What is Insulation Coordination

Embed Size (px)

Citation preview

  • 8/12/2019 What is Insulation Coordination

    1/5

    What is Insulation Coordination?

    Insulation Coordination is the process of determining the proper insulation levels of various

    components in a power system as well as their arrangements. It is the selection of an

    insulation structure that will withstand voltage stresses to which the system, or equipment

    will be subjected to, together with the proper surge arrester. The process is determined fromthe known characteristics of voltage surges and the characteristics of surge arresters.

    Some common terms that must be known when performing an Insulation

    Coordination Study.

    1. Basic Impulse Insulation Level (BIL)

    This is the reference insulation level expressed as an impulse crest (or peak) voltage with a

    standard wave not longer than a 1.2 x 50 microsecond wave.

    A 1.2 x 50 microsecond wave means that the impulse takes 1.2 microseconds to reach the

    peak and then decays to 50% of the peak in 50 microseconds. (Clickherefor a figure of the

    BIL waveform)

    2. Withstand Voltage

    This is the BIL level that can repeatedly be applied to an equipment without flashover,

    disruptive charge or other electrical failure under test conditions.

    3. Chopped Wave Insulation Level

    This is determined by using impulse waves that are of the same shape as that of the BIL

    waveform, with the exception that the wave is chopped after 3 microseconds. Generally, it is

    assumed that the Chopped Wave Level is 1.15 times the BIL level for oil filled equipment

    such as transformers. However, for dry type equipment, it is assumed that the the Chopped

    Wave Level is equal to the BIL level.

    4. Critical Flashover Voltage

    This is the peak voltage for a 50% probability of flashover or disruptive charge.

    5. Impulses Ratio

    This is normally used for Flashover or puncture of insulation. It is the ratio of the impulse

    peak voltage to the value of the 60 Hz voltage that causes flashover or puncture. Or, it is the

    ratio of breakdown voltage at surge frequency to breakdown voltage at normal system

    frequency (60 Hz).

    http://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/Figure1.JPGhttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/Figure1.JPGhttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/Figure1.JPGhttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/Figure1.JPG
  • 8/12/2019 What is Insulation Coordination

    2/5

    Overvoltages that need to be considered when doing an Insulation

    Coordination Study.

    There are three types of overvoltages that may occur on a plant:

    Internal Overvoltages Switching Surges External Overvoltages

    1. Internal Overvoltages

    These may usually be short power frequency overvoltages or weakly damped oscillatory

    voltages. The main causes of these overvoltages are:

    Phase to Earth Faults: Single line to Ground, Double line to Ground, 3 Phase toGround.

    Load Rejection. Ferro Resonance. Ferranti Effect.

    2. Switching Surges

    These surges are of short duration, irregular (or impulse form) and highly damped. The

    effects of such overvoltages are of great concern when the transmission voltage is greater

    than 300kV. However, below 300kV, some causes of these overvoltages are:

    Resonance effects when switching transformer feeders, or cables and overhead lines. Ferro resonance encountered on transformer feeder double circuits, when one circuit

    is switched out but the other parallel feeder remains energised.

    Line energisation may cause switching surges especially at the remote end of the linethat is being energised.

    3. External Overvoltages

    Power systems that operate below 145kV (example the T&TEC system) overvoltages due tolightning are of greater concern than the previous two types of overvoltages. Lightning

    discharges are usually very short, unidirectional and have a shape similar to the BIL

    waveform.

    The point of insulation flashover depends on

    (i) Geographical position of the lightning stroke

    (ii) Magnitude of the stroke

    (iii) Rise time of voltage wave

    (iv) System insulation levels

    (v) System Electrical characteristics

    (vi) Local atmospheric or ambient conditions

  • 8/12/2019 What is Insulation Coordination

    3/5

    Overvoltage Surge Protection

    There are two methods of overvoltage protection:

    1. Rod or Spark Gaps

    These devices are easy and cheap to install and are usually installed in parallel with insulators

    between the live equipment terminal and earth. Some disadvantages of these devices include:

    When they operate, they cause a short circuit fault, which may cause protection tooperate and isolate the equipment.

    The sudden reduction in the voltage during operation causes high stresses on theTransformer interturn insulation.

    The breakdown of plant insulation varies with the duration of the overvoltage. At lower voltages, where short distance gaps are used, maloperation may occur due to

    debris being deposited on the terminals of the gaps.

    2. Surge Arresters

    Modern Surge arresters are of the gapless Zinc Oxide type. Previously, Silicon Carbide

    arresters were used, but their use has been superceeded by the ZnO arresters, which have a

    non-linear resistance characteristic. Thus, it is possible to eliminate the series gaps between

    the individual ZnO block making up the arrester.

    Selection Procedure for Surge arresters

    1. Determine the continuous arrester voltage. This is usually the system rated voltage.

    2. Select a rated voltage for the arrester.

    3. Determine the normal lightning discharge current. Below 36kV, 5kA rated arresters are

    chosen. Otherwise, a 10kA

    rated arrester is used.

    4. Determine the required long duration discharge capability.

    For rated voltage < 36kV, light duty surge arrester may be specified.

    For rated voltage between 36kV and 245kV, heavy duty arresters may be specified.

    For rated voltage >245kV, long duration discharge capabilities may be specified.

    5. Determine the maximum prospective fault current and protection tripping times at the

    location of the surge arresterand match with the surge arrester duty.

    6. Select the surge arrester having porcelain creepage distance in accordance with the

    environmental conditions.

    7. Determine the surge arrester protection level and match with standard IEC 99

    recommendations.

    Some Common ratings associated with surge arresters

    1. Rated Voltage

  • 8/12/2019 What is Insulation Coordination

    4/5

    The power frequency voltage across the arrester must never exceed its rated voltage,

    otherwise the arrester may not reseal and may catastrophically fail after absorbing the energy

    of the surge.

    For effectively earthed system:

    Maximum phase to earth voltage = 80% maximum line voltage

    2. Rated Current

    Arresters are tested with 8/20 microsecond discharge current waves of varying magnitudes.

    3. Normal Voltage

    Nominal continuous voltage that the arrester can with stand before failing or flashover.

    4. BIL

    Basic Impulse Insulation Level which is the maximum impulse for a 1.2 x 50 microsecond

    waveform.

    5. Discharge voltage

    When the overvoltage impulse reaches this value, the arrester begins to channel energy to

    earth.

    This system shows a 132kV incoming feeder, which is connected to a 132/66kV transformer

    at the substation. The arrester is place between the feeder and the transformer.

    It should be noted that the rating of the arrester is 120kV. Since the system is 132kV, and a

    tolerance of 10% is assumed, then the maximum voltage that the system can experience is

    132kV * 1.1 = 145200V.

    However, the system is effectively earthed (via the arrester) and for an effectively earthed

    system, the maximum arrester voltage is 80% of the system voltage. Thus,

    Normal Arrester voltage = 145200 * 0.8 = 120000 = 120kV.

    If a lightning strike occurs on the incoming feeder, three scenarios are possible.

    1st Scenario: Impulse voltage of lightning strike is less than the Discharge Voltageof the Arrester

    In this case, the lightning strike impulse never exceeds 350kV. The traveling impulse wave passes into the substation. Since the BIL of the transformer is much greater than the peak voltage magnitude of

    the lightning impulse, the transformer is not damaged.

  • 8/12/2019 What is Insulation Coordination

    5/5

    2nd Scenario: Impulse Voltage of lightning strike is less than BIL of arrester, but

    greater than Discharge Voltage

    In this case, the lightning strike peak voltage is such that 350kV < Vpeak < 650kV. Assume that the impulse is 600kV as shownhere. As the magnitude of the traveling impulse rises to 350kV, as it moves to the arrester,

    discharge begins to take place.

    The wave is clipped at 350kV as shownhere. This clipped wave passes to the substation and since the BIL of the transformer is

    greater than 350kV, the transformer is not damaged.

    The balance of energy (600 - 350 = 250kV worth of energy) is discharged to ground.3rd Scenario: Impulse Voltage of lightning strike is greater than the BIL of arrester

    In this case, the lightning strike peak voltage is greater than 650kV.

    Since the peak voltage is greater than he BIL of the incoming feeder and the arrester,both are damaged.

    The arrester experiences flashover or disruptive charge and is destroyed. Since it is destroyed, and open circuit occurs between the incoming feeder and the

    transformer.

    None of the lightning impulse therefore reaches the transformer at the substation. The transformer therefore remains undamaged.

    http://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/600kV.jpghttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/600kV.jpghttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/350kV.jpghttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/350kV.jpghttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/350kV.jpghttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/350kV.jpghttp://www.eng.uwi.tt/depts/elec/staff/alvin/ee35t/notes/600kV.jpg