212
Ireland Innovens Pro EN Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A

Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Ireland

Innovens Pro EN

Wall-hung gas condensing boilers

MCA 45 - 65 - 90 - 115

Installation andService Manual

300024755-001-A

Page 2: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

EG declaration of conformity

The device complies with the standard type described in the EGdeclaration of conformity. It was manufactured and commissioned inaccordance with European directives.

The original of the declaration of compliance is available from themanufacturer.

R000040-A

Page 3: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Contents

1 Introduction ................................................................................................61.1 Used symbols .......................................................6

1.2 Abbreviations ........................................................6

1.3 General ..................................................................71.3.1 Manufacturer's liability .............................................71.3.2 Installer's liability .....................................................71.3.3 User's liability ..........................................................7

1.4 Homologations ......................................................81.4.1 Certifications ...........................................................81.4.2 Equipment categories .............................................81.4.3 Additional Directives ................................................81.4.4 Factory test .............................................................9

2 Safety instructions and recommendations ............................................102.1 Safety instructions .............................................10

2.2 Recommendations ..............................................10

3 Technical description ..............................................................................123.1 General description ............................................12

3.2 Main parts ............................................................12

3.3 Operating principle .............................................123.3.1 Shunt pump ...........................................................123.3.2 System in cascade ................................................133.3.3 Calorifier connection .............................................133.3.4 Water flow rate ......................................................13

3.4 Technical characteristics ...................................133.4.1 Sensor characteristics ...........................................15

4 Installation ................................................................................................164.1 Regulations governing installation ...................16

4.2 Package list .........................................................164.2.1 Standard delivery ..................................................164.2.2 Accessories ...........................................................16

4.3 Choice of the location ........................................184.3.1 Data plate ..............................................................184.3.2 Location of the appliance ......................................184.3.3 Ventilation .............................................................19

06/09/2010 - 300024755-001-A 1

Page 4: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3.4 Main dimensions ...................................................20

4.4 Positioning the boiler .........................................21

4.5 Hydraulic connections .......................................214.5.1 Flushing the system ..............................................214.5.2 Connection of the heating circuit ...........................224.5.3 Connecting the expansion vessel .........................234.5.4 Connecting the condensate discharge pipe ..........24

4.6 Gas connection ...................................................24

4.7 Flue gas system connections ............................254.7.1 Classification .........................................................254.7.2 Lengths of the air/flue gas pipes ...........................26

4.8 Installing the outside sensor .............................274.8.1 Choice of the location ............................................274.8.2 Installing the outside sensor ..................................28

4.9 Electrical connections ........................................284.9.1 Control unit ............................................................284.9.2 Recommendations ................................................294.9.3 Fitting and connecting the control panel ...............304.9.4 Position of the PCBs .............................................304.9.5 Accessing the connection terminal blocks ............314.9.6 Connecting the pump ............................................324.9.7 Connecting a direct heating circuit ........................344.9.8 Connecting a direct heating circuit and a domestic hot

water tank ..............................................................354.9.9 Connecting two circuits and a domestic hot water tank

after the mixing tank ..............................................364.9.10 Hot water storage tank connection ........................384.9.11 Pool connection .....................................................444.9.12 Connecting a mixed tank .......................................464.9.13 Connecting the options .........................................474.9.14 Connection in cascade ..........................................49

4.10 Electrical diagram ...............................................51

4.11 Filling the system ...............................................524.11.1 Water treatment ....................................................524.11.2 Filling the siphon ...................................................534.11.3 Filling the system ..................................................53

5 Start-up - DIEMATIC iSystem ..................................................................545.1 Control panel .......................................................54

5.1.1 Description of the keys ..........................................545.1.2 Description of the display ......................................555.1.3 Access to the various browsing levels ..................575.1.4 Browsing in the menus ..........................................58

5.2 Check points before commissioning ................595.2.1 Preparing the boiler for commissioning .................595.2.2 Gas circuit .............................................................605.2.3 Hydraulic circuit .....................................................60

Contents

06/09/2010 - 300024755-001-A 2

Page 5: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.2.4 Electrical connections ...........................................60

5.3 Putting the appliance into operation ................60

5.4 Gas settings ........................................................625.4.1 Adapting to another gas type ................................625.4.2 Setting the air/gas ratio (Full load) ........................625.4.3 Setting the air/gas ratio (Part load) ......................64

5.5 Checks and adjustments aftercommissioning ...................................................655.5.1 Displaying the parameters in extended

mode .....................................................................655.5.2 Setting the parameters specific to the

installation .............................................................665.5.3 Naming the circuits and generators ......................685.5.4 Setting the heating curve ......................................695.5.5 Finalizing work ......................................................71

5.6 Reading out measured values ...........................72

5.7 Changing the settings ........................................735.7.1 Language selection ...............................................735.7.2 Calibrating the sensors .........................................735.7.3 "Professional" settings ..........................................755.7.4 Configuring the network ........................................815.7.5 Return to the factory settings ................................87

6 Start-up - IniControl .................................................................................886.1 Control panel .......................................................88

6.1.1 Description of the keys ..........................................886.1.2 Description of the display ......................................89

6.2 Check points before commissioning ................906.2.1 Preparing the boiler for commissioning .................906.2.2 Gas circuit .............................................................916.2.3 Hydraulic circuit .....................................................916.2.4 Electrical connections ...........................................91

6.3 Putting the appliance into operation ................92

6.4 Gas settings ........................................................936.4.1 Adapting to another gas type ................................936.4.2 Setting the air/gas ratio (Full load) ........................936.4.3 Setting the air/gas ratio (Part load) ......................94

6.5 Checks and adjustments aftercommissioning ...................................................956.5.1 Setting the heating curve ......................................956.5.2 Finalizing work ......................................................96

6.6 Reading out measured values ...........................976.6.1 Reading out measured values ..............................976.6.2 Readout from the hour counter and percentage of

successful starts ....................................................99

06/09/2010 - 300024755-001-A 3

Page 6: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6.6.3 Status and sub-status ...........................................99

6.7 Changing the settings ......................................1006.7.1 Description of the parameters .............................1006.7.2 Modification of the installer-level parameters ......1036.7.3 Setting the maximum heat input for central heating

operation .............................................................1046.7.4 Return to the factory settings "Reset Param" ......1056.7.5 Carrying out an auto-detect .................................105

7 Switching off the appliance ...................................................................1067.1 Installation shutdown .......................................106

7.2 Frost protection ................................................106

8 Checking and maintenance ...................................................................1078.1 General instructions .........................................107

8.2 Chimney sweep instructions ...........................1078.2.1 Control panel DIEMATIC iSystem .......................1078.2.2 Control panel IniControl ......................................108

8.3 Customising maintenance ...............................1088.3.1 Maintenance message ........................................1098.3.2 Installer's contact details .....................................110

8.4 Standard inspection and maintenanceoperations .........................................................1108.4.1 Checking the hydraulic pressure .........................1108.4.2 Checking the ionisation current ...........................1118.4.3 Checking the tightness of the combusted gases

evacuation and air inlet connections ...................1118.4.4 Checking combustion ..........................................1118.4.5 Checking the automatic air vent ..........................1128.4.6 Checking the siphon ............................................1138.4.7 Checking the burner and cleaning the heat

exchanger ...........................................................114

8.5 Specific maintenance operations ....................1158.5.1 Inspection of the ignition electrode ......................1158.5.2 Replacing the non-return valve ...........................1168.5.3 Assembling the boiler ..........................................117

9 Troubleshooting .....................................................................................1189.1 Anti-hunting ......................................................118

9.2 Messages (Code type Bxx or Mxx) ..................118

9.3 Message history ................................................1219.3.1 Control panel DIEMATIC iSystem .......................1219.3.2 Control panel IniControl ......................................122

Contents

06/09/2010 - 300024755-001-A 4

Page 7: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

9.4 Faults (Code type Lxx or Dxx) .........................1239.4.1 Control panel DIEMATIC iSystem .......................1249.4.2 Control panel IniControl ......................................1249.4.3 List of errors ........................................................1249.4.4 Deletion of sensors from the memory in the

PCB .....................................................................1329.4.5 Deleting the IOBL 3WV modules from the memory in

the PCB ..............................................................133

9.5 Failure history ...................................................1339.5.1 Control panel DIEMATIC iSystem .......................1339.5.2 Control panel IniControl ......................................134

9.6 Parameter and input/output check (modetests) ..................................................................1359.6.1 Control panel DIEMATIC iSystem .......................1359.6.2 Control panel IniControl ......................................1379.6.3 Control system sequence ....................................137

10 Spare parts ..............................................................................................13910.1 General ..............................................................139

10.2 Spare parts ........................................................13910.2.1 Casing .................................................................14010.2.2 Heat exchanger and burner - MCA 45 ................14110.2.3 Heat exchanger and burner - MCA 65 ................14210.2.4 Heat exchanger and burner - MCA 90/115 .........14310.2.5 Fan - MCA 45/65 .................................................14410.2.6 Fan - MCA 90 ......................................................14510.2.7 Fan - MCA 115 ....................................................14610.2.8 Control panel .......................................................14710.2.9 Spare parts list ....................................................148

06/09/2010 - 300024755-001-A 5

Page 8: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

1 Introduction

1.1 Used symbols

In these instructions, various danger levels are employed to draw theuser's attention to particular information. In so doing, we wish tosafeguard the user's safety, obviate hazards and guarantee correctoperation of the appliance.

DANGER

Risk of a dangerous situation causing serious physicalinjury.

WARNING

Risk of a dangerous situation causing slight physicalinjury.

CAUTION

Risk of material damage.

Signals important information.

¼ Signals a referral to other instructions or other pages in theinstructions.

1.2 Abbreviations

4 3CE: Collective conduit for sealed boiler4 DHW: Domestic hot water4 Interscenario switch: Home automation switch that can be used

to centralise and control several scenarios4 IOBL: In One By Legrand - Carrier current home automation bus4 PPS: Polypropylene hardly inflammable4 PCU: Primary Control Unit - PCB for managing burner operation4 PSU: Parameter Storage Unit - Parameter storage for PCBs

PCU and SU4 SCU: Secondary Control Unit - control panel PCB4 SU: Safety Unit - Safety PCB

1. Introduction MCA 45 - 65 - 90 - 115

6 06/09/2010 - 300024755-001-A

Page 9: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

1.3 General

1.3.1. Manufacturer's liability

Our products are manufactured in compliance with the requirementsof the various european applicable Directives. They are therefore

delivered with [ marking and all relevant documentation.

In the interest of customers, we are continuously endeavouring tomake improvements in product quality. All the specifications stated inthis document are therefore subject to change without notice.

Our liability as the manufacturer may not be invoked in the followingcases:

4 Failure to abide by the instructions on using the appliance.4 Faulty or insufficient maintenance of the appliance.4 Failure to abide by the instructions on installing the appliance.

1.3.2. Installer's liability

The installer is responsible for the installation and inital start up of theappliance. The installer must respect the following instructions:

4 Read and follow the instructions given in the manuals providedwith the appliance.

4 Carry out installation in compliance with the prevailing legislationand standards.

4 Perform the initial start up and carry out any checks necessary.4 Explain the installation to the user.4 If a maintenance is necessary, warn the user of the obligation to

check the appliance and maintain it in good working order.4 Give all the instruction manuals to the user.

1.3.3. User's liability

To guarantee optimum operation of the appliance, the user mustrespect the following instructions:

4 Read and abide by the instructions given in the user manual.4 Call on qualified professionals to carry out installation and initial

start up.4 Get your fitter to explain your installation to you.4 Have the required checks and services done.4 Keep the instruction manuals in good condition close to the

appliance.

MCA 45 - 65 - 90 - 115 1. Introduction

06/09/2010 - 300024755-001-A 7

Page 10: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

This appliance is not intended to be used by persons (includingchildren) whose physcial, sensory or mental capacity is impaired orpersons with no experience or knowledge, unless they have thebenefit, through the intermediary of a person responsible for theirsafety, of supervision or prior instructions regarding use of theappliance. Care should be taken to ensure that children do not playwith the appliance.

1.4 Homologations

1.4.1. Certifications

CE identification no PIN 0063CL3333NOx classification 5 (EN 297 pr A3, EN 656)Type of connection Chimney: B23, B33

Flue gas outlet: C13, C33, C43, C53, C63, C83, C93

1.4.2. Equipment categories

Gas category Gas type Connection pressure (mbar)II2H3P Natural gas H (G20) 20

Propane (G31) 37

The boiler is preset in the factory to operate on natural gas H (G20).

For operation on another group of gases:

4 With DIEMATIC iSystem: ¼ "Adapting to another gas type",page 62.

4 With IniControl: ¼ "Adapting to another gas type", page93.

1.4.3. Additional Directives

Apart from the legal provisions and Directives, the additionalDirectives described in these instructions must also be observed.

For all provisions and Directives referred to in these instructions, it isagreed that all addenda or subsequent provisions will apply at thetime of installation.

WARNING

Installation of the appliance must be done by a qualifiedengineer in accordance with prevailing local and nationalregulations.

1. Introduction MCA 45 - 65 - 90 - 115

8 06/09/2010 - 300024755-001-A

Page 11: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

1.4.4. Factory test

Before leaving the factory, each boiler is set for optimum performanceand tested to check the following items:

4 Electrical safety4 Adjustment (CO2)4 Water tightness4 Gas tightness4 Parameter settings

MCA 45 - 65 - 90 - 115 1. Introduction

06/09/2010 - 300024755-001-A 9

Page 12: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

2 Safety instructions andrecommendations

2.1 Safety instructions

DANGER

If you smell gas:

1. Do not use a naked flame, do not smoke, do notoperate electrical contacts or switches ( doorbell,light, motor, lift, etc..).

2. Isolate the gas supply.3. Open the windows.4. Trace possible leaks and seal them immediately.5. If the gas leak is before the gas meter, contact the

gas supplier.

DANGER

If you smell flue gases:

1. Switch the appliance off.2. Open the windows.3. Trace possible leaks and seal them immediately.

2.2 Recommendations

WARNING

4 Installation and maintenance of the boiler must becarried out by a qualified professional in compliancewith prevailing local and national regulations.

4 When working on the boiler, always disconnect theboiler from the mains and close the main gas inletvalve.

4 After maintenance or repair work, check allinstallations to ensure that there are no leaks.

CAUTION

The boiler must be installed in a frost-free environment.

Keep this document close to the place where the boiler isinstalled.

Casing components

2. Safety instructions and recommendations MCA 45 - 65 - 90 - 115

10 06/09/2010 - 300024755-001-A

Page 13: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Only remove the casing for maintenance and repair operations. Putthe casing back in place after maintenance and repair operations.Instructions stickers

The instructions and warnings affixed to the appliance must never beremoved or covered and must remain legible during the entire lifespanof the boiler. Immediately replace damaged or illegible instructionsand warning stickers.Modifications

Modifications may only be made to the boiler after the writtenpermission of De Dietrich Thermique to do so.

MCA 45 - 65 - 90 - 115 2. Safety instructions and recommendations

06/09/2010 - 300024755-001-A 11

Page 14: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3 Technical description

3.1 General description

Wall-hung gas condensing boilers

4 High efficiency heating (Production of domestic hot water can beensured by a separate hot water calorifier).

4 Low pollutant emissions.4 DIEMATIC iSystem or IniControl electronic control panel.4 Flue gas evacuation by a forced flue, chimney or bi-flow type

connection.4 Very suitable for cascade systems with several boilers.

3.2 Main parts

1 Flue gas outlet / Air intake2 Casing/air box3 Heat exchanger (Central heating)4 Outlet for measuring combustion gases5 Ignition/ionization electrode6 Mixer pipe7 Combined venturi and gas valve unit8 Áir intake silencer9 Instrument box10 Siphon11 Box for the control PCBs12 Fan13 Water flow pipe

3.3 Operating principle

3.3.1. Shunt pump

The boiler is supplied without a pump. When choosing a pump, takeaccount of the boiler resistance and system resistance.¼ See chapter: "Technical characteristics", page 13.

T002036-B

8

7

4

55

6

2

3

9

11

10

12

13

1

3. Technical description MCA 45 - 65 - 90 - 115

12 06/09/2010 - 300024755-001-A

Page 15: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

If possible, install the pump directly under the boiler on the returnconnection.¼ See chapter: "Connection of the heating circuit", page 22.

CAUTION

The pump may have a maximum input of 200 W. Use anauxiliary relay for a pump with a larger input.

3.3.2. System in cascade

The boiler is ideally suited for a cascade system. There are a numberof standard solutions available. For example:

4 Cascade sets (quick assembly) for the installation of 2 to 7 boilersnext to each other or 3 to 10 boilers mounted back to back on afree-standing frame. When the boilers are mounted next to eachother, they can be mounted either on the wall or on a free-standingframe.

Please contact us for further information.

3.3.3. Calorifier connection

A calorifier can be connected to the boiler. Our product range includesvarious calorifiers.

Please contact us for further information.

The calorifier can be connected to the boiler in two ways:

4 Using a three-way valve.4 Using a calorifier pump.

3.3.4. Water flow rate

The boiler's modulating control system limits the maximum differencein temperature between the heating flow and return and the maximumspeed at which the flow temperature increases. For this reason theboiler is, so to speak, insensitive to a flow which is too low.In all cases, maintain a minimum water flow of 0,4 m3/h.

3.4 Technical characteristics

MCA 45 - 65 - 90 - 115 3. Technical description

06/09/2010 - 300024755-001-A 13

Page 16: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Boiler type MCA 45 MCA 65 MCA 90 MCA 115GeneralFlow rate setting Adjustable Modulating, Start/Stop, 0 - 10 VNominal output (Pn)Heating System (80/60 °C)

minimum-maximum kW 8,0 - 40,0 12,0 - 61,0 14,1 - 84,2 16,6 - 107,0Factory setting kW 40,0 61,0 84,2 107,0

Nominal output (Pn)Heating System (50/30 °C)

minimum-maximum kW 8,9 - 43,0 13,3 - 65,0 15,8 - 89,5 18,4 - 114,0Factory setting kW 43,0 65,0 89,5 114,0

Nominal input (Qn)Heating System (Hi)

minimum-maximum kW 8,2 - 41,2 12,2 - 62,0 14,6 - 86,0 17,2 - 110,2Factory setting kW 41,2 62,0 86,0 110,2

Nominal input(Qn)Heating System (Hs)

minimum-maximum kW 9,1 - 45,7 13,6 - 68,8 16,2 - 95,5 19,1 - 122,4Factory setting kW 45,7 68,8 95,5 122,4

Heating efficiency under full load (Hi)(80/60 °C) - % 97,2 98,3 97,9 96,6

Heating efficiency under full load (Hi)(50/30 °C) - % 102,9 104,6 104,1 102,5

Heating efficiency under partial load (Hi)(Return temperature 60°C) - % 97,5 98,3 96,6 96,5

Heating efficiency under partial load (EN92/42)(Return temperature 30°C) - % 107,7 108,9 108,1 107,1

Data on the gases and combustion gasesGas consumption G20 (Natural gas H) minimum-maximum m3/h 0,9 - 4,4 1,3 - 6,6 1,5 - 9,1 1,8 - 11,7

Gas consumption G31 (Propane) minimum-maximum m3/h 0,3 - 1,7 0,5 - 2,5 0,6 - 3,5 0,6 - 4,7

NOx-Emission per year or (EN 483) mg/kWh 37 32 45 46Mass flue gas flow rate minimum-maximum Kg/h 14 - 69 21 - 104 28 - 138 36 - 178Flue gas temperature minimum-maximum °C 30 - 67 30 - 68 30 - 68 30 - 72Maximum counter pressure Pa 150 100 160 220Characteristics of the heating circuitWater content l 5,5 6,5 7,5 7,5Water operating pressure minimum kPa (bar) 80 (0,8) 80 (0,8) 80 (0,8) 80 (0,8)Water operating pressure (PMS) maximum kPa (bar) 400 (4,0) 400 (4,0) 400 (4,0) 400 (4,0)Water temperature maximum °C 110 110 110 110Operating temperature maximum °C 90 90 90 90Water resistance (∆T = 20K) mbar 90 130 140 250Electrical characteristicsPower supply voltage V/Hz 230/50 230/50 230/50 230/50Power consumption - Full load maximum W 68 88 125 199Power consumption - Part load maximum W 18 23 20 45Power consumption - Standby maximum W 5 6 4 7Electrical protection index IP X4D X4D X4D X4DOther characteristicsWeight (empty) Total kg 53 60 67 68

Mounting(1) kg 49 56 65 65Acoustic level at 1 meter dBA 45 45 52 51(1) Front panel removed

3. Technical description MCA 45 - 65 - 90 - 115

14 06/09/2010 - 300024755-001-A

Page 17: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3.4.1. Sensor characteristics

Outside sensor Outlet sensor circuit B+CDomestic hot water sensor

Boiler sensorReturn sensor

-20 °C 2392 ¨ 0 °C 32014 ¨ -20 °C 98932 ¨-16 °C 2088 ¨ 10 °C 19691 ¨ -10 °C 58879 ¨-12 °C 1811 ¨ 20 °C 12474 ¨ 0 °C 36129 ¨-8 °C 1562 ¨ 25 °C 10000 ¨ 10 °C 22804 ¨-4 °C 1342 ¨ 30 °C 8080 ¨ 20 °C 14773 ¨0 °C 1149 ¨ 40 °C 5372 ¨ 25 °C 12000 ¨4 °C 984 ¨ 50 °C 3661 ¨ 30 °C 9804 ¨8 °C 842 ¨ 60 °C 2535 ¨ 40 °C 6652 ¨12 °C 720 ¨ 70 °C 1794 ¨ 50 °C 4607 ¨16 °C 616 ¨ 80 °C 1290 ¨ 60 °C 3252 ¨20 °C 528 ¨ 90 °C 941 ¨ 70 °C 2337 ¨24 °C 454 ¨ 80 °C 1707 ¨

90 °C 1266 ¨ 100 °C 952 ¨ 110 °C 726 ¨

MCA 45 - 65 - 90 - 115 3. Technical description

06/09/2010 - 300024755-001-A 15

Page 18: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4 Installation

4.1 Regulations governing installation

WARNING

Installation of the appliance must be done by a qualifiedengineer in accordance with prevailing local and nationalregulations.

4.2 Package list

4.2.1. Standard delivery

The boiler is composed of 2 packages:

4 1 boiler package including:- The boiler, fitted with a connection cable- Mounting rail and mounting accessories for wall mounting- Mounting template- Installation and Service Manual- User Guide

4 1 control panel package including:- The DIEMATIC iSystem or IniControl control panel- module assembly instructions

4.2.2. Accessories

Various options are available depending on the configuration of theinstallation:

Boiler optionsDescription packageHydraulic connection kit - MCA 45 HC137Hydraulic connection kit - MCA 65 / 90 / 115 HC139Right gas valve 3/4" HC1583-speed heating pump - MCA 45 HC141Electronic heating pump - MCA 45 HC1423-speed heating pump - MCA 65 HC1433-speed heating pump - MCA 90 HC145Primary pump - MCA 45 / 65 / 90 HC1473-way valve with motor 1" HC15Low loss header HW PLUS 70 HC28Low loss header HW 200 HC29

4. Installation MCA 45 - 65 - 90 - 115

16 06/09/2010 - 300024755-001-A

Page 19: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Boiler optionsDescription packageCondensates neutralisation station HC33Bracket for neutralisation station HC 33 HC342 kg refill of granulats to neutralisation station HC 33 HC35Condensates neutralisation station (Boilers up to 120 kW) DU13Condensates neutralisation station (Boilers from 120 to 350kW)

DU14

Condensates neutralisation station (Boilers above 350 kW) DU15

Control system optionsDescription packageOptional PCB for 3-way valve Diematic iSystem AD249System sensor AD250Outside radio-controlled temperature sensor Diematic iSystem AD251Boiler radio module AD252Radio remote control Diematic iSystem AD253Interactive remote control Diematic iSystem AD254BUS connection cable (length 12 m) AD134voice remote monitoring module AD152Outlet sensor after 3-way valve AD199A simplified remote control with room sensor FM52

Domestic hot water tank optionsDescription packageHeating / DHW inversion valve HC 134Heating DHW reversal valve MCA 45 / 65 HC 135Boiler/DHW tank connection kit BL / BP / BSC / DT EA 121DHW sensor AD 212

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 17

Page 20: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3 Choice of the location

4.3.1. Data plate

The data plate located on top of the boiler provides importantinformation on the appliance: serial number, model, gas category, etc.

4.3.2. Location of the appliance

4 Before mounting the boiler, decide on the ideal position formounting, bearing the Directives and the dimensions of theappliance in mind.

4 When choosing the position for mounting the boiler, bear in mindthe authorised position of the combustion gas discharge outletsand the air intake opening.

4 To ensure adequate accessibility to the appliance and facilitatemaintenance, leave enough space around the boiler.

WARNING

4 Fix the appliance to a solid wall capable of bearingthe weight of the appliance when full of water and fullyequipped.

4 It is forbidden to store inflammable products andmaterials in the boiler room or close to the boiler,even temporarily.

CAUTION

4 The boiler must be installed in a frost-freeenvironment.

4 A connection to the mains drainage system for thedischarge of condensate must be available close tothe boiler.

T001982-A

T002599-B

500

min

.1000

500

min. 400

350

min. 250

750

4. Installation MCA 45 - 65 - 90 - 115

18 06/09/2010 - 300024755-001-A

Page 21: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3.3. Ventilation

(1) Distance between the front of the appliance and theinternal wall of the cupboard.

(2) Distance to allow on either side of the appliance.

If the boiler is installed in a closed box, respect the minimumdimensions given in the diagram opposite. Also allow openings toobviate the following hazards:

4 Accumulation of gas4 Heating of the box

Minimum cross section of the openings: S1 + S2 = 150 cm2

T002600-B

1000

min. (1)

530

15 (2)

min

.1500

min. 400

min. 250

750

350

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 19

Page 22: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3.4. Main dimensions

i Connection of the combustion gas exhaust pipe ;Ø 80 mm (≤ 45 kW) / Ø 100 mm (≥ 65 kW)

h Connection of the air intake pipe ;Ø 125 mm (≤ 45 kW) / Ø 150 mm (≥ 65 kW)

â Siphon connection bush

z Heating circuit return ; 1 ¼" Male threadGas /Gaz

Gas connection ; ¾" Male thread

{ Heating circuit flow ; 1 ¼" Male thread

T002614-C

191

500

750

500

100

50

50

130

191

365

4. Installation MCA 45 - 65 - 90 - 115

20 06/09/2010 - 300024755-001-A

Page 23: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.4 Positioning the boiler

The boiler is delivered with a mounting template.

A suspension clamp situated at the rear of the casing enables theboiler to be directly suspended on the mounting bracket.

1. Position the mounting template to the wall with adhesive tape.

CAUTION

4 Using a spirit level, check that the mounting axis isperfectly horizontal.

4 During mounting, cover up the connection points forthe air supply and the combustion gas exhaust, toprotect the boiler and its connections from dust. Onlyremove this protection at the time when theseconnections are made.

2. Drill 2 holes with a Ø of 10 mm.3. Insert the rawplugs with a Ø of 10 mm.4. Attach the mounting bracket to the wall with the provided bolts with

a Ø of 10 mm.5. Hang the boiler on the mounting bracket.

4.5 Hydraulic connections

4.5.1. Flushing the system

Installation must be carried out in accordance with the prevailingregulations, the codes of practice and the recommendations in theseinstructions.

T001540-A

2

1

5

4

3

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 21

Page 24: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Installing the boiler in new installations (installationsless than 6 months old)

4 Clean the installation with a universal cleaner to eliminate debrisfrom the appliance (copper, flaxen thread, flux).

4 Thoroughly flush the installation until the water runs clear andshows no impurities.

n Installing the boiler in existing installations

4 Remove sludge from the installation.4 Flush the installation.4 Clean the installation with a universal cleaner to eliminate debris

from the appliance (copper, flaxen thread, flux).4 Thoroughly flush the installation until the water runs clear and

shows no impurities.

4.5.2. Connection of the heating circuit

1. Remove the anti-dust plug located on the heating outletconnection { under the boiler.

2. Connect the heating water outlet pipe to the heating flowconnection.

3. Install a filling and drainage valve on the installation for filling anddraining the boiler.

T002856-C

4. Installation MCA 45 - 65 - 90 - 115

22 06/09/2010 - 300024755-001-A

Page 25: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4. Remove the anti-dust button located on the heating returnconnection z under the boiler.

5. Connect the heating water return pipe to the heating returnconnection.

6. Fit the pump in the return pipe.¼ For the electrical connection of the pump, see chapter:"Connecting the pump", page 32

To facilitate maintenance work, we recommend mountinga shut off valve on the heating flow and return pipes.

CAUTION

4 The heating pipe must be mounted in accordancewith prevailing provisions.

4 If installing shut off valves, position the filling/drainage valve and the expansion vessel betweenthe shut off valves and the boiler.

4.5.3. Connecting the expansion vessel

Install the expansion vessel on the heating return pipe z.

Refer to the table below to determine the opened expansion vesselrequired for the installation.

Conditions of validity of the table:

4 3-bar safety valve4 Average water temperature: 70 °C

Flow temperature: 80 °CReturn temperature: 60 °C

4 The filling pressure in the system is lower than or equal to the initialpressure in the opened expansion vessel

Initial pressure of theexpansion vessel

Volume of the opened expansion vessel depending on the volume of the installation (in litres)100 125 150 175 200 250 300 > 300

0.5 bar 4,8 6,0 7,2 8,4 9,6 12,0 14,4 Volume of the installation x 0,0481 bar 8,0 10,0 12,0 (1) 14,0 16,0 20,0 24,0 Volume of the installation x 0,0801.5 bar 13,3 16,6 20,0 23,3 26,6 33,3 39,9 Volume of the installation x 0,133(1) Factory configuration

T002857-B

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 23

Page 26: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.5.4. Connecting the condensate discharge pipe

1. Fit the condensate drain hose and the syphon of the boiler: theseare supplied separately.

2. Mount a standard drainage pipe, Ø 32 mm or more, leading to themains drainage system.

3. Insert into this the hose of the condensate drain â.4. Mount a trap or a siphon in the discharge pipe.

CAUTION

Do not make a fixed connection owing to maintenancework on the siphon.

4 Do not plug the condensate discharge pipe.4 Set the discharge pipe at a gradient of at least 30

mm per metre, maximum horizontal length 5 metres.4 Do not drain condensation water into a roof gutter at

any time.4 Connect the condensate discharge pipe in

accordance with prevailing standards.

4.6 Gas connection

WARNING

4 Close the main gas valve before starting work on thegas pipes.

4 Before mounting, check that the gas meter hassufficient capacity. To do this, you should keep inmind the consumption of all appliances.

4 If the gas meter has too low a capacity, inform theenergy supply company.

The diameters of the pipes must be defined in accordance with thestandards in force in your country.

1. Remove the anti-dust plug from the GAS/GAZ gas inlet pipe underthe boiler.

2. Connect the gas inlet pipe.3. Mount a gas isolation valve on this pipe, directly under the boiler.4. Connect the gas pipe to the gas shut off valve.

CAUTION

4 Ensure that there is no dust in the gas pipe.4 We recommend installing a gas filter on the gas pipe

to prevent clogging of the gas valve unit.4 Connect the gas pipe in accordance with prevailing

standards and regulations.

T002858-B

T002859-C

4. Installation MCA 45 - 65 - 90 - 115

24 06/09/2010 - 300024755-001-A

Page 27: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.7 Flue gas system connections

4.7.1. Classification

6 34 2

2

2

1

5

L1

L1

Lmax = L1+L2

Lmax =

L1+L2

Lmax

Lmax

Lmax

Lmax

max max

max 1m 1m 1m

Lmax

L2

L2Lmax

Lmax

C33C93B23 C93

C33

C33C13

C53

C003034-A

1 Configuration C13Air/flue gas connection by means of concentric pipes to ahorizontal terminal (so-called forced flue)

2 Configuration C33Air/flue gas connection by means of concentric pipes to avertical terminal (roof outlet)

3 Configuration C93Air/flue gas connection by concentric pipes in the boilerroom and single pipes in the chimney (combustive air incounter current in the chimney)

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 25

Page 28: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4 Configuration C93Air/flue gas connection by concentric pipes in the boilerroom and single "flex" in the chimney (combustive air incounter current in the chimney)

WARNING

4 Only factory components are authorised forconnecting the boiler and the terminal.

4 The clear section must comply with thestandard.

4 The chimney must be swept before theinstallation of the evacuation conduit.

5 Configuration C53Air and flue gas connection separated by means of a bi-flow adapter and single pipes (combustive air taken fromoutside)

6 Configuration B23Connection to a chimney using a connection kit(combustive air taken from the boiler room)

4.7.2. Lengths of the air/flue gas pipes

Type of air/flue gas connection Diameter Maximum lengthMCA 45 MCA 65 MCA 90 MCA 115

C13 Concentric pipes connected to a horizontal terminal Alu or PPS 80/125 mm 16 m - - -100/150 mm - 9 m 8 m 5,9 m

C33 Concentric pipes connected to a vertical terminal aluminium 80/125 mm 14,5 m - - -100/150 mm - 11,5 m 10 m 9,4 m

C93 Concentric pipes in the boiler roomSingle conduits in the chimney (combustive air incounter-current)

aluminium 80/125 mm80 mm

15 m - - -

80/125 mm100 mm

11,5 m - - -

110/150 mm110 mm

- 11 m 12,5 m 10 m

Concentric pipes in the boiler roomSingle flexible pipe in the chimney (combustive air incounter-current)

PPS 80/125 mm80 mm

12 m - - -

110/150 mm110 mm

- 16,5 m 13,5 m 9,4 m

C53 Bi-flow adapter and separate single air/flue gas ducts(combustive air taken from outside)

aluminium 80/125 mm2 x 80 mm

20,5 m - - -

100/150 mm2 x 100 mm

- 23 m 17,5 m 11 m(1)

5 m(2)

B23 Chimney (rigid or flexible duct in furnace flue,combustive air taken from the premises)

PPS 80 mm(3) 23,5 m - - -

110 mm(3) - 55 m 45 m 44 m

80 mm(4) 21 m - - -

110 mm(4) - 29,5 m 24 m 17,5 m(1) Air(2) Flue gases(3) Rigid duct(4) Flexible duct

4. Installation MCA 45 - 65 - 90 - 115

26 06/09/2010 - 300024755-001-A

Page 29: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

WARNING

Maximum length = lengths of the straight air/flue gas ducts+ equivalent lengths of other components

For the list of flue gas system accessories and the equivalent lengths,refer to the current price list.

4.8 Installing the outside sensor

4.8.1. Choice of the location

It is important to select a place that allows the sensor to measure theoutside conditions correctly and effectively.

Advised positions:

4 on one face of the area to be heated, on the north if possible4 half way up the wall in the room to be heated4 under the influence of meteorological variations4 protected from direct sunlight4 easy to access

A Recommended positionB Possible positionH Inhabited height controlled by the sensorZ Inhabited area controlled by the sensor

8800N001-C

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 27

Page 30: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Positions to be avoided:

4 masked by a building element (balcony, roof, etc.)4 close to a disruptive heat source (sun, chimney, ventilation grid,

etc.)

4.8.2. Installing the outside sensor

Mount the sensor using the screws and dowels provided.

A CB wood screws diameter 4 + dowels

4.9 Electrical connections

4.9.1. Control unit

The boiler is fully pre-wired. The mains supply is made via the cableC connected to the mains. All other external connections can be madeto the connection connectors (low voltage). The main characteristicsof the control unit are described in the table below.

Power supply voltage 230 V AC/50 HzRating of the main fuse F1(230 V AC) 6.3 ATFuse rating F2(230 V AC) 2 ATFan 230 V AC

CAUTION

Keep to the polarity shown on the terminals: phase (L),neutral (N) and earth *.

8800N002-C

8800N003-B

4. Installation MCA 45 - 65 - 90 - 115

28 06/09/2010 - 300024755-001-A

Page 31: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

A Routing of the 230 V cablesB Power supply cableC Cable of housing for control PCBsD 6,3 AT fuseE 2 AT fuse

CAUTION

The following components of the appliance are at avoltage of 230 V:4 Electrical connection of the heating pump (Central

heating).4 Electrical connection of the combined gas valve unit.4 Electrical connection of the fan.4 The majority of components in the control panel.4 Most parts of the housing for control PCBs.4 Ignition transformer.4 Connection of the power supply cable.

4.9.2. Recommendations

WARNING

4 Only qualified professionnals may carry out electricalconnections, always with the power off.

4 The boiler is entirely pre-wired. Do not modify theconnections inside the control panel.

4 Earth the appliance before making any electricalconnections.

Make the electrical connections of the appliance according to:

4 the instructions of the prevailing standards.4 the instructions on the circuit diagrams provided with the

appliance.4 the recommendations in the instructions.

CAUTION

4 Separate the sensor cables from the 230 V cables.4 Outside the boiler: Use 2 pipes or cable guides at

least 10 cm apart.

T002039-A

ED

B

A

X2

C

C

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 29

Page 32: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.9.3. Fitting and connecting the control panel

1. Unscrew the 2 screws under the front panel by a quarter turn.2. Remove the front panel.3. Fit and connect the control panel.¼ To fit and connect the control panel, see the brochuredelivered in the control panel package.

4.9.4. Position of the PCBs

T001999-A

SCU PCU

N

TS + CC

LN N L

AUX

N

TS + BB

LN L N

Alim

230 V - 50 Hz

L N N L

A

TdhwToutRLBLOT

On/off

1

2

3

2

S SYST

1 2

+ S ECS S EXTTA - S DEP C S DEP B

1 2 1 2 1 2 1 2 1

+

0-10V

- 4

S CAMB S AMBB S AMPA

3 2 1 2 1 2 1 2 1

PCU

SU

SCU

PSU

C002912-A

2

1

90º

4. Installation MCA 45 - 65 - 90 - 115

30 06/09/2010 - 300024755-001-A

Page 33: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

A Do not connect anything to the terminal block.

Z Optional PCB (Package AD249)

E Do not connect anything to the terminal block.

4.9.5. Accessing the connection terminal blocks

To access the connection terminal blocks, proceed as follows:

1. Unscrew the 2 screws under the front panel by a quarter turn.2. Remove the front panel.

3. Tilt the control box forwards by opening the holding clips locatedat the sides.

4. Open the tooling box by opening the clip fastener on the front side.

5. Lift the control panel cover.

T001514-A

2

1

90º

T001991-A

2

1 1

T002040-A

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 31

Page 34: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6. Unclip the PCB cover.

4.9.6. Connecting the pump

The pump must be connected to standard control PCB (PCU). To dothis, proceed as follows:

1. Connect the cable, that is delivered with the boiler, to the pump.

T002862-A

2

x3

1

T002047-B

X81

X81

4. Installation MCA 45 - 65 - 90 - 115

32 06/09/2010 - 300024755-001-A

Page 35: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

2. Remove the grommet from the opening in the middle of the baseof the boiler. Pass the pump connection cable through the base ofthe boiler and seal the opening again by tightening the bayonetfitting to the cable.

3. Connect the pump connection cable to the cable in the instrumentbox that is connected with connector X8.

T002048-A

1

2

3

T002050-C

X8

X81

X81

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 33

Page 36: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4. Connect the pump connection cable to the cable bundle byopening and closing the cable bundle bands.

4.9.7. Connecting a direct heating circuit

C002903-B

2

4

3

On/off

OT BL RL Tout Tdhw

1

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1

S DEP B

2 1

SCU PCU

5

A Do not connect anything to the terminal block.

Z Connect the outside temperature sensor.

E Heating connection pump.

T002049-B

4. Installation MCA 45 - 65 - 90 - 115

34 06/09/2010 - 300024755-001-A

Page 37: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

R Connect a safety thermostat if the heating circuit is forunderfloor heating.

4 Remove the bridge.4 Connect the wires from the safety thermostat to the

connector.

T Do not connect anything to the terminal block.

4.9.8. Connecting a direct heating circuit and adomestic hot water tank

C002904-B

6

4

5

7

8

9

2

3

On/off

OT BL RL Tout Tdhw

1

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1

S DEP B

2 1

SCU PCU

TS + C AUXC

A Do not connect anything to the terminal block.

Z Domestic load pump connection

E Connect the heating pump

R Connect a safety thermostat if the heating circuit is forunderfloor heating.

4 Remove the bridge.4 Connect the wires from the safety thermostat to the

connector.

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 35

Page 38: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

T Connect the DHW tank anode.

CAUTION

4 If the tank is fitted with a Titan ActiveSystem® impressed current anode,connect the anode to the inlet (+ on theanode, - on the tank).

4 If the tank is not fitted with an impressedcurrent anode, put the simulationconnector in place (delivered with the DHWsensor - package AD212).

Y Connect the outside temperature sensor.

U Connect the DHW sensor (Package AD212).

I Connect the domestic hot water looping pump(Optional).

O Do not connect anything to the terminal block.

DIEMATIC iSystem - Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters

in extended mode", page 65If a domestic hot water looping pumpis connected to MAUX on theterminal block:O.PUMP AUX(1)

"Installer" level#SYSTEM menu

DHW LOOP ¼ "Setting the parametersspecific to the installation", page66

If safety thermostat is connected toBL on the connection terminal block:IN.BL

"Installer" level#PRIMARY INSTAL.Pmenu

TOTAL STOP ¼ ""Professional" settings",page 75

If a DHW tank (type BS60) isconnected(2)

"Installer" level#SYSTEM menu

ON ¼ "Setting the parametersspecific to the installation", page66

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

IniControl - Settings to be made for this type of installationNo further adjustments are necessary

4.9.9. Connecting two circuits and a domestic hotwater tank after the mixing tank

This configuration is only possible with the DIEMATICiSystem control panel.

4. Installation MCA 45 - 65 - 90 - 115

36 06/09/2010 - 300024755-001-A

Page 39: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

C002905-B

7

8

11

10

6

5

1

2

4

9

3

12

On/off

OT BL RL Tout Tdhw

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1

S DEP B

2 1

TS + C AUXC

SCU PCU

A Do not connect anything to the terminal block.

Z Connect a safety thermostat if the heating circuit is forunderfloor heating.

4 Remove the bridge.4 Connect the wires from the safety thermostat to the

connector.

E Connecting an additional circuit to the AD249 option.

R Connect the heating pump (circuit A).

If underfloor heating is being used, put a safetythermostat in place after the heating pump. Thesafety thermostat will shut down the heatingpump in the event of overheating.

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 37

Page 40: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

T Connect the DHW tank anode.

CAUTION

4 If the tank is fitted with a Titan ActiveSystem® impressed current anode,connect the anode to the inlet (+ on theanode, - on the tank).

4 If the tank is not fitted with an impressedcurrent anode, put the simulationconnector in place (delivered with the DHWsensor - package AD212).

Y Connect the outside temperature sensor.

U Connect the heating pump (circuit B).

I Connect the 3-way valve (circuit B).

O Domestic load pump connection.

P Connect the DHW sensor (Package AD212).

a Connect the domestic hot water looping pump to theMAUX outlet on the AD249 option.

z Do not connect anything to the terminal block.

4.9.10. Hot water storage tank connection

This configuration is only possible with the DIEMATICiSystem control panel.

n QUADRO DU storage tank

In this installation example, the storage tank (type QUADRO DU)incorporates a domestic hot water zone. The boiler starts upsystematically to maintain the domestic hot water zone in the storagetank or to maintain the independent tank at temperature.

If the storage tank does not have a DHW zone, use anindependent domestic hot water tank.

4. Installation MCA 45 - 65 - 90 - 115

38 06/09/2010 - 300024755-001-A

Page 41: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

C002906-B

On/off

OT BL RL Tout Tdhw

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1

S DEP B

2 1

SCU PCU

6

3

2

4

9

8

5

7

1

10

M

X81

A Do not connect anything to the terminal block.

Z Connect the load pump from the buffer tank.

E Connect the sensor from the storage tank (PackageAD250).

R Buffer tank.

T Connect the DHW tank anode.

If the tank is not fitted with an impressed currentanode, put the simulation connector in place(delivered with the DHW sensor - packageAD212).

Y Connect the DHW sensor (Package AD212).

U Connect the heating pump (Circuit A).

I Solar sensor probe.

O Connect the solar station to the solar collectors.

P Do not connect anything to the terminal block.

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 39

Page 42: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

DIEMATIC iSystem - Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters in extended mode", page

65I.SYST(1) "Installer" level

#SYSTEM menuSTORAGE TANK ¼ "Setting the parameters specific to the installation",

page 66(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

The DHW part is maintained at the DHW set point by theboiler.The heating zone is maintained at the set temperaturecalculated according to the outside temperature. The zoneis reheated when the heating buffer temperature sensorE falls -6°C below the calculated set temperature.Reheating in the heating zone stops when the heatingbuffer temperature rises above the calculated settemperature.

4. Installation MCA 45 - 65 - 90 - 115

40 06/09/2010 - 300024755-001-A

Page 43: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n PS storage tank and DHW tank connected to the boiler

5

2

3

1

C002907-B

10

On/off

OT BL RL Tout Tdhw

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1

S DEP B

2 1

SCU PCU

4

7

8

11

126

9

X81

A Do not connect anything to the terminal block.

Z D.H.W. load pump

E Buffer tank load pump.

R Connect a domestic hot water tank if the storage tank Ois only used for heating

T Connect the DHW sensor (Package AD212).

Y Connect the DHW tank anode.

If the tank is not fitted with an impressed currentanode, put the simulation connector in place(delivered with the DHW sensor - packageAD212).

U Connect the heating pump (Circuit A).

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 41

Page 44: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

I Solar sensor probe.

O Buffer tank.

P Do not connect anything to the terminal block.

a Connect the solar station to the solar collectors.

z Solar sensor probe

DIEMATIC iSystem - Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters in extended mode", page

65I.SYST(1) "Installer" level

#SYSTEM menuSTORAGE TANK ¼ "Setting the parameters specific to the installation",

page 66(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

The DHW part is maintained at the DHW set point by theboiler.The heating zone is maintained at the set temperaturecalculated according to the outside temperature. The zoneis reheated when the heating buffer temperature sensor falls -6°C below the calculated set temperature. Reheatingin the heating zone stops when the heating buffertemperature rises above the calculated set temperature.

4. Installation MCA 45 - 65 - 90 - 115

42 06/09/2010 - 300024755-001-A

Page 45: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n PS storage tank and DHW tank connected to the storagetank

The boiler only starts up production of domestic hot water if thestorage tank is not hot enough to guarantee tank loading.

C002908-A

4

7

6

2

3

1

5

9

8

On/off

OT BL RL Tout Tdhw

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1

S DEP B

2 1

SCU PCU

A Do not connect anything to the terminal block.

Z Connect the heating pump (Circuit A).

E Buffer tank load pump

R Connect the DHW tank anode.

If the tank is not fitted with an impressed currentanode, put the simulation connector in place(delivered with the DHW sensor - packageAD212).

T Buffer tank.

Y Solar sensor probe.

U Connect the solar station to the solar collectors.

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 43

Page 46: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

I Domestic hot water boiler.Connect the DHW sensor.

O Do not connect anything to the terminal block.

DIEMATIC iSystem - Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters in extended mode", page

65I.SYST(1) "Installer" level

#SYSTEM menuST.TANK+DHW ¼ "Setting the parameters specific to the installation",

page 66(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

The DHW tank is loaded from the storage tank. If, duringDHW loading, the temperature of the storage tank fallsbelow the primary DHW set point (parameterPRIM.TEMP.DHW), the boiler maintains the latter attemperature to guarantee the loading of the DHW tankThe heating zone is maintained at the set temperaturecalculated according to the outside temperature. The zoneis reheated when the heating buffer temperature sensor falls -6°C below the calculated set temperature. Reheatingin the heating zone stops when the heating buffertemperature rises above the calculated set temperature.

4.9.11. Pool connection

This configuration is only possible with the DIEMATICiSystem control panel.

C002298-i

1

35

2

6

On/off

OT BL RL Tout Tdhw

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1

S DEP B

2 1

SCU PCU

4

A Connect the secondary swimming pool pump.

4. Installation MCA 45 - 65 - 90 - 115

44 06/09/2010 - 300024755-001-A

Page 47: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Z Connect the swimming pool sensor.

E Plate heat exchanger.

R Pool heating cut-off control

When the parameter I.TEL: is on 0/1 B, theswimming pool is no longer heated when thecontact is open (factory setting), only theantifreeze continues to be active.The contact direction can still be adjusted by theparameter CT.TEL.

T Connect the primary swimming pool pump.

Y Do not connect anything to the terminal block.

DIEMATIC iSystem - Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters in

extended mode", page 65CIRC. B: "Installer" level

#SYSTEM menuSWIM.P. ¼ "Setting the parameters

specific to the installation", page 66If I.TEL: is usedI.TEL:

"Installer" level#SYSTEM menu

0/1 B

MAX. CIRC. B "Installer" level#SECONDARY LIMITS menu

Set the value of MAX.CIRC.B tothe temperature corresponding tothe needs of the exchanger

¼ ""Professional" settings", page75

n Controlling the pool circuit

The control system can be used to manage a swimming pool circuitin both cases:

Case 1: The control system regulates the primary circuit (boiler/exchanger) and the secondary circuit (exchanger/pool).

4 Connect the primary circuit pump (boiler/exchanger) to the MBoutlet on the connection terminal block. The temperatureMAX.CIRC.B is then guaranteed during comfort periods onprogramme B in summer and winter alike.

4 Connect the swimming pool sensor (package AD212) to the SDEP B inlet on the connection terminal block.

4 Set the set point of the pool sensor using key C in the range 5 -39°C.

Case 2: The pool has already a regulation system that is to bekept. The control system only regulates the primary circuit(boiler/exchanger).

4 Connect the primary circuit pump (boiler/exchanger) to the MBoutlet on the connection terminal block.The temperature MAX.CIRC.B is then guaranteed during comfortperiods on programme B in summer and winter alike.

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 45

Page 48: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

The swimming pool can also be connected to circuit C byadding the AD249 option:

4 Make the connection to the terminal blocks markedC.

4 Set the parameters for circuit C.

n Hourly programming of the secondary circuit pump

The secondary pump operates during programme B comfort periodsin summer and winter alike.

n Stopping

To prepare your pool for winter, consult your pool specialist.

4.9.12. Connecting a mixed tank

This configuration is only possible with the DIEMATICiSystem control panel.

A Do not connect anything to the terminal block.

C002909-A

6

7

8

1

2

3

4

9

5

On/off

OT BL RL Tout Tdhw

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1

S DEP B

2 1

TS + C AUXC

SCU PCU

4. Installation MCA 45 - 65 - 90 - 115

46 06/09/2010 - 300024755-001-A

Page 49: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Z Option of connecting the electric tank (with AD249option)or to E

E Outlet circuit A - Option of connecting the electric tank (orto Z)

R Power control relay to the electrical resistor

T Connect the DHW tank anode.

If the tank is not fitted with an impressed currentanode, put the simulation connector in place(delivered with the DHW sensor - packageAD212).

Y Connect the DHW sensor (Package AD212).

U Connect the outside temperature sensor

I D.H.W. load pump.

O Do not connect anything to the terminal block.

DIEMATIC iSystem - Settings to be made for this type of installationParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters in

extended mode", page 65If the electric tank is connected to MA:CIRC. A:(1)

"Installer" level#SYSTEM menu

DHW ELEC ¼ "Setting the parameters specificto the installation", page 66

If the electric tank is connected toMAUX:S.AUX:(1)

"Installer" level#SYSTEM menu

DHW ELEC

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

4.9.13. Connecting the options

For example: TELCOM remote vocal monitoring module, remotecontrols for circuits A and B, second DHW tank

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 47

Page 50: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

C002916-A

V

PRG

TELCOM 2

ALPAL2AL1

321

SET#09

V8765

4321

61

8

On/off

OT BL RL Tout Tdhw

TS + B AB

0-10V S AMB C

4 3 2 1 2 1+ -

S AMB B

2 1

S AMB A

2 1

S SYST + TA - S ECS S EXT S DEP C

2 12 12 12 1 2 1S DEP B

2 1

TS + C AUXC

SCU PCU

3

4

2

7

5

MODE r

x 0 2 4 6 8 10 12 14 16 18 22 2420

c

MODE r

x 0 2 4 6 8 10 12 14 16 18 22 2420

c

A Do not connect anything to the terminal block.

Z Connect the load pump to the second tank (Only forcontrol panel DIEMATIC iSystem).

E Second domestic hot water tank (Only for control panelDIEMATIC iSystem).

R Connect the DHW sensor from the second tank (Only forcontrol panel DIEMATIC iSystem).

T Connect the TELCOM remote vocal monitoring module(depending on its availability in your country).

Y Connecting the BUS cascade, VM

U Connect the remote control (Package AD254/FM52).

I Do not connect anything to the terminal block.

Diematic iSystem - Settings to be made to connect a second tankParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters in extended

mode", page 65If second tank connected:S.AUX:(1)

"Installer" level#SYSTEM menu

DHW ¼ "Setting the parameters specific to theinstallation", page 66

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

4. Installation MCA 45 - 65 - 90 - 115

48 06/09/2010 - 300024755-001-A

Page 51: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.9.14. Connection in cascade

n DHW tank after the mixing tank

A Master boiler (DIEMATIC iSystem)

Z Secondary boiler (DIEMATIC iSystem or IniControl)

E Secondary boiler (DIEMATIC iSystem or IniControl)

R Cable BUS

T Boiler pump

Y Low loss header

U Cascade outlet sensorConnect the sensor to the terminal block S SYST on themaster boiler.

I D.H.W. load pump

O Connect the DHW sensor (Package AD212)

C002910-B

5

1 2

6

7

89

4

3

X81

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 49

Page 52: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

DIEMATIC iSystem - Settings to be made for this type of installation: Master boilerParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters in extended

mode", page 65O.DHW:(1) "Installer" level

#SYSTEM menuPUMP ¼ "Setting the parameters specific to the

installation", page 66CASCADE:(1) "Installer" level

#NETWORK menuON ¼ "Configuring the network", page 81

MASTER CONTROLLER(1) "Installer" level#SYSTEM menu

ON

SYSTEM NETWORK(1) "Installer" level#SYSTEM menu

ADD SLAVE

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

DIEMATIC iSystem - Settings to be made for this type of installation: Follower boilersParameters Access Settings to be made SeeINSTALLATION "Installer" level

#SYSTEM menuEXTENDED ¼ "Displaying the parameters in extended

mode", page 65CASCADE:(1) "Installer" level

#NETWORK menuON ¼ "Configuring the network", page 81

MASTER CONTROLLER(1) "Installer" level#SYSTEM menu

OFF

SLAVE NUMBER(1) "Installer" level#SYSTEM menu

2, 3, ...

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

IniControl - Settings to be made for this type of installation: Follower boilersParameters Access Settings to be made See

CASCADE: FBE "Installer" level 1 ¼ "Description of the parameters", page 100SLAVE NUMBER FBF "Installer" level 2, 3, ...

4. Installation MCA 45 - 65 - 90 - 115

50 06/09/2010 - 300024755-001-A

Page 53: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.10 Electrical diagram

T002860-C

X1

X12

X3

X2 X4X5X6X7X8X9X10

X11

2 31K1

SCU-C

X2

1 32

BL

BR

GN/

YW

SCU-C

X11

1 2 3 4 5 6

WH

GY

OR

RD

GN

YW

DIS

X12

1 2 7 8 9 1 03 4 5 6

P

230V, 50Hz

L N

X1

1 23

BR

BL

GN/YW

X3

4 3 2 15

BR

BL

BR

BL

GN/

YW

3 1

4 2X51

S

X4

1 2 3

X41

BR

BL

GN/

YW

3 1 2

FAN IT

X5

2 3 4 1

E

BK

BL

GN/

YW

GY

1 23

X51

X6

1 2 3

GN/

YW

WH

BL

GB

153

X21/X61

X8

1 2 3

PUMP A

BR

BL

GN/

YW

2 1 3

X81

3 1 2

X41

HLS

X9

2 3 4 5

X91

BK

BK

BK

BK

1 2 4 5

FAN

1

BK

BK

1

2

X117

PWM

PUMP

12 13

BK

BK

1 2

X116

FTSRTS

9

RD

1

BK

1

2 2

X115

8

BL

1

2

X114

PS

10 11

BK

BK

3 1

X112

2 3

X10

4 5 7 6

X111

BK

BK

BK

BK

1 2 3 4

PSU

P Power supply E Ignition power relay FTS Flow sensorSCU Extended control PCB GB Combined venturi and gas valve

unitPS Pressure sensor

S On/Off switch PUMP A Shunt pump PSU Parameter storage for PCBs PSUand SU

FAN Fan HLS Safety thermostat PWM PUMP Modulation signal from the boilerpump

IT Ignition transformer RTS Return sensor DIS Display

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 51

Page 54: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.11 Filling the system

4.11.1. Water treatment

In most cases, the boiler and the central heating installation can befilled with normal tap water and no water treatment will be necessary.

WARNING

Do not add chemical products to the central heating waterwithout consulting De Dietrich Thermique. For example:antifreeze, water softeners, products to increase or reducethe pH value, chemical additives and/or inhibitors. Thesemay cause faults in the boiler and damage the heatexchanger.

4 Rinse the central heating installation with at least 3xthe volume of the central heating installation. Flushthe DHW pipes with at least 20 the volume of thepipes.

4 Use only untreated tap water to fill or top up the levelin the central heating installation.

For an optimum functioning of the boiler, the water of the installationmust comply with following characteristics:

Total installed heat output (kW)≤ 70 70 - 200 200 - 550 > 550

Degree of acidity (waternon-treated)

pH 7 - 9 7 - 9 7 - 9 7 - 9

Degree of acidity (watertreated)

pH 7 - 8,5 7 - 8,5 7 - 8,5 7 - 8,5

Conductivity at 25°C µS/cm ≤ 800 ≤ 800 ≤ 800 ≤ 800Chlorides mg/l ≤ 150 ≤ 150 ≤ 150 ≤ 150Other components mg/l < 1 < 1 < 1 < 1Total water hardness(1) °f 1 - 35 1 - 20 1 - 15 1 - 5

°dH 0,5 - 20,0 0,5 - 11,2 0,5 - 8,4 0,5 - 2,8mmol/l 0,1 - 3,5 0,1 - 2,0 0,1 - 1,5 0,1 - 0,5

(1) For installations that are heated at constant high temperatures with a total installed heat output; up to 200 kW a maximum total water hardnessof 8,4 °dH (1,5 mmol/l, 15 °f) applies and for above 200 kW a maximum total water hardness of 2,8 °dH (0,5 mmol/l, 5 °f) applies

If a water treatment is necessary, De DietrichThermique recommends the following manufacturers:

4 Cillit4 Climalife4 Fernox4 Permo4 Sentinel

4. Installation MCA 45 - 65 - 90 - 115

52 06/09/2010 - 300024755-001-A

Page 55: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.11.2. Filling the siphon

1. Remove the siphon.2. Fill the siphon with water. This must be completely filled.3. Re-assemble the siphon.

CAUTION

Fill the water siphon before starting the boiler to avoidcombustion products escaping from the boiler.

4.11.3. Filling the system

CAUTION

Before filling, open the valves on every radiator in theinstallation.

In order to be able to read off the water pressure from theboiler display, the boiler must be switched on.

1. Fill the system with clean tap water (advised water pressure isbetween 1,5 and 2 bar).

2. Check the tightness of the water connections.

T002037-B

1

2

3

4

T000181-B

T001507-B

MCA 45 - 65 - 90 - 115 4. Installation

06/09/2010 - 300024755-001-A 53

Page 56: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5 Start-up - DIEMATIC iSystem

5.1 Control panel

5.1.1. Description of the keys

A Temperature setting key (heating, DHW, swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections

are madeF Rotary setting button:

4 Turn the rotary button to scroll through the menus ormodify a value

4 Press the rotary button to access the menu selectedor confirm a value modification

A000866-A

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

A

B

C

D E F

( '

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

54 06/09/2010 - 300024755-001-A

Page 57: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.1.2. Description of the display

n Key functions

> Access to the various menus

( Used to scroll through the menus

' Used to scroll through the parameters? The symbol is displayed when help is available

f Used to display the curve of the parameter selectedSTD Reset of the time programmes

b Selection of comfort mode or selection of the days to beprogrammed

v Selection of reduced mode or deselection of the days tobe programmed

j Back to the previous levelESC Back to the previous level without saving the

modifications made

t Manual reset

n Flame output level

C002705-A

The whole symbol flashes: The burner starts up but theflame is not yet present

C002704-A

Part of the symbol flashes: Output is increasing

C002703-A

Steady symbol: The required output has been reached

C002702-A

Part of the symbol flashes: Output is dropping

bar

r

STD( ' t

0 2 4 6 8 10 12 14 16 18 22 2420

C002696-A

pb AUTOx c rjLg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002701-B

pb AUTOx c rjMg m

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 55

Page 58: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Operating modes

p Summer mode: The heating is off. Domestic hot watercontinues to be produced

b WINTER mode: Heating and domestic hot water working

AUTO Operation in automatic mode according to the timerprogramme

x Comfort mode: The symbol is displayed when a DAYoverride (comfort) is activated

4 Flashing symbol: Temporary override4 Steady symbol: Permanent override

m Reduced mode: The symbol is displayed when a NIGHToverride (reduced) is activated

4 Flashing symbol: Temporary override4 Steady symbol: Permanent override

g Holiday mode: The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated

4 Flashing symbol: Holiday mode programmed4 Steady symbol: Holiday mode active

m Manual mode

n System pressure

bar Pressure indicator: The symbol is displayed when a waterpressure sensor is connected

4 Flashing symbol: The quantity of water is insufficient4 Steady symbol: The quantity of water is sufficient

l Water pressure level

4 R : 0,9 to 1,1 bar4 E : 1,2 to 1,5 bar4 Z : 1,6 to 1,9 bar4 A : 2,0 to 2,3 bar4 l : > 2,4 bar

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002697-B

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002698-B

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002708-A

pb AUTOx c rjMg m

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

56 06/09/2010 - 300024755-001-A

Page 59: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Domestic Hot Water override

A bar is displayed when a DHW override is activated:

4 Flashing bar: Temporary override4 Steady bar: Permanent override

n Other information

r The symbol is displayed when domestic hot waterproduction is running

w Valve indicator: The symbol is displayed when a 3-wayvalve is connected

4 x : 3-way valve open4 c : 3-way valve closed

M The symbol is displayed when the pump is operating

Name of the circuit for which the parameters are displayed

5.1.3. Access to the various browsing levels

n "User" level

The information and settings in the "User" level can be accessed byeveryone.

1. Press the > key.

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002707-A

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002699-B

pb AUTOx c rjMg m

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 57

Page 60: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n "Installer" level

The information and settings in the "Installer" level can be accessedby experienced people.

1. Press key - for around 5 seconds.

Before the "Installer" level is displayed, the EMISSIONMEASUREMENTS menu will be displayed. Hold down the- key until #LANGUAGE is displayed.

n "After Sales" level

The information and settings in the "After Sales" level can beaccessed by initiates.

1. Press key - for around 10 seconds.

Before the "After Sales" level is displayed, the "Installer"level will be displayed. Hold key - down until#PARAMETERS is displayed.

5.1.4. Browsing in the menus

1. To select the desired menu, turn the rotary button.2. To access the menu, press the rotary button.

To go back to the previous display, press the key j.

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

#MEASURES

#CHOICE TIME PROG.

#TIME PROGRAM

#SETTING

#TIME .DAYÿ

C002220-A-04

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

58 06/09/2010 - 300024755-001-A

Page 61: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3. To select the desired parameter, turn the rotary button.4. To modify the parameter, press the rotary button.

To go back to the previous display, press the key j.

5. To modify the parameter, turn the rotary button.6. To confirm, press the rotary button.

To cancel, press key h.

7. To go back to the main display, press key j2 times.

It is possible to use the ( and ' keys instead of the rotarybutton.

5.2 Check points before commissioning

5.2.1. Preparing the boiler for commissioning

WARNING

Do not put the boiler into operation if the supplied gas isnot in accordance with the approved gas types.

Preparatory procedure for boiler commissioning:

4 Check that the gas type supplied matches the data shown on theboiler's data plate.

4 Check the gas circuit.4 Check the hydraulic circuit.4 Check the water pressure in the heating system.4 Check the electrical connections to the thermostat and the other

external controls.4 Check the other connections.4 Test the boiler at full load. Check the setting of the gas/air ratio

and, if necessary, correct it.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CURRENT PROG.B

CURRENT PROG.C

P2

P3

ÿ

C002221-B-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CURRENT PROG.C"Choice of the timeprogram applied C"

P4

ÿ

C002222-B-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

LUNDI 11:45

C002224-D-04

2x

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 59

Page 62: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4 Test the boiler at part load. Check the setting of the gas/air ratioand, if necessary, correct it.

4 Finalizing work.

5.2.2. Gas circuit

WARNING

Ensure that the boiler is switched off.

1. Open the main gas supply.2. Unscrew the two screws located under the front panel by a quarter

turn and remove the panel.3. Tilt the control box forwards by opening the holding clips located

at the sides.4. Check the gas supply pressure at the measurement point C on the

gas valve unit.

WARNING

¼ To ascertain the gas types permitted, see chapter:"Equipment categories", page 8

5. Check the tightness of the gas connections made after the gasvalve unit in the boiler.

6. Check the leak tightness of the gas inlet, including the gasvalves. The test pressure must not exceed 60 mbar.

7. Purge the gas supply pipe within the boiler by unscrewing themeasurement point on the gas block. Tighten the measurementpoint when the pipe has been sufficiently purged.

8. Check the tightness of the gas connections in the boiler.

5.2.3. Hydraulic circuit

4 Check the syphon — this must be completely filled with cleanwater.

4 Check that there are no leaks on the hydraulic connections.

5.2.4. Electrical connections

4 Check the electrical connections.

5.3 Putting the appliance into operation

1. Tilt the control box upwards again and fasten it using the clipslocated at the sides.

2. Open the main gas supply.3. Open the gas valve on the boiler.

T003243-A

C C

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

60 06/09/2010 - 300024755-001-A

Page 63: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4. Turn on the boiler using the on/off switch.

5. The first time the boiler is powered up, the #LANGUAGE menu isdisplayed. Select the desired language by turning the rotarybutton.

6. To confirm, press the rotary button.

The boiler will begin an automatic venting-programme (which lastsapprox. 3 minutes) and will do this every time the power supply isisolated.

Error during the start-up procedure:

4 No information is shown on the display:- Check the mains supply voltage- Check the fuses- Check the connection of the power cable to the connector X1

on the PCU PCB4 If there is a problem, the error is displayed on the screen.¼ See chapter: "Messages (Code type Bxx or Mxx)", page118

If a DHW sensor is connected and the anti-legionellafunction is activated, the boiler starts to heat the water inthe DHW tank as soon as the vent programme has beencompleted. The heating time depends on the size of theDHW installation.

C002366-B

Français - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Türk -

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb x c rg m

ÿLANGUE FRANCAIS

C002286-C

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 61

Page 64: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.4 Gas settings

5.4.1. Adapting to another gas type

WARNING

Only a qualified engineer may carry out the followingoperations.

The boiler is preset in the factory to operate on natural gas H (G20).

For operation on another group of gases, carry out the followingoperations.In case of functioning on propane:

1.Boiler type For conversion to propaneMCA 45 Rotate the adjusting screw A on the venturi 4¾ turns in a

clockwise directionMCA 65 Rotate the adjusting screw A on the venturi 6½ turns in a

clockwise directionMCA 90 Fit the gas restrictor in the gas blockMCA 115 First turn the setting screw A clockwise until it is closed, then:

Rotate the adjusting screw A on the gas block 3,5 - 4 turns inan anticlockwise direction

2. Regulate the fan speed as indicated in the table (if required):¼ See chapter: ""Professional" settings", page 75

3. Set the air/gas ratio. For more detailed information on this subject,see the following paragraphs:¼ "Setting the air/gas ratio (Full load)", page 62¼ "Setting the air/gas ratio (Part load)", page 64

5.4.2. Setting the air/gas ratio (Full load)

1. Unscrew the plug of the flue gas measurement point.2. Connect the flue gas analyser.

WARNING

Ensure that the opening around the sensor is completelysealed when taking measurements.

T003241-A

A A

T001581-A

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

62 06/09/2010 - 300024755-001-A

Page 65: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3. In the main display, press key -. The menu EMISSIONMEASUREMENTS is displayed on the screen.

If an automatic vent cycle is running, it is not possible toperform these operations.

4. The characteristics of the generator are displayed.

5. Turn the rotary button until PMAX is displayed. The full load is set.6. Measure the percentage of O2 or CO2 in the flue gases.7. Compare the values measured with the checking values given in

the table (Front panel removed):

8. If necessary, adjust the gas/air ratio using the adjusting screw(A).

O2/CO2 control and setting values for gas H (G20) at full loadBoiler type Setting value Checking value

O 2 (%) CO 2 (%) O 2 (%) CO 2 (%)MCA 45 4,8 ± 0,2 9,0 ± 0,1 4,8 ± 0,5 9,0 ± 0,2MCA 65 4,8 ± 0,2 9,0 ± 0,1 4,8 ± 0,5 9,0 ± 0,2MCA 90 3,9 ± 0,2 9,5 ± 0,1 3,9 ± 0,5 9,5 ± 0,2MCA 115 4,7 ± 0,2 9,1 ± 0,1 4,7 ± 0,5 9,1 ± 0,2

O2/ CO2 control and setting values for propane (G31) at full loadBoiler type Setting value Checking value

O 2 (%) CO 2 (%) O 2 (%) CO 2 (%)MCA 45 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 65 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 90 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 115 4,9 ± 0,2 10,5 ± 0,1 4,9 ± 0,5 10,5 ± 0,2

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP.: 68°

C002271-F-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx cg m rjM

GENE :BOILER TEMP.CURRENTFAILURE

PMAX68°C10µA

5600 tr/min ÿ

C002347-D-04

OFF => PMAX

T003241-A

A A

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 63

Page 66: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.4.3. Setting the air/gas ratio (Part load)

1. Unscrew the plug of the flue gas measurement point.2. Connect the flue gas analyser.

WARNING

Ensure that the opening around the sensor is completelysealed when taking measurements.

3. In the main display, press key -. The menu EMISSIONMEASUREMENTS is displayed on the screen.

If an automatic vent cycle is running, it is not possible toperform these operations.

4. The characteristics of the generator are displayed.5. Turn the rotary button until PMIN is displayed. The part load is set.6. Measure the percentage of O2 or CO2 in the flue gases.7. Compare the values measured with the checking values given in

the table (Front panel removed):

T001581-A

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP.: 68°

C002271-F-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx cg m rjM

GENE :BOILER TEMP.CURRENTFAILURE

PMIN68°C10µA

1850 tr/min ÿ

C002348-D-04

OFF => PMIN

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

64 06/09/2010 - 300024755-001-A

Page 67: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8. If necessary, adjust the gas/air ratio using the adjusting screw(B).

O2/CO2 control and setting values for gas H (G20) at low speedBoiler type Setting value Checking value

O 2 (%) CO 2 (%) O 2 (%) CO 2 (%)MCA 45 4,8 ± 0,2 9,0 ± 0,1 4,8 ± 0,5 9,0 ± 0,2MCA 65 4,8 ± 0,2 9,0 ± 0,1 4,8 ± 0,5 9,0 ± 0,2MCA 90 3,9 ± 0,2 9,5 ± 0,1 3,9 ± 0,5 9,5 ± 0,2MCA 115 4,3 ± 0,2 9,3 ± 0,1 4,3 ± 0,5 9,3 ± 0,2

O2/CO2 control and setting values for propane (G31) at low speedBoiler type Setting value Checking value

O 2 (%) CO 2 (%) O 2 (%) CO 2 (%)MCA 45 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 65 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 90 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 115 4,9 ± 0,2 10,5 ± 0,1 4,9 ± 0,5 10,5 ± 0,2

5.5 Checks and adjustments after commissioning

5.5.1. Displaying the parameters in extendedmode

The display mode on the control panel is set as standard in such away as only to show the "conventional" parameters. It is possible toswitch to "extended" mode by proceeding as follows:

1. Access the "installer" level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

3. Set the parameter INSTALLATION to EXTENDED.

"Installer" level - #SYSTEM menu

Parameter Adjustment range Description Factory setting Customer settingINSTALLATION CLASSIC Displays the parameters of a conventional

installationCLASSIC

EXTENDED Displays all parameters

Regardless of what is done to the keys, the regulatorswitches back to CLASSIC mode after 30 minutes.

T003242-A

B B

B

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 65

Page 68: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.5.2. Setting the parameters specific to theinstallation

1. Access the "installer" level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

3. Set the following parameters according to the connections madeto the PCBs:

"Installer" level - #SYSTEM menu

Parameter Adjustment range Description Factory setting Customersetting

CIRC. A: (1)(2) DIRECT Use as a direct heating circuit DIRECT PROGRAM. Use as an independent programmable outletH.TEMP Enables operation of circuit A in summer despite

manual or automatic summer shutdownDHW Connection of a second domestic hot water tankDHW ELEC Used to control the electrical resistor according to the

timer programme on circuit A in summer modeDISAB. No data for circuit A is displayed

CIRC. B: (1) 3WV Connecting a circuit with 3-way valve (For example:Underfloor heating)

3WV

SWIM.P. Using the circuit for pool managementDIRECT Use of circuit in direct heating circuit

CIRC. C: (1) 3WV Connecting a circuit with 3-way valve (For example:Underfloor heating)

3WV

SWIM.P. Using the circuit for pool managementDIRECT Use of circuit in direct heating circuit

O.PUMP A (1)

(2)CH.PUMP A Heating pump circuit A: The PUMP A outlet is used to

control the pump on circuit ACH.PUMP A

CIRC.AUX Used to resume the functions of the S.AUX parameterwithout adding the "PCB + sensor" option (PackageAD249)

DHW LOOP Used to control the domestic hot water looping pumpaccording to the DHW timer programme and force itsoperation during an override

PRIMARY PUMP The outlet PUMP A is active if a heating demand ispresent on the secondary pump

ORDER BURNER The outlet PUMP A is active when a burner demandis present

FAILURE The outlet PUMP A is active if an error is detectedO.DHW: (1) PUMP Using a tank load pump on the DHW PUMP outlet PUMP

RV Use of a reversal valve for DHW production (Notused)

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) If the pump incorporated in the boiler is used for circuit A (parameter CIRC.A set to DIRECT), the O.PUMP A outlet is free(3) This parameter is displayed only if the O.PUMP A parameter is set to CIRC.AUX or if the 3-way valve PCB option is used

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

66 06/09/2010 - 300024755-001-A

Page 69: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

"Installer" level - #SYSTEM menu

Parameter Adjustment range Description Factory setting Customersetting

BS60(1) ON Small capacity tank OFF OFF Large capacity tank

S.AUX: (1)(3) DHW LOOP Use as a domestic loop pump DHW LOOP PROGRAM. Use as an independent programmable outletPRIMARY PUMP The outlet AUX PUMP is active if a heating demand

is present on the secondary pumpORDER BURNER The outlet AUX PUMP is active when a burner

demand is presentDHW Use of primary circuit of second DHW tankFAILURE The outlet AUX PUMP is active if an error is detectedDHW ELEC Used to control the electrical resistor according to the

timer programme on circuit AUX in summer modeI.SYST (1) SYSTEM The inlet sensor is used to connect the common flow

sensor of a cascade systemSYSTEM

STORAGE TANK Hot water storage tank affected to heating onlyDHW STRAT Using the DHW tank with 2 sensors (top and bottom)ST.TANK+DHW Hot water storage tank affected to heating and

domestic hot waterO. TEL: (1) FAILURE The telephone outlet is closed in the event of failure FAILURE

REVISION The telephone outlet is closed in the event of revisiondisplay

DEF+REV The telephone outlet is closed in the event of failureor revision display

CT.TEL (1) CLOSE See table below. CLOSE OPEN

I.TEL: (1) ANTIFR Start anti-freeze in boiler command ANTIFR 0/1 A ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit A0/1 B ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit B0/1 C ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit C0/1 DHW ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit ECS0/1 AUX ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit AUX (S.AUX ifoption *1 is present or outlet O.PUMP A is configuredas CIRC.AUX)When I.TEL: is not active, the auxiliary circuit (AUX)follows the maximum boiler temperature (parameterBOILER MAX).

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) If the pump incorporated in the boiler is used for circuit A (parameter CIRC.A set to DIRECT), the O.PUMP A outlet is free(3) This parameter is displayed only if the O.PUMP A parameter is set to CIRC.AUX or if the 3-way valve PCB option is used

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 67

Page 70: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Influence of the parameter setting CT.TEL on the I.TEL contactCT.TEL I.TEL: I.TEL contact closed I.TEL contact openCLOSE ANTIFR The antifreeze mode is active on all boiler circuits. The mode selected on the boiler is active.

0/1 A The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.

0/1 B The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.

0/1 C The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.

0/1 DHW The mode selected on the DHW circuit is active. The antifreeze mode is active for the DHW circuit.0/1 AUX 4 The MAUX outlet on the connection terminal

block is active.4 The boiler operates at a set point temperature

equal to BOILER MAX.

4 The MAUX outlet on the connection terminalblock is not active.

4 The boiler operates with a set point temperatureas a function of the outside temperature.

OPEN ANTIFR The mode selected on the boiler is active. The antifreeze mode is active on all boiler circuits.0/1 A The antifreeze mode is active on the circuit

concerned.The mode selected on the circuit is active.

0/1 B The antifreeze mode is active on the circuitconcerned.

The mode selected on the circuit is active.

0/1 C The antifreeze mode is active on the circuitconcerned.

The mode selected on the circuit is active.

0/1 DHW The antifreeze mode is active for the DHW circuit. The mode selected on the DHW circuit is active.0/1 AUX 4 The MAUX outlet on the connection terminal

block is not active.4 The boiler operates with a set point temperature

as a function of the outside temperature.

4 The MAUX outlet on the connection terminalblock is active.

4 The boiler operates at a set point temperatureequal to BOILER MAX.

5.5.3. Naming the circuits and generators

1. Access the "installer" level: Press key - for around 5 seconds.2. Select the menu #NAMES OF THE CIRCUITS.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

68 06/09/2010 - 300024755-001-A

Page 71: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3. Select the circuit or generator you wish to rename.

"Installer" level - #NAMES OF THE CIRCUITS menu

Parameter Description Name given by the customerCIRC. A: Circuit A CIRC. B: Circuit B CIRC. C: Circuit C CIRC.AUX Auxiliary circuit CIRC.DHW Domestic hot water circuit GENE Generator

4. Turn the rotary button to choose the first character from the list.To confirm, press the rotary button.

5. Then press again to enter a second character or turn the rotarybutton to leave an empty space.

6. Choose the other characters in the same way. The input zone maycontain up to 6 characters.

To move from one character to another, turn the rotarybutton. To exit without modifications, press key h.

7. To confirm the name, press the rotary button and then turn thebutton slightly anti-clockwise. When the symbol U appears, pressthe rotary button. The name is confirmed.

If the name reaches 6 characters, it is automaticallyconfirmed when the last character is confirmed.

5.5.4. Setting the heating curve

If an outside temperature sensor is connected, it is possible to adaptthe heating curve.

1. Access the "installer" level: Press key - for around 5 seconds.2. Select the menu #SECONDARY INSTAL.P.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CIRC.B I

"Personalize the nameof this circuit B"

ÿ

E

F

G

H

..

.

C002344-C-04

I

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CIRC.B INPUT

"Personalize the nameof this circuit B"

ÿ

X

Y

Z

.

.

.

C002345-C-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 69

Page 72: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3. Select the parameter HEAT.CURV. ....

4. To modify the value directly, turn the rotary button.To modify the value by displaying the curve, press key f.

5. To modify the curve, turn the rotary button.6. To confirm, press the rotary button.

To cancel, press key h.

0.7 = Heating curve set

n Heating curve without BCT

The BCT (Base heat Curve Temperature) allows a minimumoperating temperature to be imposed on the heating circuit (thistemperature may be constant if the circuit gradient is nil).

A Maximum temperature of the circuit

Z Water temperature in the circuit for an outsidetemperature of 0°C

E DAY set point on the circuit

R Outside temperature for which the maximum watertemperature in the circuit is reached

T Value of the heating curveThis value corresponds to the parameter HEAT.CURV.¼ See chapter: ""Professional" settings", page 75.

When you modify the heating curve, Z and T arerecalculated and repositioned automatically.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

BUILD.INERTIA

CIRC.CURVE B

CIRC.CURVE C

SCREED DRYING

3

2.0

0.7

No ÿ

C002316-D-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

CIRC.CURVE B"Slope of the heatcurve of the circuit B"

2.0

C002317-D-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

7564

50

020 -15

C002318-B-04

0,7

0.7

20 0 -16

50

75

1.5

C002319-B

1

2

3

4

5

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

70 06/09/2010 - 300024755-001-A

Page 73: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Heating curve with BCT

The BCT (Base heat Curve Temperature) allows a minimumoperating temperature to be imposed on the heating circuit (thistemperature may be constant if the circuit gradient is nil).

A Maximum temperature of the circuit

Z Water temperature in the circuit for an outsidetemperature of 0°C

E DAY set point on the circuit

R Outside temperature for which the maximum watertemperature in the circuit is reached

T Value of the heating curveThis value corresponds to the parameter HEAT.CURV.¼ See chapter: ""Professional" settings", page 75.

x Value set to the parameter HCZP D

When you modify the heating curve, Z and T arerecalculated and repositioned automatically.

5.5.5. Finalizing work

1. Remove the measuring equipment.2. Put the flue gas sampling plug back in place.3. Refit the front panel. Tighten the two screws by a quarter turn.4. Raise the temperature in the heating system to approximately

70°C.5. Shut down the boiler.6. After about 10 minutes, vent the air in the heating system.7. Checking the hydraulic pressure. If necessary, top up the water

level in the heating system (recommended hydraulic pressurebetween 1,5 and 2 bar).

8. Tick the gas category used on the data plate.9. Explain the operation of the installation, the boiler and the

regulator to the users.10.Inform the user of the periodicity of maintenance work to be carried

out. Input the service date and the contact details of the installer.11.Give all the instruction manuals to the user.

Commissioning of the boiler is now complete.

The various boiler parameters are preset in the factory.These factory settings are suitable for the most commonheating systems. For other systems and situations, theparameters can be modified.

20 0 -15

64

50

75

0.7

C002320-B

1

2

X

3

4

5

T001522-A

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 71

Page 74: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.6 Reading out measured values

The various values measured by the appliance are displayed in the#MEASURES menu.

1. To access "user" level: Press the > key.2. To select the #MEASURES menu.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58.

"User" level - #MEASURES menu

Parameter Description UnitOUTSIDE TEMP. Outside temperature °CROOMTEMP. A (1) Room temperature of circuit A °C

ROOMTEMP. B (1) Room temperature of circuit B °C

ROOMTEMP. C (1) Room temperature of circuit C °CBOILER TEMP. Water temperature in the boiler °CPRESSURE Water pressure in the installation barWATER TEMP. (1) Water temperature in the DHW tank °C

INST DWH TEMP. (1) Instant hot water temperature °C

STOR.TANK.TEMP (1) Water temperature in the storage tank °CDCW TEMPERATURE Domestic cold water temperature °CSWIMMING P.T.B (1) Water temperature of the swimming pool on circuit B °C

SWIMMING P.T.C (1) Water temperature of the swimming pool on circuit C °C

OUTLET TEMP. B (1) Temperature of the flow water in circuit B °C

OUTLET TEMP. C (1) Temperature of the flow water in circuit C °C

SYSTEM TEMP. (1) Temperature of the system flow water if multi-generator °CT.DHW BOTTOM Water temperature in the bottom of the DHW tank °CTEMP.TANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit °C

DHW A TEMP. (1) Water temperature in the second DHW tank connected to circuit A °CBACK TEMP Temperature of the boiler return water °CWIND SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0%: Burner off or running at minimum output) %CURRENT (µA) Ionization current µANB IMPULS. Number of burner start-ups (not restartable)

The meter is incremented by 8 every 8 start-ups

RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours

h

IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options, circuits or sensors actually connected.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

72 06/09/2010 - 300024755-001-A

Page 75: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.7 Changing the settings

The boiler control panel is set for the most common heatingsystems. With these settings, practically all heating systems operatecorrectly. The user or installer can optimise the parameters accordingto own preferences.

¼ For the "user" settings, refer to the user instructions.

5.7.1. Language selection

1. Access the "installer" level: Press key - for around 5 seconds.2. Select the menu #LANGUAGE.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

"Installer" level - #LANGUAGE menu

Adjustment range DescriptionFRANCAIS Display in FrenchDEUTSCH Display in GermanENGLISH Display in EnglishITALIANO Display in ItalianESPANOL Display in SpanishNEDERLANDS Display in DutchPOLSKY Display in Polish

5.7.2. Calibrating the sensors

1. To access "user" level: Press the > key.2. To select the #SETTING menu.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

3. To set the following parameters:

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 73

Page 76: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

"User" level - #SETTING menu

Parameter Adjustment range Description Factory setting Customersetting

SUM/WIN 15 to 30 °C Used to set the outside temperature abovewhich heating will be shut down.

4 The heating pumps are shut down.4 The burner will only start for domestic

hot water needs.4 The letter E and the symbol p are

displayed.

22 °C

NO Heating is never shut down automaticallyCALIBR. OUT Outside sensor calibration: Used to correct

the outside temperatureOutsidetemperature

CALIBR. ROOM A(1)(1)

Calibration of the room sensor on circuit A:Is used to set a room offsetMake this setting 2 hours after switching on,when the room temperature has stabilised

Room temperatureof circuit A

OFFSET ROOM A(1)

-5.0 to +5.0 °C Room offset on circuit A: Is used to set aroom offsetMake this setting 2 hours after switching on,when the room temperature has stabilised

0.0

ANTIFR. ROOM A 0.5 to 20 °C Room temperature antifreeze activation oncircuit A

6 °C

CALIBR. ROOM B(1)(1)

Calibration of the room sensor on circuit B:Is used to set a room offsetMake this setting 2 hours after switching on,when the room temperature has stabilised

Room temperatureof circuit B

OFFSET ROOM B(1)

-5.0 to +5.0 °C Room offset on circuit B: Is used to set aroom offsetMake this setting 2 hours after switching on,when the room temperature has stabilised

0.0

ANTIFR. ROOM B 0.5 to 20 °C Room temperature at which the antifreezemode is activated on circuit B

6 °C

CALIBR. ROOM C(2)(1)

Calibration of the room sensor oncircuit C: Is used to set a room offsetMake this setting 2 hours after switching on,when the room temperature has stabilised

Room temperatureof circuit C

OFFSET ROOM C(3)(1)

-5.0 to +5.0 °C Room offset on circuit C: Is used to set aroom offsetMake this setting 2 hours after switching on,when the room temperature has stabilised

0.0

ANTIFR. ROOM C(4)

0.5 to 20 °C Room temperature antifreeze activation oncircuit C

6 °C

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed if a room sensor is connected to the circuit concerned(3) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence(4) The parameter is only displayed if the circuit concerned is actually connected

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

74 06/09/2010 - 300024755-001-A

Page 77: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.7.3. "Professional" settings

1. Access the "installer" level: Press key - for around 5 seconds.2. To set the following parameters:

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

"Installer" level - #PRIMARY LIMITS menu

Parameter Adjustment range Description Factory setting Customer settingBOILER MAX 20 to 90 °C Maximum boiler temperature 80 °C MAX.R.HEAT(%) (1) 0-100% Maximum boiler output during heating 100% MAX.DHW(%) (1)(2) 0-100% Maximum boiler output in DHW 100% MIN.VENT. (1) 1000-5000 rpm Minimum fan speed See table below MAX.VENT.BOIL (1) 1000-7000 rpm Maximum fan speed setting in heating See table below MAX.VENT.DHW (1) 1000-7000 rpm Maximum fan speed setting in domestic

hot waterSee table below

START RPM (1) 1000-5000 rpm Optimum start-up speed setting See table below MIN.PUMP SPEED (1) 20-100% Minimum pump speed 40 % MAX.PUMP SPEED (1) 20-100% Maximum pump speed 100 % (1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed if P.DHW is set to PUMP

"Installer" level - #SECONDARY LIMITS menu

Parameter Adjustment range Description Factory settingMAX.CIRC.A 20 to 95 °C Maximum temperature (Circuit A)

See comments below75 °C

MAX.CIRC.B 20 to 95 °C Maximum temperature (Circuit B)See comments below

50 °C

MAX.CIRC.C 20 to 95 °C Maximum temperature (Circuit C)See comments below

50 °C

OUT.ANTIFREEZE OFF, -8 to +10 °C Outside temperature at which the installation's antifreeze protectionis activated.Below this temperature the pumps are permanently on and theminimum temperatures for each circuit are respected.When NIGHT : STOP is set, the reduced temperature is maintainedin each circuit (#SECONDARY INSTAL.P menu).OFF: Antifreeze protection is not activated

+3 °C

HCZP D A (1)(2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit A) OFF

HCZP N A (1)(2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit A) OFF

HCZP D B (1)(2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit B) OFF

HCZP N B (1)(2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit B) OFF(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f.

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 75

Page 78: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

"Installer" level - #SECONDARY LIMITS menu

Parameter Adjustment range Description Factory settingHCZP D C (1)(2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit C) OFF

HCZP N C (1)(2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit C) OFFPRIM.TEMP.DHW 50 to 90 °C Boiler temperature setting if producing domestic hot water 80 °C(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f.

"Installer" level - #PRIMARY INSTAL.P menu(1)

Parameter Adjustment range Description Factory setting Customersetting

BURN.MIN.RUN 0 to 180 seconds Setting the burner minimum operation time (Inheating mode)

30 seconds

TIMER GENE P. 1 to 30 minutes Maximum post-operation duration of thegenerator pump

4 minutes

IN.BL STOP HEAT Configuration of the PCU BL inletIf the contact is open, the heating is off. If theparameter P.DHW is set to VI, DHW productionnevertheless remains functional. Automaticrestart when the contact closes.

TOTAL STOP

TOTAL STOP Configuration of the PCU BL inletIf the contact is open, heating and DHWproduction are off. Automatic restart when thecontact closes.

SAFETY MODE Configuration of the PCU BL inletIf the contact is open, the boiler goes into safetylockout. The boiler needs to be reset to restart.

(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED

"Installer" level - #SECONDARY INSTAL.P menu

Parameter Adjustment range Description Factorysetting

Customersetting

BUILD. INERTIA (1) 0 (10 hours) to 10(50 hours)

Characterisation of building's inertia:0 for a building with low thermal inertia.3 for a building with normal thermalinertia.10 for a building with high thermal inertia.Modification of the factory setting isonly useful in exceptional cases.

3 (22 hours)

CIRC.CURVE A(2) 0 to 4 Heating curve of the circuit ASee comments below

1.5

ROOM INFL. A (1) 0 to 10 Influence of room sensor ASee comments below

3

CIRC.CURVE B(2) 0 to 4 Heating curve of the circuit BSee comments below

0.7

ROOM INFL. B (1) 0 to 10 Influence of room sensor BSee comments below

3

CIRC.CURVE C(2) 0 to 4 Heating curve of the circuit CSee comments below

0.7

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) The parameter is only displayed if IN 0-10V is set to ON.(5) If a reversal valve is connected, DHW priority will always be total regardless of the setting.

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

76 06/09/2010 - 300024755-001-A

Page 79: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

"Installer" level - #SECONDARY INSTAL.P menu

Parameter Adjustment range Description Factorysetting

Customersetting

ROOM INFL. C (1) 0 to 10 Influence of room sensor CSee comments below

3

SCREED DRYING NO, B, C, B+C Drying the floorSee comments below

NO

START DRYINGTEMP(3)

20 to 50 °C Screed drying start temperature 20 °C

STOP DRYINGTEMP(3)

20 to 50 °C Screed drying stop temperature 20 °C

NUMB. DAYS DRY.(3) 0 to 99 0 NIGHT (1) DEC. The lower temperature is maintained

(Night mode)See comments below

DEC.

STOP The boiler is stopped (Night mode)See comments below

IN 0-10V OFF / TEMPERATURE /POWER %

Activating the control at 0-10 VSee comments below

OFF

VMIN/OFF 0-10V (1)(4) 0 to 10 V Voltage corresponding to the instructionset minimum

0.5 V

VMAX 0-10V (1)(4) 0 to 10 V Voltage corresponding to the instructionset maximum

9.5 V

CONS.MIN 0-10V (1)

(4)10 to 70 °C Instruction minimum set temperature 20 °C

CONS.MAX 0-10V (1)

(4)10 to 100 °C Maximum set temperature 80 °C

BAND WIDTH (1) 4 to 16 K Control unit bandwidth for the 3-wayvalves.Option of increasing the bandwidth if thevalves are rapid or of reducing it if they areslow.

12 K

BOIL/3WV SHIFT (1) 0 to 16 K Minimum temperature differencebetween the boiler and the valves

4 K

H. PUMP DELAY (1) 0 to 15 minutes Timing of the shutdown of the heatingpumps.The timing of heating pump shutdownprevents the boiler overheating.

4 minutes

HW. PUMP DELAY (1)

(2)2 to 15 minutes Timing of the shutdown of the domestic

hot water pump.The timing of the domestic hot water loadpump shutdown prevents the boiler andthe heating circuits overheating (Only if aload pump is used).

2 minutes

ADAPT ON Automatic adaptation of the heatingcurves for each circuit with a room sensorwith an influence of >0.

ON

OFF The heating curves can only be modifiedmanually.

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) The parameter is only displayed if IN 0-10V is set to ON.(5) If a reversal valve is connected, DHW priority will always be total regardless of the setting.

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 77

Page 80: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

"Installer" level - #SECONDARY INSTAL.P menu

Parameter Adjustment range Description Factorysetting

Customersetting

PRIORITY DHW(5) TOTAL Interruption of pool heating and reheatingduring domestic hot water production.

TOTAL

SLIDING Domestic hot water production andheating on the valve circuits if theavailable output is sufficient and thehydraulic connection allows.

NO Heating and domestic hot waterproduction in parallel if the hydraulicconnection allows.a Risk of overheating in the direct circuit.

LEG PROTEC The "anti legionella" function acts toprevent the development of legionella inthe dhw tank, these bacteria areresponsible for legionellosis.

OFF

OFF Anti-legionella function not activatedDAILY The tank is overheated every day from

4:00 o'clock to 5:00 o'clockWEEKLY The tank is overheated every Saturday

from 4:00 o'clock to 5:00 o'clock(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) The parameter is only displayed if IN 0-10V is set to ON.(5) If a reversal valve is connected, DHW priority will always be total regardless of the setting.

n MAX.CIRC...

WARNING

If using underfloor heating, do not modify the factorysetting (50 °C). To install this, please consult existinglegislation.

4 In the case of a direct circuit, connect a safety thermostat to theBL contact.

4 In the case of a 3-way valve circuit (B or C), connect a safetythermostat to the TS contact.

n CIRC. CURVE ...

Heating curve circuit A, B or C

x Outside temperature (°C)y Water flow temperature (°C)

A Maximum temperature of the circuit B - C

M001678-B

1

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

78 06/09/2010 - 300024755-001-A

Page 81: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n SCREED DRYING

Used to force a constant flow temperature or a train to acceleratescreed drying on underfloor heating.The setting for these temperatures must follow the screed-layer'srecommendations.Activation of this parameter (setting other than OFF) forces thepermanent display of SCREED DRYING and deactivates all othercontrol system functions.When floor drying is active on a circuit, all other circuits (e.g. DHW)are shut down. The use of this function is only possible on circuits Band C.

A STOP DRYING TEMP

Z START DRYING TEMP

E Today

R NUMB. DAYS DRY.

T Normal regulation (End of drying)

Y Heating temperature setting (°C)

For example

A STOP DRYING TEMP: 47 °C

Z START DRYING TEMP: 20 °C

R NUMB. DAYS DRY.

T Normal regulation (End of drying)

Y Heating temperature setting (°C)

Every day at midnight (00:00): the set point (STARTDRYING TEMP) is recalculated and the remaining numberof days (NB DAYS DRYING) is decremented.

n ROOM S.INFL

Used to adjust the influence of the room sensor on the watertemperature for the circuit concerned.

0 No influence (remote control fitted in a location with no influence)1 Slight influence3 Average influence (recommended)10 Room thermostat type operation

2

34

1

6

5

C002768-A

00:00 00:00 00:00

2

10 9 8 7 6 5 4 3 2 1

23

20

26

29

32

35

38

41

44

47

4

4

5

1

6

C002769-A

00:00 00:00 00:00

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 79

Page 82: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n NIGHT

This parameter is displayed if at least one circuit does notinclude a room sensor.

For circuits without a room sensor:

4 NIGHT :DEC. (Reduced): The reduced temperature is maintainedduring reduced periods. The circuit pump operates constantly.

4 NIGHT :STOP (Stop): Heating is shut down during reducedperiods. When installation antifreeze is active, the reducedtemperature is maintained during reduced periods.

For circuits with a room sensor:

4 When the room temperature is lower than the room sensor setpoint: The reduced temperature is maintained during reducedperiods. The circuit pump operates constantly.

4 When the room temperature is higher than the room sensor setpoint: Heating is shut down during reduced periods. Wheninstallation antifreeze is active, the reduced temperature ismaintained during reduced periods.

n Function 0-10 V

This function controls the boiler using an external system thatincludes a 0-10 V output connected to the 0-10 V input. This commandimposes a temperature or output instruction on the boiler. It will benecessary to ensure that the parameter BOILER MAX is higher thanCONS.MAX 0-10V.

1 Instruction set outlet temperature (°C)2 Power input signal (V) - DC3 0 V4 CONS.MIN 0-10V

5 CONS.MAX 0-10V

6 VMIN/OFF 0-10V

7 VMAX 0-10V

8 10 Vx Voltage at inputy Boiler temperature / Boiler output

If the input voltage is less than VMIN/OFF 0-10V, the boiler is off.The boiler temperature setting corresponds strictly to the 0-10 Vinput. The secondary boiler circuits continue to operate but have noimpact on the water temperature in the boiler. If using the 0-10 V inputand a secondary boiler circuit, the external regulator providing this0-10 V power supply must always request a temperature at leastequal to the needs of the secondary circuit.

M001679-A

5

1

4

3 6 2 7 8

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

80 06/09/2010 - 300024755-001-A

Page 83: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.7.4. Configuring the network

1. Access the "installer" level: Press key - for around 5 seconds.2. Select the menu #NETWORK.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

3. To set the following parameters:

"Installer" level - #NETWORK menu(1)

Parameter Adjustment range Description Factory setting Customersetting

CASCADE: ON / NO ON: System in cascade NO MASTER CONTROLLER (2) ON / NO Configure this control system as

master on the busON

SYSTEM NETWORK (3) Specific menu: Enlist generators orVMs in cascade mode (See followingchapter: "Connecting appliances incascade")

FUNCT (3) CLASSIC Operation in cascade: Successivetriggering of the various boilers in thecascade according to requirements

CLASSIC

PARALLEL Functioning in parallel cascade: If theoutside temperature is lower than thevalue PARALLEL.CASC, all of theboilers are started up at the same time

PARALLEL CASC. (4) -10 to 20 °C Outside temperature triggering allstages in parallel mode

10 °C

TEMP.P.GENE.CASC(4) 0 to 30 min Minimum duration of post-operation ofthe generator pump

0 mn

INTER STAGE TIMER (2) 1 to 30 min Time delay for starting up or shuttingdown generators.

4 mn

SLAVE NUMBER (5) 2 to 10 Set the network address of thesecondary generator

2

3WW PLC Specific menu (Not used) InOne SCENARIO Specific menu: Configure the InOne

scenarios to be managed by the SCUPCB (See following chapter:"Configuring the scenarios")

REMOVE DEVICE Specific menu: see below (1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed if CASCADE is set to YES(3) The parameter is displayed only if MASTER CONTROLER is set to YES(4) The parameter is only displayed if FUNCT is set to PARALLEL(5) The parameter is displayed only if MASTER CONTROLER is set to OFF

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 81

Page 84: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Connecting appliances in cascade

It is possible, in a cascade configuration, to enlist generators and/orVMs as slaves. Proceed as follows:

1. Set CASCADE to YES by pressing the rotary button and thenturning and pressing it again to confirm.

2. Select SYSTEM NETWORK and press the rotary button to go tothe specific menu.

3. To add a slave appliance to the network, select ADD SLAVE.

4. The screen displayed allows you to choose numbers for the slaveboilers to be added to the network. Numbers 2 to 10 are dedicatedto the generators and numbers 20 to 39 to the VM. Turn the rotarybutton to scroll through the numbers and press to confirm thenumber chosen. Press j to go back to the previous list.

5. To remove a slave appliance from the network, select ERASENETWORK.

6. The screen displayed allows you to choose the numbers of theslave boilers to be removed from the network. Turn the rotarybutton to scroll through the numbers and press to remove thenumber chosen. Press j to go back to the previous list.

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CASCADE

MASTER CONTROLER

SYSTESYSTEM NETWORK

MNETZFUNCT

INTER STAGE TIMER

ON

ON

TRADITIONAL

4'ÿ

C002409-B-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

NB.NETWORK ELEMENTS

ADD SLAVE

ERASE NETWORK

4

ÿ

C002410-B-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

SKLAVE ADDIEREN

GENE: 2, 5,

VM: 29,

4

ÿ

C002412-A-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

ERASE NETWORK

GENE: 2, 5,

VM: 29,

4

ÿ

C002413-A-04

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

82 06/09/2010 - 300024755-001-A

Page 85: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

7. Select NUMB.ELEMENTS.NETWORK. This screen summarisesthe elements in the network recognised by the system. Press jto go back to the previous list.

n Configuring the scenarios

It is possible to choose a scenario and allocate it to various IOBL unitsvia the carrier current. Proceed as follows:

1. In the menu #NETWORK, select InOne SCENARIO.

2. Choose a number to allocate to the scenario by turning the rotarybutton; up to 4 scenarios can be saved. To confirm, press therotary button.

3. Choose the desired scenario by turning the rotary button and thenconfirm.

Scenarios available DescriptionHOLIDAYS ON Holiday mode active (all circuits)HOLIDAYS OFF Holiday mode inactive (all circuits)OUT.AUX ON Aux outlet enabledOUT.AUX OFF Aux outlet disabledDHW DAY DHW in day modeDHW NIGHT DHW in night modeDEFAULT ON Default activeDEFAULT OFF No active defaultINPUT TEL.ON Telephone input activeINPUT TEL.OFF Telephone input not active

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

NB.NETWORK ELEMENTS

GENE: 2, 5,

VM: 29,

4

ÿ

C002411-B-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

INTER STAGE TIMER

3WW PLC

InOne SCENARIO

REMOVE DEVICE

4'

ÿ

C002414-B-04

1

1

2

2

rc

( t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

SCENARIO

"Please choose the scenario to define"

1

ÿ

C002415-A-04

1

1

2

2

rc

( t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

Configure the scenarioHOLIDAYS ON

ÿ

C002416-A-04

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 83

Page 86: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4. Enlist the various InOne units that have to abide by the scenarioand confirm by pressing the rotary button.

n Removing a device

To remove a device, proceed as follows:

1. In the menu #NETWORK, select REMOVE DEVICE.

2. Choose the device to be removed by turning the rotary button andpressing to confirm.

n Controlling the boiler from an IOBL Scenario Switch

It is possible to control the boiler from a scenario switch (the boiler isthen considered a slave boiler). Proceed as follows:

1. Remove the cover from the IOBL scenario switch to access theLEARN key.

1

1

2

2

rc

( t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

"Integrate the differents InOneactors. Press on the button to finish"

C002417-A-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

INTER STAGE TIMER

3WW PLC

InOne SCENARIO

REMOVE DEVICE

4'

ÿ

C002419-B-04

1

1

2

2

rc

( t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

"Select the InOne device to remove"

MASTER CONTROLER

ÿ

C002420-B-04

C002421-B

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

84 06/09/2010 - 300024755-001-A

Page 87: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

C002422-B-04

230V

230Vbar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

"An external devicetries to connect,do you want to authorize it?"

LEARN ? YES

2. Press the LEARN key and the control key used to pilot thescenario. A pairing signal is sent to the boiler by carrier current,which displays the following message on the control panel:"A device is trying to connect, do you want to allow this?"

3. Set the display to YES by turning the rotary button and pressingto confirm.

4. Choose the circuit used to run the scenario by turning the rotarybutton and pressing to confirm.

CAUTION

If one of the SCU PCBs is not correctly paired, thefollowing message appears:"NB not all of the SCUs are recognised".Start the pairing procedure again.

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

LEARN ?"An external devicetries to connect,do you want to authorize it?"

YES

C002423-A-04

YES

ÿ

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CHOICE THE CIRC. B

C002424-B-04

ÿ

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 85

Page 88: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5. Choose the desired scenario by turning the rotary button and thenconfirm.

Scenarios available DescriptionAUTO Heating according to the time programmeDAY Comfort modeNIGHT Reduced modeHOLIDAYS Holiday modeP1 Programme P1 chosenP2 Programme P2 chosenP3 Programme P3 chosenP4 Programme P4 chosen

6. Terminate pairing by pressing the LEARN key on the IOBLscenario switch.

n Erasing a scenario from the IOBL Scenario Switch

It is possible to remove a scenario using the IOBL scenario switch.Proceed as follows:

1. Press the LEARN key on the scenario switch, then the control keythat pilots the scenario to be erased. A message asking whetheryou wish to erase the scenario is displayed on the control panelinterface.

2. Set the display to YES by turning the rotary button and pressingto confirm.

3. Confirm removal by pressing the LEARN key on the IOBL scenarioswitch.

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

FUNCTION :

"Function of the scenario"

HOLIDAYS

C002425-A-04

ÿ

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

REMOVE?Scene reset

yes

C002426-A-04

ÿ

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CONFIRM:"Please close the procedure with LEARN on the scenario switch"

C002427-A-04

ÿ

5. Start-up - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

86 06/09/2010 - 300024755-001-A

Page 89: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.7.5. Return to the factory settings

To reset the appliance, proceed as follows:

1. Press key C, > and j simultaneously for 4 seconds. The menu#RESET is displayed.

2. To set the following parameters:

#RESET menu

Choice of generator Parameter DescriptionGENERATOR RESET TOTAL Performs a TOTAL RESET of all parameters

EXCEPT PROG. Performs a parameter RESET but retains the timer programmesPROG. Performs a RESET on the timer programmes but retains the parametersIOBL Resets the system's network connectionsSENSOR SCU Performs a RESET of the generator sensors connectedROOM SENSOR Performs a RESET of the room sensors connected

After reset (TOTAL RESET and RESET EXCEPT PROG.), thecontrol system goes back to the display of the language choice aftera few seconds.

1. Select the desired language by turning the rotary button.2. To confirm, press the rotary button.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

MODE

SUNDAY 11:45

C002296-B-04

4"

+ +

Français - Deutsch - English - Italiano - Espanol - Nederlands- Polski -

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb x c rg m

aLANGUE FRANCAIS

C003079-A

MCA 45 - 65 - 90 - 115 5. Start-up - DIEMATIC iSystem

06/09/2010 - 300024755-001-A 87

Page 90: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6 Start-up - IniControl

6.1 Control panel

6.1.1. Description of the keys

A Return button j, Escape G or Manual reset tB Heating temperature button d or [-]

C DHW temperature button r or [+]

D S [Enter] KeyE ) [Chimney-sweeping] keys

Press keys A and B simultaneously

F f [Menu] keysPress keys C and D simultaneously

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C002968-D

thj

A B

E F

C D

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

88 06/09/2010 - 300024755-001-A

Page 91: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6.1.2. Description of the display

n Key functions

G Back to the previous level without saving themodifications made

t Manual reset

d Central heating function:Access to the max. heating temperature parameter.

[-] To reduce a value

r Sanitary hot water function:Access to sanitary hot water temperature parameter.

[+] To increase a value

® Access the menu selected or confirm a value modification

n Operating modes

d State heating pump A

D Heating programme deactivated:The heating function is deactivated

r State DHW pump

m Manual mode

n Flame output level

e Low output level 0 - 25 %

r Average output level 25 - 50 %

t High output level 50 - 75 %

y Output level 75 - 100 %

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003042-B

thj

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003043-B

thj

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003044-B

thj

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003046-B

thj

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 89

Page 92: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n System pressure

bar Pressure indicator:The symbol is displayed next to the installation's pressurevalue. If no water pressure sensor is connected, -.-appears on the display

n Other information

" User menu:Parameters at user level can be changed

! Information menu:Reading the various current values

) Chimney-sweeping position:Forced full or part load for CO2 measurement

- Service menu:Parameters at installer level can be changed

K Display with the symbols:$ + K + Z (Maintenance message)

\ Hour counter menu:Readout of the operating hours, number of successfulstarts and hours on mains supply

a On/Off switch:After 5 lock-outs, the device must be switched off/on again

I Outside temperature sensor present

M The symbol is displayed when the boiler pump isoperating

a Fault:Boiler indicates a fault. This is signalled by a P or X codeand a flashing display

6.2 Check points before commissioning

6.2.1. Preparing the boiler for commissioning

WARNING

Do not put the boiler into operation if the supplied gas isnot in accordance with the approved gas types.

Preparatory procedure for boiler commissioning:

4 Check that the gas type supplied matches the data shown on theboiler's data plate.

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003047-C

thj

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003048-B

thj

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

90 06/09/2010 - 300024755-001-A

Page 93: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4 Check the gas circuit.4 Check the hydraulic circuit.4 Check the water pressure in the heating system.4 Check the electrical connections to the thermostat and the other

external controls.4 Check the other connections.4 Test the boiler at full load. Check the setting of the gas/air ratio

and, if necessary, correct it.4 Test the boiler at part load. Check the setting of the gas/air ratio

and, if necessary, correct it.4 Finalizing work.

6.2.2. Gas circuit

WARNING

Ensure that the boiler is switched off.

1. Open the main gas supply.2. Unscrew the two screws located under the front panel by a quarter

turn and remove the panel.3. Tilt the control box forwards by opening the holding clips located

at the sides.4. Check the gas supply pressure at the measurement point C on the

gas valve unit.

WARNING

¼ To ascertain the gas types permitted, see chapter:"Equipment categories", page 8

5. Check the tightness of the gas connections made after the gasvalve unit in the boiler.

6. Check the leak tightness of the gas inlet, including the gasvalves. The test pressure must not exceed 60 mbar.

7. Purge the gas supply pipe within the boiler by unscrewing themeasurement point on the gas block. Tighten the measurementpoint when the pipe has been sufficiently purged.

8. Check the tightness of the gas connections in the boiler.

6.2.3. Hydraulic circuit

4 Check the syphon — this must be completely filled with cleanwater.

4 Check that there are no leaks on the hydraulic connections.

6.2.4. Electrical connections

4 Check the electrical connections.

T003243-A

C C

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 91

Page 94: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6.3 Putting the appliance into operation

WARNING

If adapting to another gas type i.e. propane, the gas valvemust be adjusted before switching on the boiler.¼ See chapter: "Adapting to another gas type", page93

1. Tilt the control box upwards again and fasten it using the clipslocated at the sides.

2. Open the main gas supply.3. Open the gas valve on the boiler.4. Turn on the boiler using the on/off switch.5. Set the controls (thermostats, control system) so that they request

heat.6. The start-up cycle begins and cannot be interrupted. During the

start-up cycle, the display shows the following information:A short test where all segments of the display are visible.fK[xx : Software version

pK[xx : Parameter versionThe version numbers are displayed alternately.

7. A vent cycle of a duration of around 3 minutes is carried outautomatically.

If a DHW sensor is connected and the anti-legionellafunction is activated, the boiler starts to heat the water inthe DHW tank as soon as the vent programme has beencompleted.

By pressing the ® key for a short time, the current operating statusis shown on the display:

Heat demand d Heat demand stopped 1 : Fan ON 1 : Post-ventilation" : Boiler is igniting 5 : Burner stop

6 : Post-circulation of the pump3 : Heating System 0 : Standby

In addition to 0, in STAND-BY the display normally shows the waterpressure and the symbols d, 5tH and r.

Error during the start-up procedure:

4 No information is shown on the display:- Check the mains supply voltage- Check the main fuses- Check the fuses on the control panel:

(F1 = 6,3 AT, F2 = 2 AT)- Check the connection of the mains lead to the connector X1 in

the instrument box4 A fault is indicated on the display by the fault symbol a and a

flashing fault code.- The meaning of the error codes is given in the error table.- Press for 3 seconds on key J to restart the boiler.

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

92 06/09/2010 - 300024755-001-A

Page 95: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

If the economy setting (eco setting) is on, then, after centralheating operation, the boiler will not start to run for hot tapwater production.

6.4 Gas settings

6.4.1. Adapting to another gas type

WARNING

Only a qualified engineer may carry out the followingoperations.

The boiler is preset in the factory to operate on natural gas H (G20).

For operation on another group of gases, carry out the followingoperations.In case of functioning on propane:

1.Boiler type For conversion to propaneMCA 45 Rotate the adjusting screw A on the venturi 4¾ turns in a

clockwise directionMCA 65 Rotate the adjusting screw A on the venturi 6½ turns in a

clockwise directionMCA 90 Fit the gas restrictor in the gas blockMCA 115 First turn the setting screw A clockwise until it is closed, then:

Rotate the adjusting screw A on the gas block 3,5 - 4 turns inan anticlockwise direction

2. Regulate the fan speed as indicated in the table (if required). Thesetting can be modified using parameters p17, p18,

p19 and p20:

¼ See chapter: "Description of the parameters", page 1003. Set the air/gas ratio. For more detailed information on this subject,

see the following paragraphs:¼ "Setting the air/gas ratio (Full load)", page 93¼ "Setting the air/gas ratio (Part load)", page 94

6.4.2. Setting the air/gas ratio (Full load)

1. Unscrew the plug of the flue gas measurement point.2. Connect the flue gas analyser.

WARNING

Ensure that the opening around the sensor is completelysealed when taking measurements.

T003241-A

A A

T001581-A

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 93

Page 96: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3. Set the boiler to full load. Press keys A and B simultaneously. Thedisplay shows h3. The symbol ) appears.

4. Measure the percentage of O2 or CO2 in the flue gases.5. Compare the values measured with the checking values given in

the table (Front panel removed).

6. If necessary, adjust the gas/air ratio using the adjusting screw(A).

O2/CO2 control and setting values for gas H (G20) at full loadBoiler type Setting value Checking value

O 2 (%) CO 2 (%) O 2 (%) CO 2 (%)MCA 45 4,8 ± 0,2 9,0 ± 0,1 4,8 ± 0,5 9,0 ± 0,2MCA 65 4,8 ± 0,2 9,0 ± 0,1 4,8 ± 0,5 9,0 ± 0,2MCA 90 3,9 ± 0,2 9,5 ± 0,1 3,9 ± 0,5 9,5 ± 0,2MCA 115 4,7 ± 0,2 9,1 ± 0,1 4,7 ± 0,5 9,1 ± 0,2

O2/ CO2 control and setting values for propane (G31) at full loadBoiler type Setting value Checking value

O 2 (%) CO 2 (%) O 2 (%) CO 2 (%)MCA 45 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 65 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 90 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 115 4,9 ± 0,2 10,5 ± 0,1 4,9 ± 0,5 10,5 ± 0,2

6.4.3. Setting the air/gas ratio (Part load)

1. Unscrew the plug of the flue gas measurement point.2. Connect the flue gas analyser.

WARNING

Ensure that the opening around the sensor is completelysealed when taking measurements.

3. Set the boiler to part load. Press the [-] key several times untill2 is displayed on the screen.

4. Measure the percentage of O2 or CO2 in the flue gases.5. Compare the values measured with the checking values given in

the table (Front panel removed).

)

Ld

y

1

2

bar

C003056-A

hj

T003241-A

A A

T001581-A

)

Ld

y

1

2

bar

C003057-B

hj

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

94 06/09/2010 - 300024755-001-A

Page 97: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6. If necessary, adjust the gas/air ratio using the adjusting screw(B).

O2/CO2 control and setting values for gas H (G20) at low speedBoiler type Setting value Checking value

O 2 (%) CO 2 (%) O 2 (%) CO 2 (%)MCA 45 4,8 ± 0,2 9,0 ± 0,1 4,8 ± 0,5 9,0 ± 0,2MCA 65 4,8 ± 0,2 9,0 ± 0,1 4,8 ± 0,5 9,0 ± 0,2MCA 90 3,9 ± 0,2 9,5 ± 0,1 3,9 ± 0,5 9,5 ± 0,2MCA 115 4,3 ± 0,2 9,3 ± 0,1 4,3 ± 0,5 9,3 ± 0,2

O2/CO2 control and setting values for propane (G31) at low speedBoiler type Setting value Checking value

O 2 (%) CO 2 (%) O 2 (%) CO 2 (%)MCA 45 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 65 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 90 4,6 ± 0,2 10,7 ± 0,1 4,6 ± 0,5 10,7 ± 0,2MCA 115 4,9 ± 0,2 10,5 ± 0,1 4,9 ± 0,5 10,5 ± 0,2

6.5 Checks and adjustments after commissioning

6.5.1. Setting the heating curve

1. Press the two keys f simultaneously and then key [+] until thesymbol a flashes on the menu bar.

2. Select the installers menu using the key S. c0de appearson the display.

3. Use keys [-] or [+] to input the installer code 0012.4. Press key [+] until the symbol - is displayed.5. Press the [+] key until 5[3 is displayed

T003242-A

B B

B

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 95

Page 98: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Heating curve without BCT

A Maximum temperature of the circuit P1

Z Water temperature in the circuit for an outsidetemperature of 0°C

E DAY set point on the circuit S1

R Outside temperature for which the maximum watertemperature in the circuit is reached

T Value of the heating curveThis value corresponds to the parameter S3

6.5.2. Finalizing work

1. Remove the measuring equipment.2. Put the flue gas sampling plug back in place.3. Refit the front panel. Tighten the two screws by a quarter turn.4. Push key j to return the boiler to normal operating mode.5. Raise the temperature in the heating system to approximately

70°C.6. Shut down the boiler.7. After about 10 minutes, vent the air in the heating system.8. Checking the hydraulic pressure. If necessary, top up the water

level in the heating system (recommended hydraulic pressurebetween 1,5 and 2 bar).

9. Tick the gas category used on the data plate.10.Explain the operation of the installation, the boiler and the

regulator to the users.11.Inform the user of the periodicity of maintenance work to be carried

out. Input the service date and the contact details of the installer.12.Give all the instruction manuals to the user.

Commissioning of the boiler is now complete.

The various boiler parameters are preset in the factory.These factory settings are suitable for the most commonheating systems. For other systems and situations, theparameters can be modified.

20 0 -16

50

75

1.5

C002319-B

1

2

3

4

5

T001522-A

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

96 06/09/2010 - 300024755-001-A

Page 99: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6.6 Reading out measured values

6.6.1. Reading out measured values

The following current values can be read off the information menuQ:

4 5t = State.4 5v = Sub-status.4 t1 = Flow temperature (°C).4 t" = Return temperature (°C).4 t3 = Calorifier temperature (°C).4 t4 = Outside temperature (°C).4 t5 = Solar boiler temperature (°C).4 5p = Internal set point (°C).4 fl = Ionisation current (µA).4 Mf = Fan speed in rpm.4 pr = Water pressure (bar).4 p; = Supplied relative heat output (%).

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 97

Page 100: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

The current values can be read as follows:

1. Press the two f keys simultaneously. The symbol Q flashes.2. Confirm using key S. 5t is displayed, alternating with the

current status 3 (for example).3. Press the [+] key. 5v is displayed, alternating with the current

sub-status 30 (for example).4. Press the [+] key. t1 is displayed, alternating with the current

flow temperature 60°C (for example).5. Press the [+] key successively to scroll down the various

parameters. t", t3, t4, t5 .6. Press the [+] key. 5p is displayed, alternating with the internal

set point 88°C (for example).7. Press the [+] key. fl is displayed, alternating with the current

ionisation current 70 µA (for example).8. Press the [+] key. Mf is displayed, alternating with the current

fan rotation speed 3000 rpm (for example).9. Press the [+] key. pr is displayed, alternating with the current

water pressure #0 bar (for example). If no water pressure sensoris connected, [-.-] appears on the display.

10.Press the [+] key. p; is displayed, alternating with the currentmodulation percentage 78 % (for example).

11.Press the [+] key. The readout cycle starts again with 5t.12.Press 2 times on key j to return to the current operating mode.

)

rd

bar

C003049-A

thj

hj

4x

2x

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

98 06/09/2010 - 300024755-001-A

Page 101: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6.6.2. Readout from the hour counter andpercentage of successful starts

1. Press the two keys f simultaneously and then key [+] until thesymbol \ flashes on the menu bar.

2. Press the S key. hr and the number of hours of boileroperation 3600 (for example) are displayed alternately.

3. Press the [+] key. The display shows d. hr is displayed,alternating with the number of operating hours in central heatingoperation 560 (for example).

4. Press the [+] key. The display shows r. hr is displayed,alternating with the number of operating hours used for heatingtap water 320 (for example).

5. Press the [+] key. The display shows @. 5Z is displayed,alternating with the percentage of successful starts 92 % (forexample).

6. Press 2 times on key j to return to the current operating mode.

6.6.3. Status and sub-status

The information menu Q gives the following status and sub-statusnumbers:

State 5t Sub-status 5v0 Rest 0 Rest1 Boiler start (Heat demand) 1 Anti-hunting

2 Control three-way valve3 Start pump4 Wait for the correct temperatures for burner start

2 Burner start 10 Open flue gas damper/external gas valve11 Increase fan speed13 Pre-ventilation14 Wait for release signal15 Burner on17 Pre-ignition18 Main ignition19 Flame detection"0 Intermediate ventilation

3 / 4 Burning for central heating operation 30 Temperature control31 Limited temperature control (ΔT Safety)32 Output control33 Increase protection level 1 (Modulate down)34 Increase protection level 2 (part load)35 Increase protection level 3 (Blockage)36 Modulate up for flame control37 Temperature Stabilisation time38 Cold start

C003058-A

r

hj

d

y

5x

2x

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 99

Page 102: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

State 5t Sub-status 5v5 Burner stop 40 Burner off

41 Post ventilation42 Close flue gas damper/external gas valve43 Recirculation protection44 Stop fan

6 Boiler stop (End of heat demand) 60 Pump post circulation61 Pump off62 Control three-way valve63 Start anti-hunting

8 Stop 0 Wait for burner start1 Anti-hunting

9 Lock-out xx Shutdown code xx17 Bleed 0 Rest

2 Control three-way valve3 Start pump61 Pump off62 Control three-way valve

6.7 Changing the settings

The boiler control panel is set for the most common heatingsystems. With these settings, practically all heating systems operatecorrectly. The user or installer can optimise the parameters accordingto own preferences.

6.7.1. Description of the parameters

Parameter Description Adjustment range Factory settingMCA45 65 90 115

p1 Maximum outlet temperature 20 to 90 °C 80 80 80 80p2 Domestic hot water temperature 40 to 65 °C 60 60 60 60p3 Heating / DHW mode Do not modify 1 1 1 1p4 Mode ECO Do not modify 2 2 2 2p5 Anticipation resistance Do not modify 0 0 0 0p6 Display screen Do not modify 2 2 2 2p7 Post-circulation of the boiler pump

connected to the PCU1 to 98 minutes99 minutes = continuous

3 3 3 3

p8 Brightness of display lighting Do not modify 1 1 1 1p17 Maximum fan speed (Heating) Natural gas H (G20)(1)

(x100 rpm)54 58 62 70

Propane (G31)(x100 rpm)

54 58 60 67

p18 Maximum fan speed (DHW) Natural gas H (G20)(1)

(x100 rpm)54 58 62 70

Propane (G31)(x100 rpm)

54 58 60 67

(1) Do not modify these factory settings unless absolutely necessary.

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

100 06/09/2010 - 300024755-001-A

Page 103: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Parameter Description Adjustment range Factory settingMCA45 65 90 115

p19 Minimum fan speed (Heating+DHW) Natural gas H (G20)(1)

(x100 rpm)16 16 15 18

Propane (G31)(x100 rpm)

16 16 22 25

p20 Minimum fan speed (offset) Do not modify 0 0 50 0p21 Start speed Do not modify

(x100 rpm)25 25 25 25

p22 Minimum water pressure 0 - 3 bar(x 0,1 bar) 8 8 8 8p23 Maximum flow temperature of system 0 to 90 °C 90 90 90 90p24 Anti-hunting differential for central heating

operation-15 to 15 °C 3 3 3 3

p25 Heat curve set point(Maximum outside temperature)

Do not modify 20 20 20 20

p26 Heat curve set point(Flow temperature)

Do not modify 20 20 20 20

p27 Heat curve set point(Minimum outside temperature)

Do not modify -15 -15 -15 -15

p28 Minimum pump speed for central heatingoperation Setting the pump speed

2 - 10 (x 10 % ) 4 4 4 4

p29 Maximum pump speed for central heatingoperation Setting the pump speed

2 - 10 (x 10 % ) 10 10 10 10

p30 Antifreeze temperature Do not modify -10 -10 -10 -10p31 Legionella protection Do not modify 1 1 1 1p32 Set point increase for calorifier Do not modify 20 20 20 20p33 DHW cut-in temperature DHW sensor Do not modify 5 5 5 5p34 Control of three-way valve Do not modify 0 0 0 0p35 Boiler type 0 = Heating only

1 = Open vented0 0 0 0

p36 Shutdown input function 0 = Heating activated1 = Shutdown without frost-protection2 = Shutdown with frost protection3 = Lock-out with frost protection (Pumponly)

1 1 1 1

p37 Release function Do not modify 1 1 1 1p38 Release waiting time 0 to 255 seconds 0 0 0 0p39 Flue gas flap switching time 0 to 255 seconds 0 0 0 0p40 Fault relay function (Optional) 0 = Operation signal

1 = Alarm signal1 1 1 1

p41 GpS connected (Optional) 0 = Not connected1 = Connected

0 0 0 0

p42 HRU connected (Optional) 0 = Not connected1 = Connected

0 0 0 0

p43 Neutral inversion detection L/N 0 = Stop1 = Start

0 0 0 0

p44 Maintenance message Do not modify 1 1 1 1p45 Service operating hours Do not modify 175 175 175 175p46 Service burning hours Do not modify 30 30 30 30501 Desired room temperature 5 to 30 °C 20 20 20 20502 Shutdown time delay on heating pump A 0 to 15 minutes 4 4 4 4503 Heating curve of the circuit A 0 to 40 (x0.1) 15 15 15 15(1) Do not modify these factory settings unless absolutely necessary.

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 101

Page 104: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Parameter Description Adjustment range Factory settingMCA45 65 90 115

504 Anti-freezing protection temperature -8 to 10 °C 3 3 3 3505 Charging priority 0 = Interruption of heating during domestic hot

water production1 = Not used2 = Heating and domestic hot waterproduction in parallel if the hydraulicconnection allows

0 0 0 0

506 Time delay on the DHW pump 2 to 15 minutes 2 2 2 2507 Primary DHW temperature 50 to 90 °C 80 80 80 80508 Antilegionellosis 0 = Anti-legionella function not activated

1 = The tank is overheated every day from 4o'clock to 5 o'clock2 = The tank is overheated every Saturdayfrom 4 o'clock to 5 o'clock

0 0 0 0

509 Activating the control at 0-10 V 0 = OFF1 = Temperature2 = Output

0 0 0 0

510 Voltage corresponding to the instructionset minimum

0 to 10 V (steps of 0.1 V) 5 5 5 5

511 Voltage corresponding to the instructionset maximum

0 to 10 V (steps of 0.1 V) 100 100 100 100

512 Instruction minimum set temperature 0 to 100 °C or 0 to 100 % 5 5 5 5513 Maximum set temperature 0 to 100 °C or 0 to 100 % 100 100 100 100514 Cascade 0 = The boiler is not assembled in cascade

1 = System in cascade0 0 0 0

515 Address of the secondary boilers(cascade)

2 to 10 2 2 2 2

516 Inspection Do not modify 0 0 0 0517 Activation of the IOBL function 0 = Deactivation

1 = Activation1 1 1 1

518 Activation of the TAS function 0 = Deactivation1 = Activation

1 1 1 1

Zd Detection of connected SCUs 0 = No detection1 = Detection

0 0 0 0

df and dV Factory setting To return to the factory settings or if replacingthe PCU PCB, enter values dF and dU fromthe nameplate in parameters df and dV

X X X XY Y Y Y

rE Total reset Performs a TOTAL RESET of all SCUparameters

(1) Do not modify these factory settings unless absolutely necessary.

0-10 V function:This function controls the boiler using an external system thatincludes a 0-10 V output connected to the 0-10 V input. This commandimposes a temperature or output instruction on the boiler. It will benecessary to ensure that the parameter BOILER MAX is higher thanCONS.MAX 0-10V.

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

102 06/09/2010 - 300024755-001-A

Page 105: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

1 Instruction set outlet temperature (°C)2 Power input signal (V) - DC3 0 V4 8BC5 8BD6 8B;7 8BB8 10 Vx Voltage at inputy Boiler temperature / Boiler output

If the input voltage is less than VMIN/OFF 0-10V, the boiler is off.The boiler temperature setting corresponds strictly to the 0-10 Vinput. The secondary boiler circuits continue to operate but have noimpact on the water temperature in the boiler. If using the 0-10 V inputand a secondary boiler circuit, the external regulator providing this0-10 V power supply must always request a temperature at leastequal to the needs of the secondary circuit.

6.7.2. Modification of the installer-levelparameters

Parameters p17 to df must only be modified by a qualifiedprofessional. To prevent unwanted settings, some parameter settingscan only be changed after the special access code 0012 isentered.

CAUTION

Modification of the factory settings may be detrimental tothe functioning of the boiler.

M001679-A

5

1

4

3 6 2 7 8

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 103

Page 106: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

1. Press the two keys f simultaneously and then key [+] until thesymbol - flashes on the menu bar.

2. Select the fitter menu using the ® key. c0de appears on thedisplay.

3. Use keys [-] or [+] to input the installer code 0012.4. Confirm using key S. p[1 is displayed with 1 flashing.5. Press the S key a second time. The value 75°C appears and

flashes (for example).6. Change the value by pressing the [-] or [+] key. In this example

using key [-] to 60°C.7. Confirm the value with the S key: p[1 is displayed with 1

flashing.8. If necessary, set other parameters by selecting them using the

[-] or [+] keys.9. Press 2 times on key j to return to the current operating mode.

The boiler also returns to operating status if no keys arepressed for 3 minutes.

6.7.3. Setting the maximum heat input for centralheating operation

The speed can be changed using parameter p17. To do this,proceed as follows:

1. Press the two keys f simultaneously and then key [+] until thesymbol - flashes on the menu bar.

2. Select the installers menu using the key S. c0de appearson the display.

3. Use keys [-] or [+] to input the installer code 0012.4. Confirm using key S. p[1 is displayed with 1 flashing.5. Press the [+] key to go to parameter p[17.6. Confirm using key S.7. Press the [+] key to increase the speed from 46 to, for example,

50 (see the graphs for the associated heat output).8. Confirm the value with the S key.9. Press 2 times on key j to return to the current operating mode.

C003059-A

hj

-3x

2x

C003060-A

3x

...x

...x

2x

-

hj

6. Start-up - IniControl MCA 45 - 65 - 90 - 115

104 06/09/2010 - 300024755-001-A

Page 107: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6.7.4. Return to the factory settings "ResetParam"

1. Press the two keys f simultaneously and then key [+] until thesymbol - flashes on the menu bar.

2. Select the installers menu using the key S. c0de appearson the display.

3. Use keys [-] or [+] to input the installer code 0012.4. Confirm using key S. p[1 is displayed with 1 flashing.5. Press the [+] key several times. p[df is displayed with df

flashing.6. Press the S key. df[x is displayed with x flashing. This is

the current value of X for dF. Check this against the value of X onthe type plate.

7. Enter the value of X shown on the type plate using the [-] or [+]key.

8. Confirm the value with the S key, df[y is displayed with yflashing. This is the current value of Y for dU. Check this againstthe value of Y on the type plate.

9. Enter the value of Y shown on the type plate using the [-] or [+]key.

10.Confirm the value with the j key. The factory settings are reset.11.The display returns to the current operating mode.

6.7.5. Carrying out an auto-detect

After removing a control PCB, an auto-detect must be carried out. Todo this, proceed as follows:

1. Press the two keys f simultaneously and then key [+] until thesymbol - flashes on the menu bar.

2. Select the installers menu using the key S. c0de appearson the display.

3. Use keys [-] or [+] to input the installer code 0012.4. Confirm using key S. p[1 is displayed with 1 flashing.5. Press the [+] key several times. p[Zd is displayed with Zd

flashing.6. Confirm using key j. Auto-detect is carried out.7. The display returns to the current operating mode.

C003061-A

3x

...x

-

C003062-A

3x

...x

-

MCA 45 - 65 - 90 - 115 6. Start-up - IniControl

06/09/2010 - 300024755-001-A 105

Page 108: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

7 Switching off the appliance

7.1 Installation shutdown

CAUTION

Do not switch off the boiler. If the central heating systemis not used for a long period, we recommend activating theHOLIDAYS mode.

7.2 Frost protection

When the heating water temperature in the boiler falls by too much,the integrated protection system in the boiler starts up. This protectionfunctions as follows:

4 If the water temperature is lower than 7°C, the heating pump startsup.

4 If the water temperature is lower than 4°C, the boiler starts up.4 If the water temperature is higher than 10°C, the boiler shuts down

and the heating pump continues to run for a short time.

CAUTION

4 The anitfreeze protection does not function if theboiler is switched off.

4 The integrated protection system only protects theboiler, not the installation. To protect the installation,set the appliance to HOLIDAYS mode.

With the IniControl control panel, the HOLIDAYS mode isonly available if a room sensor is connected to the boiler.

The HOLIDAYS mode protects:

4 The installation if the outside temperature is lower than 3°C(factory setting).

4 The room temperature if a remote control is connected and theroom temperature is lower than 6 °C (factory setting).

4 The domestic hot water tank if the tank temperature is lowerthan 4 °C (the water is reheated to 10 °C).

To configure the holidays mode: ¼ Refer to the user instructions.

7. Switching off the appliance MCA 45 - 65 - 90 - 115

106 06/09/2010 - 300024755-001-A

Page 109: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8 Checking and maintenance

8.1 General instructions

WARNING

4 Maintenance operations must be done by a qualifiedengineer.

4 An annual inspection is compulsory.4 Only original spare parts must be used.

4 Have the flues swept at least once a year or more, depending onthe regulations in force in your country.¼ See chapter: "Chimney sweep instructions", page 107

4 Carry out the inspection and standard maintenance operationsonce a year.¼ See chapter: "Standard inspection and maintenanceoperations", page 110

4 Carry out specific maintenance operations if necessary.¼ See chapter: "Specific maintenance operations", page115

8.2 Chimney sweep instructions

CAUTION

Have the flues swept at least once a year or more,depending on the regulations in force in your country. Onlya qualified engineer may carry out the followingoperations.

8.2.1. Control panel DIEMATIC iSystem

1. Press the - key.2. Check the combustion each time the flues are swept.¼ See chapter: "Setting the air/gas ratio (Full load)", page62 + "Setting the air/gas ratio (Part load)", page 64

3. To go back to the main display, press key j2 times.

MCA 45 - 65 - 90 - 115 8. Checking and maintenance

06/09/2010 - 300024755-001-A 107

Page 110: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

DIEMATIC iSystem - EMISSION MEASUREMENTS menu

Generator Function available Description Values displayedGenerator name OFF normal operation BOILER TEMP.

CURRENTWIND SPEEDBACK TEMP

°CµArpm°C

PMIN Operating at minimum output BOILER TEMP.CURRENTWIND SPEEDBACK TEMP

°CµArpm°C

PMAX Operating at maximum output BOILER TEMP.CURRENTWIND SPEEDBACK TEMP

°CµArpm°C

8.2.2. Control panel IniControl

1. Press keys j and d simultaneously.2. Check the combustion each time the flues are swept.¼ See chapter: "Setting the air/gas ratio (Full load)", page93 + "Setting the air/gas ratio (Part load)", page 94

3. To go back to the normal display, press button j.

IniControl - EMISSION MEASUREMENTS menu

Function available Description Values displayed

X< Operating at minimum output System pressure bar

U< Operating at maximum output System pressure bar

8.3 Customising maintenance

Maintenance customisation is only possible with theDIEMATIC iSystem control panel.

8. Checking and maintenance MCA 45 - 65 - 90 - 115

108 06/09/2010 - 300024755-001-A

Page 111: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8.3.1. Maintenance message

The boiler incorporates a function that can be used to display amaintenance message. To set the parameters for this function,proceed as follows:

1. Access the "After Sales" level: Hold key - down until#PARAMETERS is displayed.

2. Select the menu #REVISION.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

3. To set the following parameters:

"After Sales" level - #REVISION menu

Parameter Adjustment range DescriptionTYPE NO Factory setting

No message indicating that maintenance is necessaryMANU Recommended setting

Signals that maintenance is necessary on the date selected. Set the date using theparameters below.

AUTO a Not applicable. Do not select this setting.REVISION HOUR(1) 0 to 23 Time at which the REVISION display appears

REV. YEAR(1) 2008 to 2099 Year in which the REVISION display appears

REVIS. MONTH(1) 1 to 12 Month in which the REVISION display appears

REVISION DATE(1) 1 to 31 Day on which the REVISION display appears(1) The parameter is only displayed if MANU is configured.

n Clearing the maintenance message

After carrying out the maintenance operations, modify the date in the#REVISION menu to clear the message.

n In the event of maintenance before the maintenancemessage is displayed

After carrying out early maintenance operations, it is necessary to seta new date in the #REVISION menu.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

MCA 45 - 65 - 90 - 115 8. Checking and maintenance

06/09/2010 - 300024755-001-A 109

Page 112: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8.3.2. Installer's contact details

To call up the installer's telephone number when maintenance isnecessary, proceed as follows:

1. Access the "After Sales" level: Hold key - down until#PARAMETERS is displayed.

2. Select the menu #SUPPORT.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

3. To set the following parameters:

"After Sales" level - #SUPPORT menu

Parameter DescriptionNAME Input the installer's nameTELEPHONE NUM. Input the installer's telephone number

When the message, REVISION, is displayed, press ? to display theinstaller's telephone number.

8.4 Standard inspection and maintenance operations

CAUTION

During inspection and maintenance operations, alwaysreplace all gaskets on the parts removed.

8.4.1. Checking the hydraulic pressure

The hydraulic pressure must reach a minimum of 0,8 bar. .

If the hydraulic pressure is lower than 0.8 bar:

4 Control panel DIEMATIC iSystem: The symbol bar flashes.4 Control panel IniControl: The pressure value is displayed on the

screen.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP. : 68°

PCU COM.FAIL D27

C002302-D-04

8. Checking and maintenance MCA 45 - 65 - 90 - 115

110 06/09/2010 - 300024755-001-A

Page 113: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

If necessary, top up the water level in the heating system(recommended hydraulic pressure between 1,5 and 2 bar).

8.4.2. Checking the ionisation current

Check the ionisation current at full load and low load. The value isstable after 1 minute. If the value is less than 4 µA, clean or replacethe ignition electrode.

4 Control panel DIEMATIC iSystem:The ionisation current is displayed in the menu #MEASURES.¼ See chapter: "Reading out measured values", page 72

4 Control panel IniControl:¼ See chapter: "Reading out measured values", page 97

8.4.3. Checking the tightness of the combustedgases evacuation and air inlet connections

Check the tightness of the connection for the evacuation ofcombustion gases and the air inlet.

8.4.4. Checking combustion

n Control panel DIEMATIC iSystem

The check on combustion is done by measuring the percentage ofO2/CO2 in the flue gas discharge flue. To do this, proceed as follows:

1. Unscrew the plug of the flue gas measurement point.2. Connect the flue gas analyser.

CAUTION

Ensure that the opening around the sensor is completelysealed when taking measurements.

3. Set the boiler to full load.¼ See chapter: "Setting the air/gas ratio (Full load)", page62The boiler is now operating at full load. Measure the percentageof CO2 and compare this value with the checking values given.

T001580-A

T001581-A

MCA 45 - 65 - 90 - 115 8. Checking and maintenance

06/09/2010 - 300024755-001-A 111

Page 114: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4. Set the boiler to part load.¼ See chapter: "Setting the air/gas ratio (Part load)", page64.The boiler is now operating on part load. Measure the percentageof CO2 and compare this value with the checking values given.

n Control panel IniControl

The check on combustion is done by measuring the percentage ofO2/CO2 in the flue gas discharge flue. To do this, proceed as follows:

1. Unscrew the plug of the flue gas measurement point.2. Connect the flue gas analyser.

CAUTION

Ensure that the opening around the sensor is completelysealed when taking measurements.

3. Set the boiler to full load.¼ See chapter: "Setting the air/gas ratio (Full load)", page93The boiler is now operating at full load. Measure the percentageof CO2 and compare this value with the checking values given.

4. Set the boiler to part load.¼ See chapter: "Setting the air/gas ratio (Part load)", page94.The boiler is now operating on part load. Measure the percentageof CO2 and compare this value with the checking values given.

8.4.5. Checking the automatic air vent

1. Switch off the boiler electrical power supply.2. Close the gas valve on the boiler.3. Close the main gas inlet valve.4. Unscrew the two screws located under the front panel by a quarter

turn and remove the panel.

T001581-A

T001514-A

2

1

90º

8. Checking and maintenance MCA 45 - 65 - 90 - 115

112 06/09/2010 - 300024755-001-A

Page 115: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5. Tilt the control box forwards by opening the holding clips locatedat the sides.

6. Check whether there is any water in the small hose on theautomatic air vent.

7. If any leaks are detected, replace the air vent.

8.4.6. Checking the siphon

1. Remove the siphon and clean it.2. Fill the siphon with water.3. Put the siphon back in place.

T001991-A

2

1 1

T001582-A

MCA 45 - 65 - 90 - 115 8. Checking and maintenance

06/09/2010 - 300024755-001-A 113

Page 116: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8.4.7. Checking the burner and cleaning the heatexchanger

CAUTION

During inspection and maintenance operations, alwaysreplace all gaskets on the parts removed.

1. Remove the air inlet flue on the venturi.2. Loosen the union on the gas block.3. Remove the plugs from the fan.4. Remove the plugs from the gas block.5. Remove the ignition electrode plug from the ignition transformer.6. Remove the front plate from the heat exchanger7. Carefully lift the front plate including the burner and fan from the

heat exchanger.8. Use a vacuum cleaner fitted with a special endpiece (accessory)

to clean the top part of the heat exchanger (combustion chamber).9. Thoroughly clean with the vacuum cleaner again without the top

cleaning brush on the endpiece.10.Check (using a mirror, for example) whether any dust can still be

seen. If so, hoover it up.11.Clean the lowermost part of the heat exchanger with the special

cleaning knife (accessory).12.The burner does not require any maintenance, it is self-cleaning.

If necessary, clean the cylindrical burner using compressed airCheck that there are no cracks and/or other tears on the surfaceof the dismantled burner. If this is not the case, replace the burner.

13.Checking the ignition electrode / ionization sensor.14.To re-assemble, perform the above actions in reverse order.

CAUTION

4 Remember to reconnect the connector to the fan.4 Check that the gasket is correctly positioned between

the mixing elbow and the heat exchanger.(Completely flat in the appropriate groove means it isleak proof).

15.Open the gas inlet valves and switch on the mains supply to theboiler.

T002871-B

1

3

4

11

8 9

2

5

6

7

10

12

13

8. Checking and maintenance MCA 45 - 65 - 90 - 115

114 06/09/2010 - 300024755-001-A

Page 117: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8.5 Specific maintenance operations

If the standard inspection and maintenance operations have revealedthe necessity to carry out additional maintenance work, proceed asfollows, depending on the nature of the work:

8.5.1. Inspection of the ignition electrode

1. Remove the ignition electrode plug from the ignition transformer.

The ignition cable is fixed to the ignition electrode andtherefore may not be removed.

2. Unscrew the 2 screws. Remove the unit.3. Wipe off all traces of deposits using an abrasive cloth.4. Check the ignition electrode for wear. Replace if necessary.5. Check the gasket.6. Refit all parts, replacing those that are damaged.

T002872-A

4

1

2

3

MCA 45 - 65 - 90 - 115 8. Checking and maintenance

06/09/2010 - 300024755-001-A 115

Page 118: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8.5.2. Replacing the non-return valve

Replace the nonreturn valve when faulty or when the maintenance kitcontains one. To do this, proceed as follows:

1. Remove the air inlet flue on the venturi.2. Loosen the union on the gas block.3. Remove the plugs from the fan.4. Remove the ignition electrode plug from the ignition transformer.5. Dismantle the fan.6. Completely remove the fan/mixing elbow unit.7. Replace the nonreturn valve located between the mixing elbow

and the fan.8. To re-assemble, perform the above actions in reverse order.

T002873-C

1

3

4

2x

57

6

8

2

8. Checking and maintenance MCA 45 - 65 - 90 - 115

116 06/09/2010 - 300024755-001-A

Page 119: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8.5.3. Assembling the boiler

1. Follow the procedure in reverse to re-assemble all of thecomponents.

CAUTION

During inspection and maintenance operations, alwaysreplace all gaskets on the parts removed.

2. Fill the siphon with water.3. Put the siphon back in place.4. Carefully open the main water valve, fill the installation, vent it and,

if need be, top it up with water.5. Check the seals on the gas and water connections.6. Switch the boiler back on.

T002874-C

MCA 45 - 65 - 90 - 115 8. Checking and maintenance

06/09/2010 - 300024755-001-A 117

Page 120: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

9 Troubleshooting

9.1 Anti-hunting

This display only concerns boilers with the DIEMATICiSystem control panel.

When the boiler is in "Anti-short-cycle" operating mode, the symbol"?" flashes. This is a normal operating mode. When the restarttemperature is reached, operation will be guaranteed.

9.2 Messages (Code type Bxx or Mxx)

In the event of failure, the control panel displays a message and acorresponding code.

1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.

2. Switch the boiler off and switch back on.The boiler starts up again automatically when the reason for theblocking has been removed.

3. If the code is displayed again, correct the problem by following theinstructions in the table below:

Depending on the control panel, the message display isdifferent:

4 Control panel DIEMATIC iSystem: The code and themessage are displayed.

4 Control panel IniControl: Only the code is displayed.

9. Troubleshooting MCA 45 - 65 - 90 - 115

118 06/09/2010 - 300024755-001-A

Page 121: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Messages Description Checking / solutionB00 BL.PSU ERROR The PSU PCB is incorrectly

configuredParameter error on the PSU PCB

4 DIEMATIC iSystem: Set the type of generator again in themenu #CONFIGURATION (Refer to the original rating plate)

4 IniControl: Revert to the factory settings: ¼ Seechapter "Return to the factory settings "Reset Param"",page 105

B01 BL.MAX BOILER Maximum flow temperatureexceeded

The water flow in the installation is insufficient

4 Check the circulation (direction, pump, valves)B02 BL.HEATING

SPEEDThe increase in flowtemperature has exceeded itsmaximum limit

The water flow in the installation is insufficient

4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchangerSensor error

4 Check that the sensors are operating correctly4 Check whether the boiler sensor has been correctly fitted

B07 BL.DT OUTLRET.

Maximum difference betweenthe flow and return temperatureexceeded

The water flow in the installation is insufficient

4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchangerSensor error

4 Check that the sensors are operating correctly4 Check whether the boiler sensor has been correctly fitted

B08 BL.RL OPEN The RL inlet on the PCU PCBterminal block is open

Parameter error

4 DIEMATIC iSystem: Set the type of generator again in themenu #CONFIGURATION (Refer to the original rating plate)

4 IniControl: Revert to the factory settings: ¼ Seechapter "Return to the factory settings "Reset Param"",page 105

Bad connection

4 Check the wiringB09 BL.INV. L/N 4 DIEMATIC iSystem: Set the type of generator again in the menu #CONFIGURATION (Refer to

the original rating plate)

4 IniControl: Revert to the factory settings: ¼ See chapter "Return to the factory settings"Reset Param"", page 105

B10B11

BL.BL INPUTOPEN

The BL inlet on the PCU PCBterminal block is open

The contact connected to the BL inlet is open

4 Check the contact on the BL inletParameter error

4 Check the parameter IN.BLBad connection

4 Check the wiringB13 BL. PCU COM Communication error with the

SCU PCBBad connection

4 Check the wiringSCU PCB not installed in the boiler

4 Install an SCU PCBB14 BL.WATER MIS. The water pressure is lower than

0,8 barNot enough water in the circuit

4 Top up the installation with water

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 119

Page 122: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Messages Description Checking / solutionB15 BL.GAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU PCB

4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check whether the gas pressure control system has been

correctly fitted4 Replace the gas pressure control system if need be

B16 BL.BAD SU The SU PCB is not recognised Wrong SU PCB for this boiler

4 Replace the SU PCBB17 BL.PCU ERROR The parameters saved on the

PCU PCB are impairedParameter error on the PCU PCB

4 Replace the PCU PCBB18 BL.BAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler

4 Replace the PSU PCBB19 BL.NO CONFIG The boiler has not been

configuredThe PSU PCB has been changed

4 DIEMATIC iSystem: Set the type of generator again in themenu #CONFIGURATION (Refer to the original rating plate)

4 IniControl: Revert to the factory settings: ¼ Seechapter "Return to the factory settings "Reset Param"",page 105

B21 BL. COM SU Communication error betweenthe PCU and SU PCBs

Bad connection

4 Check that the SU PCB has been correctly put in place on thePCU PCB

4 Replace the SU PCBB22 BL.FLAME LOS No flame during operation No ionization current

4 Purge the gas supply to remove air4 Check that the gas valve is fully opened4 Check the supply pressure4 Check the operation and setting of the gas valve unit4 Check that the air inlet and flue gas discharge flues are not

blocked4 Check that there is no recirculation of flue gases

B25 BL.SU ERROR Internal error on the SU PCB 4 Replace the SU PCBM04 REVISION A service is required The date programmed for the service has been reached

4 Carry out maintenance on the boiler4 To clear the inspection, programme another date in the menu

#REVISION or set the parameter REVISION TYPE to OFFM05 REVISION A An A, B or C service is required The date programmed for the service has been reached

4 Carry out maintenance on the boiler4 To clear the inspection, press key t

M06 REVISION BM07 REVISION C

M20 DISGAS A boiler vent cycle is underway Switching the boiler on

4 Wait 3 minutes

9. Troubleshooting MCA 45 - 65 - 90 - 115

120 06/09/2010 - 300024755-001-A

Page 123: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Messages Description Checking / solution FL.DRY.B XX

DAYSFloor drying is activeXX DAYS = Number of days'floor drying remaining.

Floor drying is underway. Heating on the circuits not concerned isshut down.

4 Wait for the number of days shown to change to 04 Set the parameter SCREED DRYING to OFF

FL.DRY.C XXDAYSFL.DRY.B+C XXDAYS

M23 CHANGE OUTSSENSOR

The outside temperature sensorbattery is weak

Change the outside radio temperature sensor

STOP N XX The shutdown is activeXX = Number of the activeshutdown

A shutdown is underway. The circuits selected for this stop are inAntifreeze mode during the period chosen.

4 Wait until the end date has been passed4 Set the parameter STOP NXX to OFF

9.3 Message history

9.3.1. Control panel DIEMATIC iSystem

The menu #MESSAGE HISTORIC is used to consult the last 10messages displayed by the control panel.

1. Access the "After Sales" level: Hold key - down until#PARAMETERS is displayed.

2. Select the menu #MESSAGE HISTORIC.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

3. The list of the last 10 messages is displayed.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

BL.DT BOILER

BL.WATER MIS.

BL.RL AUF

BL.FLAME LOS

BL.RL OPEN

21/10

02/09

26/08

26/08 ÿ

C002381-A-04

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 121

Page 124: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4. Select a message to consult the information pertaining to it.

9.3.2. Control panel IniControl

The boiler control is equipped with an error memory. The last 16 errorsencountered are recorded in this memory.

In addition to the error codes, the following data are also saved:

4 Number of times that the error occured: (MK[xx).4 The flow temperature (t1[xx) and the return temperature

(t2[xx) when the error occured.

To view the error memory, you first have to enter access code0012.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

BL INPUT OPEN M21

28/08/2008 - 13h32

NUMBER OF CASE

OUTSIDE TEMP.

OUTLET TEMP.B

8

1.0 °C

12.0°Cÿ

C002382-A-04

9. Troubleshooting MCA 45 - 65 - 90 - 115

122 06/09/2010 - 300024755-001-A

Page 125: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Reading the memorised messages

1. Press the two keys f simultaneously and then key [+] until thesymbol c flashes on the menu bar.

2. Select the installers menu using the key S. c0de appearson the display.

3. Use keys [-] or [+] to input the installer code 0012.4. Press the S key. er[xx appears on the display.5. Confirm using key S. Bl[xx is displayed with xx

flashing = Last error which occured, For example K2 .6. Use the [-] or [+] key to scroll through the faults or shutdowns.7. Press the S key to display the details of the faults or shutdowns.8. Press the [-] or [+] key to view the following information:M[1 = Number of times that the error occured.

hr = The number of operating hours.

t1 = Flow temperature (°C).

t" = Return temperature (°C).

t3 = Calorifier temperature (°C).

t4 = Outside temperature (°C) (Only with an outsidetemperature sensor).fl = Ionisation current (µA).

Mf = Fan speed in rpm.

pr = Water pressure (bar).9. Press the j key to interrupt the display cycle. Bl[xx is

displayed with xx flashing = Last error which occured.10.Press j times on the key 2 to exit the error memory.

9.4 Faults (Code type Lxx or Dxx)

In the event of operational failure, the control panel flashes anddisplays an error message and a corresponding code.

Depending on the control panel, the message display isdifferent:

4 Control panel DIEMATIC iSystem: The code and themessage are displayed.

4 Control panel IniControl: Only the code is displayed.

C003070-A

2x

hj

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 123

Page 126: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

9.4.1. Control panel DIEMATIC iSystem

1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.

2. Press the t key. If the code is displayed again, switch off the boilerand then switch it back on.

3. Press the ? key. Follow the instructions displayed to solve theproblem.

4. Consult the meaning of the codes in the table below:

9.4.2. Control panel IniControl

1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.

2. Press the t key. If the code is displayed again, switch off the boilerand then switch it back on.

9.4.3. List of errors

Code Faults Causeof theerror

Description Checking / solution

L00 PSU FAIL PCU PSU PCB not connected Bad connection

4 Check the wiring between the PCU and PSU PCBsPSU PCB faulty

4 Replace the PSU PCBL01 PSU PARAM FAIL PCU The safety parameters are

incorrectBad connection

4 Check the wiring between the PCU and PSU PCBsPSU PCB faulty

4 Replace the PSU PCB

bar

1

1

2

2

rc

STD( t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP. : 68°

PCU. KOM. DEF D27

C002604-A-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP. : 68°

PCU COM.FAIL D27

C002302-D-04

9. Troubleshooting MCA 45 - 65 - 90 - 115

124 06/09/2010 - 300024755-001-A

Page 127: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

L02 DEF.OUTLET S. PCU The boiler flow sensor hasshort-circuited

Bad connection

4 Check the wiring between the PCU PCB and thesensor

4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

L03 DEF.OUTLET S. PCU The boiler flow sensor is onan open circuit

Bad connection

4 Check the wiring between the PCU PCB and thesensor

4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

L04 DEF.OUTLET S. PCU Boiler temp too low Bad connection

4 Check the wiring between the PCU PCB and thesensor

4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryNo water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger

L05 STB OUTLET PCU Boiler temperature too high Bad connection

4 Check the wiring between the PCU PCB and thesensor

4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryNo water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 125

Page 128: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

L06 BACK S.FAILURE PCU The return temperaturesensor has short-circuited

Bad connection

4 Check the wiring between the PCU PCB and thesensor

4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

L07 BACK S.FAILURE PCU The return temperaturesensor is on an open circuit

Bad connection

4 Check the wiring between the PCU PCB and thesensor

4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

L08 BACK S.FAILURE PCU Return temperature too low Bad connection

4 Check the wiring between the PCU PCB and thesensor

4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryNo water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger

L09 STB BACK PCU Return temperature too high Bad connection

4 Check the wiring between the PCU PCB and thesensor

4 Check that the SU PCB is correctly in place4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryNo water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger

9. Troubleshooting MCA 45 - 65 - 90 - 115

126 06/09/2010 - 300024755-001-A

Page 129: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

L10 DEP-RET<MIN PCU Difference between the flowand return temperaturesinsufficient

Sensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryBad connection

4 Check that the sensor has been correctly fittedNo water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger4 Check that the heating pump is operating correctly

L11 DEP-RET>MAX PCU Difference between the flowand return temperatures toogreat

Sensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessaryBad connection

4 Check that the sensor has been correctly fittedNo water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger4 Check that the heating pump is operating correctly

L12 STB OPEN PCU Maximum boilertemperature exceeded(STB thermostat maximum)

Bad connection

4 Check the wiring between the PCU PCB and the STB4 Check that the SU PCB is correctly in place4 Check the electrical continuity of the STB4 Check whether the STB has been correctly fittedSensor fault

4 Replace the STB if necessaryNo water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump, valves)4 Check the water pressure4 Check the cleanliness of the heat exchanger

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 127

Page 130: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

L14 BURNER FAILURE PCU 5 burner start-up failures Absence of ignition arch

4 Check the wiring between the PCU PCB and theignition transformer

4 Check that the SU PCB is correctly in place4 Check the ionisation/ignition electrode4 Check the earthing4 SU PCB faulty: Change the PCBPresence of the ignition arc but no flame formation

4 Vent the gas flues4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check the operation and setting of the gas valve unit4 Check that the air inlet and flue gas discharge flues

are not blocked4 Check the wiring on the gas valve unit4 SU PCB faulty: Change the PCBPresence of the flame but insufficient ionization (<3 µA)

4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check the ionisation/ignition electrode4 Check the earthing4 Check the wiring on the ionisation/ignition electrode

L16 PARASIT FLAME PCU Detection of a parasite flame Ionisation current present when there should not be a flameIgnition transformer defective

4 Check the ionisation/ignition electrodeGas valve defective

4 Check the gas valve and replace if necessaryThe burner remains very hot: CO2 too high

4 Set the CO2L17 VALVE FAIL PCU Problem on the gas valve Bad connection

4 Check the wiring between the PCU PCB and the gasvalve

4 Check that the SU PCB is correctly in placeSU PCB faulty

4 Inspect the SU PCB and replace it if need beL34 FAN FAILURE PCU The fan is not running at the

right speedBad connection

4 Check the wiring between the PCU PCB and the fanFan defective

4 Check for adequate draw on the chimney connection4 Replace the fan if need be

L35 BACK>BOIL FAIL PCU Flow and return reversed Bad connection

4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensors4 Replace the sensor if necessaryWater circulation direction reversed

4 Check the circulation (direction, pump, valves)

9. Troubleshooting MCA 45 - 65 - 90 - 115

128 06/09/2010 - 300024755-001-A

Page 131: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

L36 I-CURRENT FAIL PCU The flame went out morethan 5 times in 24 hourswhile the burner wasoperating

No ionization current

4 Purge the gas supply to remove air4 Check that the gas valve is fully opened4 Checking the gas supply pressure4 Check the operation and setting of the gas valve unit4 Check that the air inlet and flue gas discharge flues

are not blocked4 Check that there is no recirculation of flue gases

L37 SU COM.FAIL PCU Communication failure withthe SU PCB

Bad connection

4 Check whether the SU PCB has been correctly fittedinto the connector on the PCU PCB

4 Change the SU PCBL38 PCU COM.FAIL PCU Communication failure

between the PCU and SCUPCBs

Bad connection

4 Check the wiring between the PCU and SCU PCBs4 DIEMATIC iSystem: Run an AUTODETECTION in

the menu #CONFIGURATIONIniControl: Perform the automatic detection function¼ see chapter "Carrying out an auto-detect",page 105

SCU PCB not connected or faulty

4 Replace the SCU PCBL39 BL OPEN FAIL PCU The BL inlet opened for a

short timeBad connection

4 Check the wiringExternal cause

4 Check the device connected to the BL contactParameter incorrectly set

4 Check the parameter IN.BLL40 TEST.HRU.FAIL PCU HRU/URC unit test error Bad connection

4 Check the wiringExternal cause

4 Suppress the external causeParameter incorrectly set

4 Check the parametersL250 DEF.WATER MIS. PCU The water pressure is too

lowHydraulic circuit incorrectly ventedWater leakMeasurement error

4 Top up with more water if necessary4 Reset the boiler

L251 MANOMETRE FAIL PCU Pressure gauge fault Wiring problemThe manometer is defectiveSensor pcb defective

4 Check the wiring between the PCU PCB and thepressure gauge

4 Check whether the pressure gauge has been correctlyfitted

4 Replace the pressure gauge if need be

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 129

Page 132: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

D03D04

OUTL S.B FAIL.OUTL S.C FAIL.

SCU Sensor fault flow circuit BSensor fault flow circuit CRemarks:The circuit pump is running.The 3-way valve motor onthe circuit is no longerpowered and can beadjusted manually.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memoryin the PCB", page 132

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D05 OUTSI.S.FAIL. SCU Fault external sensorRemarks:The boiler operates onBOILER MAX temperature.The valve setting is nolonger ensured butmonitoring the maximumtemperature of the circuitafter the valve is ensured.Valves may be manuallyoperated.Reheating the domestic hotwater remains ensured.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memoryin the PCB", page 132

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D07 AUX.SENS.FAIL. SCU Auxiliary sensor failure Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memoryin the PCB", page 132

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D09 DHW S.FAILURE SCU Domestic hot water sensorfailureRemarks:Heating of domestic hotwater is no longer ensured.The load pump operates.The load temperature of thedhw tank is the same as theboiler.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memoryin the PCB", page 132

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D11D12D13

ROOM S.A FAIL.ROOM S.B FAIL.ROOM S.C FAIL.

SCU Fault room temperaturesensor AFault room temperaturesensor BFault room temperaturesensor CNote:The circuit concernedoperates without anyinfluence from the roomsensor.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memoryin the PCB", page 132

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

9. Troubleshooting MCA 45 - 65 - 90 - 115

130 06/09/2010 - 300024755-001-A

Page 133: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

D14 MC COM.FAIL SCU Communication failurebetween the SCU PCB andthe boiler radio module

Bad connection

4 Check the link and the connectorsBoiler module failure

4 Change the boiler moduleD15 ST.TANK S.FAIL SCU Storage tank sensor failure

Note:The hot water storage tankreheating operation is nolonger assured.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memoryin the PCB", page 132

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D16D16

SWIM.P.B. S.FAILSWIM.P.C. S.FAIL

SCU Swimming pool sensorfailure circuit BSwimming pool sensorfailure circuit CNote:Pool reheating isindependent of itstemperature.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memoryin the PCB", page 132

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D17 DHW 2 S.FAIL SCU Sensor failure tank 2 Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memoryin the PCB", page 132

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D27 PCU COM. FAIL SCU Communication failure between the SCU and PCU PCBs

4 Check the wiring between the SCU and PCU PCBs4 Check that the PCU PCB is powered up (green LED on or flashing)4 Change the PCU PCB

D29 IOBL.3WV B DEF SCU Communication failurebetween the SCU PCB andthe V3V module

The V3V module is switched off

4 Check that the 3WV module is powered up (GreenLED LIT)

The V3V module and the SCU PCB are not connected tothe same live terminal

4 Check that the 3WV module and the SCU PCB are onthe same live terminal or that a live coupler is installed

The V3V module has been removed

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 131

Page 134: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

D30 IOBL.3WV C DEF SCU Communication failurebetween the SCU PCB andthe V3V module

The V3V module is switched off

4 Check that the 3WV module is powered up (GreenLED LIT)

The V3V module and the SCU PCB are not connected tothe same live terminal

4 Check that the 3WV module and the SCU PCB are onthe same live terminal or that a live coupler is installed

The V3V module has been removedD31 COM.IOBL FAIL. SCU The IOBL function is no

longer activeProblem on the SCU PCB

4 If the IOBL function is not used:- DIEMATIC iSystem: Deactivate the IOBL

function in the #CONFIGURATION menu

- IniControl: Set parameter S18 ¼ Seechapter: "Description of the parameters",page 100

4 If the IOBL function is used, change the SCU PCB andre-pair the devices (IOBL 3WV module, Interscenarioswitch)

D32 5 RESET:ON/OFF SCU 5 resets done in less than an hour

4 Switch the boiler off and switch back onD37 TA-S SHORT-CIR SCU The Titan Active System® is short-circuited

4 Check that the connection cable between the SCU PCB and the anode is not short-circuited

4 Check that the anode is not short-circuitedRemarks:Domestic hot water production has stopped but can nonetheless be restarted using keyr.The tank is no longer protected.If: A tank without Titan Active System® is connected to the boiler: Check that the TitanActive System® simulation connector (delivered with package AD212) is fitted to thesensor card.

D38 TA-S DISCONNEC SCU The Titan Active System® is on an open circuit

4 Check that the connection cable between the SCU PCB and the anode is not severed4 Check that the anode is not brokenRemarks:Domestic hot water production has stopped but can nonetheless be restarted using keyr.The tank is no longer protected.If: A tank without Titan Active System® is connected to the boiler: Check that the TitanActive System® simulation connector (delivered with package AD212) is fitted to thesensor card.

9.4.4. Deletion of sensors from the memory in thePCB

The configuration of the sensors is memorised by the SCU PCB. If asensor error appears whilst the corresponding sensor is notconnected or has been voluntarily removed, please delete the sensorfrom the memory in the SCU PCB.

The outside temperature sensor cannot be deleted.

9. Troubleshooting MCA 45 - 65 - 90 - 115

132 06/09/2010 - 300024755-001-A

Page 135: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Control panel DIEMATIC iSystem

4 Press key ? repeatedly until "Do you want to delete thissensor?" is displayed.

4 Select YES by turning the rotary button and press to confirm.

n Control panel IniControl

4 Press the t key.

9.4.5. Deleting the IOBL 3WV modules from thememory in the PCB

This function is only available with the DIEMATICiSystem control panel.

The configuration of the IOBL 3WV modules is memorised by theSCU PCB. If a IOBL.3WV B DEF or IOBL.3WV C DEF error appearsafter voluntary deletion of a 3WV module, please delete the modulefrom the memory in the SCU PCB.

4 Press key ? repeatedly until "Do you want to delete thismodule?" is displayed.

4 Select YES by turning the rotary button and press to confirm.

You have the option of removing a IOBL 3WV module fromthe memory in the SCU PCB:4 Go to the menu #NETWORK and select REMOVE

DEVICE.

9.5 Failure history

9.5.1. Control panel DIEMATIC iSystem

The menu #DEFAULT HISTORIC is used to consult the last 10 errorsdisplayed by the control panel.

1. Access the "After Sales" level: Hold key - down until#PARAMETERS is displayed.

2. Select the menu #DEFAULT HISTORIC.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 133

Page 136: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3. The list of the last 10 errors is displayed.

4. Select an error to consult the information pertaining to it.

9.5.2. Control panel IniControl

1. Press the two keys f simultaneously and then key [+] until thesymbol c flashes on the menu bar.

2. Select the installers menu using the key S. c0de appearson the display.

3. Use keys [-] or [+] to input the installer code 0012.4. Press the S key. er[xx appears on the display.5. The fault list or shutdown list can be displayed by pressing the

[-] or [+] key..6. Confirm using key S. er[xx is displayed with xx

flashing = Last error which occured, For example K2 .7. Use the [-] or [+] key to scroll through the faults or shutdowns.8. Press the S key to display the details of the faults or shutdowns.9. Press the [-] or [+] key to view the following information:M[1 = Number of times that the error occured.

hr = The number of operating hours.

t1 = Flow temperature (°C).

t" = Return temperature (°C).

t3 = Calorifier temperature (°C).

t4 = Outside temperature (°C) (Only with an outsidetemperature sensor).fl = Ionisation current (µA).

Mf = Fan speed in rpm.

pr = Water pressure (bar).10.Press the j key to interrupt the display cycle. er[xx is

displayed with xx flashing = Last error which occured.11.Press j times on the key 2 to exit the error memory.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

AUX1.SENS.FAIL

COM.IOBL FAIL.

COM.IOBL FAIL.

21/10

02/09

26/08 ÿ

C002274-D-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

AUX1.SENS.FAIL D07

28/08/2008 - 13h32

NUMBER OF CASE

OUTSIDE TEMP.

TEMP.DEPART HP

8

1.0 °C

35.0°Cÿ

C002275-B-04

C003068-B

2x

hj

9. Troubleshooting MCA 45 - 65 - 90 - 115

134 06/09/2010 - 300024755-001-A

Page 137: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

9.6 Parameter and input/output check (mode tests)

9.6.1. Control panel DIEMATIC iSystem

Use the following menus to target the cause of a malfunction.

1. Access the "After Sales" level: Hold key - down until#PARAMETERS is displayed.

2. Check the following parameters:

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 58

#PARAMETERS menu

Parameter DescriptionPERMUT Master boiler activeSTAGE Number of boilers requesting heatingNB.CASC.: Number of boilers recognised in the cascadeNB. VM: Number of control systems recognised in the cascadePOWER % Current output of the boilerPERCENT PUMP Modulating pump commandSPEED FAN (1) Fan rotation speedSETPOINT FAN Fan rotation speed desiredMEAN OUTSIDE T Average outside temperatureCALC.T. BOILER Temperature calculated by the boilerBOILER. T. (1) Measurement of the boiler flow sensorCALCULATED T. A Calculated temperature for circuit ACALCULATED T. B (2) Calculated temperature for circuit B

CALCULATED T. C(2) Calculated temperature for circuit C

OUTLET TEMP. B (1)

(2)Temperature of the flow water in circuit B

OUTLET TEMP. C (1)

(2)Temperature of the flow water in circuit C

OUTSIDE TEMP. (1) Outside temperature

ROOMTEMP. A (1) Room temperature of circuit A

ROOMTEMP. B (1) (2) Room temperature of circuit B

ROOMTEMP. C (1)(2) Room temperature of circuit C

WATER TEMP. (1) (2) Water temperature in the DHW tank

IN 0-10V (1)(2) Voltage at input 0-10 V

BACK TEMP (1) Temperature of the boiler return water

CURRENT (1) Ionization current(1) The parameter can be displayed by pressing key f.(2) The parameter is only displayed for the options, circuits or sensors actually connected

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c r Mg m

SUNDAY 11:45

10"

C002483-A-04

TEMP.: 68°

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 135

Page 138: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

#PARAMETERS menu

Parameter DescriptionPRESSURE (1) Water pressure in the installation

STOR.TANK.TEMP (1)

(2)Water temperature in the storage tank

SYSTEM TEMP. (1)(2) Temperature of the system flow water if multi-generator

T.DHW BOTTOM (1)(2) Water temperature in the bottom of the DHW tank

DHW A TEMP. (1)(2) Water temperature in the second DHW tank connected to circuit A

TEMP.TANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuitKNOB A Position of temperature setting button on room sensor AKNOB B (2) Position of temperature setting button on room sensor B

KNOB C (2) Position of temperature setting button on room sensor COFFSET ADAP A Parallel trigger calculated for circuit AOFFSET ADAP B (2) Parallel trigger calculated for circuit B

OFFSET ADAP C (2) Parallel trigger calculated for circuit C(1) The parameter can be displayed by pressing key f.(2) The parameter is only displayed for the options, circuits or sensors actually connected

#TEST OUTPUTS menu

Parameter Adjustment range DescriptionP. CIRC. A ON / NO Stop/start pump circuit AP. CIRC. B (1) ON / NO Stop/start pump circuit B

P. CIRC. C (1) ON / NO Stop/start pump circuit C

HW. PUMP (1) ON / NO Stop/start domestic hot water pumpAUX.CIRC. ON / NO On/Off auxiliary outlet3WV B (1) REST No command

OPEN: Opening 3-way valve circuit BCLOSE: Closure 3-way valve circuit B

3WV C (1) REST No commandOPEN: Opening 3-way valve circuit CCLOSE: Closure 3-way valve circuit C

TEL.OUTPUT ON / NO On/Off telephone relay outlet(1) The parameter is only displayed for the options, circuits or sensors actually connected

#TEST INPUTS menu

Parameter Status OK DescriptionPHONE REM. Bridge on telephone input (1 = presence, 0 = absence)FLAME Flame presence test (1 = presence, 0 = absence)VALVE OP/CL Opening the valve

Closing the valveFAILURE ON Error display

OFF No errorSEQ. Control system sequence. ¼ see chapter: "Control system sequence", page

137.BOILER Index of the generator in the systemTYPE Generator typeVER.ROM Version of the PCU PCB programme(1) The parameter is only displayed for the options, circuits or sensors actually connected

9. Troubleshooting MCA 45 - 65 - 90 - 115

136 06/09/2010 - 300024755-001-A

Page 139: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

#TEST INPUTS menu

Parameter Status OK DescriptionVERS.PARAM PCU Version of the PCU PCB parametersR.CTRL A (1) ON Presence of a remote control A

OFF No remote control AR.CTRL B (1) ON Presence of a remote control B

OFF No remote control BR.CTRL C (1) ON Presence of a remote control C

OFF No remote control CID MC IOBL Identifying number of the IOBL boiler moduleIOBL.VERSION IOBL version of the SCU PCBCALIBRA.CLOCK Clock calibration(1) The parameter is only displayed for the options, circuits or sensors actually connected

#CONFIGURATION menu

Parameter Adjustment range DescriptionMODE: MONO/ ALL.CIRC. To chose if the exemption made for one remote control applies to a single circuit

(MONO) or if it must be transmitted to a group of circuits (ALL CIRC)TYPE Generator type (Refer to the original rating plate)AUTODETECTION OFF/ON System reset if error L38 is displayedTAS OFF/ON Activation of the Titan Active System® functionIOBL OFF/ON Activation of the IOBL function

9.6.2. Control panel IniControl

1. Check the following parameters:

"After Sales" level - #CONFIGURATION menuParameter Adjustment range DescriptionS17 - IOBL 0 / 1 Activation of the IOBL functionS18 - TAS 0 / 1 Activation of the Titan Active System® function

9.6.3. Control system sequence

Control system sequenceStatus OK Sub-status Operation0 0 Boiler stopped1 1 Anti-short cycle activated

2 Open isolating valve3 Start-up of the boiler pump4 Awaiting burner start-up

MCA 45 - 65 - 90 - 115 9. Troubleshooting

06/09/2010 - 300024755-001-A 137

Page 140: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Control system sequenceStatus OK Sub-status Operation2 10 Open gas valve (external)

11 Fan start-up13 The fan switches to the burner start-up speed14 Check RL signal (Function not active)15 Burner on switch request17 Pre-ignition18 Ignition19 Check flame presence20 Awaiting further action to unsuccessful ignition

3 / 4 30 Burner lit and free modulation on the boiler instruction31 Burner lit and free modulation on a limited instruction, equal to a return temperature of +30°C32 Burner lit and free modulation on the boiler set point but restricted on the control panel33 Burner lit and descending modulation following too large a rise in temperature on the exchanger (4 K

in 10 seconds)34 Burner lit and minimum modulation following too large a rise in temperature on the exhanger (7 K in

10 seconds)35 Burner off following too large a rise in temperature on the exchanger (9 K in 10 seconds)36 Burner lit and ascending modulation to guarantee a correct ionization current37 Heating: Burner lit and minimum modulation after a burner start-up lasting 30 seconds

DHW production: Burner lit and minimum modulation after a burner start-up lasting 100 seconds38 Burner lit and modulation fixed higher than the minimum after burner start-up lasting 30 seconds, if the

burner was off for more than 2 hours or after powering up5 40 The burner will stop

41 The fan switches to post-sweeping speed on the burner42 The external gas valve closes43 Post-sweeping44 Stop fan

6 60 Post-operation of the boiler pump61 Stop boiler pump62 Close isolating valve63 Start anti short cycle

8 0 Awaiting burner start-up1 Anti-short cycle activated

9 -- Blockage detected10 -- Lock-out16 -- Antifreeze protection17 -- Bleed

9. Troubleshooting MCA 45 - 65 - 90 - 115

138 06/09/2010 - 300024755-001-A

Page 141: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10 Spare parts

10.1 General

When it is observed subsequent to inspection or maintenance workthat a component in the boiler needs to be replaced, use only originalspare parts or recommended spare parts and equipment.

To order a spare part, give the reference number shownon the list.

10.2 Spare parts

MCA 45 - 65 - 90 - 115 10. Spare parts

06/09/2010 - 300024755-001-A 139

Page 142: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.1. Casing

T002923-BEV 90520-1

1003

1001

1002

1005

1

10. Spare parts MCA 45 - 65 - 90 - 115

140 06/09/2010 - 300024755-001-A

Page 143: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.2. Heat exchanger and burner - MCA 45

T002924-BEV 90520-2

2001 20212016

2025

2017

2006

2010

20012014

2013

2015

2004

2005

2003

2022

2047

2023

2024

2019

2020

2037

2038

2039

2040

2041

2044

2045

2046

20072026

20302014

2009

2029

20082047

2028

2031

2032

2027

2033

2017

2012

2011

2002

2

2042

MCA 45 - 65 - 90 - 115 10. Spare parts

06/09/2010 - 300024755-001-A 141

Page 144: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.3. Heat exchanger and burner - MCA 65

T002930-BEV 90521-2

2

2017

2017

2016

20262030

2014

2025

2006

2010

2001

2013

2014

2015

2004

2009

2029

2008

2003

2005

2047

2040

2039

2038

2037

2028

2031

2032

2027

2033

2012

2011

2041

2044

2045

2046

2024

2002

2007

2021

2047

2019

2020

2042

10. Spare parts MCA 45 - 65 - 90 - 115

142 06/09/2010 - 300024755-001-A

Page 145: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.4. Heat exchanger and burner - MCA 90/115

T002936-BEV 90522-2

2017

2011

2012

2017

2016

2030

2014

2025

2006

2010

2001

2014

2013

2015

2004

2009

2008

2003

2005

2047

2029

2040

2039

2038

2037

2042

2028

2026

2031

2032

2027

2033

2041

2045

2044

2046

2024

2002

2007

2

2021

2047

2019

2020

MCA 45 - 65 - 90 - 115 10. Spare parts

06/09/2010 - 300024755-001-A 143

Page 146: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.5. Fan - MCA 45/65

T002925-BEV 90520-3

3014

3004

3007

3013

3011

3006

3010

3001

3005

3012

3003

3008

3009

3002

3

10. Spare parts MCA 45 - 65 - 90 - 115

144 06/09/2010 - 300024755-001-A

Page 147: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.6. Fan - MCA 90

T002937-AEV 90522-3

3014

3013

3

3006

3007

3016

3005

3010

3011

3015

3001

3012

3003

3008

3009

3002

MCA 45 - 65 - 90 - 115 10. Spare parts

06/09/2010 - 300024755-001-A 145

Page 148: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.7. Fan - MCA 115

T002943-CEV 90523-3

3014

3

3005

3013

3007

3008

3017

3002

3011

3010

3015

3001

3012

3003

3006

3009

3016

3018

10. Spare parts MCA 45 - 65 - 90 - 115

146 06/09/2010 - 300024755-001-A

Page 149: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.8. Control panel

T002926-BEV 90520-4

401840194015

4001

4002

4004

40234020

4023

4024

4021

4022

4015 40104017

4009

4007

4007

4008

4012

4011

4014

4013

4005

4006

4

MCA 45 - 65 - 90 - 115 10. Spare parts

06/09/2010 - 300024755-001-A 147

Page 150: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10.2.9. Spare parts list

Markers Code no. Description Part MCA 45 MCA 65 MCA 90 MCA 115Casing1001 S101575 Front casing 1 x x x x1002 S101612 Top cover (Control panel) 1 x x x x1003 S101517 Wall suspension bracket 1 x x x x1005 S101403 Screw 2 x x x x0 S101557 Boiler back light 1 x x x xHeat exchanger and burner2001 S101560 Heat exchanger 45kW 1 x 2001 S101551 Heat exchanger 65kW 1 x 2001 S101550 Heat exchanger 90-115kW 1 x x2002 S101564 Heat exchanger front plate 1 x x x x2003 S54753 Burner - 45 kW 1 x 2003 S54754 Burner - 65 kW 1 x 2003 S57477 Burner - 90-115 kW 1 x x2004 S101566 Electrode ignition ionisation 1 x x x x2005 S53489 Sealing plate for the ignition electrode 10 x x x x2006 S59118 Hatch 1 x x x x2007 S54731 Sheet metal plate insulation before the heat exchanger 1 x x x x2008 S57241 Heat exchanger front plate sealing 1 x x x x2009 S54755 M6 nut 20 x x x x2010 S100052 Screw M4x10 20 x x x x2011 S100619 Ignition transformer with ignition electrode 1 x x x x2012 S101509 Screw M4x8 5 x x x x2013 S101005 HL temperature sensor 1 x x x x2014 S101003 NTC temperature sensor 2 x x x x2015 S48950 Screw M4x10 50 x x x x2016 S55993 Flue gas discharge pipe Ø 80 mm (45kW) 1 x 2016 S55994 Flue gas discharge pipe Ø 100 mm (65-90-115kW) 1 x x x2017 S55914 Leakproof seal Ø 80 mm 5 x 2018 S55915 Leakproof seal Ø 100 mm 5 x x x2019 S100465 Combustion gas adapter 80/125 mm 1 x 2019 S101563 Combustion gas adapter 100/150 mm 1 x x x2020 S62233 Protective plug for the combustion gas evacuation

measurement point5 x x x x

2021 S62232 Protective plug for the combustion gas evacuationmeasurement point

5 x x x x

2022 S100855 Leakproof seal Ø 80 mm 5 x 2022 S101643 Leakproof seal Ø 100 mm 5 x x x2023 S101567 Flue gas discharge pipe connection piece Ø 80 mm 1 x 2024 S100901 Holding strip for the heat exchanger 1 x x x x2025 S62288 Grommet for flue gas discharge pipe 1 x x x x2026 S101568 Water flow pipe Central heating 1 x x 2026 S101572 Water flow pipe Central heating 1 x x2027 S101632 Pressure sensor 1 x x x x2028 S101608 Automatic air vent 5 x x x x2029 S100737 Sealing ring Ø 44x32x4 mm 5 x x x x2030 S101576 Cable clamp 28-35 5 x x x x2031 S101644 Clip 10,2 5 x x x x

10. Spare parts MCA 45 - 65 - 90 - 115

148 06/09/2010 - 300024755-001-A

Page 151: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Markers Code no. Description Part MCA 45 MCA 65 MCA 90 MCA 1152032 S100895 Endpiece M7x1 1 x x x x2033 S101570 Silicone hose 8x2x740 1 x x x x2037 S101558 Siphon 1 x x x x2038 S14254 Screw 4,2x9,5 20 x x x x2039 S101580 Leak proofing ring - Ø 60 mm 1 x x x x2040 S101559 Siphon cup 1 x x x x2041 S101606 Siphon hose 1 x x x x2042 S101581 Siphon gasket 1 x x x x2044 S101298 Closing plate SCU 1 x x x x2045 S62727 Grommet Ø 20 mm 15 x x x x2046 S101607 Grommet Ø 25x35x2 mm 5 x x x x2047 S101605 Sealing (Heating circuit return) 1 x x x xFan3001 S59167 Fan Mvlrg 148/1200-3633 1 x 3001 S59168 Fan Mvlrg 148/1200-3633 1 x x 3001 S100036 Fan Mvlrg 148/1200-3633-010202 1 x3002 S54765 Venturi 45kW 1 x 3002 S54766 Venturi 65kW 1 x 3002 S57488 Venturi 90kW 1 x 3002 S101595 Venturi 115kW 1 x3003 S101543 Áir intake silencer 45-65kW 1 x x 3003 S101520 Áir intake silencer 90kW 1 x 3003 S101578 Áir intake silencer 115kW 1 x3004 S101590 Clamp for suction silencer 1 x x 3005 S101569 Gas inlet pipe 1 x x 3005 S101573 Gas inlet pipe 1 x 3005 S101515 Gas inlet pipe 1 x3006 S101596 Gas block Vk8115V1168 1 x x 3006 S101597 Gas block 90kW 1 x 3006 S101510 Gas block 115kW 1 x3007 S101565 Gasket 83 mm with 45-115 kW valve 1 x x x x3008 S54777 Venturi gasket 5 x x x x3009 S48512 Bolt M5x10 10 x x x 3009 S100468 Screw M5x12 10 x3010 S101591 Set of Gaskets - 45-60kW 1 x x 3010 S101592 Set of Gaskets - 90kW 1 x 3010 S101593 Set of Gaskets - 115kW 1 x3010 S100363 33x2 O-ringmm 10 x3011 S56155 Leakproof seal (Ø 23,8x17,2x2 mm 20 x x x x3012 S101519 Cable clamp 5 x x x x3013 S54755 Flanged nut M6 20 x x x x3014 S100055 M5 nut 20 x x x x3015 S57827 Flange for gas valve unit 1 x x3016 S57828 O-ring (Gas inlet pipe) Ø 26,8x22x2,5 mm 1 x 3016 S101631 Inlet (Venturi) 1 x3017 S100054 Screw M5x16 20 x3018 S101664 O-ring (Inlet) 1 xControl panel4001 S101518 PCU-04 PCB 1 x x x x4002 S100849 SU-01 PCB 1 x x x x4003 S100859 display board 1 x x x x

MCA 45 - 65 - 90 - 115 10. Spare parts

06/09/2010 - 300024755-001-A 149

Page 152: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Markers Code no. Description Part MCA 45 MCA 65 MCA 90 MCA 1154004 S6778 6,30 glass fuse A slow 10 x x x x4004 S43562 3,15 glass fuse A slow 10 x x x x4005 S101619 Ignition transformer with ignition electrode 1 x x x x4006 S101632 Pressure sensor 1 x x x x4007 S101003 NTC temperature sensor 2 x x x x4008 S101005 HL temperature sensor 1 x x x x4009 S101554 PCU pump cable 1 x x x x4010 S101561 24 V cable 1 x x x x4011 S101589 cable form 230V - 45-65-90kW 1 x x x 4011 S101582 cable form 230V - 115kW 1 x4012 S100845 Electric cable 1500 mm 1 x x x x4013 S101588 Pump cable 1 x x x x4014 S101553 Cable for fan 1 x x x x4015 S101251 Control panel 1 x x x x4017 S101514 Fastening 2 x x x x4018 S100861 Oval sealing gasket 5 x x x x4019 S59372 Draught diverter 1 x x x x4020 S101048 SCU PCB 1 x x x x4021 S101555 SCU 230 V cable 1 x x x x4022 S101556 Cable for interface 1 x x x x4023 S101513 Box SCU 1 x x x x4024 S100862 SCU grommet 5 x x x x0 S62185 Screw Kb30x8 10 x x x x0 S101252 Outside temperature sensor 1 x x x x0 S101577 Bundle clip 1 x x x x0 S101620 Card PSU 1 x x x x

10. Spare parts MCA 45 - 65 - 90 - 115

150 06/09/2010 - 300024755-001-A

Page 153: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

MCA 45 - 65 - 90 - 115 10. Spare parts

06/09/2010 - 300024755-001-A 151

Page 154: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10. Spare parts MCA 45 - 65 - 90 - 115

152 06/09/2010 - 300024755-001-A

Page 155: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P
Page 156: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

© CopyrightAll technical and technological information contained in these technical instructions,as well as any drawings and technical descriptions supplied, remain our propertyand shall not be multiplied without our prior consent in writing.

T000249-B

06/09/2010

DE DIETRICH THERMIQUE

57, rue de la Gare F- 67580 MERTZWILLER - BP 30

Page 157: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Ireland

Innovens Pro EN

MCA 45 - 65 - 90 - 115

User Guide

300024756-001-A

Page 158: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Contents

1 Introduction ................................................................................................41.1 Used symbols .......................................................4

1.2 Abbreviations ........................................................4

1.3 General ..................................................................51.3.1 Manufacturer's liability .............................................51.3.2 Installer's liability .....................................................51.3.3 User's liability ..........................................................5

1.4 Certifications .........................................................6

2 Safety instructions and recommendations ..............................................72.1 Safety instructions ...............................................7

2.2 Recommendations ................................................8

3 Description ..................................................................................................93.1 Operating principle ...............................................9

3.1.1 Gas/air setting .........................................................93.1.2 Combustion .............................................................9

3.2 Main parts ............................................................10

3.3 Control panel DIEMATIC iSystem .....................103.3.1 Description of the keys ..........................................103.3.2 Description of the display ......................................113.3.3 Browsing in the menus ..........................................13

3.4 Control panel IniControl .....................................143.4.1 Description of the keys ..........................................143.4.2 Description of the display ......................................15

4 Operating the appliance - DIEMATIC iSystem .......................................174.1 Putting the appliance into operation ................17

4.2 Reading out measured values ...........................17

4.3 Changing the settings ........................................194.3.1 Setting the set point temperatures ........................194.3.2 Selecting the operating mode ...............................204.3.3 Forcing domestic hot water production .................214.3.4 Setting the contrast and lighting on the

display ...................................................................214.3.5 Setting the time and date ......................................224.3.6 Selecting a timer programme ................................224.3.7 Customising a timer programme ...........................23

1 06/09/2010 - 300024756-001-A

Page 159: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3.8 Setting an annual clock .........................................25

4.4 Installation shutdown .........................................27

4.5 Frost protection ..................................................28

5 Operating the appliance - IniControl ......................................................295.1 Putting the appliance into operation ................29

5.2 Reading out measured values ...........................29

5.3 Changing the settings ........................................305.3.1 Description of the parameters ...............................305.3.2 Modification of the user-level parameters .............315.3.3 Setting the manual mode ......................................325.3.4 Changing the heating temperature ........................325.3.5 Modifying the domestic hot water temperature

setting ....................................................................32

5.4 Installation shutdown .........................................33

5.5 Frost protection ..................................................33

6 Checking and maintenance .....................................................................346.1 General instructions ...........................................34

6.1.1 Control panel DIEMATIC iSystem .........................34

6.2 Periodic checks ..................................................34

6.3 Filling the system ...............................................35

6.4 Bleeding the heating system .............................38

6.5 Draining the installation .....................................40

7 Troubleshooting .......................................................................................417.1 Anti-hunting ........................................................41

7.2 Messages (Code type Bxx or Mxx) ....................41

7.3 Faults (Code type Lxx or Dxx) ...........................437.3.1 Control panel DIEMATIC iSystem .........................447.3.2 Control panel IniControl ........................................447.3.3 List of errors ..........................................................44

Contents

2 06/09/2010 - 300024756-001-A

Page 160: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8 Technical characteristics ........................................................................508.1 Technical characteristics ...................................50

9 Energy savings .........................................................................................519.1 Energy-saving advice .........................................51

9.2 Recommendations ..............................................51

10 Warranty ....................................................................................................5210.1 General ................................................................52

10.2 Warranty terms ...................................................52

3 06/09/2010 - 300024756-001-A

Page 161: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

1 Introduction

1.1 Used symbols

In these instructions, various danger levels are employed to draw theuser's attention to particular information. In so doing, we wish tosafeguard the user's safety, obviate hazards and guarantee correctoperation of the appliance.

DANGER

Risk of a dangerous situation causing serious physicalinjury.

WARNING

Risk of a dangerous situation causing slight physicalinjury.

CAUTION

Risk of material damage.

Signals important information.

¼ Signals a referral to other instructions or other pages in theinstructions.

1.2 Abbreviations

4 3CE: Collective conduit for sealed boiler4 DHW: Domestic hot water4 Interscenario switch: Home automation switch that can be used

to centralise and control several scenarios4 Hi: Lower heating value LHV4 Hs: Higher heating value HHV4 IOBL: Carrier current home automation bus4 PPS: Polypropylene hardly inflammable4 PCU: Primary Control Unit - PCB for managing burner operation4 PSU: Parameter Storage Unit - Parameter storage for PCBs

PCU and SU4 SCU: Secondary Control Unit - Diematic iSystem control panel

PCB4 SU: Safety Unit - Safety PCB4 3WV: 3-way valve

MCA 45 - 65 - 90 - 115 1. Introduction

06/09/2010 - 300024756-001-A 4

Page 162: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

1.3 General

1.3.1. Manufacturer's liability

Our products are manufactured in compliance with the requirementsof the various european applicable Directives. They are therefore

delivered with [ marking and all relevant documentation.

In the interest of customers, we are continuously endeavouring tomake improvements in product quality. All the specifications stated inthis document are therefore subject to change without notice.

Our liability as the manufacturer may not be invoked in the followingcases:

4 Failure to abide by the instructions on using the appliance.4 Faulty or insufficient maintenance of the appliance.4 Failure to abide by the instructions on installing the appliance.

1.3.2. Installer's liability

The installer is responsible for the installation and inital start up of theappliance. The installer must respect the following instructions:

4 Read and follow the instructions given in the manuals providedwith the appliance.

4 Carry out installation in compliance with the prevailing legislationand standards.

4 Perform the initial start up and carry out any checks necessary.4 Explain the installation to the user.4 If a maintenance is necessary, warn the user of the obligation to

check the appliance and maintain it in good working order.4 Give all the instruction manuals to the user.

1.3.3. User's liability

To guarantee optimum operation of the appliance, the user mustrespect the following instructions:

4 Read and abide by the instructions given in the user manual.4 Call on qualified professionals to carry out installation and initial

start up.4 Get your fitter to explain your installation to you.4 Have the required checks and services done.4 Keep the instruction manuals in good condition close to the

appliance.

1. Introduction MCA 45 - 65 - 90 - 115

5 06/09/2010 - 300024756-001-A

Page 163: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

This appliance is not intended to be used by persons (includingchildren) whose physcial, sensory or mental capacity is impaired orpersons with no experience or knowledge, unless they have thebenefit, through the intermediary of a person responsible for theirsafety, of supervision or prior instructions regarding use of theappliance. Care should be taken to ensure that children do not playwith the appliance.

1.4 Certifications

CE identification no PIN 0063CL3333NOx classification 5 (EN 297 pr A3, EN 656)Type of connection Chimney: B23, B33

Flue gas outlet: C13, C33, C43, C53, C63, C83, C93

MCA 45 - 65 - 90 - 115 1. Introduction

06/09/2010 - 300024756-001-A 6

Page 164: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

2 Safety instructions andrecommendations

2.1 Safety instructions

DANGER

If you smell gas:

1. Do not use a naked flame, do not smoke, do notoperate electrical contacts or switches ( doorbell,light, motor, lift, etc..).

2. Isolate the gas supply.3. Open the windows.4. Evacuate the premises.5. Call your fitter.

DANGER

If you smell flue gases:

1. Switch the appliance off.2. Open the windows.3. Evacuate the premises.4. Call your fitter.

WARNING

Depending on the settings of the appliance:

4 The temperature of the flue gas conduits may exceed60°C.

4 The temperature of the radiators may reach 85°C.4 The temperature of the domestic hot water may reach

65°C.

CAUTION

Do not neglect to service the appliance:4 For completely safe and optimum operation, you

must have your boiler regularly serviced by anapproved installer.

2. Safety instructions and recommendations MCA 45 - 65 - 90 - 115

7 06/09/2010 - 300024756-001-A

Page 165: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

2.2 Recommendations

WARNING

Only qualified professionals are authorised to work on theappliance and the instalation.

4 Regularly check the water pressure in the installation (minimumpressure 0,8 bar, recommended pressure between 1,5 and 2 bar).

4 Keep the appliance accessible at all times.4 Never remove or cover labels and rating plates affixed to the

appliance. Labels and rating plates must be legible throughout theentire lifetime of the appliance.

4 The appliance should be on Summer or Antrifreeze mode ratherthan switched off to guarantee the following functions:- Anti blocking of pumps- Frost protection

MCA 45 - 65 - 90 - 115 2. Safety instructions and recommendations

06/09/2010 - 300024756-001-A 8

Page 166: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3 Description

3.1 Operating principle

3.1.1. Gas/air setting

The casing fitted to the boiler is also used as an air box. Air is suckedin by the fan and gas injected into the venturi by the fan intake. Thefan rotation speed is set according to the settings parameters, thethermal energy requirement and the temperatures measured by thetemperature sensors. The gas and air are mixed in the venturi. Thegas/air ratio ensures that the quantities of gas and air are adjusted toeach other. This provides optimum combustion on the entire outputrange. The gas/air mixture is fed into the burner on top of theexchanger.

3.1.2. Combustion

The burner heats the heating water circulating in the heatexchanger. At a return temperature lower than around 55°C, the fluegases cool down to a temperature lower than the dew point, thuscausing the condensation of the water vapour contained in the fluegases in the back side of the heat exchanger. The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water. The cooled combustion gasesare evacuated via the combustion gas outlet flue. The condensationwater is evacuated via a siphon.

3. Description MCA 45 - 65 - 90 - 115

9 06/09/2010 - 300024756-001-A

Page 167: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

3.2 Main parts

1 Flue gas outlet / Air intake2 Casing/air box3 Heat exchanger (Central heating)4 Outlet for measuring combustion gases5 Ignition/ionization electrode6 Mixer pipe7 Combined venturi and gas valve unit8 Áir intake silencer9 Instrument box10 Siphon11 Box for the control PCBs12 Fan13 Water flow pipe

3.3 Control panel DIEMATIC iSystem

3.3.1. Description of the keys

A Temperature setting key (heating, DHW, swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installer

T002036-B

8

7

4

55

6

2

3

9

11

10

12

13

1

A000866-A

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

A

B

C

D E F

( '

MCA 45 - 65 - 90 - 115 3. Description

06/09/2010 - 300024756-001-A 10

Page 168: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

E Keys on which the function varies as and when selectionsare made

F Rotary setting button:

4 Turn the rotary button to scroll through the menus ormodify a value

4 Press the rotary button to access the menu selectedor confirm a value modification

3.3.2. Description of the display

n Key functions

> Access to the various menus

( Used to scroll through the menus

' Used to scroll through the parameters? The symbol is displayed when help is available

f Used to display the curve of the parameter selectedSTD Reset of the time programmes

b Selection of comfort mode or selection of the days to beprogrammed

v Selection of reduced mode or deselection of the days tobe programmed

j Back to the previous levelESC Back to the previous level without saving the

modifications made

t Manual reset

n Flame output level

C002705-A

The whole symbol flashes: The burner starts up but theflame is not yet present

C002704-A

Part of the symbol flashes: Output is increasing

C002703-A

Steady symbol: The required output has been reached

C002702-A

Part of the symbol flashes: Output is dropping

bar

r

STD( ' t

0 2 4 6 8 10 12 14 16 18 22 2420

C002696-A

pb AUTOx c rjLg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002701-B

pb AUTOx c rjMg m

3. Description MCA 45 - 65 - 90 - 115

11 06/09/2010 - 300024756-001-A

Page 169: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Operating modes

p Summer mode: The heating is off. Domestic hot watercontinues to be produced

b WINTER mode: Heating and domestic hot water working

AUTO Operation in automatic mode according to the timerprogramme

x Comfort mode: The symbol is displayed when a DAYoverride (comfort) is activated

4 Flashing symbol: Temporary override4 Steady symbol: Permanent override

m Reduced mode: The symbol is displayed when a NIGHToverride (reduced) is activated

4 Flashing symbol: Temporary override4 Steady symbol: Permanent override

g Holiday mode: The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated

4 Flashing symbol: Holiday mode programmed4 Steady symbol: Holiday mode active

m Manual mode

n System pressure

bar Pressure indicator: The symbol is displayed when a waterpressure sensor is connected

4 Flashing symbol: The quantity of water is insufficient4 Steady symbol: The quantity of water is sufficient

l Water pressure level

4 R : 0,9 to 1,1 bar4 E : 1,2 to 1,5 bar4 Z : 1,6 to 1,9 bar4 A : 2,0 to 2,3 bar4 l : > 2,4 bar

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002697-B

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002698-B

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002708-A

pb AUTOx c rjMg m

MCA 45 - 65 - 90 - 115 3. Description

06/09/2010 - 300024756-001-A 12

Page 170: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Domestic Hot Water override

A bar is displayed when a DHW override is activated:

4 Flashing bar: Temporary override4 Steady bar: Permanent override

n Other information

r The symbol is displayed when domestic hot waterproduction is running

w Valve indicator: The symbol is displayed when a 3-wayvalve is connected

4 x : 3-way valve open4 c : 3-way valve closed

M The symbol is displayed when the pump is operating

Name of the circuit for which the parameters are displayed

3.3.3. Browsing in the menus

1. To select the desired menu, turn the rotary button.2. To access the menu, press the rotary button.

To go back to the previous display, press the key j.

3. To select the desired parameter, turn the rotary button.4. To modify the parameter, press the rotary button.

To go back to the previous display, press the key j.

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002707-A

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002699-B

pb AUTOx c rjMg m

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

#MEASURES

#CHOICE TIME PROG.

#TIME PROGRAM

#SETTING

#TIME .DAYÿ

C002220-A-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CURRENT PROG.B

CURRENT PROG.C

P2

P3 ÿ

C002221-B-04

3. Description MCA 45 - 65 - 90 - 115

13 06/09/2010 - 300024756-001-A

Page 171: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5. To modify the parameter, turn the rotary button.6. To confirm, press the rotary button.

To cancel, press key h.

7. To go back to the main display, press key j2 times.

It is possible to use the ( and ' keys instead of the rotarybutton.

3.4 Control panel IniControl

3.4.1. Description of the keys

A Return button j, Escape G or Manual reset tB Heating temperature button d or [-]

C DHW temperature button r or [+]

D S [Enter] KeyE ) [Chimney-sweeping] keys

Press keys A and B simultaneously

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CURRENT PROG.C"Choice of the timeprogram applied C"

P4

ÿ

C002222-B-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

LUNDI 11:45

C002224-D-04

2x

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C002968-D

thj

A B

E F

C D

MCA 45 - 65 - 90 - 115 3. Description

06/09/2010 - 300024756-001-A 14

Page 172: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

F f [Menu] keysPress keys C and D simultaneously

3.4.2. Description of the display

n Key functions

G Back to the previous level without saving themodifications made

t Manual reset

d Central heating function:Access to the max. heating temperature parameter.

[-] To reduce a value

r Sanitary hot water function:Access to sanitary hot water temperature parameter.

[+] To increase a value

® Access the menu selected or confirm a value modification

n Operating modes

d State heating pump A

D Heating programme deactivated:The heating function is deactivated

r State DHW pump

m Manual mode

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:C003042-B

thj

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003043-B

thj

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003044-B

thj

3. Description MCA 45 - 65 - 90 - 115

15 06/09/2010 - 300024756-001-A

Page 173: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

n Flame output level

e Low output level 0 - 25 %

r Average output level 25 - 50 %

t High output level 50 - 75 %

y Output level 75 - 100 %

n System pressure

bar Pressure indicator:The symbol is displayed next to the installation's pressurevalue. If no water pressure sensor is connected, -.-appears on the display

n Other information

" User menu:Parameters at user level can be changed

! Information menu:Reading the various current values

) Chimney-sweeping position:Forced full or part load for CO2 measurement

- Service menu:Parameters at installer level can be changed

K Display with the symbols:$ + K + Z (Maintenance message)

\ Hour counter menu:Readout of the operating hours, number of successfulstarts and hours on mains supply

a On/Off switch:After 5 lock-outs, the device must be switched off/on again

I Outside temperature sensor present

M The symbol is displayed when the boiler pump isoperating

a Fault:Boiler indicates a fault. This is signalled by a P or X codeand a flashing display

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003046-B

thj

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003047-C

thj

-)

Lmr

r

d

d

d

T

y

1

2

SERVICE

°C°FhbarPsi% rpmkW uAx10 l/min

°CSt:

C003048-B

thj

MCA 45 - 65 - 90 - 115 3. Description

06/09/2010 - 300024756-001-A 16

Page 174: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4 Operating the appliance - DIEMATICiSystem

4.1 Putting the appliance into operation

1. Check the water pressure in the installation shown on the controlpanel display.

If the water pressure is lower than 0,8 bar, more watershould be added. If necessary, top up the water level in theheating system (recommended hydraulic pressurebetween 1,5 and 2,0 bar).¼ See chapter: "Filling the system", page 35

2. Open the gas valve on the boiler.3. Turn on the boiler using the on/off switch.

4. The first time the boiler is powered up, the #LANGUAGE menu isdisplayed. Select the desired language by turning the rotarybutton.

5. To confirm, press the rotary button.The boiler will begin an automatic venting-programme (which lastsapprox. 3 minutes) and will do this every time the power supply isisolated. If there is a problem, the error is displayed on the screen.

4.2 Reading out measured values

The various values measured by the appliance are displayed in the#MEASURES menu.

1. To access "user" level: Press the > key.2. To select the #MEASURES menu.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 13.

C002366-B

Français - Deutsch - English - Italiano - Espanol - Nederlands- Polski -

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb x c rg m

aLANGUE FRANCAIS

C003079-A

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

17 06/09/2010 - 300024756-001-A

Page 175: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

"User" level - #MEASURES menu

Parameter Description UnitOUTSIDE TEMP. Outside temperature °CROOMTEMP. A (1) Room temperature of circuit A °C

ROOMTEMP. B (1) Room temperature of circuit B °C

ROOMTEMP. C (1) Room temperature of circuit C °CBOILER TEMP. Water temperature in the boiler °CPRESSURE Water pressure in the installation barWATER TEMP. (1) Water temperature in the DHW tank °C

INST DWH TEMP. (1) Instant hot water temperature °C

STOR.TANK.TEMP (1) Water temperature in the storage tank °CDCW TEMPERATURE Domestic cold water temperature °CSWIMMING P.T.B (1) Water temperature of the swimming pool on circuit B °C

SWIMMING P.T.C (1) Water temperature of the swimming pool on circuit C °C

OUTLET TEMP. B (1) Temperature of the flow water in circuit B °C

OUTLET TEMP. C (1) Temperature of the flow water in circuit C °C

SYSTEM TEMP. (1) Temperature of the system flow water if multi-generator °CT.DHW BOTTOM Water temperature in the bottom of the DHW tank °CTEMP.TANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit °C

DHW A TEMP. (1) Water temperature in the second DHW tank connected to circuit A °CBACK TEMP Temperature of the boiler return water °CWIND SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0%: Burner off or running at minimum output) %CURRENT (µA) Ionization current µANB IMPULS. Number of burner start-ups (not restartable)

The meter is incremented by 8 every 8 start-ups

RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours

h

IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options, circuits or sensors actually connected.

MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem

06/09/2010 - 300024756-001-A 18

Page 176: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3 Changing the settings

4.3.1. Setting the set point temperatures

To set the various heating, DHW and swimming pool temperatures,proceed as follows:

1. Press the C key.2. To select the desired parameter, turn the rotary button.3. To modify the parameter, press the rotary button.

To go back to the previous display, press the key j.4. To modify the parameter, turn the rotary button.5. To confirm, press the rotary button.

To cancel, press key h.

Menu C

Parameter Adjustment range Description Factory settingDAY TEMP. A 5 to 30 °C Desired room temperature in comfort periods on circuit A 20 °CNIGHT TEMP. A 5 to 30 °C Desired room temperature in reduced periods on circuit A 16 °CDAY TEMP. B (1) 5 to 30 °C Desired room temperature in comfort periods on circuit B 20 °CNIGHT TEMP. B(1) 5 to 30 °C Desired room temperature in reduced periods on circuit B 16 °C

DAY TEMP. C (1) 5 to 30 °C Desired room temperature in comfort periods on circuit C 20 °CNIGHT TEMP. C(1) 5 to 30 °C Desired room temperature in reduced periods on circuit C 16 °C

WATER TEMP. (1) 10 to 80 °C Desired domestic hot water temperature in the DHW circuit 55 °CTEMP.TANK AUX(1) 10 to 80 °C Desired domestic hot water temperature in the auxiliary circuit 55 °C

DHW A TEMP. (1) 10 to 80 °C Desired domestic hot water temperature in circuit A 55 °CSWIMMING P.T.B(1) 5 to 39 °C Desired temperature for swimming pool B 20 °C

SWIMMING P.T.C(1) 5 to 39 °C Desired temperature for swimming pool C 20 °C

(1) The parameter is only displayed for the options, circuits or sensors actually connected.

MODE

C002266-A

4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

19 06/09/2010 - 300024756-001-A

Page 177: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3.2. Selecting the operating mode

To select an operating mode, proceed as follows:

1. Press the MODE key.2. To select the desired parameter, turn the rotary button.3. To modify the parameter, press the rotary button.

To go back to the previous display, press the key j.4. To modify the parameter, turn the rotary button.5. To confirm, press the rotary button.

To cancel, press key h.

Menu MODE

Parameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programme.DAY 7/7, xx:xx Comfort mode is forced until the time indicated or all the time (7/7). Present time + 1

hourNIGHT 7/7, xx:xx Reduced mode is forced until the time indicated or all the time (7/7). Present time + 1

hourHOLIDAYS 7/7, 1 to 365 The antifreeze mode is active on all boiler circuits.

Number of days' holiday: xxheating OFF: xx:xx(1)

Restarting: xx:xx(1)

Present date + 1day

SUMMER The heating is off.Domestic hot water continues to be produced.

MANUEL The generator operates according to the set point setting. All of thepumps operate. Option of setting the set point by simply turning therotary button.

FORCE AUTO ON/OFF An operating mode override is activated on the remote control(option).To force all circuits to run on AUTOMATIC mode, select YES.

(1) The start and end days and the number of days are calculated in relation to each other.

MODE

C002267-A

MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem

06/09/2010 - 300024756-001-A 20

Page 178: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3.3. Forcing domestic hot water production

To force domestic hot water production, proceed as follows:

1. Press the r key.2. To select the desired parameter, turn the rotary button.3. To modify the parameter, press the rotary button.

To go back to the previous display, press the key j.4. To modify the parameter, turn the rotary button.5. To confirm, press the rotary button.

To cancel, press key h.

Menu r

Parameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme. COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (7/7). Present time + 1 hour

4.3.4. Setting the contrast and lighting on thedisplay

1. To access "user" level: Press the > key.2. To select the #SETTING menu.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 13.

3. To set the following parameters:

"User" level - #SETTING menu

Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP. Adjusting the display contrast. BACK LIGHT COMFORT The screen is illuminated continuously in

daytime periods.ECO

ECO The screen is illuminated for 2 minuteswhenever pressed.

MODE

C002268-A

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

21 06/09/2010 - 300024756-001-A

Page 179: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.3.5. Setting the time and date

1. To access "user" level: Press the > key.2. To select the #TIME .DAY menu.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 13.

3. To set the following parameters:

"User" level - #TIME .DAY menu

Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUM. TIME: AUTO automatic switch to summer time on the last Sunday

in March and back to winter time on the last Sundayin October.

AUTO

MANU for countries where the time change is done onother dates or is not in use.

4.3.6. Selecting a timer programme

1. To access "user" level: Press the > key.2. To select the #CHOICE TIME PROG. menu.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 13.

3. To select the desired parameter.

"User" level - #CHOICE TIME PROG. menu

Parameter Adjustment range DescriptionCURRENT PROG.A P1 / P2 / P3 / P4 Comfort programme activated

(Circuit A)CURRENT PROG.B P1 / P2 / P3 / P4 Comfort programme activated

(Circuit B)CURRENT PROG.C P1 / P2 / P3 / P4 Comfort programme activated

(Circuit C)

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem

06/09/2010 - 300024756-001-A 22

Page 180: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4. Assign the desired timer programme (P1 to P4) to the circuit withthe rotary button.

4.3.7. Customising a timer programme

1. To access "user" level: Press the > key.2. To select the #TIME PROGRAM menu.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 13.

3. To select the desired parameter.

"User" level - #TIME PROGRAM menu

Parameter Time schedule DescriptionTIME PROG.A PROG P2 A

PROG P3 APROG P4 A

Timer programme for circuit A

TIME PROG.B PROG P2 BPROG P3 BPROG P4 B

Timer programme for circuit B

TIME PROG.C PROG P2 CPROG P3 CPROG P4 C

Timer programme for circuit C

TIME PROG.DHW DHW circuit timer programmeTIME PROG.AUX Auxiliary circuit timer programme

4. To select a timer programme to be modified.5. To select to days for which the timer programme is to be

modified:Turn the rotary button to the left until you reach the day desired.To confirm, press the rotary button.

6. b : Day selectionPress key b / v until the symbol b is displayed.Turn the rotary button to the right to select the day(s) desired.v : Cancelling the day selectionPress key b / v until the symbol v is displayed.Turn the rotary button to the right to cancel selection of the relevantday(s).

7. When the days desired for the programme have been selected,press the rotary button to confirm.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

PROG P2 C Mo Tu We Th Fr Sa Su"Display of the timeprogram. To continuepush on the button" ÿ

C002228-A-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

PROG P2 C Mo Tu We Th Fr Sa Su"Display of the timeprogram. To continuepush on the button" ÿ

C002229-A-04

4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

23 06/09/2010 - 300024756-001-A

Page 181: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8. To define the timer ranges for the comfort mode and reducedmode:Turn the rotary button to the left until 0:00 is displayed. The firstsegment of the graphic bar for the timer programme flashes.

9. b : Comfort mode selectionPress key b / v until the symbol b is displayed.To select a comfort time range, turn the rotary button to the right.v : Reduced mode selectionPress key b / v until the symbol v is displayed.To select a reduced time range, turn the rotary button to the right.

10.When the times for the comfort mode have been selected, pressthe rotary button to confirm.

"User" level - #TIME PROGRAM menu

Day Comfort periods / Filling enabled:P1_______________

P2 _______________ P3 _______________ P4 _______________

TIME PROG.A Monday 6:00 to 22:00 Tuesday 6:00 to 22:00 Wednesday 6:00 to 22:00 Thursday 6:00 to 22:00 Friday 6:00 to 22:00 Saturday 6:00 to 22:00 Sunday 6:00 to 22:00

TIME PROG.B Monday 6:00 to 22:00 Tuesday 6:00 to 22:00 Wednesday 6:00 to 22:00 Thursday 6:00 to 22:00 Friday 6:00 to 22:00 Saturday 6:00 to 22:00 Sunday 6:00 to 22:00

TIME PROG.C Monday 6:00 to 22:00 Tuesday 6:00 to 22:00 Wednesday 6:00 to 22:00 Thursday 6:00 to 22:00 Friday 6:00 to 22:00 Saturday 6:00 to 22:00 Sunday 6:00 to 22:00

TIME PROG.DHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

PROG P2 C Mo Tu We Th Fr Sa SuSet the time program. ÿ

C002230-D-04

06:00

06:00

MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem

06/09/2010 - 300024756-001-A 24

Page 182: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

"User" level - #TIME PROGRAM menu

Day Comfort periods / Filling enabled:P1_______________

P2 _______________ P3 _______________ P4 _______________

TIME PROG.AUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday

4.3.8. Setting an annual clock

The annual clock is used to programme up to 10 heating stop periodsover one year. The circuits selected for this stop are in Antifreezemode during the period chosen.

1. To access "user" level: Press the > key.2. Select the menu #ANNUAL PROG.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 13.

3. To select the desired parameter.

OFF No stopA circuit AB circuit BAB circuit A, BC circuit CAC circuit A, CBC circuit B, CABC circuit A, B, CSU DHW circuitA+E circuit A and DHWB+E circuit B and DHWAB+E circuit A, B and DHWC+E circuit C and DHWAC+W circuit A, C and DHWBC+W circuit B, C and DHWALL circuit A, B, C and DHW

4. Set the start date and the end date of the shutdown selected.5. To deactivate a shutdown, select the shutdown and set to OFF.6. To select another shutdown, press the ' button.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

25 06/09/2010 - 300024756-001-A

Page 183: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Annual programme (Factory setting)Stop no. Circuit concerned Start date End date1 OFF 01-01 01-012 OFF 01-01 01-013 OFF 01-01 01-014 OFF 01-01 01-015 OFF 01-01 01-016 OFF 01-01 01-017 OFF 01-01 01-018 OFF 01-01 01-019 OFF 01-01 01-0110 OFF 01-01 01-01

For example: Customised programmingStop no. Circuit concerned Start date End date1 AC 01-11 10-112 AC 20-12 02-01

If setting STOP: NO, the stop is deactivated and the start and enddates are not displayed.

"User" level - #ANNUAL PROG menu Description Factory

settingAdjustment range

STOP N 1: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 01 Setting start date of the stop 01 1-31BEG.MONTH N 01 Setting start month of the stop 01 1-12END DATE N 01 Setting end date of the stop 01 1-31END MONTH N 01 Setting end month of the stop 01 1-12

STOP N 2: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 02 Setting start date of the stop 01 1-31BEG.MONTH N 02 Setting start month of the stop 01 1-12END DATE N 02 Setting end date of the stop 01 1-31END MONTH N 02 Setting end month of the stop 01 1-12

STOP N 3: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 03 Setting start date of the stop 01 1-31BEG.MONTH N 03 Setting start month of the stop 01 1-12END DATE N 03 Setting end date of the stop 01 1-31END MONTH N 03 Setting end month of the stop 01 1-12

STOP N 4: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 04 Setting start date of the stop 01 1-31BEG.MONTH N 04 Setting start month of the stop 01 1-12END DATE N 04 Setting end date of the stop 01 1-31END MONTH N 04 Setting end month of the stop 01 1-12

MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem

06/09/2010 - 300024756-001-A 26

Page 184: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

"User" level - #ANNUAL PROG menu Description Factory

settingAdjustment range

STOP N 5: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 05 Setting start date of the stop 01 1-31BEG.MONTH N 05 Setting start month of the stop 01 1-12END DATE N 05 Setting end date of the stop 01 1-31END MONTH N 05 Setting end month of the stop 01 1-12

STOP N 6: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 06 Setting start date of the stop 01 1-31BEG.MONTH N 06 Setting start month of the stop 01 1-12END DATE N 06 Setting end date of the stop 01 1-31END MONTH N 06 Setting end month of the stop 01 1-12

STOP N 7: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 07 Setting start date of the stop 01 1-31BEG.MONTH N 07 Setting start month of the stop 01 1-12END DATE N 07 Setting end date of the stop 01 1-31END MONTH N 07 Setting end month of the stop 01 1-12

STOP N 8: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 08 Setting start date of the stop 01 1-31BEG.MONTH N 08 Setting start month of the stop 01 1-12END DATE N 08 Setting end date of the stop 01 1-31END MONTH N 08 Setting end month of the stop 01 1-12

STOP N 9: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 09 Setting start date of the stop 01 1-31BEG.MONTH N 09 Setting start month of the stop 01 1-12END DATE N 09 Setting end date of the stop 01 1-31END MONTH N 09 Setting end month of the stop 01 1-12

STOP N 10: Selection of the circuit stopped OFF OFF, A, B, AB, C, AC, BC, ABC, SU, A+E, B+E, AB+E, C+E, AC+W, BC+W, ALL

BEG.DATE N 10 Setting start date of the stop 01 1-31BEG.MONTH N 10 Setting start month of the stop 01 1-12END DATE N 10 Setting end date of the stop 01 1-31END MONTH N 10 Setting end month of the stop 01 1-12

4.4 Installation shutdown

CAUTION

Do not switch off the boiler. If the central heating systemis not used for a long period, we recommend activating theHOLIDAYS mode.

4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115

27 06/09/2010 - 300024756-001-A

Page 185: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4.5 Frost protection

CAUTION

4 The anitfreeze protection does not function if theboiler is switched off.

4 The integrated protection system only protects theboiler, not the installation. To protect the installation,set the appliance to HOLIDAYS mode.

The HOLIDAYS mode protects:

4 The installation if the outside temperature is lower than 3°C(factory setting).

4 The room temperature if a remote control is connected and theroom temperature is lower than 6 °C (factory setting).

4 The domestic hot water tank if the tank temperature is lowerthan 4 °C (the water is reheated to 10 °C).

To configure the holidays mode: ¼ See chapter: "Selecting theoperating mode", page 20.

MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem

06/09/2010 - 300024756-001-A 28

Page 186: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5 Operating the appliance - IniControl

5.1 Putting the appliance into operation

1. Check the water pressure in the installation shown on the controlpanel display.

If the water pressure is lower than 0,8 bar, more watershould be added. If necessary, top up the water level in theheating system (recommended hydraulic pressurebetween 1,5 and 2,0 bar).¼ See chapter: "Filling the system", page 35

2. Open the gas valve on the boiler.3. Switch on the boiler.4. The start-up cycle begins and cannot be interrupted. During the

start-up cycle, the display shows the following information:fK[xx : Software version

pK[xx : Parameter versionThe version numbers are displayed alternately.

5. A vent cycle of a duration of around 3 minutes is carried outautomatically.

6. In addition to 0, in STAND-BY the display normally shows thewater pressure and the symbols d, 5tH and r.

5.2 Reading out measured values

The following current values can be read off the information menuQ:

4 5t = State.4 5v = Sub-status.4 t1 = Flow temperature (°C).4 t" = Return temperature (°C).4 t3 = Calorifier temperature (°C).4 t4 = Outside temperature (°C).4 t5 = Solar boiler temperature (°C).4 5p = Internal set point (°C).4 fl = Ionisation current (µA).4 Mf = Fan speed in rpm.4 pr = Water pressure (bar).4 p; = Supplied relative heat output (%).

5. Operating the appliance - IniControl MCA 45 - 65 - 90 - 115

29 06/09/2010 - 300024756-001-A

Page 187: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

The current values can be read as follows:

1. Press the two f keys simultaneously. The symbol Q flashes.2. Confirm using key S. 5t is displayed, alternating with the

current status 3 (for example).3. Press the [+] key. 5v is displayed, alternating with the current

sub-status 30 (for example).4. Press the [+] key. t1 is displayed, alternating with the current

flow temperature 60°C (for example).5. Press the [+] key successively to scroll down the various

parameters. t", t3, t4, t5 .6. Press the [+] key. 5p is displayed, alternating with the internal

set point 88°C (for example).7. Press the [+] key. fl is displayed, alternating with the current

ionisation current 70 µA (for example).8. Press the [+] key. Mf is displayed, alternating with the current

fan rotation speed 3000 rpm (for example).9. Press the [+] key. pr is displayed, alternating with the current

water pressure #0 bar (for example). If no water pressure sensoris connected, [-.-] appears on the display.

10.Press the [+] key. p; is displayed, alternating with the currentmodulation percentage 78 % (for example).

11.Press the [+] key. The readout cycle starts again with 5t.12.Press 2 times on key j to return to the current operating mode.

5.3 Changing the settings

5.3.1. Description of the parameters

Parameter Description Adjustment range Factory settingMCA45 65 90 115

p1 Maximum outlet temperature 20 to 90 °C 80 80 80 80p2 Domestic hot water temperature: TSET 40 to 65 °C 60 60 60 60p3 Heating / DHW mode Do not modify 1 1 1 1p4 Mode ECO Do not modify 2 2 2 2p5 Anticipation resistance Do not modify 0 0 0 0

)

rd

bar

C003049-A

thj

hj

4x

2x

MCA 45 - 65 - 90 - 115 5. Operating the appliance - IniControl

06/09/2010 - 300024756-001-A 30

Page 188: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Parameter Description Adjustment range Factory settingMCA45 65 90 115

p6 Display screen Do not modify 2 2 2 2p7 Post-circulation of the boiler pump connected to the PCU 1 to 98 minutes

99 minutes = continuous3 3 3 3

p8 Brightness of display lighting Do not modify 1 1 1 1

5.3.2. Modification of the user-level parameters

Parameters p1 to p8 can be modified by the user in order to meetcentral heating and DHW comfort needs.

CAUTION

Modification of the factory settings may be detrimental tothe functioning of the boiler.

1. Press the two keys f simultaneously and then key [+] until thesymbol W flashes on the menu bar.

2. Select the users menu using the key S. p[1 is displayed with

1 flashing.3. Press the S key a second time. The value 80°C appears and

flashes (for example).4. Change the value by pressing the [-] or [+] key. In this example

using key [-] to 60°C.5. Confirm the value with the S key. p[1 is displayed with 1

flashing.6. Press 2 times on key j to return to the current operating mode.

4 The parameters p2 to p8 are changed in thesame way as p1. After step 2, use the [+] key tomove to the required parameter.

4 The parameters p1 (the maximum heating watertemperature) and p2 (the maximum drinking watertemperature) can also be modified using the quickselection menu.

)

rd

bar

C003050-A

thj

hj

1x

2x

5. Operating the appliance - IniControl MCA 45 - 65 - 90 - 115

31 06/09/2010 - 300024756-001-A

Page 189: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5.3.3. Setting the manual mode

In some cases it may be necessary to switch the boiler to manualoperation, For example, if the controller has not yet beenconnected. The boiler can be switched to automatic or manualoperation under the symbol E. To do this, proceed as follows:

1. Press the two keys f simultaneously and then key [+] until thesymbol E flashes on the menu bar.

2. Press the S key:orThe text Zv with the current water pressure (only if an outsidesensor is connected). The flow temperature is determined by theinternal heating curve.orThe value of the minimum flow temperature.

3. Press the [-] or [+] key to increase this value temporarily in manualoperation.

4. Confirm the value with the S key. The boiler is now set to manualoperation.

5. Press 2 times on key j to return to the current operating mode.

5.3.4. Changing the heating temperature

If using an outside temperature sensor, the heating flowtemperature is adjusted automatically.

In summer, it is possible to reduce the heating flow temperature whilstmaintaining comfort. To do this, proceed as follows:

1. Press the d key 1 time.2. The symbol d and the current temperature are displayed (the

temperature flashes, e.g. 80°C).3. Change the value by pressing the [-] or [+] key. In this example

using key [-] to 60°C.4. To confirm, press the S key.

It also possible to modify this setting using the parameterp1.

5.3.5. Modifying the domestic hot watertemperature setting

It may be that a lower domestic hot water temperature will be sufficientfor your needs. Reduce this temperature and save energy. To do this,proceed as follows:

)

m

rd

bar

C003051-A

thj

hj

2x

2x

bar

d

C003052-A

1x

MCA 45 - 65 - 90 - 115 5. Operating the appliance - IniControl

06/09/2010 - 300024756-001-A 32

Page 190: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

1. Press the r key 1 time.2. The symbol r and the current temperature are displayed (the

temperature flashes, e.g. 60°C).3. Change the value by pressing the [-] or [+] key. In this example

using key [-] to 55°C.4. To confirm, press the S key.

5.4 Installation shutdown

CAUTION

Do not switch off the boiler. If the central heating systemis not used for a long period, we recommend activating theHOLIDAYS mode.

5.5 Frost protection

When the heating water temperature in the boiler falls by too much,the integrated protection system in the boiler starts up. This protectionfunctions as follows:

4 If the water temperature is lower than 7°C, the heating pump startsup.

4 If the water temperature is lower than 4°C, the boiler starts up.4 If the water temperature is higher than 10°C, the boiler shuts down

and the heating pump continues to run for a short time.

CAUTION

4 The anitfreeze protection does not function if theboiler is switched off.

4 The integrated protection system only protects theboiler, not the installation. To protect the installation,set the appliance to HOLIDAYS mode.

With the IniControl control panel, the HOLIDAYS mode isonly available if a room sensor is connected to the boiler.

The HOLIDAYS mode protects:

4 The installation if the outside temperature is lower than 3°C(factory setting).

4 The room temperature if a remote control is connected and theroom temperature is lower than 6 °C (factory setting).

4 The domestic hot water tank if the tank temperature is lowerthan 4 °C (the water is reheated to 10 °C).

To configure the holidays mode: ¼ See chapter: "Selecting theoperating mode", page 20.

C003053-A

r1x

5. Operating the appliance - IniControl MCA 45 - 65 - 90 - 115

33 06/09/2010 - 300024756-001-A

Page 191: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6 Checking and maintenance

6.1 General instructions

The boiler does not require a lot of maintenance. Nevertheless, werecommend having the boiler inspected and serviced at regularintervals.

4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician.

4 Have the flues swept at least once a year or more, depending onthe regulations in force in your country.

CAUTION

4 Maintenance operations must be done by a qualifiedengineer.

4 We recommend taking out a maintenance contract.4 Only original spare parts must be used.

6.1.1. Control panel DIEMATIC iSystem

The boiler displays a message whenever maintenance is necessary.

1. When the message, REVISION, is displayed, press ? to displaythe installer's telephone number.

2. Contact the fitter.3. Have the required checks and services done.

6.2 Periodic checks

4 Check the water pressure in the installation several times a year.

If the water pressure is lower than 0,8 bar, more watershould be added. If necessary, top up the water level in theheating system (recommended hydraulic pressurebetween 1,5 and 2,0 bar).¼ See chapter: "Filling the system", page 35.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP. : 68°

PCU COM.FAIL D27

C002302-D-04

MCA 45 - 65 - 90 - 115 6. Checking and maintenance

06/09/2010 - 300024756-001-A 34

Page 192: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

4 Carry out a visual check for the presence of any water leaks.

4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up).

4 Clean the outside of the boiler using a damp cloth and a lightdetergent.

CAUTION

Only a qualified professional is authorised to clean theinside of the boiler.

6.3 Filling the system

1. Check the water pressure in the installation shown on the controlpanel display.

If the water pressure is lower than 0,8 bar, more watershould be added. If necessary, top up the water level in theheating system (recommended hydraulic pressurebetween 1,5 and 2,0 bar).

2. Open the valves on all radiators connected to the heating system.

3. Set the room thermostat to as low a temperature as possible.

4. Wait until the temperature drops below 40°C and the radiatorsseem cold before filling the central heating system.

T001507-B

1

2

3

4

T000181-B

1

2

3

4

T000181-B

T000182-A

T000185-A

6. Checking and maintenance MCA 45 - 65 - 90 - 115

35 06/09/2010 - 300024756-001-A

Page 193: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

5. To fill with water, use a filling tube with two tap connections, a ragand a bleed key.

6. Connect the filling tube to a (cold) water tap.

7. Eliminate the air from the filling tube. Slowly fill the tube withwater. Hold the end of the tube up, above a bucket. Turn off thetap as soon as water runs out of the pipe.

8. Unscrew the plug from the filling/draw-off valve.

The filling/draw-off valve is not necessarily located next tothe boiler.

T000845-A

T000846-A

T000847-A

T000848-A

MCA 45 - 65 - 90 - 115 6. Checking and maintenance

06/09/2010 - 300024756-001-A 36

Page 194: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

9. Attach the tube to the filling/draw-off valve. Firmly tighten the nuton the filling tube.

10.Open the filling/draw-off valve on the heating system.11.Open the running water tap.12.Check the water pressure in the installation shown on the control

panel display.13.Close the water tap when the water pressure reaches 2 bar.

14.Close the filling/draw-off valve on the heating system.Leave thetube on the filling/draw-off valve until the air is purged from theinstallation.

When water is added, air gets into the heating system.Degas the installation. After the air has been vented, thewater pressure can drop below the required level. Checkthe water pressure in the installation shown on the controlpanel display. If the water pressure is lower than 0,8 bar,more water should be added.

15.After filling the installation, switch the boiler on.

Filling and bleeding the installation 2 times a year shouldbe sufficient to obtain an adequate hydraulic pressure. If itis often necessary to top up the installation with water,contact your fitter.

T000849-A

T000850-A

T000853-A

6. Checking and maintenance MCA 45 - 65 - 90 - 115

37 06/09/2010 - 300024756-001-A

Page 195: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6.4 Bleeding the heating system

It is essential that you bleed any air in the calorifier, the conduits orthe taps to prevent the annoying noises likely to be produced duringheating or when tapping water. To do this, proceed as follows:

1. Open the valves on all radiators connected to the heating system.

2. Set the heating set point to as high a temperature as possible.3. Wait until the radiators are hot.

4. Switch the boiler off.5. Wait around 10 minutes until the radiators are cold.

6. Bleed the radiators. Start with the lower floors.

1

2

3

4

T000181-B

T000184-A

T000185-A

T000854-A

3

1

4

5

2

MCA 45 - 65 - 90 - 115 6. Checking and maintenance

06/09/2010 - 300024756-001-A 38

Page 196: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

7. Open the bleed connection using the bleed key provided whilstkeeping a rag pressed against the connection.

8. Wait until water comes out of the bleed valve and then close thebleed connection.

CAUTION

The water may still be hot.9. Switch on the boiler. A vent cycle of a duration of around 3 minutes

is carried out automatically.10.After venting, check whether the pressure in the installation is still

sufficient.

If the water pressure is lower than 0,8 bar, more watershould be added. If necessary, top up the water level in theheating system (recommended hydraulic pressurebetween 1,5 and 2,0 bar).¼ See chapter: "Filling the system", page 35

11.Set the heating set point.

T000217-A

T000218-A

6. Checking and maintenance MCA 45 - 65 - 90 - 115

39 06/09/2010 - 300024756-001-A

Page 197: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

6.5 Draining the installation

It may become necessary to empty the water from the heating systemwhen the radiators have to be replaced, should there be a major waterleak or a risk of frost. To do this, proceed as follows:

1. Open the valves on all radiators connected to the heating system.

2. Switch off the boiler electrical power supply.3. Wait around 10 minutes until the radiators are cold.

4. Connect an evacuation hose to the plug located at the lowestlevel. Place the end of the hose in a discharge sump or in a placewhere the water discharged from the valve can not do anydamage.

5. Open the filling/draw-off valve on the heating system. Bleed theheating installation.

WARNING

The water may still be hot.6. When no more water comes out of the drainage plug, close the

drainage valve.

1

2

3

4

T000181-B

T000185-A

T000858-A

MCA 45 - 65 - 90 - 115 6. Checking and maintenance

06/09/2010 - 300024756-001-A 40

Page 198: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

7 Troubleshooting

7.1 Anti-hunting

This display only concerns boilers with the DIEMATICiSystem control panel.

When the boiler is in "Anti-short-cycle" operating mode, the symbol"?" flashes. This is a normal operating mode. When the restarttemperature is reached, operation will be guaranteed.

7.2 Messages (Code type Bxx or Mxx)

In the event of failure, the control panel displays a message and acorresponding code.

1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.

2. Switch the boiler off and switch back on.The boiler starts up again automatically when the reason for theblocking has been removed.

3. If the code is displayed again, correct the problem by following theinstructions in the table below:

Depending on the control panel, the message display isdifferent:

4 Control panel DIEMATIC iSystem: The code and themessage are displayed.

4 Control panel IniControl: Only the code is displayed.

Code Messages Description Checking / solutionB00 BL.PSU ERROR The PSU PCB is incorrectly

configuredParameter error on the PSU PCB

4 Contact the professional who takes care of maintenance ofthe appliance

B01 BL.MAX BOILER Maximum flow temperatureexceeded

The water flow in the installation is insufficient

4 Check the circulation (direction, pump, valves)B02 BL.HEATING

SPEEDThe increase in flow temperaturehas exceeded its maximum limit

The water flow in the installation is insufficient

4 Check the circulation (direction, pump, valves)4 Check the water pressureSensor error

4 Contact the professional who takes care of maintenance ofthe appliance

7. Troubleshooting MCA 45 - 65 - 90 - 115

41 06/09/2010 - 300024756-001-A

Page 199: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Messages Description Checking / solutionB07 BL.DT OUTL RET. Maximum difference between the

flow and return temperatureexceeded

The water flow in the installation is insufficient

4 Check the circulation (direction, pump, valves)4 Check the water pressureSensor error

4 Contact the professional who takes care of maintenance ofthe appliance

B08 BL.RL OPEN The RL inlet on the PCU PCBterminal block is open

Parameter error

4 Contact the professional who takes care of maintenance ofthe appliance

Bad connection

4 Contact the professional who takes care of maintenance ofthe appliance

B09 BL.INV. L/N 4 Contact the professional who takes care of maintenance of the applianceB10B11

BL.BL INPUTOPEN

The BL inlet on the PCU PCBterminal block is open

The contact connected to the BL inlet is open

4 Contact the professional who takes care of maintenance ofthe appliance

Parameter error

4 Contact the professional who takes care of maintenance ofthe appliance

Bad connection

4 Contact the professional who takes care of maintenance ofthe appliance

B13 BL. PCU COM Communication error with theSCU PCB

Bad connection

4 Contact the professional who takes care of maintenance ofthe appliance

SCU PCB not installed in the boiler

4 Contact the professional who takes care of maintenance ofthe appliance

B14 BL.WATER MIS. The water pressure is lower than0,8 bar

Not enough water in the circuit

4 Top up the installation with waterB15 BL.GAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU PCB

4 Check that the gas valve is fully opened4 Contact the professional who takes care of maintenance of

the applianceB16 BL.BAD SU The SU PCB is not recognised Wrong SU PCB for this boiler

4 Contact the professional who takes care of maintenance ofthe appliance

B17 BL.PCU ERROR The parameters saved on thePCU PCB are impaired

Parameter error on the PCU PCB

4 Contact the professional who takes care of maintenance ofthe appliance

B18 BL.BAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler

4 Contact the professional who takes care of maintenance ofthe appliance

B19 BL.NO CONFIG The boiler has not beenconfigured

The PSU PCB has been changed

4 Contact the professional who takes care of maintenance ofthe appliance

B21 BL. COM SU Communication error betweenthe PCU and SU PCBs

Bad connection

4 Contact the professional who takes care of maintenance ofthe appliance

MCA 45 - 65 - 90 - 115 7. Troubleshooting

06/09/2010 - 300024756-001-A 42

Page 200: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Messages Description Checking / solutionB22 BL.FLAME LOS No flame during operation No ionization current

4 Check that the gas valve is fully opened4 Contact the professional who takes care of maintenance of

the applianceB25 BL.SU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of maintenance of

the applianceM04 REVISION A service is required The date programmed for the service has been reached

4 If the symbol ? flashes, press key ?. The installer's contactdetails are displayed.

4 Contact the professional who takes care of maintenance ofthe appliance

M05 REVISION A An A, B or C service is required The date programmed for the service has been reached

4 If the symbol ? flashes, press key ?. The installer's contactdetails are displayed.

4 Contact the professional who takes care of maintenance ofthe appliance

M06 REVISION BM07 REVISION C

M20 DISGAS A boiler vent cycle is underway Switching the boiler on

4 Wait 3 minutes FL.DRY.B XX

DAYSFloor drying is activeXX DAYS = Number of days' floordrying remaining.

Floor drying is underway. Heating on the circuits not concernedis shut down.

4 Contact the professional who takes care of maintenance ofthe appliance

FL.DRY.C XXDAYSFL.DRY.B+C XXDAYS

M23 CHANGE OUTSSENSOR

The outside temperature sensorbattery is weak

Change the outside radio temperature sensor

STOP N XX The shutdown is activeXX = Number of the activeshutdown

A shutdown is underway. The circuits selected for this stop arein Antifreeze mode during the period chosen.

7.3 Faults (Code type Lxx or Dxx)

In the event of operational failure, the control panel flashes anddisplays an error message and a corresponding code.

Depending on the control panel, the message display isdifferent:

4 Control panel DIEMATIC iSystem: The code and themessage are displayed.

4 Control panel IniControl: Only the code is displayed.

7. Troubleshooting MCA 45 - 65 - 90 - 115

43 06/09/2010 - 300024756-001-A

Page 201: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

7.3.1. Control panel DIEMATIC iSystem

1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.

2. Press the t key. If the code is displayed again, switch off the boilerand then switch it back on.

3. Press the ? key. Follow the instructions displayed to solve theproblem.

4. Consult the meaning of the codes in the table below:

7.3.2. Control panel IniControl

1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.

2. Press the t key. If the code is displayed again, switch off the boilerand then switch it back on.

7.3.3. List of errors

Code Faults Causeof theerror

Description Checking / solution

L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty

4 Contact the professional who takes care ofmaintenance of the appliance

L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty

4 Contact the professional who takes care ofmaintenance of the appliance

L02 DEF.OUTLET S. PCU The boiler flow sensor has short-circuited

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

bar

1

1

2

2

rc

STD( t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP. : 68°

PCU. KOM. DEF D27

C002604-A-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP. : 68°

PCU COM.FAIL D27

C002302-D-04

MCA 45 - 65 - 90 - 115 7. Troubleshooting

06/09/2010 - 300024756-001-A 44

Page 202: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

L03 DEF.OUTLET S. PCU The boiler flow sensor is on an opencircuit

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

L04 DEF.OUTLET S. PCU Boiler temp too low Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

No water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump,

valves)4 Check the water pressure

L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

No water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump,

valves)4 Check the water pressure

L06 BACK S.FAILURE PCU The return temperature sensor hasshort-circuited

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

L07 BACK S.FAILURE PCU The return temperature sensor is onan open circuit

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

L08 BACK S.FAILURE PCU Return temperature too low Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

No water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump,

valves)4 Check the water pressure

L09 STB BACK PCU Return temperature too high Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

No water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump,

valves)4 Check the water pressure

7. Troubleshooting MCA 45 - 65 - 90 - 115

45 06/09/2010 - 300024756-001-A

Page 203: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

L10 DEP-RET<MIN PCU Difference between the flow andreturn temperatures insufficient

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

No water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump,

valves)4 Check the water pressure

L11 DEP-RET>MAX PCU Difference between the flow andreturn temperatures too great

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

No water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump,

valves)4 Check the water pressure

L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

No water circulation

4 Vent the air in the heating system4 Check the circulation (direction, pump,

valves)4 Check the water pressure

L14 BURNER FAILURE PCU 5 burner start-up failures Absence of ignition arch

4 Contact the professional who takes care ofmaintenance of the appliance

Presence of the ignition arc but no flame formation

4 Check that the gas valve is fully opened4 Contact the professional who takes care of

maintenance of the appliancePresence of the flame but insufficient ionization(<3 µA)

4 Check that the gas valve is fully opened4 Contact the professional who takes care of

maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionisation current present when there should not

be a flameIgnition transformer defectiveGas valve defectiveThe burner remains very hot: CO2 too high

4 Contact the professional who takes care ofmaintenance of the appliance

L17 VALVE FAIL PCU Problem on the gas valve Bad connectionSU PCB faulty

4 Contact the professional who takes care ofmaintenance of the appliance

MCA 45 - 65 - 90 - 115 7. Troubleshooting

06/09/2010 - 300024756-001-A 46

Page 204: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

L34 FAN FAILURE PCU The fan is not running at the rightspeed

Bad connectionFan defective

4 Contact the professional who takes care ofmaintenance of the appliance

L35 BACK>BOIL FAIL PCU Flow and return reversed Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

Water circulation direction reversed

4 Check the circulation (direction, pump,valves)

L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating

No ionization current

4 Check that the gas valve is fully opened4 Contact the professional who takes care of

maintenance of the applianceL37 SU COM.FAIL PCU Communication failure with the SU

PCBBad connection

4 Contact the professional who takes care ofmaintenance of the appliance

L38 PCU COM.FAIL PCU Communication failure between thePCU and SCU PCBs

Bad connectionSCU PCB not connected or faulty

4 Contact the professional who takes care ofmaintenance of the appliance

L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set

4 Contact the professional who takes care ofmaintenance of the appliance

L40 TEST.HRU.FAIL PCU HRU/URC unit test error Bad connectionExternal causeParameter incorrectly set

4 Contact the professional who takes care ofmaintenance of the appliance

L250 DEF.WATER MIS. PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error

4 Top up with more water if necessary4 Reset the boiler

L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectiveSensor pcb defective

4 Contact the professional who takes care ofmaintenance of the appliance

D03D04

OUTL S.B FAIL.OUTL S.C FAIL.

SCU Sensor fault flow circuit BSensor fault flow circuit CRemarks:The circuit pump is running.The 3-way valve motor on the circuitis no longer powered and can beadjusted manually.

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

7. Troubleshooting MCA 45 - 65 - 90 - 115

47 06/09/2010 - 300024756-001-A

Page 205: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

D05 OUTSI.S.FAIL. SCU Fault external sensorRemarks:The boiler operates on BOILERMAX temperature.The valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensured.Valves may be manually operated.Reheating the domestic hot waterremains ensured.

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

D07 AUX.SENS.FAIL. SCU Auxiliary sensor failure Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

D09 DHW S.FAILURE SCU Domestic hot water sensor failureRemarks:Heating of domestic hot water is nolonger ensured.The load pump operates.The load temperature of the dhwtank is the same as the boiler.

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

D11D12D13

ROOM S.A FAIL.ROOM S.B FAIL.ROOM S.C FAIL.

SCU Fault room temperature sensor AFault room temperature sensor BFault room temperature sensor CNote:The circuit concerned operateswithout any influence from the roomsensor.

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

D14 MC COM.FAIL SCU Communication failure between theSCU PCB and the boiler radiomodule

Bad connection

4 Check the link and the connectorsBoiler module failure

4 Change the boiler moduleD15 ST.TANK S.FAIL SCU Storage tank sensor failure

Note:The hot water storage tankreheating operation is no longerassured.

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

D16D16

SWIM.P.B. S.FAILSWIM.P.C. S.FAIL

SCU Swimming pool sensor failure circuitBSwimming pool sensor failure circuitCNote:Pool reheating is independent of itstemperature.

Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

D17 DHW 2 S.FAIL SCU Sensor failure tank 2 Bad connectionSensor fault

4 Contact the professional who takes care ofmaintenance of the appliance

D27 PCU COM. FAIL SCU Communication failure between the SCU and PCU PCBs

4 Contact the professional who takes care of maintenance of the appliance

MCA 45 - 65 - 90 - 115 7. Troubleshooting

06/09/2010 - 300024756-001-A 48

Page 206: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

Code Faults Causeof theerror

Description Checking / solution

D29 IOBL.3WV B DEF SCU Communication failure between theSCU PCB and the V3V module

The V3V module is switched offThe V3V module and the SCU PCB are notconnected to the same live terminalThe V3V module has been removed

4 Contact the professional who takes care ofmaintenance of the appliance

D30 IOBL.3WV C DEF SCU Communication failure between theSCU PCB and the V3V module

The V3V module is switched offThe V3V module and the SCU PCB are notconnected to the same live terminalThe V3V module has been removed

4 Contact the professional who takes care ofmaintenance of the appliance

D31 COM.IOBL FAIL. SCU The IOBL function is no longeractive

Problem on the SCU PCB

4 Contact the professional who takes care ofmaintenance of the appliance

D32 5 RESET:ON/OFF SCU 5 resets done in less than an hour

4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible), contact your

heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active System® is short-circuited

4 Contact the professional who takes care of maintenance of the applianceRemarks:Domestic hot water production has stopped but can nonetheless be restarted using keyr.The tank is no longer protected.If: A tank without Titan Active System® is connected to the boiler: Check that the TitanActive System® simulation connector (delivered with package AD212) is fitted to thesensor card.

D38 TA-S DISCONNEC SCU The Titan Active System® is on an open circuit

4 Contact the professional who takes care of maintenance of the applianceRemarks:Domestic hot water production has stopped but can nonetheless be restarted using keyr.The tank is no longer protected.If: A tank without Titan Active System® is connected to the boiler: Check that the TitanActive System® simulation connector (delivered with package AD212) is fitted to thesensor card.

7. Troubleshooting MCA 45 - 65 - 90 - 115

49 06/09/2010 - 300024756-001-A

Page 207: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

8 Technical characteristics

8.1 Technical characteristics

Boiler type MCA 45 MCA 65 MCA 90 MCA 115GeneralFlow rate setting Adjustable Modulating, Start/Stop, 0 - 10 VNominal output (Pn)Heating System (80/60 °C)

minimum-maximum kW 8,0 - 40,0 12,0 - 61,0 14,1 - 84,2 16,6 - 107,0Factory setting kW 40,0 61,0 84,2 107,0

Nominal output (Pn)Heating System (50/30 °C)

minimum-maximum kW 8,9 - 43,0 13,3 - 65,0 15,8 - 89,5 18,4 - 114,0Factory setting kW 43,0 65,0 89,5 114,0

Data on the gases and combustion gasesGas consumption G20 (Natural gas H) minimum-maximum m3/h 0,9 - 4,4 1,3 - 6,6 1,5 - 9,1 1,8 - 11,7

Gas consumption G31 (Propane) minimum-maximum m3/h 0,3 - 1,7 0,5 - 2,5 0,6 - 3,5 0,6 - 4,7

NOx-Emission per year or (EN 483) mg/kWh 37 32 45 46Mass flue gas flow rate minimum-maximum Kg/h 14 - 69 21 - 104 28 - 138 36 - 178Flue gas temperature minimum-maximum °C 30 - 67 30 - 68 30 - 68 30 - 72Maximum counter pressure Pa 150 100 160 220Characteristics of the heating circuitWater content l 5,5 6,5 7,5 7,5Water operating pressure minimum kPa (bar) 80 (0,8) 80 (0,8) 80 (0,8) 80 (0,8)Water operating pressure (PMS) maximum kPa (bar) 400 (4,0) 400 (4,0) 400 (4,0) 400 (4,0)Water temperature maximum °C 110 110 110 110Operating temperature maximum °C 90 90 90 90Electrical characteristicsPower supply voltage V/Hz 230/50 230/50 230/50 230/50Power consumption - Full load maximum W 68 88 125 199Power consumption - Part load maximum W 18 23 20 45Power consumption - Standby maximum W 5 6 4 7Electrical protection index IP X4D X4D X4D X4DOther characteristicsWeight (empty) Total kg 53 60 67 68Acoustic level at 1 meter dBA 45 45 52 51

MCA 45 - 65 - 90 - 115 8. Technical characteristics

06/09/2010 - 300024756-001-A 50

Page 208: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

9 Energy savings

9.1 Energy-saving advice

4 Keep the room in which the boiler is installed well ventilated.4 Do not block ventilation outlets.4 Do not cover the radiators. Do not hang curtains in front of the

radiators.4 Install reflective panels behind the radiators to prevent heat

losses.4 Insulate the pipes in rooms that are not heated (cellars and lofts).4 Close the radiators in rooms not in use.4 Do not run hot (or cold) water pointlessly.4 Fit a water-saving shower head to save up to 40 % energy.4 Take showers rather than baths. A bath consumes twice as much

water and energy.

9.2 Recommendations

The remote control is available in the following versions:

4 Wire4 Radio

The setting of the control panel and/or of the remote control has aconsiderable influence on energy consumption.

A few tips:

4 In the room in which the room thermostat is installed, it's advisednot to use thermostatic valve radiators. If a thermostatic valve isused the valve must be fully opened.

4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations. Open and closethermostatic valves in small steps.

4 Lower the temperature to around 20°C. This reduces heating costsand energy consumption.

4 Lower the temperature when you air the rooms.4 When setting a time schedule , bear days when you are absent

and holidays in mind.

9. Energy savings MCA 45 - 65 - 90 - 115

51 06/09/2010 - 300024756-001-A

Page 209: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

10 Warranty

10.1 General

You have just purchased one of our appliances and we thank you forthe trust you have placed in our products.

Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained.

Your fitter and our customer support network are at your disposal atall times.

10.2 Warranty terms

The following provisions are not exclusive of the buyerbeing able benefit from the legal provisions applicableregarding hidden defects in the buyer's country.

Starting from the purchase date shown on the original fitter's invoice,your appliance has a contractual guarantee against anymanufacturing defect.

The length of the guarantee is mentioned in the price catalogue.

The manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified fitter).

In particular, the manufacturer shall not be held responsible for anydamage, loss or injury caused by installations which do not complywith the following:

4 applicable local laws and regulations,4 specific requirements relating to the installation, such as national

and/or local regulations,4 the manufacturer's instructions, in particular those relating to the

regular maintenance of the unit,4 the rules of the profession.

The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour, travel and carriage costs.

The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear, negligence, repairs by unqualifiedparties, faulty or insufficient monitoring and maintenance, faultypower supply or the use of unsuitable fuel.

Sub-assemblies such as motors, pumps, electric valves etc. areguaranteed only if they have never been dismantled.

The legislation laid down by european directive 99/44/EEC,transposed by legislative decree No. 24 of 2 February 2002 publishedin O.J. No. 57 of 8 March 2002, continues to apply.

MCA 45 - 65 - 90 - 115 10. Warranty

06/09/2010 - 300024756-001-A 52

Page 210: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P
Page 211: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P
Page 212: Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115€¦ · Wall-hung gas condensing boilers MCA 45 - 65 - 90 - 115 Installation and Service Manual 300024755-001-A. ... II2H3P

© CopyrightAll technical and technological information contained in these technical instructions,as well as any drawings and technical descriptions supplied, remain our propertyand shall not be multiplied without our prior consent in writing.

T000249-B

06/09/2010

DE DIETRICH THERMIQUE

57, rue de la Gare F- 67580 MERTZWILLER - BP 30