WideBand Voltage Sensors for the Modern Substation Presented By: Theo Laughner, PE Acknowledgements: Erik Sperling, Bob Elliott

WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

WideBand Voltage Sensors for the Modern Substation

Presented By: Theo Laughner, PEAcknowledgements: Erik Sperling, Bob Elliott

Page 2: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Overview• Introduction• Impacts To The High Voltage Equipment In A Network• Types Of Instrument Transformers For Voltage

Measurement• Theoretical Aspects of RC-Dividers• Frequency Response Behavior Of RC-Dividers• Conclusions

Page 3: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

IntroductionGeneration Consumer / Industrial

Page 4: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Harmonic Emissions – Per IEEE 519 Limits

Page 5: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Other Emission Sources

Page 6: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Content

Page 7: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Impacts To The High Voltage Equipment In A Network

• Increasing of power losses within the network• Increasing electric stresses within the HV insulation system (permanently

as well as transient)• Thermal stresses within the connected equipment due to harmonic

currents• Increasing sound noise emission (transformers, coils, capacitors, etc.)• Saturation effects (measuring and power transformers) • Incorrect control of equipment• Faulty activation of protection equipment (old protection system)• Forced aging of high voltage equipment

Page 8: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Types Of Instrument Transformers For Voltage Measurement

• Potential Transformer (PT)– Magnetically Coupled– Most Frequently Used

• Capacitive Coupled Voltage Transformer (CCVT)– As the name suggests capacitive coupling– Mature technology, but less frequently used

• Optically Coupled Voltage Transformer– Uses Faraday effect.– In Development.

Page 9: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Response – Magnitude Accuracy

Legend36kV-VT(light green)72.5kV-VT(dark green) 123kV-VT(blue)245kV-VT(purple)420kV-CTVT(red)420kV-RC-divider (yellow)

Page 10: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Response – Phase Shift Error

Legend36kV-VT(light green)72.5kV-VT(dark green) 123kV-VT(blue)245kV-VT(purple)420kV-CTVT(red)420kV-RC-divider (yellow)

Page 11: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Theoretical Aspects Of RC-Dividers

V1: Primary voltageV2: Secondary voltageC1: Primary capacitanceR1: Primary resistanceC2: Secondary capacitanceR2: Secondary resistanceiC: Capacitive currentiR: Resistive current

Page 12: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Theoretical Aspects Of RC-Dividers

𝑍𝑍1 =𝑅𝑅1

1 + j𝜔𝜔𝐶𝐶1𝑅𝑅1

𝑍𝑍2 =𝑅𝑅2

1 + j𝜔𝜔𝐶𝐶2𝑅𝑅2

𝑍𝑍total =𝑅𝑅1

1 + j𝜔𝜔𝐶𝐶1𝑅𝑅1+

𝑅𝑅21 + j𝜔𝜔𝐶𝐶2𝑅𝑅2

Page 13: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Theoretical Aspects Of RC-Dividers𝑘𝑘C j𝜔𝜔 =

𝐶𝐶1

𝐶𝐶1 + 𝐶𝐶2 �1 + ⁄1 j𝜔𝜔𝐶𝐶2𝑅𝑅21 + ⁄1 j𝜔𝜔𝐶𝐶1𝑅𝑅1

𝑘𝑘R j𝜔𝜔 =𝑅𝑅2

𝑅𝑅2 + 𝑅𝑅1 �1 + j𝜔𝜔𝐶𝐶2𝑅𝑅21 + j𝜔𝜔𝐶𝐶1𝑅𝑅1

𝑍𝑍2𝑍𝑍total

=𝐶𝐶1

𝐶𝐶1 + 𝐶𝐶2

𝑓𝑓 → ∞ 𝑓𝑓 → 0𝑍𝑍2𝑍𝑍total

=𝑅𝑅2

𝑅𝑅2 + 𝑅𝑅1

Page 14: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Theoretical Aspects Of RC-Dividers𝜏𝜏1 = 𝜏𝜏2 → 𝑅𝑅1 � 𝐶𝐶1 = 𝑅𝑅2 � 𝐶𝐶2

1. τ1 > τ2 , undercompensated2. τ1 = τ2 , compensated3. τ1 < τ2 , overcompensated

In case 2, the secondary voltage follows the primary voltage with a fixed time delay:

𝑇𝑇a = 2.2 � 𝜏𝜏1 = 2.2 � 𝜏𝜏2

Page 15: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Response Behavior Of RC-dividers

• For a variety of reasons, it is not possible to perfectly match the primary and secondary components, therefore:– 𝜏𝜏1 ≠ 𝜏𝜏2 → 𝑅𝑅1 � 𝐶𝐶1 ≠ 𝑅𝑅2 � 𝐶𝐶2

• Frequency-dependent error formulas may be derived.

Page 16: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Response Behavior Of RC-dividers

LegendType: AIS RC-dividerVoltage accuracy – blue Phase displacement –green

Page 17: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Response Behavior Of RC-dividers

LegendType: GIS RC-dividerVoltage accuracy – blue Phase displacement –green

Page 18: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Response Behavior Of RC-dividers

LegendVoltage accuracy – blue Phase displacement – green

IEC Accuracy Class 0.2 Voltage – RedPhase displacement –Purple

Page 19: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Response Behavior Of RC-dividers

LegendType: GIS RC-dividerInput Signal: ImpulseReference – Blue Measured – Red

Page 20: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Frequency Response Behavior Of RC-dividers

LegendType: AIS RC-dividerInput Signal: Step ResponseReference – Blue Measured – Red

Page 21: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Comparisons Between RCVD and CVT

Page 22: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

Conclusions• The grid is becoming a “more noisy” place. • Traditional measurement transformers may lack the bandwidth to

accurately observe phenomenon on the grid.• There are new types of measurement transformers which provide

adequate frequency response with low measurement error.

• Final thought – present standards may not have accuracy classes which cover all of the necessary functions in the modern grid: revenue metering, protection, power quality measurement, etc.

Page 23: WideBand Voltage Sensors For the Modern Substation · Voltage Measurement • Potential Transformer (PT) – Magnetically Coupled – Most Frequently Used • Capacitive Coupled Voltage

tsdos.org

QUESTIONS?