web-bpb121202f

Embed Size (px)

DESCRIPTION

manual

Citation preview

  • 6.35

    7.95

    3.4

    0.8

    FG21202FG21202 is a general purpose application battery. Within the FG range Fiamm offer 6V and 12V monoblocs at various amp hour capacities enable the right battery selection for each requirement. FIAMM Sealed Power is a Manufacturer of VRLA batteries; and is supported by a dedicated sales network with market knowledge and experience of small sealed lead acid battery applications.

    12 Volt12 Ah

    Features

    Nominal Voltage 12 Volt

    Nominal Capacity 12 Ah at 20 hours rate to 1.75 Vpc at 25 C

    Float charging voltage 13.50 - 13.80 V/bloc at 25 C

    Boost charge voltage 14.40 - 15.00 V/bloc at 25 C

    Float voltage compensation -18mV/C

    Maximum charging current 3 A

    Case ABS with HB flammability rate (according UL94)

    Internal resistance 14.8 m in full charged conditionWeight 3.75 kg

    Dimensions L x W x H (TH): 151 x 98 x 94 (99)

    Operative temperature range -20 C to 50 C

    Storage As batteries lose part of their capacity, during storage, due to self discharge. Fiamm Sealed Power recommends FG range of batteries can be stored for 6 months at an ambient temperature of 20 and 25 C (see attached graph on reverse). Longer storage requires a recharge. This should be carried out in line with Fiamm Sealed Power recommended method; 2.4 V/cell for no longer than 24 hours at 20 C

    FIAMM Sealed Power

    FG series

    Faston 6.3 mm151

    150

    94 99

    11.8 14.1

    6.6

    9878

    97.3

    STANDBY USE CYCLIC USEVOLTAGE REGULATIONINITIAL CURRENT

    13.50 - 13.80 V 14.4 - 15.0 V3 A MAX

    21202N.:G193064VdS

    Rechargeable Lead Acid BatteryCharging Instruction (at 20C)

    FG

    The dimensions have a tollerance of : 1.6%

  • FIAM

    M re

    serv

    es th

    e rig

    ht to

    chan

    ge o

    r rev

    ise w

    ithou

    t not

    ice a

    ny in

    form

    atio

    n or

    det

    ail g

    iven

    in th

    is pu

    bblic

    atio

    n

    MH27960

    FIAMM Sealed Power S.p.A.www.fi amm.come-mail: info.standby@fi amm.com

    FIAMM Sealed Power

    FG series FG212

    02_v

    er_1

    _18/

    01/2

    008

    40C

    5C

    30C 25C

    0 2 4 6 8 10 12 14 16 18 20

    40

    60

    80

    100

    Refreshing charge of 2.4 Vpc may be insufficient to

    recover the battery capacity. It is important to avoid

    this area

    Refreshing charge at 2.4 Vpc for 24 hours (at 20-

    25C) must be applied as soon as possible.

    The battery can be used without refreshing charge

    Storage Time (months)

    Rem

    aini

    ng C

    apac

    ity (%

    )

    dSV N.:G193064

    Battery Voltage and Charge Time for Standby Use (at 25C)

    Discharge time (min)

    Batte

    ry V

    olta

    ge (V

    )

    9

    10

    11

    12

    13

    1 10 100 1.000 10.000

    2.60 C 2 C 1.22 C 0.68 C 0.26 C 0.10 C0.05 C

    Discharge curves at different current / fi nal voltage (at 25C)

    Recharged Capacity (%)

    Battery Voltage (V)

    Charging Current (A)

    5 10 20 250Charging time (h)

    Char

    ging

    Vo

    ltage

    (V)

    13

    0

    10

    11

    12

    14

    15

    15Discharge 100%50%

    Char

    ging

    Cur

    rent

    (A)

    Rec

    harg

    ed C

    apac

    ity (%

    )

    140

    60

    100

    80

    120

    40

    20

    0

    0.10 C20

    0.05 C20

    0

    Capacity loss during storage

    at various temperatures

    Constant Current discharge table (Amperes) at 25 C

    Constant Power discharge table (Watts per bloc) at 25 C

    end voltage 5 min 10 min 15 min 20 min 30 min 45 min 1 h 2 h 3 h 5 h 10 h 20 h

    9.60 V 39.2 27.7 21.1 17.0 12.7 9.37 7.50 4.30 3.14 2.09 1.16 0.63

    9.90 V 38.1 27.0 20.7 16.7 12.5 9.23 7.44 4.25 3.10 2.07 1.15 0.62

    10.02 V 37.1 26.4 20.4 16.6 12.3 9.12 7.34 4.21 3.07 2.05 1.14 0.62

    10.20 V 35.7 25.7 20.1 16.4 12.2 9.02 7.24 4.17 3.04 2.04 1.13 0.62

    10.50 V 34.0 24.5 19.1 15.7 11.8 8.79 7.07 4.08 2.98 2.00 1.11 0.60

    10.80 V 31.5 23.0 17.8 14.8 11.2 8.39 6.78 3.96 2.91 1.97 1.09 0.60

    end voltage 5 min 10 min 15 min 20 min 30 min 45 min 1 h 2 h 3 h 5 h 10 h 20 h

    9.60 V 391 284 221 182 138 104 84.3 49.0 36.0 24.1 13.5 7.31

    9.90 V 382 279 218 179 137 103 84.0 48.6 35.8 24.0 13.4 7.29

    10.02 V 377 275 217 178 136 102 83.4 48.4 35.6 23.9 13.3 7.29

    10.20 V 373 273 215 177 135 102 82.9 48.3 35.5 23.9 13.3 7.28

    10.50 V 359 266 213 176 134 101 81.8 47.8 35.2 23.8 13.2 7.26

    10.80 V 330 246 196 165 127 96.5 78.6 46.4 34.3 23.3 13.0 7.16