Water Level Switch

Embed Size (px)

Citation preview

  • 8/12/2019 Water Level Switch

    1/2

    Water Level SwitchThis water level sensor is conducive for liquids that have a conductivity of equal to or

    more than 25m Siemens. The system is economical to install as no special cable is

    required for signal transmission. The level probe and the evaluation unit can be

    connected using a long cable. The AC is provided on the probe for preventing electrode

    deterioration.

    You can choose from among a variety of level control and installation systems such as

    Two point sensors for independent switching and automatic control of pump. Four point switching with two pump control logic. Three point switching: two for pump control logic and one independent point with

    or without a settable delay (for probe covered or uncovered).

    A variety of probes is available for your specific process.Applications

    The SLW... series water level switches work to maintain a constant water level avoiding

    material wastage in your process plant. Common applications include switching pumps

    on and off to avoid overflow, dry running and indicating water level in an empty tank to

    avoid wear and tear and production stoppage. Many of our customers in the Food,

    Power, Chemicals, Sugar, Detergent, Steel, Minerals and Textile industry have used the

    SLW... series water level indicator.

    Principle

    A low AC voltage is applied between the probe electrode and the tank wall (or referenceelectrode in case of insulated tank). When the water/liquid comes in contact with the

  • 8/12/2019 Water Level Switch

    2/2

    electrode tip, a conductive path is established between the sense electrode and the tank

    wall/reference electrode. This current is sensed, amplified and made to operate a relay

    whose contacts in turn can be used for annunciation/control.

    Technical Data

    Evaluation Unit

    Housing Cast aluminium, Weather-proof Stoving enamel painted suitable for back

    panel/wall mounting.

    Cable Entries 3 Nos. of 1/2 BSP

    Mains 110 or 230 V AC (-15 to + 10%) 50 Hz (as specified in order).

    Relay Output One set of potential free change over contacts rated at 6A 230 V AC,

    50Hz for non-inductive load.

    Power

    Consumption

    5 VA approx.

    Fail-Safe Mode High or Low field selectable.

    Response Time 0.5 second

    Switching Delay 0.5 to 20 seconds for probe covered and uncovered condition

    Maximum

    Sensitivity

    25 Micro Siemens

    Operating mode (A) Single point switching.

    (B) Two-point switching with pump control logic.

    Indication Red LED for Alarm, Green LED for Normal.

    Mounting 1 BSP Screwed or Flanged mounting.

    Operating Temp. -20 C to + 60 C.

    Weight ~2 Kg.

    Level Probe

    Voltage 12 V AC (across probe & tank wall/ grounding electrode)

    Current