40
WINS H-TEC FIRE PROTECTION PANEL (Calcium Silicate)

WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

  • Upload
    others

  • View
    19

  • Download
    2

Embed Size (px)

Citation preview

Page 1: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TECFIRE PROTECTION

PANEL(Calcium Silicate)

Page 2: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

Page 1

WINS H-TEC FIRE PROTECTION PANELPHYSICAL AND MECHANICAL PROPERTIES

Test Description Standard Test Result

Density

Resistance to impact

Moisture content

Dimension

Surface condition

Sound transmission loss

BS EN 1170-6:1998

BS 5669 :Part 1:1989, Clause 21

BS EN 772:1993

BS 5669:Part1:1989, Clause 8

By direct measurement

1.05g/cm3

Class A

12.35%

Average thickness: 8.87mm

No visible damage

13.98MPa

Dimensional changesassociated with changesin relative humidity

Tensile strength andelongation at break

BS 2782:Part 10:Method 1003:1977

BS EN 318:2002

BS 5669 :Part 1:1989,Clause 19

Increase in mass(water absorption)& thickness(swelling)

Microscopic examinationof bulk materials

In-house methodsG-T-023 & G-T-028

BS 2782:Part 10:Method 1005:1997

BS 2750 Part 3:1995

Flexural strength

Water absorption: 34.99%;Swelling: 0.08%

55dB

Non-asbestos

Length change:generally within 0.02%

Tensile strength: 6.98MPa

Elongation at break: 0.14%

Thickness change:generally within 0.12%

Page 3: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.1:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

HORIZONTAL ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 2

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Enclosure support, steel C-channel or L-angles

4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

5 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm.

6 Steel cable tray

7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

8 Steel angle minimum 25mmx25mmx0.6mm thick

Legend :

1

35

4

2

7

8

6

7

Page 4: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.2:THREE-SIDED WINS H-TEC FIRE PROTECTION PANEL

HORIZONTAL ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 3

9

7

1 2 7

3

57

48

6

6

1 2 4

7

5

107

978

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm.

5 M4 Self-tapping screw at nominal 200mm centers

6 M6 all steel expanding �xing at 500mm nominal centers

7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

8 Steel angle minimum 25mmx25mmx0.6mm thick

9 General E&M services. e.g. cable trunking and steel pipe etc.

Cantilever arm at maximum 1250mm centers

Legend :

10

Page 5: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.3:TWO-SIDED WINS H-TEC FIRE PROTECTION PANEL

ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 4

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

5 M4 Self-tapping screw at nominal 200mm centers

6 M6 all steel expanding �xing at 500mm nominal centers

7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

8 Steel angle minimum 25mmx25mmx0.6mm thick

9 General E&M services. e.g. cable trunking and steel pipe etc.

Legend :

3

9

6

8

5

7

21

7

7

4

Page 6: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.4:ONE-SIDED WINS H-TEC FIRE PROTECTION PANEL

ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 5

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

5 M4 Self-tapping screw at nominal 200mm centers

6 M6 all steel expanding �xing at 500mm nominal centers

7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

8 Steel angle minimum 25mmx25mmx0.6mm thick

9 General E&M services. e.g. cable trunking and steel pipe etc.

Legend :

39

4

6

51 2 87

Page 7: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.5:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

VERTICAL ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 6

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

5 Steel cable tray

6 M4 Self-tapping screw at nominal 200mm centers

7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

8 General E&M services. e.g. cable trunking and steel pipe etc.

9 Steel angle minimum 25mmx25mmx0.9mm thick fasten the service duct to the wall at nominal 1220mm centers.

Construction wall

Concrete �oor

Legend :

10

11

7

2

1

3

10

4

6

11

39

8

7

5

Page 8: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.6:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

HORIZONTAL ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 7

1

35

4

2

7

8

6

9

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Enclosure support, steel C-channel or L-angles

4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

5 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm.

6 Steel cable tray

7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

8 Steel angle minimum 25mmx25mmx0.6mm thick

Legend :

Page 9: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.7:THREE-SIDED WINS H-TEC FIRE PROTECTION PANEL

ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 8

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm.

5 M4 Self-tapping screw at nominal 200mm centers

6 M6 all steel expanding �xing at 500mm nominal centers

7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

8 Steel angle minimum 25mmx25mmx0.6mm thick

9 General E&M services. e.g. cable trunking and steel pipe etc.

Cantilever arm at maximum 1250mm centers

Legend :

10

9

7

1 2 7

3

57

48

6

6

1 2 4

7

5

107

978

Page 10: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.8:TWO-SIDED WINS H-TEC FIRE PROTECTION PANEL

ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 9

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

5 M4 Self-tapping screw at nominal 200mm centers

6 M6 all steel expanding �xing at 500mm nominal centers

7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

8 Steel angle minimum 25mmx25mmx0.6mm thick

9 General E&M services. e.g. cable trunking and steel pipe etc.

Legend :

3

9

6

8

5

7

21

7

7

4

Page 11: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.9:ONE-SIDED WINS H-TEC FIRE PROTECTION PANEL

ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 10

39

4

6

51 2 87

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

5 M4 Self-tapping screw at nominal 200mm centers

6 M6 all steel expanding �xing at 500mm nominal centers

7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

8 Steel angle minimum 25mmx25mmx0.6mm thick

9 General E&M services. e.g. cable trunking and steel pipe etc.

Legend :

Page 12: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

FIG. NO.10:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

VERTICAL ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

Page 11

1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

5 Steel cable tray

6 M4 Self-tapping screw at nominal 200mm centers

7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

8 General E&M services. e.g. cable trunking and steel pipe etc.

9 Steel angle minimum 25mmx25mmx0.9mm thick fasten the service duct to the wall at nominal 1220mm centers.

Construction wall

Concrete �oor

Legend :

10

11

7

2

1

3

10

4

6

11

39

8

7

5

Page 13: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

FIG. NO. 1:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

HORIZONTAL ENCLOSURE SYSTEM

Page 12

1 WINS H-Tec �re protection panel, 9mm thick

2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

3 Enclosure support, steel C-channel or L-angles

4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

5 Steel channel collar, 32x50x0.5mm thick at butt joints at nominal 1220mm centers

6 Steel cable tray

7 Steel angle minimum 25x25x0.6mm thick

8 M6 all steel expanding �xing at 500mm nominal centers

9 M4 Self-tapping screw at nominal 200mm centers

General E&M services. e.g. cable trunking and steel pipe etc.

Cantilever arm at maximum 1250mm centers

Steel angle minimum 50x50x0.9mm thick fasten the service duct to the wall at nominal 1200mm centers

Construction wall

Concrete �oor

C-channel 50x50x50x0.6mm thick

Access panel not exceeding 610mmx610mm

Legend :

10

11

12

13

14

15

16

ACCESSPANEL

(OPTIONAL)

1

15

9

16

35

4

2 6

7

Page 14: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

FIG. NO. 2: THREE-SIDED CONSTRUCTION FROM FLOOR SOFFIT

FIG. NO.2: THREE-SIDED CONSTRUCTION FROM SIDE WALL

Page 13

1 WINS H-Tec �re protection panel, 9mm thick

2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

3 Enclosure support, steel C-channel or L-angles

4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

5 Steel channel collar, 32x50x0.5mm thick at butt joints at nominal 1220mm centers

6 Steel cable tray

7 Steel angle minimum 25x25x0.6mm thick

8 M6 all steel expanding �xing at 500mm nominal centers

9 M4 Self-tapping screw at nominal 200mm centers

General E&M services. e.g. cable trunking and steel pipe etc.

Cantilever arm at maximum 1250mm centers

Legend :

10

11

4 HRS. INTEGRITY

ACCESSPANEL

(OPTIONAL)

ACCESSPANEL

(OPTIONAL)

4

487

87

10

1 2 5 9

410

1 2 5 9 9

4

5

4

5

4 HRS. INTEGRITY

ACCESSPANEL

(OPTIONAL)

ACCESSPANEL

(OPTIONAL)

81 2

5 7

10911

81

5

72

4

1 2 910

Page 15: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

Page 14

1 WINS H-Tec �re protection panel, 9mm thick

2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

3 Enclosure support, steel C-channel or L-angles

4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

5 Steel channel collar, 32x50x0.5mm thick at butt joints at Fig nominal 1220mm centers

6 Steel cable tray

7 Steel angle minimum 25x25x0.6mm thick

8 M6 all steel expanding �xing at 500mm nominal centers

9 M4 Self-tapping screw at nominal 200mm centers

General E&M services. e.g. cable trunking and steel pipe etc.

Legend :

10

4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

FIG. NO. 3:TWO-SIDED WINS H-TEC FIRE PROTECTION PANEL ENCLOSURE SYSTEM

ACCESSPANEL

(OPTIONAL)

4

10

87

5921

Page 16: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

FIG. NO. 4:ONE-SIDED WINS H-TEC FIRE PROTECTION PANEL ENCLOSURE SYSTEM

Page 15

1 WINS H-Tec �re protection panel, 9mm thick

2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

3 Enclosure support, steel C-channel or L-angles

4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

5 Steel channel collar, 32x50x0.5mm thick at butt joints at Fig nominal 1220mm centers

6 Steel cable tray

7 Steel angle minimum 25x25x0.6mm thick

8 M6 all steel expanding �xing at 500mm nominal centers

9 M4 Self-tapping screw at nominal 200mm centers

General E&M services. e.g. cable trunking and steel pipe etc.

Legend :

10

4

10

5

8

91 2 7

Page 17: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 WINS H-Tec �re protection panel, 9mm thick

2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

3 Enclosure support, steel C-channel or L-angles

4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

5 Steel channel collar, 32x50x0.5mm thick at butt joints at nominal 1220mm centers

6 Steel cable tray

7 Steel angle minimum 25x25x0.6mm thick

8 M6 all steel expanding �xing at 500mm nominal centers

9 M4 Self-tapping screw at nominal 200mm centers

General E&M services. e.g. cable trunking and steel pipe etc.

Cantilever arm at maximum 1250mm centers

Steel angle minimum 50x50x0.9mm thick fasten the serviceduct to the wall at nominal 1200mm centers

Construction wall

Concrete �oor

C-channel 50x50x50x0.6mm thick

Access panel not exceeding 610mmx610mm

Legend :

10

11

12

13

14

15

16

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

FIG. NO. 5:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

VERTICAL ENCLOSURE SYSTEM

Page 16

ACCESSPANEL

(OPTIONAL)

6

2

1

15

13

5

9

14

4

1216

10

Page 18: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 WINS H-Tec �re protection panel, 9mm thick

2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

3 Enclosure support, steel C-channel or L-angles

4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

5 Steel channel collar, 32x50x0.5mm thick at butt joints at nominal 1220mm centers

6 Steel cable tray

7 Steel angle minimum 25x25x0.6mm thick

8 M6 all steel expanding �xing at 500mm nominal centers

9 M4 Self-tapping screw at nominal 200mm centers

General E&M services. e.g. cable trunking and steel pipe etc.

Cantilever arm at maximum 1250mm centers

Steel angle minimum 50x50x0.9mm thick fasten the serviceduct to the wall at nominal 1200mm centers

Construction wall

Concrete �oor

C-channel 50x50x50x0.6mm thick

Access panel not exceeding 610mmx610mm

Steel stud channel 32x50x32x0.5mm thick

Legend :

10

11

12

13

14

15

16

17

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

4 hours �re rating, integrity in accordancewith BS EN 1364-2:1999, BS EN 1364-1:2015

FIG. NO. 6:ACCESS PANEL DETAIL

Page 17

ACCESSPANEL

OPTIONAL

1

15

9

163

4

2

close open

217

15

15

171

16

9

WINS ACCESS PANEL

A.P. 16

9

Page 19: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-tec �re protection panel, 9mm thick

2 Wins H-tec �re protection panel �llet, 100mm width, 9mm thick (inside or outside)

3 Enclosure support, steel c-channel or l-angles

4 steel hanger rod at nominal 1000mm centers sizes according to limiting stress, I.E. < 10 N/MM²

5 Steel channel collar, 32x50x0.5mm thick. Sizes may be larger to suit panel and mineral wood thickness

6 Steel cable tray

7 Mineral wool, 2 layers of 50mm thick with nominal density of 80 KG/M³

8 Access panel (optional)

9 M4 self-tapping screw at nominal 200mm centers

10 Steel angle minimum 25x25x0.6mm thick

Legend :

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

Page 18

1 hour Fire Rating, Integrity and Insulation in accordancewith BS EN 1364-2:1999, BS EN 1364-1:1999

close

open

ACCESS PANEL(OPTIONAL)

1

4

2

3

5

76

9

8

10

Fig1

FOUR-SIDED WINS 9MM THICK H-TEC FIRE PROTECTION PANELHORIZONTAL ENCLOSURE SYSTEM WITH ACCESS PANEL (OPTIONAL)

Page 20: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-tec �re protection panel, 9mm thick

2 Wins H-tec �re protection panel �llet, 100mm width, 9mm thick (inside or outside)

3 Steel channel collar, minimum 32x50x0.5mm thick at butt joints of nominal 1220mm centers

4 M4 self-tapping screw at nominal 200mm centers

5 Threaded rod hanger stress not exceed 10 N/MM², �xed to the wall

6 Steel angle, miniumum 50x50x0.9mm thick fasten the service duct to the wall at nominal 1220mm centers

7 General E&M services. E.G. Cable trunking and steel pipes, etc.

8 Mineral wool, 2 layers of 50mm thick with nominal density of 80 KG/M³

9 Construction wall

10 Concrete �oor

11 Steel angle minimum 25x25x0.6mm thick

12 Access panel (optional)

Legend :

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

Page 19

1 hour Fire Rating, Integrity and Insulation in accordancewith BS EN 1364-2:1999, BS EN 1364-1:1999

close

open

ACCESS PANEL(OPTIONAL)

78

2

1

5

4

6

9

3

10

4

512

11

Fig2

FOUR-SIDED WINS 9MM THICK H-TEC FIRE PROTECTION PANELVERTICAL ENCLOSURE SYSTEM WITH ACCESS PANEL (OPTIONAL)

Page 21: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-Tec �re protection panel, 9mm thick

2 Wins H-Tec �re protection panel �llet, 100mm width, 9mm thick (inside or outside)

3 M6 all steel expanding �xing at 500mm nominal centers

4 Steel channel collar, minimum 32x50x0.5mm thick at butt joints of nominal 1220mm centers

5 M4 self-tapping screw at nominal 200mm centers

6 Threaded rod hanger stress not exceed 10 N/MM², �xed to the wall

7 Steel angle minimum 25x25x0.6mm thick

8 General E&M services. E.G. Cable trunking and steel pipes, etc.

9 Mineral wool, 2 layers of 50mm thick with nominal density of 80 KG/M³

10 Cantilever arm at maximum 1250mm center

Legend :

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

Page 20

1 hour Fire Rating, Integrity and Insulation in accordancewith BS EN 1364-2:1999, BS EN 1364-1:1999

ACCESSPANEL

(OPTIONAL)

ACCESSPANEL

(OPTIONAL)

1

82

2 95473

8

1 9 52

7

36

54

6

4

6

7 7

ACCESSPANEL

(OPTIONAL)

ACCESSPANEL

(OPTIONAL)

3

1

295748

210

31 2 9

7

28

12527

6

Fig3

THREE-SIDED CONSTRUCTION FROM FLOOR SOFFITWITH ACCESS PANEL (OPTIONAL)

Fig3

THREE-SIDED CONSTRUCTION FROM SIDE WALLWITH ACCESS PANEL (OPTIONAL)

Page 22: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-Tec �re protection panel, 9mm thick

2 Wins H-Tec �re protection panel �llet, 100mm width, 9mm thick (inside or outside)

3 M6 all steel expanding �xing at 500mm nominal centers

4 Steel channel collar, minimum 32x50x0.5mm thick at butt joints of nominal 1220mm centers

5 M4 self-tapping screw at nominal 200mm centers

6 Threaded rod hanger stress not exceed 10 N/MM², �xed to the wall

7 Steel angle minimum 25x25x0.6mm thick

8 General E&M services. E.G. Cable trunking and steel pipes, etc.

9 Mineral wool, 2 layers of 50mm thick with nominal density of 80 KG/M³

Legend :

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

Page 21

1 hour Fire Rating, Integrity and Insulation in accordancewith BS EN 1364-2:1999, BS EN 1364-1:1999

ACCESS PANEL(OPTIONAL)

6

8

13 2 9

5247

7

Fig4

TWO-SIDED WINS 9MM THICK H-TEC FIRE PROTECTION PANELENCLOSURE SYSTEM WITH ACCESS PANEL (OPTIONAL)

Page 23: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-Tec �re protection panel, 9mm thick

2 Wins H-Tec �re protection panel �llet, 100mm width, 9mm thick (inside or outside)

3 M6 all steel expanding �xing at 500mm nominal centers

4 Steel channel collar, minimum 32x50x0.5mm thick at butt joints of nominal 1220mm centers

5 M4 self-tapping screw at nominal 200mm centers

6 Threaded rod hanger stress not exceed 10 N/MM², �xed to the wall

7 Steel angle minimum 25x25x0.6mm thick

8 General E&M services. E.G. Cable trunking and steel pipes, etc.

9 Mineral wool, 2 layers of 50mm thick with nominal density of 80 KG/M³

Legend :

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

Page 22

1 hour Fire Rating, Integrity and Insulation in accordancewith BS EN 1364-2:1999, BS EN 1364-1:1999

ACCESS PANEL(OPTIONAL)

684

3

5 12 9 7

Fig5

ONE-SIDED WINS 9MM THICK H-TEC FIRE PROTECTION PANELENCLOSURE SYSTEM WITH ACCESS PANEL (OPTIONAL)

Page 24: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-Tec �re protection panel, 9mm thick

2 Steel C-Channel at 610mm spacing 32x50x32x0.5mm thick

3 Furring channel / perimeter C-Channel 25x50x25x0.5mm thick

4 Steel wire hanger @1000mm c/c

5 Panel joints, all gaps sealed with intumescent sealant

6 Wins H-Tec �re protection panel �llet, 100mm width, 9mm thick

7 Self tapping screws at nominal 200mm centres

8 Rockwool-2 layers of 50mm thk (80KG/M³ )

9 Sti�ener galvanised steel C-Channel opening, 75x50x75x0.5mm thick

10 Access panel (optional, all panel surfaces)

Legend :

WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

Page 23

1 hour Fire Rating, Integrity and Insulation in accordancewith BS EN 1364-2:1999, BS EN 1364-1:1999

CLOSE

OPEN

9

6

10

3

3

1

6

7 1

8

WINS ACCESS PANELFig6

Page 25: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK PARTITION SYSTEM WITH ACCESS PANEL

4 hours �re rating, integrity in accordance with BS EN 1364-1:2015

Page 24

1 Wall

2 Wins H-Tec Fire Protection Panel, 9mm thick

3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

5 M4 Self-tapping screw, @200mm c/c

6 M6 steel anchor bolt, @610mm c/c

7 Board Joint, sealed with �re retardant sealant

8 Wins H-Tec Fire Protection Panel Fillet, 9mm thick, 100mm width

9 Access Panel (optional, any panel surface)

Steel stud channel 50x50x50x0.6mm thick

Legend :

10

closeopen

5

46

8

32

7

9

8

10

1

2

5

Access Port

3

Page 26: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK PARTITION SYSTEM

4 hours �re rating, integrity in accordance with BS EN 1364-1:2015

Page 25

1 Wall

2 Wins H-Tec Fire Protection Panel, 9mm thick

3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

5 M4 Self-tapping screw, @200mm c/c

6 M6 steel anchor bolt, @610mm c/c

7 Board Joint, sealed with �re retardant sealant

8 Wins H-Tec Fire Protection Panel Fillet, 9mm thick, 100mm width

Legend :

5

46

83

2

7

1

3

Page 27: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm THICK PARTITION SYSTEM

4 hours �re rating, integrity and insulation in accordance with BS EN 1364-1:2015

Page 26

1 Wall

2 Wins H-Tec Fire Protection Panel, 9mm thick

3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

5 M4 Self-tapping screw, @200mm c/c

6 M6 steel anchor bolt, @610mm c/c

7 Board Joint, sealed with �re retardant sealant

8 Wins H-Tec Fire Protection Panel Fillet, 9mm thick, 100mm width

9 Rock wool density 80kg/m3 by 50mm thick

Legend :

5

46

8

32

7

1

3

9

9

Page 28: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL12mm THICK PARTITION SYSTEM WITH ACCESS PANEL

4 hours �re rating, integrity in accordance with BS EN 1364-1:2015

Page 27

1 Wall

2 Wins H-Tec Fire Protection Panel, 12mm thick

3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

5 M4 Self-tapping screw, @200mm c/c

6 M6 steel anchor bolt, @610mm c/c

7 Board Joint, sealed with �re retardant sealant

8 Wins H-Tec Fire Protection Panel Fillet, 12mm thick, 100mm width

9 Access Panel (optional, any panel surface)

Steel stud channel 50x50x50x0.6mm thick

Legend :

10

closeopen

5

46

8

32

7

9

8

10

1

2

5

Access Port

3

Page 29: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL12mm THICK PARTITION SYSTEM

4 hours �re rating, integrity in accordance with BS EN 1364-1:2015

Page 28

1 Wall

2 Wins H-Tec Fire Protection Panel, 12mm thick

3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

5 M4 Self-tapping screw, @200mm c/c

6 M6 steel anchor bolt, @610mm c/c

7 Board Joint, sealed with �re retardant sealant

8 Wins H-Tec Fire Protection Panel Fillet, 12mm thick, 100mm width

Legend :

5

46

83

2

7

1

3

Page 30: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL12mm THICK PARTITION SYSTEM

1 hour �re rating, integrity and insulation in accordance with BS EN 1364-1:1999

Page 29

1 Wall

2 Wins H-Tec Fire Protection Panel 12mm thick

3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

5 M4 Self-tapping screw, @200mm c/c

6 M6 steel anchor bolt, @610mm c/c

7 Board Joint, sealed with �re retardant sealant

8 Access Panel (any panel surface)

9 Rock wool density 80kg/m³ by 50mm thick

10 Steel stud channel 75x50x75x0.8mm thick

Legend :

closeopen

5

46

32

7

1

3

9

9

8

10

2

5

Access Port

Page 31: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL12mm THICK PARTITION SYSTEM

4 hours �re rating, integrity and insulation in accordance with BS EN 1364-1:2015

Page 30

1 Wall

2 Wins H-Tec Fire Protection Panel, 12mm thick

3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

5 M4 Self-tapping screw, @200mm c/c

6 M6 steel anchor bolt, @610mm c/c

7 Board Joint, sealed with �re retardant sealant

8 Wins H-Tec Fire Protection Panel Fillet, 12mm thick, 100mm width

9 Rock wool density 80kg/m3 by 50mm thick

Legend :

5

46

8

32

7

1

3

9

9

Page 32: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-Tec �re protection panel 9mm thick

2 Steel C-Channel at 610mm spacing 32x50x32x0.5mm thick

3 Furring channel / perimeter C-Channel 25x50x25x0.5mm thick

4 Steel wire hanger @ 1000mm c/c

5 Board joints, all gaps sealed with intumescent sealant

6 9mm thick Wins H-Tec �re protection panel �llet, 100mm width

7 Self tapping screws at nominal 200mm centres

8 Rockwool-2 layers of 50mm thick (80KG/M³ )

9 Ceiling opening, sti�ener galvanised steel C-Channel 75x50x75x0.5mm thick

10 Access panel (optional, any board surface)

Legend :

H-TEC FIRE PROTECTION PANEL

Page 31

9mm THICK SUSPENDED CEILING SYSTEM WITH ACCESS PANEL1 hour Fire Rating, Integrity and Insulation in accordance with BS EN 1364-2:1999

1

7

56

2

2

84

3

10

ISOMETRIC VIEW60 min. CEILING SYSTEM

5

Page 33: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-Tec �re protection panel 9mm thick

2 Steel C-Channel at 610mm spacing 32x50x32x0.5mm thick

3 Furring channel / perimeter C-Channel 25x50x25x0.5mm thick

4 Steel wire hanger@1000mm c/c

5 Board joints, all gaps sealed with intumescent sealant

6 Wins H-Tec �re protection panel �llet 100mm width 9mm thick

7 Self tapping screws at nominal 200mm centres

8 Rockwool-2 layers of 50mm thk (80KG/M³ )

Legend :

H-TEC FIRE PROTECTION PANEL

Page 32

9mm THICK SUSPENDED CEILING SYSTEM WITH ACCESS PANEL1 hour Fire Rating, Integrity and Insulation in accordance with BS EN 1364-2:1999

6 7 1 6 2 5 47

3 3

8

HORIZONTAL SECTION60 min. CEILING SYSTEM

Page 34: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-Tec �re protection panel 9mm thick

2 Steel C-Channel at 610mm spacing 32x50x32x0.5mm thick

3 Furring channel / perimeter C-Channel 25x50x25x0.5mm thick

4 Steel wire hanger @ 1000mm c/c

5 Board joints -all gaps sealed by intumescent sealant

6 Wins H-Tec �re protection panel �llet 100mm width 9mm thick

7 Self tapping screws at nominal 200mm centres

8 Rockwool-2 layers of 50mm thk (80KG/M³ )

9 Ceiling opening, sti�ener galvanised steel C-Channel 75x50x75x0.5mm thick

10 Access panel (optional, any board surface)

Legend :

H-TEC FIRE PROTECTION PANEL

Page 33

9mm THICK SUSPENDED CEILING SYSTEM WITH ACCESS PANEL1 hour Fire Rating, Integrity and Insulation in accordance with BS EN 1364-2:1999

WINS ACCESS PANEL

CLOSE

OPEN

9

6 6

7

3

8

10

1

3

1

Page 35: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 wins H-Tec �re protection panel 9mm thick

2 steel C-channel at 610mm spacing 50 x 32 x 0.5mm thick

3 furring channel / perimeter channel 50 x 25 x 0.5mm thick

4 steel wire hanger @ 1000mm c/c

5 Board joints -all gaps sealed by intumescent sealant

6 Wins H-tec �re protection �llet 100mm width 9mm thick

7 Self tapping screws at nominal 200mm centres

8 Rockwool,2 layers of 50mm thick,density 80kg/m³

Legend :

H-TEC FIRE PROTECTION PANEL4 HOURS FIRE RESISTANCE CEILING SYSTEM

Page 34

9mm WINS H-Tec Fire Protection Panel4 hours �re resistance, integrity and insulation in accordance with BS EN 1364-2:1999

1

7

25

6

4

83

Page 36: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

1 Wins H-tec �re protection panel 12mm thick

2 Steel C-channel at 610mm spacing 50 x 32 x 0.5mm thick

3 Furring channel / perimeter channel 50 x 25 x 0.5mm thick

4 Steel wire hanger @ 1000mm c/c

5 Board joints -all gaps sealed by intumescent sealant

6 Wins h-tec �re protection �llet 100mm width 9mm thick

7 Self tapping screws at nominal 200mm centres

8 Rockwool,2 layers of 50mm thick, density 80kg/m³

Legend :

H-TEC FIRE PROTECTION PANEL4 HOURS FIRE RESISTANCE CEILING SYSTEM

Page 35

12mm WINS H-Tec Fire Protection Panel4 hours �re resistance, integrity and insulation in accordance with BS EN 1364-2:1999

1

7

25

6

4

83

Page 37: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

H-TEC FIRE PROTECTION PANEL4 HOURS FIRE RESISTANCE CEILING SYSTEM

Page 36

9mm WINS H-Tec Fire Protection Panel4 hours �re resistance, integrity in accordance with BS EN 1364-2:1999

1 Wins H-Tec Fire Protection Panel 9mm Thick

2 Steel C-channel At 610mm Spacing 50 X 32 X 0.5mm Thick

3 Furring Channel / Perimeter Channel 50 X 25 X 0.5mm Thick

4 Steel Wire Hanger @ 1000mm C/C

5 Board Joints -All Gaps Sealed By Intumescent Sealant

6 Wins H-Tec Fire Protection Fillet, 100mm Width 9mm Thick

7 Self Tapping Screws At Nominal 200mm Centres

1 Wins H-tec �re protection panel 9mm thick

2 Steel C-channel at 610mm spacing 50x32x0.5mm thick

3 Furring channel/perimeter c-channel 50x25x0.5mm thick

4 Steel wire hanger @1000mm c/c

5 Board joints – all gaps sealed by intumescent sealant

6 Wins h-tec �re protection �llet, 100mm width 9mm thick

7 Self tapping screws at nominal 200mm centres

4

6

3

7

21 5

1

7

25

6

4

3

Page 38: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

Page 37

1 Wins H-Tec Fire Protection Panel, 9mm thick

2 Wins H-Tec Fire Protection Fillets 100mm wide x 9mm thick

3 Top steel channel, 24mmx50mmx24mmx1mm thick

4 Horizontal steel stud, 32mmx50mmx32mmx0.5mm thick

5 Bottom steel channel, 24mmx50mmx24mmx0.5mm thick

6 M8 anchor bolt, @610mm c/c

7 M4x25mm self-tapping screw, @200mm c/c

8 Furnace wall

9 30mm free edge

Board Joints with �re retardant sealant

Vertical steel stud, 32mmx50mmx32mmx0.5mm thick, @610mm c/c

Legend :

10

11

7

Detail A

Detail B

Detail C

5

2

1

1

4

3

6

Detail A Detail B Detail C

WINS H-TEC FIRE PROTECTION PANEL9mm WINS H-TEC Smoke Barrier System

2 hours �re rating, integrity in accordance with BS 476: Part 22: 1987

Page 39: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

WINS H-TEC FIRE PROTECTION PANEL9mm WINS H-TEC Smoke Barrier System

2 hours �re rating, integrity in accordance with BS 476: Part 22: 1987

Page 38

1 Wins H-Tec Fire Protection Panel, 9mm thick

2 Wins H-Tec Fire Protection Fillets 100mm wide x 9mm thick

3 Top steel channel, 24mmx50mmx24mmx1mm thick

4 Horizontal steel stud, 32mmx50mmx32mmx0.5mm thick

5 Bottom steel channel, 24mmx50mmx24mmx0.5mm thick

6 M8 anchor bolt, @610mm c/c

7 M4x25mm self-tapping screw, @200mm c/c

8 Furnace wall

9 30mm free edge

Board Joints with �re retardant sealant

Vertical steel stud, 32mmx50mmx32mmx0.5mm thick, @610mm c/c

Legend :

10

11

5

4

3

10

7

1

2

11

2

1

2

Page 40: WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2019/07/E... · 2019-07-01 · wins h-tec fire protection panel 9mm thick enclosure system fig. no.3: two-sided

Website : www.winsconsultants.com