ACTIVE FIRE PROTECTIONWater-Based System
March, 2013
FIRE PROTECTION SYSTEM
• Active Fire Protection System
– Water-based system
– Dry chemical system
– Gaseous system
• Passive Fire Protection System
– Spacing and layout
– Structural protection
Water-Based Fire Fighting – March 2013 2
• Minimize the risk
• Minimize consequence
• Prevent escalation
• Provide protection for personnel
• Extinguishing
3
HOW TO DESIGN ???
Water-Based Fire Fighting – March 2013
DELUGE SYSTEM
4Water-Based Fire Fighting – March 2013
• Objective : Provide cooling system for equipment to prevent escalation
• Design
Fire water demand from deluge system =
equipment area X deluge rate X [ 1 + wastage factor] X [ 1 + hydraulic contingency]
Total fire water demand from deluge system
FIRE HYDRANT & FIRE MONITOR
5Water-Based Fire Fighting – March 2013
Objective : to provide cooling for adjacent equipment
Design : 1 monitor + 2 hydrant (active)
FOAM SYSTEM
6Water-Based Fire Fighting – March 2013
• Objective : extinguish hydrocarbon liquid fire
• How to design fixed foam system?
1. Determine application rate
2. Determine foam application duration
• Type of Fixed Foam Protection :
1. Primary Protection � Foam Chamber
2. Supplementary Protection � Foam Hose Line
• Output
- Foam concentrate
- Fire water required
For specified foam concentration
For specified foam concentration
FIRE WATER PUMP &JOCKEY PUMP
7Water-Based Fire Fighting – March 2013
8Water-Based Fire Fighting – March 2013
9Water-Based Fire Fighting – March 2013
JOCKEY PUMP
10Water-Based Fire Fighting – March 2013
• Objective : Maintain pressure at fire water piping system
FIRE WATER PUMP
11Water-Based Fire Fighting – March 2013
• Objective : supply FW to FW system at required pressure and flowrate
• Source energy : Normal plant supply and plant emergency power distribution system
• Start : automatically on low pressure in fire water main ring
• Number of unit : N + 1 (run and standby)
• Capacity : NFPA 20 (for single worst case in one fire zone)
12
70
75
80
85
90
95
100
105
110
JP StartJP Start
JP StopJP Stop
1st FWP Start 1st FWP Start
2nd FWP Start 2nd FWP Start
PUMP MECHANISM
Water-Based Fire Fighting – March 2013