Water Level SwitchThis water level sensor is conducive for liquids that have a conductivity of equal to or
more than 25m Siemens. The system is economical to install as no special cable is
required for signal transmission. The level probe and the evaluation unit can be
connected using a long cable. The AC is provided on the probe for preventing electrode
deterioration.
You can choose from among a variety of level control and installation systems such as
Two point sensors for independent switching and automatic control of pump. Four point switching with two pump control logic. Three point switching: two for pump control logic and one independent point with
or without a settable delay (for probe covered or uncovered).
A variety of probes is available for your specific process.Applications
The SLW... series water level switches work to maintain a constant water level avoiding
material wastage in your process plant. Common applications include switching pumps
on and off to avoid overflow, dry running and indicating water level in an empty tank to
avoid wear and tear and production stoppage. Many of our customers in the Food,
Power, Chemicals, Sugar, Detergent, Steel, Minerals and Textile industry have used the
SLW... series water level indicator.
Principle
A low AC voltage is applied between the probe electrode and the tank wall (or referenceelectrode in case of insulated tank). When the water/liquid comes in contact with the
8/12/2019 Water Level Switch
2/2
electrode tip, a conductive path is established between the sense electrode and the tank
wall/reference electrode. This current is sensed, amplified and made to operate a relay
whose contacts in turn can be used for annunciation/control.
Technical Data
Evaluation Unit
Housing Cast aluminium, Weather-proof Stoving enamel painted suitable for back
panel/wall mounting.
Cable Entries 3 Nos. of 1/2 BSP
Mains 110 or 230 V AC (-15 to + 10%) 50 Hz (as specified in order).
Relay Output One set of potential free change over contacts rated at 6A 230 V AC,
50Hz for non-inductive load.
Power
Consumption
5 VA approx.
Fail-Safe Mode High or Low field selectable.
Response Time 0.5 second
Switching Delay 0.5 to 20 seconds for probe covered and uncovered condition
Maximum
Sensitivity
25 Micro Siemens
Operating mode (A) Single point switching.
(B) Two-point switching with pump control logic.
Indication Red LED for Alarm, Green LED for Normal.
Mounting 1 BSP Screwed or Flanged mounting.
Operating Temp. -20 C to + 60 C.
Weight ~2 Kg.
Level Probe
Voltage 12 V AC (across probe & tank wall/ grounding electrode)
Current