Upload
others
View
6
Download
0
Embed Size (px)
Citation preview
1 / 12
H900WinterGard PoWer ConneCtion Kit With end Seal inStallation inStruCtionS
THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13
Power connection for H311, H611, and H621
Power connection for H612 and H622
DEScRIpTIONThe WinterGard power connection kit is for use only with the following WinterGard heating cables: H311, H611, H612, H621, and H622.Materials for one power connection and one end seal are included. All WinterGard heating cables are designed for water-pipe freeze protection applications. Only the H612 and H622 cables can be used for both pipe freeze protection and roof and gutter de-icing applications. Do not use this kit with aluminum feed wires. For additional technical support call Pentair Thermal Management at (800) 545-6258.Note: For WinterGard heating cables in pipe heating applications, refer to pages 3–5. For WinterGard Wet heating cables H612 and H622 in roof and gutter de-icing applications, refer to pages 6–8.
TOOLS REqUIRED• Needlenosepliers • Pen• Propanetorchorheatgun • Diagonalcutters• Utilityknife • PanduitCT100crimptool• Adjustablewrench • Screwdriver
ADDITIONAL MATERIALS REqUIRED• ULListedorCSACertifiedjunctionboxsuitableforthelocation,withaclearanceholefor1/2-inchconduitor1/2-inchNPTthreadedhub.
• ForH311,H611,andH621,youmustuseametallicjunctionboxtoensure proper grounding.
• YourapplicationmayrequireadditionalWinterGardaccessories;forexample,H903applicationtapeforpipeapplications;H913/H914roofclipsand/orH915downspouthangersforroofandgutterde-icing applications.
These components are electrical devices. They must be installed correctly to ensure proper operation and to prevent shock or fire. Carefully follow all of the installation instructions and read these important warnings.
• Tominimizethedangeroffirefromsustainedelectricalarcingiftheheating cable is damaged or improperly installed, and to comply with the requirements of Pentair Thermal Management and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection.
• Componentapprovalsandperformancearebasedontheuseofspecifiedparts only. Do not substitute parts or use vinyl electrical tape.
• Theblackheating-cablecoreisconductiveandcanshort.Itmustbeproperly insulated and kept dry.
• Keepcomponentsandheatingcableendsdrybeforeandduringinstallation.
• Damagedbuswirescanoverheatorshort.Donotbreakbraidorbuswirestrands when scoring the jacket or core.
• Buswireswillshortiftheycontacteachother.Keepbuswiresseparated.• Heat-damagedcomponentscanshort.Useaheatgunoratorchwithasoft,yellow,low-heatflame,notabluefocusedflame.Keeptheflamemoving to avoid overheating, blistering, or charring the heat-shrinkable tubes. Avoid heating other components. Replace any damaged parts.
• Useonlyfire-resistantinsulationmaterialssuchasfiberglasswrap.• Leavetheseinstallationinstructionswiththeuserforfuturereference.
Charring or burning the heat-shrinkable tubes in this kit will produce fumes that may cause eye, skin, nose, and throat irritation. Consult Material Safety Data Sheet RAY3122.
CHEMTREC24-houremergencytelephone: (800)424-9300
Non-emergencyhealthandsafetyinformation: (800)545-6258.
WARNING: CAUTION:
AppROvALS718K Pipe Heating Cable, Also Listed as De-Icing and Snow Melting Equipment -ws
KIT cONTENTSItem qty Description
A 4 LabelsB 1 Pipe mounting bracketC 1 LocknutD 1 Blue grommetE 1 SealingfittingwithblackgrommetF 3 Wire nutsG 1 Blackheat-shrinkabletube(1/2"x1")H 1 Green/yellowheat-shrinkabletube(1/4"x6")I 2 Blackheat-shrinkabletubes(1/8"x51/2")J 1 Green grounding screw and kep nutK 1 Gel-filled end sealL 1 RingterminalM 1 Black cloth tape (6" long)N 1 Sealinggasket
B
A
D
F
C
E
H
G
I
J
K
L
M
NWARNING
Fire and Shock Hazard
Self-regulating electrical
heating cable attached to this pipe:
Disconnect before sevicing
Electric Deicing and
Snow Melting Equipment
on PremisesWARNING
Fire and Shock Hazard
Self-regulating electrical
heating cable attached to this pipe:
Disconnect before sevicing
Electric Deicing and
Snow Melting Equipment
on Premises
THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13 2 / 12
Important: For the Pentair Thermal Management warranty to be valid,youmustcomplywithalltherequirementsoutlinedintheseguidelines.
Allthermalanddesigninformationprovidedhereisbasedupona“standard” installation with heating cable fastened to an insulated pipe. For any other application or method of installation, consult Pentair Thermal Management at (800) 545-6258.
HEATING cAbLE SELEcTION AND DESIGNMake sure that the heating cable being used is suitable for your application.RefertotheCommercialandResidentialApplicationandDesign Guide (H53585) for heating cable application information.
1. Determine the heating cable type.UseTable1toselectheatingcablesforinsulatedmetalpipes.UseTable2toselectheatingcablesforinsulatedplasticpipes.Readacross the table to find your pipe size, then drop down to the line corresponding to the lowest air temperature for that application and the correct insulation thickness. The cell at that intersection has a particularshadingandmayhaveanumber.Theshadingindicateswhichheatingcabletouse(keytotheshadingappearsabovethetableheadings). A number represents the spiraling ratio (feet of heating cable per foot of pipe).
If no number appears in the cell, straight trace the pipe. If a number does appear in the cell, spiral trace the pipe.
If your spiraling ratio is 2.0, multiple trace the pipe using two straight traces at the 4 o’clock and 8 o’clock positions.
If your spiraling ratio is 3.0, multiple trace the pipe using three straight traces at the 11 o’clock or 1 o’clock position, and at the 4 o’clock and 8 o’clock positions.
Example 1:Pipe size: 1 inLowestairtemp.: 0°FInsulation thickness: 1/2 inMetal pipe: WinterGard H311Plastic pipe: WinterGard Plus H611, H621 WinterGard Wet H612, H622
Example 2:Pipe size: 2 1/2 inLowestairtemp.: –20°FInsulation thickness: 1/2 in
Metal pipe: 1.3 WinterGard Plus H611, H621 WinterGard Wet H612, H622 (Use1.3feetofheatingcableper foot of pipe.)
Plastic pipe: 2.0 WinterGard Plus H611, H621 WinterGard Wet H612, H622 (Usetwostraighttracesatthe4o’clockand8o’clockpositions.)
Table 1. For METAL pipes with fiberglass insulation or equivalent (based on 40°F maintain temperature)
Table 2. For pLASTIc pipes with fiberglass insulation or equivalent (based on 40°F maintain temperature)
Lowest airtemp. (°F)
Insulationthickness
Nominal pipe size1/2 in 6 in4 in3 in2 1/2 in2 in1 1/2 in1 1/4 in1 in3/4 in
1/2 in1 in
1 1/2 in1/2 in1 in
1 1/2 in2 in
1/2 in1 in
1 1/2 in2 in
0
–20
–40
1.81.3
3.01.81.51.31.11.51.11.1
3.02.01.71.41.21.11.91.41.11.41.1
Key to Table 1: = H311 = H611, H612, H621, H622 = Use a thicker insulation
3.02.01.7
3.01.81.51.31.13.01.81.41.7
3.03.02.01.81.51.13.01.61.41.2
3.01.8
1.41.21.61.21.2
2.01.21.1
1.31.11.4
1.11.1 1.9
1.71.41.21.11.31.1
Lowest airtemp. (°F)
Insulationthickness
Nominal pipe size1/2 in 6 in4 in3 in2 1/2 in2 in1 1/2 in1 1/4 in1 in3/4 in
1/2 in1 in
1 1/2 in1/2 in1 in
1 1/2 in2 in
1/2 in1 in
1 1/2 in2 in
0
–20
–40
Key to Table 2: = H311 = H611, H612 H621, H622 = Use a thicker insulation
H900 DESIGN AND INSTALLATION INFORMATION FOR HEATING cAbLE ON pIpES ONLy (WINTERGARD H311, H611, H621, H612, AND H622 HEATING cAbLES).
3 / 12THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13THERMAL MANAGEMENT SOLUTIONS 3 / 12
2. calculate the total heating cable length required
Length = A + b + c + D + E + F + G + HA Pipe lengthxspiralingratiob 4ftx#gate/globevalvesxvalvelength(ft)xspiralingratioc 2ftx#ball/butterflyvalvesxvalvelength(ft)xspiralingratioD 2ftx#flangesxpipediameter(ft)xspiralingratioE 2ftx#pipesupportsvpipediameter(ft)xspiralingratioF 1 ft for each power connectionG 2 ft for each splice connectionH 3 ft for each tee connection
= Total heating cable length (ft)
3. Determine the maximum heating cable circuit length allowed.SeeTable3onthenextpage.EnsurethatyourcircuitsdonotexceedthemaximumcircuitlengthlistedinTable3.Ifnecessary,use additional shorter circuits.
Example (takenfromExample2[onmetalpipe],page3):Pipe length: 50 ftSpiralratio: 1.3(fromTable1,page3)Globevalves: 3(each0.5ftlong)Pipe supports: 10 supports for 1 in pipePower connections: 1Spliceconnections: 1
WinterGard heating cable required:A Pipelengthxspiralratio = 50 ftx 1.3 = 65.0 ftb 3globevalves(0.5fteach) = 4 ftx 3 x 0.5 x 1.3 = 7.8 ftc 0ball/butterflyvalves = 0 = 0D 0 flanges = 0 = 0E 10 pipe supports = 2 ft x10x0.085*x 1.3 = 2.2 ftF 1 power connection = 1 ft x 1 = 1.0 ftG 1 splice connection = 2 ft x 1 = 2.0 ftH 0 tee connection = 0 = 0
Total heating cable length required = 78.0 ft*1inpipediameter/12inperfoot=0.085foot
HEATING cAbLE INSTALLATION
1. prepare for installation.•Storetheheatingcableinaclean,dryplace.•Completepipingpressuretest.•ReviewtheWinterGardheatingcabledesignandcomparetomaterialsreceivedtoverifythattheproperWinterGardheatingcableandaccessoriesareavailable.TheWinterGardheatingcablewillhavetheheatingcabletypeprintedontheouterjacket.
•WalkthesystemandplantheroutingoftheWinterGardheating cable on the pipe.
2. cut the heating cable to length.•Cuttheheatingcabletothelengthrequired.Thiscanbedonebeforeorafterthecableisattachedtothepipe.Leaveaminimumof1footextraheatingcableforconnectiontopower.Forspliceandteeconnections,leaveaminimumof1footforeachsectionof heating cable. WinterGard heating cable can be cut to length without affecting its heat output per foot.
•Protecttheheatingcableendsfrommoistureormechanicaldamageiftheywillbeleftexposedbeforeconnection.
3. position and attach heating cable to pipe.•Besureallpipingtobetracedisdry.•Installheatingcable,usingstraighttracing,spiraling,ormultiple
tracing according to the “Heating cable selection and design” section on page 3.
•Forstraighttracing,installtheheatingcableonalowerhalfofthepipe;forexample,inthe4o’clockor8o’clockposition.
•Besuretoinstalltheadditionalheatingcablerequiredforvalves,flanges,etc.asindicatedinStep2ofthe“Heatingcableselectionand design” section.
•Whenthedesigncallsforspiraling,beginbysuspendingaloopevery10feetasshowninFigure1.Todeterminethelooplength,obtain the spiral factor from Table 1 or 2 and multiply by 10. For example,ifaspiralfactorof1.3iscalledfor,leavea13-footloopofheatingcableatevery10-footsectionofpipe.Grasptheloopinitscenterandwrapitaroundthepipe.Evenoutthedistancebetweenspiralsbyslidingthewrapsalongthepipe.Useglasstapetosecurethecenterofthelooptothepipe.Securetheheating cable flat to the pipe to obtain good contact.
•TapeWinterGardheatingcabletothepipeat2-footintervalsusingRaychemH903fiberglassapplicationtapeornyloncableties.Donotusevinylelectricaltape,ducttape,metalbands,orwire.
4. Install heating cable end seals, splices, tees, and power connection.•Installallendseals,splices,tees,andpowerconnectionpriorto
plugging in.•Ifsplicingorteeing,useonlytheH910WinterGardSpliceandTeeKittosatisfycodeandagencyrequirements.
•H900kitassemblyinstructionsbeginonpage9.
5. check the installation.•Priortoinstallingthermalinsulation,makesuretheheating
cable is free of mechanical damage (from cuts, clamps, etc.) and thermaldamage(fromsolder,overheating,etc.).
•Visuallycheckallpowerconnections,endseals,splices,andtees.•Usingamegohmmeter,testeachcircuitaccordingtothe
instructions in the “Heating cable testing and maintenance” section (page 5) both before and after installing the thermal insulation.
Figure1.Spiraledheattracing
10 feet
Glass tape(typical)
Heatingcable
Tape afterspiraling heatingcable on pipe
Wrap loopsin oppositedirection
Pull heatingcable looplength
Apply glasstape beforespiralingheating cableon pipe
THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13 4 / 124 / 12THERMAL MANAGEMENT SOLUTIONS
6. Install thermal insulation.•AreliableWinterGardsystemdependsonproperlyinstalledand
weather-proofed thermal insulation.
•Ensurethat type and thickness of the insulation are in accordance with the information in the heating cable selection tables on page3andthatallpipework—includingvalves,joints,wallpenetrations, and other elements—has been fully insulated.
•Minimize the potential for mechanical damage to the heating cable afterinstallationbyinstallingtheinsulationassoonasyouhavechecked the cable installation.
7. Mark the installation.•Place“Warning”labelsforpipetraceapplicationsontheoutersurfaceoftheinsulationat10-footintervals(onalternatingsides of the pipe) to indicate the presence of WinterGard electric heating cable. Additional labels and application tape are contained intheH903kit.
8. check the installation•Priortopowering,checktobesuretheheatingcableisfreeof
mechanical damage (cuts, clamps, etc.).•Visuallycheckallpowerconnections,endseals,splices,andteesfor
proper installation.•Usinga Megohmmeter, test each circuit according to the instructions
in the “Heating cable testing and maintenance” section below.
HEATING cAbLE TESTING AND MAINTENANcE
Pentair Thermal Management recommends that the insulation resistance between the bus wires and the heater grounding braid or metal pipe should be checked during installation using a 2500-Vdcmegohmmeter.Minimumreadingshouldbe1000megohms,regardless of length.Recordtheoriginalvaluesforeachcircuit.Takeadditionalreadingsduring regularly scheduled maintenance and compare to the original value.Ifthereadingsfallbelow1000megohms,inspectcablesandinsulation for signs of damage.
If physical damage is found, the entire damaged section must be removedandanewsectionofheatingcablesplicedinusingonlyapprovedWinterGardH910splicekits.Donotrepairthedamagedheating cable section.If physical damage cannot be found, the complete circuit should be removedandreplacedwithnewWinterGardheatingcable.
WARNING: Shock and Fire Hazard. Damaged heating cable or components can cause electrical shock, arcing, and fire. Do not attempt to energize damaged cable or components. Replace them immediately using a new length of heating cable and the appropriate WinterGard accessories.
ELEcTRIcAL pROTEcTION
voltage ratingH311,H611,andH612 110–120VacH621 208–240VacH622 208–240Vac
Forthemaximumheatingcablecircuitlengthpermittedforagivencircuitbreakerrating,refertoTable3.Limityourcircuitlengthbasedon your lowest anticipated start-up temperature.
Ground fault protection:PentairThermalManagementandnationalelectricalcodesrequireground-faultequipmentprotectiononeachheatingcablebranchcircuit. To reduce the risk of fire caused by damage or improper installation,circuitbreakerssuchasSquareDQO-EPDandQOB-EPDorequivalent,witha30-mAtriplevel,shouldbeused.Alternativedesignsprovidingcomparablelevelsofground-faultprotectionmayalso be acceptable. For technical assistance, call Pentair Thermal Management at (800) 545-6258.
Table 3. Maximum heating cable circuit length on pipe
circuit breaker rating (A)
Maximum heater length (ft) per circuit at start-up temperature
Heating cable type 0°F 40°FWinterGard 120 v H311 on pipe
15 150 25020 200 25030 250 250
WinterGard plus 120 v H611 on pipe
15 125 150 20 140 19530 200 200
WinterGard plus 240 v H621 on pipe
15 200 25520 250 34030 375 400
WinterGard Wet 120 v H612 on pipe
15 125 15020 140 19530 200 200
WinterGard Wet 240 v H622 on pipe
15 200 25520 250 34030 375 400
Note: Maximumcircuitlengthsarebasedonstart-upload.Steady-stateampsper foot is dependent upon heating cable temperature.
Table 4. product data—WinterGard products on pipe only
Heating cable type WinterGard WinterGard plus WinterGard WetH311 H611 H621 H612 H622
Servicevoltage(V) 120 120 240 120 240Thermaloutputat40°F(W/ft) 3 6 6 6 6Weight per 100 ft (lb) 6 6 6 9 9Minimuminstallationtemp.(°F) 0 0 0 0 0Maximumexposuretemp.(°F) 150 150 150 150 150Exposuretochemicals None None None None NoneEnvironment Useonlyindryordinary
(nonhazardous) areas. Useonlyindryordinary (nonhazardous) areas.
Useonlyinwetordryordinary(nonhazardous) areas.
5 / 12THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13
HEATING cAbLE DESIGN
OnlyWinterGardWetH612120-VandH622240-VheatingcablesaresuitableforusewiththeH900powerconnectionkitforroofand gutter de-icing applications.
1. calculate the heating cable length required.
Length = A + b + c + D + E + F + GA Roofedgelength(ft)xfeetofheatingcableperfootofroofedge
(From Table 5)b Roofedgelength(ft)x0.5*c Total gutter length (ft)D Total downspout length (ft) + 1 (ft)E 1 ft for each power connectionF 2 ft for each splice connectionG 3 ft for each tee connection
= Total heating cable length (ft)*Roofextension:Thislengthallowstheheatingcabletoextendintotheguttertoprovideacontinuousdrainpath,orwherenoguttersarepresent,extendsbeyond the roof edge to form a drip loop.
Note: Pentair Thermal Management recommends a gutter and downspouts to provideacontinuouspathformeltedwater.
Table 5. WinterGard Wet cable length for roof de-icing
Standing seam metal roof:Eave overhang Shingle roof 18 inch seam 24 inch seam0 2.0 ft 2.5 ft 2.0 ft12" 2.8 ft 2.8 ft 2.4 ft24" 3.8 ft 3.6 ft 2.9ft36" 4.8 ft 4.3 ft 3.6 ftNote: Pentair Thermal Management recommends a gutter and downspouts to provideacontinuouspathformeltedwater.
Important: For the Pentair Thermal Management warranty to be valid,youmustcomplywithalltherequirementsoutlinedintheseguidelines.
Alldesigninformationprovidedhereisbasedona“standard”shakeor shingle roof application. For any other application or method of installation, consult Pentair Thermal Management at (800) 545-6258.
HEATING cAbLE INSTALLATION
1. prepare for installation.•Storetheheatingcableinaclean,dryplace.•UseonlythefollowingPentairThermalManagementaccessoriestosatisfycodeandagencyrequirements:-H900WinterGardPlug-inPowerConnectionKit(withendseal)-H910WinterGardSpliceandTeeKit(ifsplicingorteeing)-H915DownspoutHangers-H913/H914RoofClips
•Carefullyplantheroutingoftheheatingcableforroofandgutterde-icing.
•Makecertainguttersanddownspoutsarefreeofleavesandotherdebris.
2. cut the heating cable to length.•Cuttheheatingcabletothelengthrequired.Thiscanbedonebeforeorafteritisinstalled.Leaveaminimumof1footextraheatingcableforconnectiontopower.Forspliceandteeconnectionsleaveaminimumof 1 foot for each section of heating cable. WinterGard heating cable can be cut to length without affecting its heat output per foot.
•Protecttheheatingcableendsfrommoistureandmechanicaldamageif they will be leftexposedbeforeconnection.
3. position and attach the heating cable.
On roofs•Looptheheatingcableontheoverhangareaoftheroof.Thisisthepartthatextendspastthebuildingwall.Extendthebottomofeachheatingcableloopovertheroofedgeand,usingaUV-resistantcabletie, connect the bottom of each loop to the cable running in the gutter to ensure a drainage channel off the roof and into the gutter and downspout. The cable running in the gutter should remain against thebottomofthegutter.Extendthetopofeachheatingcableloopbeyondwherethewalljoinstheroof.PentairThermalManagementrecommends2-footclip-spacingalongtheroofedge.Seethe“Heatingcable design” section (Table 5) for spacing and layout information.
•UseWinterGardH913/H914roofclipstoattachheatingcabletotheroofsurface.Onekitcontainstendoubleroofclipsforapproximately7linearfeetofroofedge.OneH914kitcontains50roofclipsforapproximately35linearfeetofroofedge.
For flat roofs, the heating cable can be spaced as needed to create runoffpathsformeltingiceandsnow.Usesingle-endedclipslocatedat3-footintervalstosecurethecabletotheroof.
Roofclipsmaybeattachedtoashakeorshingleroofwithnailsorscrews.Resealthenailorscrewholesifnecessarybeforeinstallingheatingcableintheclips.Roofclipsmaybeattachedtoametalroofusingscrew,nailoradhesive.(SeeH56723installationinstructionformore details.)
•Abarrier(snowfence)canbeplacedontheroofabovetheheatingcable.Thispreventsdamagetothecableandkeepstheinstallationfrom coming loose due to ice slides. If desired, the heating cable can beattachedtothebarrierwithUV-resistantcableties,insteadofusing roof clips. Do not use wire or other materials because they may damage the heating cable.
In gutters and downspouts•Runheatingcablealongguttersandintodownspouts,endingbelowthefreezinglevel.Permanentattachmentofthecabletothegutterbottomisnotnecessary.Looptheheatingcableindownspoutsifconvenient,suchaswhenthedownspoutisnotattheendoftherun,orusetheH910spliceandteekittoteedownthedownspout.
•UseWinterGardH915downspouthangerstoprotecttheheatingcablefromfrayingandfromdamagefromsharpedgesandtoprovidestrainrelief.RefertotheH915kitinstructionsforinstallationdetails.
•UseWinterGardH913/H914roofclipstorouteheatingcableintoandoutofthegutterinsuchawayastopreventabrasiontothecable. Protect all cable that protrudes past the lower opening of the downspout.
H900 DESIGN AND INSTALLATION INFORMATION FOR ROOF AND GUTTER DE-IcING ONLy (WinterGard Wet H612, and H622 Heating cables)
Example:
Roofedge: 40ftRoofoverhang: 1ftRoofgutter: 40ftDownspout: 15 ftPower connection: 2 eaTee connection: 1 eaVoltageavailable: 120VCBSizeAvailable: 15AStart-uptemperature: 0°F
WinterGard Wet heating cable required:A Roofedge: 40ftx2.0
(from Table 5) = 80 ftb Roofextension: =40ftx 0.5 = 20 ftc Roofgutter: = 40 ftD Downspout: = 15 ft + 1 ft = 16 ftE Power connection: 1 ft x 2 ea = 2 ftF SpliceConnections: = 0G Tee connection: 3 ft x 1 ea = 3 ft
Total WinterGard Wet heating cablerequired: = 161 ft**
**Thistotalexceeds100-ftmaximumcircuitlength(seeTable6),thereforetwoseparatecircuitsarerequired.
THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13 6 / 12
4. Install heating cable end seals, splices, tees, and power connection.•Installallendseals,splices,tees,andpowerconnectionpriorto
plugging in.•FollowtheH900kitinstallationinstructionsbeginningonpage9.•Useonlyweatherproofjunctionboxesapprovedforwetlocations
when installing WinterGard H612 and H622 heating cable with the H900PowerConnectionKitforroofandgutterapplications.
5. Mark the installation.A label indicating the presence of electric de-icing and snow-meltingequipmentonthepremisesisincludedwiththisunit.Thelabelmustbepostedattheelectricaloutletcover.Thelabelmustbeclearlyvisible.
6. check the installation.•Priortopowering,checktobesuretheheatingcableisfreeof
mechanical damage (cuts, clamps, etc.).•Visuallycheckallpowerconnections,endseals,splices,andtees
for proper installation.•Usingamegohmmeter,testeachcircuitaccordingtothe
instructions in the “Heating cable testing and maintenance” section below.
HEATING cAbLE TESTING AND MAINTENANcE
Makesurethatgutteranddownspoutsarefreeofleavesandotherdebris prior to the winter season.
Pentair Thermal Management recommends that the insulation resistance between the bus wires and the heating cable grounding braid or metal pipe should be checked during installation using a 2500-Vdcmegohmmeter.Minimumreadingshouldbe1000megohms,regardless of circuit length.
Recordtheoriginalvaluesforeachcircuit.Takeadditionalreadingsduring regularly scheduled maintenance and compare to the original value.Ifthereadingsfallbelow1000megohms,inspectheatingcablesand insulation for signs of damage.
If physical damage is found, the entire damaged section must be removedandanewsectionofheatingcablesplicedinusingonlyapprovedWinterGardH910splicekits.Donotrepairthedamagedheating cable section.
If physical damage cannot be found, the complete circuit should be removedandreplacedwithnewWinterGardheatingcable.
WARNING: Shock and Fire Hazard. Damaged heating cable or components can cause electrical shock, arcing, and fire. Do not attempt to energize damaged cable or components. Replace them immediately using a new length of heating cable and the appropriate WinterGard accessories.
ELEcTRIcAL pROTEcTION
voltage rating
H612 110–120Vac
H622 208–240Vac
Ground fault protection: PentairThermalManagementandnationalelectricalcodesrequireground-faultequipmentprotectiononeachheatingcablebranchcircuit. To reduce the risk of fire caused by damage or improper installation,circuitbreakerssuchasSquareDQO-EPDandQOB-EDPDorequivalent,witha30-mAtriplevel,shouldbeused.Alternativedesignsprovidingcomparablelevelsofground-faultprotection may also be acceptable. For technical assistance, call Pentair Thermal Management at (800) 545-6258.
Table 6. Maximum heating cable circuit length for roof and gutter de-icing, downspouts and refrigeration condensate drains
circuit breaker rating (A)
Maximum heater length (ft) per circuit at start-up temperature
Heating cable type 0°F 32°FWinterGard Wet 120 v H612 in downspout and refrigeration condensate drains
15 100 12520 125 16530 150 200
WinterGard Wet 240 v H622 in downspout and refrigeration condensate drains
15 200 25020 250 32030 305 400
Note: Maximumcircuitlengthsarebasedonstart-upload.Steady-stateampsper foot is dependent upon heating cable temperature.
Table 7. product data—WinterGard Wet H612 and H622 for roof and gutter de-icing only
H612 H622Servicevoltage(V) 120 240Thermaloutputat32°F(W/ft)(iniceandsnow) 8 8Weight per 100 ft (lb) 9 9Minimuminstallationtemp.(°F) 0 0Maximumexposuretemp.(°F) 150 150Exposuretochemicals None NoneEnvironment Useonlyinordinary(nonhazardous)areas. Useonlyinordinary(nonhazardous)areas.
7 / 12THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13
H913/H914 Roof clip
H915Downspouthanger
H915Downspout
hanger
Cable ties H910 Tee
End seal (included in H900 and H910 kits)
End seal (included inH900 and H910 kits)
H900Power connection
Note:De-icing andsnow meltingequipment labelmust be placedon junction boxcover.
H913/H914 Roof clip
H900Power
connection
Note:De-icing andsnow meltingequipment labelmust be placedon junction boxcove r.
End seal (included inH900 and H910 kits)
Drip loops
Roof without gutters or downspouts
Roof with gutters and downspouts
Note:• In all locations, route and secure cabletoavoidpossiblemechanicaldamage, such as from ladders, etc.
THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13 8 / 12
Outer jacket Braid Bus wires
Conductive coreInner jacket
Braid Bus wires
Conductive coreInner jacket
WinterGard H311, H611, H621Heating cables with braid and no outer jacket WinterGard H612, H622
Heating cables with braid and outer jacket
Compression washer -flat side up against blue grommetBlue grommet
6 3/4 in
6 in
1A For H612 and H622 heating cables only
For all cables2 3
7 in
1b
Note:Instructionsgenerallyshowheatingcablewithbraidandouterjacket.Cableswithnoouterjacketlookslightlydifferentfromthoseillustrated.
• Opensealingfittinganddiscardblackgrommet.• Slidepartsontocableasshown.
• Pushbraidbacktoloosenslightly.• Gentlyspreadapartbraidasshown.• Bendheatingcableandworkit
through the opening in the braid.
• Lightlyscorecompletelyaroundandthendownouterjacket.
• Bendheatingcabletobreakjacketatscore;peeloffouterjacket.
• Positionbraidononesideofheatingcable.• Straightenthebraidandtwistintoa“pigtail.”• Lightlyscorecompletelydownandaroundtheinnerjacket.• Bendheatingcabletobreakjacketatscore;peeloffinnerjacket.
H900 pOWER cONNEcTION KIT
Identify heating cable
For H612 and H622 heating cables only
9/12THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13
1/4 in
1/4 in
1/2 in
1/2 in
1/4 in
4
6
8
9b
5
7
9A
•Notchcoreatend.• Twistbackandpeelbuswires
from core.
• Slide51/2inblackshrink tubes into place against conductivecore.
• Shrinktubingbymovingheatsourcecontinuously from side to side.
• Center1inblackshrinktubeoverendof heating cable as shown.
•Heattubeevenlyuntilitshrinksandadhesiveflowsoutbothends.
• Immediatelypinchwithpliersbetweenwires while tube is still hot. Hold for 10 seconds to ensure seal.
• Trimbraid.• Crimpringterminalontobraid.• Discardblackgrommet
supplied with sealing fitting.• Slidepartsontoheatingcable
as shown.
• Scorebetweenbuswiresatbasejacket.• Bendcoretobreakfreeatbasejacket.• Peelcoreandanyremainingmaterialfrombuswires.
• Slipgreen/yellowtubeoverbraidandshrink.
• Slidepartsintopositionasshown.
Position flat side of compression washer against the blue grommet.
cAUTION: Health Hazard. consult material safety datasheet RAy3122.
For H612 and H622 heating cables only
For H311, H611, and H621 heating cables only
THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13 10 / 12
Lock nut
Sealing gasket
11A
12A
10
Electric Deicing and
Snow Melting Equipment
on Premises
13
11b
12b
•Metallicjunctionboxmustbeusedto ensure proper ground.
• Attachringterminalto mounting bracket as shown.
• Insertheatingcableand tighten fitting.
•Makeconnectionsas shown.
• Thewirenutsincluded are not intended for use with aluminum feed wires.
• Apply“ElectricDe-icing” label to junctionboxcover.
Note: For WinterGard Wet cables, follow instructions providedwithjunctionboxto seal against water if used in wet locations.• Insertheatingcableand
tighten fitting as shown.
•Makeconnectionsasshown.
• Thewirenutsincluded are not intended for use with aluminum feed wires.
Note:Forjunctionboxwith clearance hole, use lock nut.• Insertsealingfitting.
For H612 and H622 heating cables only
For roof and gutter applications only
For H311, H611, H621 heating cables only
For H612 and H622 heating cables onlyFor H311, H611, H621 heating cables only
For pipe applications
11 / 12THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13
Note:Theendsealisdesignedtobeinstalledonlyonce;itcannotberemovedfromtheheating cable once installed. Do not use until ready for final installation.
1 in
1A
2A
3A
2 in
1b
2b
3b
4b
• Cleanlycutofftheend of the cable.
• Scoredownandaroundouterjacket1inch from the end.
• Removetheouterjacket.
• Donotcutordamageinnerjacket.
• Unravelandremoveexposedbraid.
• Firmlypushendseal onto the cable (at least 1 1/2 inches).Somegelmay ooze out.
• Donottwistortrytoremovetheendseal during or after insertion. Do not reuse an end seal.
• Firmlypushendsealonto the cable (at least 11/2inches).Somegelmay ooze out.
• Donottwistortrytoremovetheendseal during or after insertion. Do not reuse an end seal.
• Cleanlycutofftheendof the cable.
• Pushthebraidback2inches from the cable end.
• Slidethebraidupagainst the end seal and secure with the 6-inch length of tape provided.
End Seal for H612 and H622 End Seal for H311, H611, H621
H900 END SEAL
12 / 12THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardH900-IM-H53665 01/13
WWW.THERMAL.PENTAIR.COM
© 1998-2013 Pentair. PN 951129-000
NORTH AMERICATel: +1.800.545.6258Fax: +1.800.527.5703Tel: +1.650.216.1526Fax: [email protected]
EuROPE, MIddLE EAsT, AfRICATel: +32.16.213.511Fax: [email protected]
AsIA PACIfICTel: +86.21.2412.1688Fax: [email protected]
LATIN AMERICATel: +55.11.2588.1400Fax: [email protected]
Pentair, WinterGard, WinterGard Plus and WinterGard Wet are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
LIMITED WARRANTy
PentairThermalManagementwarrantsallRaychemwholesaledistribution self-regulating heating cables and components againstfaultyworkmanshipanduseofdefectivematerialsfor two (2) years from the date of purchase. This warranty can be amended only by a written instrument signed by a duly authorized officer of Pentair Thermal Management. Buyer's exclusiveremedyunderthiswarrantyshallbetohavePentairThermal Management, within a reasonable time, repair such goods or supply replacement goods or credit Buyer's account for suchgoodsandaccepttheirreturnwhicheverPentairThermalManagement may elect at its sole discretion. Pentair Thermal Managementshallinnoeventbeliableforthecostofremovalor installation, for loss or damage to or loss of use of facilities orotherproperty,lossofrevenue,lossofuseofrevenue,lossof anticipated profits, or other damages or costs of any kind whatsoever,whetherdirect,indirect,incidental,orconsequential.
Notwithstanding the foregoing, Pentair ThermalManagementshall have no liabilitywhatsoever unless: (a) Buyer promptlynotifiesPentairThermalManagementinwritingafterdiscoveryofanallegednonconformityand includesadetailedexplanationoftheallegednonconformity; (b)Buyerpromptlyreturns thegoodsto Pentair Thermal Management postage prepaid, at the address obtainedbycallingCustomerServiceat1-800-545-6258or650-216-1526; and (c) Pentair ThermalManagement' examinationof such goods establishes to Pentair Thermal Management' satisfaction that such alleged nonconformities actually existand occurred in the cause of proper and normal use and were not caused by accident, misuse, neglect, alteration or improper installation, repair or testing or such other cause outside of the responsibilityofPentairThermalManagementunderthisLimitedWarranty.
THE FOREGOING WARRANTY IS IN LIEU OF ALL OTHERREPRESENTATIONS, WARRANTIES, OR CONDITIONS,EXPRESSOR IMPLIED, INCLUDINGWITHOUTLIMITATIONANYIMPLIEDWARRANTYOFMERCHANTABILITY, FITNESSFORAPARTICULARPURPOSEORNONINFRINGEMENT,ANDOFANYOTHEROBLIGATIONORLIABILITYONTHEPARTOFPENTAIRTHERMALMANAGEMENT,WHETHERBYSTATUTE,CONTRACT,STRICTLIABILITY,TORTOROTHERWISE.
If the goods are a consumer product in buyer’s jurisdiction,theaboveexclusionor limitationof incidental or consequentialdamages and the above disclaimer of impliedwarrantiesmaynot apply. The term of any such implied warranty is limited to the termofthistwo-yearLimitedWarranty.Somejurisdictionsdonotallow limitations on how long an implied warranty lasts, so the above limitationmaynot apply. Thiswarranty gives consumersspecific legal rights,andconsumersmayalsohaveotherrights,whichvarybyjurisdiction.