.25

80 92.5 3.712 0.23

90 102.5 4.167 0.21

100 112.5 4.621 0.19

Insulation Total R-value U-value

thickness (mm) thickness (mm) (m2K/W) (W/m2K)

25 37.5 1.212 0.57

30 42.5 1.440 0.51

35 47.5 1.667 0.45

40 52.5 1.894 0.41

45 57.5 2.121 0.37

50 62.5 2.349 0.35

55 67.5 2.576 0.32

60 72.5 2.803 0.30

65 77.5 3.031 0.28

70 82.5 3.258 0.26

75 87.5 3.485 0.25

80 92.5 3.712 0.23

90 102.5 4.167 0.21

100 112.5 4.621 0.19

Calculations are based on a 215mm thick solid brickwork wall and includes a 2mm plaster skim coat. Timber battens are 25x50mm at 600mm Centres

2013

Page 7: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

www.ecotherm.co.uk tel: 01702 52016612 13

FOR WALLS

SLIMLINE

Cert 98/3552 Cert 99/3569

FOR ROOFS

TOPLINE

Benefits

■ Facings improve the

thermal resistance of

the retained cavity

■ Produced in sizes which

combine accurately with

standard sized bricks/blocks

■ Maximum insulation for

minimum thickness within

construction depth

■ Offers excellent

thermal resistance in

practical thicknesses

■ Tough, light and easily fitted

using standard wall ties or

simple clipping methods

■ Easily achieves the UK

Building Regulations

thermal standards

Dimensions

Width (mm): 450

Length (mm): 1200

Thickness (mm): 25, 30, 35, 40, 45, 50, 55, 60, 70, 75, 100

Design considerations

A minimum 25mm cavity should always be maintained after the installation of EcoTherm Eco-Cavity lining board,

irrespective of the thickness specified. This will avoid problems associated with completely filled cavities.

BS 5628-1: 2005 Code of Practice for structural use of un-reinforced masonry and BS 5628-2: 2005 structural

use of reinforced and pre-stressed masonry should be consulted, NHBC require 50mm residual cavity.

Wall ties

Wall ties should be long enough to provide a minimum 75mm bed into the mortar joints of the inner skin and

50mm into the outer skin mortar bed. The specified ties should conform to BS EN 845-1:2003 and A1:2008

Specification for ancillary components for masonry ties tension straps, hangers and brackets.

Thermal conductivity

The λ value is typically 0.022W/mK, R varies with thickness, and U-value in traditional masonry cavity walls

with a minimum 25mm cavity is as shown below.

Thermal insulation for cavity walls

Description: Rigid polyisocyanurate foam core with

aluminium foil composite on both sides

Purpose: Partial fill cavity wall insulation

Eco-Cavity formerly Cavity-Wall

Thermal insulation for pitched roofs, floors and ceilings

Description: Polyisocyanurate foam core with aluminium foil

composite on both sides

Purpose: For warm / cold pitched roofs loft ceilings

and floors

Eco-Versal formerly Pitched Roof

Benefits

■ Allows traditional forms of

construction without modern

problems of condensation

■ EcoTherm Eco-Versal can be

used to insulate the roof and

cheeks of dormers and

ceilings

■ Roofs insulated at rafter level

create a warm roof; no pipe

or tank lagging is required

■ Can also be used in cold

pitched roof applications

Dimensions

Width (mm): 1200

Length (mm): 2400

Thickness (mm): 25 - 200

Design considerations

In all over-rafter applications counter battens should be positioned above the EcoTherm Eco-Versal insulation

boards to separate the breathable membrane from the board.

Thermal conductivity

The thermal conductivity, λ value, of EcoTherm Eco-Versal is typically 0.022W/mK. The thermal resistance 'R'

varies with the thickness as shown in the table below.

Thickness Length Width R-value Typical U-value Typical U-value Typical U-value

(mm) (mm) (mm) (m2k/W) light block medium block dense block

(W/m2k) (W/m2k) (W/m2k)

25 1200 450 1.14 0.34 0.41 0.43

30 1200 450 1.36 0.31 0.37 0.39

35 1200 450 1.59 0.29 0.35 0.36

40 1200 450 1.82 0.27 0.32 0.33

45 1200 450 2.05 0.26 0.30 0.31

50 1200 450 2.27 0.24 0.28 0.29

55 1200 450 2.50 0.23 0.26 0.27

60 1200 450 2.73 0.22 0.25 0.25

70 1200 450 3.18 0.20 0.22 0.23

75 1200 450 3.41 0.19 0.21 0.22

100 1200 450 4.55 0.16 0.17 0.17

Thickness Length Width R-value Typical U-value single Typical U-value between and

(mm) (mm) (mm) (m2k/W) layer over rafters (W/m2k) 25mm under rafters (W/m2k)

25 2400 1200 1.14 0.60 0.36

30 2400 1200 1.36 0.52 0.34

35 2400 1200 1.59 0.47 0.32

40 2400 1200 1.82 0.42 0.30

45 2400 1200 2.05 0.39 0.29

50 2400 1200 2.27 0.36 0.27

60 2400 1200 2.73 0.31 0.25

65 2400 1200 2.96 0.29 0.24

70 2400 1200 3.18 0.27 0.23

75 2400 1200 3.41 0.25 0.22

80 2400 1200 3.64 0.24 0.22

90 2400 1200 4.09 0.22 0.20

100 2400 1200 4.55 0.20 0.19

110 2400 1200 5.00 0.18 0.18

120 2400 1200 5.46 0.17 0.17

130 2400 1200 5.91 0.15 0.16

140 2400 1200 6.36 0.14 0.15

150 2400 1200 6.82 0.14 0.15

160 2400 1200 7.27 0.13 0.14

170 2400 1200 7.73 0.12 0.13

180 2400 1200 8.18 0.11 0.13

190 2400 1200 8.64 0.11 0.13

200 2400 1200 9.09 0.10 0.12 FOR FREE TECHNICAL ADVICE Call: 01268 597 212/213Email: [email protected]

SLIMLINE TOPLINE

Insulation

2013

Page 8: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

Cert 07/4487Cert 07/4487

FOR ROOFS

TOPLINE

FOR ROOFS

TOPLINE

Benefits

■ 1 board = 1m2 for easy

measurement

■ Polypropylene fleece side

up for torch on and mastic

asphalt systems

■ Bitumen tissue side up

for roll and pour and

bitumen compatible

single ply membranes

■ Maximum insulation for

minimum thickness

■ Roofs insulated with

EcoTherm Eco-Metre meet

the thermal requirements of

the UK Building Regulations

Dimensions

Width (mm): 834

Length (mm): 1200

Thickness (mm): 30 - 200

www.ecotherm.co.uk tel: 01702 52016614 15

Eco

Therm

Eco

-Metre 4 solu

tion

s in 1

Design considerations

These should be assessed

in accordance with the

BS 6399-2 1997.

Consideration should also be

given to BS 5250: 2002 Code

of Practice for control of

condensation in buildings and

BS 6229: 2003 Code of Practice

for flat roofs with continuously

supported coverings.

Mechanical fixings should be

specified as recommended in

BRUFMA information document

ID/1/2009 mechanical fixings

for rigid PIR roof boards.

Roof loading

Depending on the chosen

waterproofing system, EcoTherm

Eco-Metre is suitable for use on

roof decks that are subject to

limited maintenance foot traffic.

Walkways should be provided

on roofs requiring regular

pedestrian access.

The roof should be boarded out

with protective boarding

whenever site work is to take place

after the roofboard has been laid

and the roof made watertight.

Thermal conductivity

λ = 25-79mm = 0.026W/mK

80-119mm = 0.025W/mK

120mm + = 0.024W/mK

Benefits

■ EcoTherm Eco-Felt is a multi-

purpose roofboard suitable

for mastic asphalt or built-up

felt roofing

■ The core of EcoTherm

Eco-Felt roofboard is

temperature tolerant and

withstands the application

of hot bitumen to the surface

at up to 220°C

■ Roofs insulated with

EcoTherm Eco-Felt meet the

thermal requirements of the

UK Building Regulations

■ Maximum insulation for

minimum thickness

■ Simple application

Dimensions

Width (mm): 600

Length (mm): 1200

Thickness (mm): 30 - 200

Design considerations

These should be assessed

in accordance with

BS 6399-2 1997.

Consideration should also be

given to BS 5250: 2002 Code

of Practice for control of

condensation in buildings and

BS 6229: 2003 Code of Practice

for flat roofs with continuously

supported coverings. Mechanical

fixings should be used as

recommended in BRUFMA

information document

ID/1/2009.

Roof loading

Depending on the chosen

waterproofing system, EcoTherm

Eco-Felt roofboard is suitable for

use on roof decks that are

subject to limited maintenance

foot traffic. Walkways should be

provided on roofs requiring

regular pedestrian access.

The roof should be boarded out

with protective boarding

whenever site work is to

take place after the roofboard

has been laid and the roof

made watertight.

Thermal conductivity

λ = 25-79mm = 0.026W/mK

80-119mm = 0.025W/mK

120mm + = 0.024W/mK

Thermal insulation for flat roofs

Description: Polyisocyanurate foam core faced with bitumen/mineral on one

side and bitumen/polypropylene on the other

Purpose: Torch-on (fully and partially bonded) or roll and pour (fully and

partially bonded) asphalt and single ply bituminous systems

Thermal insulation for flat roofs

Description: Polyisocyanurate foam core faced with bitumenised glass coated

tissue on one side and plain glass tissue on the reverse

Purpose: For built-up felt roofing and asphalt applications

Eco-Felt formerly Multi-Therm

• Torch on • Roll & pour • Mastic asphalt • Single ply bitumen

compatibleEco-Metre

Thickness Length Width R-value Typical U-value Typical U-value Typical U-value

(mm) (mm) (mm) (m2k/W) on metal deck on concrete deck on timber deck

(W/m2k) (W/m2k) (W/m2k)

30 1200 834 1.15 0.72 0.68 0.57

40 1200 834 1.54 0.58 0.55 0.48

50 1200 834 1.92 0.47 0.45 0.40

60 1200 834 2.31 0.40 0.38 0.34

70 1200 834 2.69 0.35 0.34 0.31

80 1200 834 3.20 0.29 0.28 0.26

90 1200 834 3.60 0.26 0.26 0.24

100 1200 834 4.00 0.24 0.23 0.22

110 1200 834 4.40 0.22 0.21 0.20

120 1200 834 5.00 0.19 0.19 0.18

130 1200 834 5.42 0.18 0.18 0.17

140 1200 834 5.83 0.17 0.16 0.16

150 1200 834 6.25 0.15 0.15 0.15

160 1200 834 6.67 0.15 0.14 0.14

170 1200 834 7.08 0.14 0.14 0.13

180 1200 834 7.50 0.13 0.13 0.12

190 1200 834 7.92 0.12 0.12 0.12

200 1200 834 8.33 0.12 0.12 0.11

Thickness Length Width R-value Typical U-value Typical U-value Typical U-value

(mm) (mm) (mm) (m2k/W) on metal deck on concrete deck on timber deck

(W/m2k) (W/m2k) (W/m2k)

30 1200 600 1.15 0.72 0.68 0.57

40 1200 600 1.54 0.58 0.55 0.48

50 1200 600 1.92 0.47 0.45 0.40

60 1200 600 2.31 0.40 0.38 0.34

70 1200 600 2.69 0.35 0.34 0.31

75 1200 600 2.89 0.32 0.31 0.29

80 1200 600 3.20 0.29 0.28 0.26

90 1200 600 3.60 0.26 0.26 0.24

100 1200 600 4.00 0.24 0.23 0.22

110 1200 600 4.40 0.22 0.21 0.20

120 1200 600 5.00 0.19 0.19 0.18

130 1200 600 5.42 0.18 0.18 0.17

140 1200 600 5.83 0.17 0.16 0.16

150 1200 600 6.25 0.15 0.15 0.15

160 1200 600 6.67 0.15 0.14 0.14

170 1200 600 7.08 0.14 0.14 0.13

180 1200 600 7.50 0.13 0.13 0.12

190 1200 600 7.92 0.12 0.12 0.12

200 1200 600 8.33 0.12 0.12 0.11

TOPLINE TOPLINE

Insulation

2013

Page 9: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

www.ecotherm.co.uk tel: 01702 52016616 17

Cert 07/4487Cert 07/4487

FOR ROOFS

TOPLINE

FOR ROOFS

TOPLINE

Benefits

■ Provides lightweight, warm-

roof constructions

■ Insulated roofs easily meet

the thermal requirements of

the UK Building Regulations

■ Provides lightweight, warm-

roof constructions

■ Compatible with fully-

adhered and mechanically-

fixed single ply non-

bituminous membranes

■ Maximum insulation for

minimum thickness

■ Simple application

Dimensions

Width (mm): 600, 1200

Length (mm): 1200, 2400

Thickness (mm): 30 – 200

Design considerations

These should be assessed in accordance with BS 6399-2 1997.

Consideration should also be given to BS 5250: 2002 Code of Practice for control of condensation in buildings

and BS 6229: 2003 Code of Practice for flat roofs with continuously supported coverings. Mechanical fixings

should be used as recommended in BRUFMA information document ID/1/2009.

U-values

Eco-Bond waterproofed with a singly ply membrane will give the typical insulation values shown in the

table below.

Thermal conductivity

λ = 25-79mm = 0.026W/mK

80-119mm = 0.025W/mK

120mm + = 0.024W/mK

Benefits

■ Provides lightweight, warm-

roof constructions

■ Insulated roofs easily meet

the thermal requirements of

the UK Building Regulations

■ For use with mechanically

fixed single ply membranes

■ Maximum insulation for

minimum thickness

■ Simple application

Dimensions

Width (mm): 1200

Length (mm): 2400

Thickness (mm): 30 – 200

Design considerations

These should be assessed in accordance with BS 6399-2 1997.

Consideration should also be given to BS 5250: 2002 Code of Practice for control of condensation in buildings

and BS 6229: 2003 Code of Practice for flat roofs with continuously supported coverings. Mechanical fixings

should be as recommended in BRUFMA information document ID/1/2009.

EcoTherm recommends the use of thermally broken tube fasteners.

Thermal conductivity

The thermal conductivity, λ value, of EcoTherm Eco-Fix is typically 0.022W/mK. The thermal resistance ‘R’

varies with thickness as shown in the table below.

Thermal insulation for flat roofs

Description: Polyisocyanurate (PIR) foam with a mineral coated

glass fibre tissue on both sides

Purpose: For fully bonded single ply membrane systems

Thermal insulation for flat roofs

Description: Polyisocyanurate foam core with aluminium foil face

composite on both sides

Purpose: For use with fully mechanically fixed single ply membranes

Eco-Fix formerly Foil-ThermEco-Bond formerly Glass-Therm

Thickness Length Width R-value Typical U-value Typical U-value Typical U-value

(mm) (mm) (mm) (m2k/W) on metal deck on concrete deck on timber deck

(W/m2k) (W/m2k) (W/m2k)

30 1200 600 1.15 0.72 0.68 0.57

40 1200 600 1.54 0.58 0.55 0.48

50 1200 600 1.92 0.47 0.45 0.40

60 1200 600 2.31 0.40 0.38 0.34

70 1200 600 2.69 0.35 0.34 0.31

80 1200 600 3.20 0.29 0.28 0.26

90 1200 600 3.60 0.26 0.26 0.24

100 1200 600 4.00 0.24 0.23 0.22

110 1200 600 4.40 0.22 0.21 0.20

120 1200 600 5.00 0.19 0.19 0.18

130 1200 600 5.42 0.18 0.18 0.17

140 1200 600 5.83 0.17 0.16 0.16

150 1200 600 6.25 0.15 0.15 0.15

160 1200 600 6.67 0.15 0.14 0.14

170 1200 600 7.08 0.14 0.14 0.13

180 1200 600 7.50 0.13 0.13 0.12

190 1200 600 7.92 0.12 0.12 0.12

200 1200 600 8.33 0.12 0.12 0.11

Thickness Length Width R-value Typical U-value Typical U-value Typical U-value

(mm) (mm) (mm) (m2k/W) on metal deck on concrete deck on timber deck

(W/m2k) (W/m2k) (W/m2k)

30 2400 1200 1.36 0.67 0.63 0.53

40 2400 1200 1.82 0.51 0.49 0.43

50 2400 1200 2.27 0.42 0.40 0.36

60 2400 1200 2.73 0.35 0.34 0.31

70 2400 1200 3.18 0.30 0.30 0.27

80 2400 1200 3.64 0.27 0.26 0.24

90 2400 1200 4.09 0.24 0.23 0.22

100 2400 1200 4.55 0.22 0.21 0.20

110 2400 1200 5.00 0.19 0.19 0.18

120 2400 1200 5.46 0.18 0.18 0.17

130 2400 1200 5.91 0.17 0.16 0.16

140 2400 1200 6.36 0.15 0.15 0.15

150 2400 1200 6.82 0.14 0.14 0.14

160 2400 1200 7.27 0.14 0.13 0.13

170 2400 1200 7.73 0.13 0.13 0.12

180 2400 1200 8.18 0.12 0.12 0.12

190 2400 1200 8.64 0.11 0.11 0.11

200 2400 1200 9.09 0.11 0.11 0.10 FOR FREE TECHNICAL ADVICE Call: 01268 597 212/213Email: [email protected]

TOPLINE TOPLINE

Insulation

2013

Page 10: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

APPLICATIONS

• SINGLE PLY ADHERED • SINGLE PLY MECHANICAL FIX

NEW

• TORCH• ROLL AND POUR• ASPHALT• BITUMEN COMPATIBLE

SINGLE PLY

NEWWE'VE GOT IT COVERED

a tapered solution for all applications

www.ecotherm.co.uk tel: 01702 52016618 19

Cert 07/4487Cert 07/4487

FOR ROOFS

TOPLINE

FOR ROOFS

TOPLINE

Benefits

■ EcoTherm Eco-Deck is

manufactured from FSC

(Forest Stewardship Council)

certified timber ply and ZERO

ODP foam

■ EcoTherm Eco-Deck provides

roof constructions which do

not require cross ventilation

of the roof void

■ FSC certified timber OSB

grade 3 – guaranteed legal

and sustainable

■ Compatible with all built up

roofing membranes

■ Maximum insulation for

minimum thickness

■ Simple application

Dimensions

Width (mm): 1200

Length (mm): 2400

OSB thickness (mm): 9

PIR core thickness (mm): 90, 100, 110, 120, 130, 140, 150

Design considerations

These should be assessed in accordance with the BS 6399-2 1997.

Consideration should also be given to BS 5250: 2002 Code of Practice for control of condensation in buildings

and BS 6229: 2003 Code of Practice for flat roofs with continuously supported coverings. Mechanical fixings

should be specified as recommended in BRUFMA information document ID/1/2009 mechanical fixings for

rigid PIR roof boards.

Thermal conductivity

The thermal conductivity, λ value, of EcoTherm Eco-Deck insulation is typically 0.022W/mK. The OSB element

of the roof-deck has a thermal conductivity rating of 0.14W/mK. The thermal resistance ‘R’ varies with

thickness as shown in the table below.

Benefits

■ EcoTherm Eco-Taper creates

falls on flat roofs. It is

manufactured for fast and

easy application

■ Thicknesses ranging from

30-190mm, the widest range

available for a single layered

taper system

■ Mitred boards for both hips

and valleys available

■ EcoTherm Eco-Taper is

ZERO ODP

■ EcoTherm Eco-Taper provides

warm-roof constructions

Dimensions

Width (mm): 1200

Length (mm): 1200

Design considerations

These should be assessed in accordance with the BS 6399-2 1997.

Consideration should also be given to BS 5250: 2002 Code of Practice for control of condensation in

buildings and BS 6229: 2003 Code of Practice for flat roofs with continuously supported coverings.

Mechanical fixings should be specified as recommended in BRUFMA information document ID/1/2009

mechanical fixings for rigid PIR roof boards. In order to determine the U-value of a tapered scheme,

please refer to Annex-C of BS EN 6946: 2007.

Thermal insulation for flat roofs

Description: 9mm OSB grade 3 faced PIR thermal insulation tough,

structural, pre-insulated foil backed roof decking

Purpose: Insulation and decking for flat roof applications

Thermal insulation for tapered roofing schemes

Description: PIR core for single ply. Cut-to-fall for pond-free flat roofs.

Available in 1:60 falls and 1:80 falls

Purpose: For use with single ply or built-up felt roofs

Eco-TaperEco-Deck

FSC Certificate No. C806092FSC.COC.01.2006 Certification Code: CU.COC.806092

1996 Forest Stewardship Council A.C.

By buying products with the FSC label you are supporting the growth of responsible forest managementworldwide

CU-COC-806092

The profile of the boards are as follows:

Non foil (mm) Foil (mm)

1:60 1:80 1:60 1:80

A = 30-50 30-45 A = 30-50 30-45

B = 50-70 45-60 B = 50-70 45-60

C = 70-90 60-75 C = 70-90 60-75

D = 90-110 75-90 D = 90-110 75-90

E = 110-130 90-105

F = 130-150 105-120

G = 150-170 –

H = 170-190 – Thickness Length Width R-value Typical U-value

(mm) (mm) (mm) (m2k/W) (W/m2k)

99 o/all 2400 1200 4.16 0.22

109 o/all 2400 1200 4.62 0.20

119 o/all 2400 1200 5.07 0.18

129 o/all 2400 1200 5.53 0.17

139 o/all 2400 1200 5.98 0.16

149 o/all 2400 1200 6.44 0.15

159 o/all 2400 1200 6.89 0.14

TOPLINE TOPLINE

Insulation

2013

Page 11: with EcoTherm Insulation...IT’S THIN superior rigid insulation BUILT IN MEMBRANE no need for a polythene overlay SUPERB CLIP RETENTION heavy duty facing holds clips tight 8 tel:

superior rigid insulation

EcoTherm Insulation (UK) Ltd.Harvey Road, Burnt Mills Ind. Est., Basildon, Essex, SS13 1QJ tel: +44 (0) 1702 520166 fax: +44 (0) 1702 420636 www.ecotherm.co.uk email: [email protected] consult EcoTherm for details of BBA certificate numbers for specific products

EcoTherm Insulation (UK) Ltd. is registered in England No. 1873816

EcoTherm Insulation offers a wide range of services for

all architects, house builders, housing associations,

specifiers, suppliers and end users.

The services are free of charge on both new build and

refurbishment projects. Our technical support team are

continually updating their knowledge on building trends,

construction methods and the ongoing development of

building materials and Building Regulations.

To contact Technical Services

Tel: +44 (0)1702 520166

Fax: +44 (0)1702 420636

or E-Mail: [email protected]

EcoTherm Technical Support is open

8:30 – 17:00 Monday to Friday

EcoTherm Technical Support

Services available

■ U-value calculations to show compliance with current Building

Regulations for floors, walls and roofs (both flat and pitched)

supported by a detailed report

■ Condensation risk analyses are available on request, again

supported by a detailed report

■ Site visits; our technical team is available to provide on-site

assistance and advice where necessary

■ Full site surveys can be carried out for tapered roof projects

■ Advice on product selection and product data for all EcoTherm

Insulation products

■ General application and fixing on all applications

■ Specification advice

■ Impartial product advice on associated products and proposed

system elements