Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
95.1% AFUE
Direct Vent (Sealed Combustion) Forced Air
CMF95 Series Downflow Condensing Gas Furnace
For Installation in:
• ManufacturedHomes
• RecreationalVehicles,ParkModels,&
ManufacturedBuildings
• ModularHomes/Buildings
INSTALLATION INSTRUCTIONS
DO NOT DESTROY THIS MANUAL. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
FIRE OR EXPLOSION HAZARD•Failure to follow safety warnings exactly
could result in serious injury or propertydamage.
• Installationandservicemustbeperformedbyaqualifiedinstaller,serviceagencyorthegassupplier.
•Do not store or use gasoline or otherflammablevaporsandliquidsinthevicinityofthisoranyotherappliance.
WHAT TO DO IF YOU SMELL GAS•Donottrytolightanyappliance.•Donottouchanyelectricalswitch;donot
useanyphoneinyourbuilding.•Leavethebuildingimmediately.• Immediatelycallyourgassupplier froma
neighbor’sphone.Followthegassupplier’sinstructions.
• Ifyoucannotreachyourgassupplier,callthefiredepartment.
WARNING:RISQUED’INCENDIEOUD’EXPLOSION
•Le non-respect des avertissements desécurité pourrait entraîner des blessuresgraves,lamortoudesdommagesmatériels.
•L’installation et l’entretien doivent êtreeffectués par un installateur qualifié, unorganisme de service ou le fournisseur degazstaller,serviceagencyorthegassupplier.
•Nepasentreposerniutiliserdel’essencenid’autres vapeurs ou liquides inflammablesdanslevoisinagedecetappareil,nidetoutautreappareil.
QUEFAIRES’ILYAUNEODEURDEGAZ•Nepastenterd’allumeraucunappareil.•Netoucheràaucuninterrupteurélectrique;
n’utiliseraucuntéléphonedanslebâtiment.•Évacuerl’immeubleimmédiatement.•Appeler immédiatement le fournisseur de
gazenemployant le téléphoned’unvoisin.Respecter à la lettre les instructions dufournisseurdegaz.
•Sipersonnenerépond,appelerleservicedesincendies.
AVERTISSEMENT
2
IMPORTANT SAFETY INFORMATION .......................3
REQUIREMENTS & CODES .......................................3
ClearancestoCombustibleMaterials.......................5
CombustionAirQuality.............................................5
HeatingLoad............................................................5
CondensateDisposal...............................................5
COMBUSTION AIR & VENTING REQUIREMENTS ....6
ImportantInformation...............................................7
CategoryIVAppliances............................................7
DirectVentInstallation..............................................7
VentPipeLength&Diameter................................. 7
VentPipeMaterial.................................................. 8
VentPipeInstallation.............................................. 8
OutdoorTerminations-HorizontalVenting............. 8
OutdoorTerminations-VerticalVenting.................. 9
VentFreezingProtection...................................... 10
ExistingInstallations............................................. 10
VentilaireIIIorIVAirQualityPackage................... 10
CIRCULATING AIR REQUIREMENTS ...................... 11
Plenums&AirDucts.............................................. 11
SupplyAirConnections.......................................... 11
Dampers................................................................. 11
UnconditionedSpaces........................................... 11
ClosetInstallations................................................. 11
FurnaceFilter......................................................... 12
AcousticalTreatments............................................ 12
FURNACE INSTALLATION ....................................... 13
GeneralInformation................................................ 13
BeforeYouInstallthisFurnace............................... 13
LocatingtheUnit.................................................... 13
MA-200BaseInstallation....................................... 13
InstallingtheFurnaceonanMA-200Base............ 13
MA-100UniversalBaseInstallation........................ 14
InstallingtheFurnaceonanMA-100Base............. 15
CondensateDrainage............................................ 15
GAS SUPPLY & PIPING ............................................ 16
LeakCheck........................................................... 16
High-AltitudeApplication........................................ 17
ConvertingtoLP/PropaneGas............................ 18
RemovingtheBurnerOrifices.............................. 19
GasPressureVerification....................................... 19
MeasuringtheSupplyGasPressure.................... 19
Lighting&AdjustmentoftheAppliance................ 20
MeasuringtheManifoldPressure......................... 20
RemovingtheManometer/PressureGauge...... 20
CompletingtheConversion.................................... 20
ELECTRICAL WIRING ............................................... 21
LineVoltageWiring................................................ 21
Grounding............................................................... 21
Thermostat/LowVoltageConnections................. 21
HeatAnticipator.................................................... 22
START-UP&ADJUSTMENTS ................................... 23
Pre-StartChecklist................................................. 23
Start-UpProcedures.............................................. 23
Verifying&AdjustingInputRate............................. 23
Verifying&AdjustingTemperatureRise................. 23
VerifyingBurnerOperation..................................... 24
VerifyingOperationoftheSupplyAir LimitSwitch............................................................ 24
OPERATING SEQUENCE ......................................... 25
HeatingCycle......................................................... 25
CoolingCycle......................................................... 25
FanMode............................................................... 25
MAINTENANCE ......................................................... 25
AirFilters................................................................ 26
BlowerCompartment.............................................. 26
CleaningofBurners................................................ 26
VentSystem........................................................... 26
HeatExchanger&BurnerMaintenance................. 26
Lubrication............................................................... 26
TROUBLESHOOTING ............................................... 27
DESCRIPTION OF COMPONENTS .......................... 27
TABLE OF CONTENTS
3
FIGURES & TABLES ................................................. 28
Figure18-FurnaceDimensions.......................... 28
WiringDiagram....................................................... 29
Figure19-CMF95WiringDiagram...................... 29
GasInformation...................................................... 30
Table7-GasFlowRates..................................... 30
Table8-GasPipeCapacities.............................. 30
Table9-HighAltitudeDerationChartfor PropaneGas......................................... 31
Table10-NaturalGasHeatingValues.................31
Table11-HighAltitudeDerationChartfor Nat.Gas-HighHeatingValues........... 31
Table12-HighAltitudeDerationChartfor Nat.Gas-LowHeatingValues............ 31
VentingInformation................................................ 32
Table13-VentTerminationClearances............... 32
Figure20-Horizontal&VerticalVenting.............. 33
INSTALLATION / PERFORMANCE CHECKLIST ..... 36
IMPORTANT SAFETY INFORMATIONPleasereadallinstructionsbeforeservicingthisequipment.Payattentiontoallsafetywarningsandanyotherspecialnotes highlighted in the manual. Safety markings areusedfrequently throughout thismanual todesignateadegreeorlevelofseriousnessandshouldnotbeignored.WARNINGindicatesapotentiallyhazardoussituationthatifnotavoided,couldresult inpersonal injuryordeath.CAUTIONindicatesapotentiallyhazardoussituationthatifnotavoided,mayresultinminorormoderateinjuryorpropertydamage.
REQUIREMENTS & CODES
WARNING:Theinformationlistedbelowmustbefollowedduringtheinstallation,service,andoperationof this furnace. Failure to follow safetyrecommendations could result in possibledamage to the equipment, serious personalinjuryordeath.
• This furnace must be installed in accordance withtheseinstructions,allapplicablelocalbuildingcodesandthecurrentrevisionoftheNationalFuelGasCode(ANSIZ223.1/NFPA54)ortheNaturalGasandPropaneInstallationCode,CAN/CGAB149.1.
• Useonlywithtypeofgasapprovedforthisfurnace.Refertothefurnaceratingplate.
• Installthisfurnaceonlyinalocationandpositionasspecifiedonpage5.
• Provideadequatecombustionandventilationairtothefurnacespaceasspecifiedonpages6-10.
• ProvideadequateclearancesaroundtheventairintaketerminalasspecifiedinFigures1-4(pages9-10).
• Combustionproductsmustbedischargedoutdoors.Connectthisfurnacetoanapprovedventsystemonly,asspecifiedonpages7-10.
• Never test forgas leakswithanopenflame.Useacommercially available soap solution to check allconnections.Seepages16-17.
• Thisfurnaceisdesignedtooperatewithamaximumexternalpressureriseof0.3inchesofwatercolumn.ConsultTable5(page24)andtheratingplateforthepropercirculatingairflowandtemperaturerise.It isimportantthattheductsystembedesignedtoprovidethecorrectflowratesandexternalpressurerise.Animproperlydesignedductsystemcanresultinnuisanceshutdowns,andcomfortornoiseissues.
• Thisfurnacemustnotbeusedfortemporaryheatingofbuildingsorstructuresunderconstruction.
• The Commonwealth of Massachusetts requirescompliancewithregulation248CMR4.00and5.00forinstallationofthrough–the–wallventedgasappliancesasfollows:
4
1.For direct-vent appliances, mechanical-vent heatingappliancesordomestichotwaterequipment,wherethebottomoftheventterminalandtheairintakeisinstalledbelowfourfeetabovegradethefollowingrequirementsmustbesatisfied:a.)Acarbonmonoxide(CO)detectorandalarmshallbe
placedoneachfloorlevelwheretherearebedrooms.Thedetector shall complywithNFPA720 (2005Edition)andbemountedinthelivingareaoutsidethebedroom(s).
b.)A(CO)detectorshallbelocatedintheroomthathousestheapplianceorequipmentandshall:•Bepoweredbythesameelectricalcircuitasthe
applianceorequipment.Onlyoneserviceswitchshallpowertheapplianceandthe(CO)detector;
•Havebatteryback-uppower;•MeetANSI/UL2034Standardsandcomplywith
NFPA720(2005Edition);andApprovedandlistedbyaNationallyRecognizedTestingLaboratoryasrecognizedunder527CMR.
c.)AProduct-approvedvent terminalmustbeused,andifapplicable,aproduct-approvedairintakemustbeused.Installationshallbe instrictcompliancewith the manufacturer’s instructions. A copy ofthe installation instructions shall remain with theapplianceorequipmentat the completionof theinstallation.
d.)Ametalorplasticidentificationplateshallbemountedattheexteriorofthebuilding,4feetdirectlyabovethelocationofventterminal.Theplateshallbeofsufficientsize,easilyreadfromadistanceofeightfeetaway,andread“GasVentDirectlyBelow”.
2.For direct-vent appliances, mechanical vent heatingappliancesordomestichotwaterequipmentwherethebottomoftheventterminalandtheairintakeisinstalledabovefourfeetabovegradethefollowingrequirementsmustbesatisfied:a.)A(CO)detectorandalarmshallbeplacedoneach
floorlevelwheretherearebedrooms.ThedetectorshallcomplywithNFPA720(2005Edition)andbemountedinthelivingareaoutsidethebedroom(s).
b.)The(CO)detectorshall:•Belocatedintheroomthathousestheappliance
orequipment;•Behard-wired,batterypoweredorboth.•ShallcomplywithNFPA720(2005Edition).
c.)Aproduct-approvedvent terminalmustbeused,andifapplicable,aproduct-approvedairintakemustbeused.Installationshallbe instrictcompliancewith the manufacturer’s instructions. A copy ofthe installation instructions shall remain with theapplianceorequipmentat the completionof theinstallation.
Theinformationlistedbelowisforreferencepurposesonlyanddoesnotnecessarilyhavejurisdictionoverlocalorstatecodes.Alwaysconsultwithlocalauthoritiesbeforeinstallinganygasappliance.
Combustion & Ventilation Air• US:NationalFuelGasCode(NFGC/NFPA-54),Airfor
CombustionandVentilation• CANADA:NaturalGasandPropaneInstallationCodes
(NSCNGPIC), Venting Systems and Air Supply forAppliances
DuctSystems• USandCANADA:AirConditioningContractorsAssociation
(ACCA)ManualD,SheetMetalandAirConditioning-NationalAssociation(SMACNA),orAmericanSocietyofHeating,Refrigeration,andAirConditioningEngineers(ASHRAE)FundamentalsHandbook
Electrical Connections• US:NationalElectricalCode(NEC)ANSI/NFPA70• CANADA:CanadianElectricalCodeCSAC22.1
GasPiping&GasPipePressureTesting• US:NFGCandNationalPlumbingCodes• CANADA:NSCNGPIC• AmericanNationalStandard(NFPA-54)and/orCAN/CSA
B149forallgas-firedfurnacemodels.
General Installation• US:CurrenteditionoftheNFGCandtheNFPA90B.For
copies,contacttheNationalFireProtectionAssociationInc.,BatterymarchPark,Quincy,MA02269;orAmericanGasAssociation,400N.Capitol,N.W.,WashingtonDC20001orwww.NFPA.org
• CANADA:NSCNGPIC.Foracopy,contactStandardSales,CSA International, 178 Rexdale Boulevard, Etobicoke(Toronto),Ontario,M9W1R3Canada
• Federal Manufactured Home Constructions & SafetyStandard(H.U.D.Title24,Part3280.707[a][2])
• AmericanNationalStandard(ANSI-119.2/NFPA-501C)forallrecreationalvehicleinstallations.
Safety• US:(NFGC)ANSIZ223.1/NFPA54andtheInstallation
Standards, Warm Air Heating and Air ConditioningSystemsANSI/NFPA90B.
• CANADA: CAN/CGA-B149.1 and .2–M00 NationalStandardofCanada.(NSCNGPIC)
5
Clearances to Combustible MaterialsThisfurnaceisDesignCertifiedintheU.S.andCanadaby CSA International for the minimum clearances tocombustiblematerials.NOTE:The furnace is listed forinstallationoncombustibleornon-combustibleflooring.However,woodistheonlycombustibleflooringallowedforinstallation.Toobtainfurnacebasemodelnumberandspecificclearanceinformation,refertothefurnaceratingplate,locatedinsideofthefurnacecabinet.
Access for positioning and servicing the unit must beconsidered when locating unit. The need to provideclearance for access to panels or doors may requireclearancedistancesoverandabove the requirements.Allow18inchesminimumclearancefromthefrontoftheunit.However36inchesisstronglyrecommended.SeeTable1forminimumclearancerequirements.
Table1.MinimumClearanceRequirements
INSTALLATION CLEARANCES
CLOSET ALCOVE
Front* 1" 1"Rear 0" 0"Sides 0" 0"Top 6" 6"Ductw/in3ftoffurnace 1/4" 1/4"Vent 0” 0”PlenumWithoutCoilBox 1" 1"PlenumWithCoilBox 0” 0”
NOTES:
AlcoveInstallations-Allow18in.minimumclearancefromfrontofunittonearestwallorpartitionforservicing.
Closetinstallations-Requireareturnairgrillinstalledin the door or a partially louvered door across theopeningforproperaircirculation.Forclearances6”orgreater,theclosetmusthaveanopenfreeareaof235in2minimum.Forspecialclearancesbetween1”-5”,requirementsarealouvereddoorwithaminimumof250in2(1613cm2)freearea.Afullylouveredclosetdoorisstronglyrecommendedforbothinstallationtypes.
LEFTSIDE
FRONT
RIGHTSIDE
REAR
VENT
Theductworkshouldbeappropriatelysizedtothecapacityof the furnace to ensure its proper airflow rating. Forinstallationsabove2,000ft.,thefurnaceshouldhaveasealevelinputratinglargeenoughthatitwillmeettheheatingloadafterderationforaltitude.
CombustionAirQuality
CAUTION:Combustion air must not be drawn from acorrosiveatmosphere.
To maximize heat exchanger life, the combustion airmustbefreeofchemicalsthatcanformcorrosiveacidiccompoundsinthecombustiongases.Therequiredsourceofcombustionairistouseoutdoorair.
Exposuretothefollowingsubstancesinthecombustionairsupplywill result insafetyandperformancerelatedproblems.Thelistbelowcontainsexamplesofchemicalcontainments found in a wide variety of commoncommercialhouseholdproducts:
•Permanentwavesolutions•Chlorinatedwaxesandcleaners•Chlorinebasedswimmingpoolchemicals•Watersofteningchemicals•De-icingsaltsorchemicals•CarbonTetrachloride•Halogentyperefrigerants•Cleaningsolvents(perchloroethylene)•Printinginks,paintremovers,varnishes,etc.•HydrochloricAcid•Cementsandglues•Antistaticfabricsofteners•Masonryacidwashingmaterials
Heating LoadThisfurnaceshouldbesizedtoprovidethedesignheatingloadrequirement.HeatingloadestimatescanbemadeusingapprovedmethodsavailablefromAirConditioningContractorsofAmerica(ManualJ);AmericanSocietyofHeating,Refrigerating,andAirConditioningEngineers;or other approved engineering methods. Excessiveoversizing of the furnace could cause the furnaceand/orventtofailprematurely.
CondensateDisposalThemethodfordisposingofcondensatevariesaccordingtolocalcodes.Consultyourlocalcodeorauthorityhavingjurisdiction. Neutralizer kit P/N 902377 is available forusewith this furnace.Please follow the instructionsprovidedwiththekit.
6
COMBUSTION AIR & VENTING REQUIREMENTS
WARNING:CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below foreachapplianceconnectedtotheventingsystembeingplacedintooperationcouldresultincarbonmonoxidepoisoningordeath.Thefollowingstepsshallbefollowedwitheachindividualapplianceconnectedtotheventingsystembeingplacedinoperation,whileallotherappliancesconnectedtotheventingsystemarenotinoperation:
1.Seal any unused openings in the ventingsystem.
2.Inspecttheventingsystemforpropersizeandhorizontalpitch,asrequiredintheNationalFuelGasCode,ANSIZ223.1/NFPA54or theCSAB149.1,NaturalGasandPropaneInstallationCodesandtheseinstructions.Determinethatthere is no blockage or restriction, leakage,corrosionandotherdeficiencieswhichcouldcauseanunsafecondition.
3.Asfaraspractical,closeallbuildingdoorsandwindowsandalldoorsbetweenthespaceinwhichtheappliance(s)connectedtotheventingsystem are located and other spaces of thebuilding.
4.Closefireplacedampers.5.Turn on clothes dryers and any appliance
notconnectedtotheventingsystem.Turnonanyexhaust fans,suchas rangehoodsandbathroomexhausts,sotheyareoperatingatmaximum speed. Do not operate a summerexhaustfan.
6.Follow the lighting instructions. Place theappliance being inspected into operation.Adjustthethermostatsoapplianceisoperatingcontinuously.
7.Test for spillage from draft hood equippedappliances at the draft hood relief openingafter5minutesofmainburneroperation.Usetheflameofamatchorcandle.
8.Ifimproperventingisobservedduringanyoftheabovetests,theventingsystemmustbecorrectedinaccordancewiththeNationalFuelGasCode,ANSIZ223.1/NFPA54and/orCSAB149.1,NaturalGasandPropaneInstallationCodes.
9.Afterithasbeendeterminedthateachapplianceconnectedtotheventingsystemproperlyventswhentestedasoutlinedabove,returndoors,windows,exhaustfans,fireplacedampersandanyothergas-firedburningappliancetotheirpreviousconditionsofuse.
AVERTISSEMENT:RISQUED’EMPOISONNEMENTAU
MONOXYDE DE CARBONED
Le non-respect des consignes suivantes portantsur chacun des appareils raccordés au systèmed’évacuation mis en service pourrait entraînerl’empoisennement au monoxyde de carbone oula mort. Les consignes suivantes doivent êtreobservéespourchaqueappareilraccordéausystèmed’évacuationmisenservicesilesautresappareilsraccordésausystèmenesontpasenservice:
1.Scellertouteouverturenonutiliséedelasystémed’évacuation;
2.S’assurerquelasystémed’évacuationprésentedes dimensions et une pente horizontaleconformes à la norme ANSI Z223.1/NFPA54, intitulée National Fuel Gas Code ou auxcodes d’installation CSA-B149.1, ainsi qu’auxprésentesinstructions.S’assurerquelasystémed’évacuation n’est pas bloquée, restreinte,corrodée,qu’ellenefuitpasetqu’elleneprésenteaucunautredéfautpotentiellementdangereux;
3.Danslamesuredupossible, fermertouteslesportesetfenêtresdubâtiment,ettouteslesportesentrelapièceoùsetrouvel’appareilraccordéàlasystémed’évacuationetlesautrespiècesdubâtiment.
4.Fermerlesregistresdesfoyers;5.Mettre en service les sécheuses et tout autre
appareil qui n’est pas raccordé à la systémed’évacuation.Fairefonctionneràrégimemaximaltoutventilateurd’évacuation,telqueleshottesdecuisinièreetlesventilateursdesallesdebains.Nepasmettreenservicelesventilateursd’été.
6.Respecterlesinstructionsd’allumage.Mettreenservicel’appareilàl’essai.Réglerlethermostatdemanièreàcequel’appareilfonctionnesansinterruption;
7.Vérifier s’il y a débordement à l’orificed’évacuationducoupetiragedesappareilsdotésd’un coupe tirage 5 minutes après l’allumagedu brûleur principal. Utiliser la flamme d’uneallumetteoud’unechandelle.
8.Si l’on constate, au cours de l’un des essaisquiprécèdent,que l’évacuationestdéficiente,corrigerlesystèmed’évacuationconformémentà lanormANSIZ223.1/NFPA54,NationalFuelGasCode,et(ou)auxcodesd’installationCSAB149.1.
9.Après avoir déterminé que tous les appareilsraccordésà lasystémed’évacuationévacuentcorrectement tel que prescrit ci-dessus,rouvrirlesportesetlesfenêtresetremettrelesventilateursd’évacuation,lesregistresdefoyersettoutautreappareilfonctionnantaugazàleurétatdefonctionnementinitial.
7
Direct Vent InstallationThiscondensingfurnaceiscertifiedforinstallationasaDirectVent(2-pipe)appliance.DirectVent(2-pipe)furnacesdrawcombustionairdirectlyfromtheoutdoorsandthenventthecombustionproductsbackoutside,isolatingtheentiresystemfromtheindoorspace.Itisimportanttomakesurethatthewholesystemissealedandclearancestocombustiblesaremaintainedregardlessoftheinstallationbeing in a confined or unconfined space.This sectionspecifiesinstallationrequirementsforDirectVent(2-pipe)piping.Table2(page8)containsthelengthofventandcombustionairpipingforthistypeofinstallation.
Provisionsmustbemadeduringtheinstallationofthisfurnacethatprovideanadequatesupplyoffreshairforcombustionandventilation.Thecombustionairfromtheoutsideneedstobeclearofchemicalsthatcancausecorrosion. The inlet pipe should not be placed nearcorrosivechemicalssuchasthoselistedonpage5.
Airopeningsontopofthefurnaceandopeningsinclosetdoorsorwallsmustneverberestricted.Ifthefurnaceisoperatedwithoutadequateairforcombustion,theflameroll-outswitchwillopen,turningoffthegassupplytotheburners.NOTE:Thissafetydeviceisamanuallyresetswitch. DO NOT install jumper wires across theseswitches to defeat their function or reset a switchwithoutidentifyingandcorrectingthefaultcondition.Ifaswitchmustbereplaced,useonlythecorrectsizedpartspecifiedintheReplacementPartsListprovidedonline.
VentPipeLength&DiameterForproperfurnaceoperation,thecombustionairandventpipingmustnotbeexcessivelyrestrictive.
• Theventingsystemshouldbedesignedtohavetheminimumnumberofelbowsorturns.
• Allhorizontalrunsmustslopeupwardsfromthefurnaceat1/4inchminimumperrunningfootofvent.
• Transitiontothefinalventdiametershouldbedoneasclosetothefurnaceoutletaspractical.
• Alwaysusethesamesizeoralargerpipeforcombustionairthatisusedfortheexhaustvent.
Table2(page8)indicatesthemaximumallowablepipelengthforafurnaceofknowninputrate,wheninstalledwithpipingofselecteddiameterandnumberofelbows.Tousethetable,thefurnaceinputrate,thecenterlinelengthandthenumberofelbowsoneachpipemustbeknown.
Whenestimatingthelengthofventruns,considerationmustbemadetotheeffectofelbowsandotherfittings.Thisisconvenientlyhandledusingtheideaof“equivalentlength”.Thismeansthefittingsareassignedalinearlengththataccountsforthepressuredroptheywillcause.Forexample:a3”diameter, longradiuselbowisworththeequivalentof3.5feetoflinearrun.
Theequivalent lenghtsof teesandvariouselbowsarelistedinTable2.Measurethelinearlengthofyourventrunandthenaddintheequivalentlengthofeachfitting.The
ImportantInformation
WARNING:FurnaceinstallationusingmethodsotherthanthosedescribedinthefollowingsectionsmustcomplywiththeNationalFuelGasCode(NFGC)andallapplicablelocalcodes.
WARNING:Upon completion of the furnace installation,carefully inspect theentirefluesystembothinsideandoutsidethefurnacetoassureitisproperlysealed.Leaksinthefluesystemcanresultinseriouspersonalinjuryordeathduetoexposureofflueproducts,includingcarbonmonoxide.
WARNING:This furnace must not be vented with otherappliances, even if that appliance is of thecondensingtype.Thisincludeswaterheatersofanyefficiency.Commonventingcanresultinseverecorrosionofotherappliancesortheirventing and can allow combustion gases toescapethroughsuchappliancesorvents.Donotventthefurnacetoafireplacechimneyorbuildingchase.
• This furnace must be vented in compliance withthe current revision of the National Fuel Gas Code(ANSI-Z223.1/NFPA54). Instructions for determiningthe adequacy of combustion air for an installationcan be found in the current revision of the NFGC(ANSI Z223.1 / NFPA54). Consult local codes forspecial requirements. These requirements are forUSinstallationsasfoundintheNFGC.
• TherequirementsinCanada(B149.1)arestructureddifferently. In Canada, venting shall conform to therequirementsofthecurrent(CAN/CGAB149.1or.2)installationcodes.Consultlocalcodesforspecialrequirements.
CategoryIVAppliancesThisfurnaceisclassifiedasa“CategoryIV”appliance,whichrequiresspecialventingmaterialsandinstallationprocedures.CategoryIVappliancesoperatewithpositiveventpressureandrequiresthoroughlysealedventsystems.Theyalsoproduce liquidcondensate,which is slightlyacidicandcancauseseverecorrosionofordinaryventingmaterials.Furnaceoperationcanbeadverselyaffectedbyrestrictiveventandcombustionairpiping.
8
• Thequalityofoutdoorairmustalsobeconsidered.Besurethatthecombustionairintakeisnotlocatednearasourceofsolventfumesorotherchemicalswhichcancause corrosion of the furnace combustion system.(Seepage5forasamplelistofsubstances).
• Routepipingasdirectaspossiblebetweenthefurnaceand the outdoors. Longer vent runs require largerdiameters.Ventpipingmustbeslopedupwards1/4”perfootinthedirectionfromthefurnacetotheterminal.Thisensuresthatanycondensateflowsbacktothecondensatedisposalsystem.
• When a Direct Vent (2-pipe) system is used, thecombustionair intakeandtheventexhaustmustbelocatedinthesameatmosphericpressurezone.ThismeansbothpipesmustexitthebuildingthroughthesameportionofexteriorwallorroofasshowninFigure20,page33.
• Piping must be mechanically supported so that itsweightdoesnotbearonthefurnace.Pipesupportsmustbeinstalledaminimumofevery5feetalongtheventruntoensurenodisplacementafterinstallation.Supportsmaybeatshorterintervalsifnecessarytoensurethattherearenosaggingsectionsthatcantrapcondensate. It is recommended to install couplingsalongtheventpipe,oneithersideoftheexteriorwall(Figure20).Thesecouplingsmayberequiredbylocalcode.
• Ifbreakableconnectionsarerequiredinthecombustionairinletpipe(ifpresent)andexhaustventpiping,thenstraight neoprene couplings for 2” or 3” piping withhoseclampscanbeused.Thesecouplingscanbeorderedthroughyourlocalfurnacedistributor.Toinstallacoupling:1. Slidetherubbercouplingovertheendofthepipe
thatisattachedtothefurnaceandsecureitwithoneofthehoseclamps.
2. Slidetheotherendoftherubbercouplingontotheotherpipefromthevent.
3. Securethecouplingwiththesecondhoseclamp,ensuringthattheconnectionistightandleakfree.
OutdoorTerminations-HorizontalVenting• Ventandcombustionairintaketerminationsshallbe
installedasshowninFigures1&2(page9)andinaccordancewiththeseinstructions:
• VentterminationclearancesmustbeconsistentwiththeNFGC,ANSI2223.1/NFPA54and/ortheCSAB149.1,NaturalGasandPropaneInstallationCode.Table12(page32)liststhenecessarydistancesfromtheventterminationtowindowsandbuildingairintakes.
• Vent and combustion air intake terminations mustbe located to ensure proper furnace operation andconformance to applicable codes. A vent terminalmustbelocatedat least3feetaboveanyforcedairinletlocatedwithin10feet.Thisdoesnotapplytothecombustionairinletofadirectvent(twopipe)appliance.InCanada,CSAB149.1takesprecedenceovertheseinstructions.SeeTable12(page32).
totallength,includingtheequivalentfittinglengths,mustbelessthanthemaximumlengthspecifiedinthetable.
Condensingfurnacecombustionproductshaveverylittlebuoyancy,soTable2istobeusedwithoutconsiderationofanyverticalriseinthepiping.
VentPipeMaterialVentandcombustionairpipeandfittingsmustbeoneofthefollowingmaterialsinthelistandmustconformtotheindicatedANSI/ASTMstandards.CementmustconformtoASTMStandardD2564forPVCandStandardD2235forABS.PVCprimermustmeetstandardASTMF656.WhenjoiningPVCpipingtoABS,usePVCsolventcement.(SeeprocedurespecifiedinASTMStandardD3138).
In Canada, all plastic vent pipes and fittings includinganycement,cleaners,orprimersmustbecertifiedasasystemtoULCS636.Howeverthisrequirementdoesnotapplytopipinginternaltothefurnace.
Materials StandardsSCHEDULE40PVC............................................... D1785PVC-DWV.............................................................. D2665SDR-21&SDR-26................................................. D2241ABS-DWV.............................................................. D2661SCHEDULE40ABS.............................................. F628FOAM/CELLULARCOREPVC........................... F891
VentPipeInstallation
CAUTION:Combustion air must not be drawn from acorrosiveatmosphere.
Thisfurnacehasbeencertifiedforinstallationwithzeroclearancebetweenventpipingandcombustiblesurfaces.However,itisgoodpracticetoallowspaceforconvenienceininstallationandservice.
• In the absence of local codes, the location of anycombustionairinletrelativetoanyventterminalmustbeatleast8inches.Thisincludesinstallationsinvolvingmorethanonefurnace.
MaximumDirectVent,DualPipeLength(FT.)
CMF95 INPUTS(BTU)
INLET / OUTLET2” Diameter
INLET / OUTLET3” Diameter
45,000 30 60
72,000 30 60
†NOTES:
1. Subtract2.5ft.foreachadditional2inchlongradiuselbow,subtract5ftforeachadditional2”shortradiiouselbow,subtract3.5ft.foreachadditional3inchlongradiuselbow,and7ft.foreachadditional3inchshortradiuselbow.
2. Two45degreeelbowsareequivalenttoone90degreeelbow.
3. Thistableappliesforelevationsfromsealevelto2,000ft.Forhigherelevations,decreasepipelengthsby8%per1,000ftofaltitude.
Table2.VentPipeLengths
9
• Allminimumclearances(Figure2)mustbemaintainedtoprotectbuildingmaterialsfromdegradationbyfluegases.
• For optimal performance, vent the furnace throughawall thatexperiencesthe leastexposuretowinterwinds.
• The vent termination shall be located at least 3 ft.horizontallyfromanyelectricmeter,gasmeter,regulatorandanyreliefequipment.ThesedistancesapplyONLYto U.S. installations. In Canada, CSA B149.1 takesprecedenceovertheseinstructions.
• Donot install thevent terminalsuchthatexhaust isdirected into window wells, stairwells, under decksorintoalcovesorsimilarrecessedareas,anddonotterminateaboveanypublicwalkways.
• Ifventinghorizontally,sidewallventkitsareavailableaccordingtothepipediametersizeoftheinstallation.For3inchpipeusekit#904347.Faceplatekit#902375isalsoavailablefor3inchhorizontalventing.Please followtheinstructionsprovidedwiththekits.
• Concentricventterminationkitsareavailableforusewiththesefurnaces.For3inchpipeusekit#904953.Pleasefollowtheinstructionsprovidedwiththekit.
• WhentheventpipemustexitanexteriorwallclosetothegradeorexpectedsnowlevelwhereitisnotpossibletoobtainclearancesshowninFigure1,arisermaybeprovidedasshowninFigure3.Insulationisrequiredtopreventfreezingofthissectionofpipe.SeeTable3(page10)forventfreezingprotection.
OutdoorTerminations-VerticalVentingTerminationspacingrequirementsfromtheroofandfromeachotherareshowninFigure4.Theroofpenetrationmustbeproperlyflashedandwaterproofedwithaplumbingroofbootorequivalentflashing.Ventandcombustionairpipingmaybeinstalledinanexistingchimneywhichisnotinuseprovidedthat:
• Boththeexhaustventandairintakerunthelengthofthechimney.
• Thetopofthechimneyissealedandweatherproofed.• The termination clearances shown in Figure 4 are
maintained.• Noothergasfiredorfuel-burningequipmentisvented
throughthechimney.
12” min. to maximum
expected snow level
(both pipes)
90° Elbow
Exhaust vent
option B
Exhaust vent
option AMounting kit faceplate
secured to wall with screws
(both pipes)
Combustion
air inlet
Exhaust vent
option C
18” Min.
36” Max.
8” Min.
36” Max.
(all positions)
Figure1.Inlet&ExhaustPipeClearances
Note 2
Mechanical draftvent terminal
Direct ventterminal
50,000 Btuhor less
Forced air inlet
Direct ventterminal - more
than 50,000 Btuh
Mechanical
draft vent
terminal
Mechanical draft vent terminal
Less
than
10 ft.
3 ft.
NOTES:1. All dimensions shown are minimum requirements.2. Exterior vent terminations must be located at least 12” above the maximum expected snow level.
Note 2
4 ft
4 ft
12 in.
12 in.
9 in.
Note 2
Figure 2. Vent Locations
Support
NOTE: Vent Configuration to Provide 12" Minimum height above Snow Level.
1/2" ArmaflexInsulation orEquivalent(if required)
12" AboveMaximumExpected
Snow Level
19" Max.(See Note)
Outside Wall
Figure 3. Alternate Horizontal Vent InstallationFigure4.VerticalVentTermination
Com
bust
ion
Air
Exh
aust
Ven
t
12” Above MaximumExpected Snow Level
(Both pipes)
Elbows on the combustion air inlet must be positioned pointing
away from the exhaust vent.
8" Min.
36" Max.
Plumbing Vent Roof Boot(Both Pipes)
10
ExistingInstallationsWhenanexistingfurnaceisremovedfromaventsystemservingotherappliances,theexistingventsystemmaynotbesizedproperlytoventtheremainingappliances(Forexample:waterheater).Animproperlysizedventingsystemcanresultintheformationofcondensate,leakage,orspillage.Theexistingventsystemshouldbecheckedtomakesure it is incompliancewithNFGCandmustbebroughtintocompliancebeforeinstallingthefurnace.
NOTE: Ifreplacinganexistingfurnace,itispossibleyouwillencounteranexistingplasticventingsystemthatissubjecttoaConsumerProductSafetyCommissionrecall.ThepipesinvolvedintherecallareHighTemperaturePlasticVent(HTPV). IfyourventingsystemcontainsthesepipesDONOTreusethisventingsystem!Thisrecalldoesnotapplytootherplasticventpipes,suchaswhitePVCorCPVC.CheckfordetailsontheCPSCwebsiteorcalltheirtoll-freenumber(800)758-3688.
Ventilaire III or IV Air Quality Package(Accessory)TheVentilaireairqualitypackagesareavailabletomeettheventilationrequirementsasoutlinedinH.U.D.StandardPart3280.103(b)(2).Thesepackagesintroduceoutdoorairintothelivingspaceduringfurnacebloweroperation.TheVentilAireIValsoservestoexhaustmoistand/orhotairfromtheatticspace.SeeFigure5fortypicalinstallation.Completeinstallationinstructionsaresuppliedwitheachairqualitypackage.
VentilAireIII
VentilAireIV
Figure 5. VentilAire III & IV
VentFreezingProtection
CAUTION:Whentheventpipeisexposedtotemperaturesbelow freezing (i.e., when it passes throughunheated spaces, chimneys, etc.) the pipemustbeinsulatedwith1/2inchthickspongerubberinsulation,Armaflex-typeinsulationorequivalent.Insulatingpipeisimportanttoavoidcondensate icing.
• Table3liststhemaximumlengthoffluepipethatcantravelthroughanunconditionedspaceoranexteriorspace. The total vent length must not exceed thelengthsnotedintheTable.ForCanadianinstallations,pleaserefertotheCanadianInstallationCode(CAN/CGA-B149.1or2)and/orlocalcodes.
• Forextremelycoldclimatesorforconditionsofshortfurnace cycles (i.e. set back thermostat conditions)thelast18inchesofventpipecanbereduced.It isacceptabletoreducefrom3”to2-1/2”or,3”to2”ifthetotalventlengthisatleast15feetinlength,andtheventlengthiswithintheparametersspecifiedinTable2 (page 8).The restriction should be counted as 3equivalentfeet.Smallerventpipesarelesssusceptibletofreezing,butmustnotbeexcessivelyrestrictive..
• To prevent debris or creatures from entering thecombustionsystem,aprotectivescreenmaybeinstalledoverthecombustionairintakeopening.Thescreensholesizemustbelargeenoughtopreventairrestriction.
Winter DesignTemperature
MaximumFluePipeLength(FEET)inUnconditioned&ExteriorSpaces
WithoutInsulation WithInsulation*
20 45 70
0 20 70
-20 10 60
*NOTE:Insulationthicknessgreaterthan3/8inch,basedonanRvalueof3.5(ftxFxhr)/(BTUxin.)
Table 3. Vent Protection
11
CIRCULATING AIR REQUIREMENTS
WARNING:Donotallowcombustionproductstoenterthecirculating air supply. Failure to prevent thecirculation of combustion products into thelivingspacecancreatepotentiallyhazardousconditions including carbon monoxidepoisoningthatcouldresultinpersonalinjuryordeath.
Allsupplyductsmustbesecuredtothefurnacewithsheetmetalscrewsandadequatelysealed.Whensupplyairisprovidedthroughthebottomoftheunit,thejointbetweenthefurnaceandtheplenummustbeairtight.
Thesurfacethatthefurnaceismountedonmustprovidesoundphysicalsupportofthefurnacewithnogaps,cracksorsaggingbetweenthefurnaceandthefloororplatform.
Supply air ducts must not be connected toany other heat producing device such as afireplaceinsert,stove,etc.Thismayresultinfire, explosion, carbon monoxide poisoning,personalinjury,orpropertydamage.
Plenums & Air DuctsThisunitisdesignedonlyforusewithabottomsupplyduct and must be installed in accordance with thestandards of the National Fire Protection AssociationStandard for Installation of Air Conditioning Systems(NFPA90A),StandardforInstallationofResidenceTypeWarmAirHeatingandAirConditioningSystems(NFPA90B),andallapplicablelocalcodes.NFPApublicationsare available by writing to: National Fire ProtectionAssociation,BatterymarchPark,Quincy,ME02269orvisitwww.NFPA.orgontheweb.
• DesigntheairductsaccordingtomethodsdescribedbytheAirConditioningContractorsofAmerica(ACCA).
• Air ducts must be aluminum, tin plate, galvanizedsheetsteel,orotherapprovedmaterialsforoutletorreturnairducts.Snap-LockorPittsburgh-Lockseamsarepreferred.Allothertypesofseamsmustbemadetighttopreventleakage.
• It isgoodpractice tosealallconnectionsand jointswith industrial grade sealing tape or liquid sealant.Requirements for sealing ducts vary from region toregion. Consult with local codes for requirementsspecifictoyourarea.
• Gaspipingmustnotruninorthroughanyoftheairductsystem.
SupplyAirConnections• Thesupplyductsystemmustbedesignedsothatthe
staticpressuremeasuredexternaltothefurnacedoesnot exceed the listed static pressure shown on thefurnaceratingplate.Thesupplyairmustbedeliveredtotheheatedspacebyduct(s)securedtothefurnacecasing,runningfulllengthandwithoutinterruption.
• Duct system must be designed so that no supplyregistersarelocatedinductsystemdirectlybelowthefurnace.
DampersAnautomatedshutoffdamperisrequiredwhenthehomeis air conditioned by a self-contained unit. A damperis required toprevent chilledair fromflowingover thefurnaceheatexchanger.Thisdamperisdesignedtofitinthefeederductcavity,directlyunderthefurnace.Forproperinstallation,refertotheinstructionsprovidedwiththedamper.Seereplacementpartslistprovidedonline.
UnconditionedSpacesAllductworkpassingthroughunconditionedspacemustbeproperlyinsulatedtominimizeductlossesandpreventcondensation.Useinsulationwithanoutervaporbarrier.Refertolocalcodesforinsulationmaterialrequirements
Closet Installations
WARNING:Failure to comply with the the followinginstructionsmayresultinfire,asphyxiationorcarbonmonoxidepoisoning.
For proper air circulation, closet installations requirea return air grill installed in the door or side wall thatexchangeswiththelivingareaofthehomeasshowninFigure6.Apartiallylouvereddoormayalsobeusedacrosstheopening.Returnairopeningsshouldnotbelocatedtodrawairdirectlyfromabathroom.Grillesplacedinaside
Figure 6. Closet Installation
12
wallrequirea6”clearancefromthewalltothefurnacesothattheairmayenterthefrontgrilleofthefurnace.Inaddition,allreturnairsystems,includingthefloorandceilingsystems,mustmeetthefollowingconditions:• Thereturnairopening,regardlessofitslocationinthe
closet,mustnotbesmallerthansizespecifiedonunitdatalabel.Iflocatedinthefloor,theopeningmustbeprovidedwithameansofpreventing its inadvertentclosurebyflatobject(s)placedovertheopening.
• Thereturn-airopeningintothecloset,regardlessofitslocation,musthaveanopenfreeareaof200in2(1290cm2)minimum.
• Thecross-sectionalareaofthereturnductsystem(infloororceiling)leadingintotheclosetmustnotbelessthan200in2(1290cm2).
• Thetotalfreeareaoftheopeningsinthefloorortheceilingregistersservingthereturnairductsystemmustnotbenotlessthan300in2(1935cm2).
• Materialslocatedinthereturnductsystemshallhaveaflamespreadclassificationof200orless.
• Noncombustiblepanshavingoneinchupturnedflangesare locatedbeneathopenings inafloor returnductsystem.
• Hollow spaces used as ducts or plenums forenvironmentalairmaycontainmineral-insulatedmetalsheathedcable,aluminumsheathedcable,electricalmetallic tubing, rigid metal conduit, flexible metalconduit(nottoexceed4ft),ormetal-cladcables.Wiringmaterials,fixtures,aretobesuitablefortheexpectedambienttemperaturestowhichtheywillbesubjected.
• Thenegativepressureintheclosetmustnotbelessthanminus0.05incheswatercolumnwiththeclosetdoorclosedand the fanoperatingathighspeed.Areadingbelowminus0.05”indicatesadirtyfilterorarestrictedreturnairsystem.
• For floor returnsystems, themanufacturedhousingmanufacturer or installer shall affix a prominentmarkingonornear theappliancewhere it iseasilyreadwhentheclosetdoorisopen.Themarkingshallread:“CAUTION,HAZARDOFASPHYXIATION.DONOTCOVERORRESTRICTFLOORRETURNAIROPENING.”orequivalent.
• Forclosetinstallationwithlessthan6”frontclearance,butnot less than1”,a louvereddoormustbeusedhavingaminimum200in2(1290cm2)freeareaopeningdirectlyinlinewithopeningsinthefurnacedoor.Afullylouvereddoorhavingtheminimumfreeareaisalsopermittedifthefronttoleranceisnotlessthan4”.
Furnace Filter
WARNING:Never operate the furnace without a filter inplace.Accumulatingdustinthereturnaircanbuild up on internal components, resultinginlossofefficiency,equipmentdamage,andpossiblefire.
• CMF95 furnacesaresuppliedwithasingleairfilterwhenshippedfromthefactory.Accessingthefilterdoesnotrequiretoolsandcanbeeasilyremovedfromtheinsideoftheaccessdoor.Thefilterissecuredtothedoorwitharetainingbracket.Itisrecommendedthatthefilterbecleanedorreplacedmonthly.Newlybuiltorrecentlyrenovatedhomesmayrequiremorefrequentchanginguntiltheconstructiondusthasminimized.
• Replacementfiltersareavailableatmostlocalretailers.Inspectfiltersfrequentlyandreplacewhennecessarywithfilterofsamedimensionalsize.Filtersdesignedtoremovesmallerparticlessuchaspollen,mayrequireadditionalmaintenance.
Acoustical TreatmentsDamping ducts, flexible vibration isolators, or pleatedmedia-stylefiltersonthereturnair inletof thefurnacemaybeusedtoreducethetransmissionofequipmentnoiseeminatingfromthefurnace.Thesetreatmentscanproduceaquieterinstallation,particularlyintheheatedspace.However,theycanincreasethepressuredropintheductsystem.Caremustbetakentomaintainthepropermaximumpressureriseacrossthefurnace,temperatureriseandflowrate.Thismaymeanincreasingtheductsizeand/orreducingtheblowerspeed.ThesetreatmentsmustbeconstructedandinstalledinaccordancewithNFPAandSMACNAconstructionstandards.Consultwithlocalcodesforspecial requirements.Forbestsoundperformance,install all the needed gaskets and grommets aroundpenetrationsintothefurnace,suchasforelectricalwiring.
13
MA-200BaseInstallationTheMA-200baseisdesignedforO.E.M.andreplacementinstallationoftheCMF95seriesfurnace.Thewarmairductsystemshouldbedesignedsotheductstaticpressureexternaltothefurnacedoesnotexceedthestaticpressurelistedonthefurnacedatalabel.Floorcut-outsmustbecarefully located to avoid misalignment of the furnaceandairduct.
1.Usingthebasepan(Figure7)asaguide,locateandmarkthe121/8”x121/8”openingfortheFeederDuct.
2.Cutall4sidesof theFeederDuctopening1” largerthanthedrawncutout.NOTE:Cuttingtheopeningto14-1/8”x14-1/8”willallowtheflangesontheundersideofthebasepantofitintheopening.
3.Drilla1”diameterholeforthegaslinethroughthefloorandbottomboardtotheoutside.NOTE:Fuellinesarenotsuppliedwiththefurnace.Theyshouldbeinstalledtocomplywithallapplicablecodes.
4.Droptransitionduct(Figure8)upsidedownthroughtheflooropeningandcenterthetopofthefeederductin14-1/8”x14-1/8”flooropening.Usingthefeederductasaguide,markandcuta12”x12”openinginthesupplyduct.
5.Insertthefeedertabsintothemainductandbendthemovertightlysothat themainductedgesaretrappedbetweenflangesandtabs.NOTE:Metaltapemaybebeusedtoensureanairtightconnection.
6.Installthebasepanaroundthefeederduct.Securewith2screwsintheholesneartherearofthebasepan.
7.Slitthecornersofthefeederductdowntothetopofthebasepan(Figure9).Whilethetopofthedistributionductispulledupwithonehand,benddowneachsideofthefeederducttightlytothebasewiththeotherhand.Trimthemetaltoallowaoneinchflangeoverthetopofthebasepanandsealthatflangewithmetaltape.NOTE:Ifusinga“V”or“U”-boxcrossoversystem,usemanufacturersinstructionsforinstallationdetails.
InstallingtheFurnaceonanMA-200Base1.Carefullyliftthefurnaceoverthebasepanandsetinto
position.Theflangeonthebackofthefurnaceshouldrestontheinsiderailsofthebase.NOTE:InstallationonaMA-200basemay require removalof the frontportionoftherails.
2.Raisethefrontofthefurnacetoclearthegasketonthebottomofthefurnaceandslidethebackuntiltherearflangedropsintothechannelattherearofthebase.Makesurethefurnaceengagesthetabsontherearflangeofthebase.
3.Opentheaccessdoorandfastenthefrontofthefurnaceand thebase to thefloorwith#8x1/2”sheetmetalscrews.
FURNACE INSTALLATIONNOTE: Sinceallinstallationsaredifferent,thesequenceofthesestepsmaydifferfromtheactualinstallation.Theseinstallationproceduresaresuggestedfortypicalfurnaceinstallations.OnlyqualifiedHVACtechniciansshouldinstallthisfurnace.
GeneralInformationTheCMF95furnaceisdesignedonlyforindoorinstallationsand can be readily connected to the high static ductsystemofahome.Unitsareapprovedforsingle/multistoryresidentialormobile/modular/manufacturedstructuresinfreestanding/closet/alcovedownflowonlyconfigurations.
This appliance will provide many years of safe anddependable comfort, providing it is properly installedandmaintained.Abuse,improperuse,and/orimpropermaintenancecanshorten the lifeof theapplianceandcreateunsafehazards.Pleasereadallinstructionsbeforeinstallingtheunit.
Approved installation, operation, and maintenance ofthis appliance must be in accordance with the listedspecificationscontainedintheseinstructionsandotherdocumentssuppliedwiththefurnaceand/oroptionalairconditioningequipment.Unlessitisnoteddifferentlyinthismanual,onlyusefactoryauthorizedkitsandaccessorieswhenmodifyingthisappliance.Refertolocalauthoritieshavingjurisdictionforfurtherinformation.
BeforeYouInstallthisFurnace√ Thisequipment issecurelypackagedat the timeof
shipmentanduponarrivalshouldbecarefullyinspectedfordamagepriortoinstallingtheequipmentatthejobsite.Claimsfordamage(apparentorconcealed)shouldbefiledimmediatelywiththecarrier.
√ Checktheelectricalsupplyandverifythepowersupplyisadequateforunitoperation.Thesystemmustbewiredandprovidedwithcircuitprotectioninaccordancewithlocalbuildingcodes.Ifthereisanyquestionconcerningthepowersupply,contactthelocalpowercompany.
√ Verify theairdeliveryof the furnace isadequate tohandlethestaticpressuredropofthecoil,filter,andductwork.
LocatingtheUnit• Surveythejobsitetodeterminethebestlocationfor
installing theunit.Consideration shouldbegiven toavailabilityofelectricpower,serviceaccess,andnoise.
• Thedimensionsoftheroomoralcovemustbeabletoaccommodatetheoverallsizeof theunitandtheinstallationclearances inTable1 (page5).Physicaldimensions for this furnaceareshown inFigure17(page28).
• Theunitmustbeleveledatinstallationandattachedtoaproperlyinstalledductsystem.
• Thesurfacethatthefurnaceismountedonmustprovidesoundphysicalsupportoftheunit.
14
MA-100UniversalBaseInstallationTheMA-100baseisdesignedprimarilyforreplacementinstallation of the CMF95 series furnace where themanufactured home duct system may be too small orrestrictiveforproperairflow.TheMA-100baseprovidesapproximately4inchesofadditionalplenumspacebeforethedischargeairenterstheductsystem.SeeFigure10.1.Usingtheuniversalbaseasaguide,locateandmark
the12-1/8”x12-1/8”openingfortheFeederDuct.2.Cutall4sidesoftheFeederDuctopening1”largerthan
thedrawncutout.NOTE:Cuttingtheopeningto14-1/8”x14-1/8”willallowthefourflangesontheundersideofthepaneltofitintotheopening.
3.Drilla1”diameterholeforthegaslinethroughthefloorandbottomboardtotheoutside.NOTE:Fuellinesarenotsuppliedwiththefurnace.Theyshouldbeinstalledtocomplywithallapplicablecodes.
4.Settheuniversalbaseinplace.Droptransitionoroffsetfeederduct(Figure8)upsidedownthroughtheflooropeningandcenterthetopofthefeederductin14-1/8”x14-1/8”flooropening.
5.Usingthefeederductasaguide,markandcuta12”x12”openinginthesupplyduct.Removethebaseandtransition feeder duct; then cut the opening into thedistributionduct.
6.Insert the feeder tabs into the main duct and bendthemoveruntilthemainductedgesaretrappedtightlybetweenflangesandtabs.NOTE:Metaltapemaybeusedtoensureanairtightconnection.
7.Set thebottombasepanelover the feederduct.Slitthecornersofthefeederductdowntothetopofthebase.Whilethetopofthedistributionductispulledupwithonehand,benddowneachsideofthefeederduct
Figure10.MA-100UniversalBase,BottomPanel
12 1/8
Feeder DuctOpening
18 1/4
24 1/2
12 1/8
FRONTCombustion Air
Knock-outs(7-1/4” X 2-1/4”)
Figure7.MA-200BasePan
FRONT
Feeder Duct Opening
FlueLocation
24 1/8
8 3/8
12 1/8
12 1/8
9 1/818 1/4
Figure 8. Transition Duct
Heater Duct Below Joists
Flange
BendOver Tabs
Base
FloorJoists
Slit 4 CornersBend Down 4 Sides
TRANSITIONDUCT
Figure 9. Feeder Duct Installation
Heat Duct Below Joists
Base Feeder Duct
FloorJoists
Cut This Line
Bend OverAlong This Line
1"
15
tightlytothebasewiththeotherhand.Trimthemetaltoallowoneinchflangeoverthetopofthebaseandsealthatflangewithmetaltape.
8.Securethetoppaneltothefloorwith2screwsthroughthefrontflange.NOTE:Ifusinga“V”or“U”-boxcrossoversystem,usemanufacturersinstructionsforinstallationdetails.
InstallingtheFurnaceonanMA-100Base1.Carefullyliftthefurnaceovertheuniversalbasepan
andsetintoposition.Avoiddamagingthefeederductassembly.NOTE: Makesurethefurnaceispositionedagainstthebackendofthebase.
2.Openthefurnacedoorandfastenthefurnacetothebaseusing#8x1/2”sheetmetalscrews.
Condensate Drainage
WARNING:Thecondensateproducedbythefurnacemustbedrained.Donotconnectawatersupplytothedrainagehoseofthefurnace.
Figure 11. Condensate Drainage
J-Trap
Drain Pipe Routedthru Slot in CabinetTo External Drain
Inline DrainAssembly
Collector Box Drain
Collector Box Drain
CAUTION:Donotinstalladditionaltrapsinthecondensatedrain.
• If the furnace is installed in an area wheretemperaturesfallbelowfreezing,specialprecautionsmustbemadeforinsulatingcondensatedrainlinesthatdraintotheoutdoors.Ifcondensatefreezesinthelines,thiswillcauseimproperoperationordamage to the furnace. It is recommended thatalldrainlinesontheoutsideoftheresidencebewrappedwithanindustryapprovedinsulationormaterialallowedbylocalcode.
• Beforeroutingthedraintubeoutofthefurnace,loosenthetubeclampandturnthetubesothepreset90°turnfacestheintendeddirectionofexitfromthecabinet.Donotroutethedraintubewithoutrotatingthetubefirst.Thiswillkinkthetubeandpreventcondensatefromdraining.
• Careshouldbetakentoroutethedrainlineawayfromtheburnerbox.Drainlinesrestingontheburnerboxcanbecomekinkedorcollapsedduetotheheatfromtheburnerbox.
• Thecondensatedrainmayexitthroughtheleftorrightslotsinthebottomofthefurnace(Figure11).Makesuretheflexibledrainhoseisnotkinked.
• Thecondensateshoulddrainfromtheplasticcollectorboxasdropletsorasmallstream. Ifyounotice thefurnacehasoperatedformorethan5minuteswithoutdrainingorthestatuslightsonthecontrolboardindicatesanopenpressureswitch(Table6,page27)followthestepsbelow.1.Removethecollectorboxsofttube(Figure11)and
verifytheexitfromthecollectorboxisclearofanydebrisorobstructions.
2.Replacethistubeandverifythefittotheheaderspoutisairtight.Airwillbedrawnintotheheaderifthisconnectionisnottight.
3.Checkothertubeconnectionsalongthedrainsystem.Verifythatallareairtight.
16
• Allgaspipingmustbeinstalledincompliancewithlocalcodesandutilityregulations.IntheabsenceoflocalcodesthegaslineinstallationmustcomplywiththelatesteditionoftheFederalManufacturedHomeConstructions&SafetyStandard(H.U.D.Title24, Part 3280.707[a][2]), National Fuel Gas Code(ANSIZ223.1/NFPA54)or(CAN/CGAB149.1or.2)Installation Codes.
• Some local regulations require the installationofamanualmainshut-offvalveandgroundjointunionexternaltothefurnaceasshowninFigure12 (page 17).The shut-off valve should be readilyaccessible for service and/or emergency use.Consultthelocalutilityorgassupplierforadditionalrequirementsregardingplacementofthemanualmaingasshut-off.
• Gaspipingmustneverruninorthroughairducts,chimneys,gasvents,orelevatorshafts.
• CompoundsusedonthreadedjointsofgaspipingmustberesistanttotheactionsofLPpropanegas.
• Themaingasvalveandmainpowerdisconnecttothefurnacemustbeproperlylabeledbytheinstallerincaseemergencyshutdownisrequired.
• Flexiblegasconnectorsarenotrecommendedforthistypeoffurnacebutmaybeusedifallowedbylocal jurisdiction. Only new flexible connectorsmaybeused.Donotuseaconnectorwhichhaspreviouslyservicedanothergasappliance.
• Adriplegshouldbeinstalledintheverticalpiperuntotheunitifnotenteringthefurnacethroughthefloor.
Table8(page30)listsgasflowcapacitiesforstandardpipesizesasafunctionoflengthintypicalapplicationsbasedonnominalpressuredropintheline.
Thefurnaceisinstalledwithabottomgasentry.Whenconnectingthegassupply,provideclearancebetweenthegassupplylineandtheentryholeinthefurnacecasingtoavoidunwantednoiseand/ordamagetothefurnace.TypicalgashookupsareshowninFigure12.
LeakCheck
FIRE OR EXPLOSION HAZARD•Failuretofollowsafetywarningsexactlycouldresultinseriousinjuryorpropertydamage.
•Installationandservicemustbeperformedbyaqualifiedinstaller,serviceagencyorthegassupplier.
• Donotstoreorusegasolineorotherflammablevaporsandliquidsinthevicinityofthisoranyotherappliance.
WHAT TO DO IF YOU SMELL GAS•Donottrytolightanyappliance.•Donottouchanyelectricalswitch;donot
useanyphoneinyourbuilding.•Leavethebuildingimmediately.•Immediatelycallyourgassupplierfromaneighbor’sphone.Followthegassupplier’sinstructions.
•Ifyoucannotreachyourgassupplier,callthefiredepartment.
WARNING:
RISQUED’INCENDIEOUD’EXPLOSION• Lenon-respectdesavertissementsdesécurité
pourraitentraînerdesblessuresgraves,lamortou des dommages matériels.
• L’installationetl’entretiendoiventêtreeffectuéspar un installateur qualifié, un organisme deserviceoulefournisseurdegazstaller,serviceagencyorthegassupplier.
• Ne pas entreposer ni utiliser de l’essence nid’autresvapeursouliquidesinflammablesdanslevoisinagedecetappareil,nidetoutautreappareil.
QUEFAIRES’ILYAUNEODEURDEGAZ• Nepastenterd’allumeraucunappareil.• Ne toucher à aucun interrupteur électrique;
n’utiliseraucuntéléphonedanslebâtiment.• Évacuerl’immeubleimmédiatement.• Appelerimmédiatementlefournisseurdegazen
employantletéléphoned’unvoisin.Respecteràlalettrelesinstructionsdufournisseurdegaz.
• Sipersonnenerépond,appeler leservicedesincendies.
AVERTISSEMENT:
GAS SUPPLY & PIPING
FIRE OR EXPLOSION HAZARDFailuretofollowsafetywarningsexactlycouldresultinseriousinjuryorpropertydamage.
Nevertestforgasleakswithanopenflame.Use a commercially available soap solutionmade specifically for the detection of leakstocheckallconnections.Afireorexplosionmayresultcausingpropertydamage,personalinjuryorlossoflife.
WARNING:
17
After the gas piping to the furnace is complete, allconnectionsmustbetestedforgasleaks.Thisincludespipe connections at the main gas valve, emergencyshutoffvalveandflexiblegasconnectors(ifapplicable).The soap and water solution can be applied on eachjointorunionusingasmallpaintbrush.Ifanybubblingisobserved,theconnectionisnotsealedadequatelyandmust be retightened. Repeat the tightening and soapcheckprocessuntilbubblingceases.
IMPORTANTNOTE:Whenpressuretestinggassupplylinesatpressuresgreaterthan1/2psig(14inchW.C.),thegassupplypipingsystemmustbedisconnectedfromthefurnacetopreventdamagetothegascontrolvalve.Ifthetestpressureislessthanorequalto1/2psig(14inchW.C.),closethemanualshut-offvalve.
HighAltitudeApplicationHighaltitudeconversionwith this furnacedependsontheinstallationaltitudeandtheheatingvalueofthegas.Installationofthisfurnaceataltitudesabove2,000feetshallbeinaccordancewithlocalcodes,orintheabsenceoflocalcodes,theNationalFuelGasCode,ANSIZ223/NFPA54orNationalStandardofCanada,NaturalGas&PropaneInstallationCodeCGAB149.1.Pleaseconsultyourlocalcodeauthority.
The installer must indicate the furnace has beenconvertedtohighaltitude.Thismaybeaccomplishedbymarkingtheratingplatewithapermanentmarker.
WARNING:Thereductionofinputratingnecessaryforhighaltitudeinstallationmayonlybeaccomplishedwithfactorysuppliedorifices.Donotattempttodrilloutorificesinthefield.Improperlydrilledorifices may cause fire, explosion, carbonmonoxidepoisoning,personalinjuryordeath.
Thefurnacesareshippedfromthefactorywithorificesandgasregulatorsettingsfornaturalgasoperationatsealevelaltitudes.At2000feet,theNFGCrequiresthatthisappliancebederated4%foreach1000feetofaltitude.Forexample,theinputneedstobereduced8%at2,000feet,12%at3,000feet,etc.Thisderationisinreferencetotheinputrateandgasheatingvalueatsealevel.
Toderatethefurnacerequiresknowingtheheatingvalueofthegasattheinstallationsite.Heatingvaluesatparticularjobsitesvaryfortworeasons:
1.Thechemicalmixtureofthegasvariesacrossregionsandisexpressedasthe“sealevelheatingvalue”.
2.Theheatingvaluevariesbyaltitude.Forthisreason,especially inhighaltitudeareas, the localgasutilityspecifiestheheatingvalueattheresidence’sgasmeterasthe“localvalue”.
RISQUED’INDENDIEOUD’EXPLOSION
Le non-respect des avertissements desécurité pourraitd’entraînerdesblessuresgraves,lamortoudesdommagesmatériels.
Nejamaisutiliseruneflammenueporvérifierlaprésencedes fuitesdegaz.Pour lavérificationde tous les joints, utiliser plutôt une solutionsavonneusecommercialefabriquéespécifiquementpurladétectiondesfuitesdegaz.Unincendieouune explosion peut entraîner des dommagesmatériels,desblessuresoulamort.
AVERTISSEMENT:
4
Gas Valve
Shut-OffValve
Elbows
GroundJoint Union
Figure12.TypicalGasConnections
18
ConvertingtoLP/PropaneGasatAltitudesbetween0&10,000FT.
WARNING:The furnace was shipped from the factoryequippedtooperateonnaturalgas.Conversionto LP / Propane gas must be performed byqualified service personnel using a factorysupplied conversion kit. Failure to use theproperconversionkitcancausefire,explosion,propertydamage,carbonmonoxidepoisoning,personalinjury,ordeath.
ConvertingsinglestagevalvestoLP/Propanerequiresthe replacementof theburnerorificesandflipping theregulatorcaptothesidemarkedLP.TheendfacingupshouldnowreadLP.SeeFigure13.
WARNING:Shutoffthegassupplyatthemanualgasshutoffvalve,beforedisconnectingtheelectricalpower.Afireorexplosionmayresultcausingpropertydamage,personalinjuryorlossoflife.Failuretofollowthesafetywarningsexactlycouldresultinseriousinjury,deathorpropertydamage.
WARNING:Toavoidelectricshock,personalinjury,ordeath,turnoff theelectricpowerat thedisconnectorthemainservicepanelbeforemakinganyelectrical connections.
WARNING:Thereductionofinputratingnecessaryforhighaltitudeinstallationmayonlybeaccomplishedwithfactorysuppliedorifices.Donotattempttodrilloutorificesinthefield.Improperlydrilledorifices may cause fire, explosion, carbonmonoxidepoisoning,personalinjuryordeath.InstallationExample
Elevation:.................................................. 5,000feetTypeofGas:...........................................NaturalGasLocalHeatingValueofGas:..............................750
FromTable10,find750andfollowdownthecolumn,stopatthe5,000feetrow.TheheatingvaluelistedisLOW.Table12willbeusedtodetermineorificesizeandmanifoldpressure.
Foraddedflexibility, twotableshavebeenprovidedfornaturalgasinstallationswithhighorlowheatingvaluesatsealevel.Tables11and12(page31)containthemanifoldpressureandorificesizestouseatvariousaltitudes.Table11(HIGH)isfornaturalgasinstallationswithaheatingvalueofmorethan1,000Btupercubic footandTable12 (LOW) is for less than1,000Btupercubic foot.Todeterminewhichtabletouse:
1.Consult the localutility for the localheatingvalueatyourinstallationsite.
2.FromTable10(page31),findyourlocalheatingvalueas supplied by the utility company. Follow down thecolumnandstopatyouraltitudelevel.
3.IfyoursealevelheatingvalueisHIGH,useTable11orifit’sLOW,useTable12.Seeexamplebelow.
Afterchangingtheorifices,itisrequiredthatyoumeasurethegasinputrate.Thismaybeaccomplishedintheusualway,byclockingthegasmeterandusingthelocalgasheatingvalue.SeeVerifyingandAdjustingtheInputRatesection(page23).
IMPORTANTNOTE:Observetheactionoftheburnerstomakesurethereisnoyellowing,liftingorflashbackoftheflame.
InletPressure
Tap
ManifoldPressure Tap
On / Off Knob
TerminalConnectors
NAT N
AT
L
P
L
P
OROTHER SIDE
OF CAP
Regulator Cap
Figure13.GasValve
19
RemovingTheBurnerOrifices1.Set thethermostat totheOFFposition,or its lowest
temperaturesetting.2.ShutOFFthegassupplyatthemanualshutoffvalve
locatedoutsideoftheappliance.3.Turnoffallelectricalpowertotheappliance.4.Removethedoorfromtheburnerboxbyremoving6
screws.5.TurnthegasvalveON/OFFknobtotheOFFposition.
SeeFigure14.6.Removethewiresfromtheterminalsofthegasvalve.7.Removethesupplygaspipingfromthegasvalveinlet.8.Carefullyremovefourscrewssecuringthegasmanifold
assemblytotheburnerassembly.9.Set the screws aside and remove the gas manifold
assemblyfromtheappliance.10.Carefully remove the burner orifices from the gas
manifoldassembly.11.Read the rating plate affixed to the appliance to
determineitsratedinput(Btu/hr)andthesizeofthefactoryinstalledorifices.
IMPORTANT: Before installing an orifice, checkthesideorfaceoftheorificeforthedrillnumbertoensurethatitistheappropriatesize.
12.InstalltheappropriateLP/Propanegasburnerorificesintothegasmanifoldassembly.NOTE:Theorificesareincludedwiththefurnace. Topreventcrossthreading,handtightentheorificesintothegasmanifoldassemblyuntilsnug,thentightenwithawrench.
13.UnscrewthegasvalvepressureregulatorcapmarkedNAT.InvertthecapsoLPfacesup.Reinstallthecapandtightenuntilsnug.MakesureLPisvisibleafterconversion.
GasPressureVerificationMeasuringtheSupplyGasPressure1.TurnOFFthegassupplyatthemanualvalvelocated
ontheoutsideoftheunit.2.Usinga3/16”Allenwrench,removetheplugfromthe
inletpressuretap(INLETsideofgasvalve).SeeFigure13(page18).
3.Installan1/8”NPTpipethreadfitting,thatiscompatiblewithaManometerorsimilarpressuregauge.
4.ConnecttheManometerorpressuregaugetotheInletPressureTap.
5.TurnONthemaingassupplyatthemanualvalve.6.Checkandadjust the incominggas linepressure to
11.0-14.0inchesWaterColumnforLP/Propanegas.7.TurnOFFthegassupplyatthemanualvalve.8.DisconnecttheManometerorpressuregauge.9.RemovetheNPTfittingandreinstalltheINLETpressure
tapplug.Handtightentheplugfirsttopreventcross-threading.Tightenwith3/16Allenwrench.
Figure14.OrificeRemoval
Burner BoxOrifice(X4)
Gas Valve
Gas Manifold
Burner BoxDoor
(X4)
(X6)
WARNING:DonotuseTeflontapeorpipejointcompoundontheorificethreads.Theholeintheorificemaybecomeblockedandcausefire,explosion,propertydamage,carbonmonoxidepoisoning,personalinjury,ordeath.
14.Reinstall the gas manifold assembly to the burnerassemblywiththe4screws,thatwereremovedearlier.NOTE:It isimportantthatthecenteroftheorificesarealignedwiththecenteroftheburners.
15.Reinstalltheburnerboxdoorwiththe6screwsthatwereremovedearlierinstep4.
16.Reconnectthegaspipingtothegasvalveinlet.17.Reconnectthewirestothegasvalveterminals.
20
Lighting&AdjustmentoftheAppliance
WARNING:FIRE OR EXPLOSION HAZARD
Failuretofollowsafetywarningsexactlycouldresultinseriousinjuryorpropertydamage.
Nevertestforgasleakswithanopenflame.Usea commercially available soap solution madespecificallyforthedetectionofleakstocheckallconnections.Afireorexplosionmayresultcausing property damage, personal injury orlossoflife.
1.TurnONthemanualgasvalve,locatedontheoutsideoftheunittotheONposition.
2.Checkallgasconnectionsforleakswithasoapandwatersolution. If thesolutionbubbles there isagasleakwhichmustbecorrected.
3.Turnontheelectricalpowertotheappliance.4.TurnthegasvalveON/OFFknobtotheONposition.
SeeFigure13(page18).5.Setthethermostattoapointaboveroomtemperature
tobegintheheatingcycleofthefurnace.6.Checkthatthefurnaceignitesandoperatesproperly.
Refertotheinstallationinstructionsprovidedwiththeunitforthenormaloperatingsequence.
7.Afterignition,visuallyinspecttheburnerassemblytoensurethattheflameisdrawndirectlyintothecenteroftheheatexchangertube.Inaproperlyadjustedburnerassembly,theflamecolorshouldbebluewithsomelightyellowstreaksneartheouterportionsoftheflame.
NOTE:Theignitermaynotignitethegasuntilallairisbledfromthegasline.Iftheignitioncontrollocksout,turnthethermostattoitslowestsettingandwaitoneminutethenturnthethermostattoapointaboveroomtemperatureandtheigniterwilltryagaintoignitethemainburners.This process may have to be repeated several timesbefore theburnerswill ignite.After theburnersare lit,checkallgasconnectionsforleaksagainwiththesoapandwatersolution.
MeasuringtheManifoldPressureThemanifoldpressuremustbemeasuredbyinstallingapressuregauge(Manometer,MagnehelicMeter,etc.)totheoutletendofthegasvalveasfollows:1.Turnoffallelectricalpowertotheappliance.2.ShutOFFthegassupplyatthemanualshutoffvalve
locatedoutsideoftheappliance.3.Using a 3/16” Allen wrench, remove the manifold
pressuretappluglocatedontheoutletsideofthegasvalve.SeeFigure13(page18).
4.Installan1/8”NPTpipethreadfitting,thatiscompatiblewithaManometerorsimilarpressuregauge.
5.Connect the Manometer or pressure gauge to themanifoldpressuretap.
6.Settheroomthermostataboveroomtemperaturetostartthefurnace.
7.Allow the furnace tooperate for3minutesand thencheckthemanifoldpressure.ComparethemeasuredvaluewiththevalueshowninTable11(page31).
RemovingtheManometer/PressureGaugeAfter themanifoldpressure isverified, theManometerorpressuregaugemustberemovedfromthegasvalve.
1.Turnthethermostattoitslowestsetting.2.TurnOFFthemaingassupplytotheunitatthemanual
shut-offvalve,whichislocatedoutsideoftheunit.3.TurnOFFalloftheelectricalpowersuppliestotheunit.4.Removethepressuregaugeadapterfromthegasvalve
andreplaceitwiththe1/8”NPTmanifoldpressureplugthathadbeenremovedearlier.NOTE:Makesuretheplugistightandnotcross-threaded.
5.TurnONtheelectricalpowertotheunit.6.TurnONthemaingassupplytotheunitatthemanual
shut-offvalve.
CompletingtheConversion
WARNING:Donotalterorremovetheoriginalratingplatefromthefurnace.
1.AffixtheLPlabelfromtheorificepackagetotheratingplate.
2.Reinstalltheappliancedoor.3.Runtheappliancethrough3completecyclestoassure
properoperation.
21
Line Voltage Wiring• Electricalconnectionsmustbeincompliancewithall
applicablelocalcodeswiththecurrentrevisionoftheNationalElectricCode(ANSI/NFPA70).
• ForCanadianinstallationstheelectricalconnectionsandgroundingshallcomplywiththecurrentCanadianElectricalCode(CSAC22.1and/orlocalcodes).
• Itisrecommendedthatthelinevoltage(115VAC)tothefurnacebesuppliedfromadedicatedbranchcircuitcontaining thecorrect fuseorcircuitbreaker for thefurnaceaslistedinTable4(page22).
ELECTRICALSHOCK,FIREOREXPLOSIONHAZARD
Failuretofollowsafetywarningsexactlycouldresultinseriousinjuryorpropertydamage.
Improperservicingcouldresultindangerousoperation, serious injury, death or propertydamage.
• Before servicing, disconnect all electricalpowertofurnace.
• Whenservicingcontrols,labelallwirespriortodisconnecting.Reconnectwirescorrectly.
• Verifyproperoperationafterservicing.”
WARNING:
RISQUEDECHOCÉLECTRIQUE,D’INCENDIEOUD’EXPLOSION
Le non-respect des avertissements de sécuritépourraitentraînerunfonctionnementdangereuxdel’appareil,desblessuresgraves,lamortoudesdommages matériels.
Un entretein incorrect pourrait entraîner unfonctionnementdangereuxdel’appareil,desblessuresgraves,lamortoudesdommagesmatériels
• Couper toute alimentation électrique augénérateurd’airchaudavantdeprodéderauxtravauxd’entretein.
• Aumomentdel’entretiendescommandes,étiqueteztouslesfilsavantdelesdébrancher.S’assurerdelesraccordercorrectement.
• S’assurer que l’appareil fonctionneadéquatementaprésl’entretien.
AVERTISSEMENT:
ELECTRICAL WIRING IMPORTANT NOTES:If replacinganyof theoriginalwiressuppliedwiththe furnace, the replacement wire must be copperwiringandhaveatemperatureratingofatleast105°F(40°C).Forelectricalspecifications,refertothefurnacenameplateorTable4.
An electrical disconnect must be installed readilyaccessiblefromandlocatedwithinsightofthefurnace.SeeFigure18(page29)orthewiringdiagramlabelinsideofthecontroldoor.Anyotherwiringmethodsmustbeacceptabletoauthorityhavingjurisdiction.
Proper linevoltagepolaritymustbemaintained inorder for the control system to operate correctly.VerifytheincomingneutrallineisconnectedtothewhitewireandtheincomingHOTlineisconnectedtotheblackwire.ThefurnacewillnotoperateunlessthepolarityandgroundareproperlyconnectedasshowninFigure18.
Grounding
WARNING:Tominimizepersonalinjury,thefurnacecabinetmust have an uninterrupted or unbrokenelectrical ground. The controls used in thisfurnace require an earth ground to operateproperly.Acceptablemethodsincludeelectricalwireorconduitapprovedforgroundservice.Donotusegaspipingasanelectricalground!
Thermostat/LowVoltageConnections• Thefurnaceisdesignedtobecontrolledbya24VAC
thermostat.Thethermostat’swiringmustcomplywiththecurrentprovisionsoftheNEC(ANSI/NFPA70)andwithapplicablelocalcodeshavingjurisdiction.
• The thermostat must be installed according to theinstructionssuppliedbythethermostatmanufacturer.Lowvoltageconnections(24VAC)fromthethermostatarewiredtotheterminalstripontheintegratedcontrolinthefurnace.Figure15(page22)containstheproperconnectionsforheatingonly(two-wire)andheating/cooling (four-wire) applications. Recommendedminimumwiregaugefor thermostatwiring isshowninTable4(page22).
• The thermostat should be mounted about 5 feetabovetheflooronaninsidewall.DONOTinstallthethermostat onanoutsidewall or anyother locationwhereitsoperationmaybeadverselyaffectedbyradiantheatfromfireplaces,sunlight,orlightingfixtures,andconvectiveheatfromwarmairregistersorelectricalappliances. Refer to the thermostat manufacturer’sinstructionsheetfordetailedmountinginformation.
22
HeatAnticipatorSet the heat anticipator according to the instructionssuppliedbythethermostatmanufacturer.Todeterminetheheatanticipatorsetting:1.Addthecurrentdrawofthesystemcomponents;or2.MeasurethecurrentflowonthethermostatR-Wcircuit
afterthecirculatingblowermotorhasstarted.
Figure 16. Line Voltage Field Wiring
Field Supplied Disconnect w/in Sight of Furnace
Field SuppliedPanel Connector
Field SuppliedFused Service
Panel
Black (Hot)
White (Neutral)
Green or Bare(Ground)
Black
White
Black
White
Black
White
Field Line Voltage Wiring
Factory Line Voltage Wiring
Ground Ground
Junction Box (may be int. or ext. to the furnace). Theseconnections can be made in the field supplied disconnect
at the furnace. NOTE: Connections made within the furnaceburner compartment do not require a junction box.
Ground
FurnaceModel
NumberCMF95-
FurnaceInput(Btuh)
CabinetWidth(in.)
NominalElectrical
Supply
MaximumOperating
Voltage
MinimumOperating
Voltage
MaximumFurnaceAmperes
MinimumWire
Gauge
MaximumFuse or CircuitBreakerAmps*
MinimumCircuit
Ampacity1
MamimumOvercurrentProtection2
045 45,000 18 115-60-1 127 103 11.0 14 20 13.1 21.7
072 72,000 18 115-60-1 127 103 10.4 14 20 12.4 20.4
NOTE:Minimumwiregaugeandmaximumfuse/circuitbreakeramperagearebasedonMCA1andMOP2calculations.Thisfurnaceisapprovedforinstallationwitha15or20ampfuse/circuitbreakerhoweverwiringsizingmustadheretocurrentversionoftheNECand/orapplicablelocalcodesdependingupontheovercurrentprotection.
ThermostatWireGaugeRecommendedThermostatWireLength
2-wire-Heating 4or5wire-Cooling
24 55ft. 25ft.
22 90ft. 45ft.
20 140ft. 70ft.
18 225ft. 110ft.
* Time-delayfusesorcircuitbreakersarerequired.
Table4.WireLength&VoltageSpecifications
Figure15.LowVoltageField,Four-wireHeating/CoolingApplications
RC
YG
W
STATUS
FLAMEGREENRED
180C
OO
LH
EA
T
1209060
YELLOW
BLOWEROFF
DELAY
LO
WML
MH
HIG
HE
ACL1
XF
MR
HU
M
CO
M SPEEDSELECT
3 AMPFUSE
24V
5
NE
UT
RA
LS
ROOMTHERMOSTAT
A/C CONDENSING UNIT
CONDENSING UNITCONTROL BOX
EXPANSION PORT(MOTOR CONNECTION)
FIELD WIRINGLOW VOLTAGECONNECTION
RCYGW
NOTE: The “Y” terminal on the control board must be connected to the thermostat for proper cooling mode operation.
ConnectR & W
For Heating Only
2
ELECTRONIC AIR CLEANER
MOTOR SPEED TAPS (NOT USED)
HUMIDIFIER TAP
NEUTRAL LEADS
6 3
4 1
789
5 26 3
4 1
FAN
23
START-UP&ADJUSTMENTSPre-StartCheckList√ Verifythepolarityoftheconnectionsarecorrect,the
linevoltagepowerleadsaresecurelyconnectedandthefurnaceisproperlygrounded.
√ Verifythethermostatwires(R,W,Y,&G)aresecurelyconnectedtothecorrectleadsontheterminalstripofthecircuitboard.
√ Verifythegaslineservicepressuredoesnotexceed10.0inchesofW.C.,andisnotlessthan4.5inchesW.C.fornaturalgas.ForLPgasthelineservicepressuremustnotexceed14in.W.C.,andmustnotbelessthan11.0in.W.C.
√ Verify the roll-out and vent switches are closed. Ifnecessary,presstheredbuttontoresetaswitch.DO NOTinstallajumperwireacrossaswitchtodefeatitsfunction.Ifaswitchreopensonstartup,DONOTresettheswitchwithoutidentifyingandcorrectingthefaultcondition.
√ Verify the blower door is in place, closing the doorswitchinthelinevoltagecircuit.
√ Verifythegaslinehasbeenpurgedandallconnectionsareleakfree.
Start-upProceduresDonotperformthesestepsuntilallofthechecksinthepreviousstepshavebeencompleted:1.Setthethermostattothelowestsetting.2.Turnoffallelectricalpowertothefurnace.3.FollowtheOperatingInstructionsonthelabelattached
tothefurnace.4.Setthethermostataboveroomtemperatureandverify
theOperatingSequence(page25).5.After5minutesofoperation,setthethermostatbelow
roomtemperatureandverifysteps9-10oftheOperatingSequence.
Verifying&AdjustingInputRateThe input ratemustbeverified foreach installation topreventover-firingofthefurnace.NOTE:Theinputratemustnotexceedtherateshownonthefurnaceratingplate.Ataltitudesabove2,000feet,itmustnotexceedthatontheratingplateless4%foreach1,000feet.Todeterminetheexactinputrate,performthefollowingprocedures:
1.Shutoffallothergasfiredappliances.2.Startthefurnaceandrunitforatleast3minutes.3.Measure the time (in seconds) required for the gas
metertocompleteonerevolution.4.Convertthetimeperrevolutiontocubicfeetofgasper
hourusingTable7(page30).5.Multiplythegasflowrateincubicftperhrbytheheating
valueofthegasinBtupercubicfttoobtaintheinputrateinBtuh.Seeexample.
6.Themanifoldpressuremustbesettotheappropriatevalueforeachinstallationbyaqualifiedinstaller,serviceagencyorthegassupplier.
WARNING:Donotattempttodrillthegasorifices.Useonlyfactory supplied orifices. Improperly drilledorifices may cause fire, explosion, carbonmonoxidepoisoning,personalinjuryordeath.
a.)Obtain themanifoldpressuresettingrequired forthisinstallationbyreferringtoTable11forPropaneorTable12(page31)forNaturalGas.
b.)Remove the regulator capscrew from the INLETsideoftheregulator.SeeFigure30,page30-gasvalvepictureinLPsection.
c.)Slowlyturntheadjustmentscrewinsidetheregulatorto obtain the appropriate manifold pressure.NOTE:Turningthescrewclockwiseincreasesthepressureandturningthescrewcounter-clockwisedecreases the pressure. To prevent backing thescrewallthewayoutfromthevalve,turnthescrewslowly.
d.)Replaceandtightentheregulatorcapscrewovertheadjustmentscrew.
Verifying&AdjustingTemperatureRiseAfterinstallationofthefurnace,confirmthetemperatureriseofthefurnaceiswithinthelimitsspecifiedontheratingplate.Any temperatureriseoutside thespecified limitscouldresultinprematurefailureoftheheatexchanger.
For typical duct systems, the temperature rise will fallwithin the limits specified on the rating plate with theblowerspeedatthefactoryrecommendedsetting.Ifthemeasuredtemperatureriseisoutsidethespecifiedlimits,itmaybenecessarytochangethespeedoftheblower.NOTE: Lowering the blower speed will increase thetemperatureriseandahigherblowerspeedwilldecreasethetemperaturerise.
Thefurnaceisequippedwithamulti-speedmotor.Heatingandcoolingspeedselectionismadebymovingtheswitchontheintegratedcontrollocatedinthefurnace.
1.Placethermometersinthereturnandsupplyairstreamasclosetothefurnaceaspossible.IMPORTANT:Thethermometeronthesupplyairsidemustbeshieldedfromdirect radiation fromtheheatexchanger toavoidfalsereadings.
2.Consult Table 5 (page 24) and the rating plate forthe proper circulating air flow and temperature rise.
Example:• Timefor1revolutionofagasmeterwitha1cubic
ftdial=40seconds.• FromTable7read90cubicftgasperhr.• Localheatingvalueofthegas(obtainedfromgas
supplier)=1,040Btupercubicft.• Inputrate=1,040x90=93,600Btuh.
24
Table5.MaximumAirflow&TemperatureRises(°F)
MODEL NUMBER& HEATING INPUT
(BTUH)
MOTORSPEED
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
0.1 0.2 0.3 0.4 0.5
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
CMF9504545,000
HIGH* 1380 29 1335 30 1290 31 1230 32 1175 34
MEDHIGH 1350 29 1295 31 1240 32 1190 33 1135 35
MEDLOW 1100 36 1055 38 1020 39 975 41 920 43
LOW** 1000 40 970 41 935 42 900 44 860 46
CMF9507272,000
HIGH* 1485 43 1440 44 1390 46 1340 47 1290 49
MEDHIGH** 1263 50 1235 51 1205 53 1160 55 1115 57
MEDLOW 1130 56 1100 58 1175 54 1045 61 1000 63
LOW 880 72 846 75 830 76 805 79 770 82
NOTES:
*FactorySetCoolingSpeed.
**FactorySetHeatingSpeed.
1.Temperaturerises(°F)inthetableareapproximate.Actualtemperaturerisesmayvary.
2.Temperaturerisesshadedingrayareforreferenceonly.Theseconditionsarenotrecommended.
3.Airflowperformanceiswithafilter.
NOTE: This furnace is designed to operate with amaximumexternalpressureriseof0.3inchesofwatercolumn.Itisimportantthattheductsystembedesignedtoprovidethecorrectflowratesandexternalpressurerise.An improperlydesignedductsystemcanresultinnuisanceshutdowns,andcomfortornoiseissues.
3.Adjustall registersandductdampers to thedesiredpositionandrunthefurnacefor10to15minutesbeforetakinganytemperaturereadings.Thetemperatureriseis the difference between the supply and return airtemperatures.
VerifyingBurnerOperation
CAUTION:Thedoorovertheburnersmayonlybeopenforinspectionpurposesonly.Thedoormustbeinstalledduringunattendedoperation.
1.Setthethermostataboveroomtemperatureandobservetheignitionsequence.NOTE: Theburnerflameshouldcarry over immediately between all burners withoutliftingoff,curling,orfloating.Theflamesshouldbeblue,withoutyellowtips.
2.Aftervalidatingtheflame,changethermostatsettingtobelowroomtemperature.
3.Verifytheburnerflameiscompletelyextinguished.
4.Replacetheburnercompartmentdoor.
VerifyingOperationoftheSupplyAirLimitSwitch
Note: Aproperlyfunctioninglimitswitchshouldturnoffthegasvalvewhenthereturnisblocked(timedependsonhowwellthereturnairisblocked).Thecirculatingairandcombustionblowersshouldcontinuetorunwhenthelimitswitchopens.
1.Verifytheblowerdoorissecurelymountedinplaceandthatthereispowertothefurnace.
2.Blockthereturnairflowtothefurnacebyinstallingaclose-offplateinplaceoforupstreamofthefilter(s).
3.SetthethermostataboveroomtemperatureandobservetheOperatingSequence.
4.Removetheclose-offimmediatelyafterthelimitswitchopens.Ifthefurnacecontinuestooperatewithnoreturnair,setthethermostatbelowroomtemperature,shutoffpowertothefurnace,andreplacethelimitswitch.
25
ELECTRICALSHOCK,FIREOREXPLOSIONHAZARD
Failuretofollowsafetywarningsexactlycouldresultinseriousinjuryorpropertydamage.
Improperservicingcouldresultindangerousoperation, serious injury, death or propertydamage.
• Before servicing, disconnect all electricalpowertofurnace.
• Whenservicingcontrols,labelallwirespriortodisconnecting.Reconnectwirescorrectly.
• Verifyproperoperationafterservicing.”
WARNING:
RISQUEDECHOCÉLECTRIQUE,D’INCENDIEOUD’EXPLOSION
Le non-respect des avertissements de sécuritépourraitentraînerunfonctionnementdangereuxde l’appareil,desblessuresgraves, lamortoudes dommages matériels.
Unentretein incorrectpourraitentraînerunfonctionnementdangereuxdel’appareil,desblessuresgraves,lamortoudesdommagesmatériels
• Couper toute alimentation électrique augénérateurd’airchaudavantdeprodéderauxtravauxd’entretein.
• Aumomentdel’entretiendescommandes,étiquetez tous les fils avant de lesdébrancher. S’assurer de les raccordercorrectement.
• S’assurer que l’appareil fonctionneadéquatementaprésl’entretien.
AVERTISSEMENT:
OPERATING SEQUENCETheoperatingsequences for theheating,cooling,andfanmodesaredescribedbelow.Refer to thefieldandfurnacewiringdiagrams:(Figures15&16,page31)and(Figure18page28).
HeatingCycle1.The thermostat calls for heat by energizing the W
terminalwith24VAC.2.Thecontrolverifiesthepressureswitchisopen.3.Ifthepressureswitchisopen,thecontrolenergizesthe
inducerandwaitsforthepressureswitchtoclose.Thepressureswitchmustclosewithin10seconds.
4.Thecontrolrunstheinducerfora30secondpre-purge.5.The control energizes the Hot Surface Igniter (HSI)
outputfortheappropriatewarm-uptimelimit.6.Thecontrolenergizesthemaingasvalvefor3seconds.7.Iftheflameprovedandignitesthegas,thecontrolde-
energizestheHSI.Thegasvalveandinducerremainsenergized.Thecontrolgoestoblowerondelay.
8.Ifflameispresent,thecontrolenergizestheblowerontheselectedHEATspeed30secondsafterthegasvalveopened.Thegasvalveandinducerremainenergized.
9.Whenthethermostatdemandforheatissatisfied,thecontrolde-energizesthegasvalve.TheInduceroutputremainsonfora30secondpost-purgeperiod.
10.Blower off timing begins when the thermostat issatisfied.ThecontrolwilloperateattheselectedHEATspeedof60,90,120,or180seconds.Ifthebloweroffdelay jumper isnotpresent, the fanshouldstilloperatefor120secondsattheselectedHEATspeed.TheIndoorblowermotorisde-energizedafterabloweroffdelayasselectedbythemovablejumper.
CoolingCycle1.The thermostatcalls forcoolingbyenergizing theY
terminalwith24VAC.2.Thecontrolenergizestheblowerincoolingspeedand
sends24VACtothecontactorinthecondensingunit3.Whenthethermostatremovesthecallforcooling,the
contactorintheoutdoorcondensingunitisde-energizedandthecontrolcontinuestorunthefanforaperiodof60seconds.
Fan Mode• When the thermostat energizes the G terminal for
continuousfan(withoutcallingforheatorcooling),theindoorfanisenergizedontheselectedFANspeed.
• Ifacallforcoolingoccursduringcontinuousfan,theblowerwillswitchovertotheselectedCOOLspeed.
• If the W terminal receives a call for heat duringcontinuousfan,theblowerwilldeenergize.
• Acallforfanisignoredwhileinlockout.
MAINTENANCEPropermaintenanceismostimportanttoachievethebestperformancefromafurnace.Followtheseinstructionsforyearsofsafe,troublefreeoperation.
• Thesemaintenanceinstructionsareprimarilyintendedtoassistqualifiedtechniciansexperiencedinthepropermaintenanceandoperationofthisappliance.
• Alwaysclosethedooronthefurnaceafterservicingorcleaning/changingthefilters.Donotoperatethefurnacewithoutthedoorclosed.
• Verify the thermostat is properly installed and willnotbeaffectedbydraftsorheatfromlampsorotherappliances.
26
• To achieve the best performance and minimizeequipment failure it is recommended that a yearlymaintenancecheckupbeperformed.Ataminimum,thischeckshouldincludethefollowingitems:
Air Filter(s)
WARNING:Never operate the furnace without a filter inplace.Dustand lintcanbuildupon internalcomponents, resulting in loss of efficiency,equipmentdamage,andpossiblefire.
Anairfilterissuppliedwiththefurnaceasshippedfromthefactory.Filtersshouldbechangedorcleanedmonthlyduringtheheatingseason.Newlybuiltorrenovatedhomesmayrequiremorefrequentchanginguntiltheconstructiondusthasminimized.
Filters designed to remove smaller particles such aspollen,mayrequireadditionalmaintenance.
BlowerCompartmentDirt and lint can create excessive loads on the motorresultinginhigherthannormaloperatingtemperaturesandshortenedservice life. It is recommended that theblowercompartmentbecleanedofdirtor lintthatmayhaveaccumulatedinthecompartmentorontheblowerandmotoraspartoftheannualinspection.
CleaningofBurnersIf theburnersmustbecleaned,followsteps1-12.SeeFigure17(page27)forcomponentlocation.1.Shutoffgassupplytothefurnaceatthemeterorata
manualvalveinthesupplypiping.2.Turnoffallpowertothefurnaceandsetthethermostat
toit’slowestsetting.3.Turn the gas control knob to the OFF position. See
Figure13(page18).4.Disconnectthewiresfromthegasvalve,igniter,flame
sensor,andflamerolloutswitch.
CAUTION:To prevent damage to the unit or internalcomponents, it is recommended that twowrenchesbeusedwhenlooseningortighteningnuts.Donotovertighten!
5.Usingtwowrenches,separatetheground-jointunioninthegassupplypipingatthefurnace.
6.Remove the piping between the gas valve and theground-jointunion.(Ifapplicable).
7.Removetheburnerboxdoor(6screws).8.Remove4screwssecuringthemanifoldassemblyto
theburnerbox.9.Remove 4 screws from the corners of the box and
carefullyremovetheburnerassemblyfromthefurnace. IMPORTANT: DO NOT damage the igniter whileremovingtheburnerassembly.
10.Inspecttheburnersforaccumulateddustordebris.If necessary carefully clean them with a soft wirebrushandavacuumcleaner.IMPORTANT:DO NOT damage the igniter while cleaning the burnerassembly.
11.Replaceallthepartsinreverseorderthattheywereremoved.
12.Followthelightinginstructionsfoundonthefurnacedoortoreturnthefurnacetooperation.Verifyproperoperationafterservicing.
VentSystem
WARNING:Holesintheventpipeorheatexchangercancausecombustionproductstoenterthehome.Replacetheventpipeorheatexchangerifleaksare found. Failure to prevent the circulationofcombustionproductsintothelivingspacecan create potentially hazardous conditionsincluding carbon monoxide poisoning thatcouldresultinpersonalinjuryordeath.
Checktheinletpipe(ifapplicable)andoutletpipetoensurethey are not blocked by debris. Any damaged sectionofventpipemustbe replaced,andanyobstructionorblockagemustberemovedpriortooperatingthefurnace.
HeatExchanger&BurnerMaintenanceThefurnaceshouldoperateformanyyearswithoutsootbuildupinthefluepassageways,however,theflue,ventsystem,andburnersshouldbeinspectedandcleaned(ifrequired)byaqualifiedservicetechnicianannuallytoensure continued safe operation. Pay attention to anydeteriorationfromcorrosionorothersources.
LubricationThebearingsintheblowermotorandinducerblowerusedinthesefurnacesarepre-lubricatedandsealedbythemanufacturer.Nofurtheroilingofthebearingsisrequiredforthelifeofthemotor.
27
Ifthefurnacefailstooperatecheckthefollowing:• Isthethermostatoperatingproperly?• Aretheblowercompartmentdoor(s)inplace?• Isthefurnacedisconnectclosed?• Hasthecircuitbreakertrippedorthecontrolboardfuse
burnedopen?• Isthegasturnedon?• Areanymanualresetswitchesopen?• Isthefilterdirtyorplugged?• Istheflamesensorcoated?(Removeandcleanwith
steelwool.(Donotuseemeryclothorsandpaper!)• Isthereblockageinthecondensatedrainswitch?Also
verifythatthereisnodoubletrappingofcondensate.• Is thesecondaryheatexchanger freeofdebrisand
clogs?• Isevaporatorcoilcleanandfreeofdebris(Ifapplicable).• ArealltheLED’sonthefurnacecontrolboardconstantly
ON?Ifnot,refertoTable6orthewiringdiagram(Figure18,page29)todeterminefaultcondition.
IMPORTANTNOTE:Thefurnacewilllockoutafter5failedattemptsfor ignitionandwill tryagaineveryhourifthecallforheatremains.
• Iftheinducerblowerisoperating,anditemsabovehavebeenverified,checktheblowerlimitswitchandresetifnecessary.SeeFigure17forcomponentlocation.
• IfthefurnaceoperateswhentheBlowerLimitSwitchisreset,contactaqualifiedservicetechniciantoidentifyandrepairtheproblem.
• If the furnace still doesn’t operate, check the flameroll-outswitch(Figure17)andresetifnecessary.
• Ifthefurnaceoperateswhentheflamerolloutswitchisreset,contactaqualifiedservicetechniciantoidentifyandrepairtheproblem.
DiagnosticDescription Green LED Red LED
ControlFault(NoPower) Off Off
L1/NeutralPolarityFault Flash Flash
1HourLockout AlternatingFlash
NormalOperation On On
PressureSwitchClosedFault On Flash
PressureSwitchOpenFault Flash On
OpenLimitSwitchFault Flash Off
MotorFault On Off
DiagnosticDescription Yellow LED
LowFlameSensorSignal ContinuousFlash
FlamePresent On
Table 6. Control Board Fault Conditions
TROUBLESHOOTING DESCRIPTION OF COMPONENTSThedescriptionsbelowarevariousfunctionalcomponentsthataffecttheoperationandshuttingdownofthisfurnace.SomeofthesecomponentsandtheirlocationsareshowninFigure17.Ifanycomponentofthefurnacemustbereplaced,useonlyfactoryauthorizedreplacementpartsspecifiedintheReplacementPartsListprovidedonline.
BlowerLimitSwitch:Preventsoperationwhenblowerisnotoperational.
Flame Sensor: Verifieswhenaflamehascarriedoverfromtheignitertotheoppositeendburner.Ifnoflameisdetected,thefurnacewillshutdownwithin4seconds.
FlameRoll-OutSwitch:Verifiesthattheburnerflamesaredrawnintotheheatexchangertubes.Iftheburnerflamesarenotproperlydrawnintotheheatexchanger,theflameroll-outswitchwillclosethegasvalveandinitiatetheshutdowncycle.
GasValve:Controlstheflowofgastotheburners.Whenthe gas valve is energized it automatically opens andregulatesthegaspressureinthemanifold.
Inducer Assembly: Vents products of combustion totheoutside.
Pressure Switch: Verifies that the inducer is drawingthecombustiongasesthroughtheheatexchanger.Thepressureswitchpreventsfurnaceoperationwithexcessiveflue/condensateblockageorimproperinduceroperation.
Main Air Limit Switch: Prevents the air temperatureleavingthefurnacefromexceedingthemaximumallowableoutletairtemperature.
Figure17.FurnaceComponents
Blower Assembly
Inducer Assembly
Gas Valve
Gas Manifold &Burner Assembly
ON / OFF Switch
Control Board
Limit Switch
Inline DrainAssembly
24V Transformer
Igniter
Main Air Limit Switch
Flame Sensor
Roll-Out Switch
Combustion Air Pipe
Exhaust Vent Pipe
28
FIGURES & TABLES
Figure 18. Furnace Dimensions
57
18
11 5/8
11 5/8
1 3/8
1 5/8
24 3/16
4 3/4
2 7/8
1 3/4
1 3/4
16 1/2
13 5/8
3 1/2” X 1 1/2” Slots for Gas Pipe& Condensate drains (Typ.)
FRONTVIEW
LEFTSIDE
TOPVIEW
BOTTOM VIEW
3 3/4” Dia.(2 Places)
32
2
7/8 Dia. Holefor Line Voltage
RIGHTSIDE
3 1/2
1 1/2 Dia. Holefor Thermostat
22 1/2
29
WIRING DIAGRAM
Figure 19. CMF95 Wiring Diagram
IGN
ITO
R
IND
UC
ER
FLA
ME
SE
NS
OR
C
VE
NT
LIM
IT
DO
OR
SW
ITC
H
R
4 S
PE
ED
MO
TO
R
FLA
ME
RO
LLO
UT
GA
SV
ALV
E
H
MH
ML
L
C
BLO
WE
RD
EC
KLI
MIT
SU
PP
LYA
IR L
IMIT
PR
ES
SU
RE
SW
ITC
H
R C Y G W
LOW
ML
MH
HIGH
EAC
L1
XFMR
HUM
123
456
789
123
456
CO
M3
AM
P F
US
E24
V
24 V
120
V
WH
ITE
W/ B
LK S
TR
IPE
S
BLK
W/ W
HIT
E S
TR
IPE
S
12
34
12
34
11
22
33
44
55
66
77
88
99
L1ANEUTRALS
GR
EE
N YE
LLO
W
RE
D
RC
TXRXW
COM
1 21 2
1 21 2
12
34
WH
ITE
RE
D
BLU
EO
RA
NG
E
BLA
CK
WH
ITE
BLA
CK
BLU
E
BLU
E
BLUE
BLU
E/W
HIT
E
BLUE
OR
AN
GE
OR
AN
GE
GR
EE
N
WHITE
BLUE
YE
LLO
W
RE
DO
RA
NG
E
BLA
CK
WH
ITE
BLU
E
BLA
CK
RE
D
BLA
CK
BLA
CK
BLACK
BLU
E
GR
EE
N
BLUE
BLACK
BLACK
WH
ITE
YE
LLO
W
SIN
GLE
STA
GE
TH
ER
MO
STA
T
TO OUTDOOR UNIT
FIE
LD W
IRIN
G
LEG
EN
D:
LOW
VO
LTA
GE
HIG
H V
OLT
AG
E
WIR
ING
DIA
GR
AM
For
80+
and
90+
Sin
gle
Sta
ge
Furn
aces
Ref
er t
o t
he
Inst
alla
tio
n In
stru
ctio
ns
pro
vid
ed w
ith
th
e fu
rnac
e fo
r th
e p
rop
er h
eati
ng
an
d c
oo
ling
sp
eed
sfo
r yo
ur
app
licat
ion
.
If a
ny o
f th
e o
rig
inal
wir
e as
su
pp
lied
wit
hth
e fu
rnac
e m
ust
be
rep
lace
d, i
t m
ust
be
rep
lace
d w
ith
wir
ing
mat
eria
l hav
ing
ate
mp
erat
ure
of
at le
ast
105
C.
Use
co
pp
er c
on
du
cto
rs o
nly
.
Dia
gn
ost
ic D
escr
ipti
on
Gre
en L
ED
Red
LE
DC
ontr
ol F
ault
(No
Pow
er)
Off
Off
L1 /
Neu
tral
Pol
arity
Fau
ltF
lash
Fla
sh1
Hou
r Lo
ckou
tn
On
Onoitarep
O lamro
N Pre
ssur
e S
witc
h C
lose
d F
ault
On
Fla
shP
ress
ure
Sw
itch
Ope
n F
ault
Fla
shO
nO
pen
Lim
it S
witc
h F
ault
Fla
shO
ff
Dia
gn
ost
ic D
escr
ipti
on
Low
Fla
me
Sen
sor
Sig
nal
Fla
me
Pre
sent
FA
UL
T C
ON
DIT
ION
S
Yel
low
LE
DC
ontin
uous
Fla
shO
n
Alte
rnat
ing
Fla
sh
7112
16A
(Rep
lace
s 71
1216
0)05
/12
30
GAS INFORMATION
GAS PIPE CAPACITIES
NominalPipeDiameter (IN.)
LengthofPipeRun(Feet)
10 20 30 40 50 60 70 80
1/2 130 90 75 65 55 50 45 40
3/4 280 190 150 130 115 105 95 90
1 520 350 285 245 215 195 180 170
11/4 1,050 730 590 500 440 400 370 350
11/2 1,600 1,100 890 760 670 610
NOTE: Thecubicfeetperhourlistedinthetableabovemustbegreaterthanthecubicfeetperhourofgasflowrequiredbythefurnace.Todeterminethecubicfeetperhourofgasflowrequiredbythefurnace,dividetheinputrateofthefurnacebytheheatingvalue(fromgassupplier)ofthegas.
Cubic Feet Per Hour Required =Input To Furnace (Btu/hr)
Heating Value of Gas (Btu/Cu. Ft.)
Table8.CapacityofBlackIronGasPipe(cu.ft.perhour)forNaturalGasw/SpecificGravity=0.60
GAS FLOW RATES
TIME FORONE REVOLUTION
(SECONDS)
CUBIC FEET PERREVOLUTION OF GAS METER
1 5 10
10 360 1,800 3,600
12 300 1,500 3,000
14 257 1,286 2,571
16 225 1,125 2,250
18 200 1,000 2,000
20 180 900 1,800
22 164 818 1,636
24 150 750 1,500
26 138 692 1,385
28 129 643 1,286
30 120 600 1,200
32 113 563 1,125
34 106 529 1,059
36 100 500 1,000
38 95 474 947
40 90 450 900
42 86 429 857
44 82 409 818
46 78 391 783
48 75 375 750
50 72 360 720
52 69 346 692
54 67 333 667
56 64 321 643
58 62 310 621
60 60 300 600
62 58 290 581
64 56 281 563
Table7.GasFlowRates(CubicFeetperHour)
GAS FLOW RATES
TIME FORONE REVOLUTION
(SECONDS)
CUBIC FEET PERREVOLUTION OF GAS METER
1 5 10
66 55 273 545
68 53 265 529
70 51 257 514
72 50 250 500
74 49 243 486
76 47 237 474
78 46 231 462
80 45 225 450
82 44 220 439
84 43 214 429
86 42 209 419
88 41 205 409
90 40 200 400
92 39 196 391
94 38 191 383
96 38 188 375
98 37 184 367
100 36 180 360
102 35 176 353
104 35 173 346
106 34 170 340
108 33 167 333
110 33 164 327
112 32 161 321
114 32 158 316
116 31 155 310
118 31 153 305
120 30 150 300
31
LOCAL HEATING VALUES FOR NATURAL GAS
ALTITUDE ABOVE SEA LEVEL
BTU PER CUBIC FOOT
650 700 750 800 850 900 950 1,000 1,050
2,000FT LOW LOW LOW LOW LOW LOW HIGH HIGH HIGH
3,000FT LOW LOW LOW LOW LOW LOW HIGH HIGH HIGH
4,000FT LOW LOW LOW LOW LOW HIGH HIGH HIGH HIGH
5,000FT LOW LOW LOW LOW LOW HIGH HIGH HIGH HIGH
6,000FT LOW LOW LOW LOW HIGH HIGH HIGH HIGH HIGH
7,000FT LOW LOW LOW LOW HIGH HIGH HIGH HIGH HIGH
8,000FT LOW LOW LOW HIGH HIGH HIGH HIGH HIGH HIGH
9,000FT LOW LOW LOW HIGH HIGH HIGH HIGH HIGH HIGH
10,000FT LOW LOW HIGH HIGH HIGH HIGH HIGH HIGH HIGH
Table10.NaturalGasHeatingValues
Table11.OrificesforNaturalGasHighHeatingValue
HIGH HEATING VALUE &MANIFOLDPRESSURE=3.5in.W.C.
ALTITUDE ABOVESEA LEVEL
INPUT (BTU)
45,000 72,000
0to1,999FT 49 47
2,000to2,999FT 50 48
3,000to3,999FT 50 48
4,000to4,999FT 51 48
5,000to5,999FT 51 49
6,000to6,999FT 51 49
7,000to7,999FT 52 50
8,000to8,999FT 52 50
9,000to9,999FT 52 50
LOW HEATING VALUE &MANIFOLDPRESSURE=3.5in.W.C.
ALTITUDE ABOVE SEA LEVEL
INPUT (BTU)
45,000 72,000
0to1,999FT 49 47
2,000to2,999FT 49 47
3,000to3,999FT 49 47
4,000to4,999FT 50 47
5,000to5,999FT 50 47
6,000to6,999FT 50 48
7,000to7,999FT 51 48
8,000to8,999FT 51 49
9,000to9,999FT 51 49
Table12.OrificesforNaturalGasLow Heating Value
Table9.OrificesforPropaneGas
ORIFICES FOR PROPANE GASMANIFOLDPRESSURE=10in.W.C.
ALTITUDE ABOVE SEA LEVEL
INPUT (BTU)
45,000 72,000
0to1,999FT 57 56
2,000to2,999FT 57 56
3,000to3,999FT 57 56
4,000to4,999FT 57 56
5,000to5,999FT 58 56
6,000to6,999FT 59 57
7,000to7,999FT 59 57
8,000to8,999FT 60 57
9,000to9,999FT 61 57
32
VENTING INFORMATION
Table 13. Vent Termination Clearances
Clearance Location
CANADIAN INSTALLATIONS a US INSTALLATIONS b
DirectVent(2-pipe)&ConventionalVent(1-pipe)Furnaces
Direct Vent(2-pipe)Furnaces
ConventionalVent(1-pipe)Furnaces
A Clearanceabovegrade,veranda,porch,deck,balcony,ormaximumexpectedsnowlevel. 12inches(30cm) 12inches(30cm) 12inches(30cm)
B Clearancetowindowordoorthatmaybeopened.
6inches(15cm)forappliances<10,000Btuh(3kW)
6inches(15cm)forappliances<10,000Btuh(3kW)
4ft.(1.2m)belowortosideofopening;1ft.(300mm)above
opening
12inches(30cm)forappliances10,000Btuh-100,000Btuh(30kW)
9inches(23cm)forappliances10,000Btuh-50,000Btuh(30kW)
36inches(91cm)forappliances>100,000Btuh(30Kw)
12inches(30cm)forappliances>50,000Btuh(30Kw)
C Clearancetopermanentlyclosedwindow12inches(30cm)suggestedorasneededtoavoid
condensationonglass.12inches(30cm)suggestedorasneededtoavoidcondensationonglass.
DVerticalclearancetoventilatedsoffitlocatedabovetheterminalwithinahorizontaldistanceof2feet(61cm)fromthecenterlineoftheterminal.
ClearancemustbegreaterthanthedepthofthesoffitunlessitcomplieswithFigure20
(page33)
ClearancemustbegreaterthanthedepthofthesoffitunlessitcomplieswithFigure20(page33)
E Clearancetounventilatedsoffit.ClearancemustbegreaterthanthedepthofthesoffitunlessitcomplieswithFigure20(page33)
ClearancemustbegreaterthanthedepthofthesoffitunlessitcomplieswithFigure20(page33)
F Clearancetooutsidecorner.AllClearancesinthisFigureapply
onbothwallsAllClearancesinthisFigureapplyonbothwalls
G Clearancetoinsidecorner.AllClearancesinthisFigureapply
onbothwallsAllClearancesinthisFigureapplyonbothwalls
H Clearancetoeachsideofcenterlineextendedabovemeter/regulatorassembly.
3feet(91cm)withinaheight15feetabovethemeter/regulatorassembly
3feet(91cm)withinaheightof15feet
I Clearancetoserviceregulatorventoutlet. 3feet(91cm) 3feet(91cm)inanydirection
JClearancetonon-mechanicalairsupplyinlettobuildingorthecombustionairinlettoanyotherappliance.
6inches(15cm)forappliances<10,000Btuh(3kW)
6inches(15cm)forappliances<10,000Btuh(3kW)
4ft.(1.2m)belowortosideofopening;1ft.(300mm)above
opening
12inches(30cm)forappliances10,000Btuh-100,000Btuh(30kW)
9inches(23cm)forappliances10,000Btuh-50,000Btuh(30kW)
36inches(91cm)forappliances>100,000Btuh(30Kw)
12inches(30cm)forappliances>50,000Btuh(30Kw)
K Clearancetomechanicalairsupplyinlet. 6feet(1.83m)3feet(91cm)aboveifwithin
10feet(3m)horizontally3ft.(91cm)aboveifwithin10feet(3m)horizontally
L Clearanceabovepavedsidewalkordrivewaylocatedonpublicproperty. 7feet(2.13m)c 7feet(2.13m)c 7ft.(2.13m)
M Clearanceunderopenveranda,porch,deck,orbalcony. 12inches(30cm)d 12inches(30cm)d 12inches(30cm)d
NOTES:
a=InaccordancewiththecurrentCSAB149.1NaturalGasandPropaneInstallationGuideCode
b=InaccordancewiththecurrentANSIZ223.1/NFPA54NaturalFuelGasCode
c=Aventshallnotterminatedirectlyaboveasidewalkorpaveddrivewaythatislocatedbetweentwosinglefamilydwellingsandservesbothdwellings.
d=Permittedonlyifveranda,porch,deck,orbalconyisfullyopenonaminimumoftwosidesbeneaththefloor.
VENT TERMINAL AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED
33
Figure20.Horizontal&VerticalVenting
VERTICAL VENTING HORIZONTAL VENTING
FL
UE
PIP
E
Straps or Other SuitableSupports at minimum of 5 ft. Intervals
Upward Pitch - 1/4” per foot(Flue Pipe)
First support placedas close to furnace
connection as possible
WallNormal
Snow Level
CO
MB
US
TIO
N A
IR
Seal/CaulkAround Pipes
at Building
90° Elbow
7”12” Min.
90° Elbow
90° Elbow
Support System onVertical Rise
FL
UE
PIP
E
CO
MB
US
TIO
N A
IRSee Table 2 for
PVC Pipe Lengths (Field Supplied)
See Table 2 forPVC Pipe Lengths (Field Supplied)
Depth
Clea
ranc
e =
dept
h of
so�
t
Outlet
Outlet
NOTE: Only outlet vents are shown.For placement with combustion airinlet see Figure 1.
CLEARANCES FROM SOFFIT
Must beoutsideof line.
34
35
INSTALLATION / PERFORMANCE CHECK LIST
INSTALLER NAME:
CITY: STATE:
INSTALLATION ADDRESS:
CITY: STATE:
UNITMODEL#
UNITSERIAL#
MinimumclearancesperTable1(page5)?
YES NO
Hastheowner’sinformationbeenreviewedwiththehome-owner?
YES NO
Has the literaturepackagebeenleftnearthefurnace?
YES NO
ATTENTIONINSTALLERS:Itisyourresponsibilitytoknowthisproductbetterthanyourcustomer.This includesbeingable to install theproduct according to strictsafetyguidelinesand instructingthecustomeronhowtooperateandmaintaintheequipmentforthelifeoftheproduct.Safetyshouldalwaysbethedecidingfactorwheninstallingthisproductandusingcommon sense plays an important role as well. Pay attention toallsafetywarningsandanyotherspecialnoteshighlightedinthemanual.Improperinstallationofthefurnaceorfailuretofollowsafetywarningscouldresultinseriousinjury,death,orpropertydamage.
Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproperinstallationofthisappliance.Somelocalcodesrequirelicensedinstallation/servicepersonnelforthistypeofequipment.Pleasereadallinstructionscarefullybeforestartingtheinstallation.Returntheseinstructionstothecustomer’spackageforfuturereference.
PROPOSITION 65 WARNING: This productcontains chemicals known to the state ofCaliforniatocausecancer,birthdefectsorotherreproductiveharm.
WARNING:
ELECTRICAL SYSTEM:
Electricalconnectionstight? YES NO
Linevoltagepolaritycorrect? YES NO
SupplyVoltage:________________________________ VOLTS
Hasthethermostatbeencalibrated? YES NO
Isthethermostatlevel? YES NO
Istheheatanticipatorsettingcorrect? YES NO
GAS SYSTEM:
GasType:(circleone)Natural
GasPropane
Gaspipeconnectionsleaktested? YES NO
GasLinePressure:____________________________ (in-W.C.)
InstallationAltitude: ______________________________ (FT.)
DerationPercentage:______________________________ (%)
FurnaceInput:_________________________________ (Btuh)
SupplyAirTemperature:__________________________ (°F)
ReturnAirTemperature:__________________________ (°F)
TemperatureRise:_______________________________ (°F)
COMBUSTION AIR & VENTING SYSTEM:
Isthereadequatefreshairsupplyforcombustionandventilation?
YES NO
Ventfreefromrestrictions? YES NO
Filter(s)securedinplace? YES NO
Filter(s)clean? YES NO
Flueconnectionstight? YES NO
Isthereproperdraft? YES NO
709438B(Replaces709438A)Specifications&illustrationssubjecttochangewithoutnoticeorincurringobligations(03/14).