Upload
elia
View
41
Download
1
Embed Size (px)
DESCRIPTION
WATER SOUCE SYSTEM. Content. Introduction to Water Source System General Benefit of Water Source System Product Lineup Product (WH, 5WSS, WSS) Features Handset PCB Control Algorithm Selft Diagnosis & Troubleshooting Installation. INTRODUCTION to Water Source System. - PowerPoint PPT Presentation
Citation preview
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
WATER SOUCE SYSTEMWATER SOUCE SYSTEMWATER SOUCE SYSTEMWATER SOUCE SYSTEM
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Introduction to Water Source SystemIntroduction to Water Source System
General Benefit of Water Source SystemGeneral Benefit of Water Source System
Product LineupProduct Lineup
Product (WH, 5WSS, WSS)Product (WH, 5WSS, WSS)
- FeaturesFeatures
- HandsetHandset
- PCBPCB
- Control AlgorithmControl Algorithm
- Selft Diagnosis & TroubleshootingSelft Diagnosis & Troubleshooting
InstallationInstallation
Content
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
INTRODUCTION
to
Water Source System
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Introduction:What is Water Source Heat Pump?
Finned-tube heat exchanger
Water inlet
Water outlet
4 Way Valve
Compressor
Expansion device
Water-to-refrigerant heat exchanger
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
1. Water Loop Heat Pump System
2. Ground Water Heat Pump System
3. Surface Water Heat Pump System
4. Ground Coupled Heat Pump System
Water Source System Categories
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Water Loop Heat Pump Water Loop Heat Pump
• Most common configurationMost common configuration
• Re-circulating water loopRe-circulating water loop
• Cooling tower & boilerCooling tower & boiler
Water Source System Categories
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Ground Water Heat Pump Ground Water Heat Pump
• Ground water from wellGround water from well
• Drained back to well, Drained back to well, drain, stream or lakedrain, stream or lake
• Stable throughout the yearStable throughout the year
• Limited by availability of Limited by availability of water table and aquifers in water table and aquifers in the groundthe ground
Water Source System Categories
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Surface Water Heat Pump Surface Water Heat Pump
• Open or close loopOpen or close loop
• Open – water being Open – water being returned back to source or returned back to source or draindrain
• Closed – water being re-Closed – water being re-circulated in the closed circulated in the closed looploop
• Stable throughout the yearStable throughout the year
Water Source System Categories
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Ground Coupled Water Heat Ground Coupled Water Heat Pump Pump
• HE is buried into the earthHE is buried into the earth
• Installation cost is highInstallation cost is high
• Massive & stable thermal capacityMassive & stable thermal capacity
Water Source System Categories
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Water Loop Heat Pump System
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
cooling towercooling tower
pumpspumps
plate-and-frameplate-and-frameheat exchangerheat exchanger
heat pumpsheat pumps
waterwaterdistributiondistributionlooploopboilerboiler
expansionexpansiontanktank
airairseparatorseparator
Water Loop Heat Pump System
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
32ºC32ºC[90[90ºF]ºF]
heat pumps inheat pumps incooling modecooling mode
cooling cooling tower ONtower ON
boiler offboiler off
Summer Operation Summer Operation
Water Loop Heat Pump System
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Winter Operation Winter Operation
heat pumps inheat pumps inheating modeheating mode
16ºC16ºC[60[60ºF]ºF]boiler onboiler on
cooling cooling tower OFFtower OFF
Water Loop Heat Pump System
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Water Loop Heat Pump System
Spring and Fall Operation Spring and Fall Operation
boiler offboiler off
heat pumps inheat pumps inheating modeheating mode
heat pumps inheat pumps incooling modecooling mode
cooling tower cooling tower OFFOFF
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
General Benefits of a Water Source SystemGeneral Benefits of a Water Source System
• Heat recovery offers energy savingsHeat recovery offers energy savings
• Individual space controlIndividual space control
• Performs both cooling and heatingPerforms both cooling and heating
• Flexibility – additional of heat pumpFlexibility – additional of heat pump
- Individual tenant metering
• Small amount of floor space requiredSmall amount of floor space required
• Unit failure does not affect the rest of the systemUnit failure does not affect the rest of the system
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Product Lineup & Features
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Package Type
- Horizontal WSHP, WH-B/BR series
- Vertical WSHP, WV-A/AR series
Split Type
- WSS & 5WSS series + Various Indoor
Product Lineup
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
R410A Water
Source Split, 5WSS-AR
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
5CCWS 10/15/20/25/30/40/50/60 CR5CCWS 10/15/20/25/30/40/50/60 CR5CCWS 10/15/20/25/30/40/50/60 CR5CCWS 10/15/20/25/30/40/50/60 CR
5WMWS 10/15/20/25 GR5WMWS 10/15/20/25 GR5WMWS 10/15/20/25 GR5WMWS 10/15/20/25 GR
5CKWS 20/25/30/40/50 5CKWS 20/25/30/40/50 ARAR5CKWS 20/25/30/40/50 5CKWS 20/25/30/40/50 ARAR5CKWS 10/15/20 CR5CKWS 10/15/20 CR5CKWS 10/15/20 CR5CKWS 10/15/20 CR
R410A Water Source Split
5WSS – AR Series5WSS – AR Series5WSS – AR Series5WSS – AR Series
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
1. Features 1. Features 1.1 Product Information1.1 Product Information
1.2 Wide Range of Indoor 1.2 Wide Range of Indoor 1.3 Compact & Low Height Profile1.3 Compact & Low Height Profile1.4 Less Vibration Design1.4 Less Vibration Design1.5 Zero ODP Refrigerant1.5 Zero ODP Refrigerant1.6 Part Loading Capability – Tandem Type1.6 Part Loading Capability – Tandem Type1.7 Centralize Control & Networking1.7 Centralize Control & Networking
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
R410A Water Source Split
1.1 Product Introduction1.1 Product Introduction
- Heat pump Only- Heat pump Only- Split Type- Split Type- Capacity: 2.37kW – 15.77kW- Capacity: 2.37kW – 15.77kW- 8,100 Btu/hr to 53,800 Btu/hr- 8,100 Btu/hr to 53,800 Btu/hr
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
5WSS 07/10/15/16/20/25/30/40/50/60 AR5WSS 07/10/15/16/20/25/30/40/50/60 AR5WSS 07/10/15/16/20/25/30/40/50/60 AR5WSS 07/10/15/16/20/25/30/40/50/60 AR
00 1010 2020 3030 4040 5050 6060
Btu/hr x 103Btu/hr x 103
00 2.932.93 5.865.86 8.798.79 14.6514.65 17.5917.5911.7211.72kWkW
Product NameProduct Name
R410A Water Source Split
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
1.2 Wide Range of Indoor Option1.2 Wide Range of Indoor Option
1. Features1. Features
• Wall MountedWall Mounted : 1 hp to 2.5 hp: 1 hp to 2.5 hp
• Ceiling Cassette - ACeiling Cassette - A : 2 hp to 5 hp: 2 hp to 5 hp
• Ceiling Cassette - CCeiling Cassette - C : 1 hp to 2 hp: 1 hp to 2 hp
• Ceiling ConcealedCeiling Concealed : 1 hp to 6 hp: 1 hp to 6 hp
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
1.3 Compact & Low Height Profile1.3 Compact & Low Height Profile
1. Features1. Features
~ 30% volume metric reduction
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
1.4 Less Vibration Design1.4 Less Vibration Design
1. Features1. Features
• Double isolation PanelDouble isolation Panel
• Reduce noise and vibration transmissionReduce noise and vibration transmission
Upper Panel
Lower Panel
Compressor
Grommet
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
1.5 Zero ODP Refrigerant1.5 Zero ODP Refrigerant
1. Features1. Features
- In line with Montreal Protocol.- In line with Montreal Protocol.
1.6 Part Loading Capability1.6 Part Loading Capability
- Compared to 5WSS series, 5WST series is having the part - Compared to 5WSS series, 5WST series is having the part loading capability during the low load condition, which loading capability during the low load condition, which resulting in good SEER, Seasonal EER.resulting in good SEER, Seasonal EER.
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
1.7 Centralize Control by Using NIMPC or1.7 Centralize Control by Using NIMPC or Smart Manager/ HydroIntelSmart Manager/ HydroIntel
1. Features1. Features
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
2.1 Handset 2.1 Handset
2. Handset & PCB2. Handset & PCB
WM WM : G11/G12: G11/G12
CK CK : G7/G8: G7/G8
CCCC : SLM3: SLM3
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3. Control Algorithm 3. Control Algorithm 3.1 System & Mode Selection3.1 System & Mode Selection
3.2 Features3.2 Features3.3 Operating Mode3.3 Operating Mode3.4 Protection3.4 Protection
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Modes can be selected via the value of resistor RFAN through slide Modes can be selected via the value of resistor RFAN through slide
switch.switch.
3. Control Algorithm3. Control Algorithm
3.1 System Selection – 5WMWS3.1 System Selection – 5WMWS
System ROPT2
Multi split 110K
Single 22K
DX 7K5
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Modes can be selected via the Modes can be selected via the value of resistor RMODEvalue of resistor RMODE
3.1 MODE Selection – 5WMWS3.1 MODE Selection – 5WMWS
Models Modes Defrost RMODE
AP Auto > Cool > Dry > Fan > Heat > C2.4 version 3K
AP Auto > Cool > Dry > Fan > Heat > C2.3 version 7K5
AT Auto > Cool > Dry > Fan > Heat > - 22K
EC Cool > Dry > Fan > - 110K
3. Control Algorithm3. Control Algorithm
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3. Control Algorithm3. Control Algorithm
Modes can be selected via the Modes can be selected via the value of resistor ROPT2value of resistor ROPT2
3.1 System Selection – 5CCWS & 5CKWS3.1 System Selection – 5CCWS & 5CKWS
System ROPT2
Tandem Shorted
Single 7K5
DX Open
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3. Control Algorithm3. Control Algorithm
Modes can be selected via the Modes can be selected via the value of resistor RMODEvalue of resistor RMODE
3.1 MODE Selection – 5CCWS, 5CKWS3.1 MODE Selection – 5CCWS, 5CKWS
Models Modes Defrost RMODE
AP Auto > Cool > Dry > Fan > Heat > C2.4 version 3K
AP Auto > Cool > Dry > Fan > Heat > C2.3 version 7K5
AT Auto > Cool > Dry > Fan > Heat > - 22K
EC Cool > Dry > Fan > - 110K
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.2.1 Auto Random Restart3.2.1 Auto Random Restart
• Auto random restart at the last state memory settingAuto random restart at the last state memory setting
• Shorted at Shorted at J_LSTJ_LST jumper at main board jumper at main board
• Remove the jumper to have non-auto restartRemove the jumper to have non-auto restart
3.2 Features3.2 Features
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
J_LSTJ_LST
Auto Random RestartAuto Random Restart
3.2 Features3.2 Features
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Power Up SettingsPower Up Settings
Power UpPower Up
J_LST ShortedJ_LST Shorted J_LST OpenedJ_LST Opened
User Set ModeUser Set Mode
User Set TemperatureUser Set Temperature
User Set Fan SpeedUser Set Fan Speed
Mode = COOLMode = COOL
Set Temperature = 24˚CSet Temperature = 24˚C
Fan Speed = HIGHFan Speed = HIGH
3.2 Features3.2 Features
SWING OFFSWING OFF
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.2.2 Unit ON / OFF3.2.2 Unit ON / OFF3 ways to turn on / off the system:3 ways to turn on / off the system:
(a) On/Off Triggering(a) On/Off Triggering
• Emergency On/Off ButtonEmergency On/Off Button
- System mode setting will rotate in the following - System mode setting will rotate in the following
sequencesequence
Heat pumpHeat pump …….>COOL>HEAT>OFF>…..…….>COOL>HEAT>OFF>…..
CoolingCooling …….>COOL>OFF>…….…….>COOL>OFF>…….
• On/Off button on handsetsOn/Off button on handsets
3.2 Features3.2 Features
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.2 Features
3.2.2 Unit ON / OFF3.2.2 Unit ON / OFF
(b) Delay timer(b) Delay timer
• Pressing the On/Off will reset the timer to 0 hour Pressing the On/Off will reset the timer to 0 hour
(c) Real time On/Off Timer(c) Real time On/Off Timer
• Based on internal real time clockBased on internal real time clock
• The timer settings are kept so that similar switches can The timer settings are kept so that similar switches can occur 24 hours later. occur 24 hours later.
• If emergency ON/OFF switch being press, then the timer If emergency ON/OFF switch being press, then the timer will be reset. will be reset.
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.2 Features
3.2.3 Sleep Function3.2.3 Sleep Function
• Only available for COOL, HEAT & AUTO mode Only available for COOL, HEAT & AUTO mode
• This function will increase (cooling mode) or decrease This function will increase (cooling mode) or decrease (Heating mode) the set temperature with time(Heating mode) the set temperature with time
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.2.3 Sleep Function (Cool Mode) 3.2.3 Sleep Function (Cool Mode)
SLEEP set onSLEEP set on SLEEP set offSLEEP set off
TsTs
Ts + 1/2Ts + 1/2
Ts + 1Ts + 1
Ts + 2Ts + 2
00 1/21/2 11 22
HoursHours
3.2 Features
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.2 Features
SLEEP set onSLEEP set on SLEEP set offSLEEP set off
TsTs
Ts - 3Ts - 3
Ts - 2Ts - 2
Ts - 1Ts - 1
00 1/21/2 11 22 HoursHours
3.2.3 Sleep Function (Heat Mode) 3.2.3 Sleep Function (Heat Mode)
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• Indoor fan speeds are Indoor fan speeds are LOW, MEDIUM, HIGHLOW, MEDIUM, HIGH or or AUTO FANAUTO FAN in in
COOL, HEATCOOL, HEAT and and AUTOAUTO modes. modes.
• In In FAN modeFAN mode, only , only HIGH, MEDIUMHIGH, MEDIUM and and LOW LOW speeds are speeds are allowed.allowed.
3.2 Features
3.2.4 Indoor Fan Control3.2.4 Indoor Fan Control
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• The IONIZER can be turned ON when indoor fan is ON.
• The IONIZER will OFF when indoor fan is OFF.
3.2 Features
3.2.5 IONIZER Control3.2.5 IONIZER Control
IonizerIonizer
CapacitorCapacitor
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• Available in COOL, HEAT and DRY modes only.
• When TURBO function is set, indoor fan will force to HIGH for
20 minutes and working temperature for
- Cooling Cycle is Ts – 2˚C
- Heating Cycle is Ts + 2˚C
3.2 Features
3.2.6 TURBO Function3.2.6 TURBO Function
• If TURBO & Sleep function activated, Sleep function timer will
reset until TURBO function is clear.
Set Temperature
20min 30min
TURBO Function
Conventional
Time
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3. Operating Mode 3.3. Operating Mode
3.3.1 Cool Mode 3.3.1 Cool Mode
3.3.2 Heat Mode3.3.2 Heat Mode
3.3.3 Auto Fan3.3.3 Auto Fan
3.3.4 AUTO Mode3.3.4 AUTO Mode
3.3.5 Defrost Function3.3.5 Defrost Function
3.3.6 Dry Mode3.3.6 Dry Mode
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• Compressor will cut in if Tr – Ts > 0.5˚C
• Compressor will cut out if Tr < Ts – 1.0˚C
Note: Tr = Room Temperature
Ts = Set Temperature
3.3 Operating Modes
3.3.1 Cool Mode 3.3.1 Cool Mode
24C 25C 26C22C 23C
24.5C23C
ONOFF
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3 Operating Modes
• Compressor will cut in if Tr – Ts < 1.0˚C
• Compressor will cut out if Tr –Ts > 3.5˚C
Note: Tr = Room Temperature
Ts = Set Temperature
3.3.2.1 Heat Pump Model3.3.2.1 Heat Pump Model
24C 25C 26C22C 23C
27.5C23C
OFFON
27C
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• The indoor fan speed modulate according to the Tin coil:
- If Tin coil > 40˚C, indoor fan run at user set speed
- If Tin coil < 18˚C, indoor fan stop
- If Tin coil crosses 30˚C, indoor fan change to low speed
Note : TNote : Tin coilin coil = Indoor Coil Temperature = Indoor Coil Temperature
3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.2 Hot Start3.3.2.2 Hot Start
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• 2 selection available at the slide switch – ON/OFF 2 selection available at the slide switch – ON/OFF
• Factory Preset at Factory Preset at OFFOFF option option
3.3 Operating Modes3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.3 Hot Keep3.3.2.3 Hot Keep
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
When compressor cuts out, the indoor fan will runs When compressor cuts out, the indoor fan will runs according according
to hot keep options.to hot keep options.
There are 2 options of Hot Keep:There are 2 options of Hot Keep:
(a) Fan On Option(a) Fan On Option
(b) Fan Off Option (b) Fan Off Option
3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.3 Hot Keep3.3.2.3 Hot Keep
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
(a) Fan On Option (a) Fan On Option
• Thermostat Cycle Cut OFFThermostat Cycle Cut OFF
- If T- If Tin coilin coil > 40 > 40˚C, indoor fan run at set speed˚C, indoor fan run at set speed
- If T- If Tin coilin coil crosses 37˚C, indoor fan run at low speed crosses 37˚C, indoor fan run at low speed
- If T- If Tin coilin coil < 18˚C, indoor fan stop < 18˚C, indoor fan stop
3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.3 Hot Keep3.3.2.3 Hot Keep
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
(b) Fan Off Option(b) Fan Off Option
• If TIf Tin coilin coil > 40 > 40˚C, indoor fan run at set speed˚C, indoor fan run at set speed
• If TIf Tin coilin coil crosses 37˚C, indoor fan run at low speed crosses 37˚C, indoor fan run at low speed
• If TIf Tin coilin coil < 30˚C, indoor fan stop < 30˚C, indoor fan stop
3.3 Operating Modes3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.3 Hot Keep3.3.2.3 Hot Keep
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• To run heat mode, 4-way valve MUST turn ON.To run heat mode, 4-way valve MUST turn ON.
• 4-way valve can only be changed from ON to OFF or vice-4-way valve can only be changed from ON to OFF or vice-versaversa
55 +/- 5 seconds after the compressor has cut out.55 +/- 5 seconds after the compressor has cut out.
• Compressor cut in after 4s.Compressor cut in after 4s.
3.3 Operating Modes3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.4 4-Way valve Changing3.3.2.4 4-Way valve Changing
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• Cool ModeCool Mode
3.3 Operating Modes3.3 Operating Modes
3.3.3 Auto Fan 3.3.3 Auto Fan
AUTO Fan Speed during COOL modeAUTO Fan Speed during COOL mode
H M L M H M L L M HH M L M H M L L M H
COMP ON COMP OFF COMP ONCOMP ON COMP OFF COMP ON
+1.5+1.5+1.0+1.0+0.5+0.5TTss
-0.5-0.5-1.0-1.0
ooCCTTrr
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• Heat ModeHeat Mode
3.3 Operating Modes3.3 Operating Modes
3.3.3 Auto Fan 3.3.3 Auto Fan
TTrr AUTO Fan Speed during HEAT modeAUTO Fan Speed during HEAT mode
M H M L M H M LM H M L M H M L
+3.5+3.5+3.0+3.0
+2.0+2.0
+1.0+1.0
TTss
ooCC
COMPCOMPOFFOFF
COMP ONCOMP ONCOMP COMP OFFOFF
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Under Auto mode, COOL & HEAT mode can be changed Under Auto mode, COOL & HEAT mode can be changed
automatically depending on room & set temperature.automatically depending on room & set temperature.
3.3 Operating Modes3.3 Operating Modes
3.3.4 AUTO Mode 3.3.4 AUTO Mode
COOLCOOL HEATHEAT
I)I) TTrr <= T <= Tss - 3.5°C AND - 3.5°C AND
II)II) The compressor has cut out for at least 10 minThe compressor has cut out for at least 10 min..
IFIF
(a) If the present Auto mode is COOL,(a) If the present Auto mode is COOL, ( Mode Set Temperature = User Set Temperature)( Mode Set Temperature = User Set Temperature)
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.4 AUTO Mode 3.3.4 AUTO Mode
(b) If the present Auto mode is HEAT,(b) If the present Auto mode is HEAT, ( Mode Set Temperature = User Set Temperature)( Mode Set Temperature = User Set Temperature)
HEATHEAT COOLCOOL
IFIF
I)I) TTrr > T > Tss + 3°C AND + 3°C AND
II)II) The compressor has cut out for at least 10 minThe compressor has cut out for at least 10 min..
3.3 Operating Modes3.3 Operating Modes
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.5 Defrost Mode 3.3.5 Defrost Mode
• Can only be operate through HEAT modeCan only be operate through HEAT mode
• ‘ ‘Defrost Timer’ start counting when the OD coil sensor measuredDefrost Timer’ start counting when the OD coil sensor measured below +3 below +3 ooC C
• Upon crossing + 5 Upon crossing + 5 ooC to a higher temperature for 150 seconds,C to a higher temperature for 150 seconds, the timer will be reset (this timer is also reset after defrost mode)the timer will be reset (this timer is also reset after defrost mode)
• The temperature sensing can only be done when the compressor The temperature sensing can only be done when the compressor run time > 2 minutes run time > 2 minutes
3.3 Operating Modes3.3 Operating Modes
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.5 Defrost Mode 3.3.5 Defrost Mode The likelihood of ice The likelihood of ice frosting:frosting:
0 1/2 1 2Hours
ooCC+3+2
0
-2
-4
-6
-8 Defrost Mode trigger if >3 Defrost Mode trigger if >3 minmin
ToTo
3.3 Operating Modes3.3 Operating Modes
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.5 Defrost Mode 3.3.5 Defrost Mode
• During Defrost Cycle, HEAT LED will blinkDuring Defrost Cycle, HEAT LED will blink
• The defrost cycle will terminate if:The defrost cycle will terminate if:
a. temperature of outdoor coil sensor exceeds a. temperature of outdoor coil sensor exceeds +10 +10 oo C C
OROR
b. a minimum of b. a minimum of 10 min10 min compressor run time is achieved compressor run time is achieved
3.3 Operating Modes3.3 Operating Modes
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.5 Defrost Mode 3.3.5 Defrost Mode
OD fanOD fan& 4WV& 4WV
ONON
OFFOFF
ONON
OFFOFF
COMPCOMP
Defrost CycleDefrost Cycle 15 +/- 5 sec 15 +/- 5 sec
Defrost CycleDefrost Cycle
3.3 Operating Modes3.3 Operating Modes
20 sec 20 sec
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
During the 1During the 1stst 12 minutes 12 minutes
• Run under COOL mode with Auto Fan Speed for 12 minutesRun under COOL mode with Auto Fan Speed for 12 minutes
OROR
• Run Until TRun Until Trr < T < Tss – 1°C – 1°C
After the 1After the 1stst 12 minutes 12 minutes
• Run either Zone A, B, C or D (depend on temp. condition)Run either Zone A, B, C or D (depend on temp. condition)
3.3 Operating Modes3.3 Operating Modes
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
ZONE AZONE A : if T: if Trr - T - Tss > 2 > 2 o o CC
12 Minutes12 Minutes
3.3 Operating Modes3.3 Operating Modes
CompressorCompressor
Low FanLow Fan
ONON
OFFOFF
ONON
OFFOFF
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
ZONE BZONE B : : if 0°C < Tif 0°C < Trr - T - Tss < 1°C < 1°C
8 min8 min 4 min4 min
30 sec30 sec 30 sec30 sec
ONON
OFFOFF
ONON
OFFOFF
12 Minutes12 Minutes
3.3 Operating Modes3.3 Operating Modes
CompressorCompressor
Low FanLow Fan
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
ZONE CZONE C : : if 1°C < Tif 1°C < Tss - T - Trr < 2°C < 2°C
30 sec30 sec 30 sec30 sec12 Minutes12 Minutes
6 min6 min 6 min6 min
3.3 Operating Modes3.3 Operating Modes
ONON
OFFOFF
ONON
OFFOFF
CompressorCompressor
Low FanLow Fan
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
ZONE DZONE D : : if if TTss - T - Trr > 3°C > 3°C
Low FanLow Fan
CompressorCompressor
30 sec30 sec
12 Minutes12 Minutes
ONON
OFFOFF
ONON
OFFOFF
3.3 Operating Modes3.3 Operating Modes
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.4 Protections 3.4 Protections
3.4.1 Compressor 3.4.1 Compressor
3.4.2 Indoor Coil Anti Freeze3.4.2 Indoor Coil Anti Freeze
3.4.3 EWT Control3.4.3 EWT Control
3.4.4 Self Diagnostics3.4.4 Self Diagnostics
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.4 Protections
3.4.1 Compressor 3.4.1 Compressor
(a) 3 minutes Minimum OFF time(a) 3 minutes Minimum OFF time
Memory backup option not selected Memory backup option not selected (J_LST Opened)(J_LST Opened)
• Compressor can immediately cut in after the power supply is Compressor can immediately cut in after the power supply is restore; subject to thermostat cut in mode.restore; subject to thermostat cut in mode.
Memory backup option selected Memory backup option selected (J_LST Shorted)(J_LST Shorted)
• Compressor can cut in 0 to 64 seconds after the power supply Compressor can cut in 0 to 64 seconds after the power supply is restore; subject to thermostat cut in mode.is restore; subject to thermostat cut in mode.
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.4 Protections
3.4.1 Compressor 3.4.1 Compressor
(b) 150 seconds Minimum Run Time(b) 150 seconds Minimum Run Time
(c) Overload Protection(c) Overload Protection
COOL, AUTO COOL and DRYCOOL, AUTO COOL and DRY
OD coil tempOD coil temp
Comp & OD FanComp & OD Fan
68 68 o o CC
ONON
OFFOFF
HEAT, AUTO HEATHEAT, AUTO HEAT
ID coil tempID coil temp
Comp, OD FanComp, OD Fan& 4WV& 4WV
68 68 o o CC
ONON
OFFOFF
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
(d) Hardware Switch Detection(d) Hardware Switch Detection
• Normally closed switchNormally closed switch
• A counter is increased by one during the first thermostat A counter is increased by one during the first thermostat
cyclecycle
• Counter will reset after 3 minutes or unit turned offCounter will reset after 3 minutes or unit turned off
• If counter > 5, the unit will declare compressor overloadIf counter > 5, the unit will declare compressor overload
protectionprotection
3.4 Protections3.4 Protections
3.4.1 Compressor 3.4.1 Compressor
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.4 Protections
3.4.2 Indoor Coil Anti Freeze 3.4.2 Indoor Coil Anti Freeze Available in COOL and DRY mode Available in COOL and DRY mode
• IFIF ID Coil Temp reaches 1°C and below for at least 1 min ID Coil Temp reaches 1°C and below for at least 1 min
ANDAND compressor has run for at least 10 minutes compressor has run for at least 10 minutes
11ooCCComp & OD FanComp & OD Fan OFFOFF
ONON
1010ooCC
Comp & OD FanComp & OD Fan
OFFOFF
ONON
• IFIF ID Coil Temp reached 10 ID Coil Temp reached 10˚C and above for at least 1 min˚C and above for at least 1 min
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.4 Protections
Under COOL, DRY or Auto COOL Modes,Under COOL, DRY or Auto COOL Modes,
• Compressor will NOT run and alarm will be activatedCompressor will NOT run and alarm will be activated
- IF T- IF Tww 13°C or T 13°C or Tww 40°C for at least 20 seconds 40°C for at least 20 seconds
• Compressor will shut down and alarm will be activatedCompressor will shut down and alarm will be activated
- IF compressor has been running for 20 seconds and - IF compressor has been running for 20 seconds and
TTww > 47°C for 20 seconds > 47°C for 20 seconds
• Compressor will run and alarm will be deactivatedCompressor will run and alarm will be deactivated
- IF 13°C - IF 13°C T Tww 40°C 40°C
3.4.3 Water Temperature Control 3.4.3 Water Temperature Control
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Under HEAT or Auto HEAT Modes,Under HEAT or Auto HEAT Modes,
• Compressor will NOT run and alarm will be activatedCompressor will NOT run and alarm will be activated
- IF T- IF Tww 10°C or T 10°C or Tww 35°C for at least 20 seconds 35°C for at least 20 seconds
• Compressor will shut down and alarm will be activatedCompressor will shut down and alarm will be activated
- IF compressor has been running for 20 seconds and - IF compressor has been running for 20 seconds and
TTww < 6°C for 20 seconds < 6°C for 20 seconds
• Compressor will run and alarm will be deactivatedCompressor will run and alarm will be deactivated
- IF 10°C - IF 10°C T Tww 35°C 35°C
3.4 Protections
3.4.3 Water Temperature Control 3.4.3 Water Temperature Control
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
3.4 Protections3.4 Protections
3.4.4 Self Diagnostics3.4.4 Self Diagnostics EventEvent CDF LEDCDF LED Timer LEDTimer LED Other LEDsOther LEDs Error codeError code
1 Room sensor open or short Blink 1 time - Blink Fan Blink E1
2 Indoor coil sensor open Blink 2 times - Blink Sleep Blink E2
3 Outdoor coil/water sensor open Blink 3 times - Blink Dry Blink E3
4 Compressor overload/ Indoor coil sensor short/ Outdoor coil/water sensor short Blink 1 time Blink Cool Blink E4
5 Gas leak Blink 3 times Blink Cool & Dry Blink E5
6 Water pump fault Blink 2 times Blink Cool & Fan Blink E6
7 Outdoor defrost Blink Heat
8Outdoor coil sensor exist(MS model) Blink 5 times Blink Cool & Heat Blink E7
9Hardware error (tact switch pin short) Blink 6 times
Blink Heat, Cool, follow by Fan, Dry Blink E8
10 Outdoor water fault Blink 5 times Blink Cool & Sleep Blink E9
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation 4. Installation 4.1 Hanging the Unit4.1 Hanging the Unit
4.2 Location of Hanging4.2 Location of Hanging4.3 Refrigerant Piping4.3 Refrigerant Piping4.4 Water Piping4.4 Water Piping4.5 Drainage4.5 Drainage4.6 Cleaning & Flushing System4.6 Cleaning & Flushing System
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.1 Hanging the Unit4.1 Hanging the Unit
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.1 Hanging the Unit4.1 Hanging the Unit
• Recommend to use vibration isolators on Recommend to use vibration isolators on
the brackets to reduce noise and vibration the brackets to reduce noise and vibration
transmissions transmissions
• Spring isolator to be used for better vibration Spring isolator to be used for better vibration
control.control.
spring
bottom washer
PVC tube
Upper washer, welded onto bracket
nut
bracket
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.2 Location of hanging4.2 Location of hanging
Install at a location that gives sufficient space clearance for:Install at a location that gives sufficient space clearance for:
• Hanging the unitHanging the unit
• Installing and maintaining the water pipingInstalling and maintaining the water piping
• Installing and maintaining the duct workInstalling and maintaining the duct work
• Accessing the unit’s internal parts via access panelAccessing the unit’s internal parts via access panel
• Removal of air filter for cleaning Removal of air filter for cleaning
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.2 Location of hanging4.2 Location of hanging
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.3 Refrigerant Piping4.3 Refrigerant Piping
Refrigerant Piping Length, Elevation and BendsRefrigerant Piping Length, Elevation and Bends
• When piping length becomes too long, both the capacity When piping length becomes too long, both the capacity and compressor reliability drop.and compressor reliability drop.
• As the number of bends increases, system piping As the number of bends increases, system piping resistance to the refrigerant flow increase thus lowering the resistance to the refrigerant flow increase thus lowering the capacity of the unit and as a result the compressor may capacity of the unit and as a result the compressor may become defective.become defective.
• Always choose the shortest path and follow the Always choose the shortest path and follow the recommendation as tabulated in the following pages.recommendation as tabulated in the following pages.
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.3 Refrigerant Piping4.3 Refrigerant Piping
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.3 Refrigerant Piping4.3 Refrigerant Piping
Additional ChargesAdditional Charges
• The precharged in the WSS unit is suitable for Standard The precharged in the WSS unit is suitable for Standard pipe of length up to:pipe of length up to:
• 2 meter for WSS10/15/20/25/30/40/50 A2 meter for WSS10/15/20/25/30/40/50 A
• 5 meter for WSS60A5 meter for WSS60A
• When the piping is more than the standard pipe length, When the piping is more than the standard pipe length, additional of 18.5 gram is needed for a meter of additional additional of 18.5 gram is needed for a meter of additional length.length.
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.4 Water Piping4.4 Water Piping
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.4 Water Piping4.4 Water Piping
• Males couplings, BSPMales couplings, BSP
• In general, no pipe insulation required In general, no pipe insulation required
Water IN
Water OUT
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.4 Water Piping4.4 Water Piping
Flexible hoseFlexible hose
• To ease water pipe installationTo ease water pipe installation
• Steel reinforced PVC hose with 2 female BSP couplings at Steel reinforced PVC hose with 2 female BSP couplings at the end.the end.
• Use O-rings provided to have a leak-proof jointUse O-rings provided to have a leak-proof joint
Female couplings
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.4 Water Piping4.4 Water PipingPressure
gauge
Water Inlet
Water Outlet
Gate Valve
Strainer
Automatic Shut-off
Valve
Flexible joint
Thermometer
Balancing Valve
WSS Unit
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
4. Installation
4.5 Drainage4.5 Drainage
• Slanting drain pan design Slanting drain pan design
Drain
• Drain pipe must be inclined at an angle to allow free drainageDrain pipe must be inclined at an angle to allow free drainage
Drain pipe, ¾”
Slope downwards to the nearest drain(recommended 1:100)
U-Trap
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
• Water circulating system must be cleaned and flushed of all Water circulating system must be cleaned and flushed of all construction dirt and debrisconstruction dirt and debris
• The system should be filled at the city water makeup connection with all The system should be filled at the city water makeup connection with all air vents open. After filling, vents should be closedair vents open. After filling, vents should be closed
• Supplemental heater and circulator pump should be shut offSupplemental heater and circulator pump should be shut off
• Use 27°C water as flush lingerUse 27°C water as flush linger
• Refill the system with clean waterRefill the system with clean water
4. Installation
4.6 Cleaning and Flushing System4.6 Cleaning and Flushing System
Te
chn
ica
l Tra
inin
gT
ech
nic
al T
rain
ing
Horizontal Water Source Heat PumpHorizontal Water Source Heat Pump
Thank YouThank You