Level Measurement

Water Level Monitoring

Embed Size (px)

DESCRIPTION

Description of on water level

Citation preview

Page 1: Water Level Monitoring

Level Measurement

Page 2: Water Level Monitoring

Level MeasurementLevel MeasurementLevel is another common process variable that is measured in

many industries. The method used will vary widely depending on the nature of the industry, the process, and the application.

Inventory: • a constant supply or storage of material

Control: • continuous, batch, blending, and mixing control• stabilize flow to the next process

Alarming: • hi/lo limits, safety shut down

Data Logging: • material quantities for inventory and billing purposes

and where regulatory requirements are necessary

Page 3: Water Level Monitoring

What is measured?What is measured?

The measured medium can be liquid, gas or solid and stored in vessels (open/closed tanks), silos, bins and hoppers.

Units of level can be expressed in:• feet (meters)• gallons (liters)• pounds (kilograms)• cubic volume (ft3, m3)

Page 4: Water Level Monitoring

Methods – Direct or Indirect (inferential)Methods – Direct or Indirect (inferential)

• Hydrostatic Head • Float• Load Cells• Magnetic Level

Gauge• Capacitance

Transmitters• Magnetostrictive• Ultrasonic• Microwave• Laser• Radar• Guided Wave Radar• Dip Stick• Vibration

Page 5: Water Level Monitoring

Direct MethodsDirect Methods

Direct methods sense the surface or interface of the liquid and is not affected by changes in material density (Specific Gravity)

Examples:• Dip Stick• Resistance Tapes• Sight Glass• Floats• Ultrasonic

Page 6: Water Level Monitoring

Indirect Methods (Inferential)Indirect Methods (Inferential)

Indirect methods “infer” liquid level by measuring some other physical parameter such as pressure, weight, or temperature.

Changing materials means a corrective factor must be used or recalibrating the instrument.

Examples: • Hydrostatic head methods• Load Cells• Capacitance• Conductivity

Page 7: Water Level Monitoring

Selection CriteriaSelection Criteria

When determining the type of level sensor that should be used for a given application, there are a series of questions that must be answered:

• Open tank or closed tank? • Can the level sensor be inserted into the tank or should it

be completely external? Contact or non-contact?• Continuous measurement or point measurement?• Direct or Indirect measurement? • What type of material is being measured? Liquid or

Solid? Clean or Slurry?

Page 8: Water Level Monitoring

Dip StickDip Stick

• Simple and cheap• Can be used with any wet

material and not affected by density.

• Can not be used with pressurized tanks

• Visual indication only (electronic versions are available)

RodGauge - similar to a dipstick found in a car, it has weighted line markings to indicate depth or volume

Page 9: Water Level Monitoring

Resistance TapeResistance TapeThe pressure of the fluid in the tank causes the tape to

short-circuit, thus changing the total resistance of the measuring tape. An electronic circuit measures the resistance; it's directly related to the liquid level in the tank.

Page 10: Water Level Monitoring

Sight GlassSight Glass

Another simple direct method of measuring liquids.

Can be used in pressurized tanks (as long as the glass or plastic tube can handle the pressure)

Good for applications where non-contact measurement is needed (like beverages)

Page 11: Water Level Monitoring

Magnetic Level SensorsMagnetic Level Sensors

Used where the sight glass level gauge can not be.

Magneto-resistive types can provide an electrical output.

Liquid/liquid interface (such as water and oil) can be measured by changing the buoyancy of the magnetic float

Page 12: Water Level Monitoring

FloatsFloats

Float rides the surface level to provide the measurement. Many different styles are available.

Liquid density does not affect measurement

Page 13: Water Level Monitoring

Hydrostatic Head Level SensorsHydrostatic Head Level Sensors

• These methods infer level by measuring the hydrostatic head produced by the liquid column.

• A pressure sensing element is installed at the bottom of the tank and pressure is converted to level.

• Different liquid densities or closed tank applications must be accounted for.

Page 14: Water Level Monitoring

General Theory for Head MeasurementGeneral Theory for Head Measurement

The Pressure exerted by the Height of the liquid is:

P = H x Density*

If the Density of the liquid is known then

H = Pressure

Density*

Height (H)

Pressure PSI

Liquid Density (D)

*Note: For liquids other than water, use the density of water 0.0361 lb/in3 as a reference and multiply by the SG of the liquid.

Page 15: Water Level Monitoring

Example Example

Height (H)

Tank 1 PSI

WaterDensity (D) Height

(H)

Tank 2 PSI

OilDensity (D)

A dip stick measurement of the level of these 2 tanks indicates 30 feet of liquid in both tanks. Calculate the pressure that each gauge will read if tank 1 contains water (S.G. = 1) and tank 2 contains oil (S.G. = 0.85)

P = ? psi P = ? psi

Page 16: Water Level Monitoring

Example Example

Height (H)

Tank 1 PSI

WaterDensity (D) Height

(H)

Tank 2 PSI

OilDensity (D)

A dip stick measurement of the level of these 2 tanks indicates 30 feet of liquid in both tanks. Calculate the pressure that each gauge will read if tank 1 contains water (S.G. = 1) and tank 2 contains oil (S.G. = 0.85)

P = H x Density

= 30 ft x 0.0361 lbs/in3

= (30 x 12) x 0.0361

= 13 psi

P = ? psi

Page 17: Water Level Monitoring

Example Example

Height (H)

Tank 1 PSI

WaterDensity (D) Height

(H)

Tank 2 PSI

OilDensity (D)

A dip stick measurement of the level of these 2 tanks indicates 30 feet of liquid in both tanks. Calculate the pressure that each gauge will read if tank 1 contains water (S.G. = 1) and tank 2 contains oil (S.G. = 0.85)

P = H x Density x SG

= 30 ft x 0.0361 lbs/in3 x 1

= (30 x 12) x 0.0361

= 13 psi

P = H x Density x SG

= 30 ft x 0.0361 lbs/in3 x 0.85

= (30 x 12) x 0.0361 x 0.85

= 11 psi

Page 18: Water Level Monitoring

Practical Considerations when using Practical Considerations when using head type instrumentshead type instruments

The reference point of the tank vs instrument input must be considered.

Height (H)

Pressure PSI

Liquid Density (D)

Height (H)Pressure

PSI

Liquid Density (D)

This may not be practical in some applications where the tank elevation is below grade or where a remote visual reading is required.

Page 19: Water Level Monitoring

Tank ElevationsTank Elevations

Vertical rises and drops contribute to the overall height and therefore head pressure. Horizontal runs have no effect.

Height (H)

P

WaterDensity (D)

P

Page 20: Water Level Monitoring

BubblersBubblers

Bubblers allow the indicator to be located anywhere.

The air pressure in the tube varies with the head pressure of the height of the liquid.

Bottom of tube determines reference point

P

Regulated purge system

(air or nitrogen)

Instrument input does not matter

Can’t be used in closed tanks or where purging a liquid is not allowed (soap). Very popular in the paper industry because the air purge keeps the tube from plugging.

Page 21: Water Level Monitoring

Closed Tank ApplicationsClosed Tank Applications

Open tanks are vented to atmosphere so the pressure at the bottom of the tank is only due to the head pressure of the liquid.

Closed tanks are not vented to atmosphere so the pressure at the bottom of the tank is due to the head pressure of the liquid + the vapour pressure above the surface.

P Head = h x D

P (atmospheric)

P Head = (h x D) + P vapour

P vapour

Page 22: Water Level Monitoring

Using a d/P Cell TransmitterUsing a d/P Cell TransmitterThe differential pressure cell is one of the most common

methods of measuring level.

Open Tank Measurement• Lo side of the d/P cell is left open to atmosphere.• Hi side measures the hydrostatic head pressure which is proportional to the

height of the liquid and its density.

Lo side open to atmosphere

24 VDC mA

4 – 20 mA

To PLC or

Controller

Page 23: Water Level Monitoring

Using a d/P Cell TransmitterUsing a d/P Cell TransmitterIn a closed tank, the Low side of the d/P cell is connected

to the top of the tank and will cancel the effects of the vapour pressure above the surface.

Closed Tank Measurement• Lo side of the d/P cell measures the vapour pressure above the surface.• Hi side measures the hydrostatic head pressure which is proportional to the

height of the liquid and its density + vapour pressure

24 VDC mA

4 – 20 mA

To PLC or

Controller

H L

Page 24: Water Level Monitoring
Page 25: Water Level Monitoring

DisplacersDisplacers• Not the same as a float. • The displacer is immersed in the tank and the buoyant

force of the liquid produces a torque which is proportional the amount of liquid level.

The output force can be converted to provide a proportional pneumatic or electrical continuous output of tank level.

Page 26: Water Level Monitoring

Displacer – side mounted unitDisplacer – side mounted unit

The displacer float size and diameter is selected according to the size of tank and the height of the level to be measured.

The output force can be converted to provide a proportional pneumatic or electrical continuous output of level.

Advantages and disadvantages:• Very little movement of displacer

float• Affected by different liquid

densities• Limited to smaller tanks sizes

Page 27: Water Level Monitoring

Conductivity Level MeasurementConductivity Level Measurement

Point Level Measurement Continuous Level Measurement

DC Excitation voltages may create problems with some liquids (polarization) AC excitation voltages can be used but some frequencies are not suitable for all liquids.

Advantages and disadvantagesLow CostConductive, non-coating liquids onlyInsulating coatings can cause problems

Page 28: Water Level Monitoring

Capacitance Level Detection (RF Level Probes)Capacitance Level Detection (RF Level Probes)

RF Capacitance level sensors are similar in operation to conductivity sensors and are typically used when non-conductive liquids are measured.

The only variable is the dielectric of the tank material that varies in proportion to the level.

Conductive liquids like mineral water will short out the probe to the tank wall.

Good for solids

Page 29: Water Level Monitoring

Can be used for non-liquidsCan be used for non-liquids

RF capacitance probes are used in a wide range of applications and are subjected to certain limitations such as:

– Electrode Coating– Low sensitivity– Temperature– Different materials– Shielding & noise

Page 30: Water Level Monitoring

UltraSonic Level MeasurementUltraSonic Level Measurement

• Non-Contact direct level sensor

• Level is a function of the time it takes an ultrasonic pulse to hit the surface and return

Limitations include:• Surface foam absorbs signal, agitation create reflections• High Pressure & High Temperatures affect the signal speed• Vapour and condensate create false echo’s

Page 31: Water Level Monitoring

Radar Level Sensors (Microwave)Radar Level Sensors (Microwave)

Similar to ultrasonic but at a much higher frequency (6.3 GHz)

Various designs – Frequency Modulated Continuous Wave

– Pulsed Wave

– Guided Wave

These sensors have better performance in applications where vapour, dust or uneven surfaces exist.

Page 32: Water Level Monitoring

Guided wave Radar Sensor

A generated pulse of electromagnetic energy travels down the probe. Upon reaching the liquid surface the pulse is reflected.

Page 33: Water Level Monitoring

Load CellsLoad Cells

Tank level is determined by the weight of the quantity of material

Load Cells (strain gauge transducers) placed at the bottom of the tank measure the weight and then convert it to an electrical signal.

Page 34: Water Level Monitoring

SummarySummary

• Hydrostatic Head • Float• Load Cells• Magnetic Level

Gauge• Capacitance• Conductivity• Ultrasonic• Radar• Guided Wave

Radar• Dip Stick

Page 35: Water Level Monitoring

Summary

• Level is measured by locating the boundary between two media, called the interface

• Level can be measured directly or indirectly

• Noninvasive devices are preferred when the material is corrosive, hazardous, sterile, or at a high temperature or pressure

Page 36: Water Level Monitoring

Batch application using point level measurementBatch application using point level measurement

• Detect if the level is at a predetermined point

• Generally used to detect either a low-level condition or high-level condition

• The output of a point level sensor is on-off, or 1 or 0 state digital signal

A batch process does NOT use a continuous level measurement device.