Sample verification of welding
Citation preview
Sheet1Type of weld22Weld size, S4mmEffective weld size, a = 0.7 S2.8mmDepth of weld, d35mmDistance between weld lines, b35mmSection modulus of weld along the strong axis, Zx408.3333333333mm2Section modulus of weld along the weak axis, Zy1225mm2Limiting strength of fillet welds, pw220MPa Longitudunal shear capacity, PL = pw a616N/mmCoefficient for direction of shear, K1.25Transverse shear capacity, PT = PL K770N/mmFORCES ON WELDMoment along the strong axis, Mx0KN-mMoment along the weak axis, My0KN-mAxial force, P0.69KNShear along the x-axis, Vx11.14KNShear along the y-axis, Vy4.28KNShear on the weld, FL = V/ Total length of Weld170.57N/mmApplied axial force on the weld, FT = T/Total length of weld + Mx/Zx + My/Zy0.01N/mmCOMBINED FORCE INTERACTION RATIO(FL/PL)2 + (FT/PT)2 1.0(170.58 / 616) + (0.01 / 770) = 0.08 < 1.0; Weld is OK
Sheet2Z strong axisZ weak axis1204.166666666702408.3333333333122531225408.333333333341633.33333333331633.3333333333204.1666666667051429.1666666667122561633.3333333333122517962.1127501619962.1127501619408.3333333333122521225408.3333333333341633.33333333331633.333333333351429.1666666667122561633.3333333333122572858.3333333333816.6666666667962.1127501619962.11275016198
Sheet3