Where there is no design

Embed Size (px)

Citation preview

  • 7/25/2019 Where there is no design

    1/1

    This document is the property of TOTAL UPSTREAM NIGERIA LIMITED. It must not be stored, reproduced or disclosed to othe rs without written authorisation from the Company.

    NG-EGN-13-KSEC-112001_rev01_ BD - Ahmad.doc

    Doc. Ref.: NG-EGN-13-KSEC-112001

    Egina FPSO Topsides Detailed Design

    RELIEF AND BLOWDOWN

    PHILOSOPHY

    CTR Reference: NA

    Revision: 01 Rev Date : 26 Feb2014

    Discipline : PRO Document Type : PHI

    Phase: DESystem / Subsystem :

    SSEquipment Type :

    NAStatus: IFA Class: 1 Page 29 of 51

    Figure 6.1 Inlet Pressure Drop Calculations

    Calculate P

    from this point

    Flare

    Calculate P

    from this pointCalculate P

    from this point

    High

    Rating

    Low

    Rating

    Refer to [Ref. 3, Section 7.3] for more details on PSV inlet pipe sizing and design.

    6.8 Relief Valve Discharge Piping

    The discharge line nominal diameter shall not be less than the nominal diameter of the PSV outlet flange.

    When two or more PSVs in the same service (i.e. valves are operating in a 2 x 50% configuration) are

    manifolded together into a common discharge line, the cross-sectional area of the common discharge line

    should not be less than the sum of the cross sectional flow areas of the outlet flanges of the PSVs

    discharging into it.

    The discharge piping for each individual PSV shall be sized using the PSV rated relief rate for all

    contingencies. This sizing basis also applies to any manifold that collects the discharge from two or more

    PSVs in the same service. In the case of modulating pilot-operated PSVs, use required relief rate and not

    PSV rated relief rate (refer Table 12 in section 8.3.1 herein).

    All PSV discharge piping and headers shall be rigorously checked and sized using Aspen Flare System

    Analyzer and in accordance with [Ref. 3, Section 7.3].

    Where modulating PSVs are installed, the relief flow will be regulated and the discharge piping may be sized

    using the calculated relief rate rather than the rated relief rate.

    The actual back pressure at the PSV outlet must be consistent with back pressure limitations, and withflange / piping rating.

    Discharge piping for PSVs (including relief headers) discharging to a closed system shall be installed to

    continuously slope downward towards the flare KO drum. Refer section 8.2 for slope details.

    If water may be present, the risk of ice or hydrate formation shall be assessed.

    A pipe roughness of 460 m (for carbon steel) and 46 m (for stainless steel) shall be used in pressure drop

    calculations for all PSV outlet lines and headers; this assumes heavily corroded service.