103
Public Input No. 53-NFPA 1801-2015 [ Section No. 1.3.5 ] 1.3.5 This standard shall not apply to criteria for the use of thermal imagers by the fire service , the requirements for which are specified in NFPA 1408, Standard for Training Fire Service Personnel in the Operation, Care, Use, and Maintenance of Thermal Imagers . Statement of Problem and Substantiation for Public Input Clarifies application. Refer to NFPA 1982 section 1.3.3 Submitter Information Verification Submitter Full Name: JOHN MORRIS Organization: ISG INFRASYS Street Address: City: State: Zip: Submittal Date: Wed Jul 01 16:30:50 EDT 2015 Committee Statement Resolution: The Technical Committee stated that NFPA 1408 is not a use document, but a training document. National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 96 9/25/2015 3:03 PM

which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 53-NFPA 1801-2015 [ Section No. 1.3.5 ]

1.3.5

This standard shall not apply to criteria for the use of thermal imagers by the fire service, the requirements forwhich are specified in NFPA 1408, Standard for Training Fire Service Personnel in the Operation, Care, Use, andMaintenance of Thermal Imagers .

Statement of Problem and Substantiation for Public Input

Clarifies application. Refer to NFPA 1982 section 1.3.3

Submitter Information Verification

Submitter Full Name: JOHN MORRIS

Organization: ISG INFRASYS

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 16:30:50 EDT 2015

Committee Statement

Resolution: The Technical Committee stated that NFPA 1408 is not a use document, but a training document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 96 9/25/2015 3:03 PM

Page 2: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 3-NFPA 1801-2014 [ Chapter 2 ]

Chapter 2 Referenced Publications

2.1 General.

The documents or portions thereof listed in this chapter are referenced within this standard and shall beconsidered part of the requirements of this document.

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 1971, Standard on Protective Ensembles for Structural Fire Fighting and Proximity Fire Fighting, 2013edition .

2.3 Other Publications.

2.3.1 ANSI ISA Publications.

American National Standards Institute, Inc., 25 West 43d Street, 4th Floor, New York, NY 10036.

ANSI/ The International Society of Automation , 67 T.W Alexander Drive , P.O Box 12277 , ResearchTriangle Park, NC 27709 .

ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1and 2 Hazardous (Classified) Locations, 2007 2013 .

2.3.2 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM B 117, Standard Practice for Operating Salt Spray (Fog) Apparatus, 2011.

ASTM D 1003, Standard Test Method for Haze and Luminous Transmittance of Transparent Plastics, 20002013 .

2.3.3 ISO/IEC Publications.

International Standards Organization, 1 rue de Varembé, Case Postale 56, CH-1211 Genéve 20, Switzerland.

IEC 60529, Degrees of protection provided by enclosures (IP Code) Ed.2. 2, 2013/Cor 1 b : 2001 2013 .

IEC 61000-6-2, Electromagnetic compatibility (EMC) — Part 6-2: Generic standards — Immunity for industrialenvironments, 2005.

IEC 61000-6-3, Electromagnetic compatibility (EMC) — Part 6-3: Generic standards — Emission standard forresidential, commercial, and light-industrial environments, 2007 2011 .

ISO 27, Guidelines for corrective action to be taken by a certification body in the event of misuse of its mark ofconformity, 1983.

ISO 65, General requirements for bodies operating product certification systems, 1998, (Superseded by ISO/IEC17065) .

ISO DIS 9001, Quality management systems — Requirements, 2008 2014 .

ISO 17011, Conformity assessment — General requirements for accreditation bodies accrediting conformityassessment bodies, 2004.

ISO 17025, General requirements for the competence of testing and calibration laboratories, 2005/Cor 1: 2006.

ISO 17493, Clothing and equipment for protection against heat — Test method for convective heat resistanceusing a hot air circulating oven, 2000.

ISO/IEC 17021, Conformity assessment — Requirements for bodies providing audit and certification ofmanagement systems, 2006 2011 .

ISO/IEC 17065, Conformity Assessment - Requirements for Bodies Certifiying Products, Processes, andServices, 2012.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 96 9/25/2015 3:03 PM

Page 3: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

2.3.4 NIST Publications.

National Institute of Standards and Technology, 100 Bureau Drive, Stop 1070, Gaithersburg, MD 20899-1070.

NIST Technical Note 1630, Evaluation of Image Quality of Thermal Imagers Used by the Fire Service, February2009.

2.3.5 Other Publications.

Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

2.4 References for Extracts in Mandatory Sections. (Reserved)

Statement of Problem and Substantiation for Public Input

Referenced current editions.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 4-NFPA 1801-2014 [Chapter B]

Submitter Information Verification

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 27 22:07:28 EDT 2014

Committee Statement

Resolution: FR-9-NFPA 1801-2015

Statement: The changes introduced by this First Revision update the referenced documents.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 96 9/25/2015 3:03 PM

Page 4: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 12-NFPA 1801-2014 [ Section No. 2.3.1 ]

2.3.1 ANSI Publications.

American National Standards Institute, Inc., 25 West 43d Street, 4th Floor, New York, NY 10036.

ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III,Divisions 1 and 2 Hazardous (Classified) Locations, 2007 2013 .

Statement of Problem and Substantiation for Public Input

Updates publication reference to latest edition of ISA 12.12.01. Changes between the 2007 and 2013 editions do not impact existing certifications.

Submitter Information Verification

Submitter Full Name: PAUL KELLY

Organization: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Thu Nov 20 16:43:24 EST 2014

Committee Statement

Resolution: See FR 1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 96 9/25/2015 3:03 PM

Page 5: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 44-NFPA 1801-2015 [ Section No. 2.3.1 ]

2.3.1 ANSI Publications.

American National Standards Institute, Inc., 25 West 43d Street, 4th Floor, New York, NY 10036.

ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III,Divisions 1 and 2 Hazardous (Classified) Locations, 2007 2013 .

Statement of Problem and Substantiation for Public Input

The latest edition of ANSI/ISA 12.12.01 is dated 2013. The differences between the 2013 edition and the 2007 edition only involve increased certification options, and not any increases in severity of requirements.

Submitter Information Verification

Submitter Full Name: PAUL KELLY

Organization: UNDERWRITERS LABORATORIES INC

Affilliation: UNDERWRITERS LABORATORIES INC

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 05 08:30:48 EDT 2015

Committee Statement

Resolution: See FR 1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 96 9/25/2015 3:03 PM

Page 6: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 54-NFPA 1801-2015 [ Section No. 2.3.1 ]

2.3.1 ANSI Publications.

American National Standards Institute, Inc., 25 West 43d Street, 4th Floor, New York, NY 10036.

ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III,Divisions 1 and 2 Hazardous (Classified) Locations, 2007 2013 .

Statement of Problem and Substantiation for Public Input

updated

Submitter Information Verification

Submitter Full Name: JOHN MORRIS

Organization: ISG INFRASYS

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 16:36:29 EDT 2015

Committee Statement

Resolution: See FR 1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 96 9/25/2015 3:03 PM

Page 7: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 18-NFPA 1801-2014 [ Section No. 2.3.3 ]

2.3.3 ISO/IEC Publications.

International Standards Organization, 1 rue de Varembé, Case Postale 56, CH-1211 Genéve 20, Switzerland.

IEC 60529, Degrees of protection provided by enclosures (IP Code) Ed. 2.1 b:2001.

IEC 61000-6-2, Electromagnetic compatibility (EMC) — Part 6-2: Generic standards — Immunity for industrialenvironments, 2005.

IEC 61000-6-3, Electromagnetic compatibility (EMC) — Part 6-3: Generic standards — Emission standard forresidential, commercial, and light-industrial environments, 2007.

ISO 27, Guidelines for corrective action to be taken by a certification body in the event of misuse of its mark ofconformity, 1983.

ISO 65, General requirements for bodies operating product certification systems , 1998 ISO17065:2012 ,Requirements for bodies certifying products, processes and services .

ISO 9001, Quality management systems — Requirements, 2008.

ISO 17011, Conformity assessment — General requirements for accreditation bodies accrediting conformityassessment bodies, 2004.

ISO 17025, General requirements for the competence of testing and calibration laboratories, 2005/Cor 1: 2006.

ISO 17493, Clothing and equipment for protection against heat — Test method for convective heat resistanceusing a hot air circulating oven, 2000.

ISO/IEC 17021, Conformity assessment — Requirements for bodies providing audit and certification ofmanagement systems, 2006.

Statement of Problem and Substantiation for Public Input

Update reference document to current number and title.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 16-NFPA 1801-2014 [Section No. 4.1.2] Same reference document.

Submitter Information Verification

Submitter Full Name: James Rose

Organization: Safety Equipment Institute

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 24 14:05:45 EST 2014

Committee Statement

Resolution: See FR 1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 96 9/25/2015 3:03 PM

Page 8: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 101-NFPA 1801-2015 [ New Section after 3.3.16 ]

TITLE OF NEW CONTENT - 3.3.XX Model.

The collective term used to identify a group of elements or items of the same basic design and components froma single manufacturer produced by the same manufacturing and quality assurance procedures that are coveredby the same certification.

Statement of Problem and Substantiation for Public Input

The term Model should be added to Chapter 3 Degfinitions as it does not currently exist. The proposed wording was taken fron NFPA 1982 -2013. The committee may also want to include the Model # in this defiinition.

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 13:04:45 EDT 2015

Committee Statement

Resolution: FR-2-NFPA 1801-2015

Statement: The term "model" is being defined in Chapter 3 because it is used in the standard. The proposed definitionwas taken from NFPA 1982.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 96 9/25/2015 3:03 PM

Page 9: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 102-NFPA 1801-2015 [ New Section after 3.3.25 ]

TITLE OF NEW CONTENT -3.3.XX Service Life

The period for which compliant product may be useful before retirement.

Statement of Problem and Substantiation for Public Input

The term SERVICE LIFE does not exist in the current standard and should be soemthing to be considerd for the end user to be informed of. This wording was taken from NFPA 1981-2013.

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 13:14:06 EDT 2015

Committee Statement

Resolution: FR-3-NFPA 1801-2015

Statement: The term "service life" does not exist in the current standard and is being included because it is used in thestandard. The technical committee believes that end users should be aware of what this term means.Thisdefinition was taken from NFPA 1981.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 96 9/25/2015 3:03 PM

Page 10: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 16-NFPA 1801-2014 [ Section No. 4.1.2 ]

4.1.2

All certification shall be performed by a certification organization that meets at least the requirements specified inSection 4.2, Certification Program, and that is accredited for personal protective equipment in accordance withISO 65 17065 , General requirements Requirements for bodies operating product certificationsystems certifying products, processes and services . The accreditation shall be issued by an accreditation bodyoperating in accordance with ISO 17011, Conformity assessment — General requirements for accreditationbodies accrediting conformity assessment bodies.

Statement of Problem and Substantiation for Public Input

Update document number and title to current version.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 17-NFPA 1801-2014 [Section No. 4.2.3]

Public Input No. 18-NFPA 1801-2014 [Section No. 2.3.3]

Submitter Information Verification

Submitter Full Name: James Rose

Organization: Safety Equipment Institute

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 24 13:56:40 EST 2014

Committee Statement

Resolution: FR-6-NFPA 1801-2015

Statement: The technical committee is updating the ISO document number and title to the current version.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 96 9/25/2015 3:03 PM

Page 11: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 49-NFPA 1801-2015 [ New Section after 4.1.6 ]

4.1.7 Thermal imagers shall be listed to ANSI/ISA-12 .12.01, Nonincendive Electrical Equipment for Use in ClassI and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) L ocations, and shall meet therequirements for at least Class I, Division 2, Groups C and D and Class II, Division 2, Groups F and G hazardouslocations, and with a Temperature Class of T3, T3A, T3B, T3C, T4, T4A, T5 or T6. For the purpose of theimpact test referenced in 15.4 of ANSI/ISA-1 2.12.01, NFPA 1801 shall be considered the applicable standard for products in unclassified locations.

Statement of Problem and Substantiation for Public Input

There are three key aspects to this input - - 1) Relocate Clause 7.1.4 to a new clause under 4.1 on general certification requirements, 2) Expand the Division 2 certification requirement to include Class II, Division 2, Groups F and G, in addition to the existing Class I, Division 2 requirements, and 3) Include reference to the T3 and T4 temperature classifications that have "A" suffixes, in addition to the existing reference to T3, T4, T5 and T6. The rationale for 1) is because compliance with ANSI/ISA-12.12.01 includes requirements for product labeling, user information, and design requirements, in addition to performance requirements. As written and located within the current edition of NFPA 1801, it could be mistakenly assumed that only compliance with the performance requirements in ANSI/ISA-12.12,01 is required. To address this issue, comparable text to 7.1.4 could be added under 5.1, 5.2 and 6.1, in addition to 7.1.4, but simply addressing the issue of compliance with ANSI/ISA-12.12.01 solely under 4.1 seemed simpler with less potential for confusion. The rationale for 2) is because exposure to Class II explosive dust atmospheres is a concern for this equipment, in addition to exposure to Class I explosive gas atmospheres. Compliance with these Class II, Division 2 requirements mostly involves use of a NEMA Type 12 or better enclosure. The rationale for 3) is because T3A, T3B, T3C and T4A are permitted temperature classifications between T3 and T6 in both ANSI/ISA-12.12.01 and in the NEC. See also Public Input No. 50-NFPA 1801-2015.

Submitter Information Verification

Submitter Full Name: PAUL KELLY

Organization: UNDERWRITERS LABORATORIES INC

Affilliation: UNDERWRITERS LABORATORIES INC

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 05 08:58:15 EDT 2015

Committee Statement

Resolution: See FR 4, 12, 16 and 17.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 96 9/25/2015 3:03 PM

Page 12: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 17-NFPA 1801-2014 [ Section No. 4.2.3 ]

4.2.3

The certification organization shall be accredited for personal protective equipment in accordance with ISO65 17065 , General requirements Requirements for bodies operating product certification systems certifyingproducts, processes and services . The accreditation shall be issued by an accreditation body operating inaccordance with ISO 17011, Conformity assessment — General requirements for accreditation bodies accreditingconformity assessment bodies.

Statement of Problem and Substantiation for Public Input

Update ISO document number and title to current version.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 16-NFPA 1801-2014 [Section No. 4.1.2] Same reference document to be updated.

Submitter Information Verification

Submitter Full Name: James Rose

Organization: Safety Equipment Institute

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 24 14:02:13 EST 2014

Committee Statement

Resolution: FR-7-NFPA 1801-2015

Statement: The technical committee is updating the ISO document number and title to current version.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 96 9/25/2015 3:03 PM

Page 13: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 30-NFPA 1801-2014 [ Section No. 4.2.9 ]

4.2.9

The certification organization shall have a follow-up inspection program of the manufacturer’s facilities of thecompliant product with at least two random and unannounced visits per 12-month period to verify the product’scontinued compliance.

4.2.9.1

As part of the follow-up inspection program, the certification organization shall select sample compliant product atrandom from the manufacturer’s production line, from the manufacturer’s in-house stock, or from the openmarket.

4.2.9.2

Sample product shall be evaluated by the certification organization to verify the product’s continued compliancein order to ensure that the materials, components, and manufacturing quality assurance systems are consistentwith the materials, components, and manufacturing quality assurance that were inspected and tested by thecertification organization during initial certification and recertification.

4.2.9.3

The certification organization shall be permitted to conduct specific testing to verify the product’s continuedcompliance.

4.2.9.4

For products, components, and materials where prior testing, judgment, and experience of the certificationorganization have shown results to be in jeopardy of not complying with this standard, the certificationorganization shall conduct more frequent testing of sample product, components, and materials acquired inaccordance with 4.2.9.1 against the applicable requirements of this standard.

Statement of Problem and Substantiation for Public Input

Whole chapter 4.2.9 can be removed.If chapter 7.1.4 is clarified so that certification to ANSI/ISA 12.12.01 is required, no follow-up inspection program is needed for NFPA1801.The ANSI/ISA12.12.01 ”Factory audit inspection” program, together with chapter 4.4.1 annual recertification will give the same effect. ANSI/ISA requires 4 yearly factory audit inspections. There is no need for additional NFPA1801 follow-up inspections above the annual NFPA1801 recertification and four factory audit inspections for ANSI/ISA.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 29-NFPA 1801-2014 [Section No.7.1.4]

If ANSI/ISA12.12.01 certification is required, 4.2.9 isunnecessary

Submitter Information Verification

Submitter Full Name: Lea Dabiri

Organization: Flir Systems

Street Address:

City:

State:

Zip:

Submittal Date: Mon Dec 15 09:32:22 EST 2014

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 96 9/25/2015 3:03 PM

Page 14: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Resolution: The TC believes that the requirements of NFPA 1801 and ANSI/ISA 12.12.01 are two separate sets ofauditing parameters. ANSI/ISA 12.12.01 does not cover all of the performance requirements in Chapter 7 ofNFPA 1801.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 96 9/25/2015 3:03 PM

Page 15: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 55-NFPA 1801-2015 [ Section No. 5.1.6 ]

5.1.6

The following compliance statement shall be legibly printed on the product label:

“THIS THERMAL IMAGER MEETS THE REQUIREMENTS OF NFPA 1801, STANDARD ON THERMALIMAGERS FOR THE FIRE SERVICE ,

2013

20XX EDITION.

DO NOT REMOVE THIS LABEL!”

Statement of Problem and Substantiation for Public Input

The date on the standard needs to be updated and corrected to the next edition

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 20:30:40 EDT 2015

Committee Statement

Resolution: FR-10-NFPA 1801-2015

Statement: The date on the label is being updated to correspond to the next edition date of the standard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 96 9/25/2015 3:03 PM

Page 16: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 56-NFPA 1801-2015 [ Section No. 5.1.7 ]

5.1.7

Each thermal imager shall be marked directly with the serial number and the with a serial number and the yearand month of manufacture.

Statement of Problem and Substantiation for Public Input

New verbiage indicates that both a serial number and the year and month of manufacture shall be marked. Hopefully this will prevent the year and month from being embedded somewhere in in the serial number.This verbiage also is closer to similar wording in section 5.1.8 making them more consistent.

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 20:35:02 EDT 2015

Committee Statement

Resolution: FR-11-NFPA 1801-2015

Statement: The technical committee is introducing new requirements to indicate that both a serial number and the yearand month of manufacture shall be marked. The committee's intent is to prevent the year and month frombeing embedded somewhere else within the serial number.

This change is also similar to the requirements in section 5.1.8 and makes both paragraphs moreconsistent.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 96 9/25/2015 3:03 PM

Page 17: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 81-NFPA 1801-2015 [ Section No. 5.2.3 ]

5.2.3

Information and materials regarding pre-operational use shall be provided on at least the following areas:

(1) Safety considerations

(2) Pre-use checks

(3) Limitations of use

(4) Power source requirements, type, and brand

(5) Estimated operation time on fully charged power source in each available mode

(6) Estimated operational time associated with each of the four segments on the Power Source Satus Indicator

(7) Low-power source signals and power supply replacement, where applicable

(8) Charging and recharging procedures

(9) Marking recommendations and restrictions

(10) Warranty information

(11) Recommended storage practices

(12) Mounting on/in vehicles or fire apparatus

(13) Explanation and identification of the features and functions of TI BASIC/TI BASIC PLUS

(14) Symbols and functions with associated temperature references in available operating modes

(15) If equipped with a temperature bar, adequate description of the use of the temperature bar

(16) If equipped with a numeric temperature indicator, adequate description of the use of the numerictemperature indicator

(17) If equipped with colorization, adequate description of the temperature thresholds for colorization

Statement of Problem and Substantiation for Public Input

Although the standard specifies percentage of power availablepercentage means nothing to the user. We specify in section 6.1.2 that the the thermal imager shall be capable of continuously operationg for a minimum of 120 minutes in TI BASIC mode. If the manufacturer supplies a power source that is capable of operating for a minimum of 120 minutes or greater they should be able to provide the estimated level of power associated with each of the four segments in time. It should be noted that the operating time of a fully charged power source currently supplied in many thermal imagers far exceeds 120 minutes.

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 08:15:06 EDT 2015

Committee Statement

Resolution: FR-13-NFPA 1801-2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 96 9/25/2015 3:03 PM

Page 18: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Statement: The technical committee believes that although the standard specifies percentage of power availablepercentage, this means little to the user. Section 6.1.2 requires that the thermal imager shall be capable ofcontinuously operating for a minimum of 120 minutes in TI BASIC mode. If the manufacturer supplies apower source that is capable of operating for a minimum of 120 minutes or greater it should be able toprovide the estimated level of power associated with each of the four segments in time. It should be notedthat the operating time of a fully charged power source currently supplied in many thermal imagers farexceeds 120 minutes.

An Annex text and Table are also being added as explanatory material.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 96 9/25/2015 3:03 PM

Page 19: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 93-NFPA 1801-2015 [ New Section after 6.1.2 ]

6.1.2.1

All power sources consisting of battery cells and battery packs should be evaluated by a national recognizedtesting laboratory (NRTL) in accordance with the regulations outlined in UL 1642, Standard for Lithium Batteries ,or UL 2054, Standard for Household and Commercial Batteries , or .IEC62133 Safety requirements for portablesealed secondary cells, and for batteries made from them, for use in portable applications

Statement of Problem and Substantiation for Public Input

Promotion of note hidden in the appendix to the main specification. Includes proposed amendment to A.6.1.2

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 11:02:06 EDT 2015

Committee Statement

Resolution: See FR 14.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 96 9/25/2015 3:03 PM

Page 20: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 94-NFPA 1801-2015 [ New Section after 6.1.2 ]

6.1.2.2

All power sources consisting of battery cells and battery packs should have passed the UN38.3 T1 to T8 batterysafety tests at a 3rd party laboratory.

Statement of Problem and Substantiation for Public Input

In order to ensure air transport safety, and to meet customer demand for transport of cargo containing lithium batteries, according to IATA "Dangerous Goods Rules, any Lithium batteries must have passed UN38.3 testing at a 3rd party laboratory.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 11:10:58 EDT 2015

Committee Statement

Resolution: The TC believes that it is the responsibility of the manufacturer to complete the required shipping papers.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 96 9/25/2015 3:03 PM

Page 21: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 8-NFPA 1801-2014 [ Section No. 6.1.2 ]

6.1.2*

All thermal imagers shall be capable of continuously operating for a minimum of 120 minutes in TI BASIC modein room temperature without the power source being changed or recharged.

Statement of Problem and Substantiation for Public Input

Specifying environmental conditions for this requirement.

Submitter Information Verification

Submitter Full Name: Lea Dabiri

Organization: Flir Systems

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 19 13:07:44 EST 2014

Committee Statement

Resolution: FR-14-NFPA 1801-2015

Statement: In 6.1.2, the technical committee is specifying environmental conditions for this requirement.

In 6.1.2.1, the committee is clarifying that passive functions such as automatic background video and imagerecording may reduce the running time of the thermal imager preventing it from offering the required 120minutes minimum of operating time.

The committee is moving the Annex text A.6.1.2 moved to the body of the standard as a new 6.1.3.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 96 9/25/2015 3:03 PM

Page 22: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 92-NFPA 1801-2015 [ Section No. 6.1.2 ]

6.1.2 *

All thermal imagers shall be capable of continuously operating for a minimum of 120 minutes in TI BASIC modewithout the power source being changed or recharged.

The continuous operating time should be measured with any passive functions such as automatic backgroundvideo and image recording active.

Statement of Problem and Substantiation for Public Input

Passive functions such as automatic background video and image recording may reduce the running time of the thermal imager preventing it from offering the required 120 minutes minimum of operating time.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 11:00:23 EDT 2015

Committee Statement

Resolution: See FR 14.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 96 9/25/2015 3:03 PM

Page 23: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 2-NFPA 1801-2014 [ New Section after 6.1.3 ]

Minimum video refresh rate

All thermal imagers shall have a minumum video refresh rate of 30 frames per second.

Statement of Problem and Substantiation for Public Input

The original intent of the document was to require video refresh rates of 30Hz or higher. This was discussed and included in the pre-NFPA technical document but was lost somewhere along the line. A low refresh rate camera will pass the NFPA 1801 image quality tests since all the NFPA testing is done on static images. A refresh rate of less than 30Hz can make navigation more difficult and may lead to firefighter disorientation.

Submitter Information Verification

Submitter Full Name: Craig Gestler

Organization: MSA

Affilliation: MSA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Apr 25 15:58:02 EDT 2014

Committee Statement

Resolution: FR-19-NFPA 1801-2015

Statement: The technical committee observed that the original intent of the document was to require video refresh ratesof 30Hz or higher. This was discussed and included in the earlier drafts of the standard under development,but was not included in the final version. A low refresh rate camera will pass the NFPA 1801 image qualitytests since all the NFPA testing is done on static images. A refresh rate of less than 30Hz can makenavigation more difficult and may lead to firefighter disorientation.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 96 9/25/2015 3:03 PM

Page 24: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 79-NFPA 1801-2015 [ Section No. 6.1.7 ]

6.1.7

All thermal imagers shall be provided with a method of with all of the methods/devices of attaching the thermalimager to the user , and the method of attachment shall not that the manufacturer may offer. Eachmethod/device shall be attached to the thermal imager and the user as intended. When attached to both the userand the thermal imager they shall not degrade the function or performance of the thermal imager.

Statement of Problem and Substantiation for Public Input

We require that the thermal imager shall be provided with a method of attaching the thermal imager to the user, and the method of attachment shall not degrade the function or performance of the thermal imager but no where in the standard do we test for this.It is importaint to have have 6.1.7 as today most thermal imagers should and are intended to be attached to the user, possibly by a retractable lanyard or strap rather than to just be hand held. It is understood that there are several methods of attachement and it would be counterproductive to the process to have a manufactuer submitt all specimens with all the attachement variations for all the testing. It is recommended that each means of attachment that a manufacturer offers be be supplied to the testing lab and that the testing lab simply attach them to the thermal imager as intended and then to the person as intended by the manufactuer to determine if either the attachement point on the thermal imager and/or the method of attachement degrades the function or performance of the thermal imager.

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 07:41:22 EDT 2015

Committee Statement

Resolution: FR-20-NFPA 1801-2015

Statement: NFPA 1801 requires that the thermal imager shall be provided with a method of attaching the thermalimager to the user, and the method of attachment shall not degrade the function or performance of thethermal imager but nowhere in the standard is a test conducted for this.

It is important to have have the requirement in 6.1.9 as most thermal imagers are intended to be attached tothe user, possibly by a retractable lanyard or strap rather than to just be hand held. It is understood thatthere are several methods of attachment and it would be counterproductive to the process to have amanufacturer submit all specimens with all the attachment variations for all the testing. It is recommendedthat each means of attachment that a manufacturer offers be provided to the testing lab and that the testinglab simply attach them to the thermal imager as intended and then to the person to determine if either theattachment point on the thermal imager and/or the method of attachment degrades the function orperformance of the thermal imager.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 96 9/25/2015 3:03 PM

Page 25: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 57-NFPA 1801-2015 [ Section No. 6.2.1 [Excluding any Sub-Sections] ]

The thermal imager shall have a power–on/off button that cycles the thermal imager’s power. The power power–on/off button shall be located in an easily accessible area of the thermal imager.

Statement of Problem and Substantiation for Public Input

provides consistency in verbiage

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 20:56:00 EDT 2015

Committee Statement

Resolution: FR-21-NFPA 1801-2015

Statement: The technical committee is providing this change for consistency of terminology throughout the document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 96 9/25/2015 3:03 PM

Page 26: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 105-NFPA 1801-2015 [ Section No. 6.2.1.1 ]

6.2.1.1

The power–on/off button shall be capable of being switched by a gloved hand. The gloves used for this functiontest shall be contructed from American cow hide and include a PTFE moisture barrier and shall comply withstructural fire-fighting glove requirements of NFPA 1971, Standard on Protective Ensembles for Structural FireFighting and Proximity Fire Fighting.

Statement of Problem and Substantiation for Public Input

The requirements for the gloves used for the power button test are not specific enough. The NFPA 1971 requirement for a structural fire fighting glove is a minimum requirement. Many firefighters choose to wear gloves that offer additional protection but are less compliant (flexible), making it more difficult to push buttons on the TIC. The "gloved hand" requirement should not be based on just the minimum glove requirements.

Submitter Information Verification

Submitter Full Name: Craig Gestler

Organization: MSA Safety

Affilliation: MSA Safety

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 15:07:51 EDT 2015

Committee Statement

Resolution: See FR 30. Paragraph deleted.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 96 9/25/2015 3:03 PM

Page 27: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 32-NFPA 1801-2015 [ Section No. 6.2.1.1 ]

6.2.1.1

The power–on/off button shall be capable of being switched by a gloved hand. The gloves used for this functiontest shall comply with structural fire-fighting glove requirements of NFPA 1971, Standard on ProtectiveEnsembles for Structural Fire Fighting and Proximity Fire Fighting .

Statement of Problem and Substantiation for Public Input

Requirement for power-button is already covered by section 6.1.6 which covers all 'operational selection devices'

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 08:56:32 EST 2015

Committee Statement

Resolution: FR-30-NFPA 1801-2015

Statement: The technical committee is deleting this requirement for the power-button because it is redundant withSection 6.1.6 on operational selection devices.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 96 9/25/2015 3:03 PM

Page 28: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 58-NFPA 1801-2015 [ Section No. 6.2.2 ]

6.2.2

The power-on/off button shall be green in color. No other button(s) on the outside of the thermal imager shall begreen in color.

Statement of Problem and Substantiation for Public Input

provides consistency in verbiage

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:00:45 EDT 2015

Committee Statement

Resolution: FR-22-NFPA 1801-2015

Statement: The technical committee is providing this change to maintain consistency in terminology throughout thestandard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 96 9/25/2015 3:03 PM

Page 29: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 59-NFPA 1801-2015 [ Section No. 6.2.3 ]

6.2.3

The power-on/off button shall only turn the thermal imager “on,” turn the thermal imager “off,” and revert thethermal imager to the TI BASIC operational format from TI BASIC PLUS operational format.

Statement of Problem and Substantiation for Public Input

provides consistency in verbiage

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:02:57 EDT 2015

Committee Statement

Resolution: FR-23-NFPA 1801-2015

Statement: The technical committee is providing this change to maintain consistency in terminology throughout thestandard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 96 9/25/2015 3:03 PM

Page 30: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 60-NFPA 1801-2015 [ Section No. 6.2.5 [Excluding any Sub-Sections] ]

Where the power-on/off button is used to power up the thermal imager, the power-on process shall require thepower button to be pressed and held for no more than 1 second.

Statement of Problem and Substantiation for Public Input

provides consistency in verbiage

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:06:37 EDT 2015

Committee Statement

Resolution: FR-24-NFPA 1801-2015

Statement: The technical committee is providing this change to maintain consistency in terminology throughout thestandard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 96 9/25/2015 3:03 PM

Page 31: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 61-NFPA 1801-2015 [ Section No. 6.2.5.2 ]

6.2.5.2

Both the power-on/off button activation and the automatic activation shall present a useful thermal image on thedisplay in 60 seconds or less.

Statement of Problem and Substantiation for Public Input

provides consistency in verbiage

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:09:59 EDT 2015

Committee Statement

Resolution: FR-25-NFPA 1801-2015

Statement: The technical committee is providing this change to maintain consistency in terminology throughout thestandard.

The TC believes that the time of 60 seconds was originally allocated for older technology (BST) thermalimagers that required a "warm up/start up" time. The BST technology is no longer manufactured.

The TC believes that as the use of thermal imagers becomes more user-friendly through training andsimplification of use as permitted by this standard, the presentation of a useful image on the display and theicons required by the TI Basic Operational Format should not be longer than 30 seconds.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 96 9/25/2015 3:03 PM

Page 32: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 62-NFPA 1801-2015 [ Section No. 6.2.5.2 ]

6.2.5.2

Both the power button activation and the automatic activation shall present a useful thermal image on the with allthe icons required in the TI Basic Operational Format on the display in 60 30 seconds or less.

Statement of Problem and Substantiation for Public Input

The time of 60 seconds was originally allocated for older technology (BST) thermal imagers that required a "warm up/start up" time. The BST technology is no longer manufactured. As the use of thermal imagers becomes more user friendly through training and simplification of use as allotted with this standard the presentation of a useful image on the display and the icons required by the TI Basic Operational Format should not be longer than 30 seconds

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:11:16 EDT 2015

Committee Statement

Resolution: See FR 25.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 96 9/25/2015 3:03 PM

Page 33: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 78-NFPA 1801-2015 [ Section No. 6.2.5.2 ]

6.2.5.2

Both the power button activation and the automatic activation shall present a useful thermal image on the displayin 60 in 10 seconds or less.

Statement of Problem and Substantiation for Public Input

Should the thermal Imager for any reason need to have power reapplied, 60 seconds is much too long a period of time to be without an image. This reduced time of 10 seconds should be easily achievable.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 07:39:28 EDT 2015

Committee Statement

Resolution: See FR 25.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 96 9/25/2015 3:03 PM

Page 34: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 33-NFPA 1801-2015 [ Section No. 6.2.6 ]

6.2.6

The power–on/off button shall be protected from accidental change of operation and impact damage.

Statement of Problem and Substantiation for Public Input

Requirement of protection from 'accidental Change of mode of operation' is already covered by section 6.1.5 which requires for all 'operational selection devices' to be 'designed to prevent unintentional activation, deactivation, and change of operation'

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 09:03:33 EST 2015

Committee Statement

Resolution: See FR 32.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 96 9/25/2015 3:03 PM

Page 35: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 100-NFPA 1801-2015 [ Section No. 6.4.3 ]

6.4.3

TI BASIC operational format functions shall include the following:

(1) Grayscale imagery with white-hot polarity

(2) Power source status

(3) Internal electronics overheat indicator

(4) Thermal imager “on” indicator

(5) Icons related to normal operation are permitted to be displayed

Statement of Problem and Substantiation for Public Input

Manufactures display Icons on display e.g. current colour mode to help the user. Permitting these in TI Basic mode will reduce confusion when plus mode features are available and used.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 12:41:13 EDT 2015

Committee Statement

Resolution: The TC believes that this text belongs in 6.4.4. See the First Revision to 6.4.4.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 96 9/25/2015 3:03 PM

Page 36: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 63-NFPA 1801-2015 [ Section No. 6.4.3 ]

6.4.3

TI BASIC operational format functions shall include the following:

(1) Grayscale imagery with white-hot polarity

(2) Power source status indicator

(3) Internal electronics overheat indicator

(4) Thermal imager “on” indicator

Statement of Problem and Substantiation for Public Input

Consistency in wording in the document

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:24:24 EDT 2015

Committee Statement

Resolution: FR-28-NFPA 1801-2015

Statement: The technical committee is providing this change to maintain consistency in terminology throughout thestandard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 96 9/25/2015 3:03 PM

Page 37: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 9-NFPA 1801-2014 [ Section No. 6.4.3 ]

6.4.3

TI BASIC operational format functions shall include the following:

(1) Grayscale imagery with white-hot polarity

(2) Power source status

(3) Internal electronics overheat indicator

(4) Thermal imager “on” indicator

Statement of Problem and Substantiation for Public Input

Thermal imager "on" indicator does not add any relevant information for the user. When implemented on the screen it is already obvious that the TI is on. Not even when implemented as an additional indicator (e.g. LED) it does not add enought information to be motivated. There are e.g. cheaper ways to test batteries and if the display is broken, the camera is not functional any way.

Submitter Information Verification

Submitter Full Name: Lea Dabiri

Organization: Flir Systems

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 19 13:16:00 EST 2014

Committee Statement

Resolution: The TC believes that the LED indicator is a useful indicator for the functionality of the display.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 96 9/25/2015 3:03 PM

Page 38: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 64-NFPA 1801-2015 [ Section No. 6.4.4 ]

6.4.4

In addition to the requirements specified in 6.4.3, the TI BASIC operational format shall be permitted to alsoinclude the following:

(1) Heat indicating color and, if so equipped with heat indicating color, a color heat color reference bar

(2) Temperature bar

(3) Numeric temperature measurement indicator

Statement of Problem and Substantiation for Public Input

Consistent terminology throughout the document

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:31:30 EDT 2015

Committee Statement

Resolution: FR-27-NFPA 1801-2015

Statement: The technical committee is providing this change to maintain consistency in terminology throughout thestandard.

The TC also notes that new features that have become popular since the original specification was releasedand where these are invisible to the user should be made available within the TI BASIC operational formatso that they can be maintained during power cycling. See paragraph 6.5.4.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 96 9/25/2015 3:03 PM

Page 39: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 77-NFPA 1801-2015 [ Section No. 6.4.4 ]

6.4.4

In addition to the requirements specified in 6.4.3, the TI BASIC operational format shall be permitted to alsoinclude the following:

(1) Heat indicating color and, if so equipped with heat indicating color, a color reference bar

(2) Temperature bar

(3) Numeric temperature measurement indicator

(4) Passive functions such as automatic background video and image recording.

Statement of Problem and Substantiation for Public Input

New features that have become popular since the original specification was released and where these are invisible to the user they should be made available within the TIBASIC operational format so that they can be maintained during power cycling. See clause 6.5.4

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 07:03:32 EDT 2015

Committee Statement

Resolution: See FR 27.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 96 9/25/2015 3:03 PM

Page 40: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 65-NFPA 1801-2015 [ Section No. 6.5.1 ]

6.5.1

TI BASIC PLUS operational format shall have at least the TI BASIC operational format functions specified in6.4.3, and any or all of the TI BASIC operational format functions listed in 6.4.4 shall also be permitted.

Statement of Problem and Substantiation for Public Input

Consistency in wording throughout the standard

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:37:50 EDT 2015

Committee Statement

Resolution: FR-26-NFPA 1801-2015

Statement: The technical committee is providing this change to maintain consistency in terminology throughout thestandard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 96 9/25/2015 3:03 PM

Page 41: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 103-NFPA 1801-2015 [ New Section after 6.5.2 ]

TITLE OF NEW CONTENT 6.5.X Image/Audio Recording

The user shall have knowledge by some means (an icon or LED) that an internal recording device is/has beenturned on/ activated.

The recording device shall be capable of being turned off / de activated by either deprssing the greenpower/-on/off button or an alternative method of selecting the operational format other than by software accessvia a computer.

Statement of Problem and Substantiation for Public Input

An internal "Blackbox" /recording feature may be benificial but can also be an item that can be utilized negatively in certain situations and the user/fire department may be held liable. The user should have a readily accessible option to deactivate the record feature.

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 13:47:14 EDT 2015

Committee Statement

Resolution: The submitter was present at the meeting, and asked that it be withdrawn.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 96 9/25/2015 3:03 PM

Page 42: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 68-NFPA 1801-2015 [ Section No. 6.6.3.1 ]

6.6.3.1 Additional Information Area, Left Vertical Section.

The left vertical section shall be reserved for additional information in both the TI BASIC and TI BASIC PLUSoperational formats utilizing standard icons/symbols and locations

and

.

In the TI BASIC operational format the Left Vertical Section shall include only the following:

(1) Low sensitivity mode indicator

(2) TI BASIC PLUS indicator upon activation, if so equipped

In the TI BASIC PLUS operational format the Left Vertical Section shall include the following:

(1) Low sensitivity mode indicator

(2) TI BASIC PLUS indicator upon activation

(3) Activation and status of optional TI BASIC PLUS features and functions, if so equipped

Statement of Problem and Substantiation for Public Input

In the TI basic Operational Mode the Left vertical section should only display those indicators to be used by the operator in the TI Basic mode of operation. Any additional icons can be confusing and create discrepancies to user trained to use NFPA 1801 compliant thermal imagers especially if the user does not see the TI Basic Plus operational format indicator but does see other icons.

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 22:11:29 EDT 2015

Committee Statement

Resolution: FR-35-NFPA 1801-2015

Statement: The technical committee believes that the TI BASIC operational mode the left vertical section should onlydisplay those indicators to be used by the operator in the TI BASIC mode of operation. Any additional iconscan be confusing and create discrepancies to a user trained to use NFPA 1801-compliant thermal imagersespecially if the user does not see the TI BASIC PLUS operational format indicator but does see the othericons.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 96 9/25/2015 3:03 PM

Page 43: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 66-NFPA 1801-2015 [ Section No. 6.6.3.2 ]

6.6.3.2 Alarm and Operational Indicator Area, Center Vertical Section.

The center column of the display plane shall be reserved for the alarm and operational indicators and shallinclude the following:

(1) Power source status indicator

(2) Temperature measurement zone, if so equipped

(3) Internal electronics overheat indicator

Statement of Problem and Substantiation for Public Input

Consistency throughout the standard

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:40:57 EDT 2015

Committee Statement

Resolution: FR-29-NFPA 1801-2015

Statement: The technical committee is providing this change to maintain consistency in terminology throughout thestandard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 96 9/25/2015 3:03 PM

Page 44: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 104-NFPA 1801-2015 [ Section No. 6.6.4.1.11 [Excluding any Sub-Sections] ]

In the TI BASIC mode, the heat color reference bar shall have a color scale that includes only the followingcolorization:

(1) Transparent — at the bottom of the heat color reference bar before color indication begins and shall notbe more than 50% of the overall height of the heat color refernce bar.

(2) Yellow — at the low end of the heat color reference bar

(3) Orange — in the middle of the heat color reference bar

(4) Red — at the high end of the heat color reference bar

Statement of Problem and Substantiation for Public Input

Further clarification of the heat color refernce bar is required for standardization so as to not leave anything to interpretaion by the manufacturer.

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 14:00:21 EDT 2015

Committee Statement

Resolution: See FR 36.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 96 9/25/2015 3:03 PM

Page 45: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 76-NFPA 1801-2015 [ Section No. 6.6.4.1.11 [Excluding any Sub-Sections] ]

In the TI BASIC mode, the heat color reference bar shall have a color scale that includes only the followingcolorization:

(1) Transparent — GreyScale — at the bottom of the heat color reference bar before color indication begins

(2) Yellow — at the low end of the heat color reference bar

(3) Orange — in the middle of the heat color reference bar

(4) Red — at the high end of the heat color reference bar

Statement of Problem and Substantiation for Public Input

This clarifies the original intent of the standard that the reference bar should show the display content appropriate to the temperature. In the case before colour indication begins would be a greyscale. Where this has been interpreted literally the temperature bar representation could become misleading due to the scene content mixing with the bar.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 05:41:54 EDT 2015

Committee Statement

Resolution: FR-36-NFPA 1801-2015

Statement: The technical committee is clarifying the original intent of the standard that the reference bar should showthe display content appropriate to the temperature. In the case before color indication begins would be agreyscale. Where this has been interpreted literally the temperature bar representation could becomemisleading due to the scene content mixing with the bar.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 96 9/25/2015 3:03 PM

Page 46: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 97-NFPA 1801-2015 [ Section No. 6.6.4.1.12 ]

6.6.4.1.12

The heat color reference bar shall be legible, shall extend to at least 75 percent of the height of the thermalimager display, and shall and can be dynamic in that it will change if necessary to correspond to thetemperatures set by the manufacturer in whatever sensitivity mode the thermal imager is in. The relationship ofcolour to scene temperature shall be the same in all sensitivity modes.

Statement of Problem and Substantiation for Public Input

The duplication of one colour e.g. Yellow representing different temperatures eg. 150F, 400F and 800F is confusing and dangerous to the user.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 98-NFPA 1801-2015 [Section No. 6.6.4.1.13]

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 12:05:35 EDT 2015

Committee Statement

Resolution: The TC decided to retain the language in 6.6.4.1.12, and a task group will be appointed to continue to lookat this issue and provide Public Comments.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 96 9/25/2015 3:03 PM

Page 47: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 10-NFPA 1801-2014 [ Section No. 6.6.4.1.13 ]

6.6.4.1.13

Whenever any change occurs in the scale of the color reference bar, a green triangle shall be displayed for atleast x seconds above and connected to the color reference bar as shown in Figure 6.6.4.

Statement of Problem and Substantiation for Public Input

Clarification in order to make the implementation easier and more standardized.

Submitter Information Verification

Submitter Full Name: Lea Dabiri

Organization: Flir Systems

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 19 13:27:41 EST 2014

Committee Statement

Resolution: The TC did not agree with the change, however, a task group was appointed to continue to investigate theissue and provide Public Comment.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 96 9/25/2015 3:03 PM

Page 48: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 98-NFPA 1801-2015 [ Section No. 6.6.4.1.13 ]

6.6.4.1.13

Whenever any change occurs in the scale of the color reference bar, a green triangle shall be displayed aboveand connected to the color reference bar as shown in Figure 6.6.4 .

Statement of Problem and Substantiation for Public Input

The triangle will remain on permanently after the first change occurs. It is therefor unable to indicate any further changes of the scale to the user, including the original start up condition. This does not add any useful functionality to the camera and does to help the user.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 97-NFPA 1801-2015 [Section No. 6.6.4.1.12]

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 12:13:03 EDT 2015

Committee Statement

Resolution: The TC did not agree with the change, however, a task group was appointed to continue to investigate theissue and provide Public Comment.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 96 9/25/2015 3:03 PM

Page 49: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 67-NFPA 1801-2015 [ Section No. 6.6.4.5 ]

6.6.4.5 Thermal Imager-On Indicator.

A visual indication to the user user other than a usable image on the display that the thermal imager is in thepowered-on operational mode shall be and shall be visible to the user any time the thermal imager is poweredon.

Statement of Problem and Substantiation for Public Input

Although it may require more draw on the power supply an indicator should be available to the user to indicate the thermal imager is "on" in the case of a failure of the display or if a thermal imager is equipped with a Stand By/Sleep/Power Save feature

Submitter Information Verification

Submitter Full Name: ROBERT ATHANAS

Organization: FDNYSAFE-IR INCORPORATED

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 01 21:53:51 EDT 2015

Committee Statement

Resolution: FR-37-NFPA 1801-2015

Statement: The technical committee believes that although it may require more draw on the power supply, an indicatorshould be available to the user to indicate the thermal imager is "on" in the case of a failure of the display orif a thermal imager is equipped with a Stand By/Sleep/Power Save feature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 96 9/25/2015 3:03 PM

Page 50: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 75-NFPA 1801-2015 [ Section No. 6.6.4.5 ]

6.6.4.5 Thermal Imager-On Indicator.

A visual indication to the user that the thermal imager is in the powered-on operational mode shall be visible tothe user any time the thermal imager is powered on.

6.6.4.5.1

This clause is satisfied by a thermal imager where the display is illuminated whenever the imager is switchedpowered on

.

Statement of Problem and Substantiation for Public Input

The standard is not clear with regard to this clause and how it can be interpreted by manufacturers.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 05:31:38 EDT 2015

Committee Statement

Resolution: See FR 37.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 96 9/25/2015 3:03 PM

Page 51: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 34-NFPA 1801-2015 [ Section No. 6.6.4.7.2 ]

6.6.4.7.2

The TI BASIC PLUS operational format indicator shall be an indicator consisting of a solid green “plus sign” ( + )enclosed in a transparent square box with a green border as shown in Figure 6.6.4.

Statement of Problem and Substantiation for Public Input

Correction of wording.

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 09:07:39 EST 2015

Committee Statement

Resolution: FR-38-NFPA 1801-2015

Statement: The technical committee is providing an editorial text correction.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 96 9/25/2015 3:03 PM

Page 52: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 99-NFPA 1801-2015 [ New Section after 7.1 ]

7.1.18

Thermal Imagers shall be tested for spot temperature accuracy, to verify design requirement in Section 6.6.4.1.6when viewing a small object.

Thermal Imagers shall be tested for relationship of colour to temperature to verify design requirement 6.6.4.2.

Statement of Problem and Substantiation for Public Input

The specification is open to certifying a camera that can show an incorrect spot temperature due to failing to change sensitivity mode. The camera may therefore show the maximum temperature of ‘high sensitivity mode ‘say 300F while viewing a small hot object at 800F, therefore misleading the user. The same issue applies to colour related temperature.A suitable test method will require definition, but this could also be used to validate the requirement that colours are not repeated in the temperature range

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 12:23:24 EDT 2015

Committee Statement

Resolution: The submitter was present at the meeting, and requested that the Public Input be withdrawn.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 96 9/25/2015 3:03 PM

Page 53: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 19-NFPA 1801-2014 [ Section No. 7.1.4 ]

7.1.4

Thermal imagers shall be tested for listing listed to ANSI/ISA-12.12.01, Nonincendive Electrical Equipment forUse in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations, and shall meetthe requirements for at least Class I, Division 2, Groups C and D hazardous locations, and with a TemperatureClass of T3 or T4 or T5 or T6. For the purpose of the impact test referenced in 15.4 of ANSI/ISA 12.12.01, NFPA1801 shall be considered the applicable standard for products in unclassified locations.

Statement of Problem and Substantiation for Public Input

"Listed" will include ongoing compliance with the UL913 requirements since factory visits are included with listed products. Saying only "tested" only requires the manufacturer to test the product once. This change will clarify the requirement that the product shall be listed for ongoing compliance for annual re-certification.

Submitter Information Verification

Submitter Full Name: James Rose

Organization: Safety Equipment Institute

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 24 14:09:48 EST 2014

Committee Statement

Resolution: See FR 17.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 96 9/25/2015 3:03 PM

Page 54: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 29-NFPA 1801-2014 [ Section No. 7.1.4 ]

7.1.4

Thermal imagers shall be tested for listing be certified to ANSI/ISA-12.12.01, Nonincendive Electrical Equipmentfor Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations, and shallmeet the requirements for at least Class I, Division 2, Groups C and D hazardous locations, and with aTemperature Class of T3 or T4 or T5 or T6. For the purpose of the impact test referenced in 15.4 of ANSI/ISA12.12.01, NFPA 1801 shall be considered the applicable standard for products in unclassified locations.

Statement of Problem and Substantiation for Public Input

The products should be CERTIFIED to ANSI/ISA 12.12.01. Motivation: Statement from Stephen Sanders, Technical Director SEI (Safety Equipment Institute) ([email protected]): With regard to Section 7.1.4 of NFPA 1801-2013 and the need for certification vs. testing to the ANSI/ISA 12.12.01 standard… SEI has required “certification” for electronics to the various intrinsic safety and/or hazloc standards, as opposed to just testing to the requirements in the applicable standard.SEI’s rationale for requiring certification relies upon SEI understanding of the intent of the NFPA Technical Committees. In addition to NFPA 1801-2013, requirements for compliance of electronics with intrinsic safety standards exist in other similar NFPA standards, including both NFPA 1981-2013 (SCBA) and NFPA 1982-2013 (PASS). Both of these standards specifically require certification for electronics. While NFPA 1801-2013 may utilize the word “tested” in Section 7.1.4, we believe that it was the intent of both the NFPA Electronics Safety Equipment Technical Committee and its parent committee, the Correlating Committee, that a TIC’s electronics be certified (which of course includes testing/evaluation and follow-up factory visits) as opposed to just being tested.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 30-NFPA 1801-2014 [Section No. 4.2.9]

Submitter Information Verification

Submitter Full Name: Lea Dabiri

Organization: Flir Systems

Street Address:

City:

State:

Zip:

Submittal Date: Mon Dec 15 09:27:27 EST 2014

Committee Statement

Resolution: See FR 17.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 96 9/25/2015 3:03 PM

Page 55: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 50-NFPA 1801-2015 [ Section No. 7.1.4 ]

7.1.4

Thermal imagers shall be tested for listing to ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use inClass I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations, and shall meet therequirements for at least Class I, Division 2, Groups C and D hazardous locations, and with a Temperature Classof T3 or T4 or T5 or T6. For the purpose of the impact test referenced in 15.4 of ANSI/ISA 12.12.01, NFPA 1801shall be considered the applicable standard for products in unclassified locations.

Statement of Problem and Substantiation for Public Input

The key aspect to this input is that it is not simply deleting 7.1.4, but instead is relocating Clause 7.1.4 to a new clause under 4.1 on general certification requirements (along with making some proposed revisions to the text as well). The rationale for relocating 7.1.4 is because compliance with ANSI/ISA-12.12.01 includes requirements for product labeling, user information, and design requirements, in addition to performance requirements. As written and located within the current edition of NFPA 1801, it could be mistakenly assumed that only compliance with the performance requirements in ANSI/ISA-12.12,01 is required. To address this issue, comparable text to 7.1.4 could be added under 5.1, 5.2 and 6.1, in addition to 7.1.4, but simply addressing the issue of compliance with ANSI/ISA-12.12.01 solely under 4.1 seemed simpler with less potential for confusion. See also Public Input No. 49-NFPA 1801-2015 (which includes details / rationale on the proposed revisions to the text).

Submitter Information Verification

Submitter Full Name: PAUL KELLY

Organization: UNDERWRITERS LABORATORIES INC

Affilliation: UNDERWRITERS LABORATORIES INC

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 05 09:03:54 EDT 2015

Committee Statement

Resolution: See FR 17. TC decided to revise this paragraph and split out the requirements to other paragraphs 5.1.9,5.2.8 and 6.1.8.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 96 9/25/2015 3:03 PM

Page 56: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 96-NFPA 1801-2015 [ Section No. 7.1.4 ]

7.1.4

Thermal imagers shall be tested for listing to ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use inClass I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations, and shall meet therequirements for at least Class I, Division 2, Groups C and D hazardous locations, and with a Temperature Classof T3 or T4 or T5 or T6. For the purpose of the impact test referenced in 15.4 of ANSI/ISA 12.12.01, NFPA 1801shall be considered the applicable standard for products in unclassified locations.

Assessment shall include all user removable parts in isolation and the action of removing them from the camerain the powered and unpowered state.

Where the use of a tool secured feature is relied upon to meet the ANSI / ISA 12.12.01 compliance and thisfeature is not engaged the camera shall inform the user by way of a message that prevents camera normal use.

Statement of Problem and Substantiation for Public Input

Locking features that rely on the use of special tools to limit the ability to perform simple tasks such as battery replacement are often ignored by users that have not read the small print hidden in the product user guide. However the certification bodies are much more comfortable with this approach and adherence is recognised within the high risk Petrochemical / Mining Industries.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 11:55:30 EDT 2015

Committee Statement

Resolution: See FR 17.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 96 9/25/2015 3:03 PM

Page 57: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 24-NFPA 1801-2014 [ Section No. 7.1.6 ]

7.1.6

Thermal imagers shall be tested for electromagnetic emission as specified in IEC 61000-6-3 4 , Electromagneticcompatibility (EMC) — Part 6-3 4 : Generic standards — Emission standard for residential, commercial, and light-industrial environments, and shall meet the emissions requirements.

Statement of Problem and Substantiation for Public Input

Any situation requiring first responder intervention more closely mimics an industrial environment where the functionality of the equipment takes precedence over any EMC concerns that might be in place in a residential environment under normal circumstances. The industrial standard allows equipment designers greater latitude in designing equipment that must perform reliably in difficult situations.

Submitter Information Verification

Submitter Full Name: Craig Gestler

Organization: MSA Safety, Inc

Affilliation: MSA Safety, Inc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 02 08:12:10 EST 2014

Committee Statement

Resolution: The TC believes that this is currently being done.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 96 9/25/2015 3:03 PM

Page 58: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 69-NFPA 1801-2015 [ Section No. 8.1.3.5 ]

8.1.3.5

Specimens are permitted to shall be optimally focused to 1 m by the manufacturer for this test.

Statement of Problem and Substantiation for Public Input

SR targets are designed for testing at 1 meter therefor thermal imagers should be focused at 1 meter.

Submitter Information Verification

Submitter Full Name: JOHN MORRIS

Organization: ISG INFRASYS

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 02 08:02:54 EDT 2015

Committee Statement

Resolution: FR-42-NFPA 1801-2015

Statement: The technical committee believes that SR targets are designed for testing at 1 meter, therefore thermalimagers should be focused at 1 meter.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 96 9/25/2015 3:03 PM

Page 59: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 85-NFPA 1801-2015 [ Section No. 8.1.3.5 ]

8.1.3.5

Specimens are permitted to be optimally focused to 1 m by the manufacturer for this testThe specimens must be focused to 1m .

Statement of Problem and Substantiation for Public Input

The test chart was designed to be viewed at 1m. The results obtained from a camera not focused at 1m may lead to the analysis program producing rogue values that may indicate better or worse performance than the camera is actually capable of. A relatively low spatial resolution camera may still achieve the minimum pass criterial of SR = 0.06. In addition a camera whose focus point moves, to (2m to 3m) may also show an improvement in the SR value. (data can be presented to show this but is much too big to attach.)

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 10:07:57 EDT 2015

Committee Statement

Resolution: See FR 42.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 96 9/25/2015 3:03 PM

Page 60: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 35-NFPA 1801-2015 [ Section No. 8.1.4.6 [Excluding any Sub-Sections] ]

The thermal imager positioning device shall position the thermal imager facing the spatial resolution source targetat a distance of 1 m ± 5 mm (40 39.4 in. ± 0.2 in) from the outermost optical element to the stencil.

Statement of Problem and Substantiation for Public Input

The originally mentioned ranges 1m+/-5mm and 40in +/-0.2in did not even overlap.

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 09:10:47 EST 2015

Committee Statement

Resolution: FR-43-NFPA 1801-2015

Statement: The technical committee is making these conversion changes. The currently referenced ranges 1m+/-5mmand 40in +/-0.2in do not overlap.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 96 9/25/2015 3:03 PM

Page 61: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 36-NFPA 1801-2015 [ Section No. 8.1.5.11 ]

8.1.5.11

The image processing software shall scan each of the four regions of interest for the lightest pixel intensity (I max)

and the darkest pixel intensity (I min). The software shall then find the contrast of each of the four regions of

interest using Equation 8.1.5.11.

(8.1.5.11)

Additional Proposed Changes

File Name Description Approved

eg8_1_5_11.tif Corrected equation 8.1.5.11

Statement of Problem and Substantiation for Public Input

Correction of math.

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 09:13:11 EST 2015

Committee Statement

Resolution: FR-44-NFPA 1801-2015

Statement: The technical committee is correcting an error in the equation.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 96 9/25/2015 3:03 PM

Page 62: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1
Page 63: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 37-NFPA 1801-2015 [ Section No. 8.1.5.18 ]

8.1.5.18

Each of the four sets of converging lines shall be rotated such that the center line is vertical before selecting aregion of interest and performing calculations. The region of interest shall be selected from index 1 to 5 on the lowfrequency bars, and from index 5 to 9 on the high frequency bars. The region of interest shall be drawn along thelines as specified in Figure 8.1.5.18. No symbology shall be included in the ROI. In the case where symbologyinterferes with the target, the ROI shall be drawn around the interference such that horizontal lines areperpendicular to the center line and equal portions of white and dark areas are included.

Figure 8.1.5.18 Region of Interest Selection.

Additional Proposed Changes

File Name Description Approved

ROI-selection.tif original figure 8.1.5.18, rotated by 90 degrees ClockWise.

Statement of Problem and Substantiation for Public Input

Section 8.1.5.18 is asking 'that Each of the four sets of converging lines shall be rotated such that the center line is vertical before selecting a Region of interest', figure 8.1.5.18 is showing a set of converging lines with a horizontal center line. It might be clearer to Show Image with orientation that is in line with wording, i.e. rotated 90 degrees.

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 09:25:22 EST 2015

Committee Statement

Resolution: FR-45-NFPA 1801-2015

Statement: The technical committee believes that paragraph 8.1.5.18 is requiring that each of the four sets ofconverging lines shall be rotated such that the center line is vertical before selecting a region of interest.Figure 8.1.5.18 is showing a set of converging lines with a horizontal center line. It might be clearer to showthe image with an orientation that is in line with the wording, i.e. the figure should be rotated 90 degrees.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 96 9/25/2015 3:03 PM

Page 64: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1
Page 65: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 82-NFPA 1801-2015 [ Section No. 8.2.2.1 ]

8.2.2.1

Samples shall be conditioned as specified in 8.1.3.

The pre-test image recognition values in the vertical and horizontal directions shall be recorded as specified inSection 8.1 , Image Recognition Test.

Statement of Problem and Substantiation for Public Input

This may have been an unintentional consequence when the specification was revised. The thermal imagers need to be checked before they are subjected to any form of mechanical testing to confirm that they are optically compliant.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 09:34:53 EDT 2015

Committee Statement

Resolution: FR-46-NFPA 1801-2015

Statement: The technical committee believes that there may have been an unintentional consequence when thisrequirement was revised. The thermal imagers need to be checked before they are subjected to any form ofmechanical testing to confirm that they are optically compliant.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 96 9/25/2015 3:03 PM

Page 66: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 83-NFPA 1801-2015 [ Section No. 8.3.2.1 ]

8.3.2.1

SamplesThe pre-test image recognition values in the vertical and horizontal directions shall be

conditionedrecorded as specified in Section 8.1 , Image Recognition Test .

3.

Statement of Problem and Substantiation for Public Input

This may have been an unintentional consequence when the specification was revised. The thermal imagers need to be checked before they are subjected to any form of mechanical testing to confirm that they are optically compliant.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 09:43:34 EDT 2015

Committee Statement

Resolution: FR-47-NFPA 1801-2015

Statement: The technical committee believes that there may have been an unintentional consequence when therequirement was revised. The thermal imagers need to be checked before they are subjected to any form ofmechanical testing to confirm that they are optically compliant.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 96 9/25/2015 3:03 PM

Page 67: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 84-NFPA 1801-2015 [ Section No. 8.3.3.3 ]

8.3.3.3

Specimens shall be conditioned at a temperature of 22°C ± 3°C (72°F ± 5°F), and a relative humidity of 50percent ± 25 percent, for at least 4 hours.

Statement of Problem and Substantiation for Public Input

This is a duplicated requirement that is covered by the procedures in 8.3.4.1.1 / 8.3.4.1.2 / 8.3.4.1.3

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 09:46:09 EDT 2015

Committee Statement

Resolution: FR-48-NFPA 1801-2015

Statement: The technical committee is providing an editorial correction. This is a duplicated requirement that is coveredby the procedures in 8.3.2.1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 96 9/25/2015 3:03 PM

Page 68: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 25-NFPA 1801-2014 [ Section No. 8.5.3 ]

8.5.3 Specimens.

8.5.3.1

Specimens for testing shall be complete thermal imager viewing surfaces or representative plaques.

8.5.3.2

Seven specimens shall be chosen from a minimum of three viewing surfaces.

8.5.3.2.1

Four specimens shall be taken

from the left viewing area, and three specimens shall be taken from the right viewing area.

8.5.3.2.2

. One of the four specimens

taken from the left viewing area

shall be the set-up specimen.

8.5.3.3

The left test specimen specimens shall include all of the following criteria:

(1) The specimen shall be a square measuring 50 mm × 50 mm (2 in. × 2 in.).

(2) Two edges of the square section shall be parallel within ±2 degrees of the axis of the cylinder or cone in thecenter of the sample.

(3) At least 38 mm (1 1 ⁄ 2 in.) of the 50 mm × 50 mm (2 in. × 2 in.) square shall be taken from the left side ofthe center line of the viewing surface.

8.5.3.4

The right test specimens shall include all of the following criteria:

(1) The specimen shall be a square measuring 50 mm × 50 mm (2 in. × 2 in.).

(2) Two edges of the square section shall be parallel within ±2 degrees of the axis of the cylinder or cone inthe center of the sample.

(3) At least 38 mm (1 1 ⁄ 2 in.) of the 50 mm × 50 mm (2 in. × 2 in.) square shall be taken from the rightside of the centerline of the lens.

8.5.3.5

Each of the specimens shall be cleaned in the following manner:

(1) The specimen shall be rinsed with clean tap water.

(2) The specimen shall be washed with a solution of nonionic/low-phosphate detergent and water using aclean, soft gauze pad.

(3) The specimen shall be rinsed with de-ionized water.

(4) The specimen shall be blown dry with clean compressed air or nitrogen.

8.5.3.6 5

Specimens shall be conditioned at a temperature of 22°C ± 3°C (72°F ± 5°F), and a relative humidity of 50percent ± 25 percent, for at least 4 hours.

8.5.3.7 6

Specimens shall be tested within 5 minutes after removal from conditioning.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 96 9/25/2015 3:03 PM

Page 69: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Statement of Problem and Substantiation for Public Input

The display area from which the samples are taken is not generally large enough to take samples from the left and right sides. In practice, the samples have significant overlap and there is no real difference between left and right. The requirement was likely a relic from the NFPA 1981 SCBA face piece lens abrasion test where there could be significant differences from the right and left sides. Eliminating the extra samples saves time and money.

Submitter Information Verification

Submitter Full Name: Craig Gestler

Organization: MSA Safety, Inc

Affilliation: MSA Safety, Inc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 02 08:41:29 EST 2014

Committee Statement

Resolution: FR-49-NFPA 1801-2015

Statement: The technical committee believes that the display area from which the samples are taken is not generallylarge enough to take samples from the left and right sides. In practice, the samples have significant overlapand there is no real difference between left and right. The requirement was likely a relic from the NFPA 1981SCBA face piece lens abrasion test where there could be significant differences from the right and left sides.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 96 9/25/2015 3:03 PM

Page 70: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 72-NFPA 1801-2015 [ Section No. 8.5.3.2 [Excluding any Sub-Sections] ]

Seven specimens shall be chosen from a minimum of three sample viewing surfaces.

Statement of Problem and Substantiation for Public Input

Clarification

Submitter Information Verification

Submitter Full Name: JOHN MORRIS

Organization: ISG INFRASYS

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 02 10:13:29 EDT 2015

Committee Statement

Resolution: See FR 49.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 96 9/25/2015 3:03 PM

Page 71: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 21-NFPA 1801-2014 [ Section No. 8.5.3.2.1 ]

8.5.3.2.1

Four specimens shall be taken from the left viewing area, and three specimens shall be taken from the rightviewing area.

Statement of Problem and Substantiation for Public Input

This section was cut and pasted from SCBA mask standard and is not directly applicable to this standard since manufacturers typically provide representative plaques and samples are not cut from cameras. A TIC camera screen is typically not large enough to provide seven samples from a single piece.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 22-NFPA 1801-2014 [Section No. 8.5.3.2.2]

Public Input No. 23-NFPA 1801-2014 [Section No. 8.5.3.3]

Submitter Information Verification

Submitter Full Name: James Rose

Organization: Safety Equipment Institute

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 24 14:23:40 EST 2014

Committee Statement

Resolution: See FR 49.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 96 9/25/2015 3:03 PM

Page 72: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 71-NFPA 1801-2015 [ Sections 8.5.3.2.1, 8.5.3.2.2 ]

Sections 8.5.3.2.1, 8.5.3.2.2

8.5.3.2.1

Four Seven specimens shall be taken from the left viewing area, and three specimens shall be taken from theright viewing area .

8.5.3.2.2

One of the four seven specimens taken from the left viewing area shall be the set-up specimen.

Statement of Problem and Substantiation for Public Input

The original wording was taken from NFPA 1981 and was used for samples from Face piece lenses. The revised wording is suitable for smaller lens of thermal imager.

Submitter Information Verification

Submitter Full Name: JOHN MORRIS

Organization: ISG INFRASYS

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 02 10:07:32 EDT 2015

Committee Statement

Resolution: See FR 49.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 96 9/25/2015 3:03 PM

Page 73: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 22-NFPA 1801-2014 [ Section No. 8.5.3.2.2 ]

8.5.3.2.2

One of the four specimens taken from the left viewing area specimen shall be the set-up specimen.

Statement of Problem and Substantiation for Public Input

Simplify definition of the setup specimen to eliminate reference to left or right specimens in other sections which should be deleted.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 21-NFPA 1801-2014 [Section No. 8.5.3.2.1] Definition of lens specimens.

Submitter Information Verification

Submitter Full Name: James Rose

Organization: Safety Equipment Institute

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 24 14:27:19 EST 2014

Committee Statement

Resolution: See FR 49.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 96 9/25/2015 3:03 PM

Page 74: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 23-NFPA 1801-2014 [ Section No. 8.5.3.3 ]

8.5.3.3

The left test specimen specimens shall include all of the following criteria:

(1) The specimen shall be a square measuring 50 mm × 50 mm (2 in. × 2 in.).

(2) Two edges of the square section shall be parallel within ±2 degrees of the axis of the cylinder or cone in thecenter of the sample.

(3) At least 38 mm (1 1⁄2 in.) of the 50 mm × 50 mm (2 in. × 2 in.) square squares shall be taken from the leftside (four samples) and right side (three samples) of the center line of the viewing surface.

Statement of Problem and Substantiation for Public Input

Update sample descriptions to be consistent with changes to section 8.5.3.2

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 21-NFPA 1801-2014 [Section No. 8.5.3.2.1] Description of samples for testing.

Submitter Information Verification

Submitter Full Name: James Rose

Organization: Safety Equipment Institute

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 24 14:31:44 EST 2014

Committee Statement

Resolution: See FR 49.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 96 9/25/2015 3:03 PM

Page 75: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 73-NFPA 1801-2015 [ Sections 8.5.3.3, 8.5.3.4 ]

Sections 8.5.3.3, 8.5.3.4

8.5.3.3

The left test specimen shall include all of the following criteria:

(1) The specimen shall be a square measuring 50 mm × 50 mm (2 in. × 2 in.).

(2) Two edges of the square section shall be parallel within ±2 degrees of the axis of the cylinder or cone inthe center of the sample.

(3) At least 38 mm (1 1 ⁄ 2 in.) of the 50 mm × 50 mm (2 in. × 2 in.) square shall be taken from the left side ofthe center line of the viewing surface.

8.5.3.4

The right test specimens shall include all of the following criteria:

(1) The specimen shall be a square measuring 50 mm × 50 mm (2 in. × 2 in.).

(2) Two edges of the square section shall be parallel within ±2 degrees of the axis of the cylinder or cone inthe center of the sample.

(3) At least 38 mm (1 1 ⁄ 2 in.) of the 50 mm × 50 mm (2 in. × 2 in.) square shall be taken from the rightside of the centerline of the lens.

Statement of Problem and Substantiation for Public Input

clarified for thermal imager lens.

Submitter Information Verification

Submitter Full Name: JOHN MORRIS

Organization: ISG INFRASYS

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 02 10:15:46 EDT 2015

Committee Statement

Resolution: See FR 49.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

74 of 96 9/25/2015 3:03 PM

Page 76: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 26-NFPA 1801-2014 [ Section No. 8.5.5 ]

8.5.5 Procedure.

8.5.5.1

The haze of the specimen shall be measured using a haze meter in accordance with ASTM D 1003, StandardTest Method for Haze and Luminous Transmittance of Transparent Plastics, and recorded with the followingadditions:

(1) The haze shall be measured in the middle 2 mm2 of the specimen.

(2) The specimen shall be repositioned to achieve the maximum haze value within the area defined in 8.5.5.1(1).

(3) The haze meter shall have a specified aperture of 22 mm.

(4) The haze meter shall have a visual display showing 0.1 percent resolution.

(5) The haze meter shall be calibrated before and after each day’s use following procedures specified in ASTMD 1003, Standard Test Method for Haze and Luminous Transmittance of Transparent Plastics.

8.5.5.2

The set-up specimen shall be placed cover side up in the test apparatus specimen holder. The specimen holdershall be configured with a flat surface under the lens or with an inner radius support.

8.5.5.3

The pad holder shall consist of a cylinder 9.5 mm (0.4 in.) high and 25 mm (1 in.) in diameter with a radius ofcurvature equal to the radius of curvature of the outside of the lens in the viewing area ±0.25 diopter. This cylindershall be rigidly affixed to the stroking arm by a #10-32 UNF threaded rod.

8.5.5.4

The pad shall be a Blue Streak M306M wool felt polishing pad 23 mm (0.9 in.) in diameter.

8.5.5.5

The abrasive disc shall be made from 3M Part Number 7415, Wood Finishing Pad. A disc 23 mm (0.9 in.) indiameter shall be cut from the abrasive sheet. The marked side of the disc shall be placed against the pad. Careshall be exercised to maintain this orientation for each abrasive disc throughout the testing.

8.5.5.6

The pad holder, pad, and abrasive disc shall be installed on the stroking arm. The stroking arm shall be leveled to±3 degrees by adjusting the threaded pin. The pin shall be secured to prevent rotation of the pad holder. The axisof curvature of the pad holder shall be coincident with the axis of curvature of the lens.

8.5.5.7

The stroking arm shall be counterbalanced with the pad holder, pad, and abrasive disc in place.

8.5.5.8

The set-up specimen shall be replaced with one of the six three specimens to be tested.

8.5.5.9

A 1000 g ± 5 g (2.7 lb ± 0.16 oz.) test weight shall be installed on the pin above the test sample.

8.5.5.10

The test shall be run for 200 cycles ± 1 cycle. One cycle shall consist of a complete revolution of the eccentricwheel.

8.5.5.11

The length of stroke shall be 14 mm ( 1⁄2 in.), producing a pattern 38 mm (1 1⁄2 in.) long. The frequency of thestroke shall be 60 cycles per minute ± 1 cycle per minute. The center of the stroke shall be within ±2 mm (±0.08in.) of the center of the specimen.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

75 of 96 9/25/2015 3:03 PM

Page 77: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

8.5.5.12

The specimen shall be removed and cleaned following the test procedure. The abrasive disc shall be discarded.

8.5.5.13

The haze of the sample shall be measured following the test procedure.

8.5.5.14

The delta haze shall be calculated by subtracting the initial haze from the final haze.

8.5.5.15

The testing steps specified in 8.5.5.8 through 8.5.5.14 shall be repeated five two times with a new sample andabrasive disc.

Statement of Problem and Substantiation for Public Input

Correcting the number of samples required. Per the comment on 8.5.3, only 4 samples will be required; one for setup and the other three for the actual test.

Submitter Information Verification

Submitter Full Name: Craig Gestler

Organization: MSA Safety, Inc

Affilliation: MSA Safety, Inc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 02 08:57:49 EST 2014

Committee Statement

Resolution: FR-51-NFPA 1801-2015

Statement: The technical committee is providing a correction to the number of samples required. Per the comment on8.5.3, only 4 samples will be required; one for setup and the other three for the actual test.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

76 of 96 9/25/2015 3:03 PM

Page 78: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 27-NFPA 1801-2014 [ Section No. 8.5.6 ]

8.5.6 Report.

The six three delta haze values shall be averaged, recorded, and reported.

Statement of Problem and Substantiation for Public Input

Correcting the number of required samples

Submitter Information Verification

Submitter Full Name: Craig Gestler

Organization: MSA Safety, Inc

Affilliation: MSA Safety, Inc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 02 09:02:41 EST 2014

Committee Statement

Resolution: FR-52-NFPA 1801-2015

Statement: The technical committee is providing a correction as to the number of required samples

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

77 of 96 9/25/2015 3:03 PM

Page 79: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 70-NFPA 1801-2015 [ Section No. 8.6.3.5 ]

8.6.3.5

Manufacturers shall be permitted to optimally focus specimens to a distance of 1 m for this test.

Statement of Problem and Substantiation for Public Input

All samples should be focused at 1 meter for test methods.

Submitter Information Verification

Submitter Full Name: JOHN MORRIS

Organization: ISG INFRASYS

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 02 08:58:49 EDT 2015

Committee Statement

Resolution: FR-53-NFPA 1801-2015

Statement: The technical committee believes that all samples should be focused at 1 meter for test methods.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

78 of 96 9/25/2015 3:03 PM

Page 80: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 38-NFPA 1801-2015 [ Section No. 8.7.3.1 ]

8.7.3.1

Samples Specimens for testing shall be complete viewing surfaces or minimum 50 mm × 50 mm (2 in. × 2 in.)identically coated and prepared coupons. thermal imagers.

Statement of Problem and Substantiation for Public Input

Specimens for heat and flame test are complete thermal imagers.

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 09:34:06 EST 2015

Committee Statement

Resolution: FR-54-NFPA 1801-2015

Statement: The technical committee is clarifying that specimens for heat and flame test are complete thermal imagers.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

79 of 96 9/25/2015 3:03 PM

Page 81: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 95-NFPA 1801-2015 [ Section No. 8.7.3.1 ]

8.7.3.1

Samples shall be complete viewing surfaces or minimum 50 mm × 50 mm (2 in . × 2 in.) identically coated andprepared coupons.

Statement of Problem and Substantiation for Public Input

Typographical error in cut and paste.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 11:31:52 EDT 2015

Committee Statement

Resolution: See FR 54.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

80 of 96 9/25/2015 3:03 PM

Page 82: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 39-NFPA 1801-2015 [ Section No. 8.10.4.5 ]

8.10.4.5

The visible spectrum camera shall be a Nikon D3 as specified in 8.10 1 .4.7.

Statement of Problem and Substantiation for Public Input

Correction of reference.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 40-NFPA 1801-2015 [Section No. 8.10.4.6]

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 10:56:40 EST 2015

Committee Statement

Resolution: FR-55-NFPA 1801-2015

Statement: The technical committee is providing a reference correction.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

81 of 96 9/25/2015 3:03 PM

Page 83: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 40-NFPA 1801-2015 [ Section No. 8.10.4.6 ]

8.10.4.6

The visible spectrum camera shall be mounted as specified in 8.10 1 .4.8 such that the thermal imager displayfills 90 percent of the FOV in the vertical dimension and is in focus.

Statement of Problem and Substantiation for Public Input

Correction of reference.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 39-NFPA 1801-2015 [Section No. 8.10.4.5] Similar error

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 10:58:19 EST 2015

Committee Statement

Resolution: FR-56-NFPA 1801-2015

Statement: The technical committee is providing a reference correction.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

82 of 96 9/25/2015 3:03 PM

Page 84: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 87-NFPA 1801-2015 [ Section No. 8.11.5.4 ]

8.11.5.4

The rotary stage shall be turned to a position in which a distinct point on the thermal target is positioned at thecenter of the extreme left edge of furthest left active image element of the thermal imager FOV. The angularposition, AH1, of the rotary stage shall be recorded.

Statement of Problem and Substantiation for Public Input

Clarification on measurement technique, particularly in respect of icons near to the edge of the screen.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 88-NFPA 1801-2015 [Section No. 8.11.5.5]

Public Input No. 89-NFPA 1801-2015 [Section No. 8.11.6.4]

Public Input No. 90-NFPA 1801-2015 [Section No. 8.11.6.5]

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 10:32:14 EDT 2015

Committee Statement

Resolution: FR-57-NFPA 1801-2015

Statement: The technical committee is providing a clarification of the measurement technique, particularly with respectto icons near to the edge of the screen.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

83 of 96 9/25/2015 3:03 PM

Page 85: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 88-NFPA 1801-2015 [ Section No. 8.11.5.5 ]

8.11.5.5

The rotary stage shall be turned to a position in which the same distinct point on the thermal target is positioned atthe center of the extreme right edge of furthest right active image element of the thermal imager FOV. Theangular position, AH2, of the rotary stage shall be recorded.

Statement of Problem and Substantiation for Public Input

Clarification on measurement technique, particularly in respect of icons near to the edge of the screen.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 87-NFPA 1801-2015 [Section No. 8.11.5.4]

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 10:37:12 EDT 2015

Committee Statement

Resolution: FR-58-NFPA 1801-2015

Statement: The technical committee is providing a clarification of the measurement technique, particularly with respectto icons near to the edge of the screen.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

84 of 96 9/25/2015 3:03 PM

Page 86: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 89-NFPA 1801-2015 [ Section No. 8.11.6.4 ]

8.11.6.4

The rotary stage shall be turned to a position in which a distinct point on the thermal target is positioned at thecenter of the extreme bottom edge the furthest bottom active image element of the thermal imager FOV. Theangular position, AV1, of the rotary stage shall be recorded.

Statement of Problem and Substantiation for Public Input

Clarification on measurement technique, particularly in respect of icons near to the edge of the screen.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 87-NFPA 1801-2015 [Section No. 8.11.5.4]

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 10:39:28 EDT 2015

Committee Statement

Resolution: FR-59-NFPA 1801-2015

Statement: The technical committee is providing a clarification of the measurement technique, particularly with respectto icons near to the edge of the screen.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

85 of 96 9/25/2015 3:03 PM

Page 87: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 90-NFPA 1801-2015 [ Section No. 8.11.6.5 ]

8.11.6.5

The rotary stage shall be turned to a position in which the same distinct point on the thermal target is positioned atthe center of the extreme top edge the furthest top active image element of the thermal imager FOV. Theangular position, AV2, of the rotary stage shall be recorded.

Statement of Problem and Substantiation for Public Input

Clarification on measurement technique, particularly in respect of icons near to the edge of the screen.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 87-NFPA 1801-2015 [Section No. 8.11.5.4]

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 10:41:50 EDT 2015

Committee Statement

Resolution: FR-60-NFPA 1801-2015

Statement: The technical committee is providing a clarification of the measurement technique, particularly with respectto icons near to the edge of the screen.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

86 of 96 9/25/2015 3:03 PM

Page 88: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 86-NFPA 1801-2015 [ Section No. 8.11.6.6 ]

8.11.6.6

The horizontal The vertical FOV is the absolute value of the difference between AV2 and AV1.

Statement of Problem and Substantiation for Public Input

Typographical error in cut and paste from previous section.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 10:28:47 EDT 2015

Committee Statement

Resolution: FR-61-NFPA 1801-2015

Statement: The technical committee is providing the editorial correction of an error in copying text from previoussection.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

87 of 96 9/25/2015 3:03 PM

Page 89: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 41-NFPA 1801-2015 [ Section No. 8.12.4.5 ]

8.12.4.5

The temperature accuracy of the emitting surfaces shall be 0.02°C (32°F 0.04°F ) or better. The stability of theemitting surface temperatures shall be 0.01°C (32°F 0.04°F ) or better.

Statement of Problem and Substantiation for Public Input

Error in Celsius / Fahrenheit conversion corrected

Submitter Information Verification

Submitter Full Name: BERND SPELLENBERG

Organization: DRAEGER SAFETY AG & CO KGAA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 25 11:00:33 EST 2015

Committee Statement

Resolution: FR-62-NFPA 1801-2015

Statement: The technical committee is providing a correction to a temperature conversion error.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

88 of 96 9/25/2015 3:03 PM

Page 90: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 28-NFPA 1801-2014 [ Section No. 8.13.5 ]

8.13.5 Procedure 1.

8.13.5.1

The pre-test image recognition values in the vertical and horizontal directions shall be recorded as specified inSection 8.1, Image Recognition Test.

8.13.5.2

The test specimen shall be placed in the environmental conditioning test chamber that has been stabilized at49°C, +3°/-0°C (120°F, +5°/-0°F).

8.13.5.3

After 6 hours, the temperature shall be raised within 1 hour to 60°C, + 3°/-0°C (140°F, + 5°/-0°F) and maintainedfor 4 hours.

8.13.5.4

The temperature shall then be decreased within 1 hour to 49°C, +3°/-0°C (120°F, +5°/-0°F).

8.13.5.5

This cycle shall be repeated twice.

8.13.5.6

After the second cycle, the temperature shall be raised to 60°C, +3°/-0°C (140°F, +5°/-0°F) for 4 hours.

8.13.5. 7

The test specimen shall be removed following the conditioning specified in 8.13.5.2, and within 30 seconds thespecimens shall be immersed in the water dunk container containing the de-ionized water for 30 minutes, + 5/-0minutes.

8.13.5.7.1

The test specimens shall be removed from the water dunk container, wiped dry, and placed in the environmentalconditioning test chamber that has been stabilized at -20°C, + 3°/-0°C (-4°F, + 5°/-0°F) and maintained for aminimum of 4 hours.

8.13.5.7.2

Following the 4-hour conditioning of the test specimen at -20°C (-4°F), the test specimen shall be removed fromthe environmental conditioning test chamber and within 30 seconds shall be re-immersed in the water dunkcontainer for 30 minutes, + 5/-0 minutes.

8.13.5.8

The test specimens shall be removed from the water dunk container, wiped dry, and placed in the tumble testapparatus. Only one specimen shall be tested in the tumble test apparatus at a time. All specimens shall beunrestrained.

8.13.5.8.1

The tumble test apparatus shall be run at a speed of 15 rpm ± 1 rpm.

8.13.5.8.2

The test shall be run for 30 minutes, + 5/-0 minutes.

8.13.5.8.3

Upon completion of the test duration, the specimens shall be immersed in the water dunk container for 30minutes, + 5/-0 minutes.

8.13.5.8.4

The test specimens shall be blown dry with clean compressed air or nitrogen until the lens and viewing windowsare free from all moisture. Evaluation of the three specimens shall begin within 5 minutes of completion of drying.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

89 of 96 9/25/2015 3:03 PM

Page 91: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

8.13.5.8.5

The specimens shall be evaluated for post-test image as specified in Section 8.1, Image Recognition Test, andthe post-test image recognition values in the vertical and horizontal directions shall be recorded.

8.13.5.8.6

One test specimen shall be selected at random, and its electronics compartment shall be opened and checked forwater leakage.

Statement of Problem and Substantiation for Public Input

Cycling the temperature between 49C and 60C is not creating enough of a temperature differential to truly test the product. In addition, the long dwell times and multiple cycles make the test very difficult to run from a practical perspective. The test cannot be completed in a work day.The 60C soak at 4 hours provides more than ample time for the camera to come to equilibrium and provides the desired temperature stress.

Submitter Information Verification

Submitter Full Name: Craig Gestler

Organization: MSA Safety, Inc

Affilliation: MSA Safety, Inc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 02 09:19:11 EST 2014

Committee Statement

Resolution: FR-63-NFPA 1801-2015

Statement: The technical committee believes that cycling the temperature between 49C and 60C is not creating enoughof a temperature differential to truly test the product. In addition, the long dwell times and multiple cyclesmake the test very difficult to run from a practical perspective. The test cannot be completed in a work day.

The 60C soak at 4 hours provides more than ample time for the camera to come to equilibrium and providesthe desired temperature stress.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

90 of 96 9/25/2015 3:03 PM

Page 92: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 74-NFPA 1801-2015 [ Sections 8.13.5.1, 8.13.5.2, 8.13.5.3, 8.13.5.4, 8.13.5.5,

... ]

Sections 8.13.5.1, 8.13.5.2, 8.13.5.3, 8.13.5.4, 8.13.5.5, 8.13.5.6

8.13.5.1

The pre-test image recognition values in the vertical and horizontal directions shall be recorded as specified inSection 8.1, Image Recognition Test.

8.13.5.2

The test specimen shall be placed in the environmental conditioning test chamber that has been stabilized at49°C, + 3°/-0°C (120°F, + 5°/-0°F) and maintained for 4 hours .

8.13.5.3

After 6 hours, the The temperature shall then be raised within 1 hour to 60°C, + 3°/-0°C (140°F, + 5°/-0°F) andmaintained for 4 hours.

8.13.5.4

The temperature shall then be decreased within 1 hour to 49°C, + 3°/-0°C (120°F, + 5°/-0°F) and maintained for4 hours .

8.13.5.5

This cycle shall be repeated twice The temperature shell then be raised within 1 hour to 60C, 3/-0C (140F 5/-0F)and maintained for 4 hours .

8.13.5.6

After the second cycle, the The temperature shall then be raised to 60°C, + decreased within 1 hour to 49°C,3°/-0°C (140°F 120°F, + 5°/-0°F) and maintained for 4 hours.

Statement of Problem and Substantiation for Public Input

Clarifying wording.

Submitter Information Verification

Submitter Full Name: JOHN MORRIS

Organization: ISG INFRASYS

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 02 10:46:08 EDT 2015

Committee Statement

Resolution: See FR 63,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 96 9/25/2015 3:03 PM

Page 93: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 20-NFPA 1801-2014 [ Section No. 8.13.7.4 ]

8.13.7.4

The second random test specimen shall be deactivated and the any power supply compartment(s) and externalpower supplies shall be opened and inspected for water leakage.

Statement of Problem and Substantiation for Public Input

Change text to be consistent with section 8.13.8.2 and 8.13.8.3.

Submitter Information Verification

Submitter Full Name: James Rose

Organization: Safety Equipment Institute

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 24 14:17:52 EST 2014

Committee Statement

Resolution: FR-64-NFPA 1801-2015

Statement: The technical committee is providing this change for consistency with section 8.13.8.2 and 8.13.8.3.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

92 of 96 9/25/2015 3:03 PM

Page 94: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 52-NFPA 1801-2015 [ New Section after A.3.3.20 ]

TITLE OF NEW CONTENT

A.4.1.7 Listing of thermal imagers as Nonincendive equipment to ANSI/ISA-12.12.01 shall involve a combination ofClass I, Division 2 explosion protection techniques and Class II, Division 2 explsoion protection techniques. Regarding Class I, Division 2 explosion protection techniques, this can involve one or more of the following:

(1) hermetically sealed device - a device that is sealed against the entrance of an external atmosphere and inwhi ch the seal is made by fusion; e.g., soldering, brazing, welding, or the fusion of glass to metal.

(2) non-sparking device - device constructed to minimize the risk of occurrence of arcs or sparks capable ofcreating an ignition hazard during conditions of normal operation

(3) nonincendive circuit - a circuit, other than nonincendive field wiring, in which any arc or thermal effectproduced under normal operating conditions, is not capable of igniting the flammable gas-, vapor-, dust-airmixture, fibers or flyings. The circuit is evaluated under prescribed test conditions.

(4) nonincendive component - a component having contacts for making or breaking an incendive circuit and thecontacting mechanism is constructed so that the component , under normal operating conditions, is notcapable of igniting the flammable gas or vapor -air mixture. The housing of a nonincendive component isnot intended to exclude the flammable atmosphere or contain an explosion. The component is evaluatedunder prescribed test conditions.

(5) sealed device - a device so constructed that it cannot be opened during normal operational conditions oroperational maintenance; it is sealed to restrict entry of an external atmosphere.

Regarding Class II, Division 2 explosion protection techniques, this can involve one or more of the following:

(1) dust-tight - enclosures constructed so that dust will not enter under specified test conditions.

(2) hermetically sealed device - a device that is sealed against t he entrance of an external atmosphere and inwhi ch the seal is made by fusion; e.g., soldering, brazing, welding, or the fusion of glass to metal.

(3) nonincendive circuit - a circuit, other than nonincendive field wiring, in which any arc or thermal effectproduced under normal operating conditions, is not capable of igniting the flammable gas-, vapor-, dust-airmixture, fibers or flyings. The circuit is evaluated under prescribed test conditions.

(4) sealed device - a device so constructed that it cannot be opened during normal operational conditions oroperational maintenance; it is sealed to restrict entry of an external atmosphere.

Statement of Problem and Substantiation for Public Input

To help with the understanding of what listing to ANSI/ISA-12.12.01 involves, some explanatory details would be helpful.

Submitter Information Verification

Submitter Full Name: PAUL KELLY

Organization: UNDERWRITERS LABORATORIES INC

Affilliation: UNDERWRITERS LABORATORIES INC

Street Address:

City:

State:

Zip:

Submittal Date: Sun Jun 14 09:52:17 EDT 2015

Committee Statement

Resolution: The TC did not accept the Public Input, but appointed a task group to continue to investigate the issue andprovide Public Comments.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

93 of 96 9/25/2015 3:03 PM

Page 95: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 91-NFPA 1801-2015 [ Section No. A.6.1.2 ]

A.6.1.2

All power sources consisting of battery cells and battery packs should be evaluated by a national recognizedtesting laboratory (NRTL) in accordance with the regulations outlined in UL 1642, Standard for Lithium Batteries,or UL 2054, Standard for Household and Commercial Batteries, or both. IEC62133 Safety requirements forportable sealed secondary cells, and for batteries made from them, for use in portable applications

Statement of Problem and Substantiation for Public Input

New International Safety Standard for batteries, equivalent to UL1642. Many Cell manufactures will only obtain one listing.

Submitter Information Verification

Submitter Full Name: JON TURNER

Organization: E2V LTD

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 06 10:49:02 EDT 2015

Committee Statement

Resolution: See FR 18.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

94 of 96 9/25/2015 3:03 PM

Page 96: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 4-NFPA 1801-2014 [ Chapter B ]

Annex B Informational References

B.1 Referenced Publications.

The documents or portions thereof listed in this annex are referenced within the informational sections of thisstandard and are not part of the requirements of this document unless also listed in Chapter 2 for other reasons.

B.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 5000 ®, Building Construction and Safety Code ®, 2012 edition 2015 .

B.1.2 Other Publications.

B.1.2.1 JEDEC Publications.

Joint Electron Devices Engineering Council, 3103 North 10th Street, Suite 240–S, Arlington, VA 22201.

JEP131A, Potential Failure Mode and Effects Analysis (FMEA), 2005.

B.1.2.2 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

UL 1642, Standard for Lithium Batteries, 2005, Revised 2009 2013 .

UL 2054, Standard for Household and Commercial Batteries, 2004, Revised 2009 2011 .

B.2 Informational References.

(Reserved)

B.3 References for Extracts in Informational Sections.

(Reserved)

Statement of Problem and Substantiation for Public Input

Referenced current editions.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 3-NFPA 1801-2014 [Chapter 2] Referenced current editions.

Submitter Information Verification

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sat Jun 28 00:59:28 EDT 2014

Committee Statement

Resolution: FR-41-NFPA 1801-2015

Statement: Referenced current editions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

95 of 96 9/25/2015 3:03 PM

Page 97: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Public Input No. 51-NFPA 1801-2015 [ New Section after B.3 ]

Annex X Explosion Protection Requirements for Electronic Safety Equipment

(See attached draft Annex:"NFPA_1801_Annex_on_Explosion_Protection_Requirements_for_Electronic_Safety_Equipment_(rev).doc")

Additional Proposed Changes

File Name Description Approved

NFPA_1801_Annex_on_Explosion_Protection_Requirements_for_Electronic_Safety_Equipment_rev_.doc

Annex on Explosion Protection Requirements for Electronic Safety Equipment

Statement of Problem and Substantiation for Public Input

This Annex is being proposed as a resource for informative material that can be referenced when determining the applicable explosion protection standard for electronic safety equipment.

Submitter Information Verification

Submitter Full Name: PAUL KELLY

Organization: UNDERWRITERS LABORATORIES INC

Affilliation: UNDERWRITERS LABORATORIES INC

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 05 12:26:14 EDT 2015

Committee Statement

Resolution: The TC did not accept the Public Input, but did appoint a task group to continue to review the issue andprovide Public Comment as may be required.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

96 of 96 9/25/2015 3:03 PM

Page 98: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Annex X Explosion Protection Requirements for Electronic Safety Equipment

This annex is not a part of the requirements of this NFPA document but is included for informational purposes only.

X.1 Introduction. This NFPA standard includes requirements that define the level of explosion protection necessary for the electronic safety equipment under the scope of the standard. .

These explosion protection requirements include a normative reference to an American National Standards Institute (ANSI) standard for a protection technique for hazardous (classified) locations as defined in the National Electrical Code (NEC), ANSI/NFPA 70.

Note: See Articles 500, 505 and 506 of the NEC for additional details.

X.2 Overview of Hazardous (Classified) Locations. According to the NEC, there are two systems under which hazardous locations can be classified – the Division system and the Zone system. Under either system, hazardous locations are classified based on the following attributes:

Type of explosive atmosphere

Likelihood that the type of explosive atmosphere is present when equipment is operating

Ignition-related properties of the type of explosive atmosphere

Maximum surface temperature of the equipment under operating conditions

Under the Division and Zone systems, the following are three types of explosive atmospheres in accordance with the NEC:

Class I: Flammable gases, flammable liquid–produced vapors, & combustible liquid–produced vapors.

Class II: Combustible dusts.

Class III: Ignitable fibers/flyings.

Note: The terms “Class II” and “Class III” are only used under the Division system as a means to designate these explosive atmospheres. These terms are not used under the Zone system. Under the Zone system, the Zone and Group designations noted below are used to designate explosive atmospheres that involve combustible dusts or ignitable fibers/flyings.

Under the Division system, the following are designations indicating the likelihood that the type of explosive atmosphere is present when equipment is operating:

Division 1: The explosive atmosphere can exist all of the time or some of the time under normal operating conditions.

Division 2: The explosive gas or dust atmosphere respectively is not likely to exist under normal operating conditions.

Under the Zone system, the following are designations indicating the likelihood that the type of explosive atmosphere is present when equipment is operating:

Zone 0 or Zone 20: The explosive gas or dust atmosphere respectively is present continuously or for long periods of time under normal operating conditions.

Zone 1 or Zone 21: The explosive gas or dust atmosphere respectively is likely to exist under normal operating conditions.

Zone 2 or Zone 22: The explosive gas or dust atmosphere respectively is not likely to exist under normal operating conditions.

Note: The likelihood that an explosive atmosphere is present based on a Division 1 designation is the same as the combination of a Zone 0 and a Zone 1 designation, or of a Zone 20 and a Zone 21 designation. The likelihood that an explosive atmosphere is present based on a Division 2 designation is the same as a Zone 2 or a Zone 22 designation.

Under the Division system, the following are designations indicating the ignition-related properties of Class I explosive gas atmospheres:

Group A: Acetylene explosive gas atmosphere.

Page 99: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Group B: Explosive gas atmosphere mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value less than or equal to 0.45 mm or a minimum igniting current ratio (MIC ratio) less than or equal to 0.40. The representative test gas for Group B is hydrogen.

Group C: Explosive gas atmosphere mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value greater than 0.45 mm and less than or equal to 0.75 mm, or a minimum igniting current ratio (MIC ratio) greater than 0.40 and less than or equal to 0.80. The representative test gas for Group C is ethylene.

Group D: Explosive gas atmosphere mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value greater than 0.75 mm or a minimum igniting current ratio (MIC ratio) greater than 0.80. The representative test gas for Group D is propane.

Under the Zone system, the following are designations indicating the ignition-related properties of Class I explosive gas atmosphere:

Group IIC: Explosive gas atmosphere containing acetylene, hydrogen, or flammable gas, flammable liquid–produced vapor, or combustible liquid–produced vapor mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value less than or equal to 0.50 mm or minimum igniting current ratio (MIC ratio) less than or equal to 0.45. The representative test gases for Group IIC are acetylene and hydrogen. Group IIC is equivalent to a combination of Group A and Group B.

Group IIB: Explosive gas atmosphere containing acetaldehyde, ethylene, or flammable gas, flammable liquid–produced vapor, or combustible liquid–produced vapor mixed with air that may burn or explode, having either maximum experimental safe gap (MESG) values greater than 0.50 mm and less than or equal to 0.90 mm or minimum igniting current ratio (MIC ratio) greater than 0.45 and less than or equal to 0.80. The representative test gas for Group IIB is ethylene. Group IIB is equivalent to Group C.

Group IIA: Explosive gas atmosphere containing acetone, ammonia, ethyl alcohol, gasoline, methane, propane, or flammable gas, flammable liquid–produced vapor, or combustible liquid–produced vapor mixed with air that may burn or explode, having either a maximum experimental safe gap (MESG) value greater than 0.90 mm or minimum igniting current ratio (MIC ratio) greater than 0.80. The representative test gas for Group IIA is propane. Group IIA is equivalent to Group D.

Note: Equipment marked “IIB” is suitable for applications requiring Group IIA equipment. Similarly, equipment marked “IIC” is suitable for applications requiring Group IIA and Group IIB equipment. When the electrical equipment is for use in a particular gas in addition to being suitable for use in a specific gas group, the chemical formula shall follow the group and be separated with the symbol “+”, for example, “IIB + H2”.

Under the Division system, the following are designations indicating the ignition-related properties of Class II explosive dust atmospheres:

Group E: Explosive dust atmosphere containing combustible metal dusts, including aluminum, magnesium, and their commercial alloys, or other combustible dusts whose particle size, abrasiveness, and conductivity present similar hazards in the use of electrical equipment. The representative test dust for Group E is magnesium dust.

Group F: Explosive dust atmosphere containing combustible carbonaceous dusts that have more than 8 percent total entrapped volatiles, or that have been sensitized by other materials so that they present an explosion hazard. Coal, carbon black, charcoal, and coke dusts are examples of carbonaceous dusts. The representative test dust for Group F is coal dust.

Group G: Explosive dust atmosphere containing combustible dusts not included in Group E or Group F, including flour, grain, wood, plastic, and chemicals. The representative test dust for Group G is grain dust.

Note: There are no group designations for Class III explosive atmospheres under the Division system.

Under the Zone system, the following are designations indicating the ignition-related properties of explosive dust atmospheres:

Group IIIC: Explosive dust atmosphere containing combustible metal dust. Group IIIC is equivalent to Group E.

Group IIIB: Explosive dust atmosphere containing other than combustible metal dust. Group IIIB is equivalent to Groups F and G.

Page 100: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Group IIIA: Explosive fibers/flyings atmosphere containing solid particles, including fibers, greater than 500 μm in nominal size, which may be suspended in air and could settle out of the atmosphere under their own weight. Group IIIA is equivalent to Class III.

Under the Division system, the following are the designations indicating the maximum surface temperature of the equipment under operating conditions:

Class I and II Class III

T1 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6

(≤ 450 °C) (≤ 300 °C) (≤ 280 °C) (≤ 260 °C) (≤ 230 °C) (≤ 215 °C) (≤ 200 °C) (≤ 180 °C) (≤ 165 °C) (≤ 160 °C) (≤ 135 °C) (≤ 120 °C)* (≤ 100 °C) (≤ 85 °C)

Limited to 165°C for equipment not subject to overloading

Limited to 120°C for equipment that may be overloaded

Under the Zone system, the following are the designations indicating the maximum surface temperature of the equipment under operating conditions:

Zone 0, 1 and 2 Zone 20, 21 and 22

T1 T2 T3 T4 T5 T6

(≤ 450 °C) (≤ 300 °C) (≤ 200 °C) (≤ 135 °C) (≤ 100 °C) (≤ 85 °C)

Equipment marked to show the operating temperature (maximum surface temperature)

X.3 Applicable Explosion Protection Techniques for Electronic Safety Equipment. Based on the portable, lighter-weight, solid-state, control-level nature of electronic safety equipment designs, the most applicable protection techniques as defined in the NEC are as follows:

Division system protection techniques for explosive gas & dust atmospheres

Intrinsic safety – For use in Class I, Division 1 and 2, Groups A, B, C and D, Class II, Division 1 and 2, Groups E, F and G, and Class III, Division 1 and 2 hazardous (classified) locations. The applicable ANSI standards for this protection technique are: ‒ ANSI/UL 913, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and

III, Division 1, Hazardous (Classified) Locations; or ‒ ANSI/TIA 4950-A, Requirements for Battery-Powered, Portable Land Mobile Radio Applications

in Class I, II, and III, Division 1, Hazardous (Classified) Locations.

Nonincendive equipment – For use in Class I, Division 2, Groups A, B, C and D, Class II, Division 2, Groups F and G, and Class III, Division 1 and 2 hazardous (classified) locations. The applicable ANSI standard for this protection technique is ANSI/ISA 12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations.

Zone system protection techniques for explosive gas and dust atmospheres

Intrinsic safety – For use in Class I, Zone 0, 1 and 2, Groups IIC, IIB and IIA and Zone 20, 21 and 22, Groups IIIC, IIIB and IIIA hazardous (classified) locations. The applicable ANSI standards for this protection technique are ‒ ANSI/UL 60079-11, Explosive Atmospheres - Part 11: Equipment Protection by Intrinsic Safety

"i"; and ‒ ANSI/UL 60079-0, Explosive Atmospheres - Part 0: Equipment - General Requirements.

Page 101: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

Encapsulation “m” – For use in Class I, Zone 1 and Zone 2, Groups IIC, IIB and IIA and Zone 20, 21 and 22, Groups IIIC, IIIB and IIIA hazardous (classified) locations. The applicable ANSI standards for this protection technique are: ‒ ANSI/UL 60079-18, Explosive Atmospheres - Part 18: Equipment Protection by Encapsulation

"m"; and ‒ ANSI/UL 60079-0, Explosive Atmospheres - Part 0: Equipment - General Requirements.

Zone system protection techniques for explosive gas atmospheres only

Type of protection “n” (Nonincendive equipment) – For use in Class I, Zone 2, Groups IIC, IIB and IIA hazardous (classified) locations only. The applicable ANSI standards for this protection technique are: ‒ ANSI/UL 60079-15, Explosive Atmospheres - Part 15: Equipment Protection by Type of

Protection "n"; and ‒ ANSI/UL 60079-0, Explosive Atmospheres - Part 0: Equipment - General Requirements.

Increased safety “e” – For use in Class I, Zone 1 and Zone 2, Groups IIC, IIB and IIA hazardous (classified) locations only. The applicable ANSI standards for this protection technique are: ‒ ANSI/UL 60079-7, Explosive Atmospheres- Part 7: Equipment Protection by Increased Safety

"e"; and ‒ ANSI/UL 60079-0, Explosive Atmospheres - Part 0: Equipment - General Requirements.

Zone system protection techniques for explosive dust atmospheres only Protection by enclosure “t” – For use in Zone 20, 21 and 22, Groups IIIC, IIIB and IIIA hazardous (classified) locations only. The applicable ANSI standards for this protection technique are: ‒ ANSI/ISA 60079-31, Explosive Atmospheres - Part 31: Equipment Dust Ignition Protection by

Enclosure "t"; and ‒ ANSI/UL 60079-0, Explosive Atmospheres - Part 0: Equipment - General Requirements.

X.4 Determining the Applicable ANSI Explosion Protection Standard. While there may be a common ANSI explosion protection standard referenced for most electronic safety equipment, there is not necessarily only one ANSI explosion protection standard that is always applicable to all electronic safety equipment.

This is because the use of electronic safety equipment in the field by emergency services personnel does not directly relate to any one hazardous (classified) location. For example:

As noted earlier in the Overview, hazardous locations are classified as defined by the NEC based on the likelihood that the type of explosive atmosphere is present when equipment is operating.

Division 1 classification is associated with atmospheres that can exist all of the time or some of the time under normal operating conditions. Division 2 classification is associated with atmospheres that are not likely to exist under normal operating conditions.

For most of the life of a piece of electronic safety equipment, it may reside in an unclassified location (such as in a fire house), but it is not being used in such locations.

When a piece of electronic safety equipment is used in the field, it is often used in unclassified locations, but due to an abnormal condition these unclassified locations either have an explosive atmosphere present or have the potential for an explosive atmosphere being present.

Therefore, for a significant portion of its operation and use in the field, electronic safety equipment may be exposed to explosive atmospheres or have the potential of being exposed to explosive atmospheres.

However, even when exposed to an explosive atmosphere in the field, electronic safety equipment is only exposed for a limited period of time for any one field event.

In addition, electronic safety equipment may be used in the field in actual hazardous (classified) locations.

Use of electronic safety equipment in such unclassified potentially explosive atmospheres has some similar characteristics to electronic equipment used in actual hazardous (classified) locations. However, while there are some similar characteristics, there are also dissimilar characteristics. Therefore, as noted above, a direct comparison to a specific hazardous (classified) location is not possible.

Therefore, since a direct comparison between electronic safety equipment used in unclassified potentially explosive atmospheres and general electronic equipment used in hazardous (classified) locations is not possible, the risk of explosion requirements should reflect the highest level of explosion protection possible in

Page 102: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

accordance with the NEC, while not adversely restricting the performance characteristics needed by emergency personnel.

The highest level of explosion protection, under either the Division or Zone systems, that could be applicable to electronic safety equipment is Division 1 or Zone 0 Intrinsic safety. Since the Division system is significantly more broadly used in the US in comparison to the Zone system, it is recommended that the initial consideration of the applicable ANSI explosion protection standard begin with ANSI/UL 913 or ANSI/TIA 4950-A. However, after this initial consideration, additional consideration is necessary regarding whether or not any Division 1 Intrinsic safety requirements will adversely restrict the performance characteristics needed by emergency personnel.

For example, Division 1 Intrinsic safety requirements are more restrictive regarding available power from a battery than Division 2 Nonincendive requirements. Therefore, if such a restriction regarding power from a battery could adversely restrict necessary performance characteristics, then ANSI/ISA-12.12.01 would provide the highest level of explosion protection possible in accordance with the NEC, while not adversely restricting the performance characteristics needed by emergency personnel.

As another example, later editions of ANSI/UL 913 (such as the 8th edition) include restrictions on continuous transmission power, while ANSI/TIA 4950-A and earlier editions of ANSI/UL 913 (such as the 5th edition) do not. Therefore, if such a restriction regarding transmission power could adversely restrict necessary performance characteristics, then ANSI/TIA 4950 or earlier editions of ANSI/UL 913 would provide the highest level of explosion protection possible in accordance with the NEC, while not adversely restricting the performance characteristics needed by emergency personnel.

Electronic safety equipment should be regularly subjected to such a consideration regarding explosion protection requirements versus necessary performance characteristics, with a different determination regarding the applicable ANSI explosion protection standard being reasonably possible based on technological advances in electronic safety equipment.

If the above Annex X is accepted, consideration should be given to adding the following standards to Chapter 2 (or maybe creating a referenced publications section under this Annex):

‒ ANSI/UL 913, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III, Division 1, Hazardous (Classified) Locations

‒ ANSI/TIA 4950-A, Requirements for Battery-Powered, Portable Land Mobile Radio Applications in Class I, II, and III, Division 1, Hazardous (Classified) Locations

‒ ANSI/UL 60079-0, Explosive Atmospheres - Part 0: Equipment - General Requirements ‒ ANSI/UL 60079-7, Explosive Atmospheres- Part 7: Equipment Protection by Increased Safety "e" ‒ ANSI/UL 60079-11, Explosive Atmospheres - Part 11: Equipment Protection by Intrinsic Safety "i" ‒ ANSI/UL 60079-15, Explosive Atmospheres - Part 15: Equipment Protection by Type of Protection "n" ‒ ANSI/UL 60079-18, Explosive Atmospheres - Part 18: Equipment Protection by Encapsulation "m" ‒ ANSI/ISA 60079-31, Explosive Atmospheres - Part 31: Equipment Dust Ignition Protection by Enclosure

"t"

Also, if the above Annex X is accepted, consideration should be given to adding the following definition to Chapter 3 (or maybe creating a definitions section under this Annex):

‒ Intrinsic safety – Type of protection where any spark or thermal effect is incapable of causing ignition of a mixture of flammable or combustible material in air under prescribed test conditions.

‒ Nonincendive equipment – type of protection where equipment having electrical/electronic circuitry is incapable, under normal operating conditions, of causing ignition of a specified flammable gas–air, vapor–air, or dust–air mixture due to arcing or thermal means.

‒ Encapsulation “m” – Type of protection where electrical parts that could ignite an explosive atmosphere by either sparking or heating are enclosed in a compound in such a way that this explosive atmosphere cannot be ignited.

‒ Increased safety “e” – Type of protection applied to electrical equipment that does not produce arcs or sparks in normal service and under specified abnormal conditions, in which additional measures are

Page 103: which are specified in NFPA 1408, Standard for Training ......ANSI/ISA-12.12.01, Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1

applied so as to give increased security against the possibility of excessive temperatures and of the occurrence of arcs and sparks.

‒ Protection by enclosure “t” – Type of protection for explosive dust atmospheres where electrical apparatus is provided with an enclosure providing dust ingress protection and a means to limit surface temperatures.