WING TON FAN INDUSTRY LIMITED
YS SERIES AXIAL FLOW FANS
CATA-AMCA-YS JANUARY ,2021
For YS240,315,355 For YS400,450,500,560,630,710,800,900,
1000,1250 and 1500
1
YS SERIES ADJUSTABLE PITCH AXIAL FLOW FANSWing Ton Fan Industry Limited certifies that the Axial Flow Fan – YS240, 315, 355, 400, 450, 500, 560, 630, 710, 800, 900, 1000, 1250 and1500 shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.The AMCA Certified Ratings Seal applies to FEG for Models YS400, 450, 500, 560, 630, 710, 800, 900, 1000, 1250 and 1500 only.
The AMCA Certified Ratings Seal applies to air performance and sound for Models YS240, 315, 355, 400, 450, 500, 560, 630, 710, 800, 900, 1000, 1250 and 1500 only.
The YS Series of axial flow fans is available in an extensive range of variants and air flow performance. They can be manufactured to handle most conditions from ambient air and can be ordered in 14 sizes (240, 315, 355, 400, 450, 500, 560, 630, 710, 800, 900, 1000, 1250 and1500mm) diameter. They are available in direct drive type.
Typical Applications Commercial and industrial supply or exhaust air applications such as shopping centers, office buildings and car parks, through to industrial processes and equipment ventilation.
GENERAL INFORMATION
The achieved fan performances can differ from the testperformances shown on the subsequent due to two maineffects:-
The encroachment of irregular or abrupt changes within thesystem close to the fan. If good design practice is followed,then the fan will receive nearly uniform air into its inletand discharge its air flow in an almost ideal pattern. If this is achieved the fan will perform to its expected level.
Changes to the internal elements of the fan: e.g. large junctionboxes on motors, belt drive stacks or excessive blade tipclearances.
Tests were conducted to assess these effects and thegeneralised impact is shown below for fan selections madewithin the normal operating region over a wideblade-angle range.
A.)
B.)
NormalOperationRange
1
Type AFree inlet
Free outletF
Type BFree inlet
Ducted outletF
Type CDucted inlet
Free outletF
Type DDucted inlet
Ducted outletF
Type of installation
The main difference between the belowStandards, is the installation Types A, B, Cand D such that, if a fan unit is designed
for use in any one of the arrangements, the variation in performance should beestablished and shown.
Massive Fan Industries Sdn. Bhd. certifies thatthe Axial Flow Fan-MSA series shown hereinare licensed to bear the AMCA Seal.The ratings shown are based on tests andprocedures performed in accordance withAMCA Publication 211 and AMCA Publication311 and comply with the requirements of theAMCA Certified Ratings Program.
3
A two stage fan will develop approximately two times the pressure of a single-stage fan of equal diameter and speed.
This is an economical system because the component stages are standard fansindependently driven by standard motors.
A two-stage contra-ratating fan comprises assembling in series two (or more single-stage) non-guide-vane fans with impellers rotating in opposite direction. The contra-rotation of the impellers recovers rotational losses and converts the rotational energy into fan pressure.
Multi-Stage Axial Flow Fan
There are two ways to design a two-stage axial-flow fan:
with two fan wheels rotating in the same rotation with two counter rotating fan wheels
Motor Motor Motor
Other Fan Arrangement
Some required duty pressure should beadjusted to account for the below gains / losses before making a selection on the standard performance curves.
Standard Accessory Losses
FanArrangement
Effect onpressurecapability
Effect onTotalsound level
Single stage fan unit withdownstream guide vanes
Two stage fan unit withintermediate straightener
Contra-rotating twostage fan unit
Bifurcated fan unit
x 1.25
x 2.00
x 2.4
x 0.7
+ 1dB
+ 3dB
+ 8 to 10dB
+ 2dB
k'loss
0.2 Form 'A'0.38 Form B
Low loss inlet cone
k'loss
Flat 'finger type' guard 0.75
k'loss
Coned motor sideguard 0.4
k'loss
Non return dampers(airstream) operated 0.3 ~ 0.4
* Performance for single stage fan unit with downstream guide vanes, two stage fan unit with intermediate straightener, contra-retating two stage fan unit and Bifurcated fan unit are not licensed by AMCA International.
* Performance for accessory losses are not licensed by AMCA International.
2
FEATURE
Form A Form AD Form AU
Form B Form BD Form BU
Performance for Form B airflow direction are not licensed by AMCA International
A. CASINGStandard casings are made of steelCoated by strong epoxy powder.Equipped with complete flange and mounting feet.Casings can be stainless steel or durable hot-dipped galvanized steel can be supplied at request.
B. IMPELLERMost of the impellers are adjustable pitch aero foil section. (except 250 and 300mm)Impeller material is made of die cast aluminum.With a specific impeller pitch angle, it ensures selections can be made accurately to the specification.
C. MOTORThe standard motors used are foot or pad mounted.For normal duty, the motors are of squirrel cage, induction motors to suit virtually any application.They are fitted with ball or roller bearings which are fully enclosed and sealed-for life and thereforedo not require maintenance.Motors are generally wound for 380V/3ph/50Hz or 220V/1ph/50Hz.Insulation to Class F with Class B temperature rise is used throughout, allowing for operation inambient up to +40°C.
D. DIRECTION OF AIRFLOWThe standard direction of air flow is Form B, BD and BU. However, Form A, AD and AU can be suppliedif required. Motors operating at BD, DU, AD and AU require up thrust bearing. Please inform us inadvance if the fans are installed vertically.
3
GENERAL INFORMATION
The achieved fan performances can differ from the testperformances shown on the subsequent due to two maineffects:-
The encroachment of irregular or abrupt changes within thesystem close to the fan. If good design practice is followed,then the fan will receive nearly uniform air into its inletand discharge its air flow in an almost ideal pattern. If this is achieved the fan will perform to its expected level.
Changes to the internal elements of the fan: e.g. large junctionboxes on motors, belt drive stacks or excessive blade tipclearances.
Tests were conducted to assess these effects and thegeneralised impact is shown below for fan selections madewithin the normal operating region over a wideblade-angle range.
A.)
B.)
NormalOperationRange
1
Type AFree inlet
Free outletF
Type BFree inlet
Ducted outletF
Type CDucted inlet
Free outletF
Type DDucted inlet
Ducted outletF
Type of installation
The main difference between the belowStandards, is the installation Types A, B, Cand D such that, if a fan unit is designed
for use in any one of the arrangements, the variation in performance should beestablished and shown.
Massive Fan Industries Sdn. Bhd. certifies thatthe Axial Flow Fan-MSA series shown hereinare licensed to bear the AMCA Seal.The ratings shown are based on tests andprocedures performed in accordance withAMCA Publication 211 and AMCA Publication311 and comply with the requirements of theAMCA Certified Ratings Program.
3
A two stage fan will develop approximately two times the pressure of a single-stage fan of equal diameter and speed.
This is an economical system because the component stages are standard fansindependently driven by standard motors.
A two-stage contra-ratating fan comprises assembling in series two (or more single-stage) non-guide-vane fans with impellers rotating in opposite direction. The contra-rotation of the impellers recovers rotational losses and converts the rotational energy into fan pressure.
Multi-Stage Axial Flow Fan
There are two ways to design a two-stage axial-flow fan:
with two fan wheels rotating in the same rotation with two counter rotating fan wheels
Motor Motor Motor
Other Fan Arrangement
Some required duty pressure should be adjusted to account for the below gains / losses before making a selection on the standard performance curves.
Standard Accessory Losses
FanArrangement
Effect onpressurecapability
Effect onTotalsound level
Single stage fan unit withdownstream guide vanes
Two stage fan unit withintermediate straightener
Contra-rotating twostage fan unit
Bifurcated fan unit
x 1.25
x 2.00
x 2.4
x 0.7
+ 1dB
+ 3dB
+ 8 to 10dB
+ 2dB
k'loss
0.2 Form 'A'0.38 Form B
Low loss inlet cone
k'loss
Flat 'finger type' guard 0.75
k'loss
Coned motor sideguard 0.4
k'loss
Non return dampers(airstream) operated 0.3 ~ 0.4
* Performance for single stage fan unit with downstreamguide vanes, two stage fan unit with intermediatestraightener, contra-retating two stage fan unit and
Bifurcated fan unit are not licensed by AMCA International.
* Performance for accessory losses are not licensed byAMCA International.
4
BELT DRIVEN TYPE AXIAL FLOW FANS (YP SERIES)
The YP Series of axial flow fans is available in an extensive range of variants and air flow performance.
In this instance the casing covers the entire length of the impeller and v-belt drive. Motor is mounted
outside the fan case.
They can be manufactured to handle most conditions from ambient air to hot, corrosive or explosive gases
and can be ordered in 14 sizes extending from 240 to 1500mm diameter.
These units of generally specified when it is important to keep the motor away from the airstream
generated due either to temperature or the nature of the gases being processed. An additional advantage is
that by correctly specifying the positioning of the motor ease of maintenance is assured.
Commercial and industrial supply or exhaust air applications such as shopping centers, office buildings and
car parks, through to industrial processes and equipment ventilation.
To overcome the duty pressure losses, additional 30% duty pressure should be adjusted to account for the
loss before making a selection on the standard performance curves. +2dB will be adjusted due to the effect
on total sound level.
Performance of AP Series Axial Flow Fans are not licensed by AMCA International.
YS SERIES AXIAL FLOW FAN
5
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
BIFURCATED TYPE AXIAL FLOW FANS (YB SERIES)Bifurcated fans are ideal for exhausting or recirculating fumes, gases and hot air up to 80 ° C (NT) or 200 ° C
(HT) continuous operation. They can be ordered in 11 sizes extending from 400 to 1500mm diameter.
Bifurcated axial fans are used in situations where it is important that the motor is kept out of the airstream
(though with suitable access to ambient air) due to the type or temperature of the gases/fumes involved.
Compared to direct drive axial types, bifurcated fans have the following advantages:
Higher temperature ratings / Isolation of motor from heat or contaminants in the airstream / Easier
maintenance.
To overcome the duty pressure losses, additional 30% duty pressure should be adjusted to account for the
loss before making a selection on the standard performance curves. +2dB will be adjusted due to the effect
on total sound level.
Performance of YB Series Axial Flow Fans are not licensed by AMCA International.
ρ=1.2kg/m3
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
0
20
40
60
80
100
120
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
2800 2P
1400 4P
Speed (rpm)
22⁰
Lw(A) at 2800rpm
0
5
10
15
20
25
30
87
87
87
86
1400 0.07
280022
0.37
0.036 -19
0.288 0YS240-88-7-22
YS240-88-7-220
Peak Absorbed Power(Kw)Motor(Kw)Blade Angle LwA dB(A)Model No Speed(RPM)
YS SERIES AXIAL FLOW FAN
6
8101214161820222426283032
0
0.37
0.2320.2550.2720.2920.3090.3360.3520.3890.4270.4640.5010.5430.584
0.55
0.75
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 2800 RPM
Model No
8101214161820222426283032
-29
0.18
0.0090.0100.0110.0120.0120.0140.0140.0160.0170.0190.0200.0220.024
YS315-H-6/0.18-6 YS315-H-6/0.18-4
YS315-H-6/0.37-2
YS315-H-6/0.55-2
YS315-H-6/0.75-2
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
8101214161820222426283032
-18
0.18
0.0290.0320.0340.0370.0390.0420.0440.0490.0530.0580.0630.0680.073
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
ρ=1.2kg/m3
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°960 0.009 0.010 0.011 0.012 0.012 0.014 0.014 0.016 0.017 0.019 0.020 0.022 0.024
motor1400 0.029 0.032 0.034 0.037 0.039 0.042 0.044 0.049 0.053 0.058 0.063 0.068 0.073motor2800 0.232 0.255 0.272 0.292 0.309 0.336 0.352 0.389 0.427 0.464 0.501 0.543 0.584motor 0.75
N (rpm) Blade Pitch Angle [°]
0.18
0.18
00.37 0.55
LwAdB
-29
-18
0
20
40
60
80
100
120
140
160
180
200
220
240
260
0 500 1000 1500 2000 2500 3000 3500 4000 4500
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200
0.00
0.02
0.04
0.06
0.08
2800 2P
1400 4P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 3299
103
98
99
Lw(A) at 2800rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
102101
99
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500960 6P
0
5
10
15
20
25
30
35
40
45
50
55
60
650.00
0.01
0.02
100
104
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
222018161412108
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
0
10
20
30
40
50
0
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 315-125-6
103
98101
101 103 101
100
102
9998
99
100
102 103
101102
102
YS SERIES AXIAL FLOW FAN
7
8101214161820222426283032
0
0.75
0.5760.6080.6160.6480.6350.6610.6560.7200.7970.8760.9551.0331.112
1.1
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 2800 RPM
Model No
8101214161820222426283032
-30
0.18
0.0230.0250.0250.0260.0260.0270.0260.0290.0320.0350.0380.0420.045
YS355-H-7/0.18-6 YS355-H-7/0.18-4
YS355-H-7/0.75-2
YS355-H-7/0.11-2
1.5YS355-H-7/1.5-2
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
8101214161820222426283032
-20
0.0720.0760.0770.0810.0790.0830.0820.0900.1000.1100.1190.1290.139
0.18
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
ρ=1.2kg/m3
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°960 0.023 0.025 0.025 0.026 0.026 0.027 0.026 0.029 0.032 0.035 0.038 0.042 0.045
motor1400 0.072 0.076 0.077 0.081 0.079 0.083 0.082 0.090 0.100 0.110 0.119 0.129 0.139motor2800 0.576 0.608 0.616 0.648 0.635 0.661 0.656 0.720 0.797 0.876 0.955 1.033 1.112motor 1.5
N (rpm) Blade Pitch Angle [°]
0.18
0.18
0
LwAdB
-30
-20
0.75 1.1
0
50
100
150
200
250
300
350
400
450
500
0 1000 2000 3000 4000 5000 6000 7000
0.0
0.2
0.4
0.6
0.8
1.0
1.2
0 1000 2000 3000 4000 5000 6000 7000
0 500 1000 1500 2000 2500 3000 3500
0.00
0.05
0.10
0.15
2800 2P
1400 4P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 3298
100
99
105
Lw(A) at 2800rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
98100
98
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400960 6P
0
10
20
30
40
50
60
70
80
90
100
110
120
0.00
0.01
0.02
0.03
0.04
98
97
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
222018161412108
0
5
10
15
20
25
30
35
40
45
50
55
0
10
20
30
40
50
0 1000 2000 3000 4000 5000 6000 7000
Tota
l Effi
cien
cy (%
)
8
1416
1820
1210
3230
2826
2422
YS 355-150-7
97
9998
98 97
106
97
99 99
106
107
9996
97
103 105
98
YS SERIES AXIAL FLOW FAN
8
8101214161820222426283032
0
0.750.5740.6510.6880.7600.7700.8330.9100.9651.0911.2181.3441.4701.596
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 2800 RPM
Model No
8101214161820222426283032
-28
0.18
0.0230.0260.0280.0310.0310.0340.0370.0390.0440.0490.0540.0590.064
YS400-H-7/0.18-6YS400-H-7/0.18-4
YS400-H-7/0.75-2
1.1YS400-H-7/1.1-2
1.5YS400-H-7/1.5-2
2.2YS400-H-7/2.2-2
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
8101214161820222426283032
-18
0.18
YS400-H-7/0.37-4 0.37
0.0720.0810.0860.0950.0960.1040.1140.1210.1360.1520.1680.1840.200
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
ρ=1.2kg/m3
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°960 0.023 0.026 0.028 0.031 0.031 0.034 0.037 0.039 0.044 0.049 0.054 0.059 0.064
motor1400 0.072 0.081 0.086 0.095 0.096 0.104 0.114 0.121 0.136 0.152 0.168 0.184 0.200motor2800 0.574 0.651 0.688 0.760 0.770 0.833 0.910 0.965 1.091 1.218 1.344 1.470 1.596motor 2.2
N (rpm) Blade Pitch Angle [°]
0.18
0
LwAdB(A)
-28
-18
0.75 1.1 1.5
0.18 0.37
0
50
100
150
200
250
300
350
400
450
500
550
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
0.0
0.3
0.6
0.9
1.2
1.5
1.8
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
0 500 1000 1500 2000 2500 3000 3500 4000 4500
0.00
0.05
0.10
0.15
0.20
2800 2P
1400 4P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 3299
98
99
99
Lw(A) at 2800rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
102
101
99
0 500 1000 1500 2000 2500 3000960 6P
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
105
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
222018161412108
0
5
10
15
20
25
30
35
40
45
50
55
60
0
10
20
30
40
50
60
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 400-125-7
101
99
100
101
101 100
100
101
9999
102
101101
102102
103
FEG50
99
104104
YS SERIES AXIAL FLOW FAN
9
8101214161820222426283032
0
1.0081.1641.2481.3921.4401.5761.6161.8932.1712.4482.7253.0033.280
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 2800 RPM
Model No
8101214161820222426283032
-28
0.18
0.0410.0470.0500.0560.0580.0640.0650.0760.0870.0990.1100.1210.132
YS450-H-7/0.18-6
YS450-H-7/0.18-4
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
8101214161820222426283032
-19
0.18
YS450-H-7/1.1-2 1.1
YS450-H-7/1.5-2 1.5
YS450-H-7/2.2-2 2.2
YS450-H-7/3-2 3
YS450-H-7/4-2 4
YS450-H-7/0.37-4 0.37
YS450-H-7/0.55-4 0.55
0.1260.1460.1560.1740.1800.1970.2020.2370.2710.3060.3410.3750.410
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
ρ=1.2kg/m3
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°960 0.041 0.047 0.050 0.056 0.058 0.064 0.065 0.076 0.087 0.099 0.110 0.121 0.132
motor1400 0.126 0.146 0.156 0.174 0.180 0.197 0.202 0.237 0.271 0.306 0.341 0.375 0.410motor2800 1.008 1.164 1.248 1.392 1.440 1.576 1.616 1.893 2.171 2.448 2.725 3.003 3.280motor 1.1 1.5 2.2 3 4
N (rpm) Blade Pitch Angle [°]
0.18
0
LwAdB
-29
-190.18 0.37 0.55
0
100
200
300
400
500
600
700
800
0 2000 4000 6000 8000 10000 12000 14000
0
1
2
3
4
0 2000 4000 6000 8000 10000 12000 14000
0 1000 2000 3000 4000 5000 6000 7000
0.0
0.1
0.2
0.3
0.4
0.5
2800 2P
1400 4P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 3298
100
97
105
Lw(A) at 2800rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
98100
95
0 500 1000 1500 2000 2500 3000 3500 4000 4500960 6P
0
20
40
60
80
100
120
140
160
180
2000.00
0.05
0.10
0.15
99
97
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
2220
18161412108
0
10
20
30
40
50
60
70
80
90
0
10
20
30
40
50
60
70
0 2000 4000 6000 8000 10000 12000 14000
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 450-150-7
97
9898
96 97
105
97
98
98105
105
99 96
99
102104
98
FEG60
YS SERIES AXIAL FLOW FAN
10
ρ=1.2kg/m3
8101214161820222426283032
0
2.2 1.8102.1012.3332.6042.8753.1453.4163.6004.0244.4484.8725.2965.720
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 2800 RPM
Model No
8101214161820222426283032
-25
0.18
0.0730.0850.0940.1050.1160.1270.1380.1450.1620.1790.1960.2130.231
YS500-H-7/0.18-6
YS500-H-7/0.37-4
0.37YS500-H-7/0.37-6
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
8101214161820222426283032
-16
0.2260.2630.2920.3260.3590.3930.4270.4500.5030.5560.6090.6620.715
0.37
YS500-H-7/0.55-4 0.55
YS500-H-7/0.75-4
YS500-H-7/2.2-2
3YS500-H-7/3-2
4YS500-H-7/4-2
5.5YS500-H-7/5.5-2
7.5YS500-H-7/7.5-2
0.75
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°960 0.073 0.085 0.094 0.105 0.116 0.127 0.138 0.145 0.162 0.179 0.196 0.213 0.231
motor1400 0.226 0.263 0.292 0.326 0.359 0.393 0.427 0.450 0.503 0.556 0.609 0.662 0.715motor2800 1.810 2.101 2.333 2.604 2.875 3.145 3.416 3.600 4.024 4.448 4.872 5.296 5.720motor 7.5
0.37
N (rpm) Blade Pitch Angle [°]
0
LwAdB(A)
-25
-160.37 0.55 0.75
2.2 3 4 5.5
0.18
0
100
200
300
400
500
600
700
800
900
1000
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000
0
2
4
6
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
0
0.2
0.4
0.6
2800 2P
1400 4P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 32
Lw(A) at 2800rpm
ρ = 1.2kg/m
Abso
rbed
Pow
er (k
W)
109
104
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500960 6P
0
20
40
60
80
100
120
140
160
180
200
220
240
0.00
0.05
0.10
0.15
0.20
107
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
222018161412108
0
10
20
30
40
50
60
70
80
90
100
110
0
10
20
30
40
50
60
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 500-150-7
102
104
103
104 104
107108
103103
105
105
FEG50
108108
103 102 104
106
104
102103 103 103
YS SERIES AXIAL FLOW FAN
11
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
8101214161820222426283032
0
2.8563.3323.6194.0364.1364.5364.9045.6416.3797.1247.9368.7489.560
3
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 2800 RPM
Model No
8101214161820222426283032
-28
0.18
0.1150.1340.1460.1630.1670.1830.1980.2270.2570.2870.3200.3530.385
YS560-H-9/0.18-6
0.37YS560-H-9/0.37-6
0.37YS560-H-9/0.37-4
0.55YS560-H-9/0.55-4
0.75YS560-H-9/0.75-4
1.1YS560-H-9/1.1-4
1.5YS560-H-9/1.5-4
YS560-H-9/3-2
4YS560-H-9/4-2
5.5YS560-H-9/5.5-2
7.5YS560-H-9/7.5-2
11YS560-H-9/11-20.55YS560-H-9/0.55-6
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
8101214161820222426283032
-17
0.3570.4170.4520.5050.5170.5670.6130.7050.7970.8910.9921.0941.195
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
ρ=1.2kg/m3
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°960 0.115 0.134 0.146 0.163 0.167 0.183 0.198 0.227 0.257 0.287 0.320 0.353 0.385
motor 0.551400 0.357 0.417 0.452 0.505 0.517 0.567 0.613 0.705 0.797 0.891 0.992 1.094 1.195motor 0.37 1.52800 2.856 3.332 3.619 4.036 4.136 4.536 4.904 5.641 6.379 7.124 7.936 8.748 9.560motor 3
0.18 0.37
0.55 0.75 1.1
4 5.5 7.5 11
N (rpm) Blade Pitch Angle [°]
0
LwAdB
-28
-17
0
200
400
600
800
1000
1200
0 4000 8000 12000 16000 20000 24000 28000
0
2
4
6
8
10
0 4000 8000 12000 16000 20000 24000 28000
0 2000 4000 6000 8000 10000 12000 14000
0.0
0.2
0.4
0.6
0.8
1.0
1.2
2800 2P
1400 4P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 32108
105
104
110
Lw(A) at 2800rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
105105
102
0 1000 2000 3000 4000 5000 6000 7000 8000 9000960 6P
0
20
40
60
80
100
120
140
160
180
200
220
240
260
280
3000.0
0.1
0.2
0.3
0.4
106
104
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
222018161412108
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
0
10
20
30
40
50
60
70
0 4000 8000 12000 16000 20000 24000 28000
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 560-200-9
104
106106
103 106
109
105
107 107
110
109
105 105
106
107 108
107
FEG60
YS SERIES AXIAL FLOW FAN
12
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
8101214161820222426283032
0
4.0324.9365.5576.3687.1797.9898.2009.90510.2911.4912.6913.8915.09
5.5
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 2800 RPM
Model No
8101214161820222426283032
-27
0.37
0.1630.1990.2240.2570.2890.3220.3300.3670.4150.4630.5110.5600.608
YS630-H-9/0.37-6
0.55YS630-H-9/0.55-6
0.75YS630-H-9/0.75-6 YS630-H-9/2.2-4
0.18YS630-H-9/0.18-6
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
8101214161820222426283032
-17
0.5040.6170.6950.7960.8970.9991.0251.1371.2871.4371.5861.7361.886
2.2
YS630-H-9/0.55-4 0.55
YS630-H-9/0.75-4 0.75
YS630-H-9/1.1-4 1.1
YS630-H-9/1.5-4
YS630-H-9/5.5-2
7.5YS630-H-9/7.5-2
11YS630-H-9/11-2
15YS630-H-9/15-2
18.5YS630-H-9/18.5-2
1.5
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
ρ=1.2kg/m3
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°960 0.163 0.199 0.224 0.257 0.289 0.322 0.330 0.367 0.415 0.463 0.511 0.560 0.608
motor 0.181400 0.504 0.617 0.695 0.796 0.897 0.999 1.025 1.137 1.287 1.437 1.586 1.736 1.886motor 0.552800 4.032 4.936 5.557 6.368 7.179 7.989 8.200 9.095 10.29 11.49 12.69 13.89 15.09motor 18.5
N (rpm)
2.2
Blade Pitch Angle [°]
1.1 1.5
0.37 0.55 0.75
05.5 7.5 11 15
LwAdB(A)
-27
-170.75
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
0 5000 10000 15000 20000 25000 30000 35000 40000
0
4
8
12
16
0 5000 10000 15000 20000 25000 30000 35000 40000
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000
0.0
0.5
1.0
1.5
2.0
2800 2P
1400 4P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 32
Lw(A) at 2800rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
110
103
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000960 6P
0
20
40
60
80
100
120
140
160
180
200
220
240
260
280
300
320
340
0.0
0.1
0.2
0.3
0.4
0.5
0.6
115
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
222018
161412108
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
0
20
40
60
80
0 5000 10000 15000 20000 25000 30000 35000 40000
FEG56
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 630-200-9
108
107
111111
112
108
104 105 109108104 105
108108 108
111
109109
111
114113
109 110
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°720 0.181 0.224 0.259 0.298 0.338 0.377 0.409 0.462 0.515 0.568 0.621 0.673 0.726
motor960 0.430 0.532 0.614 0.707 0.801 0.894 0.970 1.095 1.220 1.345 1.471 1.596 1.721
motor1400 1.334 1.650 1.905 2.194 2.483 2.773 3.007 3.396 3.784 4.173 4.562 4.950 5.339motor 1.5
N (rpm) Blade Pitch Angle [°]
0.55 0.75 1.1 1.5 2.2
0.37 0.55 0.75
05.52.2 3.0 4.0
LwAdB(A)
-16
-10
0
50
100
150
200
250
300
350
400
450
500
0 5000 10000 15000 20000 25000 30000 35000 40000
0
2
4
6
0 5000 10000 15000 20000 25000 30000 35000 40000
0 3000 6000 9000 12000 15000 18000 21000 24000 27000
0.0
0.3
0.6
0.9
1.2
1.5
1.8
1400 4P
960 6P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 3296
97
91
98
Lw(A) at 1400rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er(k
W)
101
97
92
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000720 8P
0
20
40
60
80
100
120
140
160
180
200
220
0.0
0.2
0.4
0.6
0.8
93
103
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
2220
18161412108
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0
20
40
60
80
0 5000 10000 15000 20000 25000 30000 35000 40000
FEG63
Tota
l Effi
cien
cy(%
)
8
1416
1820
1210
323028262422
YS SERIES AXIAL FLOW FAN
YS 800-250-9
9894
92 93 94 95
97 96 96 97
98
102
10099
101100
YS SERIES AXIAL FLOW FAN
13
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
8101214161820222426283032
0
1.1 0.9571.1341.2861.4511.5861.7621.9482.2942.6402.9873.3333.6794.025
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
8101214161820222426283032
-17
0.180.1300.1540.1750.1970.2160.2400.2650.3120.3590.4060.4530.5000.547
YS710-H-9/0.18-8
0.37YS710-H-9/0.37-8
YS710-H-9/0.37-6
0.55YS710-H-9/0.55-8
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 720 RPM
Model No
8101214161820222426283032
-10
0.37
YS710-H-9/0.55-6
YS710-H-9/1.1-4
1.5YS710-H-9/1.5-4
2.2YS710-H-9/2.2-4
3YS710-H-9/3-4
4YS710-H-9/4-4
5.5YS710-H-9/5.5-4
0.55
YS710-H-9/0.75-6 0.75
YS710-H-9/1.1-6 1.1
YS710-H-9/1.5-6 1.5
0.3090.3660.4150.4680.5110.5680.6280.7400.8510.9631.0751.1861.298
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
ρ=1.2kg/m3
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°720 0.130 0.154 0.175 0.197 0.216 0.240 0.265 0.312 0.359 0.406 0.453 0.500 0.547
motor960 0.309 0.366 0.415 0.468 0.511 0.568 0.628 0.740 0.851 0.963 1.075 1.186 1.298
motor1400 0.957 1.134 1.286 1.451 1.586 1.762 1.948 2.294 2.640 2.987 3.333 3.679 4.025motor 1.1 5.5
0.55
0.37 0.55 1.1 1.5
3
N (rpm) Blade Pitch Angle [°]
0.75
1.5 2.2 4
0.18 0.37
0
LwAdB
-17
-10
0
100
200
300
400
500
0 5000 10000 15000 20000 25000 30000
0
1
2
3
4
5
0 5000 10000 15000 20000 25000 30000
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000
0.0
0.5
1.0
1.5
1400 4P
960 6P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 3296
93
90
99
Lw(A) at 1400rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
9395
89
0 2000 4000 6000 8000 10000 12000 14000720 8P
0
20
40
60
80
100
120
140
160
180
200
220
0.0
0.2
0.4
0.6
95
91
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
222018161412108
0
10
20
30
40
50
60
70
80
90
100
110
120
130
01020304050607080
0 5000 10000 15000 20000 25000 30000
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 710-250-9
91
9594
90 93
98
93
96 96
9998
94 91
94
95 97
95
FEG63
YS SERIES AXIAL FLOW FAN
14
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
8101214161820222426283032
0
1.3341.6501.9052.1942.4832.7733.0073.3963.7844.1734.5624.9505.339
1.5
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
8101214161820222426283032
-16
0.37
0.1810.2240.2590.2980.3380.3770.4090.4620.5150.5680.6210.6730.726
YS800-H-9/0.37-8
0.55YS800-H-9/0.55-8
YS800-H-9/0.55-6
0.75YS800-H-9/0.75-8
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 720 RPM
Model No
8101214161820222426283032
-10
0.4300.5320.6140.7070.8010.8940.9701.0951.2201.3451.4711.5961.721
0.55
YS800-H-9/0.75-6 0.75
YS800-H-9/1.1-6 1.1
YS800-H-9/1.5-6
YS800-H-9/1.5-4
2.2YS800-H-9/2.2-4
3YS800-H-9/3-4
4YS800-H-9/4-4
5.5YS800-H-9/5.5-4
1.5
YS800-H-9/2.2-6 2.2
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
ρ=1.2kg/m3
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°720 0.181 0.224 0.259 0.298 0.338 0.377 0.409 0.462 0.515 0.568 0.621 0.673 0.726
motor960 0.430 0.532 0.614 0.707 0.801 0.894 0.970 1.095 1.220 1.345 1.471 1.596 1.721
motor1400 1.334 1.650 1.905 2.194 2.483 2.773 3.007 3.396 3.784 4.173 4.562 4.950 5.339motor 1.5
N (rpm) Blade Pitch Angle [°]
0.55 0.75 1.1 1.5 2.2
0.37 0.55 0.75
05.52.2 3.0 4.0
LwAdB(A)
-16
-10
0
50
100
150
200
250
300
350
400
450
500
0 5000 10000 15000 20000 25000 30000 35000 40000
0
2
4
6
0 5000 10000 15000 20000 25000 30000 35000 40000
0 3000 6000 9000 12000 15000 18000 21000 24000 27000
0.0
0.3
0.6
0.9
1.2
1.5
1.8
1400 4P
960 6P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 3296
97
91
98
Lw(A) at 1400rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
101
97
92
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000720 8P
0
20
40
60
80
100
120
140
160
180
200
220
0.0
0.2
0.4
0.6
0.8
93
103
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
2220
18161412108
0
10
20
30
40
50
60
70
80
90
100
110
120
130
0
20
40
60
80
0 5000 10000 15000 20000 25000 30000 35000 40000
FEG63
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS SERIES AXIAL FLOW FAN
YS 800-250-9
9894
92 93 94 95
97 96 96 97
98
102
10099
101100
YS SERIES AXIAL FLOW FAN
15
8101214161820222426283032
0
3.3163.8164.3164.8165.2185.7036.1017.1968.2919.38710.4811.5812.67
4
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
8101214161820222426283032
-16
0.55 0.4510.5190.5870.6550.7100.7760.8300.9791.1281.2771.4261.5751.724
YS900-H-10/0.55-8 YS900-H-10/1.1-6
0.75YS900-H-10/0.75-8
1.1YS900-H-10/1.1-8
1.5YS900-H-10/1.5-8
2.2YS900-H-10/2.2-8
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 720 RPM
Model No
8101214161820222426283032
-10
1.0691.2301.3921.5531.6821.8391.9672.3202.6733.0273.3803.7334.086
1.1
YS900-H-10/1.5-6 1.5
YS900-H-10/2.2-6 2.2
YS900-H-10/3-6
YS900-H-10/4-4
5.5YS900-H-10/5.5-4
7.5YS900-H-10/7.5-4
11YS900-H-10/11-4
15YS900-H-10/15-4
3
YS900-H-10/4-6 4
YS900-H-10/7.5-6 7.5
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
ρ=1.2kg/m3
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°720 0.451 0.519 0.587 0.655 0.710 0.776 0.830 0.979 1.128 1.277 1.426 1.575 1.724
motor960 1.069 1.230 1.392 1.553 1.682 1.839 1.967 2.320 2.673 3.027 3.380 3.733 4.086
motor 1.1 7.51400 3.316 3.816 4.316 4.816 5.218 5.703 6.101 7.196 8.291 9.387 10.48 11.58 12.67motor 4 5.5 7.5 11 15 0
LwAdB
-16
-10
N (rpm) Blade Pitch Angle [°]
0.55 0.75 1.1 1.5 2.2
1.5 2.2 3 4
0
100
200
300
400
500
600
700
800
0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000
0
3
6
9
12
15
0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000
0 5000 10000 15000 20000 25000 30000 35000 40000
0
1
2
3
4
1400 4P
960 6P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 32102
100
96
103
Lw(A) at 1400rpm
ρ = 1.2kg/m
Abso
rbed
Pow
er (k
W)
9999
97
0 5000 10000 15000 20000 25000 30000720 8P
0
50
100
150
200
250
300
350
0.0
0.5
1.0
1.5
2.0
102
100
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
222018161412108
0
20
40
60
80
100
120
140
160
180
200
01020304050607080
0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 900-300-10
99
103102
98 101
104
101
103
103
103
105
99 99
101
102 104
102
FEG60
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°720 2.444 2.845 3.246 3.646 3.792 4.218 4.647 5.305 5.962 6.620 7.277 7.935 8.593
motor960 5.793 6.743 7.693 8.643 8.989 9.999 11.02 12.57 14.13 15.69 17.25 18.81 20.37
motor1400 17.97 20.91 23.86 26.81 27.88 31.01 34.16 39.00 43.83 48.67 53.50 58.34 63.17motor 18.5 22
11
55 75
11 15 18.5
30 37 45
N (rpm) Blade Pitch Angle [°]
0
LwAdB
-16
-97.5 22
3 4 5.5 7.5
0
200
400
600
800
1000
1200
1400
0 20000 40000 60000 80000 100000 120000 140000 160000
0
20
40
60
0 20000 40000 60000 80000 100000 120000 140000 160000
0 10000 20000 30000 40000 50000 60000 70000 80000 90000 100000
0
5
10
15
20
1400 4P
960 6P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 32114
111
107
116
Lw(A) at 1400rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er(k
W)
111
111
108
0 10000 20000 30000 40000 50000 60000 70000 80000720 8P
0
100
200
300
400
500
600
0
2
4
6
8
113
111
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
2220
18161412108
0
50
100
150
200
250
300
350
01020304050607080
0 20000 40000 60000 80000 100000 120000 140000 160000
Tota
l Effi
cien
cy(%
)
8
1416
1820
1210
323028262422
YS SERIES AXIAL FLOW FAN
YS 1250-420-12
110
113113
109 112
115
112
114 114
116114
111111
113
112113
113
FEG60
YS SERIES AXIAL FLOW FAN
16
8101214161820222426283032
0
5.5 5.4646.4027.2128.0878.9619.83510.5812.1913.8015.5417.2719.0020.73
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
8101214161820222426283032
-17
0.75 0.7430.8710.9811.1001.2191.3381.4401.6581.8782.1132.3492.5842.820
YS1000-H-10/0.75-8
1.1YS1000-H-10/1.1-8
1.5YS1000-H-10/1.5-8
2.2YS1000-H-10/2.2-8
2.2YS1000-H-10/2.2-6 YS1000-H-10/5.5-4
7.5YS1000-H-10/7.5-4
11YS1000-H-10/11-4
15YS1000-H-10/15-4
18.5YS1000-H-10/18.5-4
22YS1000-H-10/22-4
3YS1000-H-10/3-6
4YS1000-H-10/4-6
5.5YS1000-H-10/5.5-6
7.5YS1000-H-10/7.5-63YS1000-H-10/3-8
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 720 RPM
Model No
8101214161820222426283032
-10
1.7622.0642.3252.6072.8893.1713.4133.9294.4515.0095.5686.1266.684
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
ρ=1.2kg/m3
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°720 0.743 0.871 0.981 1.100 1.219 1.338 1.440 1.658 1.878 2.113 2.349 2.584 2.820
motor 0.75960 1.762 2.064 2.325 2.607 2.889 3.171 3.413 3.929 4.451 5.009 5.568 6.126 6.684
motor1400 5.464 6.402 7.212 8.087 8.961 9.835 10.58 12.19 13.80 15.54 17.27 19.00 20.73motor 5.5
2.2 3 4 5.5 7.5
0
N (rpm)
3
Blade Pitch Angle [°]
1.1 1.5 2.2
7.5 11 15.0 18.5 22
LwAdB(A)
-17
-10
0
100
200
300
400
500
600
700
800
900
0 10000 20000 30000 40000 50000 60000 70000 80000
0
5
10
15
20
0 10000 20000 30000 40000 50000 60000 70000 80000
0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000
0
2
4
6
1400 4P
960 6P
Air Volume (m3/h)
Stat
ic P
ress
ure
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 32
Lw(A) at 1400rpm
ρ = 1.2kg/m
Abso
rbed
Pow
er (k
W)
106
106
0 5000 10000 15000 20000 25000 30000 35000 40000720 8P
0
50
100
150
200
250
300
350
400
0.0
0.5
1.0
1.5
2.0
2.5
3.0
106
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA s ound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
2220
18161412108
0
20
40
60
80
100
120
140
160
180
200
220
0
20
40
60
80
0 10000 20000 30000 40000 50000 60000 70000 80000
FEG63
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS 1000-300-10
102
107
104
103
108
103
107
107
104 104 105 106
106
107
106106
107
107108
105105
106106
YS SERIES AXIAL FLOW FAN
17
8101214161820222426283032
0
17.9720.9123.8626.8127.8831.0134.1639.0043.8348.6753.5058.3463.17
18.5
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 1400 RPM
Model No
8101214161820222426283032
-16
32.4442.8453.2463.6463.7924.2184.6475.3055.9626.6207.2777.9358.593
YS1250-H-12/3-8
4YS1250-H-12/4-8
YS1250-H-12/7.5-6
5.5YS1250-H-12/5.5-8
7.5YS1250-H-12/7.5-8
11YS1250-H-12/11-8
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 720 RPM
Model No
8101214161820222426283032
-9
7.5
YS1250-H-12/11-6 11
YS1250-H-12/15-6 15
YS1250-H-12/18.5-6
YS1250-H-12/18.5-422YS1250-H-12/22-4
30YS1250-H-12/30-4
37YS1250-H-12/37-4
45YS1250-H-12/45-4
55YS1250-H-12/55-4
75YS1250-H-12/75-4
18.5
YS1250-H-12/22-6 22
5.7936.7437.6938.6438.9899.99911.0212.5714.1315.6917.2518.8120.37
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
ρ=1.2kg/m3
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted
inlet, ducted outlet. Ratings include the effects of duct end correction.
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°720 2.444 2.845 3.246 3.646 3.792 4.218 4.647 5.305 5.962 6.620 7.277 7.935 8.593
motor960 5.793 6.743 7.693 8.643 8.989 9.999 11.02 12.57 14.13 15.69 17.25 18.81 20.37
motor1400 17.97 20.91 23.86 26.81 27.88 31.01 34.16 39.00 43.83 48.67 53.50 58.34 63.17motor 18.5 22
11
55 75
11 15 18.5
30 37 45
N (rpm) Blade Pitch Angle [°]
0
LwAdB
-16
-97.5 22
3 4 5.5 7.5
0
200
400
600
800
1000
1200
1400
0 20000 40000 60000 80000 100000 120000 140000 160000
0
20
40
60
0 20000 40000 60000 80000 100000 120000 140000 160000
0 10000 20000 30000 40000 50000 60000 70000 80000 90000 100000
0
5
10
15
20
1400 4P
960 6P
Air Volume (m3/h)
Stat
ic P
ress
ure
(Pa)
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 32114
111
107
116
Lw(A) at 1400rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
111
111
108
0 10000 20000 30000 40000 50000 60000 70000 80000720 8P
0
100
200
300
400
500
600
0
2
4
6
8
113
111
* Performance certified is for installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for inlet LwiA sound power levels for installation type D: ducted inlet,
ducted outlet. Ratings include the effects of duct end correction.
3028
2624
2220
18161412108
0
50
100
150
200
250
300
350
01020304050607080
0 20000 40000 60000 80000 100000 120000 140000 160000
Tota
l Effi
cien
cy (%
) 8
1416
1820
1210
323028262422
YS SERIES AXIAL FLOW FAN
YS 1250-420-12
110
113113
109 112
115
112
114 114
116114
111111
113
112113
113
FEG60
YS SERIES AXIAL FLOW FAN
18
ρ=1.2kg/m3
8101214161820222426283032
0
13.6916.2918.0020.3222.6424.9525.8429.1332.4136.1640.0043.8347.67
15
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 960 RPM
Model No
8101214161820222426283032
-12
43.0183.5923.9704.4814.9925.5035.6996.4237.1477.9748.8209.66610.51
YS1500-H-12/4-10
5.5YS1500-H-12/5.5-10
7.5YS1500-H-12/7.5-10
YS1500-H-12/7.5-8
11YS1500-H-12/11-10
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 580 RPM
Model No
8101214161820222426283032
-7
5.7746.8717.5948.5729.54910.5310.9012.2913.6715.2616.8718.4920.11
7.5
YS1500-H-12/11-8 11
YS1500-H-12/15-8
YS1500-H-12/15-6
18.5YS1500-H-12/18.5-6
22YS1500-H-12/22-6
30YS1500-H-12/30-6
37YS1500-H-12/37-6
45YS1500-H-12/45-655YS1500-H-12/55-6
15
YS1500-H-12/18.5-8 18.5
YS1500-H-12/22-8 22
Peak Absorbed
Power(Kw)
Motor(Kw)
BladeAngle
LwAdB(A)
At 720 RPM
Model No
Peak Absorbed Power (kW)
8° 10° 12° 14° 16° 18° 20° 22° 24° 26° 28° 30° 32°580 3.018 3.592 3.970 4.481 4.992 5.503 5.699 6.423 7.147 7.974 8.820 9.666 10.51
motor720 5.774 6.871 7.594 8.572 9.549 10.53 10.90 12.29 13.67 15.26 16.87 18.49 20.11
motor 22960 13.69 16.29 18.00 20.32 22.64 24.95 25.84 29.13 32.41 36.16 40.00 43.83 47.67
motor 15 22 45 55
N (rpm) Blade Pitch Angle [°]
18.5 30 37 0
LwAdB(A)
-12
-7
4 5.5 7.5 11
7.5 11 15 18.5
0
100
200
300
400
500
600
700
800
900
0 20000 40000 60000 80000 100000 120000 140000 160000 180000
0
10
20
30
40
50
0 20000 40000 60000 80000 100000 120000 140000 160000 180000
0 20000 40000 60000 80000 100000 120000
0
5
10
15
20
960 6P
720 8P
Air Volume (m3/h)
Stat
ic P
ress
ure
Speed
32
8 10 12 14 16 18 20 22 24 26 28 30 32
Lw(A) at 960rpm
ρ = 1.2kg/m3
Abso
rbed
Pow
er (k
W)
109
109
0 10000 20000 30000 40000 50000 60000 70000 80000 90000 100000580 10P
0
50
100
150
200
250
300
350
400
450
500
0
2
4
6
8
10
110
* Performance certified is for installation type A - Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).* The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for outlet LwoA sound power levels for installation type A: free inlet,
free outlet.
3028
2624
222018
16141210
8
0
20
40
60
80
100
120
140
160
180
200
220
240
260
280
300
320
0
20
40
60
80
0 20000 40000 60000 80000 100000 120000 140000 160000 180000
FEG56
Tota
l Effi
cien
cy (%
) 8
14 1618
20
1210
323028262422
YS 1500-420-12
108
111
108
105
111
106 107 108 108 109
110
111
110110
112112
113
110109
110109
* Performance certified is for installation type A - Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). * The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for outlet LwoA sound power levels for installation type A: free inlet,
free outlet.
19
Dimensions (mm)
Model
YS315 312 355 408 260 408 210305 237 290Y63~Y80
φD
6-φ10 4-φ10
YS240 240 280 305 205 325 172245 180 237Y63~Y806-φ10 4-φ10
YS355 359 405 453 305 444 225355 271 335Y63~Y808-φ12 4-φ13
YS400 401 448 499 350 492 250400 306 370Y63~Y908-φ12 4-φ13
YS450 450 497 549 400 547 280450 306/366 370/430Y63~Y90/Y100~Y1128-φ12 4-φ13
YS500 504 551 599 440 607 315500 384/434 450/500Y63~Y112/Y1328-φ12 4-φ13
YS560 565 629 679 500 677 345560 376/426/576 450/500/650Y63~Y112/Y132/Y16012-φ14 4-φ13
YS630 634 698 749 570 767 400630 365/415/565/615 450/500/650/700Y63~Y100/Y132/Y160M/Y160L12-φ14 4-φ13
YS710 711 775 829 650 857 450710 364/414 450/500Y80~Y112/Y13212-φ14 4-φ16
YS800 797 861 919 730 954 502800 364/414 450/500Y80~Y112/Y13214-φ14 4-φ16
YS900 894 958 1019 800 1082 580900 342/392/592 450/500/700Y80~Y112/Y132/Y16014-φ14 4-φ20
YS1000 1003 1067 1120 800 1183 6301000 352/432/602/702 450/500/700/800Y80~Y112/Y132/Y160/Y18014-φ14 6-φ20
YS1250 1250 1314 1380 1050 1432 7501250 580/730/930 700/850/1050Y32~Y160/Y180~/Y225/Y250~Y28016-φ14 6-φ20
YS1500 1510 1580 1655 1300 1715 8951500 580/730/930 700/850/1050Y160/Y180~/Y225/Y250~Y28016-φ14 6-φ20
φD1 L L1 L2 W1 H n1-p1 n2-p2 W
WH1 Frame No
Address: 1B KAM SHING IND BLDG,1-11 KWAI WING RD.KOWLOON,HONG KONG.
Tel:(852)2410 9038 Fax:(852)2487 7317
E-mail:[email protected] http: //www.wington.com
WING TON FAN INDUSTRY LIMITED