Westaflex Australia Pty. Ltd. Airflow and Acoustic Research and Development Study of various Air Outlets This Laboratory is accredited by the National Association of Testing Authorities, Australia. The results reported herein have been determined in accordance with the terms of accreditation, and shall not be reproduced except in full. NOISE N.A.T.A. Report No. 302990-1 Prepared by Vipac Engineers & Scientists Ltd August, 2001

Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd.

Airflow and Acoustic Research and Development Study

of various Air Outlets

This Laboratory is accredited by the National Association of Testing Authorities, Australia. The results reported herein have been determined in accordance with the terms of accreditation, and shall not be reproduced except in full.

NOISE

N.A.T.A. Report No. 302990-1

Prepared by Vipac Engineers & Scientists Ltd

August, 2001

Page 2: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 2 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Page 3: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 3 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

DOCUMENT CONTROL FORM

Airflow And Acoustic Research And Development Study of various Air Outlets

FILE: REPORT CODE: GT302990-1.doc MA 77 PREPARED FOR: PREPARED BY: Westaflex Australia Pty. Ltd. Vipac Engineers & Scientists Ltd., 140-152 Bamfield Road Victorian Technology Centre,

Heidelberg West 275 Normanby Road, Victoria, Australia 3081 Port Melbourne VIC. 3207

AUSTRALIA Contact: Mr Paul Sterling Phone: (03) 9458 2122 Phone: (03) 9647-9700 Fax: (03) 9457 6271 Fax: (03) 9646-4370

AUTHOR: ..................................................................................... Greg Theodoridis Date: Project Engineer REVIEWED BY: ..................................................................................... Norm Broner Date: N.A.T.A. Signatory REVISION HISTORY:

Issue No. Date Issued Reason/Comments 0 August, 2001 Original

DISTRIBUTION:

This is Copy No.___ Issue No. Location 1 0 Client 2 0 Project File 3 0 Vipac Melbourne Library

KEY WORDS: Noise, Airflow, Diffuser

Page 4: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 4 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TABLE OF CONTENTS

DOCUMENT CONTROL FORM................................................................................................................................................3

1.0 INTRODUCTION.....................................................................................................................................................5

2.0 UNITS UNDER TEST...............................................................................................................................................5

3.0 TEST CONDITIONS AND APPLICABLE STANDARDS...............................................................................7

4.0 TEST SET UP AND PROCEDURE........................................................................................................................8

5.0 INSTRUMENTATION...........................................................................................................................................23

6.0 ORDERS OF ACCURACY...................................................................................................................................23

7.0 RESULTS.................................................................................................................................................................24

Page 5: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 5 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

1.0 INTRODUCTION This report presents the results of acoustic and airflow development tests carried out on various air outlets supplied by Westaflex, as described below. This report is issued as a NATA certified report under the terms of Vipac's NATA accreditation No's 1163 and 1506.

2.0 UNITS UNDER TEST

Table 1 : Description of Units Under Test Measured Sizes (mm) # Unit Description Nominal Size Face Neck

1 Uni-Vent Fixed Blade 9” x 9” 280 x 280 213 x 213 2 Modular type plastic ceiling diffuser 12” x 12” 350 x 350 287 x 287 3 Tested in 4-way configuration 15” x 15” 425 x 425 361 x 361 4 Throw Pattern: 45° approx. 15” x 22” 359 x 536 425 x 604 5 Uni-Vent Adjustable Blade 9” x 9” 280 x 280 213 x 213 6 Modular type plastic ceiling diffuser 12” x 12” 350 x 350 287 x 287 7 Tested in 4-way configuration 15” x 15” 425 x 425 361 x 361 8 All blades move in unison

Throw Pattern: Horizontal and 45° *

15” x 22” 359 x 536 425 x 604

9 CD 2000 9” x 9” 310 x 310 210 x 210 10 4-way louver type plastic 12” x 12” 380 x 380 280 x 280 11 ceiling diffuser, bevelled edge

Throw Pattern: Horizontal 15” x 15” 465 x 465 360 x 360

12 As above, flush face 595 x 595mm 595 x 595 430 x 430 13 Aluminium 4-way louver type 9” x 9” 340 x 340 210 x 210 14 ceiling diffuser, bevelled edge 12” x 12” 415 x 415 285 x 285 15 Throw Pattern: Horizontal 15” x 15” 490 x 490 360 x 360 16 As above, flush face 595 x 595mm 595 x 595 440 x 440 17 Aluminium 3-way louver type 9” x 9” 345 x 345 210 x 210 18 ceiling diffuser, bevelled edge 12” x 12” 415 x 415 285 x 285 19 Throw Pattern: Horizontal 15” x 15” 490 x 490 355 x 355 20 UNIJET, Jet Centre Φ150mm Φ235 Φ145 21 Plastic round ceiling diffuser

Throw Pattern: Vertical Damper fully open

Φ200mm Φ285 Φ195

22 UNIJET, Cone Centre Φ150mm Φ215 Φ140 23 Plastic round ceiling diffuser Φ200mm Φ270 Φ190 24 Throw Pattern: Vertical

Tested at x = 0 & x = 20 cone settings Φ250mm Φ320 Φ240

25 Aluminium Double Deflection Wall 14” x 4” 390 x 140 335 x 85 26 Register 20” x 12” 540 x 340 490 x 285 27 Test setting: 0° deflection 20” x 20” 540 x 540 485 x 485 28 32” x 24” 835 x 655 790 x 610

*Note: Selected tests only performed at 45° setting for the Uni-Vent Adjustable Blade samples.

Page 6: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

As indicated above, the Uni-Vent adjustable blade samples were tested for horizontal and 45° throw patterns. The blade settings required to achieve these throw patterns are shown in Figure 1 below.

Figure 1: Uni-Vent Adjustable Blade, Blade Setting

The UNIJET Cone Centre samples were tested for two alternative cone settings, as shown in Figure 2 below.

Page 7: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 7 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Figure 2: UNIJET Cone Centre, Cone Setting

The Uni-Vent 15” x 22” size samples were tested in the 4 way throw configuration as indicated in Figure 3.

Figure 2: Uni-Vent 15” x 22”, Module Settings

3.0 TEST CONDITIONS AND APPLICABLE STANDARDS

The units were tested at a range of flow conditions, as shown on the Test Certificates. The test set up was in general accordance with Air Diffusion Council (USA) Equipment Test Code 1062: GRD-84. Measurements were taken in general accordance with the following standards: ACOUSTICS Australian Standard 1217.2-1985. "Acoustic - Determination of Sound Power Levels of Noise Sources Part 2 - Precision Methods for Broad-Band Sources in Reverberation Rooms". AIRFLOW Air Diffusion Council (USA) Equipment Test Code 1062: GRD-84. THROW & STATIC PRESSURE DROP Air Diffusion Council (USA) Equipment Test Code 1062: GRD-84.

Page 8: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 8 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

4.0 TEST SET UP AND PROCEDURE

Vipac's Reverberation Test Room has a volume of 170m3 has been qualified in accordance with the procedures in AS 1217.2 - 1985 for determination of sound power in octave bands with Centre Frequencies from 125 Hz to 8000 Hz. The units under test were set up in the Air Distribution (Reverberation) Test Chamber and connected to a quiet air supply. The units were supplied with ambient temperature air at the specified airflow. The environmental test conditions in the reverberation chamber varied for each test within the following ranges:

Test Air Temperature 16 degrees C ± 2.0 degree C

Room Air Temperature 18 degrees C ± 2.0 degree C

Barometric Pressure 1045 millibar ± 5 millibar

Relative Humidity 65 + 10% Following calibration checks, sound pressure levels were measured and converted to sound power levels using the comparison method of AS1217.2 - 1985 (ie. using a reference sound source of known Sound Power to determine room correction). Airflow rate was measured using orifice plates. Static pressure drop was recorded using a (Static Pressure) probe and an inclined manometer. Throw was measured using a hotwire type anemometer. Figures 4 to 7 show the test set ups. Figures 8 to 17 show the test units.

Page 9: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 9 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Figure 4: Test Set-up for Uni-Vent Fixed Blade

Page 10: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 10 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Figure 5: Test Set-up for Uni-Vent Adjustable Blade, CD2000, Aluminium 4-way & 3-way

Page 11: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 11 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Figure 6: Test Set-up for UNIJET Jet Centre, UNIJET Cone Centre (x=0 & x=20mm)

Page 12: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 12 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Figure 7: Test Set-up for Aluminium Double Deflection Wall Register

Page 13: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 13 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 8 : Uni-Vent Fixed Blade, Square Samples

Page 14: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 14 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 9 : Uni-Vent Fixed Blade, Rectangular Sample

Page 15: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 15 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 10 : Uni-Vent Adjustable Blade, Square Samples

Page 16: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 16 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 11 : Uni-Vent Adjustable Blade, Rectangular Sample

Page 17: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 17 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 12 : CD2000

Page 18: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 18 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 13 : Aluminium 4-way Ceiling Diffuser

Page 19: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 19 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 14 : Aluminium 3-way Ceiling Diffuser

Page 20: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 20 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 15 : UNIJET, Jet Centre

Page 21: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 21 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 16 : UNIJET, Cone Centre

Page 22: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 22 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

a) Front View

b) Rear View

Figure 17 : Double Deflection Wall Register

Page 23: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 23 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

5.0 INSTRUMENTATION

INSTRUMENT MAKE & MODEL CALIBRATION SERIAL NO. BY DATE Sound Level Meter LD2900 Vipac May 2001 A0316 Microphone B&K 4145 Vipac May 2001 25415619 Acoustic Calibrator B&K 4230 Vipac 7/6/00 860700 Sound Power Reference Source

Pope Vipac 1/5/2001 -

Manometers (2) Airflow Developments

Type 504 Gas Technology Services

June 2001 36862 PM6-168

Orifice Plates Vipac Vipac May 2001 - Hotwire Probe TSI 8330 TSI 12/11/97 97110174 Thermometer Digital T200KC - - -

6.0 ORDERS OF ACCURACY

Sound Pressure Level: Octave Band Centre Standard Deviation (1) Frequency (Hz) (dB) 125 +3.0 250 +2.0 500 to 4000 +1.5 8000 +3.0 Pressure Drop: + 5% or 0.5 Pa whichever is greater Airflow: + 5% or 10 l/s whichever is greater

Page 24: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 24 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

7.0 RESULTS The results obtained are shown in the attached Test Certificates.

Report Prepared by: VIPAC ENGINEERS AND SCIENTISTS LTD. ...................................................... ............................................ GREG THEODORIDIS NORM BRONER PROJECT ENGINEER N.A.T.A. SIGNATORY

Page 25: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 25 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 1

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Fixed Blade Modular Type Ceiling Diffuser Nominal Size: 9” x 9” Test Configuration: 4-way Throw Pattern: 45° approx.

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

96 11 3.6 16 45.8 36.6 36.4 25.3 <19.9 <16.4 <18.0 114 16 >4 21 45.3 41.1 39.0 31.6 28.0 <20.3 <18.3 137 23 >4 25 48.3 44.6 41.6 36.9 34.3 28.1 <20.0 164 34 >4 30 51.5 49.4 44.8 43.1 40.5 35.8 26.2 200 52 >4 35 53.5 53.8 48.8 47.3 45.8 42.7 34.6

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 26: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 26 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Page 27: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 27 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 2

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Fixed Blade Modular Type Ceiling Diffuser Nominal Size: 12” x 12” Test Configuration: 4-way Throw Pattern: 45° approx.

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

201 13 >4 18 <41.6 38.5 32.8 24.0 <17.5 <16.2 <18.7 235 18 >4 22 <44.2 39.5 36.6 30.7 22.3 <17.5 <18.7 278 25 >4 27 <44.8 47.0 41.0 36.9 29.9 22.7 <18.9 321 34 >4 32 <46.4 50.1 44.0 41.6 35.4 29.5 <19.5 383 48 >4 36 48.8 51.5 47.9 46.2 41.3 36.3 <22.7

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 28: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 28 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Page 29: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 29 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 3

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Fixed Blade Modular Type Ceiling Diffuser Nominal Size: 15” x 15” Test Configuration: 4-way Throw Pattern: 45° approx.

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

359 15 >4 21 <47.4 41.2 34.4 26.2 <20.0 <17.4 <19.0 429 21 >4 25 <47.8 45.1 38.6 33.6 25.4 <19.6 <19.0 497 28 >4 29 <49.3 48.7 41.7 38.6 31.3 25.1 <19.4 561 37 >4 32 52.0 51.4 44.5 42.1 35.9 30.5 <21.0 631 47 >4 35 56.7 54.3 46.7 45.4 40.2 35.1 <23.5

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 30: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 30 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Page 31: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 31 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 4

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Fixed Blade Modular Type Ceiling Diffuser Nominal Size: 15” x 22” Test Configuration: 4-way Throw Pattern: 45° approx.

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T (m) NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) A B

454 12 >4 3.6 19 <44.1 38.8 33.0 27.2 <20.2 <16.9 <18.1 546 16 >4 >4 24 <45.7 42.0 37.9 31.9 24.7 <18.7 <18.3 603 20 >4 >4 27 <47.1 45.3 40.8 36.1 30.4 22.6 <18.3 691 27 >4 >4 32 51.1 49.2 45.2 41.7 36.5 30.0 <19.6 817 38 >4 >4 36 54.7 53.3 49.2 46.4 42.5 36.8 <23.6

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

A

B

Page 32: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 32 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 5

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Adjustable Blade Modular Type Ceiling Diffuser Nominal Size: 9” x 9” Test Configuration: 4-way Blade Setting: x = 14mm for Horizontal Throw Pattern

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

107 17 3.4 22 45.8 36.6 36.4 25.3 <19.9 <16.4 <18.0 127 24 4 25 45.3 41.1 39.0 31.6 28.0 <20.3 <18.3 152 37 >4 28 48.3 44.6 41.6 36.9 34.3 28.1 <20.0 182 52 >4 33 51.5 49.4 44.8 43.1 40.5 35.8 26.2 214 73 >4 39 53.5 53.8 48.8 47.3 45.8 42.7 34.6

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 33: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 33 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Page 34: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 34 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 5B (45deg)

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Adjustable Blade Modular Type Ceiling Diffuser Nominal Size: 9” x 9” Test Configuration: 4-way Blade Setting: x = 24mm for 45° Throw Pattern

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

152 25 >4 25 46.5 44.1 39.4 33.7 27.7 20.2 18.2 182 37 >4 30 48.7 48.7 44.0 39.6 35.1 29.0 21.0

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 35: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 35 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 6

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Fixed Blade Modular Type Ceiling Diffuser Nominal Size: 12” x 12” Test Configuration: 4-way Blade Setting: x = 14mm for Horizontal Throw Pattern

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

145 11 4 18 <43.6 39.1 30.7 <22.3 <17.0 <16.1 <18.7 182 16 >4 26 <43.7 41.2 39.9 27.8 <20.9 <17.0 <18.7 213 22 >4 29 <45.5 43.4 42.6 33.4 27.9 <20.2 <18.9 259 30 >4 33 48.1 47.3 46.9 39.1 35.0 28.6 <19.9 315 43 >4 36 49.8 50.6 49.3 46.0 41.0 36.3 24.6

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 36: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 36 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

Page 37: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 37 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 6B (45deg)

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Fixed Blade Modular Type Ceiling Diffuser Nominal Size: 12” x 12” Test Configuration: 4-way Blade Setting: x = 24mm for 45° Throw Pattern

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

264 22 >4 28 46.0 45.4 41.9 35.3 28.9 20.8 <19.1 299 28 >4 30 48.2 49.0 44.5 39.2 33.9 26.4 <19.9

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 38: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 38 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 7

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Fixed Blade Modular Type Ceiling Diffuser Nominal Size: 15” x 15” Test Configuration: 4-way Blade Setting: x = 14mm for Horizontal Throw Pattern

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

276 11 4 19 <44.7 37.6 33.2 22.8 <17.3 <16.0 <18.8 315 14 >4 23 <45.0 39.7 37.4 27.2 21.0 <16.9 <18.9 364 20 >4 26 46.2 43.7 40.1 32.5 27.5 <19.8 <19.0 449 30 >4 31 49.1 48.4 45.2 39.2 35.6 29.2 <20.8 536 42 >4 38 53.2 52.5 47.4 47.5 41.6 36.5 26.2

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 39: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 39 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 8

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Uni-Vent Adjustable Blade Modular Type Ceiling Diffuser Nominal Size: 15” x 22” Test Configuration: 4-way Blade Setting: x = 14mm for Horizontal Throw Pattern

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T (m) NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) A B

324 7 3.8 3.4 <16 <44.2 <37.3 <29.3 <22.1 <17.2 <16.2 <18.0 401 10 >4 4 22 <45.5 42.4 35.8 29.2 22.6 <17.0 <18.1 428 14 >4 >4 25 <45.9 43.7 39.0 32.7 27.1 <18.9 <18.2 537 20 >4 >4 30 51.0 48.1 44.3 38.9 34.8 27.6 <20.0 646 30 >4 >4 35 53.7 52.0 48.8 44.7 41.4 35.1 24.0 764 45 >4 >4 41 57.3 56.4 52.9 50.7 47.8 43.2 33.3

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

A

B

Page 40: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 40 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 9

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: CD 2000 4-way Louver Type Plastic Ceiling Diffuser Nominal Size: 9” x 9” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

103 21 3.8 16 <41.2 36.2 30.8 23.9 <19.6 <16.6 <18 120 28 5 21 <42.9 40.3 35.5 30.1 26.6 <20.0 <18.1 144 42 >5 26 45.2 43.6 40.3 35.7 33.2 28.1 <19.1 168 55 >5 31 48.0 46.5 43.9 40.7 38.3 34.0 <22.3 200 80 >5 37 52.2 50.6 47.5 45.0 44.0 40.3 30.4

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 41: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 41 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 10

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: CD 2000 4-way Louver Type Plastic Ceiling Diffuser Nominal Size: 12” x 12” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

165 22 >4 21 <42.6 39.3 34.9 26.7 21.9 <17.7 <18.7 195 29 >4 25 <44.2 42.2 38.7 32.6 28.7 22.3 <18.9 235 41 >4 28 <45.6 46.1 42.2 37.8 34.6 30.2 <20.1 278 58 >4 34 49.0 49.3 45.7 43.5 40.1 36.6 24.4 331 80 >4 38 52.2 53.1 49.9 48.3 45.4 42.9 32.5

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 42: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 42 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 11

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: CD 2000 4-way Louver Type Plastic Ceiling Diffuser Nominal Size: 15” x 15” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

245 18 >4 19 <41.7 35.6 33.5 22.9 <18.5 <16.4 <18.8 289 24 >4 23 <42.6 39.2 37.1 28.6 23.6 <18.4 <18.8 352 35 >4 26 <45.2 43.9 40.1 34.4 31.0 24.8 <19.2 414 46 >4 31 48.6 47.9 43.2 40.8 36.4 31.6 <20.8 494 65 >4 36 52.4 51.6 46.9 45.9 41.6 38.0 26.0

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 43: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 43 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 12

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: CD 2000 4-way Louver Type Plastic Ceiling Diffuser Nominal Size: 595mm x 595mm Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

324 13 >5 18 <42.7 <37.8 32.0 <23.3 <17.8 <16.0 <18.1 376 18 >5 22 <45.4 39.6 36.1 28.5 22.4 <17.5 <18.2 435 24 >5 27 <45.6 42.7 40.9 33.7 28.9 <21.3 <18.4 500 31 >5 30 48.0 47.3 43.9 38.4 34.4 28.2 <19.2 572 40 >5 33 50.6 49.8 46.9 42.4 38.7 33.6 <21.9 689 58 >5 38 56.3 54.6 50.6 48.1 44.5 40.4 30.1

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 44: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 44 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 13

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium 4-way Louver Type Ceiling Diffuser Nominal Size: 9” x 9” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

95 12 3.3 <16 <39.7 <33.7 28.8 <18.1 <14.5 <15.7 <18.0 113 17 4 20 <41.4 36.8 34.7 22.2 <16.0 <15.8 <18.0 141 27 5 23 <43.6 42.0 37.6 31.5 23.1 <17.3 <18.0 171 40 >5 28 45.2 44.7 41.5 38.4 31.2 23.1 <18.4 212 61 >5 34 49.7 48.9 46.8 44.0 39.3 33.3 <20.4

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 45: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 45 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 14

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium 4-way Louver Type Ceiling Diffuser Nominal Size: 12” x 12” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

168 13 >4 20 <41.5 <36.8 34.6 <21.8 <15.8 <16.0 <18.7 195 18 >4 23 <41.8 38.7 37.1 26.6 <18.0 <16.2 <18.7 235 26 >4 25 <43.4 43.7 39.5 34.2 24.9 <18.3 <18.8 276 36 >4 31 <45.2 46.3 42.2 40.5 32.4 23.3 <19.0 331 50 >4 35 47.8 49.0 46.1 44.6 38.6 30.9 <20.0

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 46: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 46 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 15

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium 4-way Louver Type Ceiling Diffuser Nominal Size: 15” x 15” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

245 13 4 19 <43.8 36.8 33.7 24.5 22.8 <18.6 <19.1 303 19 >4 23 <44.3 41.3 37.1 29.0 23.3 <19.4 <19.1 356 26 >4 26 <45.4 44.4 39.5 36.0 26.4 <19.0 <19.3 429 38 >4 32 49.9 46.7 42.3 41.8 34.1 26.5 <19.5 524 54 >4 36 53.4 50.6 46.7 46.2 41.7 34.8 <21.9

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 47: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 47 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 16

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium 4-way Louver Type Ceiling Diffuser Nominal Size: 595mm x 595mm Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

363 11 >4 18 <44.5 <37.9 32.3 <22.8 <17.1 <16.0 <18.1 426 15 >4 24 <44.7 41.4 37.7 30.3 21.6 <17.0 <18.2 501 21 >4 27 <46.8 45.4 41.4 36.2 29.3 <20.5 <18.3 581 28 >4 31 52.3 49.0 44.2 41.4 35.6 26.9 <18.9 677 37 >4 36 54.2 52.2 48.4 46.1 42.1 33.8 <21.5

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 48: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 48 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 17

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium 3-way Louver Type Ceiling Diffuser Nominal Size: 9” x 9” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

115 22 >4 19 <41.3 37.6 33.5 26.9 <20.1 <16.8 <18.9 135 29 >4 24 <42.8 41.9 38.0 33.2 25.0 <18.6 <18.9 160 41 >4 29 <46.1 44.6 42.1 38.9 33.2 25.6 <19.1 192 56 >4 33 47.7 47.4 45.6 43.4 40.4 33.0 <20.2 235 84 >4 41 51.5 50.5 50.9 47.7 48.3 41.7 26.3

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 49: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 49 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 18

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium 3-way Louver Type Ceiling Diffuser Nominal Size: 12” x 12” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

166 16 >4 20 <42.2 40.2 33.9 25.7 <19.0 <16.7 <18.8 201 22 >4 24 <44.7 44.7 38.3 33.2 25.9 <19.8 <18.8 242 31 >4 29 <45.1 46.6 42.5 38.7 32.8 27.4 <19.1 295 46 >4 34 <47.3 49.9 46.8 44.2 41.2 35.0 <21.5 356 67 >4 42 50.7 53.2 51.5 48.4 48.7 41.7 27.4

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 50: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 50 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 19

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium 3-way Louver Type Ceiling Diffuser Nominal Size: 15” x 15” Throw Pattern: Horizontal

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

264 16 >4 22 <41.0 42.2 34.1 26.4 <17.9 <16.2 <18.8 311 21 >4 24 <43.9 43.9 38.3 33.5 25.1 <19.5 <19.6 366 29 >4 29 46.7 46.5 42.1 38.6 30.8 22.1 <19.2 429 40 >4 34 48.6 49.4 45.4 43.5 37.4 29.8 <20.4 526 58 >4 40 53.7 52.3 50.5 47.6 47.0 37.7 <23.6

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 51: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 51 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 20

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: UNIJET, Jet Centre Plastic Round Ceiling Diffuser Nominal Size: Φ150mm Throw Pattern: Vertical

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

59 19 >4 <16 <41.8 <33.1 <26.7 22.3 <20.4 <17.5 <18 74 30 >4 22 <44.2 38.2 32.8 29.7 28.5 23.1 <18.6 89 46 >4 28 48.4 44.2 38.0 35.4 34.8 31.0 <21.1 106 65 >4 33 54.1 47.9 42.4 40.8 40.2 36.7 25.8 125 89 >4 38 57.5 52.0 46.8 45.4 45.4 42.1 31.8

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 52: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 52 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 21

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: UNIJET, Jet Centre Plastic Round Ceiling Diffuser Nominal Size: Φ200mm Throw Pattern: Vertical

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

99 21 >4 17 <46.7 <34.8 30.6 27.1 24.0 <18.5 <18.1 121 32 >4 24 <46.6 39.5 36.1 33.4 31.1 25.3 <18.5 142 43 >4 29 50.6 44.1 40.0 38.2 36.1 31.8 <20.1 161 55 >4 33 54.2 47.2 42.7 41.4 40.0 36.4 <23.6 188 76 >4 39 58.7 51.5 47.1 45.8 45.6 41.8 30.3

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 53: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 53 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 22A

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: UNIJET, Cone Centre Plastic Round Ceiling Diffuser Nominal Size: Φ150mm Throw Pattern: Vertical Cone setting: x = 0mm

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

23 32 3.6 <16 <41.1 <29.9 <24.8 <17.8 <14.5 <15.6 <18.0 30 53 >4 16 <41.0 <32.7 30.7 23.9 <16.0 <15.7 <18.0 37 66 >4 20 <39.8 <33.5 34.2 28.7 <18.1 <15.9 <18.0 44 88 >4 23 <40.6 35.8 36.5 33.3 23.0 <16.9 <18.1 52 122 >4 28 <40.9 38.7 40.3 37.9 29.9 <20.4 <18.4 61 166 >4 33 <42.3 40.7 43.1 42.7 36.3 28.1 <21.5

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 54: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 54 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 23A

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: UNIJET, Cone Centre Plastic Round Ceiling Diffuser Nominal Size: Φ200mm Throw Pattern: Vertical Cone setting: x = 0mm

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

44 47 >4 <16 <40.3 <31.2 <26.4 <20.7 <18.3 <16.1 <18.1 59 73 >4 19 <42 <34 32.5 29.1 24.4 <18.3 <18.3 78 120 >4 26 <43.4 37.7 37.6 35.9 28.2 <20.8 <18.7 94 170 >4 31 <45.3 42.6 41.5 41.2 34.3 27.4 <22

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 55: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 55 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 24A

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: UNIJET, Cone Centre Plastic Round Ceiling Diffuser Nominal Size: Φ250mm Throw Pattern: Vertical Cone setting: x = 0mm

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

49 49 >4 <16 <41.8 <30.7 <25.7 <20.1 <16.1 <15.4 <18.0 62 73 >4 17 <42.1 <32.8 31.4 26.0 <19.2 <16.2 <18.1 77 106 >4 23 <43.5 36.5 36.7 33.4 26.1 <20.5 <18.7 95 156 >4 29 <43.9 39.5 40.3 39.3 33.1 27.5 <22.8

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 56: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 56 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 22B

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: UNIJET, Cone Centre Plastic Round Ceiling Diffuser Nominal Size: Φ150mm Throw Pattern: Vertical Cone setting: x = 20mm

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

60 29 >4 <16 <40.0 <31.2 <26.0 <20.0 <16.1 <16.0 <18.0 78 45 >4 19 <42.5 37.3 33.2 27.7 20.9 <17.9 <18.2 91 60 >4 23 49.2 41.4 37.0 31.9 26.1 <21 <19 106 82 >4 27 51.9 44.7 41.5 37.3 30.9 25.8 <21.1 127 118 >4 33 56.3 49.5 47.2 42.6 37.7 32.3 26.5 148 158 >4 38 58.4 53.7 52.0 47.4 43.1 37.6 31.8

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 57: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 57 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 23B

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: UNIJET, Cone Centre Plastic Round Ceiling Diffuser Nominal Size: Φ200mm Throw Pattern: Vertical Cone setting: x = 20mm

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

78 21 >4 <16 <43 <30.4 <23.2 <17.1 <14.9 <15.4 <18.1 119 50 >4 17 <43.1 <34.8 31.0 26.0 <18.7 <16.4 <18.1 146 75 >4 24 <46.2 41.0 37.7 32.5 25.3 <19.1 <18.4 182 112 >4 29 52.0 44.9 43.1 38.8 33.1 27.4 <20.8 220 164 >4 36 56.9 49.8 48.3 45.5 39.4 35.2 29.7

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 58: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 58 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 24B

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: UNIJET, Cone Centre Plastic Round Ceiling Diffuser Nominal Size: Φ250mm Throw Pattern: Vertical Cone setting: x = 20mm

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

125 33 >4 <16 <42.3 <31.1 <24.6 <19.2 <15.3 <15.5 <18.1 170 59 >4 19 <43.9 36.0 33.7 28.8 <20.0 <16.2 <18.2 204 84 >4 25 <47.4 41.0 38.7 34.6 26.9 <18.8 <18.5 240 118 >4 30 50.5 44.5 42.9 39.8 32.8 25.1 <20.7 300 186 >4 37 55.5 50.7 48.5 47.1 40.4 33.6 30.3

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 59: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 59 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 25

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium Double Deflection Wall Register Test setting: 0° deflection Nominal Size: 14” x 4”

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

90 20 >9 17 <41.1 <33.7 31.0 <21.5 <16.4 <15.8 <18.3 106 26 >9 21 <42.0 <34.7 35.1 27.8 <19.8 <17.2 <18.4 121 34 >9 24 <44.1 38.7 38.1 33.4 24.9 <20.8 <18.8 146 48 >9 31 47.4 43.3 41.4 40.8 32.1 29.0 <21.3 174 70 >9 36 51.4 46.9 44.8 45.7 37.9 35.3 27.0

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 60: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 60 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 26

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium Double Deflection Wall Register Test setting: 0° deflection Nominal Size: 20” x 12”

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

333 10 >9 <17 <45.8 <37.9 <30.7 25.3 <19.5 <16.7 <18.3 403 14 >9 22 <45.6 42.0 36.1 31.6 25.0 <18.8 <18.2 484 22 >9 28 <47.6 46.7 42.3 38.2 32.9 25.8 <19.1 581 31 >9 34 52.6 51.0 47.1 43.6 39.2 33.8 <22.8 718 44 >9 40 56.8 56.1 52.3 49.6 45.9 41.4 31.5

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 61: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 61 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 27

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium Double Deflection Wall Register Test setting: 0° deflection Nominal Size: 20” x 20”

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

526 5 >9 18 <44.5 <37.9 31.9 26.9 <19.8 <16.5 <18.2 633 9 >9 25 <46.0 42.5 39.0 32.8 27.0 <18.9 <18.2 753 14 >9 29 48.4 46.9 43.0 38.6 33.1 25.9 <19.0 896 20 >9 34 52.3 51.1 48.4 43.8 39.4 33.2 <22.4 1127 32 >9 41 57.8 57.2 54.0 51.1 47.4 42.7 33.4

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.

Page 62: Westaflex Australia Pty. Ltd. Airflow and Acoustic ... · Westaflex Australia Pty. Ltd. August, 2001 Page 6 of 62 N.A.T.A. Report No.: 302990-001

Westaflex Australia Pty. Ltd. August, 2001 Page 62 of 62

N.A.T.A. Report No.: 302990-001 <GT302990-1.doc

TEST CERTIFICATE No. 28

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR OUTLETS AND INLETS SUPPLIED BY: WESTAFLEX AUSTRALIA PTY. LTD. TESTED BY: VIPAC ENGINEERS & SCIENTISTS LTD TEST DATE: 10/8/2001 – 20/8/2001 CLIENT: WESTAFLEX AUSTRALIA PTY. LTD. UNIT: Aluminium Double Deflection Wall Register Test setting: 0° deflection Nominal Size: 32” x 24”

TEST CONDITIONS

SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz)

Qs Ps T NR 125 250 500 1000 2000 4000 8000 (l/s) (Pa) (m)

1290 12 >9 19 <44.2 39.7 33.6 28.3 22.8 <18.8 <19.5 1437 15 >9 25 <44.8 41.9 38.7 33.0 28.4 25.0 25.9 1658 19 >9 29 46.2 45.2 43.3 37.9 32.2 28.0 26.1 1910 25 >9 33 49.5 48.9 47.4 42.4 36.8 31.6 27.5 2319 36 >9 39 54.7 52.8 52.1 48.9 42.8 37.7 31.8

LEGEND Qs - Primary Air Flow Rate (l/s) Ps - Supply Static Pressure (Pa) < - Insufficient margin above background noise to allow accurate determination > - Length of throw greater than that able to be measured NR - Noise Rating number based upon room absorption of 10 dB T - Throw in meters to a terminal velocity of 0.25 m/s ____________________________ ________________________ Greg Theodoridis Norm Broner PROJECT ENGINEER N.A.T.A. SIGNATORY

This laboratory is accredited by the National Association of Testing Authorities, Australia.

The tests reported herein have been performed in accordance with its terms of accreditation. This document shall not be reproduced except in full.