16
Reliable solutions Separators and tanks FOR STORMWATER TREATMENT IN INDUSTRIAL, STORAGE AND TRAFFIC AREAS January 2006 Labko ® Oil Separator Systems

Wavin Labko Oil Separator System

Embed Size (px)

DESCRIPTION

Wavin Labko Oil Separator System

Citation preview

Page 1: Wavin Labko Oil Separator System

Reliable solutions Separators and tanks

FOR STORMWATER TREATMENTIN INDUSTRIAL, STORAGE ANDTRAFFIC AREAS

Pic

torin

o O

y/K

irjap

aino

Her

mes

1/

2006

2.

000

www.wavin-labko.fi

Wavin-Labko Ltd reserves the rights to alterations without prior notice. Due to policy of continuousimprovement in R&D, technical specifications may change. Installation shall always be made asdocumented in manufacturer's instructions.

Wavin-Labko in brief

January 2006

Wavin-Labko LtdLabkotie 1FI-36240 KangasalaFINLANDTel. int. +358 20 1285 200Fax int. +358 20 1285 280E-mail [email protected]

Labko® Oil Separator SystemsLabko® Oil Separator Systems

Wavin-Labko Ltd is a Finnish company with over 40 years'experience in developing, manufacturing and marketing ofmeasurement devices and various plastic products. In the fieldof measurement devices we are specialized in level instrumentsand alarm devices, automation and identification, and in web-based solutions of data transfer. In the field of plastic productswe have focused our know-how on wastewater and stormwatertreatment by using various separator systems. These systemscover the separator solutions in business and servicesconstruction, the wastewater treatment in rural area settlements,as well as the wastewater treatment of private houses andsummer cottages.

Wavin-Labko Ltd is a part of international Wavin Group, whichis the leader in the European market for plastic pipe systems.Wavin Group has a presence in 27 European countries.

Page 2: Wavin Labko Oil Separator System

Labko FRWFlow RegulationWell

WavinHEK 400 TEL sandand sludge trap

WavinHEK 400 TEL

TEGRA 600inspection well

TEGRA 600inspection well

WavinHEK 400 TELsand andsludge trap

WavinHEK 400 TEL

EuroHEK sandand sludge trap

EuroPEKoil separator

EuroNOK FRWsampling shaft witha shut-off valve

SandSET-1000sludge alarm

OilSET-1000oil alarm

Labcom 200communication unit

Labko® Oil Separator SystemsLabko® Bypass System

Labko® Oil Separator Systems

Labko® Oil Separator SystemsLabko® Bypass System

Separators and tankswww.wavin-labko.fi

Labko®

BypassSystem forstormwatertreatment

TEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected]

Designed for use in• parking lots

• industrial yards and storage areas

• traffic areas

• terminals

• airfields

Many hazardous substances, such as oil

and heavy metals, are carried from surfaced

areas into the environment. Up to 80 % of

heavy metals are combined with solid matter,

such as sand and silt, which are carried

along with the rainwater.

To save nature from harmful emissions the

rainwater flowing from surfaced areas should

be cleaned. In general, the areas from which

the rainwater is collected are relatively large,

for example car parks, industrial areas, traffic

areas, terminals, or airfields. Environmentally

most delicate areas should be equipped

with a system processing all the downfall.

In normal conditions it is possible to reduce

the investment costs by using Labko Bypass

System.

Operation and structure of theLabko Bypass SystemWithin the Labko Bypass System the peak

flow of the stormwater is directed through the

Labko FRW Flow Regulation Well to pass the

separator system consisting of the EuroHEK

sand and sludge trap and the EuroPEK oil

separator. Following the separator system

there is the EuroNOK FRW sampling shaft,

in which the bypass line is reconnected with

the rainwater line. In spite of the bypass flow,

a well dimensioned Labko Bypass System

treats approximately 95 % of the annual

downfall. Thanks to the Labko Bypass

System, stormwater treatment is not only

effective, but cost-effective, too.

Efficient and cost-effectivestormwater treatmentIt is a research observation that most of the

oils and heavy metals carried with the rainwater

from surfaced areas are mainly washed away

at the beginning of the downpour.

2 3

In environmentally sensitive areas or in

areas, which for some other reason require

100 % cleaning of the rainwater, it is

reasonable to use the traditional, so called

direct system. This system is dimensioned

to treat the entire downpour, thus requiring

larger separators and causing more

substantial building costs than the Labko

Bypass System.

Directsystem

At this point the flow rate has not reached

its maximum yet, letting the separators in

the Labko Bypass System process all the

rainwater. The following peak flow that

contains fewer pollutants is directed past

the separator system. Thus, the washout

of the separator is prevented, and oil will

not be carried from the separator to the

sewer system, which normally leads the

rainwater to the ground.

Considerable savings are obtained by using

Labko Bypass System, in comparison with

cleaning systems, which are sized to treat

the whole nominal flow. Smaller and more

economical separators can be used in a

Labko Bypass System than in a direct

system.

Labko Bypass System

• prevents the washout of

the separator system

during heavy downpour

• economical solution for

stormwater treatment in

large areas

• treats 95 % of the annual

rainfall

EuroHEK sandand sludge trap

EuroPEKoil separator

EuroNOK FRWsampling shaft witha shut-off valve

Page 3: Wavin Labko Oil Separator System

Labko FRWFlow RegulationWell

WavinHEK 400 TEL sandand sludge trap

WavinHEK 400 TEL

TEGRA 600inspection well

TEGRA 600inspection well

WavinHEK 400 TELsand andsludge trap

WavinHEK 400 TEL

EuroHEK sandand sludge trap

EuroPEKoil separator

EuroNOK FRWsampling shaft witha shut-off valve

SandSET-1000sludge alarm

OilSET-1000oil alarm

Labcom 200communication unit

Labko® Oil Separator SystemsLabko® Bypass System

Labko® Oil Separator Systems

Labko® Oil Separator SystemsLabko® Bypass System

Separators and tankswww.wavin-labko.fi

Labko®

BypassSystem forstormwatertreatment

TEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected]

Designed for use in• parking lots

• industrial yards and storage areas

• traffic areas

• terminals

• airfields

Many hazardous substances, such as oil

and heavy metals, are carried from surfaced

areas into the environment. Up to 80 % of

heavy metals are combined with solid matter,

such as sand and silt, which are carried

along with the rainwater.

To save nature from harmful emissions the

rainwater flowing from surfaced areas should

be cleaned. In general, the areas from which

the rainwater is collected are relatively large,

for example car parks, industrial areas, traffic

areas, terminals, or airfields. Environmentally

most delicate areas should be equipped

with a system processing all the downfall.

In normal conditions it is possible to reduce

the investment costs by using Labko Bypass

System.

Operation and structure of theLabko Bypass SystemWithin the Labko Bypass System the peak

flow of the stormwater is directed through the

Labko FRW Flow Regulation Well to pass the

separator system consisting of the EuroHEK

sand and sludge trap and the EuroPEK oil

separator. Following the separator system

there is the EuroNOK FRW sampling shaft,

in which the bypass line is reconnected with

the rainwater line. In spite of the bypass flow,

a well dimensioned Labko Bypass System

treats approximately 95 % of the annual

downfall. Thanks to the Labko Bypass

System, stormwater treatment is not only

effective, but cost-effective, too.

Efficient and cost-effectivestormwater treatmentIt is a research observation that most of the

oils and heavy metals carried with the rainwater

from surfaced areas are mainly washed away

at the beginning of the downpour.

2 3

In environmentally sensitive areas or in

areas, which for some other reason require

100 % cleaning of the rainwater, it is

reasonable to use the traditional, so called

direct system. This system is dimensioned

to treat the entire downpour, thus requiring

larger separators and causing more

substantial building costs than the Labko

Bypass System.

Directsystem

At this point the flow rate has not reached

its maximum yet, letting the separators in

the Labko Bypass System process all the

rainwater. The following peak flow that

contains fewer pollutants is directed past

the separator system. Thus, the washout

of the separator is prevented, and oil will

not be carried from the separator to the

sewer system, which normally leads the

rainwater to the ground.

Considerable savings are obtained by using

Labko Bypass System, in comparison with

cleaning systems, which are sized to treat

the whole nominal flow. Smaller and more

economical separators can be used in a

Labko Bypass System than in a direct

system.

Labko Bypass System

• prevents the washout of

the separator system

during heavy downpour

• economical solution for

stormwater treatment in

large areas

• treats 95 % of the annual

rainfall

EuroHEK sandand sludge trap

EuroPEKoil separator

EuroNOK FRWsampling shaft witha shut-off valve

Page 4: Wavin Labko Oil Separator System
Page 5: Wavin Labko Oil Separator System
Page 6: Wavin Labko Oil Separator System

Labko® Oil Separator SystemsLabko® FRW Flow Regulation Well

Labko® Oil Separator Systems

Labko® Oil Separator SystemsEuroHEK

® sand and sludge trap • EuroHEK Omega® sand and sludge trap

Separators and tankswww.wavin-labko.fi

Labko®

FRW FlowRegulationWell

TEL. INT.+358 20 1285 200

FAX INT.-358 20 1285 280

[email protected] 7

Labko FRWFlow RegulationWell

Also during the peak flow of the heavydownpour the separator system functionsnormally. The Labko FRW Flow RegulationWell leads the excess flow exceeding thedimensioned flow of the oil separator via thebypass pipe to pass the separator system.Thus the washout of the separators isprevented.

EuroHEK®

andEuroHEKOmega®

Sand andSludgeTraps

The larger EuroHEK Omega 2000…5000

and EuroHEK 6500…50000 are the sand

and sludge traps for e.g. parking lots.

SandSET-1000 sludge alarm controls the

filling of the sludge storage space and

indicates an alarm when the sand and sludge

trap must be emptied (some 1/3 of the water

capacity is filled with sand). The timely

emptying of the sand and sludge trap

ensures the proper functioning of the oil

separator. SandSET-1000 is provided as a

standard in EuroHEK 10000 and larger sand

and sludge traps. For smaller sand and

sludge traps the SandSET-1000 is available

as an accessory.

EuroHEK Omegasand and sludgeseparator

First Flush phenomenon: Most of the oils and heavy metals carried by the rainwater areflushed from surfaced areas during the first phase of the downpour. At this point, therainwater flow has not reached its maximum yet, allowing all the rainwater flow thoughthe separators of the Labko Bypass System.

Flow rate

Concentration ofoil and solids

Time

EuroPEKOmega Filteroil separator

EuroNOK FRWsampling shaft witha shut-off valve

During a heavy downpour, the Labko FRW

Flow Regulation Well adjusts and restricts

the incoming flow to the separator system.

The Labko FRW Flow Regulation Well

contains a mechanical flow regulator, which

provides an even flow into the separators,

even if the incoming flow should exceed

the dimensioned flow of the separator

system. The excess flow is directed via

the bypass pipe to pass the separator

system. This prevents the washout of the

gathered sands and oils in the separator

system. Labko FRW Flow Regulation Well

is dimensioned to process approximately

95% of the annual downpour.

During normal downfall all the rainwater isdirected through the separator. The figurepresents the early phase of a heavy downpour,during which the FRW flow regulationmechanism starts to function. The flowregulator only allows the maximal rainwateramount corresponding to the dimensionedflow into the separator system. The excessflow is shortly dammed, until let flow viabypass pipe past the separator system.

The rainwater from surfaced areas carries

sand and finer-grained sludge. Most of the

heavy metals occurring in traffic areas are

bound to these solid particles.

SET-2000oil alarm

SandSET-1000sludge alarm

In EuroHEK sand and sludge trap the sand

carried by the rainwater is separated. Thus,

the sand and sludge trap contributes to the

smooth operation of the oil separator and

to lower maintenance costs. The rainwater

to be treated flows into the sand and sludge

trap, which separates sand, sludge and

further solids from the water. The solid-free

rainwater flows from the sand and sludge

trap into the oil separator. According to the

EN 858 standard, a sand and sludge trap

is always a part of the oil separator system.

EuroHEK 600…1500 sand and sludge traps

are designed for stormwater treatment in

parking areas, petrol station filling areas and

in yard areas.

Page 7: Wavin Labko Oil Separator System

Labko® Oil Separator SystemsLabko® FRW Flow Regulation Well

Labko® Oil Separator Systems

Labko® Oil Separator SystemsEuroHEK

® sand and sludge trap • EuroHEK Omega® sand and sludge trap

Separators and tankswww.wavin-labko.fi

Labko®

FRW FlowRegulationWell

TEL. INT.+358 20 1285 200

FAX INT.-358 20 1285 280

[email protected] 7

Labko FRWFlow RegulationWell

Also during the peak flow of the heavydownpour the separator system functionsnormally. The Labko FRW Flow RegulationWell leads the excess flow exceeding thedimensioned flow of the oil separator via thebypass pipe to pass the separator system.Thus the washout of the separators isprevented.

EuroHEK®

andEuroHEKOmega®

Sand andSludgeTraps

The larger EuroHEK Omega 2000…5000

and EuroHEK 6500…50000 are the sand

and sludge traps for e.g. parking lots.

SandSET-1000 sludge alarm controls the

filling of the sludge storage space and

indicates an alarm when the sand and sludge

trap must be emptied (some 1/3 of the water

capacity is filled with sand). The timely

emptying of the sand and sludge trap

ensures the proper functioning of the oil

separator. SandSET-1000 is provided as a

standard in EuroHEK 10000 and larger sand

and sludge traps. For smaller sand and

sludge traps the SandSET-1000 is available

as an accessory.

EuroHEK Omegasand and sludgeseparator

First Flush phenomenon: Most of the oils and heavy metals carried by the rainwater areflushed from surfaced areas during the first phase of the downpour. At this point, therainwater flow has not reached its maximum yet, allowing all the rainwater flow thoughthe separators of the Labko Bypass System.

Flow rate

Concentration ofoil and solids

Time

EuroPEKOmega Filteroil separator

EuroNOK FRWsampling shaft witha shut-off valve

During a heavy downpour, the Labko FRW

Flow Regulation Well adjusts and restricts

the incoming flow to the separator system.

The Labko FRW Flow Regulation Well

contains a mechanical flow regulator, which

provides an even flow into the separators,

even if the incoming flow should exceed

the dimensioned flow of the separator

system. The excess flow is directed via

the bypass pipe to pass the separator

system. This prevents the washout of the

gathered sands and oils in the separator

system. Labko FRW Flow Regulation Well

is dimensioned to process approximately

95% of the annual downpour.

During normal downfall all the rainwater isdirected through the separator. The figurepresents the early phase of a heavy downpour,during which the FRW flow regulationmechanism starts to function. The flowregulator only allows the maximal rainwateramount corresponding to the dimensionedflow into the separator system. The excessflow is shortly dammed, until let flow viabypass pipe past the separator system.

The rainwater from surfaced areas carries

sand and finer-grained sludge. Most of the

heavy metals occurring in traffic areas are

bound to these solid particles.

SET-2000oil alarm

SandSET-1000sludge alarm

In EuroHEK sand and sludge trap the sand

carried by the rainwater is separated. Thus,

the sand and sludge trap contributes to the

smooth operation of the oil separator and

to lower maintenance costs. The rainwater

to be treated flows into the sand and sludge

trap, which separates sand, sludge and

further solids from the water. The solid-free

rainwater flows from the sand and sludge

trap into the oil separator. According to the

EN 858 standard, a sand and sludge trap

is always a part of the oil separator system.

EuroHEK 600…1500 sand and sludge traps

are designed for stormwater treatment in

parking areas, petrol station filling areas and

in yard areas.

Page 8: Wavin Labko Oil Separator System

SandSET-1000sludge alarm

EuroPEK®

Oil SeparatorEuroPEK oil separator is a class I oil

separator. It is designed and tested

according to the requirements of the

EN 858 standard, and it can be used to

treat all kinds of oily waste and rainwaters.

EuroPEK oil separators are equipped with

coalescing plates, which separate oil from

the water. The process is based on the fact

that oil drops coalesce when they run onto

the oleophilic (oil attracting) plates. When

the size of the oil drop grows, its upward

velocity grows (Stokes' law) and the oil

drops rise along the angled plates’ surfaces

and through the holes in the coalescing

plates. The separated oil is stored as a

homogenous layer on the surface of the

water in the separator.

Labko® Oil Separator SystemsEuroPEK

® oil separator

Labko® Oil Separator Systems

Labko® Oil Separator SystemsEuroPEK Omega® Filter oil separator

Separators and tankswww.wavin-labko.fiTEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected] 9

The coalescing plates of the EuroPEK

separators can be cleaned with pressure

washer, after which they reach their proper

functioning again. The possibility to clean

the plates significantly reduces the main-

tenance and service costs of the separator,

for there are no filters, which are classified

as hazardous waste, to be disposed of.

EuroPEK separators present an extensive

range of applicability. They are best applied

in areas, in which there is a high content of

solids in the rainwater, meaning e.g. waste

treatment plants or collecting sites, scrap

yards, service and storage sites for earth-

movers, and areas with peat processing.

EuroPEK oil separators include the OilSET-

1000 oil alarm with ATEX compliance as

a standard. It indicates an alarm if the oil

storage space is full. Further information

on the alarm device and data transfer can

be found on page 12.

Operatingprinciple of the

coalescer.

EuroPEKOmega®

FilterOil SeparatorEuroPEK Omega Filter oil separators are class

I separators. They are designed and tested

in accordance with the EN 858 standard,

and they are suitable for treating oily rainwater.

EuroPEK Omega Filter separators are

available in size classes NS3-NS15. Their

high cleaning capacity is based on a

coalescent 3-D filter.

The EuroPEK Omega Filter oil separators are

made of strong and recyclable PE-plastic.

The separators are light to transport and easy

to install. The spherical bottom of the sludge

storage space allows complete emptying.

EuroPEK Omega Filter includes the SET-2000

oil alarm with ATEX compliance as a standard.

It indicates an alarm if the oil storage space

is full or in case of a high water level. Further

information on the alarm device and data

transfer can be found on page 12.

Labko FRWFlow RegulationWell

EuroHEK sandand sludge trap

EuroPEKoil separator

EuroNOK FRWsampling shaft witha shut-off valve

The superb cleaningefficiency of the EuroPEKOmega Filter oil separatorsis verified by flow tests runin compliance with theEN 858 standard.

OilSET-1000oil alarm

Page 9: Wavin Labko Oil Separator System

SandSET-1000sludge alarm

EuroPEK®

Oil SeparatorEuroPEK oil separator is a class I oil

separator. It is designed and tested

according to the requirements of the

EN 858 standard, and it can be used to

treat all kinds of oily waste and rainwaters.

EuroPEK oil separators are equipped with

coalescing plates, which separate oil from

the water. The process is based on the fact

that oil drops coalesce when they run onto

the oleophilic (oil attracting) plates. When

the size of the oil drop grows, its upward

velocity grows (Stokes' law) and the oil

drops rise along the angled plates’ surfaces

and through the holes in the coalescing

plates. The separated oil is stored as a

homogenous layer on the surface of the

water in the separator.

Labko® Oil Separator SystemsEuroPEK

® oil separator

Labko® Oil Separator Systems

Labko® Oil Separator SystemsEuroPEK Omega® Filter oil separator

Separators and tankswww.wavin-labko.fiTEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected] 9

The coalescing plates of the EuroPEK

separators can be cleaned with pressure

washer, after which they reach their proper

functioning again. The possibility to clean

the plates significantly reduces the main-

tenance and service costs of the separator,

for there are no filters, which are classified

as hazardous waste, to be disposed of.

EuroPEK separators present an extensive

range of applicability. They are best applied

in areas, in which there is a high content of

solids in the rainwater, meaning e.g. waste

treatment plants or collecting sites, scrap

yards, service and storage sites for earth-

movers, and areas with peat processing.

EuroPEK oil separators include the OilSET-

1000 oil alarm with ATEX compliance as

a standard. It indicates an alarm if the oil

storage space is full. Further information

on the alarm device and data transfer can

be found on page 12.

Operatingprinciple of the

coalescer.

EuroPEKOmega®

FilterOil SeparatorEuroPEK Omega Filter oil separators are class

I separators. They are designed and tested

in accordance with the EN 858 standard,

and they are suitable for treating oily rainwater.

EuroPEK Omega Filter separators are

available in size classes NS3-NS15. Their

high cleaning capacity is based on a

coalescent 3-D filter.

The EuroPEK Omega Filter oil separators are

made of strong and recyclable PE-plastic.

The separators are light to transport and easy

to install. The spherical bottom of the sludge

storage space allows complete emptying.

EuroPEK Omega Filter includes the SET-2000

oil alarm with ATEX compliance as a standard.

It indicates an alarm if the oil storage space

is full or in case of a high water level. Further

information on the alarm device and data

transfer can be found on page 12.

Labko FRWFlow RegulationWell

EuroHEK sandand sludge trap

EuroPEKoil separator

EuroNOK FRWsampling shaft witha shut-off valve

The superb cleaningefficiency of the EuroPEKOmega Filter oil separatorsis verified by flow tests runin compliance with theEN 858 standard.

OilSET-1000oil alarm

Page 10: Wavin Labko Oil Separator System

SET-2000oil alarm

SandSET-1000sludge alarm

Labko FRWFlow RegulationWell

EuroHEK sandand sludge trap

EuroPEK Filteroil separator

EuroNOK FRWsampling shaft witha shut-off valve

Labko® Oil Separator SystemsEuroPEK

® Filter oil separator

Labko® Oil Separator Systems

Labko® Oil Separator SystemsEuroNOK

® FRW sampling shaft with a shut-off valve • EuroHUK

® maintenance shaft • PP-HUK 600 maintenance shaft

Separators and tankswww.wavin-labko.fiTEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected] 11

EuroNOK®

FRWSamplingShaft witha shut-offvalveAccording to the EN 858 standard, a

sampling shaft always builds a part of the

oil separator system. The EuroNOK

sampling shafts make it possible to monitor

the quality of the wastewater or rainwater

that is led into the sewer system.

In a direct system the EuroNOK sampling

shaft is installed to follow the oil separator.

In the Labko Bypass System, the EuroNOK

FRW is used. The difference in the

EuroNOK FRW is that the bypass-pipe is

connected back to the rainwater sewer.

Both the EuroNOK and the EuroNOK FRW

contain a shut-off valve that makes it

possible to close the sewer line, should an

accident occur in the area.

EuroHUKmaintenanceshaft

EuroHUK® andPP-HUK 600MaintenanceShaft

EuroNOK FRW sampling shaft with ashut-off valve.

EuroHUK maintenance shafts installed.

The EuroHUK maintenance shaft is a water-

proof solution in compliance with the oil

separator standard to go with the separators.

The EuroHUK maintenance shaft is selected

according to the installation depth of the

separator.

Since the maintenance shaft is light in its

weight, the installation goes fast. Except for

the smallest model, all the shafts have steps

inside to ease the maintenance. A special-

shaped gasket, which is delivered with the

maintenance shaft, guarantees that the sep-

arator and the shaft are compatible and that

their junction is tight.

PP-HUK 600 maintenance shafts are used

with EuroPEK Filter oil separators to ease the

maintenance of their filters. PP-HUK 600 is

a waterproof solution in compliance with the

oil separator standard to go with the separa-

tors.

Cast iron covers and frames are available as

accessories for the maintenance shafts. They

are chosen according to the traffic load on

the site.

EuroPEK®

Filter OilSeparator

EuroPEK Filter is a class I oil separator.

It is designed and tested according to the

requirements of the EN 858 standard. The

cleaning capacity of the EuroPEK Filter is

based on a coalescent 3-D filter. There are

1-4 filters in each separator, depending on

the model. EuroPEK Filter separators are

made of reinforced plastic and they are

available in size classes NS20-NS150.

EuroPEK Filter separators are designed for

areas with only a low quantity of solids and

oils in the rainwater.

As a standard, an ATEX-approved SET-

2000 oil alarm is included in the EuroPEK

Filter oil separator. The oil alarm signals,

not only when emptying is needed, but in

case of blocking, too. Further information

on the alarm device and data transfer can

be found on page 12.

The superb cleaning efficiency of theEuroPEK Filter oil separators is verifiedby flow tests run in compliance with theEN 858 standard.

PP-HUK 600maintenanceshaft

A special-shapedgasket guaranteesthe standard-complianttightnessof the main-tenanceshaft.

Page 11: Wavin Labko Oil Separator System

SET-2000oil alarm

SandSET-1000sludge alarm

Labko FRWFlow RegulationWell

EuroHEK sandand sludge trap

EuroPEK Filteroil separator

EuroNOK FRWsampling shaft witha shut-off valve

Labko® Oil Separator SystemsEuroPEK

® Filter oil separator

Labko® Oil Separator Systems

Labko® Oil Separator SystemsEuroNOK

® FRW sampling shaft with a shut-off valve • EuroHUK

® maintenance shaft • PP-HUK 600 maintenance shaft

Separators and tankswww.wavin-labko.fiTEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected] 11

EuroNOK®

FRWSamplingShaft witha shut-offvalveAccording to the EN 858 standard, a

sampling shaft always builds a part of the

oil separator system. The EuroNOK

sampling shafts make it possible to monitor

the quality of the wastewater or rainwater

that is led into the sewer system.

In a direct system the EuroNOK sampling

shaft is installed to follow the oil separator.

In the Labko Bypass System, the EuroNOK

FRW is used. The difference in the

EuroNOK FRW is that the bypass-pipe is

connected back to the rainwater sewer.

Both the EuroNOK and the EuroNOK FRW

contain a shut-off valve that makes it

possible to close the sewer line, should an

accident occur in the area.

EuroHUKmaintenanceshaft

EuroHUK® andPP-HUK 600MaintenanceShaft

EuroNOK FRW sampling shaft with ashut-off valve.

EuroHUK maintenance shafts installed.

The EuroHUK maintenance shaft is a water-

proof solution in compliance with the oil

separator standard to go with the separators.

The EuroHUK maintenance shaft is selected

according to the installation depth of the

separator.

Since the maintenance shaft is light in its

weight, the installation goes fast. Except for

the smallest model, all the shafts have steps

inside to ease the maintenance. A special-

shaped gasket, which is delivered with the

maintenance shaft, guarantees that the sep-

arator and the shaft are compatible and that

their junction is tight.

PP-HUK 600 maintenance shafts are used

with EuroPEK Filter oil separators to ease the

maintenance of their filters. PP-HUK 600 is

a waterproof solution in compliance with the

oil separator standard to go with the separa-

tors.

Cast iron covers and frames are available as

accessories for the maintenance shafts. They

are chosen according to the traffic load on

the site.

EuroPEK®

Filter OilSeparator

EuroPEK Filter is a class I oil separator.

It is designed and tested according to the

requirements of the EN 858 standard. The

cleaning capacity of the EuroPEK Filter is

based on a coalescent 3-D filter. There are

1-4 filters in each separator, depending on

the model. EuroPEK Filter separators are

made of reinforced plastic and they are

available in size classes NS20-NS150.

EuroPEK Filter separators are designed for

areas with only a low quantity of solids and

oils in the rainwater.

As a standard, an ATEX-approved SET-

2000 oil alarm is included in the EuroPEK

Filter oil separator. The oil alarm signals,

not only when emptying is needed, but in

case of blocking, too. Further information

on the alarm device and data transfer can

be found on page 12.

The superb cleaning efficiency of theEuroPEK Filter oil separators is verifiedby flow tests run in compliance with theEN 858 standard.

PP-HUK 600maintenanceshaft

A special-shapedgasket guaranteesthe standard-complianttightnessof the main-tenanceshaft.

Page 12: Wavin Labko Oil Separator System

Labko® Oil Separator SystemsAlarm devices • Data transfer • LabkoNet

®

Labko® Oil Separator Systems

Labko® Oil Separator SystemsLabko® FRW Flow Regulation Wells • EuroHEK

® sand and sludge traps

Separators and tankswww.wavin-labko.fi

Alarm devices andremote monitoring

TEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected]

Alarm systems monitoringthe functioning of the separatorsAll the separators of Wavin-Labko can be equipped with alarm

units that control the functioning of the separator. Most separators

include the alarm devices as a standard. The alarm can be

transmitted directly to the user's house automation system or with

the Labcom communication unit to a GSM phone. Furthermore,

the alarm can be transmitted via LabkoNet server to those who

find the information is essential. When the separators are remotely

monitored, timely emptying is made possible, and thus the

environmental risks are minimized and costs are lowered.

LegendA = area of the yard (0.015 l/(s*m2))Du = outer diameterDu1/Du2 = inner diameterDy = outer diameter of the ventilation pipe (accessory)Dy1/Dy2 = outer diameter of the connection pipeH1/H2/H3/H4 = height

Labko FRW Flow Regulation Wells

12 13

Data transferand LabkoNet®

Labcom 200 communication unit transfersthe alarm directly to the recipientLabcom 200 sends alarms and measurement data as GSM short

messages either directly to the user's own mobile phone or via

LabkoNet system. The LabkoNet system makes sure the information

is delivered to the user, for the server also controls the functioning

of the communication unit.

LabkoNet system is an easy and reliable wayof transferring and controlling the alarm dataIntroducing and using the LabkoNet system is easy; no separate

software is needed. Only an Internet connection, Labcom 200

communication unit, gauges and alarm devices are needed. In

addition to the separator alarms, e.g. storage tank level gauging

can be connected with the LabkoNet.

For further information on LabkoNet and its possibilities,

visit www.labkonet.comEuroHEK 600...1500 sand andsludge traps

LabkoNet serverCollects the alarms and adaptstheir information to be sent furthereither as a short message or asan e-mail. The data is displayedon user's own web page, too.

LabkoNet serviceLabkoNet server collects and logs data in the Internet and it isapplicable with different user names and passwords to meetdifferent needs. Among other things, the service provides reportsas printouts.

E-mailLabkoNet can also sendthe alarm as an e-mailmessage.

OilSET-1000 oil alarmIndicates an alarm if the oil storagespace is full and it is time foremptying. This prevents leakagesinto the sewer system.

Labko Nominal Total flow A Du Du1 Dy Dy1 Dy2 H1 H2 H3 H4 h* WeightFRW flow into the of the

separator systeml/s l/s m2 mm mm mm mm mm mm mm mm mm kg

FRW 10/30 10 30 2000 1780 800 110 200 160 750 700 900 1660 187FRW 15/45 15 45 3000 1780 800 110 250 200 750 700 900 1660 188FRW 20/60 20 60 4000 1780 800 110 250 200 750 700 900 1660 191FRW 30/90 30 90 6000 1780 800 110 315 250 750 700 940 1660 211FRW 40/120 40 120 8000 1780 800 110 315 315 650 600 850 1660 225FRW 50/150 50 150 10000 1780 800 110 400 315 650 600 810 1660 232FRW 65/195 65 195 13000 2170 800 110 400 315 950 900 1090 2100 321FRW 80/240 80 240 16000 2170 800 110 500 315 950 900 1150 2100 391FRW 100/300 100 300 20000 2250 800 110 500 315 950 900 1150 2200 407FRW 125/375 125 375 25000 2200 800 110 500 400 475 500 475 1785FRW 150/450 150 450 30000 2200 800 110 *** 400 475 500 475 1785*** according to the delivery Dy1 500 or Dy1 600.EuroHUK 800 FRW 10/30 - 50/150 FRW 65/195 - 100/300 FRW 125/375 - 150/450for FRW h* (mm) h* (mm) h* (mm)9-13 1300-1700 1700-2100 2100-250013-17 1700-2100 2100-2500 2500-290017-21 2100-2500 2500-2900 2900-340021-25 2500-2900 2900-3400 3400-3900

L = lengthh = installation depthV = effective volumeVo = oil storage volumeVs = sludge storage volumeLkm = number of the coalescent 3-D filters

EuroHEK Omega sand andsludge traps

EuroHEK 6500...8000 sand andsludge traps

Dy

Nominal size10/30...100/300

Nominal size125/375...150/450

L

SandSET-1000 sludge alarm deviceIndicates an alarm when the sludge storage space is full.The timely desludging reduces unnecessary emptying andguarantees the smooth operation of the oil separator.

Labcom 200communication unitA data transfer unitdesigned for transmittingmeasurement andalarm data.

EuroHEK Du Du1 Dy Dy1 H1 H2 H3 h V Weight mm mm mm mm mm mm mm mm l kg

600 h 9-13 1000 600 110 110...250 870 850 2070 900...1300 600 91h 13-17 2470 1300...1700 106h 17-21 2870 1700...2100 122h 21-25 3270 2100...2500 137

1000 h 9-13 1400 600 110 110...250 870 850 2070 900...1300 1000 151h 13-17 2470 1300...1700 175h 17-21 2870 1700...2100 199h 21-25 3270 2100...2500 223

1500 h 9-13 1400 600 110 110...250 1410 1340 2610 900...1300 1500 183h 13-17 3010 1300...1700 207h 17-21 3410 1700...2100 231h 21-25 3810 2100...2500 255

SandSET-1000 sludge alarm as an accessory.

EuroHEK Omega Du Du1 Dy Dy1 H1 H2 H3 h* V Weightmm mm mm mm mm mm mm l kg

2000 1750 600 110 110...200 1280 1200 1650 2000 1704000 2170 600 110 110...200 1730 1650 2100 4000 2305000 2200 600 110 110...200 1820 1730 2250 5000 280* For further information on EuroHUK 600: table on page 15.SandSET-1000 sludge alarm as an accessory.

EuroHEK Du1 Du2 Dy Dy1 H1 H2 H3 L h* V Weightmm mm mm mm mm mm mm mm l kg

6500 600 1600 110 110...400 1410 1360 1860 4000 6500 3968000 600 1600 110 110...400 1410 1360 1860 4900 8000 513* For further information on PP-HUK 600: table on page 15.SandSET-1000 sludge alarm as an accessory.

SET-2000oil alarmGives an alarm ifthe oil storage spaceis full or if the watersurface level risesindicating the needfor filter maintenance.

www.labkonet.com

Lookat livedemo

GSM short messagesThe alarm can be transmitted to theuser's GSM either directly withLabcom 200 communication unit orvia LabkoNet server.

Page 13: Wavin Labko Oil Separator System

Labko® Oil Separator SystemsAlarm devices • Data transfer • LabkoNet

®

Labko® Oil Separator Systems

Labko® Oil Separator SystemsLabko® FRW Flow Regulation Wells • EuroHEK

® sand and sludge traps

Separators and tankswww.wavin-labko.fi

Alarm devices andremote monitoring

TEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected]

Alarm systems monitoringthe functioning of the separatorsAll the separators of Wavin-Labko can be equipped with alarm

units that control the functioning of the separator. Most separators

include the alarm devices as a standard. The alarm can be

transmitted directly to the user's house automation system or with

the Labcom communication unit to a GSM phone. Furthermore,

the alarm can be transmitted via LabkoNet server to those who

find the information is essential. When the separators are remotely

monitored, timely emptying is made possible, and thus the

environmental risks are minimized and costs are lowered.

LegendA = area of the yard (0.015 l/(s*m2))Du = outer diameterDu1/Du2 = inner diameterDy = outer diameter of the ventilation pipe (accessory)Dy1/Dy2 = outer diameter of the connection pipeH1/H2/H3/H4 = height

Labko FRW Flow Regulation Wells

12 13

Data transferand LabkoNet®

Labcom 200 communication unit transfersthe alarm directly to the recipientLabcom 200 sends alarms and measurement data as GSM short

messages either directly to the user's own mobile phone or via

LabkoNet system. The LabkoNet system makes sure the information

is delivered to the user, for the server also controls the functioning

of the communication unit.

LabkoNet system is an easy and reliable wayof transferring and controlling the alarm dataIntroducing and using the LabkoNet system is easy; no separate

software is needed. Only an Internet connection, Labcom 200

communication unit, gauges and alarm devices are needed. In

addition to the separator alarms, e.g. storage tank level gauging

can be connected with the LabkoNet.

For further information on LabkoNet and its possibilities,

visit www.labkonet.comEuroHEK 600...1500 sand andsludge traps

LabkoNet serverCollects the alarms and adaptstheir information to be sent furthereither as a short message or asan e-mail. The data is displayedon user's own web page, too.

LabkoNet serviceLabkoNet server collects and logs data in the Internet and it isapplicable with different user names and passwords to meetdifferent needs. Among other things, the service provides reportsas printouts.

E-mailLabkoNet can also sendthe alarm as an e-mailmessage.

OilSET-1000 oil alarmIndicates an alarm if the oil storagespace is full and it is time foremptying. This prevents leakagesinto the sewer system.

Labko Nominal Total flow A Du Du1 Dy Dy1 Dy2 H1 H2 H3 H4 h* WeightFRW flow into the of the

separator systeml/s l/s m2 mm mm mm mm mm mm mm mm mm kg

FRW 10/30 10 30 2000 1780 800 110 200 160 750 700 900 1660 187FRW 15/45 15 45 3000 1780 800 110 250 200 750 700 900 1660 188FRW 20/60 20 60 4000 1780 800 110 250 200 750 700 900 1660 191FRW 30/90 30 90 6000 1780 800 110 315 250 750 700 940 1660 211FRW 40/120 40 120 8000 1780 800 110 315 315 650 600 850 1660 225FRW 50/150 50 150 10000 1780 800 110 400 315 650 600 810 1660 232FRW 65/195 65 195 13000 2170 800 110 400 315 950 900 1090 2100 321FRW 80/240 80 240 16000 2170 800 110 500 315 950 900 1150 2100 391FRW 100/300 100 300 20000 2250 800 110 500 315 950 900 1150 2200 407FRW 125/375 125 375 25000 2200 800 110 500 400 475 500 475 1785FRW 150/450 150 450 30000 2200 800 110 *** 400 475 500 475 1785* For further information on EuroHUK 800: table below. *** According to the delivery Dy1 500 or Dy1 600.EuroHUK 800 FRW 10/30 - 50/150 FRW 65/195 - 100/300 FRW 125/375 - 150/450for FRW h (mm) h (mm) h (mm)9-13 1300-1700 1700-2100 2100-250013-17 1700-2100 2100-2500 2500-290017-21 2100-2500 2500-2900 2900-340021-25 2500-2900 2900-3400 3400-3900

L = lengthh = installation depthV = effective volumeVo = oil storage volumeVs = sludge storage volumeLkm = number of the coalescent 3-D filters

EuroHEK Omega sand andsludge traps

EuroHEK 6500...8000 sand andsludge traps

Dy

Nominal size10/30...100/300

Nominal size125/375...150/450

L

SandSET-1000 sludge alarm deviceIndicates an alarm when the sludge storage space is full.The timely desludging reduces unnecessary emptying andguarantees the smooth operation of the oil separator.

Labcom 200communication unitA data transfer unitdesigned for transmittingmeasurement andalarm data.

EuroHEK Du Du1 Dy Dy1 H1 H2 H3 h V Weight mm mm mm mm mm mm mm mm l kg

600 h 9-13 1000 600 110 110...250 870 850 2070 900...1300 600 91h 13-17 2470 1300...1700 106h 17-21 2870 1700...2100 122h 21-25 3270 2100...2500 137

1000 h 9-13 1400 600 110 110...250 870 850 2070 900...1300 1000 151h 13-17 2470 1300...1700 175h 17-21 2870 1700...2100 199h 21-25 3270 2100...2500 223

1500 h 9-13 1400 600 110 110...250 1410 1340 2610 900...1300 1500 183h 13-17 3010 1300...1700 207h 17-21 3410 1700...2100 231h 21-25 3810 2100...2500 255

SandSET-1000 sludge alarm as an accessory.

EuroHEK Omega Du Du1 Dy Dy1 H1 H2 H3 h* V Weightmm mm mm mm mm mm mm l kg

2000 1750 600 110 110...200 1280 1200 1650 2000 1704000 2170 600 110 110...200 1730 1650 2100 4000 2305000 2200 600 110 110...200 1820 1730 2250 5000 280* For further information on EuroHUK 600: table on page 15.SandSET-1000 sludge alarm as an accessory.

EuroHEK Du1 Du2 Dy Dy1 H1 H2 H3 L h* V Weightmm mm mm mm mm mm mm mm l kg

6500 600 1600 110 110...400 1410 1360 1860 4000 6500 3968000 600 1600 110 110...400 1410 1360 1860 4900 8000 513* For further information on PP-HUK 600: table on page 15.SandSET-1000 sludge alarm as an accessory.

SET-2000oil alarmGives an alarm ifthe oil storage spaceis full or if the watersurface level risesindicating the needfor filter maintenance.

www.labkonet.com

Lookat livedemo

GSM short messagesThe alarm can be transmitted to theuser's GSM either directly withLabcom 200 communication unit orvia LabkoNet server.

Page 14: Wavin Labko Oil Separator System

Labko® Oil Separator SystemsEuroHEK

® sand and sludge traps • EuroPEK

® oil separators

Labko® Oil Separator Systems

Labko® Oil Separator SystemsEuroNOK

® FRW sampling shafts with a shut-off valve • EuroHUK

® maintenance shafts • PP-HUK 600 maintenance shafts

Separators and tankswww.wavin-labko.fiTEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected] 15

EuroHEK 10000...50000 sand andsludge traps

EuroPEK oil separators

EuroPEK Filter oil separators

EuroPEK Omega Filteroil separators

EuroHEK Du1 Du2 Dy Dy1 H1 H2 H3 L h* V Weight mm mm mm mm mm mm mm mm l kg

10000 600 1600 110 110...400 1410 1360 1950 6100 10000 62013000 600 2200 110 110...400 1930 1880 2550 4400 13000 70315000 600 2200 110 110...400 1930 1880 2550 4900 15000 77416000 600 2200 110 110...400 1930 1880 2550 5200 16000 81720000 600 2200 110 110...400 1930 1880 2550 6400 20000 99730000 600 3000 110 110...400 2650 2600 3360 5400 30000 200040000 600 3000 110 110...400 2650 2600 3360 7000 40000 234050000 600 3000 110 110...400 2650 2600 3360 8500 50000* For further information on EuroHUK 600: table on page 15.SandSET-1000 sludge alarm as a standard.

EuroPEK Maximum Du1 Du2 Dy Dy1 H1 H2 H3 L h* V Vo Weight flow

l/s mm mm mm mm mm mm mm mm l l kgNS3 3 800 1000 110 110 860 790 1380 1950 860 250 180NS6 6 800 1000 110 160 860 790 1380 2200 1000 290 235NS10 10 800/600 1000 110 160 860 790 1380 4100 1950 550 355NS15 15 800 1400 110 200 1300 1230 1750 2800 2940 610 450NS20 20 800 1600 110 200 1410 1340 1950 3000 3930 770 600NS30 30 800/600 1600 110 250 1410 1340 1950 4000 5500 900 810NS40 40 800 2200 110 315 1940 1870 2550 3600 10000 1000 1100NS50 50 800/600 2200 110 315 1940 1870 2550 4600 13500 1500 1705NS65 65 800/600 3000 110 315 2740 2670 3360 5500 32200 1500 2500NS80 80 800/600 3000 110 315 2740 2670 3360 7300 41000 2000 2900NS100 100 800/600 3000 110 315 2740 2670 3360 7500 42000 2000NS125 125 800/600 3000 110 400 2740 2670 3360 8800 52500 2200NS150 150 800/600 3000 110 400 2740 2670 3360 10000* For further information on EuroHUK 600 and EuroHUK 800: table on page 15.OilSET-1000 oil alarm as a standard.

EuroPEK Maximum Du Du1 Dy Dy1 H1 H2 H3 h* V Vo Vs WeightOmega Filter flow

l/s mm mm mm mm mm mm mm l l l kgNS3/L 3 1780 600 110 110 1300 1220 1650 2100 280 950 170NS6/S 6 1780 600 110 160 1300 1220 1650 2100 280 650 170NS10 10 1780 600 110 160 1300 1220 1650 2100 280 separate 170NS15 15 2170 600 110 200 1730 1650 2100 4200 380 separate 240* For further information on EuroHUK 600: table on page 15.SET-2000 oil alarm as a standard.

EuroPEK Maximum Du1 Du2 Dy Dy1 H1 H2 H3 L h* V Vo Lkm WeightFilter flow

l/s mm mm mm mm mm mm mm mm l l pcs kgNS20 20 600 1600 110 250 1410 1340 1950 3800 6000 640 1 500NS30 30 600 1600 110 250 1410 1340 1950 3800 6000 640 2 550NS40 40 600 1600 110 315 1410 1340 1950 3800 6000 640 2 560NS50 50 600 1600 110 315 1360 1290 1950 5300 8700 1000 3 750NS65 65 600 2200 110 315 1940 1870 2550 4100 13000 900 3 1350NS80 80 600 2200 110 315 1940 1870 2550 5900 19200 1400 4 1750NS100 100 600 2200 110 400 1940 1870 2550 8700 28000 2100 4 2400NS125 125 600 2200 110 400 1940 1870 2550 11400 37100 3070 4 3000NS150 150 600 2200 110 400 1940 1870 2550 13000 42500 3520 4 3450* For further information on EuroHUK 600 and PP-HUK 600: table on page 15.SET-2000 oil alarm as a standard.

Dy

EuroNOK FRW sampling shaftswith a shut-off valve

EuroNOK sampling shaftswith a shut-off valve

EuroNOK FRW Du Du1 Dy Dy1 Dy2 H1 H2 H3 H4 h* Weight mm mm 110 mm mm mm mm mm mm kg

10/30 1300 600 110 200 160 440 410 950 54015/45 1300 600 110 250 200 440 410 950 54020/60 1300 600 110 250 200 440 410 950 54030/90 1300 600 110 315 250 440 410 950 54040/120** 1400 600 110 315 315 440 410 1390 54050/150** 1400 600 110 400 315 440 410 1390 54065/195** 1400 600 110 400 315 440 410 1390 54080/240** 1400 800 110 500 315 440 410 1390 540100/300** 1400 800 110 500 315 440 410 1390 540125/375** 1400 800 110 500 400 440 410 1390 540150/450** 1400 800 110 *** 400 440 410 1390 540* For further information on EuroHUK 600 and EuroHUK 800: table on page 15.** minimum installation depth h=1300 mm.*** according to the delivery Dy1 500 or Dy1 600.

EuroNOK Du Du1 Dy Dy1 H1 H2 H3 h* Weightmm mm mm mm mm mm mm kg

DN110 1300 600 110 110 440 410 950 80DN160 1300 600 110 160 440 410 950 84DN200 1300 600 110 200 440 410 950 101DN250 1300 600 110 250 440 410 950 124DN315 1300 600 110 315 440 410 950 155DN400** 1560 600 110 400 440 410 1310* For further information on EuroHUK 600: table on page 15.** minimum installation depth h=1300 mm.

EuroHUK 600 Du1 Du2 h Weightmm mm mm kg

9-13 600 1000 900...1300 2213-17 600 1000 1300...1700 3817-21 600 1000 1700...2100 5621-25 600 1000 2100...2500 80A suitable cover and frame set is the floating cover and frame set 600.

EuroHUK 800 Du1 Du2 h Weightmm mm mm kg

9-13 800 1000 900...1300 2513-17 800 1000 1300...1700 4217-21 800 1000 1700...2100 6021-25 800 1000 2100...2500 84A suitable cover and frame set is the floating cover and frame set 800.

PP-HUK 600 Du Du1 L h* Weightmm mm mm mm kg

9-13 670 602 1000 900...1300 1613-17 670 602 1400 1300...1700 2017-21 670 602 1800 1700...2100 2521-25 670 602 2200 2100...2500 31* connection depth of the separator from the ground surface to the water flow of the inlet.A suitable cover and frame set is the floating cover and frame set 600.

EuroHUK 600 and 800maintenance shafts

PP-HUK 600 maintenance shafts

Dy

L

L

Nominal size10/30...100/300

Nominal size125/375...150/450

L

Page 15: Wavin Labko Oil Separator System

Labko® Oil Separator SystemsEuroHEK

® sand and sludge traps • EuroPEK

® oil separators

Labko® Oil Separator Systems

Labko® Oil Separator SystemsEuroNOK

® FRW sampling shafts with a shut-off valve • EuroHUK

® maintenance shafts • PP-HUK 600 maintenance shafts

Separators and tankswww.wavin-labko.fiTEL. INT.+358 20 1285 200

FAX INT.+358 20 1285 280

[email protected] 15

EuroHEK 10000...50000 sand andsludge traps

EuroPEK oil separators

EuroPEK Filter oil separators

EuroPEK Omega Filteroil separators

EuroHEK Du1 Du2 Dy Dy1 H1 H2 H3 L h* V Weight mm mm mm mm mm mm mm mm l kg

10000 600 1600 110 110...400 1410 1360 1950 6100 10000 62013000 600 2200 110 110...400 1930 1880 2550 4400 13000 70315000 600 2200 110 110...400 1930 1880 2550 4900 15000 77416000 600 2200 110 110...400 1930 1880 2550 5200 16000 81720000 600 2200 110 110...400 1930 1880 2550 6400 20000 99730000 600 3000 110 110...400 2650 2600 3360 5400 30000 200040000 600 3000 110 110...400 2650 2600 3360 7000 40000 234050000 600 3000 110 110...400 2650 2600 3360 8500 50000* For further information on EuroHUK 600: table on page 15.SandSET-1000 sludge alarm as a standard.

EuroPEK Maximum Du1 Du2 Dy Dy1 H1 H2 H3 L h* V Vo Weight flow

l/s mm mm mm mm mm mm mm mm l l kgNS3 3 800 1000 110 110 860 790 1380 1950 860 250 180NS6 6 800 1000 110 160 860 790 1380 2200 1000 290 235NS10 10 800/600 1000 110 160 860 790 1380 4100 1950 550 355NS15 15 800 1400 110 200 1300 1230 1750 2800 2940 610 450NS20 20 800 1600 110 200 1410 1340 1950 3000 3930 770 600NS30 30 800/600 1600 110 250 1410 1340 1950 4000 5500 900 810NS40 40 800 2200 110 315 1940 1870 2550 3600 10000 1000 1100NS50 50 800/600 2200 110 315 1940 1870 2550 4600 13500 1500 1705NS65 65 800/600 3000 110 315 2740 2670 3360 5500 32200 1500 2500NS80 80 800/600 3000 110 315 2740 2670 3360 7300 41000 2000 2900NS100 100 800/600 3000 110 315 2740 2670 3360 7500 42000 2000NS125 125 800/600 3000 110 400 2740 2670 3360 8800 52500 2200NS150 150 800/600 3000 110 400 2740 2670 3360 10000* For further information on EuroHUK 600 and EuroHUK 800: table on page 15.OilSET-1000 oil alarm as a standard.

EuroPEK Maximum Du Du1 Dy Dy1 H1 H2 H3 h* V Vo Vs WeightOmega Filter flow

l/s mm mm mm mm mm mm mm l l l kgNS3/L 3 1780 600 110 110 1300 1220 1650 2100 280 950 170NS6/S 6 1780 600 110 160 1300 1220 1650 2100 280 650 170NS10 10 1780 600 110 160 1300 1220 1650 2100 280 separate 170NS15 15 2170 600 110 200 1730 1650 2100 4200 380 separate 240* For further information on EuroHUK 600: table on page 15.SET-2000 oil alarm as a standard.

EuroPEK Maximum Du1 Du2 Dy Dy1 H1 H2 H3 L h* V Vo Lkm WeightFilter flow

l/s mm mm mm mm mm mm mm mm l l pcs kgNS20 20 600 1600 110 250 1410 1340 1950 3800 6000 640 1 500NS30 30 600 1600 110 250 1410 1340 1950 3800 6000 640 2 550NS40 40 600 1600 110 315 1410 1340 1950 3800 6000 640 2 560NS50 50 600 1600 110 315 1360 1290 1950 5300 8700 1000 3 750NS65 65 600 2200 110 315 1940 1870 2550 4100 13000 900 3 1350NS80 80 600 2200 110 315 1940 1870 2550 5900 19200 1400 4 1750NS100 100 600 2200 110 400 1940 1870 2550 8700 28000 2100 4 2400NS125 125 600 2200 110 400 1940 1870 2550 11400 37100 3070 4 3000NS150 150 600 2200 110 400 1940 1870 2550 13000 42500 3520 4 3450* For further information on EuroHUK 600 and PP-HUK 600: table on page 15.SET-2000 oil alarm as a standard.

Dy

EuroNOK FRW sampling shaftswith a shut-off valve

EuroNOK sampling shaftswith a shut-off valve

EuroNOK FRW Du Du1 Dy Dy1 Dy2 H1 H2 H3 H4 h* Weight mm mm 110 mm mm mm mm mm mm kg

10/30 1300 600 110 200 160 440 410 950 54015/45 1300 600 110 250 200 440 410 950 54020/60 1300 600 110 250 200 440 410 950 54030/90 1300 600 110 315 250 440 410 950 54040/120** 1400 600 110 315 315 440 410 1390 54050/150** 1400 600 110 400 315 440 410 1390 54065/195** 1400 600 110 400 315 440 410 1390 54080/240** 1400 800 110 500 315 440 410 1390 540100/300** 1400 800 110 500 315 440 410 1390 540125/375** 1400 800 110 500 400 440 410 1390 540150/450** 1400 800 110 *** 400 440 410 1390 540* For further information on EuroHUK 600 and EuroHUK 800: table on page 15.** minimum installation depth h=1300 mm.*** according to the delivery Dy1 500 or Dy1 600.

EuroNOK Du Du1 Dy Dy1 H1 H2 H3 h* Weightmm mm mm mm mm mm mm kg

DN110 1300 600 110 110 440 410 950 80DN160 1300 600 110 160 440 410 950 84DN200 1300 600 110 200 440 410 950 101DN250 1300 600 110 250 440 410 950 124DN315 1300 600 110 315 440 410 950 155DN400** 1560 600 110 400 440 410 1310* For further information on EuroHUK 600: table on page 15.** minimum installation depth h=1300 mm.

EuroHUK 600 Du1 Du2 h Weightmm mm mm kg

9-13 600 1000 900...1300 2213-17 600 1000 1300...1700 3817-21 600 1000 1700...2100 5621-25 600 1000 2100...2500 80A suitable cover and frame set is the floating cover and frame set 600.

EuroHUK 800 Du1 Du2 h Weightmm mm mm kg

9-13 800 1000 900...1300 2513-17 800 1000 1300...1700 4217-21 800 1000 1700...2100 6021-25 800 1000 2100...2500 84A suitable cover and frame set is the floating cover and frame set 800.

PP-HUK 600 Du Du1 L h* Weightmm mm mm mm kg

9-13 670 602 1000 900...1300 1613-17 670 602 1400 1300...1700 2017-21 670 602 1800 1700...2100 2521-25 670 602 2200 2100...2500 31* connection depth of the separator from the ground surface to the water flow of the inlet.A suitable cover and frame set is the floating cover and frame set 600.

EuroHUK 600 and 800maintenance shafts

PP-HUK 600 maintenance shafts

Dy

L

L

Nominal size10/30...100/300

Nominal size125/375...150/450

L

Page 16: Wavin Labko Oil Separator System

Reliable solutions Separators and tanks

FOR STORMWATER TREATMENTIN INDUSTRIAL, STORAGE ANDTRAFFIC AREAS

Pic

torin

o O

y/K

irjap

aino

Her

mes

1/

2006

2.

000

www.wavin-labko.fi

Wavin-Labko Ltd reserves the rights to alterations without prior notice. Due to policy of continuousimprovement in R&D, technical specifications may change. Installation shall always be made asdocumented in manufacturer's instructions.

Wavin-Labko in brief

January 2006

Wavin-Labko LtdLabkotie 1FI-36240 KangasalaFINLANDTel. int. +358 20 1285 200Fax int. +358 20 1285 280E-mail [email protected]

Labko® Oil Separator SystemsLabko® Oil Separator Systems

Wavin-Labko Ltd is a Finnish company with over 40 years'experience in developing, manufacturing and marketing ofmeasurement devices and various plastic products. In the fieldof measurement devices we are specialized in level instrumentsand alarm devices, automation and identification, and in web-based solutions of data transfer. In the field of plastic productswe have focused our know-how on wastewater and stormwatertreatment by using various separator systems. These systemscover the separator solutions in business and servicesconstruction, the wastewater treatment in rural area settlements,as well as the wastewater treatment of private houses andsummer cottages.

Wavin-Labko Ltd is a part of international Wavin Group, whichis the leader in the European market for plastic pipe systems.Wavin Group has a presence in 27 European countries.